Transformer2 1250 Kva
Transformer2 1250 Kva
Transformer2 1250 Kva
EQUIPMENT DETAILS:
Make POWER STAR Rating 1250 KVA
Sl. No. PS/1250-1274 Cooling ONAN
HV (Volt) 11000V Gross Weight 4910
LV (Volt) 433V HV (Amps) 65.61 Amp
% Z Impedance 5% LV (Amps) 1666.72 Amp
Qty of Oil 1601 LTR Vector Group Dyn11
Mfg. Year 2010 Connection (HV) Delta
No of Taps 1-5 Connection (LV) Star
Normal Tap 3
CALIBRATION
INSTRUMENT MAKE SL. NO. RANGE
DUE DATE
Digital Insulation
Motwane A02747121 0 – 5 KV 12-01-2023
tester
Transformer Winding
Scope 2304.08AI1035 0-10 A/0-2000 Ω 12-01-2023
resistance
Digital Multimeter Fluke 55030407 0-1000 V 12-01-2023
Milli Clamp Meter Multi B02850 30 mA – 300 Amp 12-01-2023
*While taking IR for winding, other winding to be shorted & grounded except while taking IR value
HV/LV. Wdg to be guarded in case of three phase Wdg Trf .
4. PI TEST :
Time HV to LV HV to EARTH LV to EARTH Remarks
15 Sec 1.82 GΩ 2.78 GΩ 89.6 MΩ OK
1 Min 4.18 GΩ 4.04 GΩ 96.4 MΩ
2 Min 4.97 GΩ 4.59 GΩ 97.5 MΩ
3 Min 5.36 GΩ 4.87 GΩ 87.9 MΩ
4 Min 5.35 GΩ 5.03 GΩ 86.0 MΩ
5 Min 5.63 GΩ 5.13 GΩ 88.9 MΩ
6 Min 5.69 GΩ 5.23 GΩ 89.8 MΩ
7 Min 5.75 GΩ 5.32 GΩ 95.1 MΩ
8 Min 5.79 GΩ 5.38 GΩ 104 MΩ
9 Min 5.82 GΩ 5.42 GΩ 110 MΩ
10 Min 5.89 GΩ 5.47 GΩ 115 MΩ
Inference :