Swarco Traffic Systems GMBH: Manual
Swarco Traffic Systems GMBH: Manual
Swarco Traffic Systems GMBH: Manual
MC3224
Manual
MC3224_BE_00
SWARCO TRAFFIC SYSTEMS GMBH
Content
1 Introduction .................................................................................................................................... 4
1.1 About this manual .................................................................................................................... 4
1.2 Usage according to regulations ............................................................................................... 4
1.3 Label ........................................................................................................................................ 5
1.4 Further documentation ............................................................................................................ 5
1.5 Symbols ................................................................................................................................... 5
1.6 Safety instructions ................................................................................................................... 6
8 Appendix ...................................................................................................................................... 35
8.1 Technical data ....................................................................................................................... 35
8.2 Dimensions and housing layout ............................................................................................ 36
8.3 Mounting and dismounting .................................................................................................... 37
8.4 Pin assignment ...................................................................................................................... 37
8.4.1 Overvoltage protection of inductive loops ..................................................................... 37
8.4.2 Connection terminals on top and bottom side ............................................................... 37
8.4.3 DIN rail bus system TBUS ............................................................................................. 39
8.4.4 Pin assignment service interface (3.5 mm stereo jack plug, TRS) ................................ 40
8.5 Requirements for the usage according to regulations ........................................................... 40
8.6 EC Conformity ....................................................................................................................... 41
1 Introduction
In this chapter you will find preliminary remarks about the usage of the MC3224, as well as
explanations about the structure of this manual and the usage of symbols.
We attach great importance to the safe, appropriate and effective handling of this device.
It is therefore important to read this manual thoroughly before using the device. In the
manual you will find important instructions helping you to avoid danger and to prolong the
reliability and durability of the device and the accessories.
For your own safety you should read the safety instructions. Follow the instructions closely in
order to avoid danger for yourself and others or damage to the device.
If you have any questions about the MC3224 which are not answered in this manual, or if
you have problems understanding the descriptions, please contact:
www.swarco.com/sts
NOTE
The MC3224 is designed for precise vehicle classification and speed measurement
in interurban systems for traffic data acquisition and traffic control. It is less suited
for urban applications e.g. at traffic light intersections. The conditions for precise
vehicle classification such as constant moving are not fulfilled. For these kinds of
applications we recommend using detector types from our traffic lights product folio,
e.g. IG746 (see www.swarco.com/sts/detection).
For further requirements for the usage according to regulations see chapter 8.5.
1.3 Label
The MC3224 is provided with a quality label and serial number. You will need the indications
when talking with the customer service, e. g. ordering accessories or spare parts.
Note here the serial number and name of the device in order to have them available when
needed:
This manual is valid for all classification detectors type MC3224. Documentation of optional
functionalities are described in chapter 1.4.
CE-label:
1.5 Symbols
In several places throughout this manual you will find the following symbols stating important
safety instructions:
ATTENTION!
This symbol indicates dangers which might cause damage to people
or property
NOTE
This symbol indicates information for installation and function
of the device
ATTENTION!
Danger of electricity!
Make sure that no liquid may get inside the device. If this happens, interrupt the
power supply to the device at once.
If you notice any damage, e.g. broken or crushed cables, damaged plugs,
enclosures etc., turn off the device at once, interrupt the power supply and make
sure that the device cannot accidentally be turned on again.
The device may only be installed, brought into service and repaired by an electro-
technical expert. Inappropriate operation, improper maintenance or not observing
the instructions in this manual can lead to danger.
Any malfunction of the device which may limit the safety of its users or others must
be removed immediately. All warning and safety labels on the device must be
observed and kept complete and legible.
The appropriate usage must be observed by all means. For damage resulting from
inappropriate usage the manufacturer will not undertake any liability.
The device must not be used as a safety component in the sense of the European
Directive 98/37/EC ("Machinery Directive”). In systems with high risk additional
safety measures are necessary.
The operator of the device must ensure that the chosen means of operation will
not cause damage to material or danger to people and that all security and safety
installations are present and functioning.
Before installation and first operation please observe the instructions in the
manual.
The manual must be available at the site of usage at any time. It must be read
thoroughly and applied appropriately by the person responsible for the operation,
maintenance and service of the device.
NOTE
Our products are in a constant process of improvement and advancement.
Because of this, read the current manual thoroughly before installation and first
operation.
