Air Cooled Packaged Units

Technical Data
OPA 116, OPA 161, OPA 186, OPA 201

Cooling Capacity Heating Capacity


11.4kW - 20.0kW 11.6kW - 19.0kW
Air cooled packaged units
Contents

OPA 116, 161, 186, 201 3 PERFORMANCE DATA 6


General 3 Cooling Capacity (kW) 6
Applications 4 I ndoor Air Flow Correction Factors 6
Air Flow Selection 4 @ nominal conditions
Features 4 Heating Capacity (kW) 7
Refrigerant R410A 4 Air Handling 8
Efficiency 4 Sound Levels 9
Performance 4 Sound Power Levels (SWL) - Radiated 9
Quiet 4 Sound Pressure Levels (SPL) 9
Insulation 4 Sound Power Levels (SWL) - Supply Air Outlet 9
Durable 4
User Friendly 4 DIMENSIONS (mm) 10
Self Diagnostics 4
System Protection Features 5 SPECIFICATIONS 11
Refrigeration System 5
Wiring 5
OPA 186/201 Digital Versions 5
Optional Equpiment 5

Page 2 of 12
Air cooled packaged units
OPA 116, 161, 186, 201

Reverse Cycle (heat pump) packaged roof top A/C


Complies with AS/NZS 3823 specified conditions
Designed and tested to operate at 50˚C ambient in cooling and
-15˚C ambient in heating
(OPA 186 & 201 available with digital scroll compressor option)

Page 3 of 12
Air cooled packaged units
OPA 116, 161, 186, 201

Applications
Specifically developed for AC of commercial premises
i.e. offices, motels/ hotels, restaurants and retail outlets

AIR FLOW SELECTION


If air returning to the indoor coil is regularly expected to be above 50% relative humidity then the coil face
velocity should not exceed 2.5m/s (refer air flow graph page 8)

Consideration must be given to selecting an airflow and coil face velocity that avoids water carry - over
problems i.e. in high humidity (tropical/subtropical) conditions or when heavily moisture laden fresh air
is introduced

Applications using complete or high proportion of fresh air should be discussed with a Temperzone sales
engineer to establish the correct selection of unit

FEATURES
Refrigerant R410A circuit. This also allows for reliable operation Outdoor & indoor coil fins are epoxy coated
R410A used which has zero ozone depletion in Cooling Mode at ambients below 20°C, for extra protection in corrosive
potential and Heating mode above 15°C environments i.e. salt laden sea air

Efficiency Quiet User friendly


Incorporates high efficiency scroll Generous use of insulation ensures a quiet The optional TZT-100 has been designed to
compressor and high efficiency EC motor unit. The compressor is enclosed in an maintain a high level of comfort. Emphasis
indoor air fan accoustically insulated compartment to has been placed on providing controls that
minimise noise are easy to use
Heat exchange coils incorporate
inner grooved (rifled) tube for superior Insulation Use of the auto & timer functions allows you
heat transfer Closed cell foam insulation is used in the to “set & forget”
indoor air section to ensure no particles (refer www.temperzone.biz)
Performance enter the air stream. The insulation is foil
faced & meets fire test standards AS1530.3 Easy Access
Forward curved fan with EC motor for ease
of commissioning and adjusting airflows for (1999) & BS 476 parts 6 & 7 These packaged outdoor units are typically
air balancing installed on a rooftop, where maintenance
Durable access is relatively easy during operating
The EC motor can be controlled using a The cabinet and drain tray are constructed from hours.
0-10VDc signal (supplied by others) or by high grade galvanized steel-polyester powdered
setting up for a High / Medium / Low speed coated (Grey) for all weather protection (IP44). Self Diagnosis
arrangement External fasteners are stainless steel. Outdoor unit controller (UC7) has a display
to indicate faults & running conditions.
A variable speed head pressure control is Heat exchange coils are aluminium A common fault indicator is included for
used, ensuring the condenser airflow is corrugated plate fins on mechanically interface to external systems
suited to the pressures within the refrigerant expanded rifled copper tube.

