+0300005EN
+0300005EN
+0300005EN
User manual
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
ENG
WARNINGS DISPOSAL
All of the above suggestions likewise apply to the controllers, serial boards,
programming keys or any other accessory in the CAREL product portfolio.
CAREL adopts a policy of continual development. Consequently, CAREL
reserves the right to make changes and improvements to any product
described in this document without prior warning.
The technical specifications shown in the manual may be changed without
prior warning.
The liability of CAREL in relation to its products is specified in the CAREL general
contract conditions, available on the website www.carel.com and/or by
specific agreements with customers; specifically, to the extent where allowed
by applicable legislation, in no case will CAREL, its employees or subsidiaries
be liable for any lost earnings or sales, losses of data and information, costs of
replacement goods or services, damage to things or people, downtime or any
direct, indirect, incidental, actual, punitive, exemplary, special or consequential
damage of any kind whatsoever, whether contractual, extra-contractual or
due to negligence, or any other liabilities deriving from the installation, use or
impossibility to use the product, even if CAREL or its subsidiaries are warned
of the possibility of such damage.
5. CONTROL 20
5.1 Main and auxiliary control ........................................................................20
5.2 Superheat control ..........................................................................................20
5.3 Control with Emerson Climate Digital Scroll™ compressor .......21
5.4 BLDC Control with compressor............................................................22
5.5 Superheat regulation with 2 temperature probes ....................22
5.6 Advanced regulation ...................................................................................23
5.7 Programmable control................................................................................25
5.8 Control with refrigerant level sensor..................................................27
5.9 Auxiliary control .............................................................................................27
6. FUNCTIONS 30
6.1 Power supply mode .....................................................................................30
6.2 Battery charge delay ....................................................................................30
6.3 Network connection ....................................................................................30
6.4 Inputs and outputs .......................................................................................30
6.5 Control status ..................................................................................................32
6.6 Advanced control status............................................................................34
6.7 Quick probe alarm disabling ...................................................................34
7. PROTECTORS 35
7.1 Protectors ............................................................................................................35
Fig. 1.h
Fig. 1.d
“EVD evolution” +0300005EN - rel. 4.2 - 24.01.2024 8
ENG
2. INSTALLATION
2.1 DIN rail assembly and dimensions 2.3 Connection diagram - superheat control
EVD evolution is supplied with screen-printed connectors to simplify
wiring.
CAREL EXV
VBAT
COM 1
NO 1
G0
G
1 3 2 4
4
2 12 13
EVD evolution
3 S
110 45 1 shield
11
230 Vac 24 Vac
2 AT
COMA
NOA
20VA(*) 1 2 4
G0
3
G0
VBAT
G
G
Analog – Digital Input Network
V REF
GND
DI1
DI2
5
S1
S2
S3
S4
GND Tx/Rx
NET
70 60 EVDCNV00E0
Fig. 2.a OPEN
EVD4 service USB adapter
CLOSE
4
EVD4
PC
EEV driver
7
6
2.2 Description of the terminals
VREF
GND
DI1
DI2
S1
S4
S2
S3
GND Tx/Rx
1 3 2 4
G
G0
VBAT
NO A
COM A
EVD evolution
8 9 10
aa Fig. 2.c
Key:
1 green
2 yellow
3 brown
Analog – Digital Input Network 4 white
5 personal computer for configuration
V REF
GND
DI1
DI2
S1
S2
S3
S4
GND Tx/Rx
6 USB/tLAN converter
7 adapter
b 8 ratiometric pressure transducer - evaporation pressure
9 NTC suction temperature
Fig. 2.b 10 digital input 1 configured to enable control
11 free contact (up to 230 Vac)
Terminal Description 12 solenoid valve
G, G0 Power supply 13 alarm signal
VBAT Emergency power supply
Functional earth
Note:
1,3,2,4 Stepper motor power supply
COM1, NO1 Alarm relay
• connect the valve cable shield to the electrical panel earth;
GND Earth for the signals • the use of the driver for the superheat control requires the use of the
VREF Power to active probes evaporation pressure probe S1 and the suction temperature probe S2,
S1 Probe 1 (pressure) or 4 to 20 mA external signal which will be fitted after the evaporator, and digital input 1/2 to enable
S2 Probe 2 (temperature) or 0 to 10 V external signal control. As an alternative to digital input 1/2, control can be enabled
S3 Probe 3 (pressure)
via remote signal (tLAN, pLAN, RS485/Modbus®). For the positioning of
S4 Probe 4 (temperature)
DI1 Digital input 1 the probes relating to other applications, see the chapter on “Control”;
DI2 Digital input 2 • inputs S1, S2 are programmable and the connection to the terminals
Terminal for tLAN, pLAN, RS485, Modbus® connection depends on the setting of the parameters. See the chapters on
Terminal for tLAN, pLAN, RS485, Modbus® connection “Commissioning” and “Functions”;
Terminal for pLAN, RS485, Modbus® connection • pressure probe S1 in the diagram is ratiometric. See the general
aa service serial port (remove the cover to access ) connection diagram for the other electronic probes, 4 to 20 mA or
b serial port combined;
Tab. 2.a • four probes are needed for superheat control with BLDC compressors,
two to measure the superheat and two to measure the discharge
superheat and the discharge temperature. See chap. 5.
1
3
2
4
COMA
NOA
G
G0
VBAT
1
3
COMA
2
4
NOA
G
G0
VBAT
motor error” alarm: see paragraph 9.5;
4. carefully evaluate the maximum capacity of the relay output specified
in the chapter “Technical specifications”;
5. if necessary use a class 2 safety transformer, suitably protected pCO
against short-circuits and voltage surges. For the power ratings see
the general connection diagram and the technical specifications.
6. the minimum size of the connection cables must be 0.5 mm2 Fig. 2.g
7. power up the driver in the event of 24 Vdc power supply the drive
will close the valve.
Important: in the event of 24 Vdc power supply set the “Power supply Installation environment
mode” parameter=1 to start control. See par. 6.1.
8. program the driver, if necessary: see the chapter “User interface”; Important: avoid installing the driver in environments with the
9. connect the serial network, if featured: follow to the diagrams below following characteristics:
for the earth connection. • relative humidity greater than the 90% or condensing;
• strong vibrations or knocks;
Drivers in a serial network • exposure to continuous water sprays;
Case 1: multiple drivers connected in a network powered by the same
• exposure to aggressive and polluting atmospheres (e.g.: sulphur
transformer. Typical application for a series of drivers inside the same
and ammonia fumes, saline mist, smoke) to avoid corrosion and/or
electrical panel.
oxidation;
• strong magnetic and/or radio frequency interference (avoid installing
230 Vac
the appliances near transmitting antennae);
24 Vac • exposure of the driver to direct sunlight and to the elements in general.
2 AT 2 AT 2 AT
1
3
2
4
COMA
NOA
G
G0
VBAT
G
G0
VBAT
G
G0
VBAT
1
3
2
4
COMA
NOA
must be observed:
pCO • if the driver is used in a way not specified in this manual, the level of
protection is not guaranteed.
• incorrect connection to the power supply may seriously damage the
Fig. 2.d driver;
• use cable ends suitable for the corresponding terminals. Loosen each
screw and insert the cable ends, then tighten the screws and lightly
Case 2: multiple drivers connected in a network powered by different tug the cables to check correct tightness;
transformers (G0 not connected to earth). Typical application for a series • separate as much as possible (at least 3 cm) the probe and digital
of drivers in different electrical panels. input cables from the power cables to the loads so as to avoid possible
electromagnetic disturbance. Never lay power cables and probe cables
in the same conduits (including those in the electrical panels);
230 Vac 230 Vac 230 Vac
• install the shielded valve motor cables in the probe conduits: use
24 Vac 24 Vac
24 Vac
2 AT 2 AT 2 AT
shielded valve motor cables to avoid electromagnetic disturbance to
the probe cables;
1
3
2
4
COMA
NOA
G
G0
VBAT
1
3
2
4
COMA
NOA
G
G0
VBAT
1
3
2
4
COMA
NOA
G
G0
VBAT
1
3
2
4
COMA
NOA
G
G0
pCO
Fig. 2.f
Important: earthing G0 and G on a driver connected to a serial
network will cause permanent damage to the driver.
