Nothing Special   »   [go: up one dir, main page]

GWH 07 Agak 6 Dna 1 Ao

Download as pdf or txt
Download as pdf or txt
You are on page 1of 124

Change for life

Service Manual

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI


Table of Contents

Part Ⅰ : Technical Information................................... 2


1. Summary...........................................................................................2
2. Specifications...................................................................................4
2.1 Specification Sheet...................................................................................................4
2.2 Capacity Variation Ratio According to Temperature..................................14
2.3 Cooling and Heating Data Sheet in Rated Frequency................................15

3. Outline Dimension Diagram..........................................................16


3.1 Indoor Unit.................................................................................................................16
3.2 Outdoor Unit..............................................................................................................17

4. Refrigerant System Diagram.........................................................19


5. Electrical Part.................................................................................20
5.1 Wiring Diagram........................................................................................................20
5.2 PCB Printed Diagram.............................................................................................24

6. Function and Control.....................................................................31


6.1 Remote Controller Introduction.........................................................................31
6.2 GREE+ App Operation Manual...........................................................................36
6.3 Ewpe Smart App Operation Manual..................................................................37
6.4 Brief Description of Models and Functions...................................................38

Part Ⅱ : Installation and Maintenance ................. 40


7. Notes for Installation and Maintenance........................................40
8. Installation......................................................................................46
8.1 Installation Dimension Diagram.........................................................................46
8.2 Installation Parts-checking .................................................................................48
8.3 Selection of Installation Location......................................................................48
8.4 Electric Connection Requirement.....................................................................48
8.5 Installation of Indoor Unit.....................................................................................49

Table of Contents
8.6 Installation of Outdoor unit..................................................................................51
8.7 Vacuum Pumping and Leak Detection............................................................52
8.8 Check after Installation and Test operation...................................................53

9. Maintenance....................................................................................54
9.1 Error Code List.........................................................................................................54
9.2 Procedure of Troubleshooting...........................................................................59
9.3 Troubleshooting for Normal Malfunction.......................................................74

10. Exploded View and Parts List.....................................................76


10.1 Indoor Unit...............................................................................................................76
10.2 Outdoor Unit...........................................................................................................84

11. Removal Procedure......................................................................94


11.1 Removal Procedure of Indoor Unit.................................................................94
11.2 Removal Procedure of Outdoor Unit..............................................................99

Appendix.......................................................................... 119
Appendix 1: Reference Sheet of Celsius and Fahrenheit.............................. 119
Appendix 2: Configuration of Connection Pipe................................................ 119
Appendix 3: Pipe Expanding Method....................................................................120
Appendix 4: List of Resistance for Temperature Sensor...............................121

Table of Contents
1. Summary

Indoor Unit:

Outdoor Unit:

GWH07AGA-K6DNA1A/O GWH09AFC-K6DNA2F/O
GWH12AFC-K6DNA2F/O

GWH18AGD-K6DNA1E/O GWH24AFE-K6DNA2I/O

2 Technical Information
Remote Controller:
YAP1F7(WiFi)

ON/OFF
TURBO

FAN

MODE

I FEEL T-ON T-OFF

TEMP CLOCK

LIGHT WiFi SLEEP

Model list:

Indoor product Outdoor Remote


No Model Product code Indoor model
Outdoor model
code product code Controller
1 GWH07AGA-K6DNA1A CB385001100 GWH07AGA-K6DNA1A/I CB385N01100 GWH07AGA-K6DNA1A/O CB385W01100
2 GWH09AGC-K6DNA1F CB385009700 GWH09AGC-K6DNA1F/I CB385N09700 GWH09AFC-K6DNA2F/O CB363W02900
3 GWH09AGC-K6DNA1F CB385009701 GWH09AGC-K6DNA1F/I CB385N09700 GWH09AFC-K6DNA2F/O CB363W02901
4 GWH12AGC-K6DNA1F CB385009300 GWH12AGC-K6DNA1F/I CB385N09300 GWH12AFC-K6DNA2F/O CB363W03600
YAP1F7
5 GWH12AGC-K6DNA1F CB385009301 GWH12AGC-K6DNA1F/I CB385N09300 GWH12AFC-K6DNA2F/O CB363W03601
(WiFi)
6 GWH18AGD-K6DNA1E CB385009100 GWH18AGD-K6DNA1E/I CB385N09100 GWH18AGD-K6DNA1E/O CB385W09100
7 GWH18AGD-K6DNA1E CB385009101 GWH18AGD-K6DNA1E/I CB385N09100 GWH18AGD-K6DNA1E/O CB385W09101
8 GWH24AGE-K6DNA1A CB385007500 GWH24AGE-K6DNA1A/I CB385N07500 GWH24AFE-K6DNA2I/O CB363W04100
9 GWH24AGE-K6DNA1A CB385007501 GWH24AGE-K6DNA1A/I CB385N07500 GWH24AFE-K6DNA2I/O CB363W04101

Technical Information 3
2. Specifications
2.1 Specification Sheet
Model GWH07AGA-K6DNA1A
Product Code CB385001100
Rated Voltage V~ 220-240
Power
Rated Frequency Hz 50
Supply
Phases 1
Power Supply Mode Outdoor
Cooling Capacity W 2200
Heating Capacity W 2400
Cooling Power Input W 590
Heating Power Input W 590
Cooling Current Input A 2.9
Heating Current Input A 2.9
Rated Input W 1300
Rated Cooling Current A 5
Rated Heating Current A 6
Air Flow Volume m3/h 520/470/450/420/310/290/250
Dehumidifying Volume L/h 0.6
EER W/W 3.73
COP W/W 4.07
SEER W/W 6.6
SCOP(Average/WarmerColder) W/W 4/4.8/-
Application Area m2 10-16
Model GWH07AGA-K6DNA1A/I
Product Code CB385N01100
Fan Type Cross-flow
Fan Diameter Length(DXL) mm Φ93×505
Cooling Speed r/min 1300/1200/1120/1050/920/800/750
Heating Speed r/min 1300/1200/1120/1050/950/850/800
Fan Motor Power Output W 20
Fan Motor RLA A 0.22
Fan Motor Capacitor μF 1
Evaporator Form Aluminum Fin-copper Tube
Evaporator Pipe Diameter mm Φ5
Evaporator Row-fin Gap mm 2-1.4
Indoor Unit Evaporator Coil Length (LXDXW) mm 509×22.8×266.7
Swing Motor Model MP24AK/MP24BA/MP24HF
Swing Motor Power Output W 1.5/1.5/1.5
Fuse Current A 3.15
Cooling:39/37/34/33/29/25/21
Sound Pressure Level dB (A)
Heating:38/36/33/32/29/25/23
Cooling:55/49/46/45/41/37/33
Sound Power Level dB (A)
Heating:55/49/46/45/42/38/36

Dimension (WXHXD) mm 704X260X185

Dimension of Carton Box (LXWXH) mm 748X316X247


Dimension of Package (LXWXH) mm 753X332X258
Net Weight kg 7.5
Gross Weight kg 9

4 Technical Information
Outdoor Unit Model GWH07AGA-K6DNA1A/O
Outdoor Unit Product Code CB385W01100

Compressor Manufacturer ZHUHAI LANDA COMPRESSOR CO., LTD

Compressor Model QXF-N075zC170


Compressor Oil FW68DA
Compressor Type Rotary
Compressor LRA. A /
Compressor RLA A 3
Compressor Power Input W 633
Compressor Overload Protector /
Throttling Method Capillary
Set Temperature Range ºC 16~30
Cooling Operation Ambient
ºC -15~43
Temperature Range
Heating Operation Ambient
ºC -15~24
Temperature Range
Condenser Form Aluminum Fin-copper Tube
Condenser Pipe Diameter mm Φ7.94
Condenser Rows-fin Gap mm 1-1.2
Condenser Coil Length (LXDXW) mm 637×12.7×419
Fan Motor Speed rpm 950
Outdoor Fan Motor Power Output W 30
Unit
Fan Motor RLA A 0.35
Fan Motor Capacitor μF /
Outdoor Unit Air Flow Volume m3/h 1400
Fan Type Axial-flow
Fan Diameter mm 350
Defrosting Method /
Climate Type T1
Isolation I
Moisture Protection IPX4
Permissible Excessive Operating
MPa 4.3
Pressure for the Discharge Side
Permissible Excessive Operating
MPa 2.5
Pressure for the Suction Side
Sound Pressure Level (H/M/L) dB (A) 50
Sound Power Level (H/M/L) dB (A) 60
Dimension(WXHXD) mm 710X450X293
Dimension of Carton Box (LXWXH) mm 761X327X500
Dimension of Package(LXWXH) mm 764X330X525
Net Weight kg 21
Gross Weight kg 23
Refrigerant R32
Refrigerant Charge kg 0.4
Connection Pipe Length m 5
Connection Pipe Gas Additional Charge g/m 16
Outer Diameter Liquid Pipe 1/4"
Connection
Outer Diameter Gas Pipe 3/8"
Pipe
Max Distance Height m 10
Max Distance Length m 15
Note: The connection pipe applies metric diameter.
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Technical Information 5
Model GWH09AGC-K6DNA1F GWH09AGC-K6DNA1F
Product Code CB385009700 CB385009701
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Outdoor Outdoor
Cooling Capacity W 2700 2700
Heating Capacity W 3000 3000
Cooling Power Input W 695 695
Heating Power Input W 700 700
Cooling Current Input A 3.1 3.1
Heating Current Input A 3.2 3.2
Rated Input W 1400 1400
Rated Cooling Current A 6 6
Rated Heating Current A 6.2 6.2
Air Flow Volume m3/h 610/570/540/470/440/420/390 610/570/540/470/440/420/390//
Dehumidifying Volume L/h 1.69 1.69
EER W/W 3.885 3.88
COP W/W 4.286 4.29
SEER W/W 7.5 7.5
SCOP(Average/WarmerColder) W/W 4.2/5.3/3.4 4.2/5.3/3.4
Application Area m2 12-18 12-18
Model GWH09AGC-K6DNA1F/I GWH09AGC-K6DNA1F/I
Product Code CB385N09700 CB385N09700
Fan Type Cross-flow Cross-flow
Fan Diameter Length(DXL) mm Ф98×633.5 Ф98×633.5
Cooling Speed r/min 1200/1100/1050/950/900/850/750 1200/1100/1050/950/900/850/750
Heating Speed r/min 1150/1100/1050/1000/950/900/800 1150/1100/1050/1000/950/900/800
Fan Motor Power Output W 20 20
Fan Motor RLA A 0.31 0.31
Fan Motor Capacitor μF 1.5 1.5
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Evaporator Pipe Diameter mm Φ5 Φ5
Evaporator Row-fin Gap mm 2-1.4 2-1.4
Indoor Unit Evaporator Coil Length (LXDXW) mm 634×22.8×304.8 634×22.8×304.8
Swing Motor Model MP24BA/MP24AK/MP24HF MP24BA/MP24AK/MP24HF
Swing Motor Power Output W 1.5/1.5/1.5 1.5/1.5/1.5
Fuse Current A 3.15 3.15
Cooling:38/36/34/31/29/27/25 Cooling:38/36/34/31/29/27/25
Sound Pressure Level dB (A)
Heating:38/37/35/34/32/29/28 Heating:38/37/35/34/32/29/28
Cooling:54/48/46/43/42/39/37 Cooling:54/48/46/43/42/39/37
Sound Power Level dB (A)
Heating:56/49/47/46/44/41/40 Heating:56/49/47/46/44/41/40

Dimension (WXHXD) mm 825X293X196 825X293X196

Dimension of Carton Box (LXWXH) mm 870X349X257 870X349X257


Dimension of Package (LXWXH) mm 875X365X268 875X365X268
Net Weight kg 9.5 9.5
Gross Weight kg 11.5 11.5

6 Technical Information
Outdoor Unit Model GWH09AFC-K6DNA2F/O GWH09AFC-K6DNA2F/O
Outdoor Unit Product Code CB363W02900 CB363W02901
ZHUHAI LANDA COMPRESSOR ZHUHAI LANDA COMPRESSOR
Compressor Manufacturer
CO.,LTD CO.,LTD
Compressor Model QXF-A082zC170 QXF-A082zC170
Compressor Oil ZE-G;ES RB68GX or equivalent ZE-G;ES RB68GX or equivalent
Compressor Type Rotary Rotary
Compressor LRA. A 15 15
Compressor RLA A 2.56 2.56
Compressor Power Input W 756.6 756.6
Compressor Overload Protector / /
Throttling Method Capillary Capillary
Set Temperature Range ºC 16~30 16~30
Cooling Operation Ambient
ºC -15~50 -15~50
Temperature Range
Heating Operation Ambient
ºC -15~30 -25~30
Temperature Range
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Condenser Pipe Diameter mm Φ7 Φ7
Condenser Rows-fin Gap mm 1-1.2 1-1.2
Condenser Coil Length (LXDXW) mm 666×19.05×527 666×19.05×527
Fan Motor Speed rpm 900 900
Outdoor Fan Motor Power Output W 30 30
Unit
Fan Motor RLA A 0.4 0.4
Fan Motor Capacitor μF / /
Outdoor Unit Air Flow Volume m3/h 1950 1950
Fan Type Axial-flow Axial-flow
Fan Diameter mm 400 400
Defrosting Method Automatic Defrosting Automatic Defrosting
Climate Type T1 T1
Isolation I I
Moisture Protection IPX4 IPX4
Permissible Excessive Operating
MPa 4.3 4.3
Pressure for the Discharge Side
Permissible Excessive Operating
MPa 2.5 2.5
Pressure for the Suction Side
Sound Pressure Level (H/M/L) dB (A) 50 50
Sound Power Level (H/M/L) dB (A) 61 61
Dimension(WXHXD) mm 732X555X330 732X555X330
Dimension of Carton Box (LXWXH) mm 791X373X590 791X373X590
Dimension of Package(LXWXH) mm 794X376X615 794X376X615
Net Weight kg 23.5 23.5
Gross Weight kg 26 26
Refrigerant R32 R32
Refrigerant Charge kg 0.53 0.53
Connection Pipe Length m 5 5
Connection Pipe Gas Additional Charge g/m 16 16
Outer Diameter Liquid Pipe 1/4" 1/4"
Connection
Outer Diameter Gas Pipe 3/8" 3/8"
Pipe
Max Distance Height m 10 10
Max Distance Length m 15 15
Note: The connection pipe applies metric diameter.
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Technical Information 7
Model GWH12AGC-K6DNA1F GWH12AGC-K6DNA1F
Product Code CB385009300 CB385009301
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Outdoor Outdoor
Cooling Capacity W 3510 3510
Heating Capacity W 3810 3810
Cooling Power Input W 962 962
Heating Power Input W 953 953
Cooling Current Input A 4.3 4.3
Heating Current Input A 4.6 4.6
Rated Input W 1550 1550
Rated Cooling Current A 6.2 6.2
Rated Heating Current A 6.9 6.9
Air Flow Volume m3/h 680/620/560/490/450/420/390 680/620/560/490/450/420/390
Dehumidifying Volume L/h 1.4 1.4
EER W/W 3.649 3.649
COP W/W 3.998 3.998
SEER W/W 7.1 7.1
SCOP(Average/WarmerColder) W/W 4.1/5.2/3.1 4.1/5.2/3.1
Application Area m2 16-24 16-24
Model GWH12AGC-K6DNA1F/I GWH12AGC-K6DNA1F/I
Product Code CB385N09300 CB385N09300
Fan Type Cross-flow Cross-flow
Fan Diameter Length(DXL) mm Φ98×630 Φ98×630
Cooling Speed r/min 1300/1150/1100/1000 /950/850/750 1300/1150/1100/1000 /950/850/750
Heating Speed r/min 1250/1100/1050/1000/950/850/800 1250/1100/1050/1000/950/850/800
Fan Motor Power Output W 20 20
Fan Motor RLA A 0.31 0.31
Fan Motor Capacitor μF 1.5 1.5
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Evaporator Pipe Diameter mm Φ5 Φ5
Evaporator Row-fin Gap mm 2-1.4 2-1.4
Indoor Unit Evaporator Coil Length (LXDXW) mm 634×22.8×304.8 634×22.8×304.8
Swing Motor Model MP24BA/MP24AK/MP24HF MP24BA/MP24AK/MP24HF
Swing Motor Power Output W 1.5/1.5/1.5 1.5/1.5/1.5
Fuse Current A 3.15 3.15
Cooling:41/37/35/32/30/27/24 Cooling:41/37/35/32/30/27/24
Sound Pressure Level dB (A)
Heating:40/36/34/32/30/27/24 Heating:40/36/34/32/30/27/24
Cooling:56/49/47/44/42/39/36 Cooling:56/49/47/44/42/39/36
Sound Power Level dB (A)
Heating:51/46/44/42/40/37/34 Heating:51/46/44/42/40/37/34

Dimension (WXHXD) mm 825X293X196 825X293X196

Dimension of Carton Box (LXWXH) mm 870X349X257 870X349X257


Dimension of Package (LXWXH) mm 875X365X268 875X365X268
Net Weight kg 9.5 9.5
Gross Weight kg 11.5 11.5

8 Technical Information
Outdoor Unit Model GWH12AFC-K6DNA2F/O GWH12AFC-K6DNA2F/O
Outdoor Unit Product Code CB363W03600 CB363W03601
ZHUHAI LANDA COMPRESSOR ZHUHAI LANDA COMPRESSOR
Compressor Manufacturer
CO., LTD CO., LTD
Compressor Model FTz-AN108ACBD FTz-AN108ACBD
Compressor Oil FW68DA or equivalent FW68DA or equivalent
Compressor Type Rotary Rotary
Compressor LRA. A / /
Compressor RLA A 4.4 4.4
Compressor Power Input W / /
Compressor Overload Protector / /
Throttling Method Electron expansion valve Electron expansion valve
Set Temperature Range ºC 16~30 16~30
Cooling Operation Ambient
ºC -15~50 -15~50
Temperature Range
Heating Operation Ambient
ºC -25~30 -15~30
Temperature Range
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Condenser Pipe Diameter mm Φ7.94 Φ7.94
Condenser Rows-fin Gap mm 1-1.2 1-1.2
Condenser Coil Length (LXDXW) mm 666×19.05×527 666×19.05×527
Fan Motor Speed rpm 900 900
Outdoor Fan Motor Power Output W 30 30
Unit
Fan Motor RLA A 0.4 0.4
Fan Motor Capacitor μF / /
Outdoor Unit Air Flow Volume m3/h 1950 1950
Fan Type Axial-flow Axial-flow
Fan Diameter mm 400 400
Defrosting Method Automatic Defrosting Automatic Defrosting
Climate Type T1 T1
Isolation I I
Moisture Protection IPX4 IPX4
Permissible Excessive Operating
MPa 4.3 4.3
Pressure for the Discharge Side
Permissible Excessive Operating
MPa 2.5 2.5
Pressure for the Suction Side
Sound Pressure Level (H/M/L) dB (A) 52 52
Sound Power Level (H/M/L) dB (A) 63 63
Dimension(WXHXD) mm 732X555X330 732X555X330
Dimension of Carton Box (LXWXH) mm 791X373X590 791X373X590
Dimension of Package(LXWXH) mm 794X376X605 794X376X605
Net Weight kg 24.5 24.5
Gross Weight kg 27 27
Refrigerant R32 R32
Refrigerant Charge kg 0.57 0.57
Connection Pipe Length m 5 5
Connection Pipe Gas Additional Charge g/m 16 16
Outer Diameter Liquid Pipe 1/4" 1/4"
Connection
Outer Diameter Gas Pipe 3/8" 3/8"
Pipe
Max Distance Height m 10 10
Max Distance Length m 15 15
Note: The connection pipe applies metric diameter.
The above data is subject to change without notice. Please refer to the nameplate of the unit.

