Nothing Special   »   [go: up one dir, main page]

A6v10356072 - Fn2001-U1 Safedlink - Fcnet Network Module - en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Desigo Fire Safety

SAFEDLINK / FCnet Network Module


Model FN2001-U1
e
Architect & Engineer Specifications Product Overview
 Supports ‘peer-to-peer’ networking The SAFEDLINK network module (Model FN2001-U1) is used to network up to 16
between the following: FACPs and the fire terminal unit (Model FT2050), via the FCnet system bus. The
 Models FC2025 / FV2025 and FC2050 SAFEDLINK network module plugs into the Operating Unit (Model FCM2018-U2 or
/ FV2050 fire alarm control panels Model FCM2019-U2).
(FACPs) Model FN2001-U1 supports ‘peer-to-peer’ networking between the following systems:
 Model FT2050 fire terminal unit
 Models FC2025, FV2025
 Electrical isolation between the system  Models FC2050, FV2050
bus and FACP
 Model FT2050
 System-bus input / output connections
The Model FN2001-U1 connects to system-bus inputs and outputs. The module has
 Fast data transfer ground-fault monitoring and an integrated degrade-mode function. Redundant
networking is accomplished with one (1) network module per panel [simple loop
 Holds up to 16 network nodes trouble].
 Style 4 or Style 7 wiring There is an electrical isolation between the system
bus and the FACP. Programming software is held
 Ground-fault monitoring
in flash electrically erasable programmable read-
 Integrated degrade-mode function only memory (EEPROM).

 UL 864 10th Edition Listed, ULC-S527 Model FN2001-U1 is CSFM (#7165-0067:0264);


Listed
FM (#3010) and FDNY (#6104) Approved.
 FM, CSFM and NYC Fire Department
Approved
Model
FN2001-U1

Temperature and Humidity Range


Model FN2001-U1 is UL 864 10th Edition Listed for indoor dry locations within a
temperature range of 120+/-3°F (49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative
humidity of 93+/-2% at a temperature of 90+/-3°F (32+/-2°C).

Siemens Data Sheet 6805


Smart Infrastructure – Building Products usa.siemens.com/fire
Technical Data Physical Properties
Supply Inputs Dimensions 2” ─x─ 2.8” ─x─ 0.8”
( W-x-H-x-D ) (5.0 cm. -x- 7.0 cm. -x- 2.0 cm.)
Operating Voltage: 20.4 ─ 30 VDC

Operating Current: 45mA, max. Weight 0.44 Lbs. (20g)

System Bus
Voltage: 5VDC Details for Ordering
Power 100mA, max. MODEL PART
PRODUCT
OR TYPE NUMBER
Impedance 120 Ω
SAFEDLINK
FN2001-U1 S54400-A60-A1
Cable Types Shielded and unshielded Network Module

Protocol SAFEDLINK (UDP / IP)

Speed 312 kilobytes per second Related Documentation


Data Rate in
Operation Mode: Data Sheet
Distance 96 kilobytes per second Product
Number
Distance between two (2) 3,281 ft.
network modules: (1,000 meters), max. Fire Terminal and Equipment 6803

Electrical isolation: Desigo Fire Safety 252 / 504-point


1 kV 6815
{between FCnet and the FACP} Addressable System

 Short-circuit Desigo Fire Safety Intelligent Voice


Communication System 6821
Monitored for:  Open loop
 Ground fault
 Communication error

Connections
System Bus:
 Design 14 ─ 22 AWG
 Admissible cross-section [American Wire Gauge]
cable

Operating Unit Plug-In-Type Connection

NOTICE – The information contained in this data-sheet document is intended only


as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets – as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.

Data contained in the aforesaid type of documentation should be consulted


with a fire-safety professional before specifying or using the product.

Any further questions or assistance concerning


particular problems that might arise, relative to the
proper functioning of the equipment, please contact
Desigo Fire Safety
the Manufacturer.
Siemens Industry, Inc.
Smart Infrastructure - Building Products
2 Gatehall Drive • Parsippany, NJ 07054
Tel: (973) 593-2600
March - 2023