Page 4 of 12
Air cooled packaged units
OPA 116, 161, 186, 201

SYSTEM PROTECTION FEATURES OPA 186/201 DIGITAL VERSIONS


1. HP and loss of refrigerant protection Digital Scroll Compressor
2. Anti rapid cycle timer and internal overload for compressor ‘Digital’ systems include a digital scroll compressor. The digital
protection version of this unit provides a variable capacity ability that enables
3. Circuit breaker protected control circuits closer control of room temperature. This is achieved by avoiding on/
4. Automatic de-ice cycle provides de-ice control during heating off cycling of the compressor. These compressors have proven very
cycle under low ambient conditions reliable because of their design simplicity. Electrical harmonic noise
5. Frost protection on cooling cycle is very low.
6. Sensor fault indication
7. Crankcase heater prevents liquid refrigerant condensing in the Extended Capability
compressors during the “off” cycle Digitals are particularly suitable for applications requiring full or high
8. Compressor minimum run time to ensure oil return proportions of fresh air, VAV, close control. Supply air temperature
control is also possible using BMS or other controls.

REFRIGERATION SYSTEM Control Option


Each high efficiency scroll type compressor is hermetically sealed The system is set up for the compressor to be controlled variably by
quiet running and supported on rubber mounts to minimize a 0–10 volt DC signal that can be supplied either by a BMS system, a
vibration sophisticated controller or temperzone’s optional TZT-100
Controller.
Factory charged with HFC-410A (R410A) refrigerant. Accurator
expansion devices for precise control the flow of refrigerant
OPTIONAL EQUIPMENT
WIRING 1. Anti-vibration mounts

2. TZT-100 room temperature controller


The electrical supply required is 3 phase 342-436V ac 50Hz with
neutral & earth

The compressor crankcase heater requires a 24hr power supply

The unit’s control panel is fully wired ready to accept the main power
supply. Each system conforms with emission standards EN 55014-1,
EN 60335-1 and EN 60335-2-40.

Page 5 of 12
Air cooled packaged units
Performance Data

COOLING CAPACITY (KW)


Total = Total Capacity (kW). Note: Capacities are gross and do not include allowance for fan
Sens. = Sensible Capacity (kW). motor heat loss. For fan motor heat loss refer to fan curves.
E.A.T. = Entering Air Temperature .
= Nominal Capacity (kW).
See below for Indoor Air Flow Correction factors

Indoor Coil
Models Indoor Fan E.A.T. Outdoor Coil Entering Air Temperature °C D.B.

Indoor Unit Air D.B. W.B. 23 27 31 35 39 43


Speed
Outdoor Unit l/s °C °C Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.

21 15 11.4 9.0 11.2 9.0 10.9 8.8 10.4 8.5 9.7 8.1 8.9 7.4

23 17 12.0 8.8 11.8 8.8 11.5 8.6 11.0 8.4 10.3 7.9 9.5 7.4
OPA 116 High 650
27 19 12.6 10.1 12.4 10.1 12.1 9.9 11.6 9.6 10.9 9.2 10.1 8.5

31 21 13.2 11.9 13.0 11.9 12.7 11.8 12.2 11.4 11.5 10.9 10.7 10.2

21 15 16.0 12.7 15.8 12.6 15.4 12.4 14.6 12.0 13.7 11.3 12.5 10.5

23 17 16.9 12.4 16.7 12.4 16.2 12.2 15.5 11.8 14.5 11.2 13.3 10.4
OPA 161 High 815
27 19 17.7 14.2 17.5 14.2 17.1 14.0 16.3 13.6 15.4 12.9 14.2 12.0

31 21 18.6 16.8 18.4 16.8 17.9 16.6 17.2 16.1 16.2 15.4 15.0 14.4

21 15 18.2 14.4 18.0 14.4 17.5 14.1 16.6 13.6 15.6 12.9 14.2 11.9

23 17 19.2 14.1 18.9 14.1 18.4 13.8 17.6 13.4 16.5 12.7 15.1 11.8
OPA 186 High 1000
27 19 20.1 16.1 19.9 16.1 19.4 15.9 18.6 15.4 17.5 14.7 16.1 13.7

31 21 21.1 19.1 20.9 19.1 20.3 18.9 19.5 18.3 18.4 17.5 17.1 16.4

21 15 19.8 15.2 19.5 15.2 18.9 14.9 18.1 14.4 16.9 13.6 15.4 12.6

23 17 20.8 14.9 20.6 14.9 20.6 14.9 19.1 14.1 18.0 13.5 16.4 12.5
OPA 201 High 1100
27 19 21.8 17.1 21.6 17.1 21.1 16.8 20.0 16.3 19.0 15.5 17.5 14.5

31 21 23.0 20.2 22.7 20.2 22.1 19.9 21.2 19.3 20.0 18.5 18.6 17.3

INDOOR AIR FLOW CORRECTION FACTORS @ NOMINAL CONDITIONS


Indoor Air Flow (%)
-20% -10% Rated +10%
Total Capacity 0.95 0.975 1.0 1.025
Sensible Capacity 0.89 0.950 1.0 1.050

Page 6 of 12
Air cooled packaged units
Performance Data

HEATING CAPACITY (KW)


G = Gross Heating Capacity kW, based on nominal air flow.
N = Net Heating Capacity kW allowing for average defrost.
= Nominal Capacity (kW).

