+0300006EN
+0300006EN
+0300006EN
User manual
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
Connected Efficiency
ENG
WARNINGS DISPOSAL
All of the above suggestions likewise apply to the controllers, serial boards,
programming keys or any other accessory in the CAREL INDUSTRIES product
portfolio. IMPORTANT: Separate as much as possible the probe and digital input cables
CAREL INDUSTRIES adopts a policy of continual development. Consequently, from the cables to inductive loads and power cables to avoid possible
CAREL INDUSTRIES reserves the right to make changes and improvements to electromagnetic disturbance.
any product described in this document without prior warning. Never run power cables (including the electrical panel cables) and signal
The technical specifications shown in the manual may be changed without cables in the same conduits
prior warning.
NO POWER
The liability of CAREL INDUSTRIES in relation to its products is specified in & SIGNAL
the CAREL INDUSTRIES general contract conditions, available on the website CABLES
www.carel.com and/or by specific agreements with customers; specifically, TOGETHER
to the extent where allowed by applicable legislation, in no case will CAREL READ CAREFULLY IN THE TEXT!
INDUSTRIES, its employees or subsidiaries/affiliates be liable for any lost
earnings or sales, losses of data and information, costs of replacement goods
or services, damage to things or people, downtime or any direct, indirect,
incidental, actual, punitive, exemplary, special or consequential damage of any
kind whatsoever, whether contractual, extra-contractual or due to negligence,
or any other liabilities deriving from the installation, use or impossibility to use
the product, even if CAREL INDUSTRIES or its subsidiaries are warned of the
possibility of such damage.
6. FUNCTIONS 28
6.1 Power supply mode ..................................................................................28
6.2 Battery charge delay .................................................................................28
6.3 Network connection ................................................................................28
6.4 Inputs and outputs ....................................................................................28
6.5 Control status ...............................................................................................30
6.6 Special control status ...............................................................................32
7. PROTECTORS 33
7.1 Protectors ........................................................................................................33
New functions have been introduced with software revision 5.4 and higher: Fig. 1.c
• programmable control, both superheat and special, and programmable
positioner: these functions exploit CAREL’s technology and know-how in Valve cable E2VCABS*00 (IP67)
terms of control logic;
Shielded cable with built-in connector for connection to the valve motor. The
• custom refrigerant selection; connector code E2VCON0000 (IP65) can also be purchased on its own, to be
• control with level sensor for flooded evaporator; wired.
• control with level sensor for flooded condenser.
From the software revision following the 7.2-7.3 new features have been
introduced, including:
• battery charge delay;
• external signal 0 ... 5 V (for programmable positioner).
Fig. 1.e
Fig. 1.a
USB/RS485 converter (code CVSTDUMOR0)
The converter is used to connect the configuration computer and the EVD
evolution twin controllers, for RS485/Modbus ® models only. Fig. 1.f
Fig. 1.b
“EVD Evolution TWIN” +0300006EN - rel. 2.10 - 24.01.2024 8
ENG
2. INSTALLATION
2.1 DIN rail assembly and dimensions 2.3 Connection diagram - superheat control
EVD evolution twin is supplied with screen-printed connectors to simplify
wiring. CAREL EXV CAREL EXV
VALVE B VALVE A
VBAT
COM 1
NO 1
G0
G
1 3 2 4
EVD evolution 4 14 15
S
1 A
110 45 2
3
twin shield
shield
13
COMA
NOA
VBAT
G0
1 3 2 4
G
16
Analog – Digital Input Network
V REF
GND
DI1
DI2
COMB
S1
S2
S3
S4
NOB
GND Tx/Rx 1 3 2 4
G0
G
Fig. 2.a TRADRFE240 A B
VREF
GND
DI1
DI2
S1
S4
S2
S3
GND Tx/Rx
VBAT
NO A1
G0
G
1 3 2 4
COM A
EVDCNV00E0
Power Supply EX V connection A Relay A
EVD4 service USB adapter
1 3 2 4
COM B
4
NO B
EVD4
PC
EEV driver
E X V connection B Relay B 11
6
EVD evolution 7 8 9 10 12
aa Fig. 2.c
Key:
twin 1
2
3
green
yellow
brown
4 white
5 personal computer for configuration
Analog – Digital Input Network 6 USB/tLAN converter
7 ratiometric pressure transducer–evaporation pressure driver A
V REF
GND
DI1
DI2
S1
S2
S3
S4
2 AT
2.4 Installation 2 AT
1
3
2
4
COMA
NOA
G
G0
VBAT
1
3
2
4
COMA
NOA
G
G0
VBAT
10 metres away from the driver, or a maximum of 30 metres as long as
shielded cables with a minimum cross-section of 1 mm² are used;
2. connect any digital inputs, maximum length 30 m; pCO
3. connect the power cable to the valve motors: use 4-wire shielded cable
AWG 22 Lmax=10 m or AWG 14 Lmax=50m; failure to connect the valve Fig. 2.g
motors after connecting the controller will generate the “EEV motor error”
alarm: see paragraph 9.5;
4. carefully evaluate the maximum capacity of the relay outputs specified in the Installation environment
chapter “Technical specifications”;
5. if necessary, use a class 2 safety transformer with suitable short-circuit and Important: avoid installing the controller in environments with the
overload protection. For the power ratings of the transformer see the following characteristics:
general connection diagram and the technical specifications; • relative humidity greater than the 90% or condensing;
6. the connection cables must have a minimum cross-section of 0.5 mm2; • strong vibrations or knocks;
7. power up the controller: for 24 Vdc power supply the controller will close the • exposure to continuous water sprays;
valves; • exposure to aggressive and polluting atmospheres (e.g.: sulphur and
ammonia fumes, saline mist, smoke) to avoid corrosion and/or oxidation;
Important: for 24 Vdc power supply, set “Power supply mode” • strong magnetic and/or radio frequency interference (avoid installing the
parameter=1 to start control. See par. 6.1 appliances near transmitting antennae);
• exposure of the controller to direct sunlight and to the elements in general.
Drivers in a serial network
Case 1: multiple controllers connected in a network powered by the same Important: When connecting the controller, the following warnings
transformer. Typical application for a series of controllers inside the same must be observed:
electrical panel • if the controller is not used as specified in this user manual, the protection
indicated is not guaranteed;
• incorrect connection to the power supply may seriously damage the
controller;
230 Vac
24 Vac
• use cable ends suitable for the corresponding terminals. Loosen each
2 AT 2 AT 2 AT
screw and insert the cable ends, then tighten the screws and lightly tug
the cables to check correct tightness;
COMA
COMA
VBAT
COMA
NOA
VBAT
NOA
• separate as much as possible (at least 3 cm) the probe and digital
VBAT
NOA
G0
G0
G
1
3
2
4
G0
1
3
2
4
G
1
3
2
4
pCO
input cables from the power cables to the loads so as to avoid possible
electromagnetic disturbance. Never lay power cables and probe cables in
the same conduits (including those in the electrical panels;
Fig. 2.d • install the shielded valve motor cables in the probe conduits: use shielded
valve motor cables to avoid electromagnetic disturbance to the probe
Case 2: multiple controllers connected in a network powered by different cables;
transformers (G0 not connected to earth). Typical application for a series of • avoid installing the probe cables in the immediate vicinity of power devices
controllers in different electrical panels. (contactors, circuit breakers, etc.). Reduce the path of the probe cables as
much as possible and avoid enclosing power devices;
• avoid powering the controller directly from the main power supply in the
230 Vac 230 Vac 230 Vac panel if this supplies different devices, such as contactors, solenoid valves,
24 Vac 24 Vac 24 Vac etc., which will require a separate transformer.
2 AT 2 AT
2 AT
• * EVD EVO is a control to be incorporated in the end equipment, do not
COMA
COMA
VBAT
NOA
COMA
VBAT
NOA
VBAT
NOA
G0
1
3
2
4
G0
1
3
2
4
G
1
3
2
4
pCO
• * DIN VDE 0100: Protective separation between SELV circuit and other
circuits must be guaranteed. The requirements according to DIN VDE 0100
must be fulfilled. To prevent infringement of the protective separation
Fig. 2.e (between SELV circuit to other circuits) an additional fixing has to be
provided near to the terminals. This additional fixing shall clamp the
Case 3: multiple controllers connected in a network powered by different insulation and not the conductor”.
transformers with just one earth point. Typical application for a series of
controllers in different electrical panels.
NOA
COMA
VBAT
NOA
VBAT
NOA
G0
G0
1
3
2
4
G
1
3
2
4
G0
G
1
3
2
4
pCO mode, whereby if one valve opens, the other closes by the same percentage.
To achieve such behaviour, simply set the “valve” parameter (“Two EXV
connected together”) and connect the valve motor power supply wires to
the same connector. In the example shown below, for operation of valve B_2
Fig. 2.f
with valve B_1 in complementary mode simply swap the connection of wires
1 and 3.
