PM32xx UserManual
PM32xx UserManual
PM32xx UserManual
DOCA0006EN 06/2012
PM3200 series
Power Meters
User Manual
DOCA0006EN-01
06/2012
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific
user applications. It is the duty of any such user or integrator to perform the appropriate and complete
risk analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information that is contained herein. If you have any suggestions for improvements or
amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical,
including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result
in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
2012 Schneider Electric. All rights reserved.
DOCA0006EN 06/2012
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
7
9
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Physical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
11
Chapter 2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
Safety Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DIN Rail Mounting and Dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
15
16
18
Chapter 3 Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input/Output Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multi-tariff. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Logging (PM3255) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
26
31
34
36
39
Chapter 4 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modifying Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clock Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Full Screen Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
43
49
50
51
59
61
62
62
63
64
65
66
67
68
74
74
89
89
91
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
91
93
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Password Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Language Download . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
94
95
96
97
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
99
101
101
103
103
DOCA0006EN 06/2012
DOCA0006EN 06/2012
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, or maintain it. The following special messages may appear throughout this
documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.
DOCA0006EN 06/2012
DOCA0006EN 06/2012
At a Glance
Document Scope
This manual is intended for use by designers, system builders, and maintenance technicians who are
concerned with electrical distribution systems featuring monitoring devices.
Validity Note
The power meters are used to measure electrical parameters of an installation or a part of an installation.
This function meets the requirements for:
installation monitoring,
alarming on consumption drifts,
consumption monitoring,
evaluation of energy items (cost, accounting, and so on.),
logging of historical consumption,
identifying harmonic disturbances.
This function also satisfies the power-saving incentives implemented by many countries.
Related Documents
Title of Documentation
Reference Number
S1B46605
S1B62913
S1B46607
S1B62914
You can download these technical publications and other technical information from our website at
www.schneider-electric.com.
User Comments
We welcome your comments about this document. You can reach us by e-mail at techcomm@schneiderelectric.com.
DOCA0006EN 06/2012
DOCA0006EN 06/2012
PM3200 series
Power Meter Presentation
DOCA0006EN 06/2012
Presentation
1
What Is in This Chapter?
This chapter contains the following topics:
Topic
DOCA0006EN 06/2012
Page
Presentation
10
Physical Description
11
Presentation
Use of Power Meters to Measure Electrical Systems
The power meters provide accurate 3-phase electrical parameters monitoring.
The offer is composed of 4 commercial references described below.
Functions of Power Meters
The product functions of power meters provide the various measurement capabilities required to monitor
an electrical installation such as current, voltage, power, power factor, frequency and energy.
The key features of power meters are:
electrical parameters monitoring such as I, In, U, V, PQS, E, PF, Hz,
power/current demand, peak demand,
time stamped alarms,
minimum/maximum,
up to 4 tariffs management,
up to 2 digital inputs and 2 digital outputs,
Modbus communication.
Main Characteristics
Function
10
PM3200
PM3210
PM3250
PM3255
Measurement inputs
through CTs (1 A, 5 A)
Measurement inputs
through VTs
Electrical
measurements (I, In, V,
PQS, PF, Hz)
Minimum/Maximum of
instantaneous values
Multi-tariff (internal
clock)
Multi-tariff (external
control by DI)
Multi-tariff (external
control by
communication)
Measurement display
Digital inputs/Digital
outputs
0/1
2/2
15
Modbus communication
DOCA0006EN 06/2012
Physical Description
PM3200 / PM3210
The various features of the listed power meters are shown in the diagram below:
Control power
Cancellation
Confirmation
Up
Down
10 Sealable covers
DOCA0006EN 06/2012
11
PM3250 / PM3255
The various features of the listed power meters are shown in the diagram below:
Communication port
Cancellation
Confirmation
Up
Down
12
DOCA0006EN 06/2012
PM3200 series
Power Meter Installation
DOCA0006EN 06/2012
Installation
2
What Is in This Chapter?
This chapter contains the following topics:
Topic
DOCA0006EN 06/2012
Page
Safety Measures
14
Dimensions
15
16
Connection
18
13
Safety Measures
Specific Hazard Associated with Power Meters
In the case of almost all electric and electronic devices, the devices power supply is the root cause of
electrical hazards. The hazard can be eliminated by disconnecting the power supply.
Consequently, this connection must be broken before carrying out any kind of work on the product.
DANGER
RISK OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Before carrying out work of any kind, disconnect connection wires. Disconnect all the power supplies
running to the power meter and the equipment on which it is installed.
Always use a correctly calibrated voltage tester to check that the power supply has been properly
disconnected.
DANGER
RISK OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Wear suitable personal protective equipment and follow the currently applicable electrical safety
instructions.
This equipment may only be installed by qualified electricians who have read all the relevant
information.
NEVER work alone.
Before performing visual inspections, tests, or maintenance on this equipment, disconnect all
sources of electric power. Assume that all circuits are live until they have been completely deenergized, tested and tagged. Pay particular attention to the design of the power system. Consider
all power supply sources, particularly the potential for backfeed.
Before closing protective covers and doors, carefully inspect the work area to ensure that no tools or
objects have been left inside the equipment.
Take care when removing or replacing panels. Take special care to ensure that they do not come
into contact with live busbars. To minimize the risk of injuries, do not tamper with the panels.
The successful operation of this equipment depends upon proper handling, installation, and
operation. Failure to follow basic installation procedures can lead to personal injury as well as
damage to electrical equipment or other property.
NEVER shunt an external fuse/circuit breaker.
The power meters must be installed in a suitable electrical cabinet.
14
DOCA0006EN 06/2012
Dimensions
Dimensions of PM3200 / PM3210
Unit: mm
Dimensions of PM3250 / PM3255
Unit: mm
DOCA0006EN 06/2012
15
16
Action
Position the 2 upper slots on the rear of the power meter on the DIN rail.
Press the device against the DIN rail until the locking mechanism engages. The
device is now attached to the rail.
DOCA0006EN 06/2012
DOCA0006EN 06/2012
Action
Using a flat screwdriver (6.5 mm), lower the locking mechanism to release the
device.
17
Connection
Overview
The diagrams below illustrate how to connect the power meters to a single-phase or three-phase 3- or 4wire power system.
Connection Diagram of PM3200 / PM3210
18
DOCA0006EN 06/2012
Power Supply
Power Supply
100...300 V DC
DOCA0006EN 06/2012
19
1PH2W L-N
1PH2W L-L
1PH3W L-L-N
2 CTs
3 CTs
20
DOCA0006EN 06/2012
3PH3W
1 CT (balanced)
2 CTs
3 CTs
3PH4W
1 CT (balanced)
3 CTs
DOCA0006EN 06/2012
21
3PH3W
2 VTs, 2 CTs
2 VTs, 3 CTs
22
DOCA0006EN 06/2012
Power System
3PH4W
3 VTs, 3 CTs
1
2
3
DOCA0006EN 06/2012
Protection containing a voltage disconnect switch with a fuse or disconnect circuit breaker (be adapted to suit the
supplied voltage rating and the available short-circuit current at connection point, 250 mA for control power)
Shorting switch unit
A fuse or disconnect circuit breaker (be adapted to suit the supplied voltage rating and theavailable short-circuit
current at the connection point, 250 mA for control power)
23
24
DOCA0006EN 06/2012
PM3200 series
Power Meter Functions
DOCA0006EN 06/2012
Functions
3
What Is in This Chapter?
