Nothing Special   »   [go: up one dir, main page]

Juno Net: Networkable Fire Detection System

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Global Fire Equipment // ​globalfire.

pt dt_junonet_01_010002_en_200406

JUNO NET
Networkable Fire Detection System

EN54-2 and EN54-4


1328-CPR-0160
CERTIFIED

JUNO NET is a powerful Analogue Addressable Fire Alarm Control System with networking capabilities that
facilitate the configuration of complex Wide Area Fire Detection Systems. Modular construction and distributed
intelligence allow systems of up to 96 Loops to be constructed. With a high level of built-in redundancy and
emergency backup features, the JUNO NET is fully equipped to control the most complex installations.

Using its wide array of interfacing capabilities the JUNO NET is ideally placed to provide an efficient and effective solution to
the logistics of protecting large institutions. JUNO NET is available as a standalone system of up to 13 Loops in a single
cabinet and can be expanded to up to 96 Loops via a networked array of sub-panels which can be supplied in a blank box
version or combined with a repeater to allow remote display and control of the system. Networking is done by a monitored,
redundant, double RS422/RS485, Fibre optic loop or TCP/IP network.

The JUNO NET networking capabilities are further enhanced by a wide range of programming options which provide the
capability to customise the system according to the needs of the customer. Flexible cause and effect programming of I/O
devices and warning devices ensure that Fire/ Fault warnings trigger the appropriate response.

An interactive graphic representation of the system can be displayed on the users' computer via the ODYSSEY graphical
software (optional). All the devices on the system can be displayed on a building plan showing their status in real time. In the
event of Fire or Fault the customer can control the system and access all the necessary information with a few mouse-clicks.

Automatic device detection at start up reduces time spent at the commissioning stage. In Installation mode the JUNO NET
detects and recognises addressed and connected devices with the system being fully operational in less than two minutes.
The default programming ensures that the system is ready to detect Fire/ Fault alerts from the moment that power is applied.

Additional programming, to customise the system can be implemented via the onboard keypad, IR programmer, PS/2
keyboard or with a laptop PC running the GFE CONNECTOR software which is available free of charge on the ​website​.

MAIN FEATURES
● Fully expandable system from 1-96 Loops with distributed intelligence for added security
● 125 Device addresses per loop
● Up to 96 Loop sounders with 32 individually programmable addresses per Loop
● 96 VULCAN 2 (addressable) ultra low current sounders or beacons per Loop. Only 64 of these units should be installed
per loop when combined sounder beacons are being used. This number includes addressable, shadow, auxiliary and
detector-sounder/beacon versions of these units
● Compatible with major analogue addressable communications protocols
● 2 Fire output changeover relays and 1 Fault output relay (NC)
● Open collector outputs for Fire, Fault and pre-alarm remote indication
● 2 Fully monitored conventional sounder outputs on main panel and each sub panel
● Repeaters with optional integrated Sub-Panels (J-NET-REP + Loop Card)
● 384 Programmable zones
● 512 Fully programmable sounder and I/O groups
● Event Log 2000 entries FIFO
● Backlit LCD display 4 row x 40 characters
● Programming options: onboard keypad, Remote IR (optional), PS2 Keyboard and GFE CONNECTOR Software
● PC Graphics package ODYSSEY for alarm management and reporting (optional)
● Multiple Language support (menu selectable)
● MODBUS (ASCII & RTU) and BMS support.

1
Global Fire Equipment // ​globalfire.pt dt_junonet_01_010002_en_200406

TECHNICAL SPECIFICATIONS 1 - 3 LOOPS 4 - 13 LOOPS


LOOPS 1 to 4 loops - Max 275 mA per loop 4 to 13 loops - Max 275 mA per loop

SOUNDER OUTPUTS 2 at 28 V DC / 500 mA each 4/6/8 24 V DC / 500 mA each

AUX. RELAYS FIRE 2 rated 50 VAC / DC 1A resistive 2 rated 50 V AC / DC 1A resistive

AUX. RELAY FAULT 1 rated 50 VAC / DC 1A resistive 1 rated 50 V AC / DC 1A resistive

AUX SUPPLY OUTPUT 28 V DC; 2x230 mA 28 V DC; 2x230 mA

ADDITIONAL OUTPUTS Multiplexed up to 384 Zones Multiplexed up to 384 Zones

PRIMARY SUPPLY 230 +10% -15% V AC 230 +10% -15% V AC

SECONDARY SUPPLY 28 V DC Nominal 28 V DC Nominal

POWER SUPPLY RATING 65 W 150 W (4-6 Loop) - 200 W (7-13 Loop)

QUIESCENT CURRENT (NO DEVICES) 130 mA 130 mA + 90 mA / sub-panel

BATTERIES (INTERNAL) 2 x 12 V 12 AH 2 x 12 V 12 AH

OPERATING TEMPERATURE -10ºC to 50ºC -10ºC to 50ºC

STORAGE TEMPERATURE -10ºC to 50ºC -10ºC to 50ºC

HUMIDITY Max 95% no condensation Max 95% no condensation

PROTECTION IP21 IP21

DIMENSIONS 375 (L) x 345 (W) x 139 (H) mm 420 (L) x 550 (H) x 127 (W) mm

WEIGHT 5,1 Kg (no batteries) 8,1 Kg (no batteries)

COLOUR White or Red White or Red

ORDER CODE

J-NET-EN54-SC-001 1328-CPR-0160 1 LOOP - PSU 2.4A

J-NET-EN54-SC-002 1328-CPR-0160 2 LOOPS - PSU 2.4A

J-NET-EN54-SC-003 1328-CPR-0160 3 LOOPS - PSU 2.4A

J-NET-EN54-SC-004-L LARGE BOX - 4 LOOPS - PSU 5A

J-NET-EN54-SC-005 LARGE BOX - 5 LOOPS - PSU 5A

J-NET-EN54-SC-006 LARGE BOX - 6 LOOPS - PSU 5A

J-NET-EN54-SC-007 LARGE BOX - 7 LOOPS - PSU 7.5A

J-NET-EN54-SC-008 LARGE BOX - 8 LOOPS - PSU 7.5A

J-NET-EN54-SC-009 LARGE BOX - 9 LOOPS - PSU 7.5A

J-NET-EN54-SC-010 LARGE BOX - 10 LOOPS - PSU 7.5A

J-NET-EN54-SC-011 LARGE BOX - 11 LOOPS - PSU 7.5A

J-NET-EN54-SC-012 LARGE BOX - 12 LOOPS - PSU 7.5A

J-NET-EN54-SC-013 LARGE BOX - 13 LOOPS - PSU 7.5A