Technical Information 9
Model GWH18AGD-K6DNA1E GWH18AGD-K6DNA1E
Product Code CB385009100 CB385009101
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Outdoor Outdoor
Cooling Capacity W 5300 5300
Heating Capacity W 5600 5600
Cooling Power Input W 1501 1501
Heating Power Input W 1393 1393
Cooling Current Input A 7.2 7.2
Heating Current Input A 6.3 6.3
Rated Input W 2350 2350
Rated Cooling Current A 10 10
Rated Heating Current A 10.5 10.5
Air Flow Volume m3/h 1000/850/760/650/580/520/450 1000/850/760/650/580/520/450
Dehumidifying Volume L/h 1.9 1.9
EER W/W 3.53 3.53
COP W/W 4.02 4.02
SEER W/W 7.3 7.3
SCOP(Average/WarmerColder) W/W 4.2/5.7/3.5 4.2/5.7/3.5
Application Area m2 23-34 23-34
Model GWH18AGD-K6DNA1E/I GWH18AGD-K6DNA1E/I
Product Code CB385N09100 CB385N09100
Fan Type Cross-flow Cross-flow
Fan Diameter Length(DXL) mm Φ106×739 Φ106×739
Cooling Speed r/min 1300/1150/1030/960/800/700/650/500 1300/1150/1030/960/800/700/650/500
Heating Speed r/min 1300/1150/1040/950/900/880/800 1300/1150/1040/950/900/880/800
Fan Motor Power Output W 45 45
Fan Motor RLA A 0.25 0.25
Fan Motor Capacitor μF / /
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Evaporator Pipe Diameter mm Φ5 Φ5
Evaporator Row-fin Gap mm 2-1.3 2-1.3
Indoor Unit Evaporator Coil Length (LXDXW) mm 745×22.8×342.9 745×22.8×342.9
Swing Motor Model MP24AK/MP24BA/MP24HF MP24AK/MP24BA/MP24HF
Swing Motor Power Output W 1.5/1.5 /1.5 1.5/1.5 /1.5
Fuse Current A 3.15 3.15
Cooling:45/42/41/37/34/29/26/23 Cooling:45/42/41/37/34/29/26/23
Sound Pressure Level dB (A)
Heating:48/44/42/37/36/35/32 Heating:48/44/42/37/36/35/32
Cooling:60/55/54/50/47/42/39/36 Cooling:60/55/54/50/47/42/39/36
Sound Power Level dB (A)
Heating:60/57/55/50/49/48/45 Heating:60/57/55/50/49/48/45
Dimension (WXHXD) mm 982X311X221 982X311X221
Dimension of Carton Box (LXWXH) mm 1039X377X287 1039X377X287
Dimension of Package (LXWXH) mm 1044X385X297 1044X385X297
Net Weight kg 12.5 12.5
Gross Weight kg 15 15

10 Technical Information
Outdoor Unit Model GWH18AGD-K6DNA1E/O GWH18AGD-K6DNA1E/O
Outdoor Unit Product Code CB385W09100 CB385W09101
ZHUHAI LANDA COMPRESSOR ZHUHAI LANDA COMPRESSOR
Compressor Manufacturer
CO.,LTD CO.,LTD
Compressor Model QXF-A120zH170A QXF-A120zH170A
Compressor Oil FW68DA or equivalent FW68DA or equivalent
Compressor Type Rotary Rotary
Compressor LRA. A 18 18
Compressor RLA A 5 5
Compressor Power Input W 1096 1096
Compressor Overload Protector HPC115/95U1/KSD115ºC HPC115/95U1/KSD115ºC
Throttling Method Electron expansion valve Electron expansion valve
Set Temperature Range ºC 16~30 16~30
Cooling Operation Ambient
ºC -15~50 -15~50
Temperature Range
Heating Operation Ambient
ºC -15~30 -25~30
Temperature Range
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Condenser Pipe Diameter mm Φ7 Φ7
Condenser Rows-fin Gap mm 2-1.4 2-1.4
Condenser Coil Length (LXDXW) mm 895×38.1×528 895×38.1×528
Fan Motor Speed rpm 880 880
Outdoor Fan Motor Power Output W 30 30
Unit
Fan Motor RLA A 0.4 0.4
Fan Motor Capacitor μF / /
Outdoor Unit Air Flow Volume m3/h 2200 2200
Fan Type Axial-flow Axial-flow
Fan Diameter mm 420 420
Defrosting Method Automatic Defrosting Automatic Defrosting
Climate Type T1 T1
Isolation I I
Moisture Protection IPX4 IPX4
Permissible Excessive Operating
MPa 4.3 4.3
Pressure for the Discharge Side
Permissible Excessive Operating
MPa 2.5 2.5
Pressure for the Suction Side
Sound Pressure Level (H/M/L) dB (A) 56 56
Sound Power Level (H/M/L) dB (A) 65 65
Dimension(WXHXD) mm 802X555X350 802X555X350
Dimension of Carton Box (LXWXH) mm 869X395X594 869X395X594
Dimension of Package(LXWXH) mm 872X398X620 872X398X620
Net Weight kg 30.5 30.5
Gross Weight kg 33.5 33.5
Refrigerant R32 R32
Refrigerant Charge kg 0.85 0.85
Connection Pipe Length m 5 5
Connection Pipe Gas Additional Charge g/m 16 16
Outer Diameter Liquid Pipe 1/4" 1/4"
Connection
Outer Diameter Gas Pipe 1/2" 1/2"
Pipe
Max Distance Height m 10 10
Max Distance Length m 25 25
Note: The connection pipe applies metric diameter.
The above data is subject to change without notice. Please refer to the nameplate of the unit.

Technical Information 11
Model GWH24AGE-K6DNA1A GWH24AGE-K6DNA1A
Product Code CB385007500 CB385007501
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Outdoor Outdoor
Cooling Capacity W 7100 7100
Heating Capacity W 7800 7800
Cooling Power Input W 2030 2030
Heating Power Input W 2000 2000
Cooling Current Input A 9 9
Heating Current Input A 9.3 9.3
Rated Input W 3000 3000
Rated Cooling Current A 13 13
Rated Heating Current A 13.5 13.5
Air Flow Volume m3/h 1250/1100/1000/950/900/850/800/600 1250/1100/1000/950/900/850/800/600
Dehumidifying Volume L/h 2.4 2.4
EER W/W 3.5 3.5
COP W/W 3.9 3.9
SEER W/W 7 7
SCOP(Average/WarmerColder) W/W 4.2/5.4/3.4 4.2/5.4/3.4
2
Application Area m 27-42 27-42
Model GWH24AGE-K6DNA1A/I GWH24AGE-K6DNA1A/I
Product Code CB385N07500 CB385N07500
Fan Type Cross-flow Cross-flow
Fan Diameter Length(DXL) mm 108×830 108×830
Cooling Speed r/min 1250/1100/1000/950/900/850/800/600 1250/1100/1000/950/900/850/800/600
Heating Speed r/min 1400/1250/1100/1050/1000/900/850 1400/1250/1100/1050/1000/900/850
Fan Motor Power Output W 60 60
Fan Motor RLA A 0.24 0.24
Fan Motor Capacitor μF / /
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Evaporator Pipe Diameter mm φ7 φ7
Evaporator Row-fin Gap mm 2-1.4 2-1.4
Indoor Unit Evaporator Coil Length (LXDXW) mm 845×25.4×381 845×25.4×381
Swing Motor Model MP24HF/MP24AK/MP24HF MP24HF/MP24AK/MP24HF
Swing Motor Power Output W 1.5/1.5/1.5 1.5/1.5/1.5
Fuse Current A 3.15 3.15
Cooling:48/44/41/40/38/36/33/27 Cooling:48/44/41/40/38/36/33/27
Sound Pressure Level dB (A)
Heating:50/47/43/41/40/36/35 Heating:50/47/43/41/40/36/35
Cooling:64/59/56/55/53/51/48/42 Cooling:64/59/56/55/53/51/48/42
Sound Power Level dB (A)
Heating:64/62/58/56/55/51/50 Heating:64/62/58/56/55/51/50
Dimension (WXHXD) mm 1075X333X246 1075X333X246
Dimension of Carton Box (LXWXH) mm 1128X406X323 1128X406X323
Dimension of Package (LXWXH) mm 1133X414X333 1133X414X333
Net Weight kg 16 16
Gross Weight kg 19 19

12 Technical Information
Outdoor Unit Model GWH24AFE-K6DNA2I/O GWH24AFE-K6DNA2I/O
Outdoor Unit Product Code CB363W04100 CB363W04101
ZHUHAI LANDA COMPRESSOR ZHUHAI LANDA COMPRESSOR
Compressor Manufacturer
CO,LTD. CO,LTD.
Compressor Model QXFS-M180zX170 QXFS-M180zX170
Compressor Oil FW68DA or equivalent FW68DA or equivalent
Compressor Type Twin Rotary Twin Rotary
Compressor LRA. A 35 35
Compressor RLA A 3.5 3.5
Compressor Power Input W 1610 1610
Compressor Overload Protector KSD115ºC HPC 115/95U1 KSD115ºC HPC 115/95U1
Throttling Method Electron expansion valve Electron expansion valve
Set Temperature Range ºC 16~30 16~30
Cooling Operation Ambient
ºC -15~50 -15~50
Temperature Range
Heating Operation Ambient
ºC -15~30 -25~30
Temperature Range
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Condenser Pipe Diameter mm Φ7 Φ7
Condenser Rows-fin Gap mm 2-1.4 2-1.4
Condenser Coil Length (LXDXW) mm 839×38.1×616 839×38.1×616
Fan Motor Speed rpm 800 800
Outdoor Fan Motor Power Output W 60 60
Unit
Fan Motor RLA A 0.65 0.25
Fan Motor Capacitor μF / /
3
Outdoor Unit Air Flow Volume m /h 3600 3600
Fan Type Axial-flow Axial-flow
Fan Diameter mm 520 520
Defrosting Method Automatic Defrosting Automatic Defrosting
Climate Type T1 T1
Isolation I I
Moisture Protection IPX4 IPX4
Permissible Excessive Operating
MPa 4.3 4.3
Pressure for the Discharge Side
Permissible Excessive Operating
MPa 2.5 2.5
Pressure for the Suction Side
Sound Pressure Level (H/M/L) dB (A) 59 59
Sound Power Level (H/M/L) dB (A) 70 70
Dimension(WXHXD) mm 958X660X402 958X660X402
Dimension of Carton Box (LXWXH) mm 1029X453X715 1029X453X715
Dimension of Package(LXWXH) mm 1032X456X737 1032X456X737
Net Weight kg 41.5 41.5
Gross Weight kg 46 46
Refrigerant R32 R32
Refrigerant Charge kg 1.5 1.5
Connection Pipe Length m 5 5
Connection Pipe Gas Additional Charge g/m 40 40
Outer Diameter Liquid Pipe 1/4" 1/4"
Connection
Outer Diameter Gas Pipe 5/8" 5/8"
Pipe
Max Distance Height m 10 10
Max Distance Length m 25 25
Note: The connection pipe applies metric diameter.
The above data is subject to change without notice. Please refer to the nameplate of the unit.

Technical Information 13
2.2 Capacity Variation Ratio According to Temperature
GWH07AGA-K6DNA1A
Cooling Heating

120 140

100 120

100
80
80
60
Condition 60
Indoor:DB27°C WB19°C Conditions
40 Indoor air flow: High
Pipe length:5m 40 Indoor:DB20°C
Indoor air flow:Super High
20 20 Pipe length:5m

0 0
-7 2 21
-15 -10 -5 0 5 10 15 20 25 30 35 40 43 -15 -10 -5 0 5 10 15 20 24

Heating operation ambient temperature range is -15ºC~30ºC


Cooling Heating

120 120
24K
18K 24K
100 18K 100

80 80
9/12K 9/12K
60 60
Condition
Indoor:DB27°C WB19°C Conditions
40 Indoor air flow: High 40
Indoor:DB20°C
Pipe length:5m
Indoor air flow:Super High
20 20 Pipe length:5m

0 0
-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 -15 -10 -5 0 5 10 15 20 25 30

Heating operation ambient temperature range is -25ºC~30ºC


Cooling Heating
120 120
24K
18K 24K
100 18K 100

80 80
9/12K
9/12K
60 60
Condition Conditions
Indoor:DB27°C WB19°C
40 40 Indoor:DB20°C
Indoor air flow: High
Pipe length:5m Indoor air flow:Super High
Pipe length:5m
20 20

0 0
-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 -25 -20 -15 -10 -5 0 5 10 15 20 25 30

14 Technical Information
2.3 Cooling and Heating Data Sheet in Rated Frequency
Cooling:

Pressure of gas pipe connecting Inlet and outlet pipe temperature of


Rated cooling condition(°C) (DB/WB)
indoor and outdoor unit heat exchanger Fan speed of Fan speed of
Model
indoor unit outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)

27/19 35/24 7/9K 0.8~1.1 12 ~ 15 65 ~ 38 Super High High


27/19 35/24 12K 0.9~1.1 12 ~ 14 75 ~ 37 Super High High
27/19 35/24 18K 0.9~1.1 12 ~ 14 75 ~ 37 Super High High
27/19 35/24 24K 0.9~1.1 12 ~ 14 75 ~ 37 Super High High

Heating:

Pressure of gas pipe connecting Inlet and outlet pipe temperature of


Rated heating condition(°C) (DB/WB)
indoor and outdoor unit heat exchanger Fan speed of Fan speed of
Model
indoor unit outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)

20/- 7/6 7/9K 2.8~3.2 63 ~ 35 2~5 Super High High


20/- 7/6 12K 2.2~2.4 70 ~ 35 2~4 Super High High
20/- 7/6 18K 2.2~2.4 70 ~ 40 1~5 Super High High
20/- 7/6 24K 2.2~2.4 70 ~ 35 2~4 Super High High

Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5 m.

Technical Information 15
3. Outline Dimension Diagram
3.1 Indoor Unit
W D

H
AGA W1 W2 W3

Φ55

42 42
75 75
W1 W2 W3
AGC

Φ55
43

116 155
W1 W2 W3
AGD

Φ55
40
40

Unit:mm
178 89
AGE W1 W2 W3

Φ70
43

175 60

Model W H D W1 W2 W3
AGA 704 260 185 93 462 149
AGC 825 293 196 113 542 170
AGD 982 311 221 122.5 707.5 152
AGE 1075 333 246 184 707.5 183.5
* Recommended distance

16 Technical Information
3.2 Outdoor Unit
GWH07AGA-K6DNA1A/O
244 650

450

293 710

272
Unit:mm 430

GWH09AFC-K6DNA2F/O GWH12AFC-K6DNA2F/O
285 675
555

330 732

455
310

Unit:mm

Technical Information 17
GWH18AGD-K6DNA1E/O
300 745

555

350 802

332
Unit:mm
512

GWH24AFE-K6DNA2I/O
340 889
660

402 958
371

Unit:mm
570

18 Technical Information
4. Refrigerant System Diagram COOLING

7/9K

Indoor unit Outdoor unit

Gas pipe
side
Valve
4-Way valve

Discharge

Heat Suction Accumlator


exchanger
Compressor
(evaporator)
Heat
exchanger
Liquid pipe (condenser)
side
Valve
Strainer Capillary Strainer

COOLING
HEATING

Connection pipe specification:


Liquid pipe:1/4"
Gas pipe:3/8"

12/18/24K
Indoor unit Outdoor unit

Gas pipe
side
Valve
4-Way valve

Discharge

Heat Suction
exchanger Accumlator
Compressor
(evaporator)
Heat
exchanger
Liquid pipe (condenser)
side
Valve Electric
Strainer Strainer
expand
valve
COOLING
HEATING

Connection pipe specification:


Liquid pipe:1/4"
Gas pipe:3/8" (12K),1/2" (18K),5/8" (24K)

Technical Information 19
5. Electrical Part
5.1 Wiring Diagram
●Instruction

Symbol Symbol Color Symbol Symbol Color Symbol Name

WH White GN Green CAP Jumper cap

YE Yellow BN Brown COMP Compressor

RD Red BU Blue Grounding wire

YEGN Yellow/Green BK Black / /

VT Violet OG Orange / /

Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.

● Indoor Unit
GWH07AGA-K6DNA1A/I

TUBE ROOM OPTIONAL OPTIONAL


TEMP. TEMP. RECEIVER AND FAN MOTOR WIRED DRY
SENSORSENSOR DISPLAY BOARD CONTROLLER CONTACT

AP1 DISPLAY
M1 AP3 AP4
θ θ
PE
RT1 RT2
EVAPORATOR
YEGN
T-SENSOR DISP PG PGF COM-MANUAL (DRY-C) PE
DOOR-C EARTH-PLATE
CAP YEGN
AP2 XT
OUTDOOR UNIT

JUMP PRINTED CIRCUIT BOARD BU N(1) BU


N(N1)
BK BK
COM-OUT 2
BN BN
SWING-UD1 SWING-UD2 AC-L 3
SWING-LR HEALTH CONNECTING
TERMINAL CABLE
BLOCK
M2 M3
M4
PLASMACLUSTER
UP-DOWN UP-DOWN LEFT-RIGHT ION
STEPPING STEPPING STEPPING
MOTOR MOTOR MOTOR
OPTIONAL OPTIONAL 600007063739

20 Technical Information
GWH09AGC-K6DNA1F/I GWH12AGC-K6DNA1F/I

TUBE ROOM OPTIONAL OPTIONAL


TEMP. TEMP. RECEIVER AND FAN MOTOR WIRED GATE
SENSORSENSOR DISPLAY BOARD CONTROLLER CONTROL

AP1 DISPLAY
M1 AP3 AP4
θ θ
RT1 RT2

T-SENSOR DISP PG PGF COM-MANUAL (DRY-C)


TERMINAL
DOOR-C
BLOCK
CAP BU N(1)
BU
AP2 N(N1)

OUTDOOR UNIT
BK BK
JUMP PRINTED CIRCUIT BOARD COM-OUT 2
BN 3 BN
AC-L
YEGN
SWING-UD1 SWING-UD2 CONNECTING
SWING-LR HEALTH YEGN XT CABLE
PE
EVAPORATOR
M2 M3
M4
PLASMACLUSTER
UP-DOWN UP-DOWN LEFT-RIGHT ION
STEPPING STEPPING STEPPING
MOTOR MOTOR MOTOR
OPTIONAL OPTIONAL 600007063888

GWH18AGD-K6DNA1E/I GWH24AGE-K6DNA1A/I

TUBE ROOM
TEMP. TEMP. RECEIVER AND OPTIONAL
SENSOR SENSOR DISPLAY BOARD LEFT-RIGHT
STEPPING FAN MOTOR WIRED
AP1 DISPLAY MOTOR CONTROLLER
θ θ M1
M4
RT1 RT2

TERMINAL
T-SENSOR DISP SWING-LR DC-MOTOR COM-MANUAL BLOCK
BU BU
OUTDOOR UNIT

CAP N N(1)
BK
AP2 COM-OUT 2
BK
JUMP PRINTED CIRCUIT BOARD BN BN
AC-L 3
YEGN YEGN YEGN
E
SWING-UD1 SWING-UD2 (DRY-C) CONNECTING
DOOR-C HEALTH XT CABLE
PE
EVAPORATOR
M2 M3

PLASMACLUSTER
UP-DOWN UP-DOWN DRY ION
STEPPING STEPPING CONTACT
MOTOR MOTOR OPTIONAL 60000706411701
OPTIONAL

Technical Information 21
● Outdoor Unit
GWH07AGA-K6DNA1A/O

OPTIONAL OPTIONAL OPTIONAL


WARNING
OUTTUBE OUTROOM EXHAUST 4-WAY Bottom ELECTRONIC
Please don't touch any terminal Band EXPANSION
TEMP. TEMP. TEMP. VALVE
when the machine is running , SENSOR SENSOR SENSOR Heater VALVE
stopping or has been powered off 4YV EKV
for less than 30 minutes to prevent 20K 15K 50K VT (YE) EH1
the risk of electric shock ! RT1 RT2 RT3
VT(YE)

T-SEN 4WAY HEAT-B FA


XT MAGNETIC RING
BU
BU L2
N(1)
INDOOR UNIT

N
BK BK L2 AP: Main Board
2 COMU(COM-IN)
BN BN L2
L(3) AC_L(AC-L)
YEGN
TERMINAL YEGN E CN1 OFAN
BLOCK
LX1-2 LX1-1
BU PE
N
BN(BK) L1 L1 L1
MAGNETIC

L OG WH M
RING

YEGN L
BU YE RD
POWER REACTOR FAN
U V W OPTIONAL MOTOR
COMP
600007064715

GWH09AFC-K6DNA2F/O GWH12AFC-K6DNA2F/O

WARNING OPTIONAL OPTIONAL OPTIONAL


Please don't touch any terminal OUTTUBE OUTROOM EXHAUST 4-WAY Bottom ELECTRONIC
TEMP. TEMP. TEMP. VALVE Band EXPANSION
when the machine is running , VALVE
SENSOR SENSOR SENSOR Heater
stopping or has been powered off
4YV EKV
for less than 30 minutes to prevent 20K 15K 50K EH1
the risk of electric shock ! RT1 RT2 RT3 VT VT

MAGNETIC RING
XT
BU BU L2 T-SEN 4WAY HEAT-B FA
N(1) N
BK BK L2
2 COMU(COM-IN) AP: Main Board
INDOOR UNIT

BN BN L2
L(3) AC_L(AC-L)
YEGN CN2 OFAN
TERMINAL YEGN
BLOCK E

BU BU RD
N YE
MAGNETIC

L BN(BK)
L1 L1
RING

YEGN PE L1
M YEGN
ELECTRICAL
POWER BOX PE
BU YE RD
FAN PE
V W MOTOR
U
COMP NOTE: Motor ground only applies
to the iron shell motor.
COMP. 600007064727

22 Technical Information
GWH18AGD-K6DNA1E/O GWH24AFE-K6DNA2I/O

WARNING OPTIONAL OPTIONAL


Please don't touch any terminal OUTTUBE OUTROOM EXHAUST BOTTOM ELECTRONIC
when the machine is running , TEMP. TEMP. TEMP. BAND EXPANSION
stopping or has been powered off SENSOR SENSOR SENSOR HEATER VALVE
for less than 30 minutes to prevent 20K 15K 50K EH1 EKV
the risk of electric shock ! RT1 RT2 RT3

XT MAGNETIC RING
BU BU L2
N(1) N T-SENSOR(T-SEN) HEAT-B FA
INDOOR UNIT

BK BK L2
2 COM-INNER (COM-IN) AP1: PRINTED CIRCUIT BOARD
BN BN L2
L(3) AC-L
YEGN YEGN CN2 OVC-COMP 4WAY OFAN
TERMINAL E
PE BLOCK
BU PE
N VT VT
MAGNETIC

L BN(BK)
L1 L1 L1 WH WH
RING

YEGN
4YV M
POWER PE
BU YE RD SAT 4-WAY
FAN
V W VALVE
U MOTOR
COMP OVERLOAD OPTIONAL
PROTECTOR

COMP. OPTIONAL 600007065005

These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.