Indoor
Entering Air
Models Temp. °C Outdoor coil entering air temperature °C D.B.

Indoor Unit -5 -3 -1 1 3 5 7 9
D.B.
Outdoor Unit G N G N G N G N G N G N G N G N

15 7.5 6.8 8.2 7.3 8.7 7.8 8.7 8.0 9.8 8.4 10.6 10.1 11.3 11.3 11.8 11.8

OPA 116 20 7.4 6.7 8.0 7.2 8.6 7.6 9.1 7.8 9.7 8.3 10.4 9.9 11.0 11.0 11.6 11.6

25 7.1 6.4 7.7 6.9 8.2 7.3 8.8 7.5 9.3 8.0 10.4 9.9 10.6 10.6 11.2 11.2

15 9.7 8.7 10.5 9.5 11.2 10.0 12.0 10.3 12.7 10.8 13.6 12.9 14.5 14.5 15.2 15.2

OPA 161 20 9.5 8.6 10.3 9.3 11.0 9.8 11.7 10.1 12.4 10.6 13.4 12.7 14.2 14.2 14.9 14.9

25 9.2 8.3 9.9 8.9 10.6 9.4 11.3 9.7 12.0 10.2 12.9 12.1 13.7 13.7 14.4 14.4

15 12.6 11.9 13.3 11.8 14.1 11.9 14.8 12.6 15.5 14.2 16.2 16.2 16.9 16.9 17.7 17.7

OPA 186 20 12.4 11.7 13.2 11.6 13.9 11.8 14.6 12.5 15.3 14.0 16.0 16.0 16.8 16.8 17.5 17.5

25 12.0 11.4 12.8 11.3 13.5 11.5 14.2 12.2 14.0 12.0 15.0 14.1 16.0 16.0 16.8 16.8

15 14.3 13.7 15.1 13.5 15.9 13.7 16.7 16.7 17.6 17.6 18.4 18.4 19.2 19.2 20.0 20.0

OPA 201 20 14.1 13.5 14.9 13.3 15.7 15.7 16.5 16.5 17.4 17.4 18.2 18.2 19.0 19.0 19.8 19.8

25 13.6 13.1 14.5 13.0 15.3 14.5 16.1 16.1 16.9 16.9 17.7 17.7 18.5 18.5 19.3 19.3

Page 7 of 12
Air cooled packaged units
Performance Data

AIR HANDLING
Note: Airflows are for a dry coil. Reduce airflow by 5% in high moisture removal conditions. In a free blow or low resistance application,
beware of exceeding indoor fan motor’s full load amp limit (refer back page). Air flows given are for units installed without filters.

OPA 116 OPA 161


l/s - Pa - - - - l/s - W l/s - Pa - - - - l/s - W
500 800
INPUT (W)

INPUT (W)
1200 RPM RPM
400 1300 700
2.0A
1100 RPM PM
300 1200 R 600
1000 RPM
1.7A
M
200 1100 RP 500
AVAILABLE EXTERNAL PRESSURE (Pa)

AVAILABLE EXTERNAL PRESSURE (Pa)


200 100 200 400
1.0A 13
00
1.4A RP
M
150 150 12
0.8A 00
12 RP
00 M
RP 8V
11 M 11
0.6A 0 8V 0 0R
100 0R 100
PM PM 2.9A
10 10
00 00
RP 1.8A RP
90 M M
50 0R 50 90 2.7A
80 PM 0R
0R 1.5A PM
6V
PM 6V
0 1.1A 2.2A
0
300 400 500 600 700 800 400 500 600 700 800 900
AIR VOLUME (l/s) 2.5 m/s Face Velocity AIR VOLUME (l/s) 2.5 m/s Face Velocity

OPA 186 OPA 201


l/s - Pa - - - - l/s - W l/s - Pa - - - - l/s - W
1.1 1.2
INPUT (kW)

