RU RHX 1120A Web 110520
RU RHX 1120A Web 110520
RU RHX 1120A Web 110520
RU-RHX-1120A
Replaces RU-RHX-0820B
HEAVY DUTY
UNIT COOLER
Medium to Large Walk-Ins
Cooler and Freezer Applications
Designed for Walk-in Coolers and Freezers in boxes less than 3,000 sq. ft.
Air Defrost
31,200 to 253,100 BTUH
Electric Defrost
33,100 to 227,400 BTUH
Fins
Per Defrost BTUH in Unit Motor
Brand Style Vintage
Inch Type Thousands Voltage Type
(FPI)
R = Russell H = Heavy Duty 4 A = Air D = 208-230/1/60 D = Dual
Y = Reverse Connections 6 E = Electric E = 208-230/3/60 Speed EC
H = Hot Gas 3-Pipe - F = 460/1/60
Electric Drain Pan G = 460/3/60
G = Hot Gas Reverse -
Electric Drain Pan
K = Hot Gas 3-Pipe -
Hot Gas Drain Pan
L = Hot Gas Reverse -
Hot Gas Drain Pan
The AWEF of an evaporator is calculated using the dry coil capacity and the daily evaporator power consumption.
Power consumption included fan and defrost power. Evaporator net capacity reported to the DOE database is dry
coil capacity less the full power fan watts. DOE test conditions are at 10°F evaporator/SST temperature difference
and less than 50% relative humidity and 96°F liquid temperature. These conditions create a uniform test method,
but should not be used for equipment selection. The equipment selected would be oversized for the application.
Russell’s published application ratings are a guideline for proper equipment selection. They account for true
operating conditions experienced by equipment.
208-230V/1 460V/1
Model MCA MOPD MCA MOPD
Number Base EcoNet Base EcoNet Base EcoNet Base EcoNet
Model Enabled1 Model Enabled1 Model Enabled1 Model Enabled1
RH6A031*DA
RH6A043*DA 15.0 15.0 20 20 15.0 15.0 20 20
RH6A052*DA
RH6A063*DA
RH6A087*DA 15.0 16.2 20 20 15.0 15.0 20 20
RH6A105*DA
RH6A132*DA
20.5 22.5 25 25 15.0 15.0 20 20
RH6A156*DA
RH6A175*DA
26.8 28.8 30 30 15.0 15.0 20 20
RH6A209*DA
* Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature.
^ R407A, R448A and R449A are rated at dew point temperature. Use R407A capacity ratings for R407C and R407F.
† Dual Speed EC motors are compliant with California Title 24 regulations.
1. EcoNet Enabled Units are not powered by Condensing Unit so Defrost Heaters are incorporated into shown MCA/MOPD.
Models were designed in anticipation of the July 2020 Department of Energy Annual Walk-in Energy Factor (AWEF)
regulations for evaporators for Walk-in Coolers and Freezers in boxes less than 3,000 sq. ft. See pages 13-14 for AWEF
compliance ratings.
6
6 FPI
RH6E033*DA 33,100 38,700 5,920
RH6E044*DA 44,500 50,900 5,870 1 6.3 3.1
RH6E053*DA 53,800 62,100 5,750
RH6E066*DA 66,400 76,600 11,850
RH6E089*DA 89,400 102,300 11,730 2 12.6 6.2
RH6E109*DA 109,200 125,700 11,500
RH6E134*DA 134,500 153,800 17,600
3 18.9 9.3
RH6E163*DA 163,500 188,800 17,250
RH6E199*DA 199,100 227,400 23,000 4 25.2 12.4
4 FPI
RH4E035*DA 35,800 41,100 5,870
1 6.3 3.1
RH4E044*DA 44,000 50,800 5,750
RH4E071*DA 71,400 83,000 11,730
2 12.6 6.2
RH4E087*DA 87,400 100,900 11,500
RH4E107*DA 107,700 122,900 17,600
3 18.9 9.3
RH4E131*DA 131,900 152,300 17,250
RH4E167*DA 167,000 190,200 23,000 4 25.2 12.4
2. EcoNet Enabled Units are not powered by Condensing Unit so Defrost Heaters are incorporated into shown MCA/MOPD.
* Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature.
^ R407A, R448A and R449A are rated at dew point temperature. Use R407A capacity ratings for R407C and R407F.
† Dual Speed EC motors are compliant with California Title 24 regulations.
Models were designed in anticipation of the July 2020 Department of Energy Annual Walk-in Energy Factor (AWEF)
regulations for evaporators for Walk-in Coolers and Freezers in boxes less than 3,000 sq. ft. See pages 13-14 for AWEF
compliance ratings.
Hot Gas Electric Drain Hot Gas Reverse Cycle 2-Pipe Model
Reverse MOPD Pan Heater A changeover valve is located in the discharge
Cycle Model Amps Heater suction line of the compressor, so that when
defrost is required, the valve changes over
Number Watts
208- 460V/ 208- 460V/ from the normal refrigeration flow so that the
(RH*G, discharged gas flows into the suction connection
230V/1 1 230V/1 1
RH*L) and bypasses TX valve.