VBAT
G0
G
(“Two EXV connected together”) and connect the valve motor power
supply wires to the same connector. In the example shown below, for EVD Battery module
EVBAT00400
operation of valve B_2 with valve B_1 in complementary mode simply 4 AT
BAT ERR
swap the connection of wires 1 and 3.
GND
+
-
2 CAREL valves connected in parallel 2 CAREL valves connected in comple-
mode mentary mode
VBAT
G0
G
VALVE A_1 VALVE B_1
4 4
2 2
3
EVD evolution
3
1 1
GND
CAREL ExV CAREL ExV
DI1
DI2
VALVE A_2 VALVE B_2
4 4
2 2 230 Vac 24 Vac
3 1
1 3 35 VA
2 AT
TRADRFE240
1 3 2 4 1 3 2 4
Fig. 2.j
Fig. 2.h
Note: set the “Battery charge delay” parameter, depending on the
Note: operation in parallel and complementary mode can only be application. See the chapter “Functions”.
used for CAREL valves, within the limits shown in the table below, where
OK means that the valve can be used with all refrigerants at the rated
operating pressure. 2.8 Connecting the USB-tLAN converter
CAREL valve model Procedure:
E2V* E3V* E4V* E5V* E6V* E7V* • remove the LED board cover by pressing on the fastening points;
Two EXVs OK E3V45, E4V85, NO NO NO • plug the adapter into the service serial port;
con- MOPD = 35 bars MOPD = 22 bars
nected E3V55, E4V95,
• connect the adapter to the converter and then this in turn to the
together MOPD = 26 bars MOPD = 15 bars computer.
E3V65, • power up the driver.
MOPD = 20 bars
press
Note:
• MOPD = Maximum Operating-Pressure Differential EVD evo
luti on
• The two CAREL ExV valves must be the same model (e.g. 2x E2V, 2x
OPEN
CLOSE
E3V, 2x E4V).
press
1 3 2 4
G0
VBAT
G
“remote” option for the other drivers, up to the fifth. EVD evolution6 must EVDCNV00E0
OPEN
2
CLOSE
4
EVD4
PC
EEV driver
EXAMPLE 3
EVD Evolution1 to EVD Evolution5 EVD Evolution6
VREF
GND
DI1
DI2
S1
Probe S1 -0.5 to 7 barg (P1) to remote, -0.5 to 7 barg -0.5 to 7 barg (P2)
S4
S2
S3
GND Tx/Rx
VREF
VREF
GND
GND
GND
DI1
DI1
DI2
DI2
DI1
DI2
S1
S1
S4
S4
S2
S2
S1
S3
S3
S4
S2
S3
Note: when using the service serial port connection, the VPM
P1 P2
program can be used to configure the driver and update the driver and
display firmware, downloadable from http://ksa.carel.com.
Fig. 2.i
See the appendix.
Key: P1 Shared pressure probe
P2 Pressure probe
COMA
NOA
1 3 2 4
G0
VBAT
G
NET 1
OPEN
CLOSE
2
VREF
GND
DI1
DI2
S1
S4
S2
S3
GND Tx/Rx
shield
Fig. 2.m
Note:
• the serial port can be used for configuration with the VPM program and
for updating the driver firmware, downloadable from http://ksa.carel.
com;
• to save time, up to 8 EVD evolution drivers can be connected to the
computer, updating the firmware at the same time (each driver must
have a different network address).
UPLOAD
DOWNLOAD
RESET
Fig. 2.n
Important:
• the procedure must be carried out with driver powered;
• DO NOT remove the display from the driver during the UPLOAD,
DOWNLOAD, RESET procedure;
• the parameters cannot be downloaded if the source driver and the
target driver have incompatible firmware.
CASE 1: CASE 3:
230 Vac power supply with emergency module 24 Vdc power supply
CAREL EXV
H G
Sporlan DANFOSS ALCO
2 G0
VBAT
EVD0000UC0
G0
G
G G0
11
with battery
35 VA
TRADRFE240
13
COMA
NOA
A
1 3 2 4
G0
VBAT
G
230 Vac 24 Vac
EVD evolution
Tx/Rx
GND
without battery
2 AT pCO
20 VA (*)
G0
G
shield
CASE 2:
GND
230 Vac power pCO
GND
EVD4
DI1
DI2
PC
EEV driver
S1
module
S4
S2
S3
GND Tx/Rx
GND
7 pCO
5 6 Modbus®
RS485
shield
EVD0000E0*: tLAN version
EVD0000E1*: pLAN version 16
17
EVD0000E2*: RS485 version
CVSTDUM0R0
8 9 10
B C E VREF
GND
DI1
VREF
VREF
DI2
GND
GND
S1
S4
S2
DI1
DI1
S3
DI2
DI2
GND Tx/Rx
S1
S1
S4
S4
S2
S2
S3
S3
3 4 1 4
15 14
D
G L
VREF
VREF
VREF
F
GND
GND
GND
DI1
DI1
DI1
DI2
DI2
DI2
S1
S1
S1
S4
S4
S4
S2
S2
S2
S3
S3
S3
1
1 2
4 14
15
Fig. 2.o
Key:
1 green 10 digital input 1 configured to enable A Connection to EVD0000UC0
2 yellow control B Connection to electronic pressure probe (SPK**0000) or piezoresistive
3 brown 11 free contact (up to 230 Vac) pressure transducer (SPKT00**C0)
4 white 12 solenoid valve C Connection as positioner (0 to 10 Vdc input)
5 configuration computer 13 alarm signal D Connection as positioner (4 to 20 mA input)
6 USB/tLAN converter 14 red E Connection to combined pressure/temperature probe (SPKP00**T0)
7 adapter 15 black F Connection to backup probes (S3, S4)
8 ratiometric pressure transducer 16 configuration/supervision computer G Ratiometric pressure transducer connections (SPKT00**R0)
9 NTC probe H Connections o other types of valves
L Connection to float level sensor (P/N LSR00*3000)
Note: for the configuration of the digital inputs see par. 6.3. The maximum length of the connection cable to the EVD0000UC0 modu-
1 le is 5 m.
(*): in combination with Alco EX7 or EX8 valves, use a 35 VA transformer code The connection cable to the valve motor must be 4-wire shielded, AWG
TRADRFE240. 2 22 with Lmax= 10 m, AWG 14 con Lmax= 50 m
VBAT
COM 1
NO 1
G0
G
1 3 2 4
3
Analog – Digital Input Network
V REF
GND
Fig. 3.c
DI1
DI2
S1
S2
S3
S4
GND Tx/Rx
Key:
Fig. 3.a 1 1st variable displayed
Key: 2 2nd variable displayed
LED ON OFF Flashing 3 relay status
NET Connection available No connection Communication error 4 alarm (press “HELP”)
OPEN Opening valve - Driver disabled (*) 5 protector activated
CLOSE Closing valve - Driver disabled (*) 6 control status
Active alarm - - 7 adaptive control in progress
Driver powered Driver not powered Wrong power supply Display writings
(see chap. Alarms) Control status Protection active
Tab. 3.a ON Operation LowSH Low superheat
(*) Awaiting completion of the initial configuration OFF Standby LOP Low evaporation
temperature
POS Positioning MOP High evaporation
temperature
WAIT Wait HiTcond High condensing
3.1 Assembling the display board temperature
(accessory) CLOSE
INIT
Closing
Valve motor error
The display board, once installed, is used to perform all the configuration recognition procedure (*)
and programming operations on the driver. It displays the operating TUN Tuning in progress
status, the significant values for the type of control that the driver Tab. 3.b
is performing (e.g. superheat control), the alarms, the status of the
digital inputs and the relay output. Finally, it can save the configuration (*) The valve motor error recognition procedure can be disabled. See
parameters for one driver and transfer them to a second driver (see the paragraph 9.5
procedure for upload and download parameters).
For installation: Keypad
• remove the cover, pressing on the fastening points; Button Function
• fit the display board, as shown; Prg opens the screen for entering the password to access programming
mode.