This chapter contains the following topics:
Topic
DOCA0006EN 06/2012
Page
Metering
26
Alarms
31
Input/Output Capabilities
34
Multi-tariff
36
39
25
Metering
26
Contents
Page
Real-Time Measuring
Minimum/Maximum Values
Demands Readings
Energy Readings
Other Characteristics
DOCA0006EN 06/2012
Description
Current
Voltage
Frequency
40...70 Hz
Active power
Reactive power
Apparent power
Total
Current unbalance
Voltage unbalance
Minimum/Maximum Values
When any one-second real-time reading reaches its highest or lowest value, the power meter saves the
values in its nonvolatile memory. These values are called the minimum and maximum (min./max.) values.
From the power meter display, you can:
view all min./max. values since the last reset and the reset date and time.
reset min./max. values.
All running min./max. values are arithmetic minimum and maximum values. For example, the minimum
phase A-N voltage is the lowest value in the range from 0 to 1 MV that has occurred since last reset of
the min./max. values.
The power meter provides time stamping for 6 important minimum/maximum values. Refer to register
number 45130 to 45164 in the register list for details.
The following table lists the minimum and maximum values stored in the power meter:
Characteristics
Description
Current
Voltage
Frequency
Active power
Reactive power
Apparent power
Power factor
Total (1)
(2)
DOCA0006EN 06/2012
(1)
(2)
Demand Readings
The power meter provides a variety of demand readings.
Characteristics
Description
Current
Total
Total
(1)
Peak Demand
In nonvolatile memory, the power meter maintains a maximum operating demand values called peak
demand. The peak is the highest value (absolute value) for each of these readings since the last reset.
You can reset peak demand values from the power meter display. You should reset peak demand after
changes to basic power meter setup such as CT ratio or power system configuration.
28
DOCA0006EN 06/2012
Energy Readings
The power meter calculates and stores total and partial energy values for active, reactive, and apparent
energy.
You can view energy values from the display. The resolution of the energy value automatically changes
from kWh to MWh (kVAh to MVARh).
The energy values automatically resets to 0 when it reaches the limit of 1 x 106 MWh, 1 x 106 MVAh, or
1 x 106 MVARh. Manual reset of total energy is not allowed. You can reset the partial energies including
partial energy import, energy by tariff, and phase energy manually on HMI.
Energy values can be reported over communications as 64-bit signed integers. The units are always Wh,
VARh, or VAh.
The following table lists the energy readings from the power meter:
Characteristics
Description
Reactive energy
Apparent energy
Total
0 to 1 x 1012 Wh
Auto reset to 0 in case of over limit
Reactive energy
Total
0 to 1 x 1012 VARh
Auto reset to 0 in case of over limit
Apparent energy
Total
0 to 1 x 1012 VAh
Auto reset to 0 in case of over limit
HC (Harmonic Content) =
H1 = Fundamental Content
THD (Total Harmonic Distortion) = HC/H1 X 100%
THD is the power analysis value and a quick measure of the total distortion present in a waveform. THD
is the ratio of harmonic content to the fundamental and provides a general indication of the quality of a
waveform. THD is calculated for both voltage and current.
The following table lists the power quality values of the power meter
Characteristics
Description
Per phase current and per phase voltage (L-L and L-N)
Worst of 3 phases
Average of 3 phases (1)
(1)
DOCA0006EN 06/2012
29
Other Characteristics
The following table lists other characteristics of the power meter:
Characteristics
Description
Reset
Epart
Primary 5 to 32,767 A
Secondary 5 A, 1 A
1 to 60 minutes
30
DOCA0006EN 06/2012
Alarms
DOCA0006EN 06/2012
Contents
Page
Overview
Alarms Configuration
31
Overview
The power meter provides setpoints driven alarms. The alarms include:
Alarms
PM3210, PM3250
PM3255
Standard Alarms
Customized Alarms
Over Energy, Total Active
Alarms Configuration
For the standard alarms, you must configure the following features by using HMI or communication:
Pickup setpoint
Trigger delay (Pickup/Dropout delay)
Dropout setpoint (Deviation percentage from pickup setpoint)
Among the standard alarms, dropout setpoint and trigger delay are common features of all the alarms.
Pickup setpoint is identical for each alarm.
For more information on power meter handling the setpoint-driven alarms, refer to the figure below.
EV1 An alarm is active. The power meter records the date, time, and value at EV1 when the pickup setpoint and time
delay are satisfied. The power meter performs any tasks assigned to the event such as operation of a digital
output, backlight flashing, and alarm symbol flashing.
EV2 An alarm is inactive when the dropout setpoint and time delay are satisfied. The power meter performs any tasks
assigned to the event such as switch off a digital output, backlight, and alarm symbol stop flashing.
NOTE: The time delay is satisfied only if during the delay, the actual value does not fall between the
pickup setpoint and dropout setpoint.
For the over energy alarm, you also need to configure the method, which refers to the energy
accumulation and detection period.
32
DOCA0006EN 06/2012
DOCA0006EN 06/2012
33
Input/Output Capabilities
34
Contents
Page
DOCA0006EN 06/2012
Active Tariff
Tariff 1 active
DI1/DI2 = OFF/ON
Tariff 2 active
DI1/DI2 = ON/OFF
Tariff 3 active
DI1/DI2 = ON/ON
Tariff 4 active
Meter with 2 tariffs (always associated with DI1, and DI2 can be left floating or
configured as other mode):
DI1 = OFF
Tariff 1 active
DI1 = ON
Tariff 2 active
DOCA0006EN 06/2012
35
Multi-tariff
36
Contents
Page
Presentation
DOCA0006EN 06/2012
Presentation
The power meter provides multi-tariff energy accumulation. It supports up to 4 tariffs.
The tariff switching has the following 3 kinds of control modes:
Digital input
Communication
Internal RTC
You can configure the control mode by using HMI (all the 3 modes) or by using communication (not for
RTC).
Command number 2060 is used to configure the control mode by communication. Refer to Modbus
communication (see page 61) for more details.
The following table presents the rules to change multi-tariff control mode by Modbus command:
From
To
Disable
Communication
Digital input
RTC
Communication
Communication
Disable
Weekdays
Weekend
Day mode
Week
mode
A scheduler supports maximum 4 time segments (Ta, Tb, Tc, and Td) for maximum 4 tariffs (T1, T2, T3,
and T4). You can assign Ta, Tb, Tc, or Td to any tariff provided that any adjacent time segment has
different tariff. A valid scheduler should always start from Ta segment and skipping the intermediate
segment is not allowed.
DOCA0006EN 06/2012
37
In the setup of a scheduler, you should define the tariff switching time and the target tariff rate from the
switching time. In the application, when the set switching time reaches, the current tariff rate switches to
the target rate automatically.
38
DOCA0006EN 06/2012
Page
Energy Log
The power meter provides power demand log and energy log. It stores all these logs in nonvolatile
memory of the power meter. Power demand log and energy day log can be read as a log file. The 3 types
of energy log can be read as registers.
