Relay
AX series
Safety information
Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury
WARNING WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
CAUTION CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury
DANGER
The electric shock may occur in the input/output terminal so please never let your body and/
or conductive substance to be contacted by the input/output terminal.
WARNING
Since this product is not designed as a safely used device the user must install double
safety equipment when this product is used for equipment with possible fatal accident or
large property damage.
The power switch and fuse are not installed on this product so users need to install them
separately on the outside. (Fuse rating : 250 V 0.5 A)
Please supply in the rated power supply voltage in order to prevent this product from
breaking down or damaged.
To prevent electric shock or devise malfunction of this product, do not supply the power until
the wiring is completed.
This is not designed as explosion-protective structure so avoid using this product at places
where gas inflammability and explosive gases exist.
Do not supply in the power until all wiring is fully completed in order to prevent the product
from breaking down and prevent users from getting electric shock.
Do not disassemble, manufacture, upgrade and repair the product by yourself. Doing so
will break down the product, generate the electric shock and cause malfunction to occur.
Please turn OFF the product and disassemble the product. Not doing so will break down
the product, generate the electric shock and cause malfunction to occur.
Electric shock may occur when operating this product so please install this product to the panel and use it
CAUTION
The contents of this manual may be changed without prior notification
Please check for correct model type and specification
Please check for any damage or abnormality may caused during shipment.
Please use this product at following range.
Ambient temperature : -5 ~ 50 (when installing them close to each other, max. 40 ) /
humidity : 35 ~ 85 % R.H (but without dew condensation)
Please avoid the places where corrosive gas(especially noxious gas, ammonia and etc) and inflammable gas exist
Please do not use this product at places where the vibration or impact is applied directly.
Please avoid the places where liquid, oil, medical substances, dust, salt or iron contents
exist(avoid place of pollution level 1 or 2)
Do not clean the product with the organic solvent such as alcohols, benzene and etc. (Use neutral detergents)
Please avoid the places where huge inductive interference exists and places where static
electricity/self noise are generated.
Please avoid the places where heat accumulates due to the direct sunlight, radiation and etc
We recommend using it at altitude below the 2000 m.
If the device is touched or contacted by water then short-circuit and fire may occur so
please inspect the device carefully.
With the thermocouple input, please use the stated compensation cable.
(Using regular compensation cable will generate the temperature error)
With the RTD input, please use the cable with less lead-wire resistance and no difference in
the resistance among 3-wires. (Using regular cable will generate the temperature error)
For the input signal wire, please avoid from the power line and load line in order to avoid
from the induction noise.
Separate the input signal wire and output signal wire and if separating them from each other
is impossible, then please use the shield wire for the input signal wire.
For the thermocouple, please use It as the un-grounding type.
(When using the grounding type, malfunction may occur due to the electric leakage)
When there are too much noises generating from the power, we recommend using the insulation
Trans and noise filter. Noise filter must be mounted to the panel or etc that is grounded and
please try to make the wiring of output and power terminal meter as short as possible.
Tightly twisting the power line meter will reduce the noise generation
If alarm function is not set properly, alarm will not be generated when it should so please
check for the operation before running the product.
When replacing the sensor, please turn OFF the power
If operation frequency is too high (such as proportional operation and etc) and connecting
the maximum rated load to output relay will shorten the life expectancy therefore, please use
the auxiliary relay. We recommend using the SSR output type in such cases.
- When using the electrical switch: Set proportional cycle min 20 sec
- When using the SSR: Set proportional cycle min 1 sec
Do not wire anything to the un-using terminal
Please check the polarity of terminal before wiring.
When installing this product to the panel, please use the authorized switch or circuit
breaker (authorized by IEC60947-1 or IEC60947-3)
Please install the switch or circuit breaker close to the operator for usersconvenience
Because switch or circuit breaker is being installed, please make a note on the panel that
operating the switch or circuit breaker will block the power.
We recommend the continuous inspection and repair in order to use it safely for a long period of time.
It the
value is ON, Alarm is not cancelled evenif it becomes the alarm cancel condition.
If users want to stop the alarm forcedly, please press the
key for approx 2 sec.
CYC
S.S.R
INSTRUCTION MANUAL
Thank you for purchasing HANYOUNG product.
Please check whether the product is the exactly same as you ordered.
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time
Jl. cempaka blok F16, No.02 Delta Silicon II Cikarang Bekasi Indonesia
TEL : 62-21-8911-8120~4 FAX : 62-21-8911-8126
Some parts in this product have life expectancy and gets old as time elapses.
The warranty period is one year including the parts only under the condition where the
product is used properly
It needs the preparation time for contact output when supplying in the power. When
applied as signal to the external interlock circuit and etc, please jointly use the delay relay.
When changing the instrument or if the product broke down, users can replace with the
prepared product but even suffix code stays same, operation may differ due to the
parameter difference so please check for the compatibility and perform such action.
Before using a temperature controller, there could be a temperature difference between PV
of the temperature controller and the actual temperature so please operate the temperature
controller after compensating the temperature difference appropriately.
Suffix code
Model
AX
Dimension
Specification
Model
AX2 : 48 X 96
AX3 : 96 X 48
AX4 : 48 X 48
AX7 : 72 X 72
Power consumption
5.5 VA max
Ambient temperature
-5 ~ 50
Ambient humidity
Vibration (resistance)
Shock (resistance)
Weight
320 g
320 g
180 g
300 g
400 g
When selecting the control output type as SSR, users will be able to select the types for voltage
pulse output. The timeshare cycle control turns ON/OFF the output by proportioning the certain
time to an output amount in cycle. Set the cycle of control output in the
parameter.