Without prior consent of the manufacturer, no modifications, neither mechanical
nor electrical, may be done. Only parts that have the consent of the manufacturer
may be used for backfitting or as accessories. Any violations will lead to the
termination of conformity and the manufacturer’s warranty. The user will
subsequently bear the risk.
2 Product description
2.1 General
The MC3224 now offers the functions and outstanding features of the SWARCO TRAFFIC
SYSTEMS 19“ plug in classification detectors also in a DIN rail mount version. Based on the
proven and tested MC2224, it includes a complete overvoltage protection module for the
induction loops. This integration, together with the mounting concept and the compact
housing, considerably reduces the required wiring effort and space.
The MC3224 is a classification detector operating with two induction loops per lane
according to TLS-specifications. The usage of powerful 32-Bit controllers allows the
improvement of all features such as classification accuracy, power consumption, as well as
the function range.
The MC3224 classifies the vehicles into the TLS-classes ((8+1), (5+1) vehicle classes or car-
similar / HGV-similar). When using TLS loops, the classification meets the definitions of
BASt. The vehicle class is determined by means of the detection curves, which show typical
features for the different classes and the loop type used.
ATTENTION!
The MC3224 is availabe in two versions especially adjusted for the two inductive
loops type 1 and 2 defined in the TLS. Please indicate the correct type when
ordering, e.g.: MC3224T9 (standard TLS loop type 2) resp. MC3224T9I (TLS loop
type 1).
Only by the use of the correct loop type, the excellent classification accuracy could
be achieved.
The detection quality is not influenced by e.g. the weather. By activating the directional logic,
messages for wrong way drivers can be generated.
The detector can provide the following single vehicle data via service interface and RS485
data interface:
Single vehicle data: vehicle class, speed (up to 300 km/h), length, distance, driving
direction
Additionally available at data Interval occupancy and time gap to calculate the occupancy rate;
interface: single-vehicle occupancy and time gap
(8+1)-vehicle classes: other vehicles / motorbike / car / van / car with trailer / HGV / HGV
with trailer / HGV articulated / bus
The classification into (5+1) vehicle classes resp. car-similar /
HGV-similar vehicles is based on the (8+1) vehicle classes
according to TLS definitions.
Table 1: Data of the MC3224 at the service and data interface
Single vehicle data is transmitted via the RS485-bus to a controller, which carries out the
further data-aggregation according to TLS-specification.
The detector aligns itself automatically to the loops and feed combination connected.
Variations in temperature do not affect the data acquisition. The measurement systems are
permanently checked for short-circuited or open loops and only put in an error status when a
definite malfunction is recognized. If one loop of the TLS double-loop system is defective, the
remaining loop still provides time of occupancy, time gap and a classification of car-similar
and lorry-similar vehicles. Speed and vehicle length cannot be detected anymore.
Short measurement intervals and a particular speed measurement processes ensure the
high accuracy of measurement data and the high detection speed according to BASt
requirements.
The detector processes the loops one after the other in a predetermined sequence (multiplex
mode); i.e. there is always only one loop switched as inductance L to the LC oscillating circuit
of the detector. Since there is always only current flow through one loop, the channels of a
detector cannot interfere with each other. The channel reaction times and the cycle time of
the detector indicated in the technical data result from the multiplex mode.
If a metallic object is located within the range of action of the connected induction loop, the
frequency of the LC oscillator also changes owing to reduction in the loop inductance. The
detector evaluation circuit determines these changes and generates e.g. vehicle profiles for
the classification.
The detector is configured via service interface on the front. The free PC service software
LoopMaster provides a convenient operator interface for modifying and displaying all
parameters and diagnostic values. The configured parameters are stored in a non-volatile
memory (EEPROM).
ATTENTION!
The loop detector MC3224 is solely designed for use by qualified personnel trained
in dealing with traffic detection equipment. Improper use of the MC3224 may result
in unpredictable behavior of the systems controlled by the detector.
1
Without speed and length measurement, no recognition of driving direction (not possible for CD9234)
Wire the device according to the terminal assignment in the appendix (chapter 8.4).
Please refer to the technical data for the specification of the supply voltage.
HINWEIS
When connecting the loops, all feeder cables must be twisted up to the terminal
clamps of the MC3224! Do not use the feeder cables parallel to e.g. AC-power
supply or communication cables! The loop installation manual by SWARCO
TRAFFIC SYSTEMS GMBH must be observed (available on request).
ATTENTION!