The following table lists the maximum number of entries of each log:
Log Type
DOCA0006EN 06/2012
4608
45
30
13
39
Log date/time
4 Registers
Demand value
2 Registers
The demand log file is circular. If the number of log days exceeds the maximum, it overwrites the log data
of the oldest day.
NOTE: The overwriting unit is day, not entry. This means if overwriting happens, it erases the entire log
of the oldest day along with the oldest entry.
With ION Enterprise, you can view and save the power demand log file to a disk.
Special Notes for Power Demand Log
If date/time is not set by the user after date/time resets due to previous power interruption or the
inoperable RTC (diagnosis code #205 or #207 is reported), new entries are not generated in the
demand log.
If you change date/time, all logged entries with log date/time after the new date/time are erased.
For example, some entries were logged in October 20, 2012, if you change the date of the meter to
October 19, 2012 by mistake, the entries of October 20, 2012 are erased.
If you change the log interval option, the demand log system is reset and all logged entries are erased.
Energy Log
The meter also has the log for accumulated active energy.
The energy log entry structure is shown in the following table:
Log Entry
Log date/time
4 Registers
Energy value
4 Registers
You can configure the energy log only by HMI. The day log, week log, and month log are enabled or
disabled together during the configuration. However, the energy accumulation always starts from the
fixed log time instead of the time of log enabled.
With ION Enterprise, you can view and save the energy day log file to a disk. You can also access day
log, week log, and month log by reading the registers.
Special Notes for Energy Log
40
If the date/time is not set by the user after the date/time resets due to previous power interruption,
energy keeps accumulating. After the date/time is set and the log time is reached, all the accumulated
energy is written into the log.
If you reset the date, the logged entries with log date after the reset date are not erased.
When the log time is reached, the meter checks the enable/disable status of the energy log. The meter
logs the accumulated energy if the status is enable and discards if the status is disable. The
accumulated energy resets to 0.
The energy log is circular. If the number of the log entries exceeds the maximum, the oldest log entries
are overwritten.
DOCA0006EN 06/2012
PM3200 series
Power Meter HMI
DOCA0006EN 06/2012
Operation
DOCA0006EN 06/2012
Page
Presentation
42
Configuration Mode
43
Modifying Parameters
49
Clock Setting
50
Display Mode
51
59
41
Presentation
Introduction
The power meter features a sophisticated and intuitive human machine interface (HMI) with signaling
LEDs, a graphic display, and contextual menu buttons for accessing the information required to operate
the power meter and modify parameter settings.
The Navigation menu allows to display, configure, and reset parameters.
General Display
The general display of the power meters is shown in the following picture:
1
2
3
4
5
6
7
8
Main title
Configuration mode
Cancellation
Confirmation
Up
Down
Values/Parameters
Sub menu
Status Information
The display and the LED on the power meters indicate the device current status.
LED Indicator
Description
OFF
ON
Off
LCD is in power saving mode
ON/Dimness
OFF
ON/Normal
OFF
Flashing
Flashing
Alarm/Diagnosis is active for 3 hours
and LCD is in power saving mode
ON/Dimness
Flashing
ON/Normal
/
ON
ON/Dimness
42
DOCA0006EN 06/2012
Configuration Mode
Settings for all Power Meters
The following settings have to be configured in configuration mode:
Function
PM3200
PM3210
PM3250
PM3255
Wiring
CT and VT Ratio
Nominal frequency
Date/Time
Multi-tariffs
Demand
Log
Digital Outputs
Digital Inputs
Pulse Output
Communication
Alarms
HMI
Language
DOCA0006EN 06/2012
Function
Factory settings
Wiring
CT Ratio
CT Secondary = 5 A; CT Primary = 5 A
VT Ratio
NA
Nominal Frequency
50 Hz
A-B-C
Date/Time
1-Jan-2000/00:00:00
Multi-tariffs
Disable
Demand
Disable
Energy Log
Disable
Digital Outputs
Disable
Digital Inputs
Input status
Pulse Output
Communication
Password
Alarms
Disable
HMI LCD
Backlight: 4; Contrast: 5
HMI Mode
Language
English
43
or
Confirmation button
Cancellation button
To enter the configuration mode, hold
and
for 2 seconds.
The following figures describe in details the configuration navigation, refer to Modifying Parameters
(see page 49) to change the default selection.
Configuration Mode Menu Tree for PM3200
44
DOCA0006EN 06/2012
DOCA0006EN 06/2012
45
46
DOCA0006EN 06/2012
DOCA0006EN 06/2012
47
48
DOCA0006EN 06/2012
Modifying Parameters
Presentation
To modify any of the values, you must be thoroughly familiar with how the interface menus are structured
and the general navigation principles. For more information about how the menus are structured, refer to
menu trees of each power meter model (see page 43).
To modify the value of a parameter, follow either of the 2 methods described below:
selecting an item in a list,
modifying a numerical value, digit by digit.
The parameters listed below are the only ones which the numerical value can be modified:
Date
Time
Voltage Transformer (VT) Primary
Current Transformer (CT) Primary
Password
Modbus address of the power meter
Pickup Setpoint
Dropout Setpoint
Time delay/Interval duration
Selecting the Value in a List
The following table explains how to select a value in a list:
Step
1
Action
Use the
or
button to scroll through the parameter values until you
reach the desired value.
Press
Action
Use the
Press
or
Aborting an Entry
To abort the current parameter entry, press the
DOCA0006EN 06/2012
49
Clock Setting
Description
The time must be set when switching from winter to summer time.
The power meter automatically displays the screen to set Date and Time in case of loss of date and time
when the power is interrupted for longer than 5 minutes.
The power meter retains the date and time settings before the interruption.
Setting
To set the date and time, refer to procedure for modifying a numerical value (see page 49).
Date/Time Format
The date is displayed in the format: DD-MMM-YYYY.
The time is displayed using the 24-hour clock in the format: hh:mm:ss.
Clock Setting Menu
NOTE: Clock is set only after the date/time is reset due to power interruption.
50
DOCA0006EN 06/2012
Display Mode
Enter the Display Mode
If Full Screen mode is enabled, press any key to switch from Full Screen mode to Display mode.
DOCA0006EN 06/2012
51
52
DOCA0006EN 06/2012
DOCA0006EN 06/2012
53
54
DOCA0006EN 06/2012
DOCA0006EN 06/2012
55
56
DOCA0006EN 06/2012
DOCA0006EN 06/2012
57
58
DOCA0006EN 06/2012
Full screen mode is enabled by default. You can modify full screen enable/disable information, auto scroll
enable/disable, and auto scroll interval in HMI configuration.
Full Screen
Auto Scroll
Description
Enable
Disable
Any value
Enable
Enable
Any value
Disable
If Full Screen mode is enabled and without key pressing for 5 minutes, Display mode switches to Full
Screen mode.
DOCA0006EN 06/2012
59
60
DOCA0006EN 06/2012
PM3200 series
PM3250 / PM3255 - Communication
DOCA0006EN 06/2012
5
What Is in This Chapter?
This chapter contains the following sections:
Section
DOCA0006EN 06/2012
Topic
Page
5.1
Modbus Configuration
62
5.2
Modbus Functions
63
5.3
Command Interface
66
5.4
74
5.5
89
61
5.1
Modbus Configuration
Authorized Values
Default Value
Baud rate
9600 Baud
19 200 Baud
38 400 Baud
19 200 Baud
Parity
Odd
Even
None
Even
1247
62
If...