Technical Information 23
5.2 PCB Printed Diagram
Indoor Unit
GWH07AGA-K6DNA1A/I

5 6 7 8 9 10 11

4 12

13

14

15

16

No. Name No. Name

1 Communication interface 9 Up&down 1 swing interface

Terminal of live wire used for


2 10 Left&right swing interface
supplying power for outdoor unit

3 Fuse 11 Interface of PG feedback

4 Live wire 12 Display board

Needle stand for tube


5 Neutral wire 13
temperature sensor

6 Interface of PG motor 14 Jump

7 Interface of health function 15 Interface of gate-control

8 Up&down 2 swing interface 16 Wired controller

24 Technical Information
GWH09AGC-K6DNA1F/I GWH12AGC-K6DNA1F/I

3 4 5 6 7 8 9 16

10

11
15

1
12

13

14

No. Name No. Name

1 Communication interface 9 Left&right swing interface

2 Live wire 10 Terminal for display board

3 Interface of PG motor 11 Needle stand for temperature sensor

4 Interface of neutral wire 12 Interface of gate-control

5 Fuse 13 Wired controller

6 Interface of health function 14 Jumper cap

7 Up&down swing interface 2 15 Output terminal of live wire

8 Up&down swing interface 1 16 Interface of PG feedback

Technical Information 25
GWH18AGD-K6DNA1E/I GWH24AGE-K6DNA1A/I

3 4 5 6 7 8

15
10

11

12

14

13

No. Name No. Name

1 Fuse 9 Up&down swing 1

2 Live wire 10 Interface of display board

3 Neutral wire 11 Temperature sensor

4 Dommunication wire 12 Door control

5 DC fan 13 Wired controller

6 Cold plasma 14 Earthing wire

7 Left&right swing 15 Terminal of live wire

8 Up&down swing 2

26 Technical Information
Outdoor Unit
GWH07AGA-K6DNA1A/O
1 2 3

14

5 6 7 8 9 10 11 12 13 14
5

10

11

12

13

No. Name No. Name

1 E store 8 4-way valve

2 Electronic expansion valve 9 Neutral wire

3 Overload 10 communication cable

4 Temperature sensor 11 Live wire

5 Outdoor fan 12 Earthing wire

6 DRED(preliminary) 13 Fuse

7 Electric heating belt of chasssis 14 Three-phase terminal of compressor

Technical Information 27
GWH09AFC-K6DNA2F/O GWH12AFC-K6DNA2F/O

5 6 7

No. Name

1 Earthing wire

2 Neutral wire, live wire and communication cable

3 4-way valve

4 Electric heating belt of chassis

5 Outdoor fan

6 Electronic expansion valve

7 Temperature sensor

8 Three-phase terminal of compressor

28 Technical Information
GWH18AGD-K6DNA1E/O

2
3

14

8 9 10 11 12 13

No. Name No. Name

1 Earthing wire 8 Outdoor fan

2 Live wire 9 DRED(preliminary)

3 Neutral wire 10 Electronic expansion valve

4 communication cable 11 Overload

5 4-way valve 12 Temperature sensor

6 Electric heating belt of chassis 13 EE flash drive

7 DRED-DC(preliminary) 14 Three-phase terminal of compressor

Technical Information 29
GWH24AFE-K6DNA2I/O

5 6 7 8 9 10 11 12 13 14

15

16
3

2
1

No. Name No. Name

1 Terminal of electronic expansion valve 9 4-way valve

2 E disk(Reserved) 10 Electric heating belt of chassis

3 Computer monitoring interface 11 2-way valve

4 EE flash drive 12 DC motor

5 Grounding wire 13 Temperature sensor

6 Live wire 14 Overload interface of compressor

7 Neutral wire 15 Terminal of compressor

8 Communication wire 16 Interface of program debugs

30 Technical Information
6. Function and Control
6.1 Remote Controller Introduction
NOTE:
● This is a general use remote controller. It could be used for the air conditioner with multifunction. For the functions which the model
doesn't have, if press the corresponding button on the remote controller, the unit will keep the original running status.
● After putting through the power, the air conditioner will give out a sound. Power indicator " " iis ON. After that, you can operate the
air conditioner by using remote controller.
● Under on status, pressing the button on the remote controller, the signal icon " " on the display of remote controller will blink once
and the air conditioner will give out a " di " sound, which means the signa has been sent to the air conditioner.
● As for the models with functions of WiFi or wired controller, the indoor unit must has been controlled by standard remote controller
under auto mode first, and then the function of adjustable temperature under auto mode can be realized by APP or the wired controller.
● This remote controller can adjust the temperature under auto mode. When matching with the unit which is without the function of
adjustable temperature under auto mode, the set temperature under auto mode may be invalid, or the displayed set temperature on
the unit is not same as that on the remote controller under auto mode.

ON/OFF
Press this button to turn on the unit. Press this button again
to turn off the unit.

MODE

Press this button to select your required operation mode.


AUTO COOLD RY FAN HEAT

ON/OFF

● When selecting auto mode, air conditioner will operate


automatically according to ex-factory setting. Press "FAN"
TURBO

FAN

MODE
button can adjust fan speed. Press " " / " " button can
adjust fan blowing angle.
● After selecting cool mode, air conditioner will operate under
I FEEL T-ON T-OFF cool mode. Cool indicator " " on indoor unit is ON. (This
TEMP CLOCK indicator is not available for some models.) Press " " or " "
LIGHT WiFi SLEEP button to adjust set temperature. Press "FAN" button to adjust
fan speed. Press " " / " " button to adjust fan blowing
angle.
Introduction for icons on display screen ● When selecting dry mode, the air conditioner operates
I feel
at low speed under dry mode. Dry indicator " " on indoor
Set fan speed
unit is ON. (This indicator is not available for some models.)
Turbo mode
Send signal Under dry mode, fan speed can’t be adjusted. Press " "/
Auto mode " "button to adjust fan blowing angle.
Operation mode

Cool mode
● When selecting fan mode, the air conditioner will only blow
Dry mode
Fan mode fan, no cooling and no heating. All indicators are OFF. Press
Heat mode "FAN" button to adjust fan speed. Press " " / " " button to
Sleep mode
adjust fan blowing angle.
8 heating function
Health mode ● When selecting heating mode, the air conditioner operates
Scavenging function under heat mode. Heat indicator " " on indoor unit is ON.
Quiet
(This indicator is not available for some models.) Press " "
X-FAN function
Set temp.
or " " button to adjust set temperature. Press "FAN" button
Indoor ambient to adjust fan speed. Press " " / " " button to adjust fan
Temp. temp.
display type blowing angle. (Cooling only unit won’t receive heating mode
Outdoor ambient
temp. signal. If setting heat mode with remote controller, press ON/
Clock
OFF button can’t start up the unit).
Set temperature
WiFi function NOTE:
Set time ● For preventing cold air, after starting up heat mode, indoor
TIMER ON / TIMER OFF unit will delay 1~5 minutes to blow air (actual delay time
Left & right swing
depends on indoor ambient temperature).
Up & down swing
Child lock

Technical Information 31
● Set temperature range from remote controller: 16~30OC(61- NOTE:
86O C ). Fan speed: auto,quiet,low speed, low-medium ● Press this button continuously more than 2s, the main unit
speed,medium speed,medium-high speed, high speed. will swing back and forth from left to right, and then loosen
● This mode indicator is not available for some models. the button, the unit will stop swinging and present position of
guide louver will be kept immediately.
FAN ● Under left and right swing mode, when the status is
switched from off to , if press this button again 2s later,
This button is used for setting Fan Speed in the sequence status will switch to off status directly; if press this button
that goes from AUTO, , , , , to , then again within 2s, the change of swing status will also depend
back to Auto. on the circulation sequence stated above.
NOTE: ● The function is only available for some models.
● Under AUTO speed, air conditioner will select proper fan
speed automatically according to factory default setting.
● It's low fan speed under dry mode.
● X-FAN function: Holding fan speed button for 2s in cool
or dry mode, the icon " " is displayed and the indoor fan Press this button can select up & down swing angle. Fan blow
will continue operation for a few minutes in order to dry the angle can be selected circularly as below:
indoor unit even though you have turned off the unit. After
energization, X-FAN OFF is defaulted. X-FAN is not available no display
(horizontal louvers stops
in auto, fan or heat mode. at current position)
This function indicates that moisture on evaporator of indoor
unit will be blowed after the unit is stopped to avoid mould. ● When selecting " ", air conditioner is blowing fan
● Having set X-FAN function on: After turning off the unit by automatically. Horizontal louver will automatically swing up &
pressing ON/OFF button, indoor fan will continue running for down at maximum angle.
a few minutes at low speed. In this period, hold fan speed ● When selecting " 、 、 、 、 ", air conditioner
button for 2s to stop indoor fan directly. is blowing fan at fixed position. Horizontal louver will stop at
Having set X-FAN function off: After turning off the unit by the fixed position.
pressing ON/OFF button, the complete unit will be off directly. ● When selecting " 、 、 ", air conditioner is blowing
fan at fixed angle. Horizontal louver will send air at the fixed
angle.
● Hold " "button above 2s to set your required swing angle.
When reaching y our required angle, release the button.
TURBO NOTE:
● “ 、 、 " may not be available. When air conditioner
Under COOL or HEAT mode, press this button to turn to quick
receives this signal, the air conditioner will blow fan
COOL or quick HEAT mode. " " icon is displayed on remote
automatically.
controller. Press this button again to exit turbo function and
● Press this button continuously for more than 2s, the main
" " icon will disappear. If start this function, the unit will
unit will swing back and forth from up to down, and then
run at super-high fan speed to cool or heat quickly so that
loosen the button, the unit present position of guide louver will
the ambient temp.approachs the preset temp. as soon as
be kept immediately.
possible.
● Under up and down swing mode, when the status is
switched from off to , if press this button again 2s later, status
/ will switch to off status directly; if press this button again
within 2s, the change of swing status will also depend on the
● Press " " or " " button once increase or decrease set circulation sequence stated above.
temperature 1OC (°F). Holding " " or " " button, 2s later,
set temperature on remote controller will change quickly. On
releasing button after setting is finished, temperature indicator
on indoor unit will change accordingly. T-ON T-OFF
● When setting T-ON, T-OFF or CLOCK, press " " or "
"button to adjust time. (Refer to CLOCK, TON, T-OFF buttons) ● T-ON button
"T-ON" button can set the time for timer on. After pressing this
button, " " icon disappears and the word "ON" on remote
controller blinks. Press " " or " " button to adjust T-ON
Press this button can select left & right swing angle. Fan blow
setting. After each pressing " " or " " button, T-ON setting
angle can be selected circularly as below:
will increase or decrease 1min. Hold " " or " " button, 2s
later, the time will change quickly until reaching your required
no display time. Press "T-ON" to confirm it. The word "ON" will stop
(stops at current
position)

32 Technical Information
blinking. " " icon resumes displaying. Cancel T-ON: Unde Otherwise, remote controller will quit setting status. Operation
the condition that T-ON is started up, press "T-ON " button to for TIMER ON/TIMER OFF is the same.
cancel it.
● T-OFF button
"T-OFF" button can set the time for timer off. After pressing
SLEEP
this button, " " icon disappears and the word "OFF" on
remote controller blinks. Press " " or " " button to adjust ● Press this button, can select Sleep 1 ( 1), Sleep 2 ( 2),
T-OFF setting. After each pressing " " or " " button, T-OFF Sleep 3 ( 3) and cancel the Sleep, circulate between these,
setting will increase or decrease 1min. Hold " " or " "button, after electrified, Sleep Cancel is defaulted.
2s later, the time will change quickly until reaching your ● Sleep 1 is Sleep mode 1, in Cool modes; sleep status
required time. Press "T-OFF" word "OFF" will stop blinking. after run for one hour, the main unit setting temperature will
" " icon resumes displaying. Cancel T-OFF. Under the increase 1 , two hours, setting temperature increased 2OC,
condition that T-OFF is started up, press "T-OFF" button to then the unit will run at this setting temperature; In Heat mode:
cancel it. sleep status after run for one hour, the setting temperature
NOTE: will decrease 1 , two hours, setting temperature will decrease
● Under on and off status, you can set T-OFF or T-ON 2 , then the unit will run at this setting temperature.
simultaneously. ● Sleep 2 is sleep mode 2, that is air conditioner will run
● Before setting T-ON or T-OFF, please adjust the clock time. according to the presetting a group of sleep temperature
● After starting up T-ON or T-OFF,set the constant circulating curve.
valid. ● Sleep 3-the sleep curve setting under Sleep mode by DIY;
After that,air conditioner will be turned on or turned off (1) Under Sleep 3 mode, press “TURBO” button for a long
according to setting time.ON/OFF button has no effect on time, remote controller enters into user individuation sleep
setting.If you don’t need this function, please use remote setting status, at this time, the time of remote controller will
controller to cancel it. display “1hour”, the setting temperature “88” will display the
corresponding temperature of last setting sleep curve and
blink (The first entering will display according to the initial
I FEEL curve setting value of original factory);
(2) Adjust “ ” and “ ” button, could change the corresponding
Press this button to start I FEEL function and " " will be setting temperature, after adjusted, press “TURBO” button for
displayed on the remote controller. After this function is confirmation;
set, the remote controller will send the detected ambient (3) At this time, 1hour will be automatically increased at the
temperature to the controller and the unit will automatically timer position on the remote control, (that are "2hours" or
adjust the indoor temperature according to the detected "3hours" or "8hours"), the place of setting temperature "88"
temperature. Press this button again to cancel I FEEL function will display the corresponding temperature of last setting sleep
and " " will disappear. curve and blink;
● Please put the remote controller near user when this (4) Repeat the above step (2)~(3) operation, until 8 hours
function is set. Do not put the remote contro ller near the temperature setting finished, sleep,curve setting finished, at
object of high temperature or low temperature in order to this time, the remote controller will resume the original timer
avoid detecting inaccurate amb ient temperature. display; temperature display will resume to original setting
When I FEEL function is turned on, the remote controller temperature.
should be put within the area where indoor unit can receive ● Sleep3- the sleep curve setting under Sleep mode by DIY
the signal sent by the remote controller. could be inquired:
The user could accord to sleep curve setting method to inquire
the presetting sleep curve, enter into user individuation sleep
setting status, but do not change the temperature, press
CLOCK "TURBO" button directly for confirmation. Note: In the above
presetting or enquiry procedure, if continuously within 10s,
Press this button to set clock time. " " icon on remote there is no button pressed, the sleep curve setting within 10s,
controller will blink. Press " " or " " button within 5s to set there is no button pressed, the sleep curve setting status
clock time. Each pressing of " " or " " button, clock time will be automatically quit and resume to display the original
will increas e or decrease 1 minute.If hold " " or " " button, displaying. In the presetting or enquiry procedure, press "ON/
2s later, time will change quickly. Release this button when OFF" button, "MODE" button, "SLEE" button, the sleep curve
reaching your required time. Press "CLOCK" button to confirm setting or enquiry status will quit similarly.
the time. " " icon stops blinking.
NOTE:
● Clock time adopts 24-hour mode.
● The interval between two operations can't exceed 5s.

Technical Information 33
WiFi ● Sleep function and energy-saving function can't operate at
the same time. If energy-saving function has been set under
Press " WiFi " button to turn on WiFi function, " WiFi " icon will cool mode, press "SLEEP" button will cancel energy-saving
be displayed on the remote controller; Hold " WiFi " button for function. If sleep function has been set under cool mode, start
5s to turn off WiFi function and " WiFi " icon will disappear. up the energy-saving function will cancel sleep function.
Under off status, press "MODE" and " WiFi " buttons
simultaneously for 1s, WiFi module will restore factory
settings. 8OC heating function(This function is not available for
cool only models.)
Under heat mode, press "TEMP" and "CLOCK" buttons
simultaneously to start up or turn off 8OC heating function.
When this function is started up, " " and "8OC" will be
Press this button to achieve the on and off of health and
shown on remote controller, and the air conditioner keep the
scavenging functions in operation station. Press this button for
heating status at 8OC. Press "TEMP" and "CLOCK" buttons
the first time to start scavenging function; LCD displays
simultaneously again to exit 8OC heating function.
" ". Press the button for the second time to start health and
NOTE:
scavenging functions simultaneously; LCD displays
● Under 8OC heating function, fan speed is defaulted at auto
" " and " ". Press this button for the third time to quit
speed and it can't be adjusted.
health and scavenging functions simultaneously. Press the
● Under 8O C heating function, set temperature can't be
button for the fourth time to start health function; LCD display
adjusted. Press "TURBO" button and the remote controller
" ". Press this button again to repeat the operation above.
won't send signal.
● This function is applicable to partial of models .
● Sleep function and 8OC heating function can't operate at the
same time. If 8OC heating function has been set under heat
LIGHT
mode, press "SLEEP" button will cancel 8OC heating function.
If sleep function has been set under heat mode, start up the
Press this button to turn off display light on indoor unit. " " 8OC heating function will cancel sleep function.
icon on remote controller disappears. ● Under OF temperature display, the remote controller will
Press this button again to turn on display light. " " icon is display 46OF heating.
displayed.

TEMP
Child lock function
Press this button, you can see indoor set temperature, indoor Press “ ” and “ ” simultaneously to turn on or turn off child
ambient temperature on indoor unit' s display. The setting on lock function. When child lock function is on, " " icon is
remote controller is selected circularly as below: displayed on remote controller. If you operate the remote
controller, the " " icon will blink three times without sending
no display
signal to the unit.

Temperature display switchover function


Function introduction for combination
buttons Under OFF status, press " " and "MODE" buttons
simultaneously to switch temperature display between OC and
Energy-saving function OF.
Under cooling mode, press "TEMP" and "CLOCK" buttons
simultaneously to start up or turn off energy-saving function. Auto clean function
When energy-saving function is started up, "SE" will be shown Under unit off status, hold "MODE" and "FAN" buttons
on remote controller, and air conditioner will adjust the set simultaneously for 5s to turn on or turn off the internal clean
temperature automatically according to ex-factory setting to function. When the internal clean function is turned on,
reach to the best energy-saving effect. indoor unit displays “CL” . During the self-cleaning process of
Press "TEMP" and "CLOCK" buttons simultaneously again to evaporator, the unit will perform fast cooling or fast heating.
exit energy-saving function. There may be some noise, which is the sound of flowing liquid
or thermal expansion or cold shrinkage. The air conditioner
NOTE: may blow cool or warm air, which is a normal phenomenon.
● Under energy-saving function, fan speed is defaulted at During cleaning, please make sure the room is well ventilated
auto speed and it can't be adjusted. to avoid affecting the degree of comfort.
● Under energy-saving function, set temperature can't be
adjusted. Press "TURBO" button and the remote controller
won't send signal.

