r48-2000 - Datasheet - Rev3 1 - 20100113 PDF
r48-2000 - Datasheet - Rev3 1 - 20100113 PDF
R48-2000
R48-2000 DC Power
for Business-Critical Continuity™
% of output power
Input Voltage, Permitted Variation 85 to 300 V AC
100
Line Frequency 45 to 65 Hz 80
Max Input Current 13 A 60
Power Factor 0.99 40
20
THD (Total Harmonic Distortion) <5% from 50 to 100% of rated load
0
-40 -20 0 20 40 60 80 100
% of output power
120
Control and Monitoring 100
80
Rectifier Alarm and Signaling Alarm and status reported via CAN bus to system controller
60
Visual Indications Green LED: Normal Operation 40
Yellow LED: Alarm 20
Red LED: Failure 0
0 50 100 150 200 250 300 350
Flashing Red LED: Fan Failure
For R48-2000 Input voltage (VAC)
Environmental
Temperature Range, Operating -40 to +80°C, -40 to +176°F
Temperature Range, Storage -40 to +80°C, -40 to +176°F
Relative Humidity 0 to 95%
Altitude 2000 m, 6560 ft at full power
EMC ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B,
Telcordia GR-1089-CORE class B
Safety IEC 60950, EN 60950, UL 60950
Mechanics
Dimensions (H×W×D) 86×84.5×272mm (3.37×3.31×10.66 inches)
Weight 2.4 kg (5.3lbs)
Other parts
Controller Units See separate ACU / ACU+ and SCU / SCU+ datasheets
Ordering information
Product Name R48-2000
Shelf 19 inch with 5 rectifier positions
Shelf 19 inch with 4 rectifier positions +1 controller position
Shelf 23 inch with 6 rectifier positions
Shelf 23 inch with 5 rectifier positions +1 controller position