Then...
DOCA0006EN 06/2012
5.2
Modbus Functions
DOCA0006EN 06/2012
Page
Function List
64
Table Format
65
63
Function List
Introduction
There are 3 different ways of using the Modbus communication:
by sending commands using the command interface (see page 66),
by reading the Modbus registers (see page 74).
by reading the Device Identification (see page 89).
Description
Sending commands using the command interface is supported by Modbus function 16.
Reading Modbus registers is supported by Modbus function 3.
Read Device Identification is supported by Modbus function 43/14.
The table below describes the three Modbus functions:
Function Code
Function Name
Decimal
Hexadecimal
0x03
16
0x10
43/14
0x2B/0x0E
For example:
To read different parameters from the power meter, use the function 3 (Read).
To change the tariff, use the function 16 (Write) by sending a command to the power meter.
64
DOCA0006EN 06/2012
Table Format
Action
(R/W/WC)
Size
Type
Units
Range
Description
Register Address: Modbus address of register encoded in the Modbus frame, in decimal (dec)
Action: The read/write/write by command property of the register
Size: The data size in Int16
Type: The encoding data type
Units: The unit of the register value
Range: The permitted values for this variable, usually a subset of what the format allows
Description: Provides information about the register and the values that apply
Unit Table
The following data types appear in the Modbus register list:
Type
Description
Range
UInt16
0...65535
Int16
-32768...+32767
UInt32
UTF8
8 bit field
Float32
32 bit value
Bitmap
DATETIME
See below
DATETIME format:
Word
Bits
15
14
13
Reserved (0)
SU (0)
Millisecond (0...59999)
11
10
Month (1...12)
0
R4 :
Year :
Month :
Day :
Hour :
Minute :
Millisecond :
WD (day of the week) :
SU (summer time) :
iV (validity of received data) :
DOCA0006EN 06/2012
12
Hour (0...23)
R4 (0)
Year (0...127)
WD (0)
iV
Day (1...31)
0
Minute (0...59)
Reserved Bit
7 bits: (year from 2000)
4 bits
5 bits
5 bits
6 bits
2 octets
1-7: Sunday to Saturday
Bit to 0 if this parameter is not used.
Bit to 0 if this parameter is not valid or not used.
65
5.3
Command Interface
66
Page
Presentation
67
Command List
68
DOCA0006EN 06/2012
Presentation
Description
The command interface allows to configure the power meter by sending specific command requests
using Modbus function 16.
Command Request
The following table describes a Modbus command request:
Slave
Number
Function Code
Command block
CRC
Register Address
Command Description
1247
16 (W)
Checking
Content
Size (Int16)
Data (example)
5250
Command Number
5251
(Reserved)
52525374
Parameter
4 (Tariff=4)
NOTE: Command number 2008 supports
only one parameter with the size of 1.
Command Result
The command result can be obtained by reading registers 5375 and 5376.
The following table describes the command result:.
Register Address
Content
Size (Int16)
Data (example)
5375
0 (Valid Operation)
5376
Result
(1)
DOCA0006EN 06/2012
(1)
67
Command List
68
Command
Page
Set Date/Time
1003
Set Wiring
2000
2002
2003, 2038
Set Tariff
2008, 2060
2009
2015
6017
6014
Alarm Setup
Communications Setup
5000
2020
2023
DOCA0006EN 06/2012
Set Date/Time
Command
Number
Action
(R/W)
1003
Size
Type
Unit
Range
Description
UInt16
(Reserved)
UInt16
20002099
Year
UInt16
112
Month
UInt16
131
Day
UInt16
023
Hour
UInt16
059
Minute
UInt16
059
Second
UInt16
(Reserved)
Command
Number
Action
(R/W)
Size
Type
Unit
Range
Description
2000
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
0, 1, 2, 3, 11, 13
UInt16
Hz
50, 60
Nominal Frequency
Float32
(Reserved)
Float32
(Reserved)
Float32
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
Float32
VT Secondary1000000.0
VT Primary
UInt16
VT Secondary
UInt16
1, 2, 3
Number of CTs
UInt16
132767
CT Primary
UInt16
1, 5
CT Secondary
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
0, 1, 2
VT Connection type:
0 = Direct Connect
1 = Delta (2 VTs)
2 = Wye (3 VTs)
Set Wiring
DOCA0006EN 06/2012
69
Action
(R/W)
Size
Type
Unit
Range
Description
2002
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
1, 2
Demand method:
1 = Timed interval sliding block
2 = Timed interval fixed block
UInt16
min
UInt16
(Reserved)
Action
(R/W)
Size
Type
Unit
Range
Description
2003
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
0, 1
Pulse Output
0 = DO1 Disable
1 = DO1 Enable
Float32
pulse/kWh
UInt16
(Reserved)
UInt16
0, 2
0 = DO2 Disable
2 = DO2 Enable
Float32
pulse/kVARh
UInt16
(Reserved)
UInt16
(Reserved)
Float32
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
ms
2038
Set Tariff
Command
Number
Action
(R/W)
Size
Type
Unit
Range
Description
2060
UInt16
(Reserved)
UInt16
03
Multi-tariff mode:
0 = Disable Multi-tariff
1 = Use COM as Tariff Control (maximum 4 tariffs)
2 = Use DI1 as Tariff Control (2 tariffs)
3 = Use 2 Digital inputs as Tariff Control (4 tariffs)
4 = Use RTC as Tariff Control (maximum 4 tariffs)
UInt16
(Reserved)
UInt16
14
Tariff (1)