4 4
CLOS
E
2 2
3 1
1 3
press
1 3 2 4 1 3 2 4 Fig. 2.j
Fig. 2.h
VBAT
G0
COMA
NOA
G
1 3 2 4
COMB
NOB
1 3 2 4
4 NET
Note: operation in parallel and complementary mode can only be 1
used for CAREL valves, within the limits shown in the table below, where OK OPEN A OPEN B
means that the valve can be used with all refrigerants at the rated operating
CLOSE A CLOSE B
pressure. EVDCNV00E0 EVD evolution
A B
TWIN
Model of CAREL valve EVD4 service USB adapter
4
EVD4
EEV driver
2
Two EXV OK E3V45, MOPD=35bar E4V85, MOPD=22bar NO NO NO Analog - Digital Input Network
con- E3V55, MOPD=26bar E4V95, MOPD=15bar 3
VREF
GND
DI1
DI2
S1
S4
S2
S3
GND Tx/Rx
nected E3V65, MOPD=20bar
together
Tab. 2.b
Fig. 2.k
Nota: MOPD = Maximum Operating-Pressure Differential Key:
1 service serial port
2 adapter
3 USB/tLAN converter
4 personal computer
2.6 Shared pressure probe
Only 4 to 20 mA pressure probes (not ratiometric) can be shared. The probe
can be shared by a maximum of 5 drivers. For multiplexed systems where Note: when using the service serial port connection, the VPM program
twin1, twin2 and twin 3 controllers share the same pressure probe, choose the can be used to configure the controller and update the controller and display
normal option for driver A on the twin 1 controller and the “remote” option for firmware, downloadable from http://ksa.carel.com. See the appendix.
the other drivers. Driver B on the twin3 controller must use another pressure
probe, P2.
Example
twin1 twin2 twin3
Probe S1 -0.5 to 7 barg (P1) remote, -0.5 to 7 barg remote,
(driver A) -0.5 to 7 barg
Probe S3 remote, -0.5 to 7 barg remote, -0.5 to 7 barg -0.5 to 7 barg (P2)
(driver B)
Tab. 2.c
VREF
GND
GND
GND
DI1
DI1
DI2
DI2
DI1
DI2
S1
S1
S4
S4
S2
S2
S1
S3
S3
S4
S2
S3
P1 P2
Fig. 2.i
Key:
P1 shared pressure probe
P2 pressure probe
VBAT
EVBAT00500
G0
G
3. confirm by pressing ENTER;
EVD Battery module 4. the display will prompt for confirmation, press ENTER;
EVBAT00400 5. at the end a message will be shown to notify the operation if the operation
4 AT was successful.
BAT ERR
GND
• UPLOAD: the display saves all the values of the parameters on the source
+
- controller;
• DOWNLOAD: the display copies all the values of the parameters to the
target controller;
• RESET: all the parameters on the controller are restored to the default
values.
• See the table of parameters in chapter 8.
VBAT
G0
G
DI1
DI2
Fig. 2.n
230 Vac 24 Vac
Important:
35 VA 2 AT
• the procedure must be carried out with controller/controllers powered;
TRADRFE240
• DO NOT remove the display from the controller during the UPLOAD,
Fig. 2.l DOWNLOAD, RESET procedure;
• the parameters cannot be downloaded if the source controller and the
target controller have incompatible firmware;
Note: set the “Battery charge delay” parameter, depending on the
application. See the chapter “Functions”.
• the parameters cannot be copied from driver A to driver B.
COMA
NOA
G
1 3 2 4
COMB
NOB
1 3 2 4
NET
OPEN A OPEN B
CLOSE A CLOSE B 1
EVD evolution
A B
TWIN
DI1
DI2
S1
S4
S2
S3
GND Tx/Rx
shield 2
Fig. 2.m
Key:
1 personal computer for configuration
2 USB/RS485 converter
Note:
• the serial port can be used for configuration with the VPM program and for
updating the controller firmware, downloadable from http://ksa.carel.com;
• to save time, up to 8 controllers EVD evolution twin can be connected to
the computer, updating the firmware at the same time (each controller
must have a different network address).
A 4 18 19
S
1 A
2
VBAT
3
G0
G
shield shield
EVD 17
ULTRACAP
COMA
VBAT
G0
NOA
G
1 3 2 4
14
with battery
COMB
NOB
1 3 2 4
OPEN A OPEN B
G0
G
35 VA 15 16
TRADRFE240
EVD evolution CLOSE A CLOSE B
A B
TWIN
without battery
Tx/Rx
GND
230 Vac 24 Vac pCO
2 AT
35 VA
G0
G
shield
TRADRFE240 Analog - Digital Input Network
VREF
GND
GND
DI1
DI2
pCO
S1
S4
S2
S3
GND Tx/Rx
5
EVDCNV00E0
shield
EVD4 service USB adapter
4
GND
EVD4
PC
EEV driver
7 pCO
Modbus®
6 12
shield
RS485
23
22
VREF
9 10 11 13
VREF
B
GND
C 8
DI1
DI2
DI1
DI2
S1
S4
S2
S1
S3
S4
S2
S3
VREF
F
GND
GND
L
DI1
DI1
DI2
DI2
S1
S4
S1
S2
S4
S3
S2
S3
1
1 4
VREF
GND
D
DI1
DI2
20
S1
S4
2
S2
S3
GND Tx/Rx 21 20
VREF
GND
DI1
DI2
S1
S4
S2
S3
GND Tx/Rx
E
Fig. 2.o
Key:
1 green 21 black
2 yellow 22 computer for configuration/supervision
3 brown
4 white A Connection to EVD0000UC0
5 computer for configuration B Connection to ratiometric pressure transducer (SPKT00**R0)
6 USB/tLAN converter C Connection to electronic pressure probe (SPK**0000) or piezoresistive
7 adapter pressure transducer (SPKT00*C00)
8 ratiometric pressure transducer driver A D Connection as positioner (4 to 20 mA input)
9 NTC probe driver A E Connection as positioner (0 to 10 Vdc input)
10 ratiometric pressure transducer driver B F Connection to combined pressure/temperature probe (SPKP00**T0)
11 NTC probe driver B L Connection to Float level sensor (cod. LSR00*3000)
12 digital input 1 configured to enable driver A control The maximum length of the connection cable to the EVD0000UC0 module
13 digital input 2 configured to enable driver B control 1 is 5 m.
14 voltage-free contact (up to 230 Vac) driver B The connection cable to the valve motor must be 4-wire shielded, AWG 22
15 solenoid valve driver B 2 Lmax= 10 m or AWG14 Lmax= 50 m.
16 alarm signal driver B
17 voltage-free contact (up to 230 Vac) driver A
18 solenoid valve driver A
19 alarm signal driver A
20 red
VBAT
COM 1
NO 1
G0
G
1 3 2 4
7
1 Surriscaldam. ON
4.9 K A/B
EVD
6
MOP
evolution
Apertura T 5
2 valvola ALARM
44 % -- Rele 4
twin 3
8
Fig. 3.c
Analog – Digital Input Network
Key:
V REF
GND
DI1
DI2
S1
S2
S3
S4
GND Tx/Rx
Fig. 3.d
Modifying the Manufacturer parameters
Important: the probe S1 parameter is common to both drivers, while the The Manufacturer level is used to configure all the controller parameters, and
main control parameter must be set for each driver. See the table of parameters. consequently, in addition to the Service parameters, the parameters relating
to alarm management, the probes and the configuration of the valve. See the
table of parameters.
Procedure:
3.4 Display mode (display) 1. press Esc one or more times to switch to the standard display;
Display mode is used to display the useful variables showing the operation 2. Select driver A or B to set the corresponding parameters (see paragraph 3.3);
of the system. 3. press Prg : the display shows a screen with the PASSWORD request;
The variables displayed depend on the type of control selected. 4. press ENTER and enter the password for the Manufacturer level: 66,
1. Press Esc one or more times to switch to the standard display; starting from the right-most figure and confirming each figure with
2. Select driver A or B to display the corresponding variables (see paragraph 3.3); ENTER;
3. press UP/DOWN: the display shows a graph of the superheat, the percentage 5. if the value entered is correct, the list of parameter categories is shown:
of valve opening, the evaporation pressure and temperature and the - Configuration
suction temperature variables; - Probes
4. press UP/DOWN: the variables are shown on the display followed by the - Control
screens with the probe and valve motor electrical connections; - Special
5. press Esc to exit display mode. - Alarm configuration
For the complete list of variables used according to the type of control see - Valve
paragraph “Variables used based on the type of control”. 6. press the UP/DOWN buttons to select the category and ENTER to access the
first parameter in the category;
SH=4.9K
7. press UP/DOWN to select the parameter to be set and ENTER to move to the
6.4°C A/B value of the parameter;
8. press UP/DOWN to modify the value;
211stp 3.8barg 9. press ENTER to save the new value of the parameter;
69% 1.5°C 10. repeat steps 7, 8, 9 to modify the other parameters;
11. press Esc to exit the procedure for modifying the Manufacturer parameters
CONFIGURAZIONE A/B
Fig. 3.e SONDE
REGOLAZIONE
SPECIALI
CONFIG.ALLARMI
VALVOLA
3.5 Programming mode (display)
The parameters can be modified using the front keypad. Access differs
according to the user level: Service (Installer) and Manufacturer parameters. Fig. 3.g
Note:
Modifying the Service parameters • all the controller parameters can be modified by entering the Manufacturer
The Service parameters, as well as the parameters for commissioning the level;
controller, also include those for the configuration of the inputs, the relay • if when setting a parameter the value entered is out-of-range, this is not
output, the superheat set point or the type of control in general, and the accepted and the parameter soon after returns to the previous value;
protection thresholds. See the table of parameters. • if no button is pressed, after 5 min the display automatically returns to the
Procedure: standard mode.