34 Technical Information
NOTE: Replacement of batteries in remote
The self-cleaning function can only work under normal controller
ambient temperature. If the room is dusty, clean once a
month; if not, clean once every three months. After the self-
① ④
cleaning function is turned on, you may leave the room. When

self-cleaning is finished, the air conditioner will enter standby

mode.
This function is applicable for some models.
Fig.1 Fig.2

function
Press "MODE" and "SLEEP" buttons simultaneously to start 1. Lift the cover along the direction of arrow (as shown in Fig
function. 1 ① ).
function is for limiting power of the whole unit. 2.Take out the original batteries (as shown in Fig 1 ② ).
Press this button, the remote controller will circularly display 3.Place two 7# (AAA 1.5V) dry batteries, and make sure the
as the following: position of “ + ” polar and “ - ” polar is correct (as shown in Fig
2 ③ ).
4.Reinstall the cover (as shown in Fig 2 ④ ).
● Maximum power limited under the mode is lower than
that of mode.
● If you want to cancel the power limiting function, press the Notice:
button till the icon in remote controller is not displayed. ● During operation, point the remote control signal
● When the remote controller is turned off, power limiting sender at the receiving window on indoor unit.
function is cancelled. If you want to activatethe function, ● The distance between signal sender and receiving window
please repress this button. should be no more than 8m, and there should be no obstacles
● If the current power is lower than the maximum power of between them.
mode, then the power will not be limited after entering into ● Signal may be interfered easily in the room where there
such mode. is fluorescent lamp or wireless telephone; remote controller
● For the model with one outdoor unit and two indoor units, should be close to indoor unit during operation.
if any one of indoor units enters into power limiting function, ● Replace new batteries of the same model when replacement
the outdoor unit will enter into the set limiting power mode of is required.
indoor unit; when two indoor units enter into power limiting ● When you don't use remote controller for a long time, please
mode, then the power of outdoor unit will be limited according take out the batteries.
to the lower power of the two indoor units. ● If the display on remote controller is fuzzy or there's no
NOTE: display, please replace batteries.
This function is only available for some models.
Emergency operation
If remote controller is lost or damaged, please use aux.button
If “H1” is displayed on the remote controller while it’s not to turn on or turn off the air conditioner. The operation in
operated by the professional person/after-sales person, it details is as below: As shown in the figure, open panel and
belongs to the misoperation. press aux.button to turn off the air conditioner. When the air
Please operate it as below to cancel it.Under the OFF status conditioner is turned on, it will operate under auto mode.
of remote controller, hold the Mode button for 5s to cancel “H1”
aux. button
display.
Note:
● If remote controller displays “H1”, it belongs to the normal
function reminder. If the unit is defrosting under heating mode,
it operates according to H1 defrosting mode. “H1” won’t be
displayed on the panel of indoor unit;
● Once you set H1 mode, if you turn off unit by remote
controller, H1 will display 3 times on the remote controller and
then disappear;
● Also, when you set H1 mode, when you change to heating
mode, H1 will display 3 times on the remote controller and
then disappear.

Technical Information 35
6.2 GREE+ App Operation Manual

Control Flow Chart

Internet
Gree Cloud

Gree
intelligent Home Wi-Fi Cellular/
home Other Wi-FI
appliances
Home wireless router
Home Wi-Fi
GREE+ APP

Operating Systems

Requirement for User's smart phone:

iOS system Android system


Support iOS7.0 and Support Android 4.4 and
above version above version

Download and installation

GREE+ App Download Linkage

Scan the QR code or search "GREE+" in the application market to download and install it. When "GREE+" App is installed, register the
account and add the device to achieve long-distance control and LAN control of Gree smart home appliances.
For more information, please refer to "Help" in App.

36 Technical Information
6.3 Ewpe Smart App Operation Manual

Control Flow Chart

Internet
Cloud

intelligent Home Wi-Fi Cellular/


home Other Wi-FI
appliances

Home wireless router


Home Wi-Fi
APP

Operating Systems

Requirement for User's smart phone:

iOS system Android system


Support iOS7.0 and Support Android 4.4 and
above version above version

Download and installation

App Download Linkage

Scan the QR code or search "Ewpe Smart" in the application market to download and install it. When "Ewpe Smart" App is installed,
register the account and add the device to achieve long-distance control and LAN control of smart home appliances.
For more information, please refer to "Help" in App.

Technical Information 37
6.4 Brief Description of Models and Functions
●Indoor Unit General timer and clock timer functions are compatible by
1.Basic function of system equipping remote controller with different functions.
(1)Cooling mode (6) Memory function
(1) Under this mode, fan and swing operates at setting status. memorize compensation temperature, off-peak energization value.
Temperature setting range is 16~30OC. Memory content: mode, up&down swing, light, set temperature,
(2) During malfunction of outdoor unit or the unit is stopped set fan speed, general timer (clock timer cant be memorized).
because of protection, indoor unit keeps original operation status. After power recovery, the unit will be turned on automatically
(2)Drying mode according to memory content.
(1) Under this mode, fan operates at low speed and swing (7) Health function
operates at setting status. Temperature setting range is 16~30OC. During operation of indoor fan, set health function by remote
(2) During malfunction of outdoor unit or the unit is stopped controller. Turn off the unit will also turn off health function.
because of protection, indoor unit keeps original operation status. Turn on the unit by pressing auto button, and the health is
(3) Protection status is same as that under cooling mode. defaulted ON.
(4) Sleep function is not available for drying mode. (8)I feel control mode
(3)Heating mode After controller received I feel control signal and ambient
(1) Under this mode, Temperature setting range is 16~30OC. temperature sent by remote controller, controller will work
(2) Working condition and process for heating mode: according to the ambient temperature sent by remote controller.
When turn on the unit under heating mode, indoor unit enters into (9)Entry condition for compulsory defrosting function
cold air prevention status. When the unit is stopped or at OFF When turn on the unit under heating ode and set temperature is
status, and indoor unit has been started up just now, the unit 16OC (or 16.5OC by remote controller), press “ , , , , , ”
enters into residual heat-blowing status. button successively within 5s and then indoor unit will enter into
(4)Working method for AUTO mode: compulsory defrosting setting status:
1.Working condition and process for AUTO mode: (1) If theres only indoor units controller, it enters into indoor normal
a.Under AUTO mode, standard heating Tpreset=20O C and defrosting mode.
standard cooling Tpreset=25O C. The unit will switch mode (2) If theres indoor units controller and outdoor units controller,
automatically according to ambient temperature. indoor unit will send compulsory defrosting mode signal to outdoor
2.Protection function unit and then outdoor unit will operate under normal defrosting
a. During cooling operation, protection function is same as that mode. After indoor unit received the signal that outdoor unit has
under cooling mode. entered into defrosting status, indoor unit will cancel to send
b. During heating operation, protection function is same as that compulsory mode to outdoor unit. If outdoor unit hasnt received
under heating mode. feedback signal from outdoor unit after 3min, indoor unit will also
3. Display: Set temperature is the set value under each condition. cancel to send compulsory defrosting signal.
Ambient temperature is (Tamb.-Tcompensation) for heat pump (10)Refrigerant recovery function:
unit and Tamb. for cooling only unit. Enter into Freon recovery mode actively: Within 5min after
4. If theres I feel function, Tcompensation is 0. Others are same energization, turn on the unit at 16OC under cooling mode, and
as above. press light button for 3 times within 3s to enter into Freon recovery
(5)Fan mode mode. Fo is displayed and Freon recovery mode will be sent to
Under this mode, indoor fan operates at set fan speed. outdoor unit.
Compressor, outdoor fan, 4-way valve and electric heating tube (11)Ambient temperature display control mode
stop operation. Indoor fan can select to operate at high, medium, 1. When user set the remote controller to display set temperature
low or auto fan speed. Temperature setting range is 16~30OC. (corresponding remote control code: 01), current set temperature
2. Other control will be displayed.
(1) Buzzer 2. Only when remote control signal is switched to indoor ambient
Upon energization or availably operating the unit or remote temperature display status (corresponding remote control code:
controller, the buzzer will give out a beep. 10) from other display status (corresponding remote control code:
(2) Auto button 00, 01,11),controller will display indoor ambient temperature for 3s
If press this auto button when turning off the unit, the complete and then turn back to display set temperature.
unit will operate at auto mode. Indoor fan operates at auto fan Under this mode, indoor fan operates at set fan speed.
speed and swing function is turned on. Press this auto button at Compressor, outdoor fan, 4-way valve and electric heating tube
ON status to turn off the unit. stop operation. Indoor fan can select to operate at high, medium,
(3) Auto fan low or auto fan speed. Temperature setting range is 16~30OC.
Heating mode: During auto heating mode or normal heating ode, (12)Off-peak energization function:
auto fan speed will adjust the fan speed automatically according Adjust compressors minimum stop time. The original minimum
to ambient temperature and set temperature. stop time is 180s and then we change to:
(4) Sleep The time interval between two start-ups of compressor cant be
After setting sleep function for a period of time, system will adjust less than 180+Ts(0≤T≤15). T is the variable of controller. Thats to
set temperature automatically. say the minimum stop time of compressor is 180s~195s. Read-
(5) Timer function: in T into memory chip when refurbish the memory chip each time.

38 Technical Information
After power recovery, compressor can only be started up after 2oC, compressor stops operation and outdoor fan will stop 30s
180+T s at least. later. Indoor fan will be in residual-heat blowing status.
(13) SE control mode ④ When unit is turned off under heating mode or changed to other
The unit operates at SE status. modes from heating mode, 4-way valve will be power-off 2min
(14) X-fan mode after compressor stops working (compressor is in operation status
When X-fan function is turned on, after turn off the unit, indoor fan under heating mode).
will still operate at low speed for 2min and then the complete unit ⑤ When Toutdoor ambient temperature > 30oC, compressor
will be turned off. When x-fan function is turned off, after turn off stops operation immediately. Outdoor fan will stop 30s later.
the unit, the complete unit will be turned off directly. ⑥ Under the condition that compressor is turned on, when unit
(15) 8OC heating function is changed to heating mode from cooling or drying mode, 4-way
Under heating mode, you can set 8oCheating function by remote valve will be energized in 2~3mins delay.
controller. The system will operate at 8oC set temperature. Note: Tcompensation is determined by IDU and ODU. If IDU
(16)Turbo function controls the compensation temperature, then Tcompensation is
Turbo function can be set under cooling and heating modes. determined according to the value sent by IDU to ODU; If
Press Fan Speed button to cancel turbo setting. Turbo function is IDU does not control the compensation temperature, then
not available under auto, drying and fan modes. Tcompensation will default to 3oC by the ODU.
5. Freon recovery mode
●Outdoor Unit After the Freon recovery signal from IDU is received, cooling at
1. Cooling mode: rated frequency will be forcibly turned on to recover Freon.
Working condition and process of cooling mode: Indoor unit will display Fo. If any signal from remote controller is
① When Tindoor ambient temperature≥Tpreset, unit enters into received, unit will exit from Freon recovery mode and indoor unit
cooling mode. Indoor fan, outdoor fan and compressor start stops displaying Fo.
operation. Indoor fan operates according to set fan speed.
6. Compulsory defrosting
② When Tindoor ambient temperature≤Tpreset-2oC, compressor
If unit is turned on under heating mode and set temperature is
stops operation and outdoor fan will stop 30s later. Indoor fan
16OC (by remote controller), press “ , , , , , ” within 5s,
operates according to set fan speed.
unit will enter into compulsory defrosting mode and send the
③ When Tpreset-2oC < Tindoor ambient temperature < Tpreset,
signal to ODU. When the compulsory defrosting signal from ODU
unit operates according to the previous status.
is received, IDU will exit from the compulsory defrosting mode and
Under cooling mode, 4-way valve is not energized. Temperature
stop sending the signal to ODU.
setting range is 16~30 o C. If compressor stops because of
After ODU receives the compulsory defrosting code, it will start
malfunction in cooling mode, indoor fan and swing motor will work
compulsory defrosting. Defrosting frequency and opening
according to the original status.
angle will be the same as in normal defrosting mode. When
2. Drying mode compulsory defrosting is finished, the complete unit resumes
(1) Working condition and process of drying mode original status.
① When Tindoor ambient temperature > Tpreset, unit will be in
7. Auto mode
drying mode. Outdoor fan and compressor start operation while
Auto mode is determined by controller of IDU. See IDU logic for
indoor fan will operate at low fan speed.
details.
② When Tpreset-2oC≤Tindoor ambient temperature≤Tpreset, unit
operates according to the previous status. 8. 8oC heating
③ When Tindoor ambient temperature < Tpreset-2 o C, Set temperature is 8oC. Display board of IDU displays 8oC. Under
compressor stops operation and outdoor fan will stop 30s later. this mode, “Cold air prevention” function is shielded.
(2) Under drying mode, 4-way valve is not energized. Temperature If compressor is operating under this mode, fan speed will adjust
setting range is 16~30oC. according to auto fan speed; if compressor stops operation
(3) Protection function: same as in cooling mode. under this mode, indoor fan will be in residual-heat blowing status.
3. Fan mode
(1) Under this mode, indoor fan can select different fan speed When power on, communication light will be blinking in a
(except Turbo) or auto fan speed. Compressor, outdoor fan and normal way (after receiving a group of correct signals,
4-way valve all stop operation. blinking stops for 0.2s~0.3s). If theres no communication,
(2) In fan mode, temperature setting range is 16~30oC. communication light will be always on. If other ODU has
malfunction, communication light will be on for 1s and off for
4. Heating mode 1s in a circular way.
Working condition and process of heating mode:
① When Tpreset-(Tindoor ambient temperature-
Tcompensation)≥1oC, unit enters into heating mode. Compressor,
outdoor fan and 4-way valve start operation.
② When -2 o C < Tpreset-(Tindoor ambient temperature-
Tcompensation) < 1oC, unit operates according to the previous
status.
③ When Tpreset-(Tindoor ambient temperature-Tcompensation)≤-

Technical Information 39
7. Notes for Installation and Maintenance
Safety Precautions: Important! 12. Make sure all wires and pipes are connected properly and
the valves are opened before energizing.
Please read the safety precautions carefully before 13. Check if there is electric leakage on the unit body. If yes,
installation and maintenance. please eliminate the electric leakage.
The following contents are very important for installation and 14. Replace the fuse with a new one of the same specification
maintenance. if it is burnt down; dont replace it with a cooper wire or
conducting wire.
Please follow the instructions below. 15. If the unit is to be installed in a humid place, the circuit
breaker must be installed.
●The installation or maintenance must accord with the
instructions.
●Comply with all national electrical codes and local electrical
codes.
●Pay attention to the warnings and cautions in this manual.
●All installation and maintenance shall be performed by
distributor or qualified person.
●All electric work must be performed by a licensed technician
according to local regulations and the instructions given in
this manual.
Installation Safety Precautions:
●Be caution during installation and maintenance. Prohibit
1. Select the installation location according to the requirement
incorrect operation to prevent electric shock, casualty and
of this manual.(See the requirements in installation part)
other accidents.
2. Handle unit transportation with care; the unit should not be
carried by only one person if it is more than 20kg.
3. When installing the indoor unit and outdoor unit, a
sufficient fixing bolt must be installed; make sure the
installation support is firm.
4. Ware safety belt if the height of working is above 2m.
5. Use equipped components or appointed components
during installation.
6. Make sure no foreign objects are left in the unit after
finishing installation.
WARNINGS
Electrical Safety Precautions:
Refrigerant Safety Precautions:
1. Cut off the power supply of air conditioner before checking
and maintenance. 1. When refrigerant leaks or requires discharge during
2. The air condition must apply specialized circuit and installation, maintenance, or disassembly, it should be
prohibit share the same circuit with other appliances. handled by certified professionals or otherwise in compliance
3. The air conditioner should be installed in suitable location with local laws and regulations.
and ensure the power plug is touchable. 2.Avoid contact between refrigerant and fire as it generates
4. Make sure each wiring terminal is connected firmly during poisonous gas; Prohibit prolong the connection pipe by
installation and maintenance. welding.
5. Have the unit adequately grounded. The grounding wire 3. Apply specified refrigerant only. Never have it mixed with
cant be used for other purposes. any other refrigerant. Never have air remain in the refrigerant
6. Must apply protective accessories such as protective line as it may lead to rupture or other hazards.
boards, cable-cross loop and wire clip. 4. Make sure no refrigerant gas is leaking out when
7. The live wire, neutral wire and grounding wire of power installation is completed.
supply must be corresponding to the live wire, neutral wire 5. If there is refrigerant leakage, please take sufficient
and grounding wire of the air conditioner. measure to minimize the density of refrigerant.
8. The power cord and power connection wires cant be 6. Never touch the refrigerant piping or compressor without
pressed by hard objects. wearing glove to avoid scald or frostbite.
9. If power cord or connection wire is broken, it must be
replaced by a qualified person.
10. If the power cord or connection wire is not long enough,
please get the specialized power cord or connection wire
from the manufacture or distributor. Prohibit prolong the wire
by yourself. Improper installation may lead to fire hazard,
11. For the air conditioner without plug, an air switch must explosion, electric shock or injury.
be installed in the circuit. The air switch should be all-pole
parting and the contact parting distance should be more than
3mm.

40 Installation and Maintenance


Safety Precautions for Installing and Relocating the Unit:

To ensure safety, please be mindful of the following precautions.

WARNINGS
1. When installing or relocating the unit, be sure to 5.When installing the unit, make sure that connection
keep the refrigerant circuit free from air or substances pipe is securely connected before the compressor
other than the specified refrigerant. starts running.

Any presence of air or other foreign substance in the refrigerant If compressor starts running when stop valve is open and
circuit will cause system pressure rise or compressor rupture, connection pipe is not yet connected, air will be sucked in and
resulting in injury. cause pressure rise or compressor rupture, resulting in injury.

2.When installing or moving this unit, do not charge 6.Prohibit installing the unit at the place where there
the refrigerant which is not comply with that on the may be leaked corrosive gas or flammable gas.
nameplate or unqualified refrigerant.
If there leaked gas around the unit, it may cause explosion and
Otherwise, it may cause abnormal operation, wrong action, other accidents.
mechanical malfunction or even series safety accident.
7.Do not use extension cords for electrical connections.
3.When refrigerant needs to be recovered during If the electric wire is not long enough, please contact
relocating or repairing the unit, be sure that the unit is a local service center authorized and ask for a proper
running in cooling mode.Then, fully close the valve at electric wire.
high pressure side (liquid valve).About 30-40 seconds
later, fully close the valve at low pressure side (gas Poor connections may lead to electric shock or fire.
valve), immediately stop the unit and disconnect power.
Please note that the time for refrigerant recovery
8.Use the specified types of wires for electrical
should not exceed 1 minute.
connections between the indoor and outdoor units.
Firmly clamp the wires so that their terminals receive
If refrigerant recovery takes too much time, air may be sucked in no external stresses.
and cause pressure rise or compressor rupture, resulting in injury.
Electric wires with insufficient capacity, wrong wire connections
4.During refrigerant recovery, make sure that liquid and insecure wire terminals may cause electric shock or fire.
valve and gas valve are fully closed and power is
disconnected before detaching the connection pipe.

If compressor starts running when stop valve is open and


connection pipe is not yet connected, air will be sucked in and
cause pressure rise or compressor rupture, resulting in injury.

Installation and Maintenance 41


has running fire (such as fire source,working coal gas ware,
Safety Precautions for Refrigerant operating heater).
●To realize the function of the air conditioner unit, a special ●It is not allowed to drill hole or burn the connection pipe.
refrigerant circulates in the system. The used refrigerant is ●The air conditioner must be installed in a room that is larger
the fluoride R32,which is specially cleaned. The refrigerant than the minimum room area.
The minimum room area is shown on the nameplate or
is flammable and inodorous. Furthermore, it can leads to
following table a.
explosion under certain conditions. But the flammability of
●Leak test is a must after installation.
the refrigerant is very low. It can be ignited only by fire.
●Compared to common refrigerants, R32 is a nonpolluting table a - Minimum room area ( m2 )
refrigerant with no harm to the ozonosphere. The influence
upon the greenhouse effect is also lower. R32 has got very
good thermodynamic features which lead to a really high
energy efficiency. The units therefore need a less filling.

WARNING:

●Do not use means to accelerate the defrosting process or to


clean, other than those recommended by the manufacture.
Should repair be necessary,contact your nearest authorized
Service Centre. Any repairs carried out by unqualified
personnel may be dangerous. The appliance shall be stored
in a room without continuously operating ignition sources.
(for example:open flames , an operating gas appliance or an
operating electric heater.)
●Do not pierce or burn.
●Appliance shall be installed, operated and stored in a room
with a floor area larger than Xm2.
●Appliance filled with flammable gas R32. For repairs,
strictly follow manufacturers instructions only.Be aware that
refrigrants not contain odour.
●Read specialists manual.

Maintenance notes

●Check whether the maintenance area or the room area meet


the requirement of the nameplate.
— Its only allowed to be operated in the rooms that meet the
requirement of the nameplate.
●Check whether the maintenance area is well-ventilated.
— The continuous ventilation status should be kept during
the operation process.
●Check whether there is fire source or potential fire source in
Safety Operation of Flammable Refrigerant the maintenance area.
Qualification requirement for installation and — The naked flame is prohibited in the maintenance area;
maintenance man and the “no smoking” warning board should be hanged.
●Check whether the appliance mark is in good condition.
●Any person who is involved with working on or breaking — Replace the vague or damaged warning mark.
into a refrigerant circuit should hold a current valid certificate
from an industry-accredited assessment authority, which Welding
authorises their competence to handle refrigerants safely
in accordance with an industry recognised assessment ●If you should cut or weld the refrigerant system pipes in the
specification. process of maintaining, please follow the steps as below:
●Servicing shall only be performed as recommended by the a. Shut down the unit and cut power supply
equipment manufacturer. Maintenance and repair requiring b. Eliminate the refrigerant
the assistance of other skilled personnel shall be carried out c. Vacuuming
under the supervision of the person competent in the use of d. Clean it with N2 gas
flammable refrigerants. e. Cutting or welding
Installation notes f. Carry back to the service spot for welding
●Make sure that there isnt any naked flame near the outlet of
the vacuum pump and its well-ventilated.
●The air conditioner is not allowed to use in a room that

42 Installation and Maintenance


●The refrigerant should be recycled into the specialized surveyed to make sure that there are no flammable hazards or
storage tank. ignition risks. “ NO Smoking ” signs shall be displayed.