• the display will come on, and if the driver is being commissioned, the • if in alarm status, displays the alarm queue;
guided configuration procedure will start. • in the “Manufacturer” level, when scrolling the parameters, shows
the explanation screens (Help).
press Esc • exits the Programming (Service/Manufacturer) and Display
modes;
• after setting a parameter, exits without saving the changes.
• navigates the display screens;
• increases/decreases the value.
UP/
DOWN
• switches from the display to parameter programming mode;
• confirms the value and returns to the list of parameters.
Enter
Tab. 3.c
Note: the variables displayed as standard can be selected by
press configuring the parameters “Display main var. 1” and “Display main var. 2”
Fig. 3.b accordingly. See the list of parameters.
CONFIGURATION
3.4 Programming mode (display) PROBES
CONTROL
The parameters can be modified using the front keypad. Access differs SPECIAL
according to the user level: Service (Installer) and manufacturer. ALARM CONFIGURATION
VALVE
Modifying the Service parameters
IThe Service parameters, as well as the parameters for commissioning
the driver, also include those for the configuration of the inputs, the relay Fig. 3.f
output, the superheat set point or the type of control in general, and the
protection thresholds. See the table of parameters.
Procedure: Note:
1. press Esc one or more times to switch to the standard display; • all the driver parameters can be modified by entering the Manufacturer
2. press Prg: the display shows a screen with the PASSWORD request; level;
3. press ENTER and enter the password for the Service level: 22, • if when setting a parameter the value entered is out-of-range, this is
starting from the right-most figure and confirming each figure with not accepted and the parameter soon after returns to the previous
ENTER; value;
4. if the value entered is correct, the first modifiable parameter is • if no button is pressed, after 5 min the display automatically returns to
displayed, network address; the standard mode.
5. press UP/DOWN to select the parameter to be set;
6. press ENTER to move to the value of the parameter;
7. press UP/DOWN to modify the value;
8. press ENTER to save the new value of the parameter;
9. repeat steps 5, 6, 7, 8 to modify the other parameters;
10. press Esc to exit the procedure for modifying the Service parameters.
PASSWORD
0001
Fig. 3.e
Note:
• if when setting a parameter the value entered is out-of-range, this is
not accepted and the parameter soon after returns to the previous
value;
• if no button is pressed, after 5 min the display automatically returns to
the standard mode;
• to set a negative value move to the left-most digit and press Up/Down.
4.1 Commissioning
pGD pGD C OK
Once the electrical connections have been completed (see the chapter
on installation) and the power supply has been connected, the operations 3
required for commissioning the driver depend on the type of interface 1 3 2 4
VB AT
G
G0
1 3 2 4 1 3 2 4
VB AT
VB AT
NO 1
G
G
G0
G0
COM 1
1 3 2 4
VB AT
NO 1
NO 1
G
G0
COM 1
COM 1
NO 1
COM 1
Pow er Supply E X V conne ction R elay Pow er Supply E V conne ction
X
R elay Pow er Supply E V conne ction
X
R elay Pow er Supply E X V conne ction R elay
V REF
GND
V REF
V REF
DI1
DI2
GND
GND
V REF
• DISPLAY: after having correctly configured the setup parameters,
S1
S2
S3
S4
DI1
DI2
DI1
DI2
GND
GND Tx/Rx
S1
S2
S3
S4
S1
S2
S3
S4
DI1
DI2
GND Tx/Rx GND Tx/Rx
S1
S2
S3
S4
GND Tx/Rx
GND
CANL
CANH
GND
CANL
CANH
controller via LAN or when digital input DI1/DI2 closes. See paragraph
4.2;
• VPM: to enable control of the driver via VPM, set “Enable EVD control” pCO
to 1; this is included in the safety parameters, in the special parameters
menu, under the corresponding access level. However, the setup
ADDR = 1 ADDR = 2 A
parameters should first be set in the related menu. The driver will then
be enabled for operation and control will be able to commence when
requested by the pCO controller via LAN or when digital input DI1/
+5 V REF
+Vterm
+5 V REF
+Vterm
GND
DI2 closes. If due to error or for any other reason “Enable EVD control”
GND
G0
U1
U2
U3
G
G0
U1
U2
U3
G
should be set to 0 (zero), the driver will immediately stop control and pCO pCO
will remain in standby until re-enabled, with the valve stopped in the
1
last position; Fig. 4.a
• SUPERVISOR: to simplify the commissioning of a considerable number
of drivers using the supervisor, the setup operation on the display can
be limited to simply setting the network address. The display will then Important: if the addresses are not assigned in this way, as for
be able to be removed and the configuration procedure postponed to a example shown in the following figure, malfunctions will occur if one of
later stage using the supervisor or, if necessary, reconnecting the display. the pCO controllers is offline.
To enable control of the driver via supervisor, set “Enable EVD control”;
this is included in the safety parameters, in the special parameters menu, ADDR = 31 ADDR = 32
NO
under the corresponding access level. However, the setup parameters
should first be set in the related menu. The driver will then be enabled pGD pGD C
for operation and control will be able to commence when requested
by the pCO controller via pLAN or when digital input DI1/DI2 closes.
As highlighted on the supervisor, inside of the yellow information field 3
relating to the “Enable EVD control” parameter, if due to error or for 1 3 2 4
VB AT
G
G0
1 3 2 4 1 3 2 4
VB AT
VB AT
NO 1
G
G
G0
G0
COM 1
1 3 2 4
VB AT
NO 1
NO 1
G
G0
COM 1
COM 1
NO 1
COM 1
Pow er Supply E X V conne ction R elay Pow er Supply E X V conne ction R elay Pow er Supply E X V conne ction R elay Pow er Supply E X V conne ction R elay
any other reason “Enable EVD control” should be set to 0 (zero), the
B
ADDR = 9 ADDR=17 ADDR=10 ADDR=18
driver will immediately stop control and will remain in standby until
re-enabled, with the valve stopped in the last position; Anal og – Digita l Input Netw or k Anal og – Digita l Input Netw or k Anal og – Digita l Input Netw or k Anal og – Digita l Input Netw or k
V REF
GND
V REF
V REF
DI1
DI2
GND
GND
V REF
S1
S2
S3
S4
DI1
DI2
DI1
DI2
GND
GND Tx/Rx
S1
S2
S3
S4
S1
S2
S3
S4
DI1
DI2
S2
S3
S4
GND Tx/Rx
• pCO PROGRAMMABLE CONTROLLER: the first operation to be EVD EVD EVD EVD
performed, if necessary, is to set the network address using the display.
2
Important: for the driver with pLAN serial port, see the
GND
CANL
CANH
GND
CANL
CANH
pCO
If a pLAN, tLAN or RS485/Modbus® driver is used, connected to a pCO
family controller, the setup parameters will not need to be set and ADDR = 1 ADDR = 2 A
confirmed. In fact, the application running on the pCO will manage the
correct values based on the unit controlled. Consequently, simply set the
pLAN, tLAN or RS485/Modbus® address for the driver as required by the
application on the pCO, and after a few seconds communication will
+5 V REF
+Vterm
+5 V REF
+Vterm
GND
GND
G0
U1
U2
U3
G
G0
U1
U2
U3
G
commence between the two instruments and the driver automatically pCO pCO
be enabled for control. The main screen will shown on the display, which Fig. 4.b
can then be removed, and control will be able to commence when
requested by the pCO controller or digital input DI1/DI2. If there is no
communication between the pCO and the driver (see the paragraph
“LAN error alarm”), the driver will be able to continue control based on
the status of digital input DI1/DI2. See par. 6.3.
TxRx
GND
brown
S1
S4
S2
S3
yellow
TEMP S2 white = R407H; 43 = R454A; 44 = R454C; 45 = R470A; 46 = R515B; 47 = R466A
white
Tab. 4.e
G0
VBAT
NO1
PRESS S1
4
COM1
G
black
1
3
green
Note:
• for CO2 cascade systems, at the end of the commissioning procedure
check that the electrical connections are correct; also set the auxiliary refrigerant. See the following paragraph.
if the configuration is correct
• if the refrigerant is not among those available for the “Refrigerant”
Configurtion
exit the procedure, otherwise parameter:
End configuration?