LIQUID LINE
6 FPI LIQUID LINE SOLENOID
RH6*033*DA
RH6*044*DA 20 20 8.3 4.3 2,000
RH6*053*DA
RH6*066*DA
RH6*089*DA 20 20 16.7 8.7 4,000
RH6*109*DA
CHECK VALVE
RH6*134*DA
25 20 25.0 13.0 6,000
RH6*163*DA
RH6*199*DA 30 20 33.3 17.4 8,000
4 FPI
RH4*035*DA EXPANSION
20 20 8.3 4.3 2,000 VALVE
RH4*044*DA DISTRIBUTOR
RH4*071*DA
20 20 16.7 8.7 4,000
RH4*087*DA * Each asterisk represents a variable character based on
voltage and defrost ordered. See page 4 for nomenclature.
RH4*107*DA
25 20 25.0 13.0 6,000 1. See capacity correction table and additional notes on page 7.
RH4*131*DA
RH4*167*DA 30 20 33.3 17.4 8,000
10
Shipping Information - Department of Energy Annual Walk-In Energy Factor (AWEF) Ratings
All Models Base Model Number FPI AWEF
Cooler Models - Air Defrost
+
Shipping Est.
No. Dimensions R*6A031*DA 6 9.0
Ship
of (Inches) R*6A043*DA 6 9.0
Wt.
Fans R*6A052*DA 6 9.0
L W H (Lbs.)
R*6A063*DA 6 9.0
1 69 42 66 470
R*6A087*DA 6 9.0
2 109 42 66 730
R*6A105*DA 6 9.0
3 146 42 66 1,000
R*6A132*DA 6 9.0
4 189 42 66 1,130
R*6A156*DA 6 9.0
R*6A175*DA 6 9.0
R*6A209*DA 6 9.0
TYPICAL APPLICATIONS:
Medium to Large Warehouses Cold Storage Warehouses Walk-in Coolers and Freezers
14
Department of Energy Annual Walk-In Energy Department of Energy Annual Walk-In Energy
Factor (AWEF) Ratings Factor (AWEF) Ratings
Base Model Number FPI AWEF Base Model Number FPI AWEF
Cooler Models - Electric and Hot Gas Defrost
+- Freezer Models++ - Electric and Hot Gas Defrost
R*6*033*DA 6 9.0 R*6*033*DA 6 4.15
R*6*044*DA 6 9.0 R*6*044*DA 6 4.15
R*6*053*DA 6 9.0 R*6*053*DA 6 4.15
R*6*066*DA 6 9.0 R*6*066*DA 6 4.15
R*6*089*DA 6 9.0 R*6*089*DA 6 4.15
R*6*109*DA 6 9.0 R*6*109*DA 6 4.15
R*6*134*DA 6 9.0 R*6*134*DA 6 4.15
R*6*163*DA 6 9.0 R*6*163*DA 6 4.15
R*6*199*DA 6 9.0 R*6*199*DA 6 4.15
R*4*035*DA 4 4.15
R*4*044*DA 4 4.15
R*4*071*DA 4 4.15
R*4*087*DA 4 4.15
R*4*107*DA 4 4.15
R*4*131*DA 4 4.15
R*4*167*DA 4 4.15
* Each asterisk represents a variable character based on style, defrost and voltage ordered. See page 4 for nomenclature.
^ For units with mounted TXV components. See Nozzle/TXV table for distributor connection size when TXV is field installed.
1. For dimensional distance between hanger slots, consult model’s corresponding dimension drawing. Hanger slots are 1/2” deep x 1”
wide.
2. Drain is 1-1/4” NPT for all models.
3. For shipping dimensions and weights, see Shipping Information table on page 13.
+
If the model has a numerical value in the table above, the following statement applies: “The refrigeration system is designed and
certified for use in walk-in cooler applications less than 3,000 sq. ft.”
++
If the model has a numerical value in the table above, the following statement applies: “The refrigeration system is designed and
certified for use in walk-in freezer applications less than 3,000 sq. ft.”
15
LIQUID Notes:
• All mounting holes are 1/2” diameter.
44-3/8 AIR
• Evaporators must be mounted with 1/2”
per foot slope to the drain fitting.
4-1/8 • All dimensions are in inches.
SUCTION
27-3/8
3X 1-3/8
2X 1-3/8 KNOCKOUT
KNOCKOUT (BACKSIDE)
(BACKSIDE)
49-1/4 46-1/8
2X 1-3/8 3X 1-3/8
KNOCKOUT KNOCKOUT
(BACKSIDE) (BACKSIDE)
49-1/4 46-1/8
LIQUID Notes:
• All mounting holes are 1/2” diameter.
44-3/8 AIR
• Evaporators must be mounted with 1/2”
per foot slope to the drain fitting.
4-1/8 • All dimensions are in inches.
SUCTION
27-3/8
2X 1-3/8
KNOCKOUT
24
3X 1-3/8
2X 1-3/8
KNOCKOUT
KNOCKOUT
(BACKSIDE)
(BACKSIDE)
49-1/4 46-1/8
3X 1-3/8
2X 1-3/8
KNOCKOUT
KNOCKOUT
(BACKSIDE)
(BACKSIDE)
49-1/4 46-1/8
Due to continuing product development, specifications are subject to change without notice.
201 Thomas French Drive, Scottsboro, AL 35769 • PHONE (256) 259-7400 • FAX (256) 259-7478 • russell.htpg.com
E-mail or call us for help: parts@htpg.com or 1-855-HTPARTS (1-855-487-2787)