1. press Esc one or more times to switch to the standard display and select driver
A or B to set the corresponding parameters (see paragraph 3.3);
2. press Prg: the display shows a screen with the PASSWORD request;
3. press ENTER and enter the password for the Service level: 22, starting from
15 “EVD Evolution TWIN” +0300006EN - rel. 2.10 - 24.01.2024
ENG
4. COMMISSIONING
Important: if the refrigerant is not available among the refrigerant 4.2 Setting the pLAN network address
parameter options, contact CAREL service to: The pLAN addresses of the devices in the network must be assigned according
1. confirm that the system: pCO controller + CAREL electronic expansion to the following rule:
valve is compatible with the desired refrigerant (custom); 1. the EVD Evolution driver addresses must be assigned in increasing order from
2. identify the values that define the custom refrigerant: “Dew a…f high/ left to right, starting with the controllers (A),
low” and “Bubble a…f high/low”. See the parameter table. 2. then the drivers (B) and finally
3. the terminals (C).
ADDR = 31
4.1 Commissioning ADDR = 32
Once the electrical connections have been completed (see the chapter pGD pGD C OK
on installation) and the power supply has been connected, the operations
required for commissioning the controller depend on the type of interface
used, however essentially involve setting just 4 parameters: refrigerant, valve, 3
type of pressure probe (S1 for driver A and S3 for driver B) and type of main
G0
VBAT
COM 1
NO 1
G
1 3 2 4
G0
G0
VBAT
COM 1
NO 1
VBAT
COM 1
NO 1
G
G
1 3 2 4 1 3 2 4
G0
VBAT
COM 1
NO 1
G
1 3 2 4
Power Supply E XV connection Relay Power Supply E XV connection Relay Power Supply E XV connection Relay Power Supply E XV connection Relay
V REF
GND
V REF
V REF
V REF
GND
GND
DI1
DI2
GND
S1
S2
S3
S4
DI1
DI2
DI1
DI2
S1
S2
S3
S4
S1
S2
S3
S4
DI1
DI2
GND Tx/Rx
S1
S2
S3
S4
GND Tx/Rx GND Tx/Rx
GND Tx/Rx
confirmation will be requested. Only after confirmation will the controller EVD EVD EVD EVD
be enabled for operation, the main screen will be shown on the display and
control will be able to commence when requested by the pCO controller
2
via LAN or when digital input DI1 closes for driver A and DI2 for driver B.
CANH
CANL
GND
CANH
CANL
GND
See paragraph 4.2;
• VPM: to enable control of the drivers via VPM, set “Enable EVD
control” to 1; this is included in the safety parameters, in the special pCO
parameters menu, under the corresponding access level. However,
the setup parameters should first be set in the related menu.
ADDR = 1 ADDR = 2 A
The drivers will then be enabled for operation and control will be able to
commence when requested by the pCO controller via LAN or when digital
input DI1/DI2 closes. If due to error or for any other reason “Enable EVD
+5 VREF
+Vterm
+5 VREF
+Vterm
GND
GND
G0
U1
U2
control” should be set to 0 (zero), the controller will immediately stop U3
G
G0
U1
U2
U3
G
control and will remain in standby until re-enabled, with the valve stopped pCO pCO
should first be set in the related menu. The controller will then be enabled
for operation and control will be able to commence when requested by
pGD pGD C NO!
the pCO controller via pLAN or when digital input DI1 closes for driver A
and DI2 for driver B. As highlighted on the supervisor, inside of the yellow 3
information field relating to the “Enable EVD control” parameter, if due to
G0
VBAT
COM 1
NO 1
G
1 3 2 4
NO 1
G0
VBAT
COM 1
NO 1
G0
VBAT
COM 1
G
1 3 2 4 1 3 2 4
G0
VBAT
COM 1
NO 1
G
1 3 2 4
Power Supply E XV connection Relay Power Supply E XV connection Relay Power Supply E XV connection Relay Power Supply E XV connection Relay
error or for any other reason “Enable EVD control” should be set to 0 (zero),
ADDR = 9 ADDR=17 ADDR=10 ADDR=18
the controller will immediately stop control and will remain in standby until B
re-enabled, with the valve stopped in the last position; Analog – Digital Input Network Analog – Digital Input Network Analog – Digital Input Network Analog – Digital Input Network
V REF
V REF
GND
V REF
GND
V REF
GND
DI1
DI2
S2
S3
S4
DI1
DI2
DI1
DI2
S1
S2
S3
S4
S1
S2
S3
S4
DI1
DI2
GND Tx/Rx
S1
S2
S3
S4
Important: for the driver with pLAN serial port, see the
CANH
CANL
GND
CANH
CANL
GND
+5 VREF
+Vterm
GND
GND
G0
U1
U2
U3
the application on the pCO, and after a few seconds communication will
G
G0
U1
U2
U3
G
pCO pCO
commence between the two instruments and the controller automatically
be enabled for control. The main screen will shown on the display, which 1
can then be removed, and control will be commence when requested
by the pCO controller or digital input DI1 for driver A and DI2 for driver B. Fig. 4.b
(see paragraph 6.3). If there is no communication between the pCO and
the controller (see the paragraph “LAN error alarm”), this will be able to
continue control based on the status of the digital inputs.
GND
green
TxRx
DI1
DI2
S1
S4
S2
S3
brown
TEMP S2
yellow
white Network address 198 1 207 -
white Tab. 4.a
NOA
G0
COMA
VBAT
PRESS S1
G
4
2
1
black
3
green
For network connection of the RS485/Modbus® models the communication
speed also needs to be set, in bits per second, using the parameter “Network
settings”. See paragraph 6.2.
7. check that the probe electrical 8. check that the electrical
connections are correct for driver A; connections are correct for valve A;
then set the same parameters for Refrigerant
driver B (see step 6); The type of refrigerant is essential for calculating the superheat. In addition, it
9. set the values of the parameters for driver B: refrigerant, valve B, pressure is used to calculate the evaporation and condensing temperature based on
probe S3, main control; the reading of the pressure probe.
Parameter/description Def.
B B CONFIGURATION
VREF
GND
GND
green
TxRx
DI1
DI2
S1
S4
S2
S3
brown
TEMP S4
yellow
white
Refrigerant R404A
white 0 = user definer
PRESS S3
4
NOB
COMB
2
1
black
3
Fig. 5.a
A
PA, PB pressure probe
TA,TB temperature probe
F1
CP1
For the wiring, see paragraph “General connection diagram”. S1
C
PA TA
E2 EVD evolution
EEVA_2 twin
L
S1
S2
S3
S4
C2
F
EVD evolution CP
twin
L2
S
B
S1
S2
S3
S4
F2
CP2
M V S2
E1 E3
M V2
EEVA EEVB_1
PA TA
PB TB
E4
EEVB_2
E2
EEVB PB TB
Fig. 5.c
Key:
CP1,2 compressor 1, 2
Fig. 5.b
C1,C2 condenser 1, 2
Key:
E1, E2, E3, E4 evaporator 1, 2, 3, 4
CP compressor F1, F2 dewatering filter 1, 2
C condenser S1, S2 liquid indicator 1, 2
L liquid receiver EEVA_1, electronic expansion valves driver A
F dewatering filter EEVA_2
S liquid indicator EEVB_1, electronic expansion valves driver B
EEVA, electronic expansion valve A EEVB_2
EEVB electronic expansion valve B TA, TB temperature probe
E1, E2 evaporator 1, 2 L1, L2 liquid receiver 1, 2
PA, PB pressure probe driver A, B V1, V2 solenoid valve 1, 2
TA,TB temperature probe driver A, B
V solenoid valve For the wiring, see paragraph “General connection diagram”.
For the wiring, see paragraph “General connection diagram”.
PID parameters
Superheat control, as for any other mode that can be selected with the “main
Nota: in this example only one electronic pressure transducer control” parameter, is performed using PID control, which in its simplest form
with 4 to 20 mA output (SPK**0000) can be used, shared between is defined by the law:
driver A and B.
Ratiometric transducers cannot be shared. 1 de(t)
u(t)= K e(t) +T ∫e(t)dt + Td dt
i
Key:
u(t) Valve position Ti Integral time
e(t) Error Td Derivative time
K Proportional gain
S1
S2
S3
S4
the value of T (integral time), the more intense the action will be. The S GND Tx/Rx
integration time, in summary, represents the intensity of the reaction of the EEVA
M V
valve, especially when the superheat value is not near the set point;
PA TA
• the derivative action is linked to the speed of variation of the superheat value,
that is, the gradient at which the superheat changes from instant to instant.
It tends to react to any sudden variations, bringing forward the corrective E1
action, and its intensity depends on the value of the time T (derivative time).
EEVB E2
Parameter/Description Def. Min. Max. UOM PB TB
CONTROL
Superheat set point 11 LowSH: 180 (324) K(°F)
GND
threshold pCO
PID: proportional gain 15 0 800 -
shield
PID: integral time 150 0 1000 s
PID: derivative time 5 0 800 s Fig. 5.d
Tab. 5.b Key:
See the “EEV system guide” +030220810 for further information on calibrating CP Compressor V Solenoid valve
PID control. C Condenser S Liquid gauge
L Liquid receiver EEV Electronic expansion valve
Note: when selecting the type of main control (both superheat control F Dewatering filter E1, E2 Evaporator
and special modes), the PID control values suggested by CAREL will be TA, TB Temperature probes PA, PB Pressure probes
automatically set for each application.