When connecting the integrated overvoltage protection of the inductive loops, the
DIN-rail must be connected with the protective earth (PE) (see also chapter 8.4.1).
ATTENTION!
Incorrect connection of the unit may result in malfunctions or destruction of the unit.
SWARCO TRAFFIC SYSTEMS GMBH does not provide any warranty coverage for
unit function in case of incorrect installation and cannot be held liable in this case.
The general electro-technical rules must be complied with when connecting the
detector.
After switching on the unit for the first time, the detector aligns to the connected loop
inductance. Short-circuited or open loop connections are indicated by the ERR (ERROR)
collective error LED and flashing of the channel LED of the disturbed channel (see also
chapter 6.2). The FCT (FUNCTION) LED flashes during normal operation with a frequency
of 1 Hz.
Before the detectors are installed, the loop values must be checked. The values for loop
inductance, ohmic resistance and insulation resistance should be checked and documented.
For more information about loop installation see the manual “Loop installation TLS“.
For longer distances to the roadside station, we recommend using an outdoor telephone
cable type A-2Y (L) 2Y resp. A-2YF (L) 2Y (see also chapter 8.1). Please also observe the
according information about loop connection and cable types to be used stated in the TLS.
In order minimize the coupling of channels caused by a shared feeder cable, both channels
of a measurement system must be connected to the opposing leads of a star quad (e.g.
channel 1: 1a – 1b and channel 2: 2a – 2b).
1a
channel 1
2a 2b
1b
channel 2
Figure 3: Connection of the inductive loops in a star quad of cable type A-2Y (L) 2Y
HINWEISE
With the MC3224, for feed cable lengths up to 300 m and the indicated cable type only
one pair of wires per loop is necessary in the feed cable. No expensive double pair
of wires – often impossible in existing systems – is needed.
For feeder cable lengths longer than 300 m up to approx. 500 m, a double pair of wires per
loop can also be used (please inquire). Here, a star quad is used per channel. The parallel
wiring of 1a / 1b and 2a / 2b reduces the ohmic resistance of the feeder cable by half, the
inductance of the feeder cable is reduces to approx. 25 % of the value using one pair of
wires.
Malfunctions, indicated at the ERR LED are displayed in the LoopMaster operating program
and can be determined by the blinking of the channel LED with the help of Table 2. If
operation is faultless, the correct function of the traffic data acquisition should be checked on
location using single vehicle data after having detected a minimum of approx. 50 cars.
Classification, vehicle length and driving direction can be controlled by monitoring cars
passing the loop system and comparing them with the vehicle data read out at the service
interface (see chapter 6.3).
An exact evaluation of speeds can only be done by means of a calibrated speed reference
(e.g. laser / radar gun).
4.1 General
The MC3224 is operated via service interface on the front (SERVICE) by means of the
LoopMaster operating program installed on a PC or laptop computer. The detector is
connected directly with an USB interface of the PC.
NOTE
Please use an USB adapter cable with 3.5 mm jack plug. SWARCO TRAFFIC
SYSTEMS GMBH label KA_Service_AJ-USB (order number: D.000.604.466).
Please use the LoopMaster program only, the preceding program IGBT does not
support this detector type.
In the LoopMaster program the following interface parameters can be set: (Settings –
Communication settings…):
COM port
Baud rate: 4800 Baud (default)
The LoopMaster program provides an extensive help function, therefore only the most
important functions will be described in the following.
4.2 Functionalities
In the parameter and diagnosis windows of LoopMaster the parameter and diagnosis values
used in the MC3224 are displayed as clear text. There are windows for individual channels,
normally 4 in the MC3224, and one detector window. The detector window lists the according
values for several channels and / or of the complete device. The data of these values
between LoopMaster and MC3224 is transferred together with the channel values.
The displayed values in the channel and detector windows are classified into alterable
parameter values and unalterable diagnosis values. The entry fields for the alterable
parameters are white, the display fields for the diagnosis values are grey.
Besides these windows a terminal window is located at the left side of the LoopMaster
program which logs the serial communication via service interface. In this window also all
current vehicle data are listed.
When the LoopMaster program is started, all channel and detector data are automatically
requested and displayed in the according windows, the status bar at the bottom part of the
window is updated.