YES NO
choose NO and return to step 2; 1. set any refrigerant (e.g. R404);
2. select the model of valve, the pressure probe S1, the type of main
control and end the commissioning procedure;
3. enter programming mode and set the type of refrigerant: custom,
and the parameters “Dew a…f high/low” and “Bubble a…f high/
At the end of the configuration procedure the controller activates the low” that define the refrigerant;
valve motor error recognition procedure, showing “INIT” on the display. 4. start control, for example by closing the digital input contact to
See paragraph 9.5 enable operation.
To simplify commissioning and avoid possible malfunctions, the driver
will not start until the following have been configured:
1. network address; Valve
2. refrigerant; Setting the type of valve automatically defines all the control parameters
3. valve; based on the manufacturer’s data for each model.
4. pressure probe S1; In Manufacturer programming mode, the control parameters can then
5. type of main control, that is, the type of unit the superheat control be fully customised if the valve used is not in the standard list. In this case,
is applied to. the driver will detect the modification and indicate the type of valve as
“Customised”.
Note: Parameter/description Def.
• to exit the guided commissioning procedure press the DOWN button CONFIGURATION
repeatedly and finally confirm that configuration has been completed. Valve: CAREL
The guided procedure CANNOT be ended by pressing Esc; 0=custom ; 1= CAREL EXV; 2= Alco EX4; 3= Alco EX5; 4= Alco EX6; 5= Alco EXV
• if the configuration procedure ends with a configuration error, access EX7; 6= Alco EX8 330Hz suggested by CAREL; 7= Alco EX8 500Hz specified by
Alco; 8=Sporlan SEI 0.5-11; 9= Sporlan SER 1.5-20; 10= Sporlan SEI 30; 11=
Service parameter programming mode and modify the value of the
Sporlan SEI 50; 12= Sporlan SEH 100; 13= Sporlan SEH 175; 14= Danfoss
parameter in question; ETS 12.5-25B; 15= Danfoss ETS 50B; 16= Danfoss ETS 100B; 17= Danfoss
• if the valve and/or the pressure probe used are not available in the ETS 250; 18= Danfoss ETS 400; 19= two CAREL ExV connected together 20=
list, select any model and end the procedure. Then the driver will Sporlan Ser(I)G, J, K.; 21= Danfoss CCM 10-20-30; 22= Danfoss CCM 40;
be enabled for control, and it will be possible to enter Manufacturer 23=Danfoss CCMT 2-4-8; 24 = Disabled; 25= CAREL Ejector E2J17A-
programming mode and set the corresponding parameters manually. S1N0; 26= CAREL Ejector E2J23AT1N0; 27= CAREL Ejector E3J26AT2N0;
28= CAREL Ejector E3J33AU2N0; 29= CAREL Ejector E3J39AV3N0; 30=
CAREL Ejector E6J50AV3N0; 31= Danfoss CCMT 16; 32= Danfoss CCMT
Important: for 24 Vdc power supply, at the end of the guided 24; 33= Danfoss CCMT 30; 34= Danfoss CCMT 42; 35= Danfoss Colibri
commissioning procedure, to start control set “Power supply mode” Tab. 4.f
parameter=1, otherwise the valve remains in the closed position. See
paragraph 6.1. Note: select Valve = disabled if Main control = I/O expansion for
pCO to prevent the EEV motor error from being displayed. I/O expansion
for pCO control can be selected at the end of the commissioning
procedure, by entering programming mode.
Example: to use the same pressure probe, -0.5 to 7 bars, for 3 drivers
For the first driver, select: -0.5 to 7 barg
For the second and third driver select: remote -0.5 to 7 barg.
See paragraph 2.6
Note:
• the range of measurement by default is always in bar gauge (barg).In
the manufacturer menu, the parameters corresponding to the range
of measurement and the alarms can be customised if the probe used
is not in the standard list. If modifying the range of measurement, the
driver will detect the modification and indicate the type of probe S1
as “Customised”.
• The software on the driver takes into consideration the unit of measure.
If a range of measurement is selected and then the unit of measure is
changed (from bars to psi), the driver automatically updates in limits
of the range of measurement and the alarm limits.BY default, the main
control probe S2 is set as “CAREL NTC”. Other types of probes can be
selected in the service menu.
• Unlike the pressure probes, the temperature probes do not have any
modifiable parameters relating to the range of measurement, and
consequently only the models indicated in the list can be used (see
the chapter on “Functions” and the list of parameters). In any case,
in manufacturer programming mode, the limits for the probe alarm
signal can be customised.
Note:
• if main refrigerant= custom and secondary refrigerant = custom, the
secondary refrigerant is the same as the main refrigerant, defined by
parameters dew a...f high/low and bubble a...f high/low;
• if main refrigerant is selected between 1 and 26 and secondary
refrigerant= custom, the secondary refrigerant parameters will be
those pertaining to the custom refrigerant: “Dew a...f high/low” and
“Bubble a...f high/low”.
7=Reserved
8=Subcooling measurement S
9=Reverse high condensing temp. protection on S3
Tab. 5.b
Important: the “High condensing temperature protection” and M
“Modulating thermostat” auxiliary settings can only be enabled if the E
main control is also superheat control with settings 1 to 10 and 17, 18. On
V EEV
the other hand, the “Backup probes on S3 and S4” auxiliary control can be P T
activated, once the corresponding probes have been connected, only for
settings from 1 to 18.
Fig. 5.a
The following paragraphs explain all the types of control that can be set
on EVD evolution.
Fig. 5.b
Key:
CP Compressor V Solenoid valve
C Condenser T Temperature probe
L Liquid receiver EV Electronic valve
F Dewatering filter E Evaporator
S Liquid gauge P Pressure probe
GND Tx/Rx
C
S
shield
V M
Modbus®
RS485 L
E
EV
PA TA EVD
evolution
F S2
CP
S4
GND
pCO
S
Fig. 5.c
Key:
V M
CP Compressor V Solenoid valve
C Condenser S Liquid gauge
L Liquid receiver EV Electronic valve EV
F Dewatering filter E Evaporator
TA, TB Temperature probes PA, PB Pressure probes
T E
For information on the wiring see paragraph “General connection T
diagram”.
To optimise performance of the refrigerant circuit, compressor operation
must always be inside a specific area, called the envelope, defined by the Fig. 5.e
compressor manufacturer. Key:
CP Compressor V Solenoid valve
Inviluppo ⁄ Envelope C Condenser S Liquid gauge
L Liquid receiver EV Electronic valve
F Dewatering filter E Evaporator
T Temperature probe
Temperatura di condensazione (C°)
Fig. 5.d
F CP
EVD
evolution
S
EVD
S1
evolution
P
S1
E
M T
P
E
EV M T
V1 V2
A
V1 V2
EVD
evolution
E
S1
E M T
M T
P B
EV V1 V2
V1 V2
Fig. 5.g
Key:
Fig. 5.f CP Compressor V1 Solenoid valve
Key: C Condenser V2 Thermostatic expasnion valve
V1 Solenoid valve E Evaporator L Liquid receiver EV Electronic valve
V2 Thermostatic expasnion valve EV Electronic valve F Dewatering filter E Evaporator
S Liquid indicator
For the wiring, see paragraph “General connection diagram”.
For the wiring, see paragraph “General connection diagram”.
This involves PID control without any protectors (LowSH, LOP, MOP, High
This involves PID control without any protectors (LowSH, LOP, MOP, High
Tcond, see the chapter on Protectors), and without auxiliary control.
Tcond, see the chapter on Protectors), and without auxiliary control.
Control is performed on the pressure probe value read by input S1,
Control is performed on the hot gas bypass pressure probe value read by
compared to the set point: “EPR pressure set point”. Control is direct, as
input S1, compared to the set point: “Hot gas bypass pressure set point”.
the pressure increases, the valve opens and vice-versa.
Control is reverse, as the pressure increases, the valve closes and vice-
versa.
Parameter/description Def. Min. Max. UOM
CONTROL
EPR pressure set point 3.5 -20 (-290) 200 (2900) barg (psig) Parameter/description Def. Min. Max. UOM
PID proport. gain 15 0 800 - CONTROL
PID integration time 150 0 1000 s Hot gas bypass pressure set point 3 -20 200 barg (psig)
PID derivative time 5 0 800 s (290) (2900)
Tab. 5.j PID proport. gain 15 0 800 -
PID integration time 150 0 1000 s
PID derivative time 5 0 800 s
Tab. 5.k
S1
S2
For the wiring, see paragraph “General connection diagram”. GC
EV
This involves PID control without any protectors (LowSH, LOP, MOP, High P T
Tcond, see the chapter on Protectors), and without auxiliary control. CP
Control is performed on the hot gas bypass temperature probe value
read by input S2, compared to the set point: “Hot gas bypass temperature
set point”.