INPUT (kW)
1400 RPM
1.0 1.0
14
00
0.9 250 3.8A RP 0.8
PM M
14 00 R 1100 RPM
2.7A 0.8 0.6
RPM
1300
AVAILABLE EXTERNAL PRESSURE (Pa)

AVAILABLE EXTERNAL PRESSURE (Pa)

4.4A
200 0.7 200 13 0.4
2.3A RPM 800 RPM 00
1200 0.6 RP 0.2
2.0A M
12
00
150 0.5 150 RP
M
2.1A 14 11 8V
00 0
RP 0R
13 PM
100 00 M 100 10
12 RP 9V 00
00 M RP
M
11 RP 90
0 M 0R
0R 8V PM 2.7A
50 10 PM 50 6V
00 3.3A 4.0A 800
RP RP
M
M 2.7A
0 0 1.3A
700 800 900 1000 1100 1200 700 800 900 1000 1100 1200
AIR VOLUME (l/s) 2.5 m/s Face Velocity AIR VOLUME (l/s) 2.5 m/s Face Velocity

Page 8 of 12
Air cooled packaged units
Performance Data

SOUND LEVELS

Sound Power Levels (SWL) - Radiated


Measured in decibels re 1 picowatt, at nominal airflow.

OCTAVE BAND FREQUENCY Hz


OUTDOOR 125 250 500 1K 2K 4K
Models FAN SPEED SWL dB(A) SOUND POWER LEVELS (SWL) dB
OPA 116 HIGH 71 81 67 68 67 61 51
OPA 161 HIGH 71 81 67 68 67 61 51
OPA 186 HIGH 75 81 75 73 71 66 58
OPA 201 HIGH 75 81 75 73 71 66 58

Sound Pressure Levels (SPL)


Measured in decibels re 20 µPa, at nominal airflow.

OCTAVE BAND FREQUENCY Hz


OUTDOOR 125 250 500 1K 2K 4K
Models FAN SPEED SPL dB(A) @ 3m SOUND PRESSURE LEVELS (SPL) dB
OPA 116 HIGH 55 65 51 52 51 45 35
OPA 161 HIGH 55 65 51 52 51 45 35
OPA 186 HIGH 59 65 59 57 55 51 44
OPA 201 HIGH 59 65 59 57 55 51 44

Sound Power Levels (SWL) - Supply Air Outlet


Test Conditions: BS 848 PT2 1985. Direct method of measurement (reverberant room).
Installation Type A (free inlet and outlet). Measured in decibels re 1 picowatt.

OCTAVE BAND FREQUENCY Hz


125 250 500 1K 2K 4K
Models AIR FLOW l/s SWL dB(A) SOUND POWER LEVELS (SWL) dB
450 62 58 60 60 57 53 50
OPA 116 550 65 61 63 63 60 56 53
650 68 64 66 65 63 59 56
700 65 61 63 63 60 56 53
OPA 161 760 68 64 66 65 63 59 56
815 70 66 68 67 66 62 59
850 66 61 55 50 45 40 52
OPA 186 925 68 68 81 67 63 60 54
1000 71 83 70 67 63 59 52
580 73 76 69 68 67 66 63
OPA 201 1030 77 80 74 72 72 70 68
1450 81 81 76 75 76 74 72

Page 9 of 12
Air cooled packaged units
Dimensions (mm)

Model A B C D E F G H J K L M
OPA 116 1110 915 73 1038 185 1052 273 207 120 1154 675 80
OPA 161 1160 1070 160 860 225 1062 342 208 125 1154 725 75
OPA 186 1160 1070 45 1095 195 1032 440 203 100 1158 725 95
OPA 201 1230 1175 95 1032 255 1032 440 206 100 1158 800 95

POINT LOAD (kg)


Note: The manufacturer reserves the right to make
Model W X Y Z
changes in specifications at any time without notice or
OPA 116 25 57 42 69 obligation. Certified data is available on request.
OPA 161 37 60 60 68
OPA 186 46 55 72 61
OPA 201 50 60 88 72

500 MIN. CLEARANCE Not to Scale


A
OVERALL PROJECTION

W X 11
500 MIN. CLEARANCE

1200
OVERALL

ELECTRICAL
HOLES
25 DIA.

