Description/Overview
A modulating air to water heat pump in compact design for outdoor installation.
Consisting of
• Hermetically sealed rotary compressors with inverter control.
• A copper-soldered plate heat exchanger made of stainless steel with polypropylene insulation
and frost protection heating.
• Multi-row fin evaporator with large surface area with hydrophilic coating.
• Speed-controlled axial fans.
• A supporting frame structure with powder coating RAL 9001, External cladding made
of surface-coated steel sheet RAL 9001 and including sound-insulating cladding.
• A flow monitor.
• Frost protection heating.
• Temperature sensors on the flow and the return.
• A drain valve.
• Hydraulic connections with Victaulic couplings.
• A Safety valve with a 6 bar maximum setting.
An Electrical box internally wired ready for connection and an external operator terminal with
graphical display and function keys. This can be mounted on the unit or remotely.
Version1.0_M M_ TS_Belari_fit_(53)_7019107_09/22 1
Hoval Belaria-fit (53)
Air to Water Heat Pump
Technical Data
Performance
Cooling
Cooling Capacity A35W18(1) 75.6 kW
EER A35W18 3.3
Cooling Capacity A35W7 55 kW
EER A35W7 2.6
2/4
Hoval Belaria-fit (53)
Air to Water Heat Pump
3/4
Hoval Belaria-fit (53)
Air to Water Heat Pump
• Units are designed to be installed externally in fixed positions. They should be raised from the
ground onto suitable plinths with the bearing points aligned and levelled (refer to O&M for
details).
• Discharged condensation from the evaporator must be drained in such a way as to not cause
harm or danger to people or property.
• Limit vibration transmissions using the anti-vibration feet supplied along with the flexible
connection joints on the heating pipework. The spring vibration feet add to the height
dimension indicated. Anti-vibration feet and flexible couplings are included in the scope of supply.
• Located to avoid obstacles to airflow, heat or pollution sources, stratification or recirculation of
air supply by incorrect positioning.
• Refer to Technical Information Installation/Operation instructions prior to installation for
necessary clearances around the units.
• Integration with heating/cooling systems requires a suitably sized thermal store (a Hoval
EnerVal vessel).
• Option to include Hoval TopTronic E system control elements depending on the hydraulic
arrangement. Refer to Hoval Technical.
• A water filter must be installed directly at the water inlet of the machine, the filter must have
adequate mesh to prevent the entry of particles greater than 0.5mm. A simple Y strainer filter is
included in the scope of the supply for the installer to fit in the return pipework to the heat pump.
• The unit must accommodate frost protection and be protected from freezing. This may require
system separation and use of an anti-freeze solution.
• Installation to comply with all current regulations.
Electrical Connections
Electrical box: Connection terminals main supply, AC filter, phase sequence protection, surge voltage
protection of the compressors, voltage-free contact for ON/OFF, voltage-free contact
for summer/winter changeover, volt free fault signal.wired up ready to connect.
External operator terminal with graphical display and function keys. Control and monitiring of the
modulating heat pumps, setting the heating and cooling curves, selection of opearting mode,
standard, silent and super silient and display of the current operating parameters. The control terminal
can be installed in any room.