IHE
Control is reverse, as the temperature increases, the valve closes.
Parameter/description Def. Min. Max. UOM
CONTROL
Hot gas bypass temp. set point 10 -60 (-76) 200 (392) °C (°F) E
PID: proportional gain 15 0 800 - M T
PID integration time 150 0 1000 s
PID derivative time 5 0 800 s
Tab. 5.l V1 V2
Another application that exploits this control function uses the connection Fig. 5.j
of two EXV valves together to simulate the effect of a three-way valve, Key:
called “reheating”. To control humidity, valve EV_1 is opened to let the CP Compressor V2 Thermostatic expasnion valve
GC Gas cooler EV Electronic valve
refrigerant flow into exchanger S. At the same time, the air that flows E Evaporator IHE Inside heat exchanger
through evaporator E is cooled and the excess humidity removed, yet the V1 Solenoid valve
temperature is below the set room temperature. It then flows through
exchanger S, which heats it back to the set point (reheating). For the wiring, see paragraph “General connection diagram”.
EV_2 This involves PID control without any protectors (LowSH, LOP, MOP, High
Tcond, see the chapter on Protectors), and without auxiliary control.
C
Control is performed on the gas cooler pressure probe value read by
input S1, with a set point depending on the gas cooler temperature read
EV_1 CP
by input S2; consequently there is not a set point parameter, but rather
a formula:
EVD “CO2 gas cooler pressure set point”= Coefficient A * Tgas cooler (S2) +
evolution
Coefficient B. The set point calculated will be a variable that is visible in
s
display mode. Control is direct, as the pressure increases, the valve opens.
S1
S2
V3
Parameter/description Def. Min. Max. UOM
T ADVANCED
CO2 regul. ‘A’ coefficient 3.3 -100 800 -
CO2 regul. ‘B’ coefficient -22.7 -100 800 -
CONTROL
E PID proport. gain 15 0 800
M T
PID integration time 150 0 1000 s
PID derivative time 5 0 800 s
V1 V2
Tab. 5.m
Fig. 5.i
Key:
“EVD evolution” +0300005EN - rel. 4.2 - 24.01.2024 24
ENG
Analogue positioner (4 to 20 mA) I/O expander for pCO
The valve will be positioned linearly depending on the value of the “4 to The EVD Evolution driver is connected to the pCO programmable
20 mA input for analogue valve positioning” read by input S1. controller via LAN, transferring the probe readings quickly and without
There is no PID control nor any protection (LowSH, LOP, MOP, High Tcond, filtering. The driver operates as a simple actuator, and receives the
see the chapter on Protectors), and no auxiliary control. information needed to manage the valves from the pCO.
Parameter/Description Def.
EV CONFIGURATION
Main control multiplexed showcase/cold
… room
EVD
T I/O expander for pCO
evolution regulator Tab. 5.n
P
S1
4-20 mA
A
100%
EVD
EV
evolution
0%
4 20 mA
S1
S2
S3
S4
GND Tx/Rx
Fig. 5.k
Key: T
EV Electronic valve A Valve opening
P
For the wiring, see paragraph “General connection diagram”.
T
GND
Forced closing will only occur when digital input DI1 opens, thus pCO
switching between control status and standby. The pre-positioning and
repositioning procedures are not performed. Manual positioning can be P
enabled when control is active or in standby. shield
Fig. 5.m
Key:
Analogue positioner (0 to 10 Vdc) T Temperature probe P Pressure probe
EV Electronic valve
The valve will be positioned linearly depending on the value of the “0 to
10 V input for analogue valve positioning” read by input S1.
There is no PID control nor any protection (LowSH, LOP, MOP, High Tcond),
and no auxiliary control, with corresponding forced closing of the valve
and changeover to standby status. 5.7 Programmable control
The following types of programmable control are available:
• Programmable superheat control (SH);
EV
• Programmable special control;
EVD T • Programmable positioner.
evolution regulator Parameter/description Def Min Max U.M.
CONFIGURATION
P Main control Multiplexed - - -
S2
… cabinet
22= Programmable SH control ¦ / cold room
0-10 Vdc 23 = Programmable special control¦
A
24 = Programmable positioner
100% …
SPECIAL
Programmable control configuration 0 0 32767 -
Programmable control input 0 0 32767 -
Programmable SH control options 0 0 32767 -
0% Programmable control set point 0 -800 800
0 10 Vdc (-11603) (11603)
Tab. 5.o
Fig. 5.l The table shows the programmable control functions and the related
Key: parameter settings.
EV Electronic valve A Valve opening
Function Parameter to be set
For the wiring, see paragraph “General connection diagram”. Direct/reverse setting Programmable control
configuration
Type of physical value controlled Programmable control
Important: the pre-positioning and repositioning procedures configuration
are not performed. Manual positioning can be enabled when control is Input processing to determine measurement Programmable control
active or in standby. configuration
Correction to each individual input for integra- Programmable control input
tion in measurement calculation
Association between physical inputs and logical Programmable control input
outputs
Pressure [MPa]
measure
F A B
Direct operation: error = measurement - set point
Reverse operation: error = set point - measurement
S2
S1
mA, with direct PID control of the valve. E
MAX = 100 %
Setpoint = 50 %
EXAMPLE 3 MIN = 0 %
• Main control = 23à Programmable special control;
• Programmable control configuration = 10050à reverse PID voltage S
control;
• Programmable control input = 0100à Measurement =S2
• Programmable control options = XXXX: no affect
• Programmable control set point = 7.0 (V) EEV
FLOODED
FROM CONDENSER
This involves control of refrigerant liquid level with flooded evaporator, SHELL AND
TUBE EVAPORATOR
using the voltage value at input S2 as the measurement and a set point
of 7.0 V, with reverse PID control of the valve.
Fig. 5.o
Key:
EXAMPLE 4 S Float level sensor
• Main control = 24à Programmable positioner; EEV Electronic valve
• Programmable control configuration = 00070à current (mA) for E Flooded evaporator
positioner;
• Programmable control input = 00010à Measurement =S3; With the condenser, the action is direct: if the liquid level measured by
• Programmable control options = XXXX: no affect; the float level sensor is lower (higher) than the set point, the EEV valve
• Programmable control set point = XXXX: no affect. closes (opens).
This involves a 4 to 20 mA analogue positioner (without PID): the valve
will be positioned linearly, depending on the “4 to 20 mA input value for For the wiring, see paragraph “General connection diagram”.
analogue valve positioning”, read by input S3.
set point
M
t
E 2. offset too high
ON
V EEV SV
P T OFF
t
Fig. 5.p
Key:
CP Compressor EEV Electronic expansion valve S4
C Condenser V Solenoid valve set point + diff
L Liquid receiver E Evaporator
set point
F Dewatering filter P Pressure probe (transducer)
S Liquid indicator T Temperature probe 3. offset correct
t
For the wiring, see paragraph “General connection diagram”. ON
SV
As already mentioned, the HITCond protection can only be enabled if the OFF
controller measures the condensing pressure/temperature, and responds t
moderately by closing the valve in the event where the condensing
temperature reaches excessive values, to prevent the compressor from
shutting down due to high pressure. The condensing pressure probe Fig. 5.q
must be connected to input S3. Key:
diff= differential
SV= solenoid valve (showcase temperature control)
S4= temperature
Modulating thermostat
This function is used, by connecting a temperature probe to input
C
S4, to modulate the opening of the electronic valve so as to limit the
lowering of the temperature read and consequently reach the control
set point. This is useful in applications such as the multiplexed cabinets
to avoid the typical swings in air temperature due to the ON/OFF control L
(thermostatic) of the solenoid valve. A temperature probe must be
connected to input S4, located in a similar position to the one used for EVD
evolution
the traditional temperature control of the cabinet. In practice, the close F
the controlled temperature gets to the set point, the more the control CP
S1
S2
S4
S (HiTcond) on S3
The aim of reverse HiTcond protection is to limit the condensing pressure
in the refrigerant circuit by opening the valve rather than closing it. This
M function is recommended, rather than the HiTcond protection function
described previously, in refrigerant circuits without a liquid receiver and
E where the condenser is smaller than the evaporator (e.g. air-to-water
V EEV
P T P T heat pumps). In this case, in fact, closing the valve would obstruct the
flow of refrigerant to the condenser that, lacking sufficient volume for
the refrigerant to accumulate, would cause an increase in condensing
pressure. This function is especially useful for condensers in CO2 cascade
Fig. 5.s systems. See the chapter on Protectors.