For information on the wiring see paragraph “General connection diagram”.
Protection function control parameters
See the chapter on “Protectors”. Note that the protection thresholds are set by
the installer/manufacturer, while the times are automatically set based on the
PID control values suggested by CAREL for each application.
S4
S1
S2
A is used for superheat control on circuit Y.
EEVA
M
C
E TB
V
PA TA
L
EVB
Fig. 5.g
Key:
F CP
EVD evolution CP Compressor V Solenoid valve
twin C Condenser EEVA Electronic expansion valve A
S L Liquid receiver EVB Electronic valve B
S1
S2
S3
This involves PID control without any protectors (LowSH, LOP, MOP, see the
EVB_2 EVD evolution
twin
chapter on Protectors), without any valve unblock procedure. Control is
performed on the gas cooler pressure probe value read by input S1, with
S1
S2
S3
S4
S a set point depending on the gas cooler temperature read by input S2;
CP consequently there is not a set point parameter, but rather a formula: “CO2 gas
cooler pressure set point” = Coefficient A * Tgas cooler (S2) + Coefficient B. The
V3 set point calculated will be a variable that is visible in display mode. Control is
TB direct, as the pressure increases, the valve opens.
Transcritical CO2 gas cooler Forced closing will only occur when digital input DI1 opens for driver A or
DI2 for driver B, thus switching between control status and standby. The
This solution for the use of CO2 in refrigerating systems with a transcritical
pre-positioning and repositioning procedures are not performed. Manual
cycle involves using a gas cooler, that is a refrigerant/air heat exchanger
positioning can be enabled when control is active or in standby.
resistant to high pressures, in place of the condenser.
In transcritical operating conditions, for a certain gas cooler outlet temperature,
there is pressure that optimises the efficiency of the system: EVA
EVD evolution T
twin regulator
Set= pressure set point in a gas cooler with transcritical CO2
T= gas cooler outlet temperature P
S1
EVD evolution
EVD evolution T
twin regulator
twin
P
S1
S2
S3
S4
S3
EVA GC
PA TA 4...20 mA
A1, A2
CP
100%
IHE
0%
4 20 mA
Fig. 5.j
Key:
M EEVB
EVA Electronic valve A A1 Valve opening A
E EVB Electronic valve B A2 Valve opening B
V1 PB TB
For the wiring, see paragraph “General connection diagram”.
Fig. 5.i
“EVD Evolution TWIN” +0300006EN - rel. 2.10 - 24.01.2024 24
ENG
Analogue positioner (0 to 10 Vdc) 5.5 Programmable control
This control function is only available for driver A. The valve will be positioned With programmable control, the unused probe can be exploited to activate
linearly depending on the value of the “0 to 10 V input for analogue valve an auxiliary control function and maximise the controller’s potential. The
positioning” read by input S2. following types of programmable control are available:
There is no PID control nor any protection (LowSH, LOP, MOP), and no valve • Programmable superheat control (SH);
unblock procedure. The opening of digital input DI1 stops control on driver • Programmable special control;
A, with corresponding forced closing of the valve and changeover to standby • Programmable positioner.
status.
Parameter/description Def Min Max U.M.
EVA CONFIGURATION
Main control Multi- - - -
… plexed
EVD evolution T 22= Programmable SH control ¦ cabinet
twin regulator / cold
23 = Programmable special control¦
P 24 = Programmable positioner room
S2
…
SPECIAL
0...10 Vdc Programmable control configuration 0 0
32767 -
Programmable control input 0 0
32767 -
A1
Programmable SH control options 0 0
32767 -
100% Programmable control set point 0 800 -800
(-11603)
(11603)
Tab. 5.j
The table shows the programmable control functions and the related
0% parameter settings.
0 10 Vdc Function Parameter to be set
Direct/reverse setting Programmable control config.
Fig. 5.k Type of physical value controlled Programmable control config.
Key: Input processing to determine measur. Programmable control config.
Correction to each individual input for inte- Programmable control input
EVA Electronic valve A A1 Valve opening A
gration in measurement calculation
For the wiring, see paragraph “General connection diagram”. Association between physical inputs and Programmable control input
logical outputs
setpoint error
I/O expander for pCO PID
The EVD Evolution driver is connected to the pCO programmable controller
via LAN, transferring the probe readings quickly and without filtering. The
measure
driver operates as a simple actuator, and receives the information needed to
manage the valves from the pCO.
Parameter/Description Def.
CONFIGURATION Direct operation: error = measurement - set point
Main control multiplexed showcase/cold Reverse operation: error = set point - measurement
… room
I/O expander for pCO Programmable control configuration
Tab. 5.i
Important: for the explanation of the HiTcond (high condensing
temperature), reverse HiTcond protectors and the “Modulating thermostat”
auxiliary control function, see Appendix 2.
GND Tx/Rx
Hundreds Do not select -
Tens Controlled value Select the type of
TB controlled physical
value (temperature,
PB pressure…)
Units Measurement function Select the function for
TA calculating the value
GND
pCO
controlled by the PID
PA (measurement)
shield Tab. 5.a
Fig. 5.l
Key:
T Temperature probe P Pressure probe
EV Electronic valve
E D C EXAMPLE 2
Superheat control with hot gas bypass by temperature. Programmable control
Pressure [MPa]
L
EVB
F CP
EVD evolution
twin
S
S4
S1
S2
EEVA S3
M
E TB
V
PA TA
Fig. 5.n
The action is reverse: if the liquid level measured by the float level sensor is
higher (lower) than the set point, the EEV valve closes (opens).
TO
COMPRESSOR
EVD
evolution
S2
S1
E
MAX = 100 %
Setpoint = 50 %
MIN = 0 %
EEV
FLOODED FROM
SHELL AND CONDENSER
TUBE EVAPORATOR
Fig. 5.o
Key:
S Float level sensor
EEV Electronic valve
E Flooded evaporator
With the condenser, the action is direct: if the liquid level measured by the
float level sensor is lower (higher) than the set point, the EEV valve closes
(opens).
ON T3 W t
A
OFF Fig. 6.e
Key:
ON t A Control request T3 Repositioning time
S
OFF
C Change capacity W Wait
NP Repositioning t Time
R Control
ON t
P
OFF
Stop/end control
t The stop procedure involves closing the valve from the current position until
ON
R reaching 0 steps, plus a further number of steps so as to guarantee complete
OFF closing. Following the stop phase, the valve returns to standby.
T1 W T2 t A
ON
OFF
Fig. 6.d
Key:
ON t
A Control request W Wait S
S Standby T1 Pre-position time OFF
P Pre-positioning T2 Start delay after defrost
R Control t Time
ON t
ST
OFF
ON t
R
OFF
T4 t
Fig. 6.f
Key:
A Control request R Control
S Standby T4 Stop position time
ST Stop t Time
Manual positioning
Manual positioning can be activated at any time during the standby or control
phase. Manual positioning, once enabled, is used to freely set the position of
the valve using the corresponding parameter.
Note:
• the manual positioning status is NOT saved when restarting after a power
failure;
• in for any reason the valve needs to be kept stationary after a power failure,
proceed as follows:
- remove the valve stator;
- in Manufacturer programming mode, under the configuration
parameters, set the PID proportional gain =0. The valve will remain
stopped at the initial opening position, set by corresponding parameter.
Note:
• realignment is in intrinsic part of the forced closing procedure and is
activated whenever the driver is stopped/started and in the standby phase;
• the possibility to enable or disable the synchronisation procedure depends
on the mechanics of the valve. When the setting the “valve” parameter, the
two synchronisation parameters are automatically defined. The default
values should not be changed.
ON t
Low_SH
OFF
7.1 Protectors
There are 3 protectors: ON t
• LowSH, low superheat; A
• LOP, low evaporation temperature; OFF
• MOP, high evaporation temperature;
D B t
The protectors have the following main features:
Fig. 7.a
• activation threshold: depending on the operating conditions of the Key:
controlled unit, this is set in Service programming mode; SH Superheat A Alarm
• integral time, which determines the intensity (if set to 0, the protector is Low_SH_TH Low_SH protection threshold D Alarm delay
disabled): set automatically based on the type of main control; Low_SH Low_SH protection t Time
• alarm, with activation threshold (the same as the protector) and delay (if set B Automatic alarm reset
to 0 disables the alarm signal).
LOP_TH ON t
PID
OFF
ON t
LOP ON
t
OFF ALARM
OFF
t
A
ON D t
OFF
Fig. 7.c
D B t Key:
Fig. 7.b T_EVAP Evaporation temperature MOP_TH MOP threshold
Key: PID PID superheat control ALARM Alarm
MOP MOP protection t Time
T_EVAP Evaporation temperature D Alarm delay D Alarm delay
LOP_TH Low evaporation temperature ALARM Alarm
protection threshold
LOP LOP protection t Time Important: the MOP threshold must be greater than the rated
B Automatic alarm reset evaporation temperature of the unit, otherwise it would be activated
unnecessarily. The MOP threshold is often supplied by the manufacturer of
the compressor. It is usually between 10°C and 15 °C.