Within the half cycle of power wave shape, the phase control (depending on an output amount)
controls an output amount by computing the output ON phase. However, when using the phase
control, users must use the RANDOM ON/OFF type SSR.
Load current with 50 % of output
50 % of AC LINE cycle
AX9 : 96 X 96
SSR + Relay1 + Relay2
1B
2B
4 - 20 + Relay2
4 - 20 + Relay2 + Relay3
Input
Multi input (selectable in operator setup mode)
Thermocouple : K, J, R, T (IEC)
RTD : Pt100 (IEC)
Input selection
Input sampling time
Down Key
Model
Up Key
Down Key
Shift Key
Mode Key
Allowable wiring
resistance
Operation
indicators
Performance
Input type
K
J
Range
Celsius ()
Fahrenheit ()
- 100 ~ 1200
-148 ~ 2192
-100.0 ~ 500.0
-148 ~ 932
-100.0 ~ 500.0
-148 ~ 932
0 ~ 1700
32 ~ 3092
-100.0 ~ 400.0
-148 ~ 752
Pt100
-100.0 ~ 400.0
-148.0 ~ 752.0
Timeshare cycle
control
Parameter composition
Dielectric strength
AC LINE cycle
Information
Display the current temperature in the operation screen
1 max
Insulation resistance
Up Key
Shift Key
0.1 sec
Input impedance
Display accuracy
Phase control
Mode Key
RTD
Thermocouple
Voltage fluctuation
Information
Classification
Control type
Code
Output selection
Accuracy : 0.5 % of F.S, Ripple Vp-p : 0.3 % of F.S, Resistive load : Max 600
4 - 20
HANYOUNGNUX CO.,LTD
HEAD OFFICE
12 - 15 V DC pulse voltage
(resistive load min 600 )
PHA
display
When input break (sensor break) occurs or exceeds the maximum temperature range,
will be displayed in the measured value displaying unit.
Alarm
Using the alarm
AX series supports 2 independent alarms (AL1 and AL2). These alarms can allocate AL1 or
AL2 signal in the RLY1, RLY2 and RLY3 and be used. If alarm signal is not allocated in the
RLY1 to RLY3 then the menu related to the alarm will not be displayed.
Operation
mode
2 sec
2 sec
*1
Operation mode
Manual reset
Supplying in the power after finish wiring will display the current temperature. Pressing the
key will display the set temperature and output amount alternatively on the set value (SV)
displaying unit.
0.0 ~ 100.0 %
With P control
Output amount
with input break 0 ~ 100 %
User setup mode is the setting mode that sets the set value that is changed by users
frequently such as alarm set value and loop break alarm (LBA). It made the parameter of user
setup mode to be displayed on the operator setup mode that allows users to set easily
(divided the setting level).
Dimension
Panel cutout
When output
selection is 1 or 2
and
is not
RLY
: Alarm 1 output
Relay 1 property
: Alarm 2 output
: LBA output
[unit : ]
AX2
At all times
: Not using
AX2-B
: Not using
SV setting
Symbol
(PV)
Lists
Information
set temperature
EU 0 ~ 100 %
Display
condition
Default
value (SV)
at all times
EU 0%
EU 0%
EU 100%
When
RLYn
ALn is
set
EU 0 ~ 100 % or
EUS 0 ~ 100 %
(temperature unit)
EU 100%
EUS 0%
When
LBA is
set in the
RLYn
: Not using
Alarm 2 mode
(Alarm 1 or 2)
Alarm 1 type
Alarm 2 type
Alarm 1 standby mode
480
KEY LOCK
at all
times
: Not using
---[
AX3
Dimension
]--[
Panel cutout
Lists
Information
Display condition
AX4
AX3-B
Change SV on the
operation
: No change SV
At all times
: Change SV
AX4
Panel cutout
Operator setup mode is the setting mode that sets the specification of temperature controller
when engineer installs it for the first time. Pressing the
key and
key synchronously in
the operation screen or user setup mode will enter into the operator setup
and
keys
one more time for 2 sec will return to the operation screen.
Connection diagram
AX3
]---
Dimension
Symbol
(PV)
At all times
(Option)
: Alarm 2 output
: LBA output
Alarm 1 mode
(Alarm 1 or 2)
: NO LOCK function
: Operator setup mode LOCK,
Auto-tuning prohibited
: Alarm 1 output
Relay 3 property
EU 0%
At all times
: Alarm 2 output
: LBA output
EUS 0%
: Alarm 1 output
Relay 2 property
Connection diagram
AX4
AX2
Default
value
: J thermocouple
: R thermocouple
AX7
At all times
Dimension
Panel cutout
: T thermocouple
Connection diagram
AX7
AX7-B
: RTD Pt100
Temperature unit / option
Decimal point
ON (YES)
OFF (NO)
0 ~ 120 sec
Voltage pulse
output type
Control output
cycle
Control output
action
At all times
At all times
At all times
At all times
When output
selection 1 or 2
When
or
is CYC
is RLY
At all times
At all times
: ON / OFF control
Proportional band 1 (0.1) ~ EUS 100 %
AX9
AX7
: P.I.D control
Control type
AX3
At all times
Select decimal point
Integral time
0 ~ 3600 sec
Derivative time
0 ~ 3600 sec
AX9
Dimension
Panel cutout
Connection diagram
AX9
AX9-B