2.3
A
B
C
D
E
:
:
:
:
Cable Trays
All cable trays shall be of heavy duty type with return flange not less than 50 mm.
Perforated cable trays shall be hot-dip zinc coated galvanized steel after
manufacture, with heavy duty galvanizing coating of 350 g/m2 and Z2 bending
grade according to BS EN ISO. 1461
Provided all manufacturer's standard accessories and fittings such as clamps,
hangers, brackets, splice plates, reducer plates, blind ends, barrier strips,
connectors, grounding straps and angles shall be of the same specification as
that of the cable tray finish and shall be standard products from t he same
manufacturer as the cable tray. Site fabrication shall not be permitted.
Perforated type cable trays and accessories shall be of a thickness of not less
than:
1.5 mm up to 450 mm width.
2.0 mm above 450 mm width.
Cable Ladder
All cable ladders shall be heavy duty gauge (>2 mm), manufactured from hot-dip
galvanized steel after manufacture according to BS EN ISO 1416 with a standard
heavy duty galvanizing coating of 350 g/m2 and Z2 bending grade.
All accessories and fittings such as couplers, bends, tees, elbows, etc. shall be
by the same manufacturer as the ladder.
Ladder system supports shall be determined in accordance with the
manufacturer's structural information to ensure that undue stress or bending
shall not occur.
Tinned copper earth straps shall be provided at every joint of cable ladders.
In outdoor locations and areas subject to corrosive atmosphere, the ladders shall
be painted with chlorinated rubber paint or PVC/Epoxy coating, as approved by
the engineer
Compliance
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
To be complied by MEP contractor
Claus
e
2.5
Specification
SURFACE/FLOOR CABLE TRUNKING
Surface/floor cable trunking shall be used with prior approval of the Engineer,
wherever possible to replace multiple conduit runs.
Compliance
Noted
Metal surface/floor cable trunking shall comply with BS 4678 Part 1: Class 3 and
shall be manufactured from galvanised steel sheets.
Comply
Only purpose made bends, tees, risers, end stops, fittings, connectors, covers
and accessories by the same manufacturer as the trunking shall be used and
finished in hot dipped galvanized steel. Site fabrication shall not be permitted.
Covers for surface type cable trunking, suspended for fixed on surface of wall or
under raised floor, shall be of the overlapping type and secured to the trunking by
an approved type of fastening arrangement such as clips, etc.
Comply
Comply
Comply
Heavy Duty UPVC trunking with clip on lid (all insulated) shall be used, if shown
on the Drawings or specified elsewhere, to replace multiple conduit runs. All PVC
cable trunking and accessories shall be obtained from the same manufacturer.
Only standard accessories fabricated by the manufacturer shall be used and no
site fabrication shall be allowed.
Not Applicable