Filling the refrigerant ●Ventilated area


●Use the refrigerant filling appliances specialized for R32. Ensure that the area is in the open or that it is adequately
Make sure that different kinds of refrigerant wont contaminate ventilated before breaking into the system or conducting any hot
with each other. work. A degree of ventilation shall continue during the period that
●The refrigerant tank should be kept upright at the time of
the work is carried out. The ventilation should safely disperse
filling refrigerant.
any released refrigerant and preferably expel it externally into the
●Stick the label on the system after filling is finished (or
havent finished). atmosphere.
●Dont overfilling.
●After filling is finished, please do the leakage detection ●Checks to the refrigeration equipment
before test running; another time of leak detection should be Where electrical components are being changed, they shall be
done when its removed. fit for the purpose and to the correct specification. At all times
the manufacturer’s maintenance and service guidelines shall
Safety instructions for transportation and storage be followed. If in doubt, consult the manufacturer’s technical
department for assistance.
●Please use the flammable gas detector to check before The following checks shall be applied to installations using
unload and open the container. flammable refrigerants:
●No fire source and smoking.
---The actual refrigerant charge is in accordance with the room
●According to the local rules and laws.
size within which the refrigerant containing parts are installed;
Prior to beginning work on systems containing flammable ---The ventilation machinery and outlets are operating adequately
refrigerants, safety checks are necessary to ensure that the and are not obstructed;
risk of ignition is minimised. For repair to the refrigerating ---If an indirect refrigerating circuit is being used, the secondary
system, the following precautions shall be complied with prior circuit shall be checked for the presence of refrigerant;
to conducting work on the system. ---Marking to the equipment continues to be visible and legible.
●Work procedure Markings and signs that are illegible shall be corrected;
Work shall be undertaken under a controlled procedure so as to ---Refrigeration pipe or components are installed in a position
minimise the risk of a flammable gas or vapour being present while where they are unlikely to be exposed to any substance which
the work is being performed. may corrode refrigerant containing components, unless the
components are constructed of materials which are inherently
●General work area resistant to being corroded or are suitably protected against being
All maintenance staff and others working in the local area shall be so corroded.
instructed on the nature of work being carried out. Work in confined
spaces shall be avoided. The area around the workspace shall be ●Checks to electrical devices
sectioned off. Ensure that the conditions within the area have been Repair and maintenance to electrical components shall include
made safe by control of flammable material initial safety checks and component inspection procedures. If a
fault exists that could compromise safety, then no electrical supply
●Checking for presence of refrigerant shall be connected to the circuit until it is satisfactorily dealt with.
The area shall be checked with an appropriate refrigerant detector If the fault cannot be corrected immediately but it is necessary to
prior to and during work, to ensure the technician is aware of continue operation, an adequate temporary solution shall be used.
potentially toxic or flammable atmospheres. This shall be reported to the owner of the equipment so all parties
Ensure that the leak detection equipment being used is suitable for are advised.
use with all applicable refrigerants, i.e. non-sparking, adequately Initial safety checks shall include:
sealed or intrinsically safe. 1.That capacitors are discharged: this shall be done in a safe
manner to avoid possibility of sparking;
●Presence of fire extinguisher 2.That no live electrical components and wiring are exposed while
If any hot work is to be conducted on the refrigeration equipment
charging, recovering or purging the system;
or any associated parts, appropriate fire extinguishing equipment
3.That there is continuity of earth bonding.
shall be available to hand. Have a dry powder or CO 2 fire
extinguisher adjacent to the charging area.
●Repairs to sealed components
1. During repairs to sealed components, all electrical supplies shall
●No ignition sources
be disconnected from the equipment being worked upon prior to
No person carrying out work in relation to a refrigeration system
any removal of sealed covers, etc. If it is absolutely necessary to
which involves exposing any pipe work shall use any sources
have an electrical supply to equipment during servicing, then a
of ignition in such a manner that it may lead to the risk of fire
permanently operating form of leak detection shall be located at
or explosion. All possible ignition sources, including cigarette
the most critical point to warn of a potentially hazardous situation.
smoking, should be kept sufficiently far away from the site of
2. Particular attention shall be paid to the following to ensure that
installation, repairing, removing and disposal, during which
by working on electrical components, the casing is not altered
refrigerant can possibly be released to the surrounding space.
in such a way that the level of protection is affected.This shall
Prior to work taking place, the area around the equipment is to be
include damage to cables, excessive number of connections,

Installation and Maintenance 43


terminals not made to original specification, damage to seals, ●Removal and evacuation
incorrect fitting of glands, etc. When breaking into the refrigerant circuit to make repairs – or
Ensure that the apparatus is mounted securely. for any other purpose –conventional procedures shall be used.
Ensure that seals or sealing materials have not degraded to the However, for flammable refrigerants it is important that best
point that they no longer serve the purpose of preventing the practice is followed since flammability is a consideration. The
ingress of flammable atmospheres. following procedure shall be adhered to:
Replacement parts shall be in accordance with the manufacturer’s 1.remove refrigerant;
specifications. 2.purge the circuit with inert gas; evacuate;
NOTE : The use of silicon sealant can inhibit the effectiveness of some 3.purge again with inert gas;
types of leak detection equipment. Intrinsically safe components do not 4.open the circuit by cutting or brazing.
have to be isolated prior to working on them.
The refrigerant charge shall be recovered into the correct recovery
●Repair to intrinsically safe components cylinders.
Do not apply any permanent inductive or capacitance loads to the For appliances containing flammable refrigerants, the system shall
circuit without ensuring that this will not exceed the permissible be “flushed” with OFN to render the unit safe. This process may
voltage and current permitted for the equipment in use. need to be repeated several times.Compressed air or oxygen
Intrinsically safe components are the only types that can be worked
on while live in the presence of a flammable atmosphere. The test
apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer.
Other parts may result in the ignition of refrigerant in the
atmosphere from a leak.

●Cabling
Check that cabling will not be subject to wear, corrosion,
excessive pressure, vibration, sharp edges or any other adverse
environmental effects. The check shall also take into account
the effects of aging or continual vibration from sources such as
compressors or fans.

●Detection of flammable refrigerants


Under no circumstances shall potential sources of ignition be used
in the searching for or detection of refrigerant leaks. A halide torch
(or any other detector using a naked flame) shall not be used.

●Leak detection methods


The following leak detection methods are deemed acceptable for
all refrigerant systems.
Electronic leak detectors may be used to detect refrigerant leaks
but, in the case of flammable refrigerants, the sensitivity may not
be adequate, or may need re-calibration.
(Detection equipment shall be calibrated in a refrigerant-free area.)
Ensure that the detector is not a potential source of ignition and is
suitable for the refrigerant used.
Leak detection equipment shall be set at a percentage of the
LFL of the refrigerant and shall be calibrated to the refrigerant
employed, and the appropriate percentage of gas (25 % maximum)
is confirmed.
Leak detection fluids are suitable for use with most refrigerants
but the use of detergents containing chlorine shall be avoided as
the chlorine may react with the refrigerant and corrode the copper
pipe-work.
If a leak is suspected, all naked flames shall be removed/
extinguished.
If a leakage of refrigerant is found which requires brazing, all of
the refrigerant shall be recovered from the system, or isolated (by
means of shut off valves) in a part of the system remote from the
leak. For appliances containing flammable refrigerants, oxygen
free nitrogen (OFN) shall then be purged through the system both
before and during the brazing process.

44 Installation and Maintenance


Main Tools for Installation and Maintenance

Level meter Measuring tape Screw driver Impact drill

Drill head Electric drill Electroprobe Universal meter

Torque wrench Open-end wrench Inner hexagon Electronic


spanner leakage detector

Vacuum pump Pressure meter Pipe pliers Pipe pliers

Pipe cutter Pipe expander Pipe bender Soldering appliance

Refrigerant container Electronic scale

Installation and Maintenance 45


8. Installation
8.1 Installation Dimension Diagram

g
Space to the ceilin
At least 15 cm

Space to the wall


At least 15cm

Space to the wall


At least 15cm

Space to the obstruction


Space to the floor At least 300cm
At least 250cm

Space to the obstruction


At least 50cm

Space to the obstructio


n
At least 30cm

Drainage pipe

wall
the
to
ace
Sp

Space to
the obstr
uc
Space At least 5 tion
to the 0cm
obs
At leas truction
t 200c
m

46 Installation and Maintenance


Installation Procedures
Start installation

Preparation before installation

Read the requirements select installation Prepare tools


for electric connection location

Select indoor unit Select outdoor unit


installation location installation location

Install wall-mounting Install the support of outdoor unit


frame, drill wall holes (select it according to the actual situation)

Connect pipes of indoor Fix outdoor unit


unit and drainage pipe

Connect wires of indoor unit Install drainage joint of outdoor unit


(only for cooling and heating unit)

Bind up pipes and


hang the indoor unit

Make the bound pipes pass


through the wall hole and then
connect outdoor unit

Connect pipes of outdoor unit

Connect wires of outdoor unit

Neaten the pipes

Vacuum pumping and leakage detection

Check after installation and test operation

Finish installation

Note: this flow is only for reference; please find the more detailed installation steps in this section.

Installation and Maintenance 47


8.2 Installation Parts-checking (3) The location should be able to withstand the weight of outdoor
unit.
No. Name (4) Make sure that the installation follows the requirement of
1 Indoor unit installation dimension diagram.
(5) Select a location which is out of reach for children and far
2 Outdoor unit away from animals or plants.If it is unavoidable, please add fence
3 Connection pipe for safety purpose.
4 Drainage pipe
5 Wall-mounting frame 8.4 Electric Connection Requirement
6 Connecting cable(power cord) 1. Safety Precaution
(1) Must follow the electric safety regulations when installing the
7 Wall pipe
unit.
8 Sealing gum (2) According to the local safety regulations, use qualified power
9 Wrapping tape supply circuit and air switch.
(3) Make sure the power supply matches with the requirement
10 Support of outdoor unit
of air conditioner. Unstable power supply or incorrect wiring may
11 Fixing screw result in electric shock,fire hazard or malfunction. Please install
12 Drainage plug(cooling and heating unit) proper power supply cables before using the air conditioner.
(4) Properly connect the live wire, neutral wire and grounding wire
13 Owners manual, remote controller
of power socket.
(5) Be sure to cut off the power supply before proceeding any
Note:
work related to electricity and safety.
1.Please contact the local agent for installation.
(6) Do not put through the power before finishing installation.
2.Dont use unqualified power cord.
(7) If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in
8.3 Selection of Installation Location order to avoid a hazard .
1. Basic Requirement: (8) The temperature of refrigerant circuit will be high, please keep
Installing the unit in the following places may cause malfunction. If the interconnection cable away from the copper tube.
it is unavoidable, please consult the local dealer: (9) The appliance shall be installed in accordance with national
(1) The place with strong heat sources, vapors, flammable or wiring regulations.
explosive gas, or volatile objects spread in the air. (10) Appliance shall be installed, operated and stored in a room
(2) The place with high-frequency devices (such as welding with a floor area larger than Xm 2(Please refer to table "a" in
section of " Safety Operation of Inflammable Refrigerant" for
machine, medical equipment). Space X.)
(3) The place near coast area.
Please notice that the unit is filled with
(4) The place with oil or fumes in the air.
flammable gas R32. Inappropriate treatment of
(5) The place with sulfureted gas.
the unit involves the risk of severe damages of
(6) Other places with special circumstances.
people and material. Details to this refrigerant
(7) The appliance shall nost be installed in the laundry.
are found in chapter “refrigerant”.
(8) It’s not allowed to be installed on the unstable or motive base
structure(such as truck) or in the corrosive environment (such as
chemical factory). 2. Grounding Requirement:
(1) The air conditioner is the first class electric appliance.It must
2. Indoor Unit:
(1) There should be no obstruction near air inlet and air outlet. be properly grounding with specialized grounding device by a
(2) Select a location where the condensation water can be professional.
dispersed easily andwont affect other people. Please make sure it is always grounded effectively,otherwise it
(3) Select a location which is convenient to connect the outdoor may cause electric shock.
unit and near the power socket. (2) The yellow-green wire in air conditioner is grounding wire,
(4) Select a location which is out of reach for children. which cant be used for other purposes.
(5) The location should be able to withstand the weight of indoor (3) The grounding resistance should comply with national electric
unit and wont increase noise and vibration. safety regulations.
(6) The appliance must be installed 2.5m above floor. (4) The appliance must be positioned so that the plug is
(7) Dont install the indoor unit right above the electric appliance. accessible.
(8) Please try your best to keep way from fluorescent lamp. (5) An all-pole disconnection switch having a contact separation of
at least 3mm in all poles should be connected in fixed wiring.
3. Outdoor Unit:
(1) Select a location where the noise and outflow air emitted by (6) Including an air switch with suitable capacity, please note
the outdoor unit will not affect neighborhood. the following table. Air switch should be included magnet buckle
(2) The location should be well ventilated and dry, in which the and heating buckle function, it can protect the circuit-short and
outdoor unit wont be exposed directly to sunlight or strong wind. overload. (Caution: please do not use the fuse only for protect the
circuit)

48 Installation and Maintenance


Model Air switch capacity Power cord 4. Outlet Pipe
07/09/12K 10A 3G1.0 (1) The pipe can be led out in the direction of right, rear right, left
18K 16A 3G1.5 or rear left.(As show in Fig.3)
24K 25A 3G2.5 (2) When selecting leading out the pipe from left or right, please
cut off the corresponding hole on the bottom case.(As show in
Fig.4)
8.5 Installation of Indoor Unit
1. Choosing Installation Iocation
Recommend the installation location to the client and then confirm Left Right

it with the client.

2. Install Wall-mounting Frame Left Rear left Cut off


(1) Hang the wall-mounting frame on the wall; adjust it in Rear right
the hole
Right
horizontal position with the level meter and then point out the
screw fixing holes on the wall. Fig.3 Fig.4
(2) Drill the screw fixing holes on the wall with impact drill (the
specification of drill head should be the same as the plastic 5. Connect the Pipe of Indoor Unit
expansion particle) and then fill the plastic expansion particles in (1) Aim the pipe joint at the corresponding bellmouth.(As show in
the holes. Fig.5)
(3) Fix the wall-mounting frame on the wall with tapping screws (2) Pretightening the union nut with hand.
and then check if the frame is firmly installed by pulling the frame. (3) Adjust the torque force by referring to the following sheet.
If the plastic expansion particle is loose, please drill another fixing Place the open-end wrench on the pipe joint and place the
hole nearby. torque wrench on the union nut. Tighten the union nut with torque
wrench.(As show in Fig.6)
3. Install Wall-mounting Frame (4) Wrap the indoor pipe and joint of connection pipe with
(1) Choose the position of piping hole according to the direction of insulating pipe, and then wrap it with tape.(As show in Fig.7)
outlet pipe. The position of piping hole should be a little lower than
the wall-mounted frame,shown as below.(As show in Fig.1)
Open-end
Mark in the m wrench
Wall iddle of it
Union nut
Space Pipe joint Union nut Pipe
to the Wall Pipe
Space Torque wrench
wall to the
above wall
150mm above Indoor pipe
Left 150mm
Right Fig.5 Fig.6
(Rear piping hole) Level meter
(For some models)
(Rear piping hole)
Fig.1

(2) Open a piping hole with the diameter of Φ55mm or Φ70mm on


the selected outlet pipe position. In order to drain smoothly, slant Insulating pipe

the piping hole on the wall slightly downward to the outdoor side
Fig.7
with the gradient of 5-10°.(As show in Fig.2)
Indoor Outdoor Refer to the following table for wrench moment of force:

Piping size Tightening torque(N.m)


Φ55/70mm
5-10°
1/4" 15~20

3/8" 30~40
Fig.2
1/2" 45~55

Note: 5/8" 60~65

Pay attention to dust prevention and take relevant safety 3/4" 70~75
measures when opening the hole.

Installation and Maintenance 49


6. Install Drain Hose
(1) Connect the drain hose to the outlet pipe of indoor unit.(As 7K 9/12/18/24K
show in Fig.8)
N(1) 2 3 N(1) 2 3
(2) Bind the joint with tape.(As show in Fig.9)
yellow- blue black brown blue black brown yellow-
green green

Outdoor unit connection Outdoor unit connection


Drain hose
Outlet pipe Fig.13
Note: The wiring connect is for reference only, please refer to
the actual one.
Outlet Drain hose
Tape (4) Put wiring cover back and then tighten the screw.
pipe
(5) Close the panel.
Fig.8 Fig.9
Note:
Note: (1) All wires of indoor unit and outdoor unit should be connected
(1) Add insulating pipe in the indoor drain hose in order to by a professional.
(2) If the length of power connection wire is insufficient, please
prevent condensation.
contact the supplier for a new one. Avoid extending the wire by
(2) The plastic expansion particles are not provided.
yourself.
(As show in Fig.10) (3) For the air conditioner with plug, the plug should be reachable
after finishing installation.
(4) For the air conditioner without plug, an air switch must be
Drain hose installed in the line. The air switch should be all-pole parting and
the contact parting distance should be more than 3mm.

Insulating pipe 8. Bind up Pipe


(1) Bind up the connection pipe, power cord and drain hose with
Fig.10 the band.(As show in Fig.14)
(2) Reserve a certain length of drain hose and power cord for
7. Connect Wire of Indoor Unit installation when binding them. When binding to a certain degree,
(1) Open the panel, remove the screw on the wiring cover and separate the indoor power and then separate the drain hose.(As
then take down the cover.(As show in Fig.11) show in Fig.15)
(3) Bind them evenly.
(4) The liquid pipe and gas pipe should be bound separately at the
Screw
Panel end.

Indoor and
outdoor power cord
Wiring cover Indoor unit Gas
Fig.11 pipe

(2) Make the power connection wire go through the cable-cross


Liquid
hole at the back of indoor unit and then pull it out from the front pipe
Band
side.(As show in Fig.12) Drain hose

Fig.14

Cable-cross
hole
Connection pipe Drain hose Band
Power connection
wire

Fig.12

(3) Remove the wire clip; connect the power connection wiresignal
control wire (only for cooling and heating unit) to the wiring Indoor power cord
terminal according to the color; tighten the screw and then fix the Fig.15
power connection wire with wire clip.(As show in Fig.13)

50 Installation and Maintenance


Note:
(1) The power cord and control wire cant be crossed or winding.
(2) The drain hose should be bound at the bottom.