The displayed information are used to identify the detector hardware and firmware:
Detector type, e.g. MC3224
Serial Number, e.g. SN123456
Country code of the service interface output, e.g. E (English) or D (German)
Detector firmware date, e.g. Dec 10 2012 (10.12.2012)
Version status of the detector firmware, e.g. V1.03 (Version 1.03)
Identification for the detector-specific display in LoopMaster, loop configuration,
e.g.: LC22: 2 loop systems with 2 double loops each
Opposite to detectors for traffic light systems, the MC3224 is normally used as double loop
detector, i.e. in order to function a loop system with 2 inductive loops arranged successively
is necessary. Channels 1 and 2 form the first loop system, channels 3 and 4 the second loop
system.
This makes no difference in the operation of the LoopMaster program: the 4 channels are
separately listed. However, please pay attention to the following notes.
NOTE
In order to parameterize a double loop system, use the window of the according
first channel. Alterable parameters are thus only available for channel 1 resp.
channel 3.
The detector automatically adopts the correct parameters for the according second
channel of the loop system. The parameters of the channels 2 resp.
4 cannot be altered.
The diagnosis values of the channels are still displayed individually.
Figure 5: front panel of MC3224 with LEDs, pushbutton and service interface
The detector has an LED for each channel to indicate vehicle detection (CH1…CH4).
Furthermore, in case of a malfunction, the LEDs display the cause of the malfunction (e.g.
loop open) by means of a predetermined number of LED blinkings (see chapter 6.2).
The reception and transmission processes of the RS485 data bus interface are indicated at
the RXD and TXD LEDs for the reception and transmission direction of the MC3224 .
The FCT LED flashes with a frequency of 1 Hz during normal operation of the detector. With
activation of MASTER-SLAVE synchronization, the flashing frequency during normal
operation is reduced to 0.5 Hz.
The RES LED pushbutton has 3 functions, depending on how long the button is being
pushed:
All detector settings are made using the front service interface (labeled: "SERVICE").
6.1 Alignment
Alignment is defined as initialization of a detector channel. In doing so, all settings are
configured according to the parameters saved in the EEPROM (e.g. frequency, sensitivity).
There must be no extended vehicle passages during the alignment. If a convoy of vehicles
passes during alignment, the MC3224 attempts to adjust to the gaps between the vehicles.
There are no vehicle detections possible during the alignment. After the alignment, the
channel is always in an "undetected" status.
ATTENTION!
When a channel is aligned, vehicles located within the range of action of the
induction loop at this point in time are ignored. This means that they are not
detected during and directly after the alignment!
After RESET, all activated channels are aligned. When prompted by a parameter transfer via
service interface by means of LoopMaster, only the selected channels for which at least one
parameter has changed are realigned. All other channels continue to operate without any
influence on their detection in this case. The alignment takes approx. 1 sec. with an
unaffected induction loop and may take longer e.g. with disturbances on the loop. The
corresponding channel LED CH1 ... CH4 is activated during the alignment and additionally
the FCT LED flashes faster (approx. 5 Hz). Once alignment has been successfully
completed, the channel LEDs CH1 ... CH4 are switched off and used for the indication of the
detection status.
These errors are displayed in the channel windows in the LoopMaster as "channel error"
diagnostic parameters (see chapter 7.3.5). Furthermore, the ERR collective error LED
indicates an error status with at least one channel.
In case of a short-circuited or open loop, the alignment algorithm detects that the connected
inductance (induction loop + feeder cable!) is outside the permissible range (see chapter
8.1). The error cause is to be found and eliminated.
If the selected frequency range cannot be set, the loop inductance lies outside the
recommended range (see chapter 8.1). To solve this problem, set another frequency range
(see chapter 7.1.2).
The error message "Disturbance" indicates external interferences during alignment. This
causes longer alignment times (more than approx. 2 s per channel). The external inter-
ferences must be determined and eliminated in order to ensure the correct detector function.
Otherwise, misdetections may occur, i.e. the according channel switches even without loop
attenuation. The external inferences may be caused by electromagnetic fields or pulses in
the environment of the induction loop or feeder cable. Selecting another frequency range
may solve this problem.
If the disturbances are caused by other identical loop detectors, the interference can be
eliminated by synchronizing the detectors by means of the synchronization leads of the
terminal strip (see chapter 7.5).
The duration of the channel alignment is restricted to the set duration using the "maximum
loop alignment duration" parameter. The error message "maximum loop alignment duration
exceeded" is generated if this time is exceeded.