1 = T1
2 = T2
3 = T3
4 = T4
2008
(1)
70
DOCA0006EN 06/2012
Action
(R/W)
Size
Type
Unit
Range
Description
2009
UInt16
(Reserved)
Action
(R/W)
Size
Type
Unit
Range
Description
2015
UInt16
(Reserved)
Action
(R/W)
6017
Size
Type
Unit
Range
Description
UInt16
(Reserved)
UInt16
0, 1, 2, 3
Action
(R/W)
Size
Type
Unit
Range
Description
6014
UInt16
(Reserved)
UInt16
1, 2
20
UTF8
string size 40
Label
Float32
110000
Pulse Weight
UInt16
(Reserved)
UInt16
DOCA0006EN 06/2012
71
Alarm Setup
Command
Number
7000
20000
20001
NOTE:
(1)
Action
(R/W)
Size
Type
Unit
Range
UInt16
(Reserved)
UInt16
(1)
(2)
Alarm ID
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
0, 1
0 = Disable
1 = Enable
Float32
(3)
(4)
(5)
(6)
(7)
Pickup Setpoint
UInt32
(Reserved)
Float32
(Reserved)
UInt32
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
Float32
0.099.0
Dropout Setpoint
UInt32
0999999
Bitmap
0, 1, 2, 3
PM 3250: Reserved
PM 3255:
Digital Output to Associate:
0 = None
1 = DO1
2 = DO2
3 = DO1 and DO2
UInt16
(Reserved)
PM3250: 1, 6, 8, 9, 11, 30
(2)
PM3255: 1, 2, 5, 6, 7, 8, 9, 10, 11, 12, 13, 16, 19, 28, 30, 31, 32, 41
(3)
(4)
(5)
(6)
(7)
72
Description
DOCA0006EN 06/2012
Communications Setup
Command
Number
5000
Action
(R/W)
Size
Type
Unit
Range
Description
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
(Reserved)
UInt16
1247
Address
UInt16
0, 1, 2
Baud Rate
0 = 9600
1 = 19 200
2 = 38 400
UInt16
0, 1, 2
Parity
0 = Even
1 = Odd
2 = None
UInt16
(Reserved)
Action
(R/W)
Size
Type
Unit
Range
Description
2020
UInt16
(Reserved)
Action
(R/W)
Size
Type
Unit
Range
Description
2023
UInt16
(Reserved)
DOCA0006EN 06/2012
73
5.4
Register List
74
Register
Page
System
Command Interface
Communication
Digital Inputs
Digital Outputs
Demand
MinMax Reset
Minimum Values
Maximum Values
Power Quality
Alarms
Energy Log
DOCA0006EN 06/2012
System
Register
Address
Action (R/W/WC)
PM3250
PM3255
Size
Type
Units
Description
30
50
20
UTF8
Meter Name
20
UTF8
Meter Model
70
130
20
UTF8
Manufacturer
UInt32
Serial Number
132
Date/Time
Date of Manufacture
136
UTF8
Hardware Revision
1637
UInt16
1701
UInt16
18451848
R/WC
R/WC
1X4
UInt16
Date/Time
Reg. 1845: Year 0-99 (year from 2000 to
2099)
Reg. 1846: Month (b11:b8), Weekday (b7:b5),
Day (b4:b0)
Reg. 1847: Hour (b12:b8) and Minute (b5:b0)
Reg. 1848: Millisecond
Action (R/W/WC)
PM3250
PM3255
Size
Type
Units
Description
2004
2014
UInt32
Second
UInt16
Number of Phases
2015
UInt16
Number of Wires
2016
R/WC
R/WC
UInt16
2017
R/WC
R/WC
UInt16
Hz
Nominal Frequency
2024
R/WC
R/WC
UInt16
2025
UInt16
Number VTs
2026
R/WC
R/WC
Float32
VT Primary
2028
R/WC
R/WC
UInt16
VT Secondary
2029
R/WC
R/WC
UInt16
Number CTs
2030
R/WC
R/WC
UInt16
CT Primary
2031
R/WC
R/WC
UInt16
CT Secondary
2036
R/WC
R/WC
UInt16
VT Connection Type:
0 = Direct Connect
1 = 3PH3W (2 VTs)
2 = 3PH4W (3 VTs)
Action (R/W/WC)
PM3250
Size
Type
Units
Description
UInt16
Millisecond
PM3255
R/WC
DOCA0006EN 06/2012
75
Register
Address
Action (R/W/WC)
PM3250
PM3255
Size
Type
Units
Description
2131
R/WC
UInt16
2132
R/WC
Float32
pulse/kWh
R/WC
UInt16
2136
R/WC
Float32
pulse/kVARh
Size
Type
Units
Description
Command Interface
Register
Address
Action (R/W/WC)
PM3250
PM3255
5250
R/W
R/W
UInt16
Requested Command
5252
R/W
R/W
UInt16
5374
R/W
R/W
UInt16
5375
UInt16
Command Status
5376
UInt16
5377
UInt16
5499
UInt16
Communications
Register
Address
Action (R/W/WC)
PM3250
PM3255
6500
Size
Type
Units
Description
UInt16
Protocol
0 = Modbus
6501
R/WC
R/WC
UInt16
Address
6502
R/WC
R/WC
UInt16
Baud Rate:
0 = 9600
1 = 19 200
2 = 38 400
6503
R/WC
R/WC
UInt16
Parity:
0 = Even
1 = Odd
2 = None
Size
Type
Units
Description
20
UTF8
Label
Action R/W/WC)
PM3250
PM3255
R/WC
7052
R/WC
Float32
pulse/unit
Pulse Frequency
7055
R/WC
UInt16
R/WC
20
UTF8
Label
DOCA0006EN 06/2012
Register
Address
Action R/W/WC)
PM3250
Size
Type
Units
Description
PM3255
7076
R/WC
Float32
pulse/unit
Pulse Frequency
7079
R/WC
UInt16
Digital Inputs
Register
Address
Action (R/W/WC)
Size
Type
Units
Description
PM3250
PM3255
7274
UInt16
7298
UInt16
8905
Bitmap
Size
Type
Units
Description
Digital Outputs
Register
Address
Action (R/W/WC)
PM3250
PM3255
9673
UInt16
9681
UInt16
Action (R/W/WC)
Size
Type
Units
Description
PM3250
PM3255
3000
Float32
3002
Float32
Current
3004
Float32
3006
Float32
3010
Float32
Current Avg
3020
Float32
Voltage L1-L2
3022
Float32
Voltage L2-L3
3024
Float32
Voltage L3-L1
3026
Float32
3028
Float32
Voltage L1-N
3030
Float32
Voltage L2-N
3032
Float32
Voltage L3-N
3036
Float32
3054
Float32
kW
3056
Float32
kW
3058
Float32
kW
Voltage
Power
DOCA0006EN 06/2012
77
Register
Address
Action (R/W/WC)
PM3250
PM3255
Size
Type
Units
Description
3060
3062
Float32
kW
Float32
kVAR
3064
3066
Float32
kVAR
Float32
kVAR
3068
Float32
kVAR
3070
Float32
kVA
3072
Float32
kVA
3074
Float32
kVA
3076
Float32
kVA
3078
Float32
3080
Float32
3082
Float32
3084
Float32
Power Factor
Current Unbalance
3012
Float32
Current Unbalance I1
3014
Float32
Current Unbalance I2