MOP (high evaporation pressure)
MOP= Maximum Operating Pressure. If the closing of the valve also causes an excessive increase in the suction
temperature (S2) above the set threshold – only set via supervisor (PlantVisor,
The MOP protection threshold is applied as a saturated evaporation pCO, VPM), not on the display - the valve will be stopped to prevent
temperature value so that it can be easily compared against the technical overheating the compressor windings, awaiting a reduction in the refrigerant
specifications supplied by the manufacturers of the compressors. The charge. If the MOP protection function is disabled by setting the integral time
protector is activated so as to prevent too high evaporation temperatures to zero, the maximum suction temperature control is also deactivated.
from causing an excessive workload for the compressor, with consequent
overheating of the motor and possible activation of the thermal protector. Parameter/description Def. Min. Max. UOM
The protector is very useful in units with compressor on board if starting with CONTROL
a high refrigerant charge or when there are sudden variations in the load. MOP protection: suction temperature 30 -60 (-72) 200 (392) °C(°F)
The protector is also useful in multiplexed systems (showcases), as allows threshold
all the utilities to be enabled at the same time without causing problems of Tab. 7.e
high pressure for the compressors. To reduce the evaporation temperature,
the output of the refrigeration unit needs to be decreased. This can be done At the end of the MOP protection function, superheat control restarts in a
by controlled closing of the electronic valve, implying superheat is no longer controlled manner to prevent the evaporation temperature from exceeding
controlled, and an increase in the superheat temperature. The protector the threshold again..
will thus have a moderate reaction that tends to limit the increase in the If the suction temperature is greater than or equal to the set temperature
evaporation temperature, keeping it below the activation threshold while protection threshold, the MOP protection does not work.
trying to stop the superheat from increasing as much as possible. Normal
operating conditions will not resume based on the activation of the protector,
but rather on the reduction in the refrigerant charge that caused the increase
in temperature. The system will therefore remain in the best operating
conditions (a little below the threshold) until the load conditions change.
Modbus®
Type **
CAREL
SVP
user *
CONFIGURATION
A Network address pLAN: 30 1 207 - I 11 138 CO
others: 198
A Refrigerant: R404A - - - I 13 140 -
0= user defined;
1= R22 2= R134a 3= R404A 4= R407C 5= R410A
6= R507A 7= R290 8= R600 9= R600a 10= R717
11= R744 12= R728 13= R1270 14= R417A 15= R422D
16= R413A 17= R422A 18= R423A 19= R407A 20= R427A
21= R245FA 22= R407F 23= R32 24= HTR01 25= HTR02
26= R23 27 = R1234yf 28 = R1234ze 29 = R455A 30 = R170
31 = R442A 32 = R447A 33 = R448A 34 = R449A 35 = R450A
36 = R452A 37 = R508B 38 = R452B 39 = R513A 40 = R454B
41 = R458A
A Valve: CAREL EXV - - - I 14 141
0= user defined 13= Sporlan SEH 175 26= CAREL ejector
E2J23AT1N0
1= CAREL E V X
14= Danfoss ETS 12.5-25B 27= CAREL ejector
E3J26AT2N0
2= Alco EX4 15= Danfoss ETS 50B 28= CAREL ejector
E3J33AU2N0
3= Alco EX5 16= Danfoss ETS 100B 29= CAREL ejector
E3J39AV3N0
4= Alco EX6 17= Danfoss ETS 250 30= CAREL ejector
E6J50AV3N0
5= Alco EX7 18= Danfoss ETS 400 31= Danfoss CCMT 16
6= Alco EX8 330Hz 19= Two EXV CAREL con- 32= Danfoss CCMT 24
recommend CAREL nected together
7= Alco EX8 500Hz 20= Sporlan SER(I)G,J,K 33= Danfoss CCMT 30
specific Alco
8= Sporlan SEI 0.5-11 21= Danfoss CCM 10-20-30 34= Danfoss CCMT 42
9= Sporlan SER 1.5-20 22= Danfoss CCM 40 35= Danfoss Colibri
10= Sporlan SEI 30 23= Danfoss CCM T 2-4-8
11= Sporlan SEI 50 24= Disabled
12= Sporlan SEH 100 25= CAREL ejector E2J17AS1N0
A Probe S1: Ratiometric: - - - I 16 143 CO
0= user defined -1 to 9.3 barg
Ratiometric (OUT=0 to 5 V) Electronic (OUT=4 - 20 mA)
1= -1 to 4.2 barg 8= -0.5 to 7 barg
2= 0.4 to 9.3 barg 9= 0 to 10 barg
3= -1 to 9.3 barg 10= 0 to 18.2 bar
4= 0 to 17.3 barg 11= 0 to 25 barg
5= 0.85 to 34.2 barg 12= 0 to 30 barg
6= 0 to 34.5 barg 13= 0 to 44.8 barg
7= 0 to 45 barg 14= remote, -0.5 to 7 barg
21= -1 to 12.8 barg 15= remote, 0 to 10 barg
22= 0 to 20.7 barg 16= remote, 0 to 18.2 barg
23= 1.86 to 43.0 barg 17= remote, 0 to 25 barg
24= CAREL liquid level 18= remote, 0 to 30 barg
25 = 0...60,0 barg 19= remote, 0 to 44.8 barg
26 = 0...90,0 barg 20= 4 to 20mA external signal
27 = external signal 0…5 V
A Main control: Multiplexed - - - I 15 142 -
0= user defined; showcase/
1= Multiplexed showcase/cold room cold room
2= Showcase/cold room with compressor on board
3= “Perturbed” showcase/cold room
4= Showcase/cold room with sub-critical CO2
5= R404A condenser for sub-critical CO2
6= Air-conditioner/chiller with plate heat exchanger
7= Air-conditioner/chiller with tube bundle heat exchanger
8= Air-conditioner/chiller with finned coil heat exchanger
9= Air-conditioner/chiller with variable cooling capacity
10= “Perturbed” air-conditioner/chiller
11= EPR back pressure
12= Hot gas bypass by pressure
13= Hot gas bypass by temperature
14= Transcritical CO2 gas cooler
15= Analogue positioner (4 to 20 mA)
16= Analogue positioner (0 to 10 V)
17= Air-conditioner/chiller or showcase/cold room with adaptive control
18= Air-conditioner/chiller with Digital Scroll compressor (*)
19= AC or chiller with BLDC scroll compressor (CANNOT BE SELECTED)
20= superheat regulation with 2 temperature probes (CANNOT BE SELECTED)
21= I/O expander for pCO (**)
22= Programmable SH regulation
23= Programmable special regulation
24= Programmable positioner
25= Evaporator liquid level regulation with CAREL sensor
26= Condenser liquid level regulation with CAREL sensor
(*) only for controls for CAREL valves
(**) common parameter between driver A and driver B
Modbus®
Type **
CAREL
SVP
user *
Modbus®
Type **
CAREL
SVP
user *
Modbus®
Type **
CAREL
SVP
user *
C Temperature S4: MAXIMUM alarm value 105 Temperature 200 (392) °C (°F) A 45 44 CO
S4: MINIMUM
alarm value
C Maximum difference S1/S3 (pressure) 0 0 200(2900) bar(psig) A 114 113 CO
C Maximum difference S2/S4 (temperature) 0 0 180(324) °C (°F) A 115 114 CO
C Alarm delay S1 0 0 240 s I 131 258 CO
C Alarm delay S2 0 0 240 s I 132 259 CO
C Alarm delay S3 0 0 240 s I 133 260 CO
C Alarm delay S4 0 0 240 s I 134 261 CO
C Enable S1 0 0 1 - D 16 15 CO
C Enable S2 0 0 1 - D 17 16 CO
C Enable S3 0 0 1 - D 18 17 CO
C Enable S4 0 0 1 - D 19 18 CO
CONTROL
A Superheat set point 11 LowSH: 180 (324) K (°F) A 50 49 -
threshold
A Valve opening at start-up (evaporator/valve capacity ratio) 50 0 100 % I 37 164 -
C Valve open in standby 0 0 1 - D 23 22 -
(0= disabled= valve closed; 1=enabled = valve open according
to parameter “Valve position in stand-by”)
C Valve position in stand-by 0 0 100 % I 91 218 -
0 = 25%
1…100% = % opening
C start-up delay after defrost 10 0 60 min I 40 167 -
A Pre-position time 6 0 18000 s I 90 217
A Hot gas bypass temperature set point 10 -85(-121) 200 (392) °C (°F) A 28 27 -
A Hot gas bypass pressure set point 3 -20 (-290) 200 (2900) barg (psig) A 62 61 -
A EPR pressure set point 3.5 -20 (-290) 200 (2900) barg (psig) A 29 28 -
C PID: proportional gain 15 0 800 - A 48 47 -
C PID: integral time 150 0 1000 s I 38 165 -
C PID: derivative time 5 0 800 s A 49 48 -
A LowSH protection: threshold 5 -40 (-72) SH set point K (°F) A 56 55 -
C LowSH protection: integral time 15 0 800 s A 55 54 -