After troubleshooting, an alignment of all channels or a reset of the MC3224 with subsequent
alignment of all channels can be initiated using the pushbutton on the front panel in order to
restore correct functionality.
If the channel flag "Automatic recalibration in case of channel error" (see chapter 7.1.9) is
activated (factory setting: deactivated), a cyclical alignment is performed in case of a channel
error. At the latest 1 min. after troubleshooting, the channel faults will automatically be
removed in this case, except for the following fault:
In this case also, a vehicle located within the range of action of the loop at the time of
troubleshooting will be ignored.
If one loop of a double loop system is faulty, the other loop works in limited operation. A high-
quality classification (e.g. TLS-(8+1)) is not possible anymore, because vehicle lengths and
speeds cannot be determined. The classification will automatically be reduced to car-similar /
HGV-similar vehicles. In order to reach the original data acquisition quality, the failure cause
must be eliminated.
The adjustment of the sensitivity is not possible, since the response thresholds for the
vehicle detection are permanently evaluated by using the norm value. The automatic
alignment usually has achieved sufficient accuracy after a detection of approx. 50 cars.
Afterwards, a control of the single vehicle detection can be done by visually comparing the
vehicles with the data readouts at the service interface on the front. To do so, the
LoopMaster terminal window or any terminal program can be used. The following data are
displayed separated by detection system:
Vehicle class
Vehicle speed
Vehicle length
Driving direction
Vehicle distance
Examples:
Detection system1 (channel 1 / 2): vehicle class delivery van, length 5.21 m,
speed 54.3 km/h,
driving direction 0 ≡ loop 1 2,
distance 14 m
With the standard width of the terminal window (16 characters) the traffic data is displayed in
4 rows per vehicle. When the width is set >63, the data is displayed in one row per vehicle.
Afterwards, the norm value should be checked (LoopMaster: channel diagnosis value). The
norm value is different for each loop type and is mainly determined by loop length and
installation depth. Also, the norm value is reduced when the length of the loop feeder cable is
increased. Typical values for the norm value with common loop types depending on the
feeder cable lengths are indicated in the following table:
If you notice strongly diverging values or big differences between the loops of a double loop
system, the quality of the data may be reduced. Reasons for this can be e.g. metallic objects
in the area of the inductive loops.
ATTENTION!
For the precise and reliable vehicle detection, a homogenous (uninterrupted)
magnetic field in the loop area is indispensable. Metallic components such as
manhole covers and reinforcement in concrete carriageways as well as the
installation of inductive loops in bridges with metallic fundaments can have a
negative influence on the quality of the vehicle detection.
Without these influences and with correctly installed inductive loops, the difference of the
norm value between the loops of a double loops system is usually less than 3 %.
For the exemplary reference value for TLS type 2 without additional feeder cable from Table
3 this is 1.45 % and 1.55 % as norm values of the two loops.
Further reasons for bigger differences are different installation depths, number of windings or
loop dimensions.
In addition to the user-adjustable parameters, the MC3224 also provides diagnostic data,
which can be displayed in the LoopMaster. These values cannot be directly modified but
result from the parameters (e.g. frequency from configured frequency range), are determined
during operation (e.g. last amplitude) or result from the unit operating status (e.g. channel
status, RESET counter). It is to be noted that all displayed data show the current status of
the detector at the time of parameter request (LoopMaster menu item: "Read parameter“).
ATTENTION!
The user must take care that the configured parameters ensure a logical and
reliable detector function.
‘0’ 30 - 44
‘1’ 45 - 64
‘2’ 65 - 84
‘3’ 85 - 110
Table 4: frequency levels and ranges, factory setting (bold)
The oscillator of the MC3224 is designed in such way that, when using loops with inductan-
ces within the recommended range, all frequency ranges can be used (see chapter 8.1).
In order to have the best noise immunity, the maximum measurement frequency should be
used.
An interconnection of detector channels can be the result when the distance between
inductive loops is too small and / or when they share the loop feeding. The smaller the
distance between the loops and the longer the channels are e.g. lead through a shared
feeder cable, the larger is the interconnection.
ATTENTION!
Please observe that the interconnected detectors must work with different
frequencies and that additionally the synchronization function must be activated
(see chapter 7.5.1).
When several MC3224 are used as a standard for a detection cross section, e.g. on the
motorway, we recommend the following procedure to set the frequency.