9. Hang the Indoor Unit


(1) Put the bound pipes in the wall pipe and then make them pass Drain vent
Chassis
through the wall hole. Drain hose Outdoor drain joint
At least 3cm above the floor
(2) Hang the indoor unit on the wall-mounting frame.
Fig.18 Fig.19
(3) Stuff the gap between pipes and wall hole with sealing gum.
(4) Fix the wall pipe.(As show in Fig.16)
(5) Check if the indoor unit is installed firmly and closed to the 2. Install Drain Joint(Only for cooling and heating unit)
wall.(As show in Fig.17) (1) Connect the outdoor drain joint into the hole on the chassis.
(2) Connect the drain hose into the drain vent.
(As show in Fig.19)

Indoor Outdoor Upper hook 3. Fix Outdoor Unit


Wall pipe (1) Place the outdoor unit on the support.
Sealing gum (2) Fix the foot holes of outdoor unit with bolts.
(As show in Fig.20)

Lower hook of
wall-mounting frame
Foot holes
Fig.16 Fig.17

Note: Handle
Do not bend the drain hose too excessively in order to prevent
blocking. Foot holes
Valve cover

Fig.20 Fig.21

8.6 Installation of Outdoor unit 4. Connect Indoor and Outdoor Pipes


(1) Remove the screw on the right handle of outdoor unit and then
1. Fix the Support of Outdoor Unit(Select it according remove the handle.(As show in Fig.21)
to the actual installation situation) (2) Remove the screw cap of valve and aim the pipe joint at the
(1) Select installation location according to the house structure. bellmouth of pipe.(As show in Fig.22)
(2) Fix the support of outdoor unit on the selected location with
expansion screws.
Liquid pipe Pipe joint
Liquid gas pipe
valve
Note:
Union nut
gas valve

(1) Take sufficient protective measures when installing the outdoor Fig.22
unit.
(2) Make sure the support can withstand at least four times the (3) Pretightening the union nut with hand.
unit weight. (4) Tighten the union nut with torque wrench .
(3) The outdoor unit should be installed at least 3cm above the
floor in order to install drain joint.(As show in Fig.18) Refer to the following table for wrench moment of force:
(4) For the unit with cooling capacity of 2300W~5000W, 6 Piping size Tightening torque(N.m)
expansion screws are needed; for the unit with cooling capacity of 1/4" 15~20
6000W~8000W, 8 expansion screws are needed; for the unit with
3/8" 30~40
cooling capacity of 10000W~16000W, 10 expansion screws are
1/2" 45~55
needed.
5/8" 60~65
3/4" 70~75

Installation and Maintenance 51


5. Connect Outdoor Electric Wire
(1) Remove the wire clip; connect the power connection wire and
signal control wire (only for cooling and heating unit) to the wiring
terminal according to the color; fix them with screws.(As show in
The drain hose can't be fluctuant
Fig.23)

The water outlet


The drain
hose can't
can't be placed
be fluctuant The water in water
outlet can't
N(1) 2 L(3) be fluctuant

yellow- brown yellow- Fig.26 Fig.27


green blue black brown blue (black) green

N L
Indoor unit connection POWER
8.7 Vacuum Pumping and Leak Detection
Fig.23 1. Use Vacuum Pump
(1) Remove the valve caps on the liquid valve and gas valve and
the nut of refrigerant charging vent.
Note: the wiring connect is for reference only,please refer to the (2) Connect the charging hose of piezometer to the refrigerant
actual one. charging vent of gas valve and then connect the other charging
hose to the vacuum pump.
(2) Fix the power connection wire and signal control wire with wire (3) Open the piezometer completely and operate for 10-15min to
clip (only for cooling and heating unit). check if the pressure of piezometer remains in -0.1MPa.
(4) Close the vacuum pump and maintain this status for 1-2min
Note: to check if the pressure of piezometer remains in -0.1MPa. If the
(1) After tightening the screw, pull the power cord slightly to check pressure decreases, there may be leakage.
(5) Remove the piezometer, open the valve core of liquid valve
if it is firm.
and gas valve completely with inner hexagon spanner.
(2) Never cut the power connection wire to prolong or shorten the (6) Tighten the screw caps of valves and refrigerant charging
distance. vent.(As show in Fig.28)

6. Neaten the Pipes


(1) The pipes should be placed along the wall, bent reasonably and
hidden possibly. Min. semidiameter of bending the pipe is 10cm.
Liquid valve Piezometer
(2) If the outdoor unit is higher than the wall hole, you must set Lo Hi

a U-shaped curve in the pipe before pipe goes into the room, in Gas valve
order to prevent rain from getting into the room.(As show in Fig.24) Refrigerant charging Valve cap
vent
Nut of refrigerant
Charging vent
The drain hose
can't raise Vacuum pump
upwards.

Wall Inner hexagon


spanner

Close
U-shaped curve
Open

Drain hose
Fig.24 Fig.25
Fig.28
Note:
2. Leakage Detection
(1) The through-wall height of drain hose shouldnt be higher than (1) With leakage detector:
the outlet pipe hole of indoor unit.(As show in Fig.25) Check if there is leakage with leakage detector.
(2) Slant the drain hose slightly downwards. The drain hose cant (2) With soap water:
be curved, raised and fluctuant, etc.(As show in Fig.26) If leakage detector is not available, please use soap water for
(3) The water outlet cant be placed in water in order to drain leakage detection. Apply soap water at the suspected position and
smoothly.(As show in Fig.27) keep the soap water for more than 3min. If there are air bubbles
coming out of this position, there's a leakage.

52 Installation and Maintenance


8.8 Check after Installation and Test operation
1. Check after Installation
Check according to the following requirement after finishing
installation.

NO. Items to be checked Possible malfunction


Has the unit been installed The unit may drop, shake or
1
firmly? emit noise.
Have you done the It may cause insufficient
2
refrigerant leakage test? cooling (heating) capacity.
Is heat insulation of pipeline It may cause condensation
3
sufficient? and water dripping.
It may cause condensation
4 Is water drained well?
and water dripping.
Is the voltage of power
supply according to the It may cause malfunction or
5
voltage marked on the damage the parts.
nameplate?
Is electric wiring and pipeline It may cause malfunction or
6
installed correctly? damage the parts.
Is the unit grounded It may cause electric
7
securely? leakage.
Does the power cord follow It may cause malfunction or
8
the specification? damage the parts.
Is there any obstruction in It may cause insufficient
9
air inlet and air outlet? cooling (heating) capacity.
The dust and sundries
It may cause malfunction or
10 caused during installation
damaging the parts.
are removed?
The gas valve and liquid
It may cause insufficient
11 valve of connection pipe are
cooling (heating) capacity.
open completely?
It may cause insufficient
Is the inlet and outlet of
12 cooling(heating) capacity or
piping hole been covered?
waster eletricity.

2. Test Operation
(1) Preparation of test operation
● The client approves the air conditioner installation.
● Specify the important notes for air conditioner to the client.
(2) Method of test operation
● Put through the power, press ON/OFF button on the remote
controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and
HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 16oC, the air conditioner
cant start cooling.

Installation and Maintenance 53


9. Maintenance
9.1 Error Code List
Display Method Possible Causes(For specific maintenance
Malfunction
of Indoor Unit A/C Status method, please refer to the following procedure of
Name
(Error Code) troubleshooting)
1. Refrigerant was superabundant;
High pressure Cool/Dry: except indoor fan operates, all
2. Poor heat exchange (including filth blockage of heat
protection of E1 loads stop operation.
exchanger and bad radiating environment ); Ambient
system Heat: all loads stops operation.
temperature is too high.
Anti-freezing
Cool/Dry: compressor and outdoor fan Not the error code. It’s the status code for the
protection for E2
stop while indoor fan operates. operation.
evaporator
System block The Dual-8 Code Display will show 1.Low-pressure protection
or refrigerant E3 E3 until the low pressure switch stop 2.Low-pressure protection of system
leakage operation. 3.Low-pressure protection of compressor
High discharge
Cool/Dry: compressor and outdoor fan
temperature Please refer to the malfunction analysis (discharge
E4 stop while indoor fan operates. Heat: all
protection of protection, overload).
loads stop.
compressor
Cool/Dry:compressor and outdoor fan 1. Supply voltage is unstable;
Overcurrent
E5 stop while indoor fan operates. Heat: all 2. Supply voltage is too low and load is too high;
protection
loads stop. 3. Evaporator is dirty.
Communi- Cool:compressor stops while indoor fan
cation E6 motor operates. Heat: all loads stops Refer to the corresponding malfunction analysis.
Malfunction operation.
High
Cool: compressor will stop while indoor
temperature Refer to the malfunction analysis (overload, high temperature
E8 fan will operate.
resistant resistant).
Heat: all loads stops operation.
protection
Cool/Dry:compressor will stop while
EEPROM Replace outdoor control panel AP1
EE indoor fan will operate;
malfunction
Heat: all loads stops operation.
Limit/decrease Discharging after the complete unit is de-energized for
frequency due 20mins, check whether the thermal grease on IPM Module
All loads operate normally, while
to high EU of outdoor control panel AP1 is sufficient and whether the
operation frequency for compressor is
temperature of radiator is inserted tightly.
decreased
module If its no use, please replace control panel AP1.
1. No jumper cap insert on mainboard.
Malfunction
Wireless remote receiver and button are 2. Incorrect insert of jumper cap.
protection of C5
effective, but can not dispose the related 3. Jumper cap damaged.
jumper cap
command 4. Abnormal detecting circuit of mainboard.
1. Is system cooling under high humidity environment, thus
temperature difference of heat transfer is small;
2. Check whether the big valve and small valve of outdoor
unit are opened completely;
Refrigerant Cool/Dry:compressor and outdoor fan
3. Is the temperature sensor of evaporator of indoor unit
insufficient F0 will stop while indoor fan will operate;
loose?
protection Heat: all loads stops operation.
4. Is the temperature sensor of condenser of outdoor unit
loose?
5. Is the capillary or the electronic expansion valve blocked?
6. Is refrigerant leaking?
1. Loosening or bad contact of indoor ambient temp. sensor
Indoor ambient
and mainboard terminal.
temperature Cool/Dry:indoor unit operates while other
2. Components in mainboard fell down leads short circuit.
sensor is F1 loads will stop; Heat: all loads stops
3. Indoor ambient temp. sensor damaged.(check with sensor
open/short operation.
resistance value chart)
circuited
4. Mainboard damaged.

54 Installation and Maintenance


1. Loosening or bad contact of Indoor evaporator temp.
Indoor
AC stops operation once reaches the sensor and mainboard terminal.
evaporator
setting temperature. Cooling, drying: 2. Components on the mainboard fall down leads short
temperature
F2 internal fan motor stops operation while circuit.
sensor is
other loads stop operation; heating: AC 3. Indoor evaporator temp. sensor damaged.(check temp.
open/short
stop operation sensor value chart for testing)
circuited
4. Mainboard damaged.
Outdoor ambient Cool/Dry: compressor stops while indoor Outdoor temperature sensor hasnt been connected well or is
temperature sensor is F3 fan operates; Heat: all loads stops damaged. Please check it by referring to the resistance table
open/short circuited operation. for temperature sensor)
Outdoor condenser Cool/Dry: compressor stops while indoor Outdoor temperature sensor hasnt been connected well or is
temperature sensor is F4 fan will operate; Heat: all loads stops damaged. Please check it by referring to the resistance table
open/short circuited operation. for temperature sensor)
Cool/Dry: compressor will sop after 1.Outdoor temperature sensor hasnt been connected well
Outdoor discharge operating for about 3 mins, while indoor or is damaged. Please check it by referring to the resistance
temperature sensor is F5 fan will operate; table for temperature sensor)
open/short circuited Heat: the complete unit will stop after 2.The head of temperature sensor hasnt been inserted into
operating for about 3 mins. the copper tube
Limit/decrease
All loads operate normally, while operation Refer to the malfunction analysis (overload, high temperature
frequency due to F6
frequency for compressor is decreased resistant)
overload
Decrease frequency All loads operate normally, while operation The input supply voltage is too low; System pressure is too
F8
due to overcurrent frequency for compressor is decreased high and overload

Decrease frequency
All loads operate normally, while operation Overload or temperature is too high; Refrigerant is
due to high air F9
frequency for compressor is decreased insufficient; Malfunction of electric expansion valve (EKV)
discharge
Limit/decrease
All loads operate normally, while operation
frequency due to FH Poor air-return in indoor unit or fan speed is too low
frequency for compressor is decreased
antifreezing
1. Measure the voltage of position L and N on wiring board
(XT), if the voltage is higher than 265VAC, turn on the unit
Cool/Dry: compressor will stop while indoor after the supply voltage is increased to the normal range.
Voltage for DC bus-
PH fan will operate; 2.If the AC input is normal, measure the voltage of electrolytic
bar is too high
Heat: all loads stops operation. capacitor C on control panel (AP1), if its normal, theres
malfunction for the circuit, please replace the control panel
(AP1)
1. Measure the voltage of position L and N on wiring board
(XT), if the voltage is higher than 150VAC, turn on the unit
Cool/Dry: compressor will stop while indoor after the supply voltage is increased to the normal range.
Voltage of DC bus-bar
PL fan will operate; 2.If the AC input is normal, measure the voltage of electrolytic
is too low
Heat: all loads stops operation. capacitor C on control panel (AP1), if its normal, theres
malfunction for the circuit, please replace the control panel
(AP1)
Compressor Min
P0 Showing during min. cooling or min. heating test
frequence in test state
Compressor rated
P1 Showing during nominal cooling or nominal heating test
frequence in test state
Compressor maximum
P2 Showing during max. cooling or max. heating test
frequence in test state
Compressor
intermediate P3 Showing during middle cooling or middle heating test
frequence in test state
Overcurrent protection Cool/Dry: compressor will stop while indoor Refer to the malfunction analysis (IPM protection, loss of
of phase current for P5 fan will operate; synchronism protection and overcurrent protection of phase
compressor Heat: all loads stops operation. current for compressor.
Charging malfunction Cool/Dry: compressor will stop while indoor
Refer to the part three—charging malfunction analysis of
of capacitor PU fan will operate;
capacitor
Heat: all loads stops operation.

Installation and Maintenance 55


Malfunction of module Cool/Dry: compressor will stop while indoor
temperature sensor P7 fan will operate; Replace outdoor control panel AP1
circuit Heat: all loads stops operation.

After the complete unit is de-energized for 20mins, check


Module high Cool:compressor will stop while indoor whether the thermal grease on IPM Module of outdoor
temperature P8 fan will operate; Heat: all loads stops control panel AP1 is sufficient and whether the radiator is
protection operation. inserted tightly. If its no use, please replace control panel
AP1.
1. Wiring terminal OVC-COMP is loosened. In normal state,
Cool/Dry: compressor will stop while indoor
Overload protection the resistance for this terminal should be less than 1ohm.
H3 fan will operate;
for compressor 2.Refer to the malfunction analysis ( discharge protection,
Heat: all loads stops operation.
overload)
Cool/Dry: compressor will stop while indoor Refer to the malfunction analysis (IPM protection, loss of
IPM protection H5 fan will operate; synchronism protection and overcurrent protection of phase
Heat: all loads stops operation. current for compressor.

Malfunction of zero- 1.Power supply is abnormal;


U8 All loads stops operation.
cross detection circuit 2.Detection circuit of indoor control mainboard is abnormal.

1. Bad contact of DC motor feedback terminal.


Internal fan motor, external fan motor,
2. Bad contact of DC motor control end.
Internal motor (fan compressor and electric heater stop
H6 3. Fan motor is stalling.
motor) do not operate operation,guide louver stops at present
4. Motor malfunction.
location.
5. Malfunction of mainboard revdetecting circuit.
Cool/Dry: compressor will stop while indoor Refer to the malfunction analysis (IPM protection, loss of
Desynchro-nizing of
H7 fan will operate; synchronism protection and overcurrent protection of phase
compressor
Heat: all loads stops operation. current for compressor.
Cool/Dry: compressor will stop while indoor
PFC protection HC fan will operate; Refer to the malfunction analysis
Heat: all loads stops operation.
Outdoor DC fan motor Outdoor DC fan motor malfunction lead to DC fan motor malfunction or system blocked or the connector
L3
malfunction compressor stop operation, loosed
compressor stop operation and Outdoor
To protect the electronical components when detect high
power protection L9 fan motor will stop 30s latter , 3 minutes
power
latter fan motor and compressor will restart
Indoor unit and
compressor and Outdoor fan motor cant
outdoor unit doesnt LP Indoor unit and outdoor unit doesnt match
work
match
Cool/Dry: compressor will stop while indoor
Failure start-up LC fan will operate; Refer to the malfunction analysis
Heat: all loads stops operation.
Heating
indicator
off for Defrosting will occur in heating mode.
Defrosting 0.5s and Compressor will operate while indoor fan Not the error code. It’s the status code for the operation
then will stop operation.
blinks
for 10s
1.Supply voltage is lower than AC175V;
The four-way valve is If this malfunction occurs in heating mode,
U7 2.Wiring terminal 4V is loosened or broken;
abnormal all loads stop
3.4V is damaged, please replace 4V.
Malfunction of phase Cool/Dry: compressor will stop while indoor
current detection U1 fan will operate; Replace outdoor control panel AP1
circuit for compressor Heat: all loads stops operation.

56 Installation and Maintenance


Malfunction of voltage Cool/Dry: compressor will stop while indoor
dropping for DC U3 fan will operate; Supply voltage is unstable
busbar Heat: all loads stops operation.

Malfunction of Cool/Dry: the compressor will stop while


Theres circuit malfunction on outdoor units control panel
complete units current U5 indoor fan will operate;
AP1, please replace the outdoor units control panel AP1.
detection Heat: all loads stops operation.
Cold air prevention Not the error code. It’s the status code for the
E9
protection operation.
Refrigerant recovery Cool/Dry: compressor and outdoor fan Refrigerant recovery. The maintenance personnel operate it
Fo
mode stops operation, while indoor fan operates. when he is maintaining the unit.
1. Outdoor ambient temperature exceeds the operation range
of unit (eg: less than-20oC or more than 60oC for cooling;
Cool: compressor and outdoor fan stops
more than 30oC for heating);
Undefined outdoor unit operation, while indoor fan operates;
oE 2. Failure startup of compressor?
error Heat: compressor, outdoor fan and indoor
3. Are wires of compressor not connected tightly?
fan stop operation.
4. Is compressor damaged?
5. Is main board damaged?
1. Main board of indoor unit is damaged;
Malfunction of Loads operate normally, while the unit 2. Detection board is damaged;
JF
detecting plate(WIFI ) can’t be normally controlled by APP. 3. The connection between indoor unit and detection board is
not good;

Analysis or processing of some of the malfunction display:


1. Compressor discharge protection
Possible causes: shortage of refrigerant; blockage of air filter; poor ventilation or air flow short pass for condenser; the sys-
tem has noncondensing gas (such as air, water etc.); blockage of capillary assy (including filter); leakage inside four-way
valve causes incorrect operation; malfunction of compressor; malfunction of protection relay; malfunction of discharge sen-
sor; outdoor temperature too high.
Processing method: refer to the malfunction analysis in the above section.
2. Low voltage overcurrent protection
Possible cause: Sudden drop of supply voltage.
3.Communication malfunction
Processing method: Check if communication signal cable is connected reliably.
4. Sensor open or short circuit
Processing method: Check whether sensor is normal, connected with the corre sponding position on the controller and if
damage of lead wire is found.
5. Compressor over load protection
Possible causes: insufficient or too much refrigrant; blockage of capillary and increase of suction temp.; improper running of
compressor, burning in or stuck of bearing, damage of discharge valve; malfunction of protector.
Processing method: adjust refrigerant amount; replace the capillary; replace the compressor; use universal meter to check if
the contactor of compress or is fine when it is not overheated, if not replace the protector.
6. System malfunction
i.e.overload protection.When tube temperature(Check the temperature of outdoor heat exchanger when cooling and check
the temperatur e of indoor heat exchanger when heating) is too high, protection will be activated.
Possible causes: Outdoor temperature is too high when cooling; insufficient outdoor air circulation; refrigerant flow malfunc-
tion.
please refer to the malfunction analysis in the previous section for handling method .
7. IPM module protection
Processing method:Once the module malfunction happens,if it persists for a long time and can not be selfcanceled, cut off
the power and turn off the unit,and then re-energize the unit again after about 10 min.After repeating the procedure for sever
times, if the malfunction still exists,replace the module.

Installation and Maintenance 57


If malfunction occurs,corresponding code will display and the unit will resume normal until protection or
malfunction disappears.

58 Installation and Maintenance


9.2 Procedure of Troubleshooting
●Indoor unit:
1. Malfunction of Temperature Sensor F1, F2
Main detection points:
● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
● Is there short circuit due to trip-over of the parts?
● Is the temperature sensor broken?
● Is mainboard broken?
Malfunction diagnosis process: Start

Is the wiring terminal between the


temperature sensor and the controller Yes
loosened or poorly contacted?

Insert the temperature


sensor tightly

No
No Is malfunction
eliminated

Is there short circuit due to trip- Yes


over of the parts

Make the parts upright

No

No Is malfunction Yes
eliminated

Is the temperature sensor normal No Yes


according to the resistance table?

Replace it with a
temperature sensor with
the same model

Yes

No Is malfunction
eliminated

Replace the mainboard with


the same model.

Yes

End

Installation and Maintenance 59


2. Malfunction of Blocked Protection of IDU Fan Motor H6
Main detection points:
● SmoothlyIs the terminal of motor connected tightly?
● The fan motor can't operate?
● The motor is broken?
● Detectioncircuit of the mainboard is defined abnormal?
Malfunction diagnosis process:
2.1 PG motor
Start

While power is off stir the blade


No
with a tool to see whether the
blade rotates smoothly
Tighten the screw; reassemble the blade, motor
and shaft bearing rubber base sub-assy to make
sure there is no foreign object between them
Yes

No Is malfunction Yes
eliminated

Check if the connection of PG No


motor feedback terminal is firm
Insert the control terminal
of PG motor tightly

Yes
No Is malfunction Yes
eliminated

Check if the connection of PG No


motor control terminal is firm

Reinstall the blade


and motor correctly
Yes

No Is malfunction Yes
eliminated

Turn on the unit again; measure


whether the output voltage on Yes
control terminal for PG motor is Yes
more than 50V within 1 min after
the louvers are opened

Yes Is the motor started up

No
Measure the voltage of this foot to
neutral wire on the mainboard Replace PG motor
No

No Is malfunction Yes
eliminated

Replace the mainboard


with the same model

End

60 Installation and Maintenance


2.2 DC motor

Display shows "H6"

Pull the blade with hand


under de-energization
status

Check whether the Adjust the motor and the blade


blade operates smoothly 1 to make the motor operate
smoothly.

< Put through the


power to check whether the
1
malfunction is
eliminated

Under power-off status,


check whether the wiring terminal < Insert the wiring terminal
between the indoor fan and the of indoor fan again
main board is loose

Put through the


1 1 power and turn on the unit to <
check whether the malfunction is
eliminated

Put through the power and


turn on the unit to check whether the It's the malfunction of main board.
voltage between terminal 1 and terminal 2 1 Replace the main board with a
of motor is 280~310VD new one with the same model.