A LOP protection: threshold -50 -85(-121) MOP protec- °C (°F) A 52 51 -
tion: threshold
C LOP protection: integral time 0 0 800 s A 51 50 -
A MOP protection: threshold 50 LOP protec- 200 (392) °C (°F) A 54 53 -
tion: threshold
C MOP protection: integral time 20 0 800 s A 53 52 -
A Enable manual valve positioning 0 0 1 - D 24 23 -
A Manual valve position 0 0 9999 step I 39 166 -
C Discharge superheat setpoint (CANNOT BE SELECTED) 35 -40(-72) 180 (324) K (F°) A 100 99
C Discharge temperature setpoint (CANNOT BE SELECTED) 105 -85(-121) 200 (392) °C (°F) A 101 100
C Liquid level set point 50 0 100 % A 119 118 -
SPECIAL
A HiTcond: threshold - SELECT WITH PROG. CONT. 80 -85(-121) 200 (392) °C (°F) A 58 57 -
C HiTcond: integral time - SELECT WITH PROG. CONT. 20 0 800 s A 57 56 -
A Modulating thermostat: set point - SELECT WITH PROG. CONT. 0 -85(-121) 200 (392) °C (°F) A 61 60 -
A Modulating thermostat: differential - SELECT WITH PROG. CONT. 0. 1 0.1 (0.2) 100 (180) °C (°F) A 60 59 -
C Mod. thermostat: SH set point offset - SELECT WITH PROG. CONT. 0 0 (0) 100 (180) K (°F) A 59 58 -
C Coefficient ‘A’ for CO2 control 3.3 -100 800 - A 63 62 -
C Coefficient ‘B’ for CO2 control -22.7 -100 800 - A 64 63 -
C Impostazioni di rete 2 0 30 - I 74 201 CO
Parity Bit di stop Baud rate
0 no parity 2 stop bits 4800 bps
1 no parity 2 stop bits 9600 bps
2 no parity 2 stop bits 19200 bps
4 no parity 1 stop bit 4800 bps
5 no parity 1 stop bit 9600 bps
6 no parity 1 stop bit 19200 bps
16 even 2 stop bits 4800 bps
17 even 2 stop bits 9600 bps
18 even 2 stop bits 19200 bps
20 even 1 stop bit 4800 bps
21 even 1 stop bit 9600 bps
22 even 1 stop bit 19200 bps
24 odd 2 stop bits 4800 bps
25 odd 2 stop bits 9600 bps
26 odd 2 stop bits 19200 bps
28 odd 1 stop bit 4800 bps
29 odd 1 stop bit 9600 bps
30 odd 1 stop bit 19200 bps
A Power supply mode 0 0 1 - D 47 46 CO
0= 24 Vac; 1= 24 Vdc
C Enable mode single on twin (parameter disabled) 0 0 1 - D 58 57 CO
0= Twin; 1= Single
C Stop manual positioning if net error 0 0 1 - D 59 58 CO
0 = Normal operation; 1 = Stop
C Programmable regulation configuration 0 0 32767 - I 101 228
C Programmable regulation input 0 0 32767 - I 102 229
“EVD Evolution TWIN” +0300006EN - rel. 2.10 - 24.01.2024 38
ENG
Modbus®
Type **
CAREL
SVP
user *
CAREL SVP
Modbus®
Type **
Parameter/description Def. Min. Max. UOM Note
user *
CONFIGURATION
A Network address pLAN: 30 1 207 - I 11 138 CO
altri: 198
A Refrigerant: R404A - - - I 55 182 -
0= User defined;
1= R22 2= R134a 3= R404A 4= R407C 5= R410A
6= R507A 7= R290 8= R600 9= R600a 10= R717
11= R744 12= R728 13= R1270 14= R417A 15= R422D
16= R413A 17= R422A 18= R423A 19= R407A 20= R427A
21= R245FA 22= R407F 23=R32 24=HTR01 25= HTR02
26=R23 27 = R1234yf 28 = R1234ze 29 = R455A 30 = R170
31 = R442A 32 = R447A 33 = R448A 34 = R449A 35 = R450A
36 = R452A 37 = R508B 38 = R452B 39 = R513A 40 = R454B
41 = R458A
A Valve: CAREL EXV - - - I 54 181
0= user defined 13= Sporlan SEH 175 26= CAREL ejector
E2J23AT1N0
1= CAREL EXV 14= Danfoss ETS 27= CAREL ejector
12.5-25B E3J26AT2N0
2= Alco EX4 15= Danfoss ETS 50B 28= CAREL ejector
E3J33AU2N0
3= Alco EX5 16= Danfoss ETS 100B 29= CAREL ejector
E3J39AV3N0
4= Alco EX6 17= Danfoss ETS 250 30= CAREL ejector
E6J50AV3N0
5= Alco EX7 18= Danfoss ETS 400 31= Danfoss CCMT 16
6= Alco EX8 330Hz 19= Two EXV CAREL 32= Danfoss CCMT 24
recommend CAREL connected together
7= Alco EX8 500Hz 20= Sporlan SER(I)G,J,K 33= Danfoss CCMT 30
specific Alco
8= Sporlan SEI 0.5-11 21= Danfoss CCM 34= Danfoss CCMT 42
10-20-30
9= Sporlan SER 1.5-20 22= Danfoss CCM 40 35= Danfoss Colibri
10= Sporlan SEI 30 23= Danfoss CCM T
2-4-8
11= Sporlan SEI 50 24= Disabled
12= Sporlan SEH 100 25= CAREL ejector
E2J17AS1N0
A Probe S1: Ratiometric: - - - I 16 143 CO
0= User defined; -1 to 9.3 barg
Ratiometric (OUT=0 to 5 V) Electronic (OUT=4 - 20 mA)
1= -1 to 4.2 barg 8= -0.5 to 7 barg
2=-0.4…9.3 barg 9= 0 to 10 barg
3= -1 to 9.3 barg 10= 0 to 18.2 bar
4= 0 to 17.3 barg 11= 0 to 25 barg
5= 0.85 to 34.2 barg 12= 0 to 30 barg
6= 0 to 34.5 barg 13= 0 to 44.8 barg
7= 0 to 45 barg 14= remote, -0.5 to 7 barg
15= remote, 0 to 10 barg
16= remote, 0 to 18.2 barg
17= remote, 0 to 25 barg
18= remote, 0 to 30 barg
19= remote, 0 to 44.8 barg
20= 4 to 20mA external signal
21= -1 to 12.8 barg
22= 0 to 20.7 barg
23= 1.86 to 43.0 barg
24= CAREL liquid level
25 = 0...60,0 barg
26 = 0...90,0 barg
27 = external signal 0…5 V
CAREL SVP
Modbus®
Type **
Parameter/description Def. Min. Max. UOM Note
user *
CAREL SVP
Modbus®
Type **
Parameter/description Def. Min. Max. UOM Note
user *
CAREL SVP
Modbus®
Type **
Parameter/description Def. Min. Max. UOM Note
user *
CAREL SVP
Modbus®
Type **
Parameter/description Def. Min. Max. UOM Note
user *
CONTROL
A Superheat set point 11 LowSH: 180 (324) K (°F) A 83 82 -
threshold
A Valve opening at start-up (evaporator/valve capacity ratio) 50 0 100 % I 60 187 -
C Valve open in standby 0 0 1 - D 36 35 -
(0= disabled= valve closed; 1=enabled = valve open according
to parameter “Valve position in stand-by”)
C Valve position in stand-by 0 0 100 % I 92 219 -
0 = 25%
1…100% = % opening
C start-up delay after defrost 10 0 60 min I 40 167 CO
A Pre-position time 6 0 18000 s I 87 214
A Hot gas bypass temperature set point 10 -85(-121) 200 (392) °C (°F) A 84 83 -
A Hot gas bypass pressure set point 3 -20 (-290) 200 (2900) barg (psig) A 85 84 -
A EPR pressure set point 3.5 -20 (-290) 200 (2900) barg (psig) A 86 85 -
C PID: proportional gain 15 0 800 - A 87 86 -
C PID: integral time 150 0 1000 s I 61 188 -
C PID: derivative time 5 0 800 s A 88 87 -
A LowSH protection: threshold 5 -40 (-72) SH set point K (°F) A 89 88 -
C LowSH protection: integral time 15 0 800 s A 90 89 -
A LOP protection: threshold -50 -85(-121) MOP protec- °C (°F) A 91 90 -
tion: threshold
C LOP protection: integral time 0 0 800 s A 92 91 -
A MOP protection: threshold 50 LOP protec- 200 (392) °C (°F) A 93 92 -
tion: threshold
C MOP protection: integral time 20 0 800 s A 94 93 -
A Enable manual valve positioning 0 0 1 - D 32 31 -
A Manual valve position 0 0 9999 step I 53 180 -
C Discharge superheat setpoint (CANNOT BE SELECTED) 35 -40(-72) 180 (324) K (F°) A 100 99
C Discharge temperature setpoint (CANNOT BE SELECTED) 105 -85(-121) 200 (392) °C (°F) A 101 100
C Liquid level perc. set point 50 0 100 % A 119 118 -
SPECIAL
A HiTcond: threshold - SELECT WITH PROG. CONT. 80 -85(-121) 200 (392) °C (°F) A 58 57 CO
C HiTcond: integral time - SELECT WITH PROG. CONT. 20 0 800 s A 57 56 CO
A Modulating thermostat: set point - SELECT WITH PROG. CONT. 0 -85(-121) 200 (392) °C (°F) A 61 60 CO
A Modulating thermostat: differential - SELECT WITH PROG. CONT. 0. 1 0.1 (0.2) 100 (180) °C (°F) A 60 59 CO
C Mod. thermostat: SH set point offset - SELECT WITH PROG. CONT. 0 0 (0) 100 (180) K (°F) A 59 58 CO
C Coefficient ‘A’ for CO2 control 3.3 -100 800 - A 95 94 -
C Coefficient ‘B’ for CO2 control -22.7 -100 800 - A 96 95 -
C Impostazioni di rete 2 0 30 - I 74 201 CO
Parity Bit di stop Baud rate
0 no parity 2 stop bits 4800 bps
1 no parity 2 stop bits 9600 bps
2 no parity 2 stop bits 19200 bps
4 no parity 1 stop bit 4800 bps
5 no parity 1 stop bit 9600 bps
6 no parity 1 stop bit 19200 bps
16 even 2 stop bits 4800 bps
17 even 2 stop bits 9600 bps
18 even 2 stop bits 19200 bps
20 even 1 stop bit 4800 bps
21 even 1 stop bit 9600 bps
22 even 1 stop bit 19200 bps
24 odd 2 stop bits 4800 bps
25 odd 2 stop bits 9600 bps
26 odd 2 stop bits 19200 bps
28 odd 1 stop bit 4800 bps
29 odd 1 stop bit 9600 bps
30 odd 1 stop bit 19200 bps
A Power supply mode 0 0 1 - D 47 46 CO