Normally, 2 resp. 3 lanes per driving direction must be detected. To do so, 4 resp. 6 double
loop measurement systems are necessary, which are distributed over the different detectors,
i.e. systems with longer feeder cables use lower frequencies and systems with shorter feeder
cables use higher frequencies.
Here, it is sensible to set the frequency ranges for both measurement systems of a detector
identically.
Detector 1 2
Driving direction 1 2
Lane 1 2 1 2
Frequency range 3 3 2 2
Frequency [kHz]
(2 channels per 92 and 91 86 and 87 66 and 67 77 and 76
system)
Table 5: Example for a motorway with 2 lanes per driving direction
As shown, with 2 lanes it is reasonable to allocate the lanes of one driving direction to one
detector. The inductive loops of neighboring lanes of one driving direction don’t interfere with
each other because of the multiplex mode, the large distances of the inductive loops of
different driving directions also avoid interference. If the feeder cables are separate for each
driving direction, an interference of the two detectors can be ruled out. If these conditions are
not met, different frequency ranges must be used as indicated in the example.
Detector 1 2 3
Driving direction 1 1/2 2
Lane 1 2* 3* 1** 2** 3
Frequency range 3 3* 2* 2** 1** 1
Detector 1
Individual feeder cable per detector
1.1 – 1.4
Detector 2
2.1 – 2.4
Inductive
Lane loops Detector 3
3.1 – 3.4
1 1.2 1.1
3 2.2 2.1
Possible interference with
3 3.3 3.4 adjacent systems
1 2.3 2.4
In this case also the inductive loops of different driving directions cannot interfere with each
other either if the feeder cables are separated. Thus, only the inductive loops of neighboring
lanes in one driving direction which are controlled by different detectors are subject to a
direct interference (values in Table 6 marked in bold). Here, with identical measurement
frequencies, an interference of measurement systems would exist because of the sidewise
distance of approx. 0.7 m up to 1.6 m. The selected frequency ranges and the resulting
measurement frequencies avoid this as far as possible (frequency gap > 5 kHz). Further
improvement can be reached by activating the synchronization function (see chapter 7.5).
Since the loop length is directly related to the loop type and since it cannot be changed, it is
displayed as diagnosis value (see chapter 7.3.1).
For the standard loop type with defined loop distance, the loop distance cannot be changed.
Thus, a second loop type with variable loop distance is defined. Here, the parameter loop
distance defines the head distance of the loops e.g. from the beginning of the first loop to the
beginning of the second one. Values which are too low or too high are automatically limited
to the permitted range.
ATTENTION!
In order to reach a highly-precise classification, the loop geometry (length and
width) may not differ from TLS definitions.
Changing the length correction value can be necessary in the following cases:
Strongly diverging loop lengths. In this case, please take into account the strong
influence of the actual loop length on the classification accuracy
Inductive loop laid in greater depth
Metallic objects (manholes, reinforcement in concrete roads) in a distance of much less
than 1 m
Otherwise, when using standard TLS loops and observing the tolerances and / or geometry
and laying depth, no length correction is needed; the correct length correction value is set as
default for each loop type resp. loop length.
The adjustment of the length correction may be effected only after a new alignment and the
detection of approx. 50 cars. For this, the length value of a car with known length as
indicated at the service interface (e.g. VW Golf 4.0 – 4.2 m) must be checked and the length
correction must be adjusted until there is an accordance to the known vehicle length. A
higher / lower value of the length correction causes a lower / higher value of the real length.
In the single vehicle data of the service interface (see also chapter 6.3) the “normal” driving
direction is displayed as “di.“, the wrong way driver as “ww.“.
If the evaluation of direction is turned off, the wrong way driver message on the data and
service interface is deactivated.
Service interface:
di.0 di.1 di.0 ww.1 ww.0 di.1
Single vehicle readout
Data interface:
Wrong way driver flag 0 0 0 1 1 0
single vehicle telegram
Table 7: Overview wrong way driver detection: Parameterizing and data readout
Therefore, the sensitivity cannot be changed. The MC3224 has an automatic sensitivity
adjustment and very short measurement times in order to ensure optimum single vehicle
detection also at high speeds.
When the detector is delivered, the measurement time is optimally set for the application and
usually does not need to be changed.
If the vehicle leaves the loop afterwards, the original sensitivity is reached at approx. 4 s after
leaving the loop. Further vehicles restart this time period.