3016
Float32
Current Unbalance I3
3018
Float32
Voltage Unbalance
3038
Float32
3040
Float32
3042
Float32
3044
Float32
3046
Float32
3048
Float32
3050
Float32
3052
Float32
Float32
Float32
Hz
Frequency
Float32
Temperature
3204
Int64
Wh
3208
Int64
Wh
3220
Int64
VARh
3224
Int64
VARh
3236
Int64
VAh
3240
Int64
VAh
Date/Time
DOCA0006EN 06/2012
Register
Address
Action (R/W/WC)
PM3250
PM3255
Size
Type
Units
3256
3272
3288
Description
Int64
Wh
Int64
VARh
Int64
VAh
Int64
Wh
3522
Int64
Wh
3526
Int64
Wh
3530
Int64
VARh
3534
Int64
VARh
3538
Int64
VARh
3542
Int64
VAh
3546
Int64
VAh
3550
Int64
VAh
R/WC
R/WC
UInt16
4196
Int64
Wh
4200
Int64
Wh
4204
Int64
Wh
4208
Int64
Wh
Input Metering
3554
Date/Time
3558
Int64
Unit
3562
Int64
Unit
Size
Type
Units
Description
Demand
Register
Address
Action (R/W/WC)
PM3250
PM3255
R/WC
R/WC
UInt16
Demand Method:
1 = Timed Interval Sliding Block
2 = Timed Interval Fixed Block
3702
R/WC
R/WC
UInt16
Minute
3706
Date/Time
Power/Current Demand
3766
Float32
kW
3770
Float32
kW
3772
Date/Time
3782
Float32
kVAR
3786
Float32
kVAR
3788
Date/Time
3798
Float32
kVA
3802
Float32
kVA
3804
Date/Time
3814
Float32
3818
Float32
3820
Date/Time
3830
Float32
3834
Float32
DOCA0006EN 06/2012
79
Register
Address
Action (R/W/WC)
PM3250
PM3255
Size
Type
Units
Description
3836
3846
Date/Time
Float32
3850
Float32
3852
Date/Time
3862
Float32
3866
Float32
3868
Date/Time
3878
Float32
3882
Float32
3884
Date/Time
Size
Type
Units
Description
Date/Time
Size
Type
Units
Description
MinMax Reset
Register
Address
Action (R/W/WC)
PM3250
PM3255
27214
Minimum Values
Register
Address
Action (R/W/WC)
PM3250
PM3255
27218
Float32
Minimum Current I1
27220
Float32
Minimum Current I2
27222
Float32
Minimum Current I3
27224
Float32
Minimum Current N
27228
Float32
27238
Float32
27240
Float32
27242
Float32
Current
Voltage
27244
Float32
27246
Float32
27248
Float32
27250
Float32
27254
Float32
27272
Float32
kW
27274
Float32
kW
Power
27276
Float32
kW
27278
Float32
kW
27280
Float32
kVAR
27282
Float32
kVAR
27284
Float32
kVAR
27286
Float32
kVAR
27288
Float32
kVA
27290
Float32
kVA
27292
Float32
kVA
27294
Float32
kVA
4Q FP PF
Power Factor
27306
80
DOCA0006EN 06/2012
Register
Address
Action (R/W/WC)
PM3250
PM3255
Size
Type
Units
Description
27308
27310
4Q FP PF
4Q FP PF
27312
4Q FP PF
Float32
Float32
27340
Float32
27342
Float32
27344
Float32
Float32
27362
Float32
27364
Float32
27366
Float32
27368
Float32
27370
Float32
27372
Float32
27376
Float32
Float32
Hz
Minimum Frequency
Frequency
27616
Maximum Values
Register
Address
Action (R/W/WC)
Size
Type
Units
Description
Float32
Maximum Current I1
Float32
Maximum Current I2
Float32
Maximum Current I3
PM3250
PM3255
27694
27696
27698
Current
27700
Float32
Maximum Current N
27704
Float32
27714
Float32
27716
Float32
27718
Float32
27720
Float32
27722
Float32
27724
Float32
27726
Float32
27730
Float32
27748
Float32
kW
27750
Float32
kW
Voltage
Power
27752
Float32
kW
27754
Float32
kW
27756
Float32
kVAR
27758
Float32
kVAR
27760
Float32
kVAR
27762
Float32
kVAR
DOCA0006EN 06/2012
81
Register
Address
Action (R/W/WC)
PM3250
PM3255
Size
Type
Units
Description
27764
27766
Float32
kVA
Float32
kVA
27768
27770
Float32
kVA
Float32
kVA
27782
4Q FP PF
27784
4Q FP PF
27786
4Q FP PF
27788
4Q FP PF
Float32
Power Factor
Float32
27816
Float32
27818
Float32
27820
Float32
Float32
27838
Float32
27840
Float32
27842
Float32
27844
Float32
27846
Float32
27848
Float32
27852
Float32
Float32
Hz
Maximum Frequency
Size
Type
Units
Frequency
28092
Action (R/W/WC)
PM3250
PM3255
Description
45130
Date/Time
45134
Float32
45136
Date/Time
45140
Float32
45142
Date/Time
45146
Float32
45148
Date/Time
45152
Float32
kW
45154
Date/Time
45158
Float32
kVA
45160
Date/Time
45164
Float32
Size
Type
Units
Description
Power Quality
Register
Address
Action (R/W/WC)
PM3250
PM3255
45100
Float32
THD Current I1
45102
Float32
THD Current I2
82
DOCA0006EN 06/2012
Register
Address
Action (R/W/WC)
PM3250
PM3255
Size
Type
Units
Description
45104
45106
Float32
THD Current I3
Float32
45108
45110
Float32
Float32
45112
Float32
45114
Float32
45116
Float32
45118
Float32
45120
Float32
45122
Float32
45124
Float32
45126
Float32
45128
Float32
Size
Type
Units
Description
Alarms
Register
Address
Action (R/W/WC)
PM3250
PM3255
Alarm Status
Activated Alarm Bitmaps
11021
Bitmap
0 = Alarm is inactive
1 = Alarm is active
BitN = Alarm ID N (1-16)
11022
Bitmap
11023
Bitmap
11024
Bitmap
Bitmap
0 = Alarm is disabled
1 = Alarm is enabled
BitN = Alarm ID N (1-16)
11041
Bitmap
11042
Bitmap
11043
Bitmap
Bitmap
11079
Bitmap
11080
Bitmap
11081
Bitmap
UInt16
11114
UInt16
11115
UInt16
UInt16
Entry Number
Entry 001
11116
DOCA0006EN 06/2012
83
Register
Address
Action (R/W/WC)
PM3250
Size
Type
Units
Description
PM3255
11117
Date/Time
Date/Time
11121
UInt16
Record Type:
0xFF10 = UInt16
0xFF40 = Float32
11122
UInt16
11123
UInt16
Value:
Primary Event: Alarm Attributes Register
Address.
Secondary Event: Worst value of source
registers.