0= 24 Vac; 1= 24 Vdc
C Enable mode single on twin (parameter disabled) 0 0 1 - D 58 57 CO
0= Twin; 1= Single
C Stop manual positioning if net error 0 0 1 - D 59 58 CO
0 = Normal operation; 1 = Stop
C Programmable regulation configuration 0 0 32767 - I 101 228 -
C Programmable regulation input 0 0 32767 - I 102 229 -
C Programmable SH regulation options 0 0 32767 - I 103 230 -
C Programmable regulation set point 0 -800(-1233) 800(1233) - A 112 111 -
C CUSTOMIZED REFRIGERANT
Dew a high -288 -32768 32767 - I 107 234 CO
Dew a low -15818 -32768 32767 - I 108 235 CO
Dew b high -14829 -32768 32767 - I 109 236 CO
Dew b low 16804 -32768 32767 - I 110 237 CO
Dew c high -11664 -32768 32767 - I 111 238 CO
Dew c low 16416 -32768 32767 - I 112 239 CO
Dew d high -23322 -32768 32767 - I 113 240 CO
CAREL SVP
Modbus®
Type **
Parameter/description Def. Min. Max. UOM Note
user *
Probe S1 0 0 1 D 4 3 R
Probe S2 0 0 1 D 5 4 R
Probe S3 0 0 1 D 6 5 R
Probe S4 0 0 1 D 7 6 R
EEV motor error 0 0 1 D 8 7 R
Status of relay 0 0 1 D 9 8 R
LOP (low evaporation temperature) 0 0 1 D 10 9 R
ALARMS
Note: the readings of probes S1, S2, S3, S4 is always displayed, regardless
of whether or not the probe is connected
Note:
• to display the alarm queue, press the Help button and scroll using the
twin A B
twin A B UP/DOWN buttons. If at the end of the alarms for driver A/B the following
message is shown:
Alarms active on driver B/A
1. press Esc to return to the standard display;
Fig. 9.a 2. press the Help and Enter buttons together to move to the corresponding
driver;
Note:the alarm LED comes on to signal a mains power failure only if the 3. press Help to display the required alarm queue.
EVBAT*** module (accessory) has been connected, guaranteeing the power
required to close the valve. • the control alarms can be disabled by setting the corresponding delay to
zero.
The display shows both types of alarms, in two different modes:
system alarm: on the main page, the ALARM message is displayed, flashing.
Pressing the Help button displays the description of the alarm and, at the
top right, the total number of active alarms and the driver where the alarm
occurred (A / B). The same alarm may occur on both drivers (e.g. probe alarm)
Table of alarms
Type of alarm Cause of LED Display Relay Reset Effects on Checks/ solutions
the alarm control
Probe S1 Probe S1 faulty red alarm ALARM Depends on automatic Depends on Check the probe connections. Check
or exceeded set LED flashing configuration parameter “Probe the “Probe S1 alarm management”, &
alarm range parameter S1 alarm manage- “Pressure S1: MINIMUM & MAXIMUM
ment” alarm value” parameters
Probe S2 Probe S2 faulty red alarm ALARM Depends on automatic Depends on Check the probe connections. Check
or exceeded set LED flashing configuration parameter “Probe the “Probe S2 alarm management”, &
alarm range parameter S2 alarm manage- “Temperature S2: MINIMUM & MAXI-
ment” MUM alarm value” parameters
Probe S3 Probe S3 faulty red alarm ALARM Depends on automatic Depends on Check the probe connections. Check
or exceeded set LED flashing configuration parameter “Probe the “Probe S3 alarm management”, &
alarm range parameter S3 alarm manage- “Pressure S3: MINIMUM & MAXIMUM
ment” alarm value” parameters
Probe S4 Probe S4 faulty red alarm ALARM Depends on automatic Depends on Check the probe connections. Check
or exceeded set LED flashing configuration parameter “Probe the “Probe S4 alarm management”, &
alarm range parameter S4 alarm manage- “Temperature S4: MINIMUM & MAXI-
ment” MUM alarm value ”
LowSH (low LowSH protection - ALARM flashing Depends on automatic Protection action Check the “LowSH protection: th-
superheat) activated & LowSH configuration already active reshold & alarm delay” parameters
parameter
LOP (low evapora- LOP protection - ALARM flashing Depends on automatic Protection action Check the “Protection
tion temperature) activated & LOP configuration already active LOP: threshold & alarm delay” para-
parameter meters
MOP (high evapo- MOP protection - ALARM flashing Depends on automatic Protection action Check the “MOP protection: threshold
ration tempera- activated & MOP configuration already active & alarm delay” parameters
ture) parameter
Low suction Threshold and de- - ALARM Depends on automatic No effect Check the threshold and delay
temperature lay time exceeded flashing configuration parameters.
parameter
Fig. 12.d
Fig. 12.a
• go to Configure device: the list of parameters will be displayed, allowing
Then the user can choose to: the changes relating to the application to be made.
1. directly access the list of parameters for the EVD evolution twin saved
to EEPROM: select “tLAN”;
This is done in real time (ONLINE mode), at the top right set the network
address 198 and choose the guided recognition procedure for the USB
communication port. Enter at the Service or Manufacturer level.
Fig. 12.e
Fig. 12.f
Note: the program On-line help can be accessed by pressing F1.
12.5 Updatingthecontrolleranddisplayfirmware
The controller and display firmware must be updated using the VPM program
on a computer and the USB/tLAN converter, which is connected to the device
being programmed (see paragraph 2.7 for the connection diagram). The
firmware can be downloaded from http://ksa.carel.com. See the VPM On-line
help.
COM 1
NO 1
G0
G
1 3 2 4
Power Supply E X V connection Relay • pressure probe S1 in the diagram is ratiometric. See the general connection
diagram for the other electronic probes, 4 to 20 mA or combined;
• four probes are needed for superheat control with BLDC compressors, two
to measure the superheat and two to measure the discharge superheat
EVD evolution
and the discharge temperature.
DI1
DI2
S1
S2
S3
S4
GND Tx/Rx
Main control Multiplexed
… showcase/
Fig. 13.a 19 =air-conditioner/chiller with BLDC compressor cold room
20 = superheat control with 2 temperature probes
13.3 Connection diagram - superheat control Auxiliary control Disabled
1 = Disabled
EVD Evolution Twin works as a single valve driver (on driver A). 2 = High condensing temperature protection on S3
3 = Modulating thermostat on S4
CAREL EXV 4 = Backup probes on S3 and S4
VALVE A
5, 6, 7= reserved
8 = Subcooling measurement
9 = Reverse high condensing temperature protection on S3
Probe S3 Ratiometric:
4 14 15 … -1 to 9.3 barg
S
1 A 20 = external signal (4 to 20 mA) (CANNOT BE SELECTED)
2
3 Variable 1/2 on the display Superheat
shield
…
13
11 = Modulating thermostat temperature
S1 probe alarm management Valve in fixed
COMA
NOA
VBAT
G0
1 3 2 4
G
… position
Use backup probe S3
COMB
NOB
1 3 2 4
S2 probe alarm management Valve in fixed
EVD NET
evolution
… position
230 Vac 24 Vac OPEN A OPEN B
Use backup probe S4
2 AT CLOSE A CLOSE B Auxiliary refrigerant 0
35 VA
twin
G0
G
TRADRFE240 A B
0 = same as main control;
1= R22 2= R134a 3= R404A
5
Analog - Digital Input Network
4= R407C 5= R410A 6= R507A
7= R290 8= R600 9= R600a
VREF
GND
DI1
DI2
S1
S4
S2
S3
GND Tx/Rx
10= R717 11= R744 12= R728
EVDCNV00E0
13= R1270 14= R417A 15= R422D
EVD4 service USB adapter 16= R413A 17= R422A 18= R423A
4
EEV driver
Fig. 13.c There are four possible cases of digital input configurations with primary or
secondary functions.
shield
C
V M
Modbus®
E RS485
EV
PA TA
L
EVD
GND
pCO
evolution
F
shield
CP
S2
S4
Fig. 13.d
Legenda:
S
CP Compressor V Solenoid valve
C Condenser S Liquid gauge
L Liquid receiver EV Electronic valve V M
F Dewatering filter E Evaporator
TA,TB Temperature probes PA, PB Pressure probes
EV
For information on the wiring see paragraph “General connection diagram”.