With static hold time (infinite hold time), external interferences may reduce the actually
achievable hold time. Setting a finite hold time generally ensures reliable operation in these
cases. Still, the requirements of traffic data acquisition, which don’t permit a short hold time,
must be observed (e.g. detection of congestions).
NOTE
If congestion detection is necessary due to traffic data acquisition requirements, the
default ”infinite hold time“ must not be changed.
The channel alignments initiated by exceeded hold times are displayed in the channel
diagnostic value in the (see chapter 7.3.6).
Automatic recalibration in case of channel error (for functionality see chapter 6.2)
Contact position of the switching outputs
Contact position in case of an error
The contact position of the switching outputs (open collector) can be influenced in the
following manner:
Normally Open (NO): open collector HIGH when loop not occupied
(factory setting),
Normally Closed (NC): open collector LOW when loop not occupied
On detection (loop occupied), the output switches to the respective other position.
The contact position in case of an error in the channel can be adjusted as follows:
The default values should only be changed in exceptional cases if the detector function is
strongly influenced by interferences. In this case, the noise threshold must be raised step by
step.
If several detectors are to be synchronized with one another in order to avoid their mutual
interaction, the MASTER setting must be configured here for just one detector. For further
information concerning synchronization see chapter 7.5.
The deactivation of the data bus hardware address cannot be changed since there is no
hardware address for this detector type.
In the standard version of the MC3224 (double loop system), this configuration is displayed
as “Double loop function (v, l , dir.): On“ and measurements of speed (v) and length (l) as
well as detection of direction (dir.) are possible.
The "Channel error history (since POR):" flag is reset in case of a Power On Reset
(abbreviation: POR, i.e. reset on switching on the supply voltage).
Standard: (8+1)
Option 1: (5+1)
Option 2: car-similar / HGV-similar vehicles
The number of exceeded hold times is indicated in a separate counter and is also included in
the number of (total) alignments. In the default setting of the hold time (infinite) there are no
exceeded hold times possible.
These values can be reset using the LoopMaster menu item: "Reset counter".
7.3.7 Inductance
The inductance of the inductive loop (including feeder cable!) is indicated in µH with a
resolution of 10 µH. The inductance is determined with an accuracy of approx. +/- 20 %
within the recommended inductance range.
7.3.8 Frequency
The frequency indicated here in kHz lies within the set frequency range and is used e.g. for
controlling the frequency gaps to channels of other detectors (see Instructions for setting
the frequency with several detectors in chapter 7.1.2).
If the value exceeds resp. falls below the turn-on threshold the "channel occupied" resp.
"channel not occupied" message is issued on the channel LED and the switching output.
The maximum attenuation indicates the maximum detuning since the last alignment and
should be approx. 2 – 3 times of the norm value.
These values can be reset using the LoopMaster menu item: "Reset counter"
When the synchronization function is activated, the cycle time is the sum of the accordingly
longest channel measurement times of all synchronized detectors. Please note that the cycle
time should not exceed 8 ms.
To activate the synchronization first the bus system TBUS, which can be integrated in the
DIN-rail, must be installed (see chapter 8.4.3). The synchronization line of the detectors, as
well as the power supply and the RS485 data interface are then connected with each other
via this bus system. At the middle connection of the screw clamp of the TBUS (clamp 3) the
synchronization line can be wired with further devices (maximum 30 ) such as detectors with
identical synchronization methods installed in a rack (e.g. MC2224).
Additionally, exactly one detector must be defined as MASTER. All other devices must
remain in the default setting SLAVE.
ATTENTION!
Configuration of several MASTERs is not permitted!
For SLAVE detectors, that are already synchronized with a MASTER, the activation
of the MASTER function will automatically be prevented.
When the MASTER-SLAVE setting is changed no RESET is executed and the traffic data
acquisition is not interrupted. The start and the end of the SLAVE-synchronization is
performed as part of an alignment of all channels of the SLAVE units if:
After all detectors have finished the initialization of synchronization and the channel
alignment, all FCT LEDs flash synchronously with a frequency of 0.5 Hz, however, the ones
of the MASTER inversely to the SLAVE units.
To terminate the RS485 bus at the detector, a 4-pole DIP switch is located behind the front
panel which can be removed:
NOTE
As default the switches 1 - 4 are in OFF position, i.e. the RS485 bus is not
terminated! Activate the termination once at the detector at the end of the RS485
bus line!
With lower baud rates (e.g. in default setting 9600 baud) and with short data bus
lengths < 1 m, usually no termination is necessary.