11127
UInt16
Sequence Number
11344
UInt16
Entry Number
11345
Date/Time
Date/Time
Entry 020
11349
UInt16
Record Type
11350
UInt16
11351
UInt16
Value
11355
UInt16
Sequence Number
UInt16
12317
UInt16
12318
UInt16
UInt16
Entry Number
Entry 001
12319
12320
Date/Time
Date/Time
12324
UInt16
Record Type:
0xFF10 = UInt16
0xFF40 = Float32
12325
UInt16
12326
UInt16
Value:
Primary Event: Alarm Attributes Register
Address
Secondary Event: Worst value of source
registers
12330
UInt16
Sequence Number
12547
UInt16
Entry Number
12548
Date/Time
Date/Time
Entry 020
12552
UInt16
Record Type
12553
UInt16
12554
UInt16
Value
12558
UInt16
Sequence Number
Alarm ID = 1
14005
R/WC
R/WC
Float32
Pickup Setpoint
14007
R/WC
R/WC
UInt32
Second
14009
R/WC
R/WC
Float32
Dropout Setpoint
Deviation percentage from pickup setpoint
14011
R/WC
R/WC
UInt32
Second
84
DOCA0006EN 06/2012
Register
Address
Action (R/W/WC)
PM3250
PM3255
14013
R/WC
R/WC
Size
Type
Units
Description
Bitmap
Alarm ID = 2
14025
R/WC
Float32
Pickup Setpoint
14027
R/WC
UInt32
Second
14029
R/WC
Float32
Dropout Setpoint
14031
R/WC
UInt32
Second
14033
R/WC
Bitmap
Alarm ID = 5
14085
R/WC
Float32
Pickup Setpoint
14087
R/WC
UInt32
Second
14089
R/WC
Float32
Dropout Setpoint
14091
R/WC
UInt32
Second
14093
R/WC
Bitmap
Alarm ID = 6
14105
R/WC
R/WC
Float32
Pickup Setpoint
14107
R/WC
R/WC
UInt32
Second
14109
R/WC
R/WC
Float32
Dropout Setpoint
14111
R/WC
R/WC
UInt32
Second
14113
R/WC
R/WC
Bitmap
Alarm ID = 7
14125
R/WC
Float32
Pickup Setpoint
14127
R/WC
UInt32
Second
14129
R/WC
Float32
Dropout Setpoint
14131
R/WC
UInt32
Second
14133
R/WC
Bitmap
Alarm ID = 8
14145
R/WC
R/WC
Float32
Pickup Setpoint
14147
R/WC
R/WC
UInt32
Second
14149
R/WC
R/WC
Float32
Dropout Setpoint
14151
R/WC
R/WC
UInt32
Second
14153
R/WC
R/WC
Bitmap
Alarm ID = 9
14165
R/WC
R/WC
Float32
kW
Pickup Setpoint
14167
R/WC
R/WC
UInt32
Second
14169
R/WC
R/WC
Float32
Dropout Setpoint
14171
R/WC
R/WC
UInt32
Second
14173
R/WC
R/WC
Bitmap
Alarm ID = 10
14185
R/WC
Float32
kVAR
Pickup Setpoint
14187
R/WC
UInt32
Second
14189
R/WC
Float32
Dropout Setpoint
14191
R/WC
UInt32
Second
14193
R/WC
Bitmap
Alarm ID = 11
14205
R/WC
R/WC
Float32
kVA
Pickup Setpoint
14207
R/WC
R/WC
UInt32
Second
14209
R/WC
R/WC
Float32
Dropout Setpoint
DOCA0006EN 06/2012
85
Register
Address
Action (R/W/WC)
PM3250
PM3255
Size
Type
14211
R/WC
14213
R/WC
Units
Description
R/WC
R/WC
UInt32
Second
Bitmap
R/WC
Float32
Pickup Setpoint
Alarm ID = 12
14227
R/WC
UInt32
Second
14229
R/WC
Float32
Dropout Setpoint
14231
R/WC
UInt32
Second
14233
R/WC
Bitmap
R/WC
Float32
Pickup Setpoint
Alarm ID = 13
14247
R/WC
UInt32
Second
14249
R/WC
Float32
Dropout Setpoint
14251
R/WC
UInt32
Second
14253
R/WC
Bitmap
Float32
kW
R/WC
Alarm ID = 16
Pickup Setpoint
14307
R/WC
UInt32
Second
14309
R/WC
Float32
Dropout Setpoint
14311
R/WC
UInt32
Second
14313
R/WC
Bitmap
Float32
kVA
R/WC
Alarm ID = 22
Pickup Setpoint
14427
R/WC
UInt32
Second
14429
R/WC
Float32
Dropout Setpoint
14431
R/WC
UInt32
Second
14433
R/WC
Bitmap
R/WC
Float32
Alarm ID = 28
Pickup Setpoint
14547
R/WC
UInt32
Second
14549
R/WC
Float32
Dropout Setpoint
14551
R/WC
UInt32
Second
14553
R/WC
Bitmap
R/WC
Float32
kW
Pickup Setpoint
R/WC
Alarm ID = 30
14827
R/WC
R/WC
UInt32
Second
14829
R/WC
R/WC
Float32
Dropout Setpoint
14831
R/WC
R/WC
UInt32
Second
14833
R/WC
R/WC
Bitmap
Float32
Pickup Setpoint
Alarm ID = 31
14867
R/WC
UInt32
Second
14869
R/WC
Float32
Dropout Setpoint
14871
R/WC
UInt32
Second
14873
R/WC
Bitmap
R/WC
Float32
Pickup Setpoint
Alarm ID = 32
14907
R/WC
UInt32
Second
14909
R/WC
Float32
Dropout Setpoint
14911
R/WC
UInt32
Second
14913
R/WC
Bitmap
86
DOCA0006EN 06/2012
Register
Address
Action (R/W/WC)
PM3250
Size
Type
Units
Description
PM3255
Alarm ID = 41
14942
R/WC
UInt16
Source Register:
ENERGY_LOG_DAY_REALTIME_VALUE:
41504
ENERGY_LOG_WEEK_REALTIME_VALUE:
41874
ENERGY_LOG_MONTH_REALTIME_VALUE:
42043
14945
R/WC
Float32
Wh
Pickup Setpoint
14947
R/WC
UInt32
Second
14949
R/WC
Float32
Dropout Setpoint
14951
R/WC
UInt32
Second
14953
R/WC
Bitmap
Energy Log
Register
Address
Action (R/W/WC)
PM3250
Size
Type
Units
Description
PM3255
UInt16
Enable/Disable:
0x0000 = Disable
0xFFFF = Enable
45601
UInt16
45602
UInt16
45603
UInt16
Latest Entry ID
45604
UInt16
Oldest Entry ID
45605
Int64
Wh
45609
Date/Time
45613
Int64
Wh
45961
Date/Time
45965
Int64
Wh
UInt16
Enable/Disable:
0x0000 = Disable
0xFFFF = Enable
45970
UInt16
45971
UInt16
45972
UInt16
Latest Entry ID
45973
UInt16
Oldest Entry ID
45974
Int64
Wh
45978
Date/Time
45982
Int64
Wh
46130
Date/Time
46134
Int64
Wh
UInt16
Enable/Disable:
0x0000 = Disable
0xFFFF = Enable
46139
UInt16
46140
UInt16
46141
UInt16
Latest Entry ID
46142
UInt16
Oldest Entry ID
46143
Int64
Wh
DOCA0006EN 06/2012
87
Register
Address
Action (R/W/WC)
PM3250
PM3255
46147
46151
46243
46247
88
Size
Type
Units
Description
Date/Time
Int64
Wh
Date/Time
Int64
Wh
DOCA0006EN 06/2012
5.5
Register List
Read Device Identification
The power meter supports the Basic Device Identification with the mandatory objects:
VendorName
ProductCode
Revision Number
ObjectID
Object Name/Description
Object Length
Object Value
Note
0x00
VendorName
16
SchneiderElectric
0x01
ProductCode
11
METSEPM3200
METSEPM3210
METSEPM3250
METSEPM3255
0x02
MajorMinorRevision
04
V1.0
DOCA0006EN 06/2012
89
90
DOCA0006EN 06/2012
PM3200 series
Power Meter Specifications
DOCA0006EN 06/2012
Technical Characteristics
6
Specifications
Electrical Characteristics
Characteristic
Measured voltage
input
Measured current
input
Value
Power
Meters
Direct/VT secondary
50330 V AC (Ph-N)
80570 V AC (Ph-Ph)
PM32
With external VT
VT primary up to 1 MV AC
Frequency range
4565 Hz
CT primary
CT secondary
1 A or 5 A
Permissible overload
Control power
Two solid state relay
digital outputs
Internal clock
PM32
100/173277/480 V AC (20%),
4565 Hz, 3 W/5 VA, 100300 V DC, 3 W
PM32
Voltage
5...40 V DC
PM3255
Current
50 mA maximum
Output resistance
50 Ohm maximum
Isolation
3.5 kV
Voltage
5...30 V DC
Current
1...15 mA
Pulses/kWh
Configurable
Pulse width
Isolation
3.5 kV
Standard
Voltage off
0...5 V DC
Voltage on
Current
Isolation
3.5 kV
Standard
Time error
Backup time
> 5 minutes
PM3210
PM3255
PM32
Measurement Accuracy
Performance Standard
DOCA0006EN 06/2012
Measurement quantity
Accuracy
0.3%, 0.56 A
0.5%, 0.11.2 A
Voltage
Power factor
91
Measurement quantity
Accuracy
Class 0.5
Class 1
Reactive power
Class 2
Frequency
0.05%, 4565 Hz
IEC62053-21 Class 1
Reactive energy
IEC62053-23 Class 2
Mechanical Characteristics
Characteristic
Value
Power Meters
Weight
0.26 kg
PM32
PM32
IP degree of
protection
Front panel
IP40
Casing
IP20
Recommended
terminal tightening
torque
Control power
PM32
Voltage input
PM32
Current input
PM32
Pulse output
PM3210
Digital inputs/outputs
PM3255
RS-485
PM325
Other Characteristics
Characteristic
Value
Operating temperature
25 C...+55 C (K55)
Storage temperature
40 C...+85 C (K55)
Humidity rating
5 to 95% RH at 50 C (non-condensing)
Pollution degree
III
Electromagnetic
compatibility
Electrostatic discharge
Level IV (IEC61000-4-2)
Level IV (IEC61000-4-4)
Immunity to surge
Level IV (IEC61000-4-5)
Conducted immunity
CE as per IEC61010-1
Meter indicator
1 second
Communication
92
Class B (EN55022)
DOCA0006EN 06/2012
PM3200 series
Power Meters - Maintenance and Troubleshooting
DOCA0006EN 06/2012
7
What Is in This Chapter?