Key:
CP Compressor EEV Electronic expansion valve C
C Condenser V Solenoid valve
L Liquid receiver E Evaporator
F Dewatering filter P Pressure probe (transducer)
S Liquid indicator T Temperature probe
P
For the wiring, see paragraph “General connection diagram”.
F
EVD CP
evolution
Subcooling measurement S
S3
S1
S2
EEV E
P T
TB PB
L
Fig. 5.u
CP Key:
F EVD CP Compressor EEV Electronic expansion valve
evolution C Condenser V Solenoid valve
F Filter-drier E Evaporator
S S1 S2 S3 S4 S Liquid gauge P Pressure probe (transducer)
T Temperature probe
EEV E
PA TA
Fig. 5.t
Key:
CP Compressor EEV Electronic expansion valve
C Condenser V Solenoid valve
L Liquid receiver E Evaporator
F Filter-drier PA, PB Pressure probes
S Liquid gauge TA, TB Temperature probes
Forced closing
Forced closing is performed after the driver is powered-up and
corresponds to a number of closing steps equal to the parameter “Closing
steps”, based on the type valve selected. This is used to realign the valve
steps
to the physical position corresponding to completely closed. The driver 0 25%
and the valve are then ready for control and both aligned at 0 (zero). On Min_step_EEV Max_step_EEV
power-up, first a forced closing is performed, and then the standby phase
starts. Fig. 6.b
Parametro/description Def. Min. Max. UOM (**) In this case, the formula used is:
VALVE Apertura / Opening = P*(Max_step_EEV / 100)
EEV closing steps 500 0 9999 step
P = Posizione valvola in stand-by / Position valve in stand-by
Tab. 6.k
The valve is closed in the event of power failures with 24 Vac power
supply when the EVD0000UC0 module is connected. In this case, the
parameter “Forced valve closing not completed”, visible only on the
supervisor, is forced to 1. If when restarting forced closing of the valve
1% 99% steps
was not successful: 0% 100%
1. the Main programmable controller checks the value of the parameter Min_step_EEV Max_step_EEV
and if this is equal to 1, decides the best strategy to implement based
on the application; Fig. 6.c
2. the driver on restart positions the valve as explained in the paragraph Note: if “Valve open in standby=1”, the positions of the valve when
“Pre-positioning/start control The parameter is reset to 0 (zero) by setting “Valve position in standby”=0 and 25 do not coincide.
the Main controller (e.g. pCO), once the parameter has been set to Refer to the above formulae.
1 the driver returns it to 0 (zero) only if forced emergency closing is
completed successfully.
The valve opening parameter should be set based on the ratio between
the rated cooling capacity of the evaporator and the valve (e.g. rated ON t
evaporator cooling capacity: 3kW, rated valve cooling capacity: 10kW, P
OFF
valve opening = 3/10 = 33%).
SH
7.1 Protectors
Low_SH_TH
The protectors are 5:
• LowSH, low superheat;
• LOP, low evaporation temperature; t
ON
• MOP, high evaporation temperature; Low_SH
• High Tcond, high condensing temperature; OFF
• Reverse HiTcond.
Note: the HiTcond protectors require an additional probe (S3) to ON t
A
those normally used, either installed on the driver, or connected via tLAN,
OFF
pLAN, RS485/ Modbus® to a controller.
The protectors have the following main features: D B t
• activation threshold: depending on the operating conditions of the Fig. 7.a
controlled unit, this is set in Service programming mode; Key:
• integration time, which determines the intensity (if set to 0, the SH Superheat A Alarm
protector is disabled): set automatically based on the type of main Low_SH_TH Low_SH protection threshold D Alarm timeout
Low_SH Low_SH protection t Time
control;
B Automatic alarm reset
• alarm, with activation threshold (the same as the protector) and
timeout (if set to 0 disables the alarm signal).
ON t
MOP
ON t OFF
LOP
OFF
ON t
PID
ON t OFF
ALARM
OFF
ON
t
ALARM
D B t OFF
Fig. 7.b
Key:
T_EVAP Evaporation temperature D Alarm timeout D t
LOP_TH Low evaporation temperature ALARM Alarm Fig. 7.c
protection threshold Key:
LOP LOP protection t Time T_EVAP Evaporation temperature MOP_TH MOP threshold
B Automatic alarm reset PID PID superheat control ALARM Alarm
MOP MOP protection t Time
D Alarm timeout
MOP (high evaporation pressure) Important: the MOP threshold must be greater than the rated
MOP= Maximum Operating Pressure. evaporation temperature of the unit, otherwise it would be activated
unnecessarily. The MOP threshold is often supplied by the manufacturer
The MOP protection threshold is applied as a saturated evaporation
of the compressor. It is usually between 10 °C and 15 °C.
temperature value so that it can be easily compared against the technical
specifications supplied by the manufacturers of the compressors. The
If the closing of the valve also causes an excessive increase in the suction
protector is activated so as to prevent too high evaporation temperatures
temperature (S2) above the set threshold – only set via supervisor
from causing an excessive workload for the compressor, with consequent
(PlantVisor, pCO, VPM), not on the display - the valve will be stopped
overheating of the motor and possible activation of the thermal protector.
to prevent overheating the compressor windings, awaiting a reduction
The protector is very useful in self-contained units if starting with a high
in the refrigerant charge. If the MOP protection function is disabled by
refrigerant charge or when there are sudden variations in the load. The
setting the integral time to zero, the maximum suction temperature
protector is also useful in multiplexed systems (showcases), as allows all
control is also deactivated.
the utilities to be enabled at the same time without causing problems
of high pressure for the compressors. To reduce the evaporation Parameter/description Def. Min. Max. UOM
CONTROL
temperature, the output of the refrigeration unit needs to be decreased.
MOP protection: suction temperature 30 -60 (-72) 200 (392) °C(°F)
This can be done by controlled closing of the electronic valve, implying threshold
superheat is no longer controlled, and an increase in the superheat Tab. 7.e
temperature. The protector will thus have a moderate reaction that tends
to limit the increase in the evaporation temperature, keeping it below the At the end of the MOP protection function, superheat regulation restarts
activation threshold while trying to stop the superheat from increasing in a controlled manner to prevent the evaporation temperature from
as much as possible. Normal operating conditions will not resume based exceeding the threshold again.
on the activation of the protector, but rather on the reduction in the If the suction temperature is greater than or equal to the set temperature
refrigerant charge that caused the increase in temperature. The system protection threshold, the MOP protection does not work.
will therefore remain in the best operating conditions (a little below the
threshold) until the load conditions change. High Tcond (high condensing temperature)
Parameter/description Def. Min. Max. UOM To activate the high condensing temperature protector (High Tcond), a
CONTROL pressure probe must be connected to input S3.
MOP protection threshold 50 Protection LOP: 200 °C (°F) The protector is activated so as to prevent too high evaporation
threshold (392)
temperatures from stopping the compressor due to the activation of the
MOP protection integration time 20 0 800 s
ALARM CONFIGURATION high pressure switch.
High evaporation temperature 600 0 18000 s Parameter/description Def. Min. Max. UOM
alarm timeout (MOP) ADVANCED
(0= alarm DISABLED) High Tcond threshold 80 -60 200 °C (°F)
Tab. 7.d (-76) (392)
High Tcond integration time 20 0 800 s
The integration time is set automatically based on the type of main ALARM CONFIGURATION
control. High condensing temperature alarm timeout 600 0 18000 s
(High Tcond)
When the evaporation temperature rises above the MOP threshold, the (0= alarm DISABLED)
system enters MOP status, superheat control is interrupted to allow the Tab. 7.f
pressure to be controlled, and the valve closes slowly, trying to limit the The integration time is set automatically based on the type of main
evaporation temperature. control.
T_COND L2
T_COND_TH
B CP2
F2
T_COND_TH - Δ
t S2
ON
HiTcond
OFF
T V2 E
V1 M
ON t
PID
OFF
Fig. 7.e
t Key:
ON CP1/2 Compressor 1/2 EEV Electronic expansion
ALARM
valve
OFF CHE Cascade heat exchanger C Condenser
L1/2 Liquid receiver 1/2 V Solenoid valve
D t F1/2 Filter-drier 1/2 E Evaporator
Fig. 7.d S1/2 Liquid gauge 1/2 P1/2 Pressure probe
(transducer)
Key: T1 Temperature probe V2 Thermostatic
T_COND Condensing temperature T_COND_TH High Tcond expansion valve
threshold
High Tcond High Tcond protection status ALARM Alarm For the wiring, see paragraph “General connection diagram”
PID PID superheat control t Time
D Alarm timeout
Note: for this type of application, the auxiliary refrigerant must be
Note: set as CO2 (R744).
• the High Tcond threshold must be greater than the rated condensing Parameter / Description Def.
temperature of the unit and lower then the calibration of the high Refrigerant Alls refrigerants, not R744
Main regulation Subcooling regulation 1...10
pressure switch;
Auxiliary refrigerant R744
• the closing of the valve will be limited if this causes an excessive
decrease in the evaporation temperature. The driver controls refrigerant superheat in the primary circuit (A), and
at the same time measures the refrigerant condensing pressure in the
secondary circuit (B). When the condensing temperature exceeds the
Reverse HiTcond (for CO2 cascade systems) HiTCond protection threshold, normal superheat control is overridden by
forced opening of the valve, at a rate that is inversely proportional to the
As mentioned earlier, reverse high condensing temperature protection
HiTCond protection integral time. Opening the EEV lowers the superheat
(HiTcond) on S3, opens the valve to limit refrigerant circuit condensing
in the primary circuit, which increases the heat exchange coefficient and
pressure by filling part of the evaporator. The graph of how the function
consequently reduces the condensing pressure in the secondary circuit.
works is similar to the one shown for HiTCond protection.
The reverse HiTcond threshold for CO2 cascade applications should be
Important: opening the valve will probably also cause activation of set in relation to the expected evaporation temperature in the primary
the low superheat protection LowSH, which tends to limit the opening of circuit. The threshold must be set to a value that is at least 3-5°C higher
the valve. The ratio between the integral times of these two concurrent than the minimum evaporation temperature in the primary circuit. Lower
yet opposing protectors determines how effective one is compared to values make achieving the set pressure limit incompatible with heat
the other. exchange efficiency. In addition, swings in operation may occur due the
This function is especially useful for condensers in CO2 cascade systems, attempt to limit low superheat in the primary circuit and the pressure in
where condensation in the low temperature circuit (also called the secondary circuit at the same time.
“secondary”, B) takes place when evaporating the refrigerant in the
medium temperature circuit (“primary”, A).
CAREL SVP
Modbus®
Type **
Parameter/description Def. Min. Max. UOM
Notes
user*
CONFIGURATION
A Network address pLAN: 30 1 207 - I 11 138
others: 198
A Refrigerant: 0= user defined; R404A - - - I 13 140
1= R22 2= R134a 3= R404A 4= R407C 5= R410A
6= R507A 7= R290 8= R600 9= R600a 10= R717
11= R744 12= R728 13= R1270 14= R417A 15= R422D
16= R413A 17= R422A 18= R423A 19= R407A 20= R427A
21= R245FA 22= R407F 23= R32 24= HTR01 25= HTR02
26= R23 27= R1234yf 28= R1234ze 29= R455A 30= R170
31= R442A 32= R447A 33= R448A 34= R449A 35= R450A
36= R452A 37= R508B 38= R452B 39= R513A 40= R454B
41= R458A 42 = R407H 43 = R454A 44 = R454C 45 = R470A
46 = R515B 47 = R466A
A Valve: CAREL EXV - - - I 14 141
0= user defined 13= Sporlan SEH 175 26= CAREL ejector E2J23AT1N0
1= CAREL EXV 14= Danfoss ETS 12.5-25B 27= CAREL ejector E3J26AT2N0
2= Alco EX4 15= Danfoss ETS 50B 28= CAREL ejector E3J33AU2N0
3= Alco EX5 16= Danfoss ETS 100B 29= CAREL ejector E3J39AV3N0
4= Alco EX6 17= Danfoss ETS 250 30= CAREL ejector E6J50AV3N0
5= Alco EX7 18= Danfoss ETS 400 31= Danfoss CCMT 16
6= Alco EX8 330Hz 19= Two EXV CAREL 32= Danfoss CCMT 24
recommend CAREL connected together
7= Alco EX8 500Hz 20= Sporlan SER(I)G,J,K 33= Danfoss CCMT 30
specific Alco
8= Sporlan SEI 0.5-11 21= Danfoss CCM 34= Danfoss CCMT 42
10-20-30
9= Sporlan SER 1.5-20 22= Danfoss CCM 40 35= Danfoss Colibri
10= Sporlan SEI 30 23= Danfoss CCM T 2-4-8
11= Sporlan SEI 50 24= Disabled
12= Sporlan SEH 100 25= CAREL ejector
E2J17AS1N0
A Probe S1: 0= user defined Ratiometric: -1 - - - I 16 143
Ratiometric (OUT=0…5 V) Electronic (OUT=4…20 mA) to 9.3 barg
1= -1…4,2 barg 8= -0,5…7 barg
2= -0,4…9,3 barg 9= 0…10 barg
3= -1…9,3 barg 10= 0…18,2 bar
4= 0…17,3 barg 11= 0…25 barg
5= 0,85…34,2 barg 12= 0…30 barg
6= 0…34,5 barg 13= 0…44,8 barg
7= 0…45 barg 14= remoto, -0,5…7 barg
21= -1…12,8 barg 15= remoto, 0…10 barg
22= 0…20,7 barg 16= remoto, 0…18,2 barg
23= 1,86…43,0 barg 17= remoto, 0…25 barg
24= Livello liquido CAREL 18= remoto, 0…30 barg
25 = 0...60,0 barg 19= remoto, 0…44,8 barg
26 = 0...90,0 barg 20= external signal 4…20 mA
27= external signal 0…5 V
A Main control: Multiplexed - - - I 15 142
0= user defined 14= transcritical CO2 gas cooler cabinet/cold
1= Centralized cabinet/cold room 15= analog positioner (4 to 20 mA) room
2= Self contained cabinet/cold room 16= analog positioner (0 to10 V)
3= Perturbated cabinet/control room 17= AC/chiller or cabinet/cold room
with adaptative regulation
4= Subcritical CO2 cabinet/cold room 18= AC or chiller with Digital Scroll
compressor
5= R404A condenser for subcritical CO2 19= AC/chiller with BLDC compressor (*)
6= AC or chiller with plate evaporator 20= superheat regulation with 2
temperature probes
7= AC or chiller with shell tube 21= I/O expander for pCO
evaporator
8= AC or chiller with battery coil 22= Programmable SH regulation
evaporator
9= AC or chiller with variable cooling 23= Programmable special regulation
capacity
10= AC or chiller perturbated unit 24= Programmable positioner
11= EPR Back pressure 25= Evaporator liquid level regulation
with CAREL sensor
12= Hot gas by-pass by pressure 26= Condenser liquid level regulation
with CAREL sensor
13= Hot gas by-pass by temperature (*)= only for controls for CAREL valves
A Probe S2: CAREL NTC - - - I 17 144
0= user defined 1= NTC CAREL
2= CAREL NTC- HT high 3= combined NTC SPKP**T0
4= 0 to 10V external signal 5= NTC – LT CAREL low temperature
A Auxiliary control: Disabled - - - I 18 145
0= user defined
1= Disabled
2= high condensing temperature protection on S3 probe
3= modulating thermostat on S4 probe
4= backup probes on S3 and S4
5, 6, 7 = Reserved
8= Subcooling measurement
9= Inverse high condensation temperature protection on S3 probe
10= Reserved
CAREL SVP
Modbus®
Type **
Parameter/description Def. Min. Max. UOM
Notes
user*
CAREL SVP
Modbus®
Type **
Parameter/description Def. Min. Max. UOM
Notes
user*
CAREL SVP
Modbus®
Type **
Parameter/description Def. Min. Max. UOM
Notes
user*
When changing the unit of measure, all the values of the parameters
saved on the driver and all the measurements read by the probes will
be recalculated. This means that when changing the units of measure,
control remains unaltered.
Example 1: The pressure read is 100 barg, this will be immediately
converted to the corresponding value of 1450 psig.
Example 2: The “superheat set point” parameter set to 10 K will be
immediately converted to the corresponding value of 18 °F.
Example 3: The “S4 alarm MAX temp.” parameter, set to 150 °C, will be
immediately converted to the corresponding value of 302 °F
Probe S3 0 0 1 D 6 5 R
Probe S4 0 0 1 D 7 6 R
EEV motor error 0 0 1 D 8 7 R
Relay status 0 0 1 D 9 8 R
LOP (low evaporation temperature) 0 0 1 D 50 49 R
ACTIVATED
PROTECT.
BLDC compres.
Hot gas by-pass
pass / pressure
Superheat control
AC/chiller with
2 temperature
/ temperature
Superheat re-
gulation with
I/O expander
Scroll compr.
Control with
AC or chiller
Auxiliary control
Transcritical
level sensor
with Digital
Hot gas by-
EPR back
HiTcond/ Subco-
pressure
Variable displayed
for pCO
Modulat.
probes
HiTcond oling
thermostat
CO2
inverse measure
Valve opening(%)
Valve position (step)
Current unit cooling capacity
Control setpoint
Superheat
Suction temperature
Evaporation temperature
Evaporation pressure
Condensing temperature
Condensing pressure
Modulating thermostat temperature
EPR pressure (back pressure)
Hot gas bypass pressure
Hot gas bypass temperature
CO2 gas cooler outlet temperature
CO2 gas cooler outlet pressure
CO2 gas cooler pressure set point
Condensation pressure for subcooling
measure (SBC)
Condensation Temperature bubble
for subcooling measure (SBC)
Liquid temperature for subcooling
measure (SBC)
Subcooling measurement
S1 probe measurement
S2 probe measurement
S3 probe measurement
S4 probe measurement
4 to 20 mA input value
0 to 10 Vdc input value
DI1 digital input status (*)
DI2 digital input status (*)
EVD firmware version
Display firmware version
Adaptative regulation status
0= Not enabled or stopped
1= Monitoring superheat
2= Monitoring suction temperature
3= Wait superheat stabilisation
4= Wait suction temperature stabilisation
5= Applying step
6= Positioning valve
7= Sampling response to step
8=Wait stabilisation in response to step
9= Wait tuning improvement
10= Stop, max attempts exceeded
Last tuning result
0= No attempt performed
1= Attempt interrupted
2= Step application error
3= Time constant/delay error
4= Model error
5= Tuning ended successfully on suction
temperature
6= Tuning ended successfully on superheat
Discharge superheat
Discharge temperature
Liquid level percentage
Tab. 8.c
(*) Digital input status: 0= open, 1= closed.
Note: the readings of probes S1, S2, S3, S4 are always displayed,
regardless of whether or not the probe is connected.
All the alarms are reset automatically, once the causes are no longer
present. The alarm relay contact will open if the relay is configured as
alarm relay using the corresponding parameter. The signalling of the
alarm event on the driver depends on whether the LED board or the Fig. 9.b
display board is fitted, as shown in the table below. • control alarm: next to the flashing ALARM message, the main page
Note: the alarm LED only comes on for the system alarms, and not shows the type of protector activated.
for the control alarms.
Surriscaldam. ON
Example: display system alarm on LED board: 4.9 K
MOP
Apertura
valvola ALARM
EVD evolution
44 % Rele
Fig. 9.c
Note:
• to display the alarm queue, press the Help button and scroll using the
Fig. 9.a UP/DOWN buttons;
• the control alarms can be disabled by setting the corresponding
Note: the alarm LED comes on to signal a mains power failure only timeout to zero.
if the EVBAT*** module (accessory) has been connected, guaranteeing
the power required to close the valve.
Table of alarms
Type of alarm Cause of alarm LED Display Relay Reset Effect on control Checks/ solutions
Probe S1 Probe S1 faulty or red alarm ALARM flashing Depends on confi- automatic Depends on pa- Check the probe connections. Check the
exceeded set alarm LED guration parameter rameter “S1 probe “S1 probe alarm manag.”, and “S1 alarm
range alarm manag.” MIN & MAX pressure” parameters
Probe S2 Probe S2 faulty or red alarm ALARM flashing Depends on confi- automatic Depends on pa- Check the probe connections. Check the
exceeded set alarm LED guration parameter rameter “S2 probe “S2 probe alarm manag.”, and “S2 alarm
range alarm manag.” MIN & MAX temperature” parameters
Probe S3 Probe S3 faulty or red alarm ALARM flashing Depends on confi- automatic Depends on pa- Check the probe connections. Check the
exceeded set alarm LED guration parameter rameter “S3 probe “S3 probe alarm manag.”, and “S3 alarm
range alarm manag.” MIN & MAX pressure” parameters
Probe S4 Probe S4 faulty or red alarm ALARM flashing Depends on confi- automatic Depends on pa- Check the probe connections. Check the
exceeded set alarm LED guration parameter rameter “S4 probe “S4 probe alarm manag.”, and “S4 alarm
range alarm manag.” MIN & MAX temperature” parameters
(LowSH) low LowSH protection - ALARM & LowSH Depends on confi- automatic Protection action Check the “LowSH alarm threshold and
superheat activated flashing guration parameter already active timeout” parameters
(LOP) low evapora- LOP protection - ALARM & LOP Depends on confi- automatic Protection action Check the “LOP alarm threshold and
tion temperature activated flashing guration parameter already active timeout” parameters
(MOP) high evapo- MOP protection - ALARM & MOP Depends on confi- automatic Protection action Check the “MOP alarm threshold and
ration temperature activated flashing guration parameter already active timeout” parameters”
(High Tcond) high High Tcond protec- - ALARM & MOP Depends on confi- automatic Protection action Check the “Hitcond alarm threshold and
conden tempe- tion activated flashing guration parameter already active timeout” parameters”
rature
Low suction tem- Threshold and - ALARM flashing Depends on confi- automatic No effect Check the threshold and timeout
perature timeout exceeded guration parameter parameters.
EEPROM damaged EEPROM for red alarm ALARM flashing Depends on confi- Replace Total shutdown Replace the driver/Contact service
operating and/or LED guration parameter driver/Contact
unit parameters service
damaged
EEV motor error Valve motor fault, red alarm ALARM flashing Depends on confi- automatic Interruption Check the connections and the condi-
not connected LED guration parameter tion of the motor
Switch driver off and on again
LAN error LAN network com- green ALARM flashing Depends on confi- automatic Control based on Check the network address settings
munication error NET LED guration parameter DI1/DI2
flashing
LAN network con- NET LED ALARM flashing Depends on confi- automatic Control based on Check the connections and that the pCO
nection error off guration parameter DI1/DI2 is on and working
Then the user can choose to: • go to Configure device: the list of parameters will be displayed,
4. directly access to the list of parameters for the EVD evolution saved to allowing the changes relating to the application to be made.
EEPROM: select “tLAN”;
This is done in real time (ONLINE mode), at the top right set the network
address 198 and choose the guided recognition procedure for the USB
communication port. Enter at the Service or Manufacturer level.
Fig. 12.e
At the end of the configuration, to save the project choose the following
command, used to save the configuration as a file with the .hex extension.
Fig. 12.b File -> Save parameter list.
To transfer the parameters to the driver, choose the “Write” command.
During the write procedure, the 2 LEDs on the converter will flash.
Fig. 12.f
Note: the program On-line help can be accessed by pressing F1.
The driver parameters driver will now have the default settings.
Agenzia / Agency: