2021 ANNUAL MAINTENANCE ON TRANSFORMER AT GEOLIS CABLE NKPOR

ONITSHA.

TRANSFORMER II (FACTORY) DATA


1 Make OCREV[BROGLIANO VICENZA]ITALY
2 Year of Manufacture 1999
3 Serial No 61120
4 Voltage Level 500KVA[33/0.415KV]
5 Vector Group DYnll
6 Percentage Impedance 3.4%

Table 1.1: Insulation Resistance Test

HV-G LV-G HV- OIL WINDING DATE OF


(GΩ) (MΩ) LV TEMP. TEMP (ᵒc) MEASUREMENT
(MΩ) (ᵒc)
Red Ø 2400 1000 2700 37.2
Yellow Ø 2300 1100 2700 37.4
Blue Ø 2200 1060 2700 37.2
Instrument used in carrying out the test is 5kV Digital Insulation Resistance Tester (Megger)
MIT1020/2

Table 1.2: RATIO TEST WITH POTENTIAL AT THE PRIMARY SIDE [33KV]
ry 430v
yb 432v
br 433v
rn 242v
yn 241v
bn 243v

Table 1.3: WINDING RESISTANCE TEST


RY 3.72 ohms
YB 3.74 ohms
BR 3.72 ohms

ry 0.9
yb 0.7
br 0.8
rn 0.8

1
yn 0.6
bn 0.7

Table 1.4: T/F Oil Test

TEST KV
First 56
Second 60
Third 60
Fourth 60
Fifth 58
Sixth 60
Average is 59.1KV PASS

OBSERVATION
1. No oil leakage
2. The earth pit is WET, which is recommended
3. The transformer sub-station is OK

ITEM REPLACE/ADD:
1. Silica gel

RECOMMENDATION:

We recommend that 400Amps CHANGEOVER SWITCH should be installed in between


TRANSFORMER 1 AND 11, to increase the LIFESPAN of TRANSFORMER 11 since
TRANSFORMER 1 carries no load for now.

REMARKS:

The transformer is FIT for service

2
TRANSFORMER 11[FACTORY]

TRANSFORMER II (FACTORY) DATA


1 Make OCREV[BROGLIANO VICENZA]ITALY
2 Year of Manufacture 1999
3 Serial No 60303
4 Voltage Level 500KVA[33/0.415KV]
5 Percentage Impedance 5.71%

Table 1.1: Insulation Resistance Test

HV-G LV-G HV- OIL WINDING DATE OF


(GΩ) (MΩ) LV TEMP. TEMP (ᵒc) MEASUREMENT
(MΩ) (ᵒc)
Red Ø 604 302 560 37.2
Yellow Ø 602 306 560 37.4
Blue Ø 604 310 560 37.2
Instrument used in carrying out the test is 5kV Digital Insulation Resistance Tester (Megger)
MIT1020/2

Table 1.2: RATIO TEST WITH POTENTIAL AT THE PRIMARY SIDE [33KV]
ry 420v
yb 422v
br 420v
rn 232v
yn 236v
bn 234v

Table 1.3: WINDING RESISTANCE TEST


RY 42.0 ohms
YB 44.2 ohms
BR 43.2 ohms

ry 0.8
yb 0.8
br 0.7
rn 0.8

3
yn 0.8
bn 0.7

Table 1.4: T/F Oil Test

TEST KV
First 60
Second 59
Third 60
Fourth 60
Fifth 60
Sixth 60
Average is 59.8KV PASS

OBSERVATION
4. No oil leakage
5. The earth pit is WET, which is recommended
6. The transformer sub-station is OK

ITEM REPLACE/ADD:
1. Silica gel

REMARKS:

The transformer is FIT for service