To optimise performance of the refrigerant circuit, compressor operation T E
must always be inside a specific area, called the envelope, defined by the
compressor manufacturer. T
Inviluppo ⁄ Envelope
Fig. 13.f
Key:
CP Compressor V Solenoid valve
C Condenser S Liquid gauge
Temperatura di condensazione (C°)
T Temperature probe
ON t
MOP
HITCond protection (high condensing temperature) OFF
The functional diagram is shown below.
ON t
C PID
OFF
L ON
t
P ALARM
EVD OFF
evolution
F
CP D t
S1
S2
S3
S Fig. 13.h
Key:
M T_COND Condensing temperature T_COND_TH HiTcond: threshold
E HiTcond High Tcond protection status HiTcond ALARM Alarm
PID PID superheat control t Time
V EEV
P T D Alarm timeout
Note:
Fig. 13.g • the High Tcond threshold must be greater than the rated condensing
temperature of the unit and lower then the calibration of the high pressure
Key: switch;
CP Compressor EEV Electronic expansion valve
• the closing of the valve will be limited if this causes an excessive decrease
C Condenser V Solenoid valve in the evaporation temperature.
L Liquid receiver E Evaporator
F Dewatering filter P Pressure probe (transducer)
S Liquid indicator T Temperature probe Modulating thermostat
This function is used, by connecting a temperature probe to input S4, to
For the wiring, see paragraph “General connection diagram”. modulate the opening of the electronic valve so as to limit the lowering of
the temperature read and consequently reach the control set point. This is
As already mentioned, the HITCond protection can only be enabled if the useful in applications such as the multiplexed cabinets to avoid the typical
controller measures the condensing pressure/temperature, and responds swings in air temperature due to the ON/OFF control (thermostatic) of the
moderately by closing the valve in the event where the condensing solenoid valve. A temperature probe must be connected to input S4, located
temperature reaches excessive values, to prevent the compressor from in a similar position to the one used for the traditional temperature control
shutting down due to high pressure. The condensing pressure probe must be of the cabinet. In practice, the close the controlled temperature gets to the
connected to input S3. set point, the more the control function decreases the cooling capacity of
the evaporator by closing the expansion valve. By correctly setting the related
Parameter/description Def. Min. Max. UOM parameters (see below), a very stable cabinet temperature can be achieved
ADVANCED around the set point, without ever closing the solenoid valve. The function is
High Tcond threshold 80 -60 (-76) 200 (392) °C (°F) defined by three parameters: set point, differential and offset.
High Tcond integration time 20 0 800 s
ALARM CONFIGURATION Parameter/description Def. Min. Max. UOM
High condensing temperature alarm 600 0 18000 s ADVANCED
timeout (High Tcond) Modul. thermost setpoint 0 -60 (-76) 200 °C (°F)
(0= alarm DISABLED) (392)
Tab. 13.j Modul. thermost differential 0.1 0.1 (0.2) 100 °C (°F)
(180)
The integration time is set automatically based on the type of main control. Modul. thermost SHset offset (0= fun- 0 0 (0) 100 K (°R)
ction disabled) (180)
Note:
Tab. 13.k
• the protector is very useful in units with compressors on board if the air-
cooled condenser is undersized or dirty/malfunctioning in the more critical The first two should have values similar to those set on the controller for the
operating conditions (high outside temperature); cabinet or utility whose temperature is being modulated.
• the protector has no purpose in multiplexed systems (showcases), where The offset, on the other hand, defines the intensity in closing the valve as
the condensing pressure is maintained constant and the status of the the temperature decreases: the greater the offset, the more the valve will be
individual electronic valves does not affect the pressure value. modulated. The function is only active in a temperature band between the set
point and the set point plus the differential.
To reduce the condensing temperature, the output of the refrigeration
unit needs to be decreased. This can be done by controlled closing of the
electronic valve, implying superheat is no longer controlled, and an increase in Important: the “Modulating thermostat” function should not be used
the superheat temperature. The protector will thus have a moderate reaction on stand-alone refrigeration units, but only in centralised systems. In fact, in
that tends to limit the increase in the condensing temperature, keeping the former case closing the valve would cause a lowering of the pressure and
it below the activation threshold while trying to stop the superheat from consequently shut down the compressor.
increasing as much as possible. Normal operating conditions will not resume
based on the activation of the protector, but rather on the reduction in the
outside temperature. The system will therefore remain in the best operating
conditions (a little below the threshold) until the environmental conditions
61 “EVD Evolution TWIN” +0300006EN - rel. 2.10 - 24.01.2024
ENG
Examples of operation: Backup probes on S3 & S4
S4 Important: this type of control is compatible with the “main control”
set point + diff parameter setting between 1 and 18.
set point In this case, pressure probe S3 and temperature probe S4 will be used to
1. offset too low (or function
t replace probes S1 and S2 respectively in the event of faults on one or both, so
disabled) ON as to guarantee a high level of reliability of the controlled unit.
SV
OFF
t C
S4 L
set point + diff
EVD
set point
evolution
t F
2. offset too high CP
S1
S2
S3
S4
ON
SV S
OFF
t
M
S4 E
set point + diff V EEV
P T P T
set point
t
3. offset correct
ON Fig. 13.k
SV Key:
OFF
t CP Compressor EEV Electronic expansion valve
C Condenser V Solenoid valve
L Liquid receiver E Evaporator
Fig. 13.i
F Dewatering filter P Pressure probe (transducer)
S Liquid indicator T Temperature probe
Key:
diff= differential For the wiring, see paragraph “General connection diagram”.
SV= solenoid valve (showcase temperature control)
S4= temperature
Subcooling measurement
C This function measures subcooling using a pressure probe and a temperature
probe connected to inputs S3 and S4 respectively. The reading can be sent to
a controller connected in the serial network (e.g. pCO).
C
L
EVD TB PB
evolution
F L
CP
S1
S2
S4
S
CP
F EVD
evolution
M
S S1 S2 S3 S4
T E
V EEV
P T
V M
A subcooling value that is too high, for example above 20 K, when not required A CP1
by the application may indicate excessive refrigerant charge in the circuit, and F1
can cause unusually high condensing pressure values with a consequent
decline in circuit cooling efficiency and possible compressor shutdown due
EVD
to the high pressure switch tripping. S1 evolution
S1 S2 S3 S4
M
V
Reverse high condensing temperature protection
(HiTcond) on S3 EEV
The aim of reverse HiTcond protection is to limit the condensing pressure in CHE
the refrigerant circuit by opening the valve rather than closing it. This function
is recommended, rather than the HiTcond protection function described P1 T1
previously, in refrigerant circuits without a liquid receiver and where the
condenser is smaller than the evaporator (e.g. air-to-water heat pumps). In P2
this case, in fact, closing the valve would obstruct the flow of refrigerant to the
L2
condenser that, lacking sufficient volume for the refrigerant to accumulate,
would cause an increase in condensing pressure. This function is especially B CP2
useful for condensers in CO2 cascade systems. See the chapter on Protectors. F2
C
S2
T V2 E
P V1 M
F
EVD CP Fig. 13.n
evolution
S
S3
S1
S2
Key:
CP1/2 Compressor 1/2 EEV Electronic expansion valve
CHE Cascade heat exchanger C Condenser
L1/2 Liquid receiver 1/2 V Solenoid valve
V M F1/2 Filter-drier 1/2 E Evaporator
S1/2 Liquid gauge 1/2 P1/2 Pressure probe (transducer)
T1 Temperature probe V2 Thermostatic expansion valve
EEV E
P T
For the wiring, see paragraph 2.11 “General connection diagram”
The driver controls refrigerant superheat in the primary circuit (A), and at the
Fig. 13.m same time measures the refrigerant condensing pressure in the secondary
Key:
circuit (B). When the condensing temperature exceeds the HiTCond protection
CP Compressor EEV Electronic expansion valve threshold, normal superheat control is overridden by forced opening of
C Condenser V Solenoid valve the valve, at a rate that is inversely proportional to the HiTCond protection
F Filter-drier E Evaporator integral time. Opening the EEV lowers the superheat in the primary circuit,
S Liquid gauge P Pressure probe (transducer) which increases the heat exchange coefficient and consequently reduces the
T Temperature probe condensing pressure in the secondary circuit.
For the wiring, see paragraph “General connection diagram”
The reverse HiTcond threshold for CO2 cascade applications should be set in
relation to the expected evaporation temperature in the primary circuit. The
Important: opening the valve will probably also cause activation of threshold must be set to a value that is at least 3-5°C higher than the minimum
the low superheat protection LowSH, which tends to limit the opening of evaporation temperature in the primary circuit. Lower values make achieving
the valve. The ratio between the integral times of these two concurrent yet the set pressure limit incompatible with heat exchange efficiency. In addition,
opposing protectors determines how effective one is compared to the other. swings in operation may occur due the attempt to limit low superheat in the
primary circuit and the pressure in the secondary circuit at the same time.
Agenzia / Agency: