Trafo I p643
Trafo I p643
Trafo I p643
VI-IMSP-O&M-01-F02
1. Test Equipment’s:
NO. Device Name Device Type
1 Test kit make PONOVO
2 Type PW460
3 Version 2.5
4 Serial No IN127101202
3. General Check:
4. Measurement Test:
INJECTED
MEASURED VALUES (In terms of Primary
CURRENT(Amp)
Values)
R Y B
L1 0.218 0.292 36 39
L2 0.218 0.292 36 39
L3 0.218 0.292 36 38
L1,L2,L3 0.147 0.197 40 51
Injected current ( A )
S.NO STATUS Time (Sec)
HV SIDE LV SIDE
0.145∟0° 0.194 ∟180°
1. 0.145∟-120° 0.194∟60° Stable No –Trip
0.145∟+120° 0.194∟300°
0.145∟0° 0.194∟0° T
2. 0.145∟-120° 0.194∟60° Unstable rip
0.145∟+120° 0.194∟300°
8.SLOPE TEST:Is1=0.200
K1=30.0%
Is2=1.500
K2=80.0%
9. VOLT/HERTZ PROTECTION:
Ref Operated Voltage Set V /Hz Operating Set time Optd. Time
V/Hz (Sec)
R-Phase 146.05 at 50Hz 2.310 2.310 10.00 10.08
Y-Phase 146.05 at 50Hz 2.310 2.310 10.00 10.07
B-Phase 146.05 at 50Hz 2.310 2.310 10.00 10.09
Ref Operated Voltage Set V /Hz Operating V/Hz Set time Optd. Time (Sec)
INJECTED INJECTED
S.NO STAGES CURRENT CURRENT AT N STATUS
AT 50Hz TIMES OF 50 Hz
1. 2nd HARMONICS HV Side 1A AT 50HZ 0.211 AT 100HZ BLOCKING
2 5th HARMONICS HV Side 1A AT 50HZ 0.191 AT 100HZ TRIP
3. 2nd HARMONICS LV Side 1A AT 50HZ 0.350 AT 100HZ BLOCKING
4. 5th HARMONICS LV Side 1A AT 50HZ 0.340 AT 100HZ TRIP
REMARKS NO