This chapter contains the following topics:
Topic
DOCA0006EN 06/2012
Page
Safety Precautions
94
Password Recovery
95
Language Download
96
Troubleshooting
97
93
Safety Precautions
Presentation
The following safety precautions must be thoroughly implemented before attempting to repair electrical
equipment or carry out maintenance. Carefully read and follow the safety precautions described below.
DANGER
RISK OF ELECTRIC SHOCK, ARC FLASH OR BURNS
Wear suitable personal protective equipment and follow the currently applicable electrical safety
instructions. See, for example, standard NFPA 70E when carrying out work in the USA.
Only qualified personnel should maintain this equipment. Such work should be performed only after
reading all the installation instructions.
Turn off all power supplying this equipment before working on or inside it.
NEVER work alone.
Beware of potential hazards and wear personal protective equipment.
NOTICE
RISK OF DAMAGE TO THE POWER METER
94
DOCA0006EN 06/2012
Password Recovery
If you forget your password, contact Schneider Electric service or send an email to Global-PMC-Techsupport@schneider-electric.com for password recovery assistance.
Technical support provides you a new password based on the serial number of your power meter.
NOTE: Make sure that you include serial number of your power meter in your e-mail or have it readily
available when you call technical support.
DOCA0006EN 06/2012
95
Language Download
The power meter supports the downloading of new language files over the communications link. This
action requires the free DLF3000 software, which is available at www.schneider-electric.com. The
DLF3000 offers an extensive Help file with information on operating the software. The most recent
language files are also available on the website.
96
DOCA0006EN 06/2012
Troubleshooting
PM3200
PM3210
PM3250
PM3255
Description
Possible solution
Metering continues.
Mismatch between wiring
settings and wiring inputs.
Metering continues.
Phase sequence reverse.
Metering continues.
Date and Time are reset due
to last power failure.
Metering continues.
Pulse missing due to
overspeed of energy pulse
output or yellow meter
indicator.
Metering continues.
Abnormal internal clock
function.
101, 102
201
202
203
205
206
207
The power meter does not contain any user-serviceable parts. If the power meter requires service,
contact your local sales representative. Do not open the power meter. Opening the power meter voids
the warranty.
DOCA0006EN 06/2012
97
98
DOCA0006EN 06/2012
PM3200 series
DOCA0006EN 06/2012
Appendices
DOCA0006EN 06/2012
Chapter Name
Page
101
103
99
100
DOCA0006EN 06/2012
PM3200 series
Power Factor Register Format
DOCA0006EN 06/2012
A
Register Format in Power Factor
Each power factor (PF) value occupies 1 floating point register. The power meter display interprets the
register format according to the PQS Coordinate System chart. The PQS Coordinate System chart uses
the power factor register value to provide information on leading or lagging power factor and current, and
also energy import or export.
Power Factor (PF): Difference between the total power and the portion of total power that does the
useful work. The ratio of Active (P) power to Apparent (S) power (kW/kVA).
True Power Factor: Includes harmonic content.
Leading PF: Active (P) and Reactive (Q) power are flowing in opposite directions.
Lagging PF: Active (P) and Reactive (Q) power are flowing in same directions.
Leading Current (I): Current is leading voltage up to 180 .
Lagging Current (I): Current is lagging voltage up to 180 .
The PQS Coordinate System chart quadrants are based on the IEC convention.
DOCA0006EN 06/2012
101
Action
Use the register value to determine in which quadrant the system is operating.
NOTE: The quadrant determines lead/lag for power factor and current.
value.
If the register value is within -1 to +1, the power factor value is derived
differently for active energy import and active energy export systems:
for active energy import: PF = 2 - (the register value)
for active energy export: PF = -2 - (the register value)
For example:
Register value = 0.999: Apparent power is in quadrant 1, current (I) is
lagging, and active energy is imported to the customer load with a lagging
power factor of 0.999.
Register value = -1.1: Apparent power is in quadrant 2, current (I) is lagging,
and active energy is exported by the customer load with a leading power
factor of -0.9 (PF = (-2) - (-1.1)).
Register value = -0.986: Apparent power is in quadrant 3, current (I) is
leading, and active energy is exported by the customer load with a lagging
power factor of 0.986.
Register value = 1.14: Apparent power is quadrant 4, current (I) is leading,
and active energy is imported to the customer with a leading power factor
of 0.86 (PF = 2 - 1.14).
102
DOCA0006EN 06/2012
PM3200 series
Abbreviations and Symbols
DOCA0006EN 06/2012
B
Abbreviations and Symbols
DOCA0006EN 06/2012
Abbreviations/Symbols
Description
Comon
Common
Dfault
Default
DMD
Demand
DMDPk
Peak Demand
Ea
Active Energy
Er
Reactive Energy
Eap
Apparent Energy
Epart
HiMax
LangDL
Language download
LoMin
MnMx
Minimum, Maximum
Oper
Operation
Pk1DT
PknDT
PFLed
PFLag
PWD
Password
TgPhi
THDU
THDV
THDI
Uubl
Vubl
Ver
Version
WAGES
103
104
DOCA0006EN 06/2012
DOCA0006EN-01
Schneider Electric Industries SAS
35, rue Joseph Monier
CS30323
F - 92506 Rueil Malmaison Cedex
www.schneider-electric.com
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
06/2012