Technical Data
OPA 116, OPA 161, OPA 186, OPA 201
Page 2 of 12
Air cooled packaged units
OPA 116, 161, 186, 201
Page 3 of 12
Air cooled packaged units
OPA 116, 161, 186, 201
Applications
Specifically developed for AC of commercial premises
i.e. offices, motels/ hotels, restaurants and retail outlets
Consideration must be given to selecting an airflow and coil face velocity that avoids water carry - over
problems i.e. in high humidity (tropical/subtropical) conditions or when heavily moisture laden fresh air
is introduced
Applications using complete or high proportion of fresh air should be discussed with a Temperzone sales
engineer to establish the correct selection of unit
FEATURES
Refrigerant R410A circuit. This also allows for reliable operation Outdoor & indoor coil fins are epoxy coated
R410A used which has zero ozone depletion in Cooling Mode at ambients below 20°C, for extra protection in corrosive
potential and Heating mode above 15°C environments i.e. salt laden sea air
Page 4 of 12
Air cooled packaged units
OPA 116, 161, 186, 201
The unit’s control panel is fully wired ready to accept the main power
supply. Each system conforms with emission standards EN 55014-1,
EN 60335-1 and EN 60335-2-40.
Page 5 of 12
Air cooled packaged units
Performance Data
Indoor Coil
Models Indoor Fan E.A.T. Outdoor Coil Entering Air Temperature °C D.B.
21 15 11.4 9.0 11.2 9.0 10.9 8.8 10.4 8.5 9.7 8.1 8.9 7.4
23 17 12.0 8.8 11.8 8.8 11.5 8.6 11.0 8.4 10.3 7.9 9.5 7.4
OPA 116 High 650
27 19 12.6 10.1 12.4 10.1 12.1 9.9 11.6 9.6 10.9 9.2 10.1 8.5
31 21 13.2 11.9 13.0 11.9 12.7 11.8 12.2 11.4 11.5 10.9 10.7 10.2
21 15 16.0 12.7 15.8 12.6 15.4 12.4 14.6 12.0 13.7 11.3 12.5 10.5
23 17 16.9 12.4 16.7 12.4 16.2 12.2 15.5 11.8 14.5 11.2 13.3 10.4
OPA 161 High 815
27 19 17.7 14.2 17.5 14.2 17.1 14.0 16.3 13.6 15.4 12.9 14.2 12.0
31 21 18.6 16.8 18.4 16.8 17.9 16.6 17.2 16.1 16.2 15.4 15.0 14.4
21 15 18.2 14.4 18.0 14.4 17.5 14.1 16.6 13.6 15.6 12.9 14.2 11.9
23 17 19.2 14.1 18.9 14.1 18.4 13.8 17.6 13.4 16.5 12.7 15.1 11.8
OPA 186 High 1000
27 19 20.1 16.1 19.9 16.1 19.4 15.9 18.6 15.4 17.5 14.7 16.1 13.7
31 21 21.1 19.1 20.9 19.1 20.3 18.9 19.5 18.3 18.4 17.5 17.1 16.4
21 15 19.8 15.2 19.5 15.2 18.9 14.9 18.1 14.4 16.9 13.6 15.4 12.6
23 17 20.8 14.9 20.6 14.9 20.6 14.9 19.1 14.1 18.0 13.5 16.4 12.5
OPA 201 High 1100
27 19 21.8 17.1 21.6 17.1 21.1 16.8 20.0 16.3 19.0 15.5 17.5 14.5
31 21 23.0 20.2 22.7 20.2 22.1 19.9 21.2 19.3 20.0 18.5 18.6 17.3
Page 6 of 12
Air cooled packaged units
Performance Data
Indoor
Entering Air
Models Temp. °C Outdoor coil entering air temperature °C D.B.
Indoor Unit -5 -3 -1 1 3 5 7 9
D.B.
Outdoor Unit G N G N G N G N G N G N G N G N
15 7.5 6.8 8.2 7.3 8.7 7.8 8.7 8.0 9.8 8.4 10.6 10.1 11.3 11.3 11.8 11.8
OPA 116 20 7.4 6.7 8.0 7.2 8.6 7.6 9.1 7.8 9.7 8.3 10.4 9.9 11.0 11.0 11.6 11.6
25 7.1 6.4 7.7 6.9 8.2 7.3 8.8 7.5 9.3 8.0 10.4 9.9 10.6 10.6 11.2 11.2
15 9.7 8.7 10.5 9.5 11.2 10.0 12.0 10.3 12.7 10.8 13.6 12.9 14.5 14.5 15.2 15.2
OPA 161 20 9.5 8.6 10.3 9.3 11.0 9.8 11.7 10.1 12.4 10.6 13.4 12.7 14.2 14.2 14.9 14.9
25 9.2 8.3 9.9 8.9 10.6 9.4 11.3 9.7 12.0 10.2 12.9 12.1 13.7 13.7 14.4 14.4
15 12.6 11.9 13.3 11.8 14.1 11.9 14.8 12.6 15.5 14.2 16.2 16.2 16.9 16.9 17.7 17.7
OPA 186 20 12.4 11.7 13.2 11.6 13.9 11.8 14.6 12.5 15.3 14.0 16.0 16.0 16.8 16.8 17.5 17.5
25 12.0 11.4 12.8 11.3 13.5 11.5 14.2 12.2 14.0 12.0 15.0 14.1 16.0 16.0 16.8 16.8
15 14.3 13.7 15.1 13.5 15.9 13.7 16.7 16.7 17.6 17.6 18.4 18.4 19.2 19.2 20.0 20.0
OPA 201 20 14.1 13.5 14.9 13.3 15.7 15.7 16.5 16.5 17.4 17.4 18.2 18.2 19.0 19.0 19.8 19.8
25 13.6 13.1 14.5 13.0 15.3 14.5 16.1 16.1 16.9 16.9 17.7 17.7 18.5 18.5 19.3 19.3
Page 7 of 12
Air cooled packaged units
Performance Data
AIR HANDLING
Note: Airflows are for a dry coil. Reduce airflow by 5% in high moisture removal conditions. In a free blow or low resistance application,
beware of exceeding indoor fan motor’s full load amp limit (refer back page). Air flows given are for units installed without filters.
