Transformer2 1250 Kva

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 4

1.

EQUIPMENT DETAILS:
Make POWER STAR Rating 1250 KVA
Sl. No. PS/1250-1274 Cooling ONAN
HV (Volt) 11000V Gross Weight 4910
LV (Volt) 433V HV (Amps) 65.61 Amp
% Z Impedance 5% LV (Amps) 1666.72 Amp
Qty of Oil 1601 LTR Vector Group Dyn11
Mfg. Year 2010 Connection (HV) Delta
No of Taps 1-5 Connection (LV) Star
Normal Tap 3

2.TESTING EQUIPMENT DETAILS:

CALIBRATION
INSTRUMENT MAKE SL. NO. RANGE
DUE DATE
Digital Insulation
Motwane A02747121 0 – 5 KV 12-01-2023
tester
Transformer Winding
Scope 2304.08AI1035 0-10 A/0-2000 Ω 12-01-2023
resistance
Digital Multimeter Fluke 55030407 0-1000 V 12-01-2023
Milli Clamp Meter Multi B02850 30 mA – 300 Amp 12-01-2023

 Test Condition : Both Side Cable Disconnected . Temp:- 22ºC

3. INSULATION RESISTANCE TEST :

Description Voltage(KV) 1 Min 10 Min PI value Remarks

HV to LV 5.0 KV 4.18 GΩ 5.89 GΩ 1.40 P.I Value is OK

HV to EARTH 5.0 KV 4.04 GΩ 5.47 GΩ 1.55 P.I Value is OK

LV to EARTH 0.5 KV 96.4 MΩ 115 MΩ 1.19 P.I Value is Low

*While taking IR for winding, other winding to be shorted & grounded except while taking IR value
HV/LV. Wdg to be guarded in case of three phase Wdg Trf .

4. PI TEST :
Time HV to LV HV to EARTH LV to EARTH Remarks
15 Sec 1.82 GΩ 2.78 GΩ 89.6 MΩ OK
1 Min 4.18 GΩ 4.04 GΩ 96.4 MΩ
2 Min 4.97 GΩ 4.59 GΩ 97.5 MΩ
3 Min 5.36 GΩ 4.87 GΩ 87.9 MΩ
4 Min 5.35 GΩ 5.03 GΩ 86.0 MΩ
5 Min 5.63 GΩ 5.13 GΩ 88.9 MΩ
6 Min 5.69 GΩ 5.23 GΩ 89.8 MΩ
7 Min 5.75 GΩ 5.32 GΩ 95.1 MΩ
8 Min 5.79 GΩ 5.38 GΩ 104 MΩ
9 Min 5.82 GΩ 5.42 GΩ 110 MΩ
10 Min 5.89 GΩ 5.47 GΩ 115 MΩ

5. VOLTAGE RATIO TEST WITH MAGNETIZING CURRENT

HIGH VOLTAGE SIDE


Tap Applied Voltage (In Volts) Measured Magnetizing. Current in (mA)
Position R-Y Y-B B-R R Y B
1 400.8 401.3 399.1 14.32 16.68 6.75
3 400.3 403.2 399.2 14.39 16.79 7.37
5 400.7 404.3 399.9 14.69 17.26 8.10

LOW VOLTAGE SIDE


Tap Measured Voltage (Volt) Measured Voltage (Volt)
Position r-y y-b b-r r-n y-n b-n
1 15.14 15.10 14.33 8.66 8.78 8.67
3 15.90 15.87 15.62 9.10 9.24 9.10
5 16.77 16.75 16.58 9.64 9.73 9.62

6. NO LOAD LOSS : (Preferably From HV Side) ( In Normal Tap ) :


Applied Voltage (In Volts) Measured Current (A/mA) Total Loss Remarks
V RY V YB V BR IR IY IB (Watts) Loss Calculated at
400.3 403.2 399.2 14.39 16.79 7.37 3080 rated voltage

7. MAGNETIC BALANCE TEST : HV / LV Side :( STAR WINDING )

Applied Voltage (In Volts) Measured Voltage (In Volts) Measured


current Remarks
r-n y-n b-n r-n y-n b-n
(Amp)
100.1 ---- ---- ---- 78.18 21.89 1.90
---- 100.7 ---- 50.88 ---- 49.92 1.36 OK
---- ---- 100.8 20.46 79.80 ---- 2.01
8. WINDING RESISTANCE TEST : (In normal tap)

HIGH VOLTAGE SIDE


HV Between R-Y Between Y-B Between B-R Remarks
Winding
Tap. No. Asc Asc Asc
OK
3 1704.0 mΩ 1693.1 mΩ 1692.8 mΩ

LOW VOLTAGE SIDE


Lv r-y y-b b-r r-n y-n b-n
Winding 2.287 µΩ 2.294 µΩ 2.298 µΩ 1.255 µΩ 1.246 µΩ 1.248 µΩ

9. VECTOR GROUP TEST (HV-LV) : (At normal Tap for DYn11)


Applied Voltage (Volt) Measured Voltage (Volt)
R-Y 400 B-b 386.7 Y-b 387.4
Y-B 405.5 B-y 401.89 Y-y 386.4
B-R 399.5 R-n 9.15
Y-n 391.8

Inference :

VBb < VBy


VYy = VYb Hence It is DYn11.
Rn+ Yn = RY
10. PERCENTAGE IMPEDANCE TEST : ( At Normal Tap )
Winding Shorted at L.V Side :- r, y, b shorted.
PHASE Current (A) Current (A) Average
Voltage (Volt) Remarks
REFERENCE HV Side LV Side %Z
R-Y 70.2 4.87 126.7
Y-B 71.3 5.16 133.2 5.004 OK
B-R 69.2 5.02 122.5

11. FUNCTIONAL CHECKS :


Alarms on
Devices Set Value Simulation Aux Relay Lock out Remarks
SER
Buchholz Trip NA By shorting NA NA OK OK
By moving
PRD Trip NA NA NA OK OK
PRD flag
By moving Circuit checked
OTI Alarm 85ºC NA NA NA
dial till panel
By moving
OTI Trip 90ºC NA NA OK OK
dial
By moving Circuit checked
WTI Alarm 85ºC NA NA NA
dial till panel
By moving
WTI Trip 90ºC NA NA OK OK
dial
Remarks :-i) PI Value of LV to EARTH Is Low But IR Value Is Ok.
ii) Rest Test result found satisfactory.