ATTENTION!
The DIL-switches may only be set when the device is not connected to supply
power. To do so, unplug all connections of the device and take it out of the DIN-rail.
To remove the front panel: Slightly push apart the housing at the long side of the front panel
and loosen the panel at the 4 fixation points.
8 Appendix
8.1 Technical data
Technical Data
Supply voltage Standard: nominal voltage 24 V DC,
range: 10 V DC - 38 V DC
optional: 5 V DC +/-5 % (regulated and load-independent),
on request
Power consumption max. 0.7 W with 24 V DC
Loop frequency range 30 kHz – 110 kHz
RS485 interface 9600 baud, 11-bit transmission frames, 8 data bits, even parity,
1 start bit, 1 stop bit
transmission procedures in accordance with IEC-870,
asynchronous, half-duplex, manufacturer-specific telegram
content available on request
Termination resistance 120 and pullup / pulldown resistance
adjustable via switch.
Connection see chapter 8.4.2 and 8.4.3
Service interface USB adapter cable with 3.5 mm stereo phone connector (TRS),
(at front, “SERVICE“) label: KA_Service_AJ-USB
order number: D.000.604.466
Switching outputs switching output per channel: Open Collector (not potential free)
Umax = 38 V DC, Imax = 50 mA DC,
Ptot = 125 mW Ic 50 mA: Ucesat 0,4 V
Max. length of feeder cable approx. 300 m for TLS loop type (approx. 25 ), values apply
to indicated loop induction ranges and the following cable types:
A-2Y (L) 2Y Zx2x0,8 BdStlll or
A-2YF (L) 2Y Zx2x0,8 BdStlll (Ø 0,8 mm, Z e.g. 2, 10)
optional: feeder cable lengths up to approx. 600 m (on request)
Duration of loop measurement 1.5 ms per channel / 6.0 ms for 4 channels
Definition of inductive loops to TLS type 2 (standard)
be used L x B: 1.0 m x (lane width - 2 x 0.35) m
head distance: 2.5 m
TLS type 1
L x B: 2.5 m x (lane width - 2 x 0.80) m
head distance: 4.0 m
Number of windings: 4
Inductance range:
120 - 190 µH / 150 - 240 µH (with above mentioned data for
TLS type 2 / 1, lane width: 3.0 m - 5.0 m)
Total inductance (incl. feeder Maximum approx. 500 H
cable) (for 300 m feeder cable with above mentioned inductive loops
and cable types)
Ohmic resistance (loop and
Maximum 25
feeder cable)
Isolation resistance of loops At installation: > 1G
(without feeder cable)
During operation: Values as low as approx. 1 M are permitted,
value must be constant
TBUS-
plug connector
To dismount the device, e.g. a suited screwdriver can be placed in the slot at the bottom side
of the locking mechanism at the back and then pressed down until the device can be slightly
tilted up and taken out.
Inductive loops resp. Open Collector switching outputs of the four channels are always
connected with the plugs at the bottom resp. at the top on the backside.
Loop 1 Loop 2
Loop 3 Loop 4
NOTE
The TBUS bus system includes the bus connectors and a plug connector at the right side
where the RS485 data bus, the synchronization line (to external detectors) and the supply
voltage can be connected:
Alternatively, for the connection at the TBUS at the side, the supply voltage and the RS485
data bus can also be connected via the 4-pole connecting plug at the front top of one device.
The connection of the synchronization with external detectors with identical synchronization
method which are not connected with the TBUS can only be done via the plug at the side
(max. length approx. 1 m). Doing so, the reference potentials GND of the supply voltages of
the different detector types must also be connected with each other, if necessary.
8.4.4 Pin assignment service interface (3.5 mm stereo jack plug, TRS)
GND RX TX
In compliance with the underlying pollution degree 2 the installation in an enclosure or control
panel with at least IP54 is required.
If the device is to be exposed surges above the overvoltage category II, then additional surge
protection have to be installed.
N * A ≤ 60 m2
The loop type to be used (TLS) and the product class 2 (A < 30 m², N > 1) to be applied meet
the requirements.
Installation of loops
For the installation of the inductive loops the regulations of TLS and the documentation “Loop
Installation TLS” by SWARCO TRAFFIC SYSTEMS GMBH apply.
8.6 EC Conformity
Thank you for choosing a SWARCO TRAFFIC SYSTEMS GMBH quality product.