<
<

Check whether the It's the malfunction of main board.


voltage between terminal 2 and 1 Replace the main board with a
terminal 3 of motor is 15VDC new one with the same model.

Check whether there's It's the malfunction of main board.


voltage signal between terminal 2 1 Replace the main board with a
and terminal 4 of motor new one with the same model.

<

It's the malfunction of motor.


Replace the motor with a new End
one with the same mode

Installation and Maintenance 61


3. Malfunction of Protection of Jumper Cap C5
Main detection points:
● Is there jumper cap on the mainboard?
● Is the jumper cap inserted correctly and tightly?
● The jumper is broken?
● The motor is broken?
● Detection circuit of the mainboard is defined abnormal?
Malfunction diagnosis process:

Start

No Appearance of the
Is there jumper cap on the mainboard?
jumper cap

Assemble the jumper


cap with the same model
Yes

No Is malfunction
eliminated

Is the jumper cap inserted correctly No


and tightly?

Insert the jumper


cap tightly
Yes

No Is malfunction Yes
eliminated

Replace the jumper cap with


the same model

Is malfunction Yes
eliminated

Yes
No

Replace the mainboard


with the same model

End

62 Installation and Maintenance


4. Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8
Main detection points:
● Instant energization afte de-energization while the capacitordischarges slowly?
● The zero-cross detectioncircuit of the mainboard is defined abnormal?
Malfunction diagnosis process:

Start

Turn power off for


1minute,the turn
back on

The unit returns to normal.


U8 is still No Conclusion:U8 is displayed due to
displayed power off/on while the
capacitor discharges slowly.

Yes

The zero-cross detection circuit


of the mainboard is defined
abnormal.Replace the mainboard
with the same model

End

Installation and Maintenance 63


5. High Temperature and Overload Protection (AP1 below means control board of outdoor unit) E8

Start

Normal protection, please use it


If the outdoor ambient temperature is Yes Unit restarts Yes
after improving the outdoor ambient
higher than 53°C? normally
temperature

No
No

Improve the radiating environment of


Unit restarts Yes
unit (clean the heat exchanger and
is good? remove surrounding obstacles) normally

No
No

If the indoor and outdoor fan are Yes Adjust the


Connect normally?
running normally? connection

Yes

Yes
Yes Replace fan
Fan capacitor is broken? capacitor
Replace outdoor
mainboard
No

Motor is broken? Yes


Replace motor

No

Replace mainboard

End

64 Installation and Maintenance


6. Malfunction of detecting plate(WIFI) JF

Start

check if the connection wire


are correctly connected

Yes

Replace the detecting


plate with the same model

Is malfunction
No eliminated

Yes
Replace the mainboard
with the same model

The end

Installation and Maintenance 65


●Outdoor unit:
1.Capacity charging malfunction (outdoor unit malfunction) (AP1 below is control board of outdoor unit)

Main detection point:

● Detect if the voltage of L and N terminal of wiring board is between 210AC-240AC by alternating voltage meter;
● Is reactor (L) well connected? Is connection wire loosened or pull-out? Is reactor (L) damaged?

Malfunction diagnosis process:

Turn on the unit


and wait 1 minute

Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor

Fault with the Replace the


Voltage higher than Y voltage testing control
200V? circuit on panel AP1
control panel AP1

Measure the AC voltage


between
terminal L and and N on wiring
board XT(power supply)

Shut down the


Voltage within N power and repair power on and If the fault is
210VAC~250VAC? the power supply to restart the unit eliminated? Y
restore the range
210VAC~250VAC

Shut down the power and wait 20 minutes;


or use DC voltmeter to measure the voltage
on the two ends of capacitor (test3), N
until the voltage is lower than 20V

Check the
connection of reactor
(Lin the Electrical Wiring
Diagram)

Connect the reactor


Laccording to Elec- Re-energize and
If the wiring of N turn on the unit If the fault is Y
reactor Lis normal? trical Wiring Diagr- eliminated?
am correctly

Replace the control


panel AP1 N

End

66 Installation and Maintenance


2.Diagnosis for anti-high temperature, overload protection (AP1 below is control board of outdoor unit)

Main detection point:

● If the outdoor ambient temperature is in normal range;


● If the indoor and outdoor fan is running normal;
● If the radiating environment of indoor and outdoor unit is well.

Malfunction diagnosis process:

Anti-high temperature,
overload protection

Normal protection, please use


If the outdoor ambient temperature is it after improve the outdoor
higher than 53 °C? Y
ambient temperature

After the unit de-


energized for 20min

Improve the
If the radiating of outdoor radiating
and indoor unit is well? Y environment of
unit

N
1. Check if fan terminal
OFAN is connected well
If the indoor and outdoor N 2. Test if resistance value
fan work well? of any two terminals is less
than 1kΩ with ohmic meter

Replace fan
capacitor C1
Replace
control board
AP1

Replace
outdoorfan

End

Installation and Maintenance 67


3.IPM protection, phase current overcurrent (the control board as below indicates the control board
of outdoor unit) H5/P5
Mainly detect:
(1) Compressor COMP terminal (2) voltage of power supply (3) compressor
(4) Refrigerant-charging volume (5) air outlet and air inlet of outdoor/indoor unit
Troubleshooting:

Turn on the unit


after energization

Check the connection


Whether IPM between the control board
protection occurs after the unit has N and the compressor by
operated for a while? referring to the electric
wiring diagram

Whether Correctly connect the wires of Check whether wires


compressor according to the Y of compressor (UVW) are connected
the voltage between
terminal L and terminal N electric wiring diagram, and correctly
of XT is within 210AVC~ then turn on the unit
250VAC? N

Measure the resistance value


among three terminals (UVW)
Check the power of compressor with a resistance
Whether IPM supply voltage and measuring meter.
protection occurs after the unit has N make the power voltage
operated for a while? resume to the range
of 210VAC~250VAC Whether the
resistance value of three terminals
are almost the same.
Y

1. Whether the heat exchangers of indoor unit and outdoor unit are Measure the resistance
dirty? Whether the radiation is affected because the unit is between three terminals (UVW)
covered by the objects? of compressor and the copper pipe
2. When indoor fan and outdoor unit are operate normally? with resistance measuring meter
3. Whether the system pressure is too high?
4. Whether the pressure is because there's too much refrigerant?

Whether the
resistance value is more than
500ohm?

Whether there's Correct it one by one N


abnormal phenomenons Y according to the Service
described as above? Manual, and then turn on
the unit. N Replace the
compressor
N
Y

Whether the unit


can operate normally?

Y
Replace control Y
board

End

68 Installation and Maintenance


4. Start-up failure (following AP1 for outdoor unit control board)

Mainly detect:
●Whether the compressor wiring is connected correct?
●Is compressor broken?
●Is time for compressor stopping enough?
Fault diagnosis process:

Power on the unit

Is stop time of the compressor No Restart it up after


longer than 3 minutes? 3 minutes

Yes

Does startup fail?

Yes

Connect the wires as


Are the wires for the compressor connected No per the connection
correctly? Is connection sequence right? diagram

Yes

Replace the control panel AP1

No

If the fault is eliminated?

No

Replace the
compressor

Yes

End

Installation and Maintenance 69


5. Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit)

Mainly detect:
●Is the system pressure too high?
●Is the input voltage too low?
Fault diagnosis process:

Out of step occurs once the Out of step occurs in


unit is powered on. operation

No

Is stop time of the No Check if the fan terminal Replace the fan
compressor longer than Is the outdoor fan working OFAN is connected capacitor C1
3 minutes? normally?
correctly

Yes
Yes
Replace the
outdoor fan
Is the outdoor unit blocked Yes Remove foreign
by foreign objects? objects
Are the wires for the compressor connected
correctly? Is connection sequence right? No
Is the connection made in clockwise
direction?
Replace the
No control panel AP1
Connect the Yes
wires correctly

Replace the
control panel AP1
Yes
If the fault is eliminated?

Yes
If the fault is eliminated? No

No Replace the
compressor
Replace the
compressor

End
End

70 Installation and Maintenance


6. Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)

Mainly detect:
●Is the PMV connected well or not? Is PMV damaged?
●Is refrigerant leaked?
Fault diagnosis process:

20 minutes after the


complete unit is
powered off

Is the terminal FA for the Connect the


electronic expansion valve No
wires correctly
connected correctly?

Yes

Resistances between the first four pins


close to the terminal hole and the fifth
pin are almost the same, less than 100
ohm.

Replace the electronic


expansion valve

If the fault is eliminated? Yes

No

Replace the
control panel
AP1

If the fault is eliminated? Yes

No

Coolant leakage, refilling


the coolant

End

Installation and Maintenance 71


7. Communication malfunction: (following AP1 for outdoor unit control board)

Mainly detect:
●Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged?
●Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not, if is
there any
damage?
Fault diagnosis process:

Start

Did the equipment operate No


normally before the failure
Yes occurs?

Check the wiring of the indoor and


outdoor units with reference to the
wiring diagram

Check wiring inside


of the indoor and Yes Is the connection right?
outdoor units
No
No

Correctly connect the


The AP1 voltage corresponding wires for
Yes Are wires broken? the indoor and outdoor
detection circuit
is at fault units with reference to
the wiring diagram
No

No Check the communication


If the fault is eliminated?
circuit of the outdoor unit

If the fault is eliminated?

The communication Yes Replace the main board


circuit is abnormal AP1 of the outdoor unit

No
If the fault is eliminated?

No
Replace the main board
of the indoor unit
Yes

Yes Yes
End

72 Installation and Maintenance


8. Malfunction of Overcurrent Protection
Main detection points:
● Is the supply voltage unstable with big fluctuation?
● Is the supply voltage too low with overload?
● Hardware trouble?
Malfunction diagnosis process:

Start

Yes Is malfunction Yes


Is the supply voltage unstable
of the rated voltage on the nameplate eliminated

No No

Is the supply voltage too low Yes Adjust the supply voltage to maintain it Is malfunction Yes
with overload? within normal range eliminated

No No

Is the indoor / outdoor Yes Clean the indoor and outdoor heat Is malfunction Yes
heat exchanger dirty,or are the air inlet exchangers and remove the blockage eliminated
and outlet blocked? of air inlet and outlet

No
No

The fan is abnormal? Fan Yes Check the motor and reinstall the Is malfunction Yes
speed is too low or fan doesnt rotate motor to have the fan run normally eliminated

No No

Measure the current of live wire on


the main board with a clamp ampere No Replace the mainboard with the same Yes
Is malfunction
meter. Is the current higher than the model eliminated
value of the overcurrent protection?

Yes No

Is there blockage inside the system? Yes


(Filth blockage, ice plug, greasy Flush the heat exchangers with high Is malfunction Yes
blockage, the cut off valve hasnt been pressure nitrogen eliminated
opened completely)

No No

Is the compressor running abnormally? Yes


Is malfunction Yes
Is there abnormal sound or oil leakage; Replace the compressor
eliminated
Is the temperature of the shell too high,
etc.?

No

Replace the mainboard


with the same model

End

Installation and Maintenance 73


9.3 Troubleshooting for Normal Malfunction
1. Air Conditioner Cant be Started Up
Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Confirm whether its due to power failure. If yes,
No power supply, or poor connection After energization, operation indicator isnt bright wait for power recovery. If not, check power
for power plug and the buzzer cant give out sound supply circuit and make sure the power plug is
connected well.
Wrong wire connection between Check the circuit according to circuit diagram
Under normal power supply circumstances,
indoor unit and outdoor unit, or poor and connect wires correctly. Make sure all wiring
operation indicator isnt bright after energization
connection for wiring terminals terminals are connected firmly
Make sure the air conditioner is grounded reliably
Make sure wires of air conditioner is connected
After energization, room circuit breaker trips off at correctly
Electric leakage for air conditioner
once Check the wiring inside air conditioner. Check
whether the insulation layer of power cord is
damaged; if yes, place the power cord.
Model selection for air switch is
After energization, air switch trips off Select proper air switch
improper
After energization, operation indicator is bright,
Replace batteries for remote controller
Malfunction of remote controller while no display on remote controller or buttons
Repair or replace remote controller
have no action.

2. Poor Cooling (Heating) for Air Conditioner


Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting

Set temperature is improper Observe the set temperature on remote controller Adjust the set temperature
Rotation speed of the IDU fan
Small wind blow Set the fan speed at high or medium
motor is set too low
Filter of indoor unit is blocked Check the filter to see its blocked Clean the filter
Check whether the installation postion is proper
Installation position for indoor unit Adjust the installation position, and install the
according to installation requirement for air
and outdoor unit is improper rainproof and sunproof for outdoor unit
conditioner
Discharged air temperature during cooling is
higher than normal discharged wind temperature;
Find out the leakage causes and deal with it. Add
Refrigerant is leaking Discharged air temperature during heating is lower
refrigerant.
than normal discharged wind temperature; Units
pressure is much lower than regulated range
Malfunction of 4-way valve Blow cold wind during heating Replace the 4-way valve
Discharged air temperature during cooling is
higher than normal discharged wind temperature;
Discharged air temperature during heating is lower
Malfunction of capillary Replace the capillary
than normal discharged wind temperature; Unitt
pressure is much lower than regulated range. If
refrigerant isnt leaking, part of capillary is blocked
The pressure of valves is much lower than that
Flow volume of valve is insufficient Open the valve completely
stated in the specification
Malfunction of horizontal louver Horizontal louver cant swing Refer to point 3 of maintenance method for details
Refer to troubleshooting for H6 for maintenance
Malfunction of the IDU fan motor The IDU fan motor cant operate
method in details
Malfunction of the ODU fan motor The ODU fan motor cant operate Refer to point 4 of maintenance method for details

Malfunction of compressor Compressor cant operate Refer to point 5 of maintenance method for details

3. Horizontal Louver Cant Swing


Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Wrong wire connection, or poor Check the wiring status according to circuit Connect wires according to wiring diagram to make
connection diagram sure all wiring terminals are connected firmly
Stepping motor is damaged Stepping motor cant operate Repair or replace stepping motor
Others are all normal, while horizontal louver cant
Main board is damaged Replace the main board with the same model
operate

74 Installation and Maintenance


4. ODU Fan Motor Cant Operate
Possible causes Discriminating method (air conditioner status) Troubleshooting
Wrong wire connection, or poor Check the wiring status according to circuit Connect wires according to wiring diagram to make
connection diagram sure all wiring terminals are connected firmly
Measure the capacity of fan capacitor with an
Capacity of the ODU fan motor is universal meter and find that the capacity is out of
Replace the capacity of fan
damaged the deviation range indicated on the nameplate of
fan capacitor.
Use universal meter to measure the power supply
Power voltage is a little low or high Suggest to equip with voltage regulator
voltage. The voltage is a little high or low
When unit is on, cooling/heating performance is
Change compressor oil and refrigerant. If no better,
Motor of outdoor unit is damaged bad and ODU compressor generates a lot of noise
replace the compressor with a new one
and heat.
5. Compressor Cant Operate
Possible causes Discriminating method (air conditioner status) Troubleshooting
Wrong wire connection, or poor Check the wiring status according to circuit Connect wires according to wiring diagram to make
connection diagram sure all wiring terminals are connected firmly
Measure the capacity of fan capacitor with an
Capacity of compressor is universal meter and find that the capacity is out of
Replace the compressor capacitor
damaged the deviation range indicated on the nameplate of
fan capacitor.
Use universal meter to measure the power supply
Power voltage is a little low or high Suggest to equip with voltage regulator
voltage. The voltage is a little high or low
Use universal meter to measure the resistance
Coil of compressor is burnt out Repair or replace compressor
between compressor terminals and its 0
Cylinder of compressor is blocked Compressor cant operate Repair or replace compressor

6. Air Conditioner is Leaking


Possible causes Discriminating method (air conditioner status) Troubleshooting

Drain pipe is blocked Water leaking from indoor unit Eliminate the foreign objects inside the drain pipe

Drain pipe is broken Water leaking from drain pipe Replace drain pipe
Water leaking from the pipe connection place of
Wrapping is not tight Wrap it again and bundle it tightly
indoor unit

7. Abnormal Sound and Vibration

Possible causes Discriminating method (air conditioner status) Troubleshooting


When turn on or turn off the unit,
Normal phenomenon. Abnormal sound will
the panel and other parts will Theres the sound of "PAPA"
disappear after a few minutes.
expand and theres abnormal sound
When turn on or turn off the unit,
Normal phenomenon. Abnormal sound will
theres abnormal sound due to flow Water-running sound can be heard
disappear after a few minutes.
of refrigerant inside air conditioner
Foreign objects inside the indoor Remove foreign objects. Adjust all parts position
unit or therere parts touching Theres abnormal sound fro indoor unit of indoor unit, tighten screws and stick damping
together inside the indoor unit plaster between connected parts
Foreign objects inside the outdoor Remove foreign objects. Adjust all parts position
unit or therere parts touching Theres abnormal sound fro outdoor unit of outdoor unit, tighten screws and stick damping
together inside the outdoor unit plaster between connected parts
Short circuit inside the magnetic During heating, the way valve has abnormal
Replace magnetic coil
coil electromagnetic sound
Adjust the support foot mat of compressor, tighten
Abnormal shake of compressor Outdoor unit gives out abnormal sound
the bolts
If add too much refrigerant during maintenance,
Abnormal sound inside the
Abnormal sound inside the compressor please reduce refrigerant properly. Replace
compressor
compressor for other circumstances.

Installation and Maintenance 75


10. Exploded View and Parts List
10.1 Indoor Unit

GWH07AGA-K6DNA1A/I

39 40 41 42 1 2 3 4 5 6

ON/OFF

TURBO

FAN
MODE

I FEEL T-ON T-OFF

TEMP CLOCK

LIGHT WiFi SLEEP

38
37

36 7
8
9
10
11
12
13
35 14
15
34 16
17
18
19
20
21

33

32 31 30 29 28 27 26 25 24 23 22

The component picture is only for reference; please refer to the actual product.

76 Installation and Maintenance


NO. Description Qty

1 Evaporator Support 1
2 Axile Bush Sub-assy 1
3 Cross Flow Fan 1
4 Evaporator Assy 1
5 Motor Press Plate 1
6 Wall Mounting Frame Sub-assy 1
7 Fan Motor 1
8 Rear Case 1
9 Connecting pipe clamp 1
10 Screw Cover 1
11 Plasmacluster Ion /
12 Rubber Plug (Water Tray) 1
13 Air Louver 1
14 Crank 2
15 Stepping Motor 1
16 Stepping Motor 1
17 Air Louver (Auto) 1
18 Stepping Motor 1
19 Electric Box Assy 1
20 Wire Clamp 1
21 Electric Box 1
22 Earthing 1
23 Terminal Board 1
24 Cable Clamp 1
25 Main Board 1
26 Jumper 1
27 Plug Pin 4
28 Helicoid Tongue 1
29 Guide Louver (lower) 1
30 Guide Louver (upper) 1
31 Electric Box Cover2 1
32 Display Board 1
33 Front Panel 1
34 Front Case 1
35 Filter Sub-Assy 1
36 Swing Lever 1
37 Left Axile Bush 2
38 Drainage Hose 1
39 Power Cord 1
40 Connecting Cable 0
41 Connecting Cable /
42 Remote Controller 1

Some models may not contain some parts, please refer to the actual product.

Installation and Maintenance 77


GWH09AGC-K6DNA1F/I GWH12AGC-K6DNA1F/I

33 34 35 36

13

12
ON/OFF

TURBO

FAN
MODE

I FEEL T-ON T-OFF

11
TEMP CLOCK

LIGHT WiFi SLEEP

10

14

16
15
1 2 3 4 5 6 7 8 9

17

18

19
20
24
25
21
26
27 22

23

32 31 30 29 28

The component picture is only for reference; please refer to the actual product.

78 Installation and Maintenance


NO. Description Qty

1 Front Panel 1
2 Guide Louver (upper) 1
3 Guide Louver (lower) 1
4 Screw Cover 1
5 Front Case 1
6 Filter Sub-Assy 1
7 Helicoid Tongue 1
8 Air Louver(left) 1
9 Left Axile Bush 2
10 Rear Case assy 1
11 Ring of Bearing 1
12 O-Gasket sub-assy of Bearing 1
13 Evaporator Support 1
14 Wall Mounting Frame 1
15 Evaporator Assy 1
16 Cross Flow Fan 1
17 Motor Press Plate 1
18 Fan Motor 1
19 Connecting pipe clamp 1
20 Drainage Hose 1
21 Stepping Motor 1
22 Stepping Motor 1
23 Crank 2
24 Air Louver(auto) 1
25 Sweeping connecting rod 1
26 Stepping Motor 1
27 Air Louver(right) 1
28 Main Board 1
29 Electric Box Assy 1
30 Terminal Board 1
31 Electric Box Cover 1
32 Display Board 1
33 Power Cord 1
34 Connecting Cable 0
35 Connecting Cable 0
36 Remote Controller 1

Some models may not contain some parts, please refer to the actual product.