INPUT (W)
1200 RPM RPM
400 1300 700
2.0A
1100 RPM PM
300 1200 R 600
1000 RPM
1.7A
M
200 1100 RP 500
AVAILABLE EXTERNAL PRESSURE (Pa)
INPUT (kW)
1400 RPM
1.0 1.0
14
00
0.9 250 3.8A RP 0.8
PM M
14 00 R 1100 RPM
2.7A 0.8 0.6
RPM
1300
AVAILABLE EXTERNAL PRESSURE (Pa)
4.4A
200 0.7 200 13 0.4
2.3A RPM 800 RPM 00
1200 0.6 RP 0.2
2.0A M
12
00
150 0.5 150 RP
M
2.1A 14 11 8V
00 0
RP 0R
13 PM
100 00 M 100 10
12 RP 9V 00
00 M RP
M
11 RP 90
0 M 0R
0R 8V PM 2.7A
50 10 PM 50 6V
00 3.3A 4.0A 800
RP RP
M
M 2.7A
0 0 1.3A
700 800 900 1000 1100 1200 700 800 900 1000 1100 1200
AIR VOLUME (l/s) 2.5 m/s Face Velocity AIR VOLUME (l/s) 2.5 m/s Face Velocity
Page 8 of 12
Air cooled packaged units
Performance Data
SOUND LEVELS
Page 9 of 12
Air cooled packaged units
Dimensions (mm)
Model A B C D E F G H J K L M
OPA 116 1110 915 73 1038 185 1052 273 207 120 1154 675 80
OPA 161 1160 1070 160 860 225 1062 342 208 125 1154 725 75
OPA 186 1160 1070 45 1095 195 1032 440 203 100 1158 725 95
OPA 201 1230 1175 95 1032 255 1032 440 206 100 1158 800 95
W X 11
500 MIN. CLEARANCE
1200
OVERALL
ELECTRICAL
HOLES
25 DIA.
Z Y
ELECTRICAL
ACCESS OUTDOOR ACCESS
AIR FLOW PANEL 60 C D
PANEL
SUPPLY
OUTDOOR AIR
H
AIR FLOW
RETURN
AIR G
B
OVERALL
35 J
DRAIN
15 BSPF M F
L
187 MOUNTING CENTRES K
12 DIA. HOLES MOUNTING CENTRES
Page 10 of 12
Air cooled packaged units
Specifications
Model OPA 116 OPA 161 OPA 186 OPA 186G OPA 201 OPA 201G
System
Cooling Capacity * 1 kW 11.6 16.1 18.6 18.2 20.0 20.0
Net Cooling Capacity (MEPS) * 1 kW 11.33 15.55 18.2 17.6 19.5 19.7
EER / AEER (cooling) 3.35 / 3.33 3.24 / 3.23 3.30 / 3.28 3.17 / 3.15 3.20 / 3.19 3.14 / 3.13
Heating Capacity * kW2
10.8 14.4 16.7 16.2 19.0 18.1
COP / ACOP (heating) 3.58 / 3.56 3.52 / 3.50 3.52 / 3.50 3.44 / 3.42 3.55 / 3.53 3.33 / 3.31
Air Flow *3 l/s 650 815 1000 1000 1100 1100
Compressor Type fixed speed variable speed fixed speed variable speed
Power Source 3 phase 400 V a.c. 50 Hz
Indoor Fan Maximum Current A 5 5 5 5 8 8
Running Amps (Total System) A/ph. 9/5/5 11 / 7 / 7 12 / 8 / 8 12.5 / 8 / 8 13 / 8 / 8 13 / 8.6 / 8.6
Max. Running Amps (Total) A/ph. 10 / 7 / 7 15 / 11 / 11 16.5 / 10.5 / 10.5 16 / 10.5 / 10.5 18 / 12 / 12 24 / 13 / 13
Controller UC7
Finish
Outdoor Unit grey polyester powder coat
Weight kg
Net Weight 193 225 235 235 270 265
Shipping Weight (approx.) 229 266 276 276 325 320
Notes:
* 1 Nominal Cooling Capacity at AS/NZS 3823 conditions:
- Indoor Entering Air Temp. 27°C D.B., 19°C W.B.;
- Outdoor Entering Air Temp. 35°C D.B.
Subtract indoor fan power to calculate Net Capacity.
Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.
Page 11 of 12
www.temperzone.biz
WELLINGTON LAUNCESTON
ADELAIDE
Phone (04) 569 3262 Phone (03) 6331 - 4209
Fax (04) 566 6249 Phone (08) 8115 - 2111 Fax (03) 6333 - 0224
Fax (08) 8115 - 2118
CHRISTCHURCH JAKARTA
MELBOURNE
Phone (03) 379 3216 Phone +62 (21) 2963 4983
Fax (03) 379 5956 Phone (03) 8769 - 7600 Fax +62 (21) 2963 4984
Fax (03) 8769 - 7601
SINGAPORE
BRISBANE
Phone +65 6733 4292
Phone (07) 3308 - 8333 or Fax +65 6235 7180
1800 - 897 - 253
Fax (07) 3308 - 8330
SHANGHAI
PERTH Phone +86 (21) 5648 2078
Phone (08) 9314 - 3844
Fax (08) 9314 - 3855
Available from