Z Y

1000 MIN. CLEARANCE

2000 MIN. CLEARANCE

ELECTRICAL
ACCESS OUTDOOR ACCESS
AIR FLOW PANEL 60 C D
PANEL

SUPPLY
OUTDOOR AIR
H
AIR FLOW

RETURN
AIR G
B
OVERALL

35 J

DRAIN
15 BSPF M F
L
187 MOUNTING CENTRES K
12 DIA. HOLES MOUNTING CENTRES

Page 10 of 12
Air cooled packaged units
Specifications

Model OPA 116 OPA 161 OPA 186 OPA 186G OPA 201 OPA 201G
System
Cooling Capacity * 1 kW 11.6 16.1 18.6 18.2 20.0 20.0
Net Cooling Capacity (MEPS) * 1 kW 11.33 15.55 18.2 17.6 19.5 19.7
EER / AEER (cooling) 3.35 / 3.33 3.24 / 3.23 3.30 / 3.28 3.17 / 3.15 3.20 / 3.19 3.14 / 3.13
Heating Capacity * kW2
10.8 14.4 16.7 16.2 19.0 18.1
COP / ACOP (heating) 3.58 / 3.56 3.52 / 3.50 3.52 / 3.50 3.44 / 3.42 3.55 / 3.53 3.33 / 3.31
Air Flow *3 l/s 650 815 1000 1000 1100 1100
Compressor Type fixed speed variable speed fixed speed variable speed
Power Source 3 phase 400 V a.c. 50 Hz
Indoor Fan Maximum Current A 5 5 5 5 8 8
Running Amps (Total System) A/ph. 9/5/5 11 / 7 / 7 12 / 8 / 8 12.5 / 8 / 8 13 / 8 / 8 13 / 8.6 / 8.6
Max. Running Amps (Total) A/ph. 10 / 7 / 7 15 / 11 / 11 16.5 / 10.5 / 10.5 16 / 10.5 / 10.5 18 / 12 / 12 24 / 13 / 13
Controller UC7
Finish
Outdoor Unit grey polyester powder coat
Weight kg
Net Weight 193 225 235 235 270 265
Shipping Weight (approx.) 229 266 276 276 325 320

Notes:
* 1 Nominal Cooling Capacity at AS/NZS 3823 conditions:
- Indoor Entering Air Temp. 27°C D.B., 19°C W.B.;
- Outdoor Entering Air Temp. 35°C D.B.
Subtract indoor fan power to calculate Net Capacity.

*2 Heating Capacity at AS/NZS 3823 conditions:


- Indoor Entering Air Temp. 21°C D.B.;
- Outdoor Entering Air Temp. 7°C D.B., 6°C W.B.

*3 Supply air flow at Nominal Cooling Capacity conditions stated above.

Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.

Page 11 of 12
www.temperzone.biz

AUCKLAND SYDNEY NEWCASTLE


Head Office Head Office Phone (02) 4962 - 1155
38 Tidal Rd, Mangere, N.Z. 14 Carnegie Place, Blacktown, Fax (02) 4961 - 5101
Private Bag 93303, Otahuhu, NSW 2148
NEW ZEALAND. PO Box 8064, Seven Hills West,
NSW 2147, AUSTRALIA.
TOWNSVILLE
Email sales@temperzone.co.nz
Phone (09) 279 5250 Email sales@temperzone.com.au Phone (07) 4774 - 3506
Fax (09) 275 5637 Phone (02) 8822 - 5700 Fax (07) 4774 - 3001
Fax (02) 8822 - 5711

WELLINGTON LAUNCESTON
ADELAIDE
Phone (04) 569 3262 Phone (03) 6331 - 4209
Fax (04) 566 6249 Phone (08) 8115 - 2111 Fax (03) 6333 - 0224
Fax (08) 8115 - 2118

CHRISTCHURCH JAKARTA
MELBOURNE
Phone (03) 379 3216 Phone +62 (21) 2963 4983
Fax (03) 379 5956 Phone (03) 8769 - 7600 Fax +62 (21) 2963 4984
Fax (03) 8769 - 7601

SINGAPORE
BRISBANE
Phone +65 6733 4292
Phone (07) 3308 - 8333 or Fax +65 6235 7180
1800 - 897 - 253
Fax (07) 3308 - 8330

SHANGHAI
PERTH Phone +86 (21) 5648 2078


 Phone (08) 9314 - 3844
Fax (08) 9314 - 3855




Available from

© temperzone limited 2021 05/21 Pamphlet No. 3949

You might also like