Installation and Maintenance 79


GWH18AGD-K6DNA1E/I

34 33 32 31 30 12

ON/OFF

11

TURBO

FAN
MODE

I FEEL

LIGHT
TEMP

WiFi
T-ON T-OFF

CLOCK

SLEEP
13

14
10

9
15
8

7
6
16
5
17
4
3 18
37
19
2

23
24
25
35 26
1 21 20
36
22
27

28
29

The component picture is only for reference; please refer to the actual product.

80 Installation and Maintenance


NO. Description Qty

1 Front Panel 1
2 Front Case Assy 1
3 Guide Louver Sub-assy 1 1
4 Guide Louver Sub-assy 2 1
5 Plug Pin 2
6 Left Axile Bush 2
7 Rear Case 1
8 Cross Flow Fan 1
9 Ring of Bearing 1
10 O-Gasket sub-assy of Bearing 1
11 Evaporator Support 1
12 Evaporator Assy 1
13 Fan Motor 1
14 Motor Press Plate 1
15 Wall Mounting Frame Sub-assy 1
16 Electric Box Assy 1
17 Connecting pipe clamp 1
18 Rubber Plug (Water Tray) 1
19 Supporter 1
20 Electric Box 1
21 Main Board 1
22 Jumper 1
23 Stepping Motor 1
24 Stepping Motor 1
25 Crank 2
26 Drainage Hose 1
27 Filter Sub-Assy 1
28 Screw Cover 2
29 Electric Box Cover 1
30 Remote Controller 1
31 Connecting Cable 0
32 Connecting Cable /
33 Power Cord 1
34 Temperature Sensor 1
35 Plasmacluster Ion /
36 Stepping Motor 1
37 Teminal Board 1

Some models may not contain some parts, please refer to the actual product.

Installation and Maintenance 81


GWH24AGE-K6DNA1A/I

40 41 42 43
17

16 18
ON/OFF

TURBO
15
FAN
MODE

I FEEL T-ON T-OFF

TEMP CLOCK

LIGHT WiFi SLEEP

14

13 19
12
11

10
9 20
8 21
22
5 6 7
23
24

1 2 3 4 25
28
26
29
30 27

31
32

33

34

39 38 37 36 35

The component picture is only for reference; please refer to the actual product.

82 Installation and Maintenance


NO. Description Qty

1 Front Panel 1
2 Filter Sub-Assy 1
3 Screw Cover 3
4 Front Case 1
5 Plug Pin 4
6 Guide Louver Sub-assy 1 1
7 Guide Louver Sub-assy 2 1
8 Sweeping Connecting Rod 1
9 Air Louver(Automatic) 2
10 Helicoid Tongue 1
11 Left Axile Bush 2
12 Rear Case 1
13 Drainage Hose 1
14 Cross Flow Fan 1
15 O-Gasket sub-assy of Bearing 1
16 Ring of Bearing 1
17 Evaporator Support 1
18 Evaporator Assy 1
19 Wall Mounting Frame 1
20 Motor Press Plate 1
21 Fan Motor 1
22 Plasmacluster Ion 1
23 Connecting pipe clamp 1
24 Rubber Plug (Water Tray) 1
25 Crank 2
26 Stepping Motor 1
27 Stepping Motor 1
28 Stepping Motor 1
29 Sweep Blade 1
30 Air Louver(Automatic) 1
31 Electric Box 1
32 Display Board 1
33 Main Board 1
34 Jumper 1
35 Supporter 1
36 Terminal Board 1
37 Cable Clamp 1
38 Electric Box Assy 1
39 Electric Box Cover 1
40 Connecting Cable 0
41 Power Cord 0
42 Temperature Sensor 1
43 Remote Controller 1
Some models may not contain some parts, please refer to the actual product.

Installation and Maintenance 83


10.2 Outdoor Unit
GWH07AGA-K6DNA1A/O

1 2 3 4 5 6 7 8

10

11

12

28
27

13

26 14

15

16
25

24 23 22 21 20 19 18 17

The component is only for rererence;please refer to the actual product

84 Installation and Maintenance


NO. Description Qty
1 Left Side Plate 1
2 Motor Support 1

3 Top Cover Sub-Assy 1

4 Top cover 1

5 Condenser Sub-Assy 1

6 Sponge(Condenser) /

7 Condenser Assy 1

8 Electric Box Assy 1

9 Electric Box 1

10 Temp Sensor Sleeving 1

11 Main Board 1

12 Terminal Board 1

13 Silencer 1

14 Earthing Plate Sub-assy 1

15 Handle 1

16 Valve Support Block 2

17 Right Side Plate 1

18 Cut-off valve 1/4(N) 1

19 Valve Support 1

20 Sensor Insert 1

21 Compressor and Fittings 1

22 4-Way Valve Assy 1

23 Chassis Sub-assy 1

24 Cabinet 1

25 Front Grill 1

26 Axial Flow Fan 1

27 Fan Motor 1

28 Capillary Sub-assy 1

Some models may not contain some parts, please refer to the actual product.

Installation and Maintenance 85


GWH09AFC-K6DNA2F/O

1 2 3 4
32 33

27
28 5
29
30
31 6
26
7
25
8
24

10

11

34

12

23 22 21 20 19 18 17 16 15 14 13

The component is only for rererence;please refer to the actual product

86 Installation and Maintenance


NO. Description Qty
1 Coping 1
2 4-Way Valve 1

3 4-Way Valve Assy 1

4 Sponge(Condenser) 1

5 Temperature Sensor Support 1

6 Condenser Assy 1

7 Capillary Sub-assy 1

8 Sensor Insert 1

9 Right Side Plate 1

10 Earthing Plate Sub-Assy 1

11 Wire Clamp 1

12 Valve Cover 1

13 Silencer 1

14 Cut-off valve 3/8(N) 1

15 Cut-off valve 1/4(N) 1

16 Valve Support 1

17 Compressor and Fittings 1

18 Chassis Sub-assy 1

19 Motor Support 1

20 Fan Motor 1

21 Axial Flow Fan 1

22 Cabinet 1

23 Front Grill 1

24 Drainage Joint(ODU) /

25 Left Side Plate 1

26 Clapboard 1

27 Electric Box Assy 1

28 Electric Box 1

29 Main Board 1

30 Electric Box Cover 1

31 Terminal Board 1

32 Temperature Sensor 1

33 Raidator 1

34 Handle (Right) 1

Some models may not contain some parts, please refer to the actual product.

Installation and Maintenance 87


GWH12AFC-K6DNA2F/O

1 2 3
36 37

31
32 4
33
34
35 5
30
6
29
7
28 8

10

11

12

13

14

27 26 25 24 23 22 21 20 19 18 17 16 15

The component is only for rererence;please refer to the actual product

88 Installation and Maintenance


NO. Description Qty
1 Coping 1
2 Supporting Board(Condenser) 1
3 4-Way Valve 1
4 Temperature Sensor Support 1
5 Condenser Assy 1
6 Temp Sensor Sleeving 1
7 Sensor Insert 1
8 Handle 1
9 Right Side Plate 1
10 Earthing Plate Sub-assy 1
11 Wire Clamp 1
12 Electronic Expansion Valve 1
13 Electric Expand Valve Fitting 1
14 Valve Cover 1
15 Silencer 1
16 Cut off Valve Sub-Assy 1
17 Strainer 1
18 Cut off Valve Assy 1
19 Valve Support 1
20 4-Way Valve Assy 1
21 Compressor and Fittings 1
22 Chassis Sub-assy 1
23 Motor Support 1
24 Brushless DC Motor 1
25 Axial Flow Fan 1
26 Cabinet 1
27 Front Grill 1
28 Drainage Joint(ODU) 1
29 Left Side Plate 1
30 Clapboard 1
31 Electric Box Assy 1
32 Electric Box 1
33 Main Board 1
34 Electric Box Cover 1
35 Terminal Board 1
36 Temperature Sensor 1
37 Radiator 1

Some models may not contain some parts, please refer to the actual product.

Installation and Maintenance 89


GWH18AGD-K6DNA1E/O

30 31 1 2 3

4
25 5
26
27
24 6
28 29
7

8
9
23 10

11
22
21
12
20

19 18 17 16 15 14 13

The component is only for rererence;please refer to the actual product

90 Installation and Maintenance


NO. Description Qty
1 Top Cover Assy 1
2 Condenser Assy 1
3 4-Way Valve 1
4 Tempreture Sensor clamp 1
5 4-Way Valve Assy 1
6 Electric Expand Valve Fitting 1
7 Electric Expansion Valve Sub-Assy 1
8 Wire Clamp 1
9 Right Side Plate 1
10 Earthing Plate Sub-assy 1
11 Handle 1
12 Valve Cover 1
13 Cut-off valve 1/4(N) 1
14 Cut-off valve 1/2(N) 1
15 Valve Support 1
16 Compressor and Fittings 1
17 Chassis Sub-assy 1
18 Cabinet 1
19 Front Grill 1
20 Axial Flow Fan 1
21 Brushless DC Motor 1
22 Motor Support 1
23 Left Side Plate 1
24 Clapboard Assy 1
25 Electric Box Assy 1
26 Electric Box 1
27 Main Board 1
28 Electric Box Cover 1
29 Terminal Board 1
30 Temperature Sensor 1
31 Radiator 1

Some models may not contain some parts, please refer to the actual product.

Installation and Maintenance 91


GWH24AFE-K6DNA2I/O

22 21 20 19 18 17 16

15
23
14
24
13

25 12

26
11

1 2 3 4 5 6 7 8 9 10

The component is only for rererence;please refer to the actual product

92 Installation and Maintenance


NO. Description Qty
1 Front Grill 1
2 Front Panel 1
3 Axial Flow Fan 1
4 Chassis Sub-assy 1
5 Compressor and Fittings 1
6 Electronic Expansion Valve Assy 1
7 Right Side Plate 1
8 Valve Support 1
9 Cut-off valve 1/4(N) 1
10 Cut-off valve 5/8(N) 1
10 Valve Cover 1
11 Handle 1
12 Terminal Board 1
14 4-Way Valve Assy 1
15 Condenser Assy 1
16 Clapboard Assy 1
17 Motor Support 1
18 Brushless DC Motor 1
19 Top Cover Assy 1
20 Left Side Plate 1
21 Condenser Left Border Plate 1
22 Electric Box Assy 1
23 Radiator 1
24 Electric Box 1
25 Main Board 1
26 Electric Box Cover 1

Some models may not contain some parts, please refer to the actual product.

Installation and Maintenance 93


11. Removal Procedure
11.1 Removal Procedure of Indoor Unit Caution: discharge the refrigerant
completely before removal.

Step Procedure

Before disassemble

Turn off the air conditioner and disconnect the


power before disassemble the air conditioner.

1. Remove filter

Filter

Hold the handle on the filter, pull it upwards to let


the clasp at the top part of the filter loose, push it
forwards and then the filter can be pulled out.

Handle

2.Remove upper and lower guide louver

Push out the plug pin on upper and lower guide louver,
Bend the guide louver with hand and then separate
the guide louver from the crank shaft of step motor to
remove it.

Guide Louver

94 Installation and Maintenance


Step Procedure

3.Remove panel
Panel rotation
Panel Display

Open the front panel; separate the panel rotation shaft Screws
from the groove fixing the front panel and then removes
the front panel.

Note:
The display of some models is fixed on the panel;
unscrew the screws fixing the display on the panel
before removing the panel.

4.Remove electric box cover 2

Screw

Remove the screws on the electric box cover 2 to


remove the electric box cover 2.

Electric box cover 2

5.Remove front case sub-assy


Screws
a

Remove the screws fixing front case.

Note:
(1) Open the screw caps before removing the screws
around the air outlet.
(2) The quantity of screws fixing the front case sub-assy Front case
Screw caps
is different for different models. sub-assy
b Screws
Left clasp Middle clasp Right clasp

Loosen the clasps at left, middle and right sides of front


case. Life the front case sub-assy upwards to remove it.

Installation and Maintenance 95


Step Procedure

6.Remove electric box assy


a Remove the screw fixing electric box assy.

Step motor

Grounding Indoor tube


screw temperature sensor Electric box assy

b
① Cut off the wire binder and pull out the Main board
indoor tube temperature sensor.
② Screw off one grounding screw.
③ Remove the wiring terminals of motor, cold plasma
generator and stepping motor. Wiring terminal
④ Remove the electric box assy. of motor
⑤ Screw off the screws that are locking each. Wiring terminal
of cold plasma
generator
Wiring terminal
of stepping motor

Screws
Wire binder
Rotate the electric box assy. Twist off the screws that
are locking the wire clip and loosen the power cord.
C
Remove the wiring terminal of power cord. Lift up the
main board and take it off. Power cord

Screw Wire clip

Instruction:Some wiring terminal of this products is


with lock catch and other devices.The pulling method Circlip
Holder
is as below:
1.Remove the soft sheath for some terminals at first,
hold the circlip and then pull out the terminals,
2.Pull out the holder for some terminals at first(holder
Connector
is not available for some wiring terminal).hold the
Soft sheath
connector and then pull the terminal.

96 Installation and Maintenance


Step Procedure

5.Remove panel
a Remove 3 screws fixing evaporator assy.

At the back of the unit, Loosen the clasp of the


connection pipe clamp and then remove the
b connection pipe clamp.

First remove the left side of evaporator from


the groove of bottom shell and then remove
the right side from the clasp on the bottom
shell.
c

Adjust the position of connection pipe on evaporator


Clasp
slightly and then lift the evaporator upwards to
remove it.

d Connection pipe

Installation and Maintenance 97


Step Procedure

8. Remove motor and cross flow fan


a Remove 3 screws fixing motor clamp and then remove
the motor clamp.

Screw

Screw
b
Loose the screws (2-3 circles) used for fixing the
cross flow fan, pull right to pull out the motor.

9. Remove swing motor


Screw off the screws that are locking the swing
motor and take the motor off.

Screws

98 Installation and Maintenance


11.2 Removal Procedure of Outdoor Unit Caution: discharge the refrigerant
completely before removal.
GWH07AGA-K6DNA1A/O

Step Procedure

1. Before disassembly

2. Remove top cover

top cover

Remove the screws fixing top panel and then remove


the top panel.

3. Remove big handle

Remove the screws fixing big handle, then remove the


big handle.

big handle

Installation and Maintenance 99


Step Procedure

4. Remove front panel assy

Remove connection screws connecting the front panel


assy with the chassis and the motor support, and then
remove the front panel assy.

Front Panel Assy

5. Remove right side plate assy

Rescrew the ground screws, remove the ground wires,


loosen the screws fixing terminal board, remove the
terminal board, rescrew the screws fixing the right
plate, and remove the right side plate assy.
Right Side
Plate Assy

6. Remove valve suppprt

Remove the valve support bolck, remove the screws


fixing valve support, remove the screws fixing the liquid valve supprt
valve and gas valve then remove the valve support.

Valve Support Block

100 Installation and Maintenance


Step Procedure

7. Remove gas valve and liquid valve

Unsolder the welding joint connecting the gas valve


and the liquid valve, remove them.
Note:
Discharge the refrigerant completely befor unsoldering; liquid valve
when unsoldering, wrap the gas valve with a wet cloth
completely to avoid damage to the valve caused by
welding joint
high temperature.

gas valve

8. Remove Capillary Sub-assy

Unsolder the welding joint connecting the capillary sub-


assy and then remove the capillary sub-assy.

welding joint

Capillary Sub-assy

9. Remove electric box assy

Unplug the terminals, unscrew 1 screw that secures the


electrical box assy, raise it to the top right and remove
the electrical box.

Electric Box Assy

Installation and Maintenance 101


Step Procedure

10. Remove axial flow fan

Remove the nut on the fan and then remove the axial
flow fan.

axial flow fan

11. Remove motor

Remove the screws fixing the motor and then remove


the motor.

motor

12. Remove motor support

Remove the screws fixing the motor support and lift the
motor support to remove it.

motor support

102 Installation and Maintenance


Step Procedure

13. Remove 4-way valve assy

4-way valve assy


Unsolder the welding joints connecting the 4-way valve
assy, remove the 4-way valve.
Note:
Before unsoldering the welding joint, wrap the 4-way
valve with a wet cloth completely to avoid damage to
the valve caused by high temperature.

14. Remove clapboard assy

Remove the 3 screws fixing the clapboard assy and


then remove the clapboard assy.

clapboard assy

15. Remove compressor

compressor
Remove the 3 foot nuts on the compressor and then
remove the compressor.

Installation and Maintenance 103


GWH09AFC-K6DNA2F/O GWH12AFC-K6DNA2F/O Caution: discharge the refrigerant
completely before removal.

Step Procedure

1. Before disassembly

2. Remove top cover

top cover

Remove the screws fixing top panel and then remove


the top panel.

3. Remove big handle and valve cover

big handle
Remove the screws fixing big handle, valve cover and
then remove them.

valve cover

104 Installation and Maintenance


Step Procedure

4. Remove front panel assy

Remove connection screws connecting the front panel


assy with the chassis and the motor support, and then
remove the front panel assy.

Front Panel Assy

5. Remove right side plate assy

Rescrew the ground screws, remove the ground wires,


loosen the screws fixing terminal board, remove the
terminal board, rescrew the screws fixing the right
plate, and remove the right side plate assy.
Right Side
Plate Assy

6. Remove valve suppprt

Remove the valve support bolck, remove the screws


valve supprt
fixing valve support, remove the screws fixing the liquid
valve and gas valve then remove the valve support.

Valve Support Block

Installation and Maintenance 105


Step Procedure

7. Remove gas valve and liquid valve

Unsolder the welding joint connecting the gas valve


and the liquid valve, remove them.
Note:
Discharge the refrigerant completely befor unsoldering; liquid valve
when unsoldering, wrap the gas valve with a wet cloth
completely to avoid damage to the valve caused by
welding joint
high temperature.

gas valve

8. Remove electronic expansion valve


electric expand
valve fitting

Remove the terminals of the electronic expansion valve


coil and rotate to remove the electronic expansion valve
coil. electric expansion
Unsolder the welding joint connecting the electronic valve sub-Assy
expansion Valve and then remove the electronic
expansion valve.

welding joint

9. Remove electric box assy

Unplug the terminals, unscrew 1 screw that secures


the electrical box assy, release the two snaps on the
electrical box assy (in the clapboard and condenser Electric Box Assy
angle), pull outwards, and remove the electrical box
assy.

106 Installation and Maintenance


Step Procedure

10. Remove axial flow fan

Remove the nut on the fan and then remove the axial
flow fan.

axial flow fan

11. Remove motor

Remove the screws fixing the motor and then remove


the motor.
motor

12. Remove motor support

Remove the screws fixing the motor support and lift the
motor support to remove it.

motor support

Installation and Maintenance 107


Step Procedure

13. Remove 4-way valve assy 4-way valve assy

Unsolder the welding joints connecting the 4-way valve


assy, remove the 4-way valve.
Note:
Before unsoldering the welding joint, wrap the 4-way
valve with a wet cloth completely to avoid damage to
the valve caused by high temperature.

14. Remove clapboard assy

clapboard assy
Remove the screws fixing the clapboard assy and then
remove the clapboard assy.

15. Remove compressor

compressor

Remove the 3 foot nuts on the compressor and then


remove the compressor.

108 Installation and Maintenance


GWH18AGD-K6DNA1E/O Caution: discharge the refrigerant
completely before removal.

Step Procedure

1. Before disassembly

2. Remove big handle and valve cover

big handle
Remove the screws fixing big handle, valve cover and
then remove them.

valve cover

3. Remove top cover

top cover

Remove the screws fixing top panel and then remove


the top panel.

Installation and Maintenance 109


Step Procedure

4. Remove front panel assy

Remove connection screws connecting the front panel


assy with the chassis and the motor support, and then
remove the front panel assy.

front panel

5. Remove right side plate assy

Rescrew the ground screws, remove the ground wires,


loosen the screws fixing terminal board, remove the
terminal board, rescrew the screws fixing the right
plate, and remove the right side plate assy.

right side plate

6. Remove axial flow fan

Remove the nut on the fan and then remove the axial
flow fan.

axial flow fan

110 Installation and Maintenance


Step Procedure

7. Remove electric box assy

Remove the terminals, lift up and rotate the electrical


box assy to the right so that the snaps on the clapboard
are removed and the electrical box assy are removed.

8. Remove motor

Remove the screws fixing the motor and then remove


the motor.

motor

9. Remove motor support

Remove the screws fixing the motor support and lift the
motor support to remove it.

motor support

Installation and Maintenance 111


Step Procedure

10. Remove gas valve and liquid valve

Remove the valve support bolck, remove the screws


fixing the gas valve and the liquid valve,unsolder the
welding joint connecting the gas valve and the liquid
valve, remove them.
Note:
Discharge the refrigerant completely befor unsoldering; welding joint
when unsoldering, wrap the gas valve with a wet cloth
completely to avoid damage to the valve caused by
liquid valve
high temperature.

gas valve

11. Remove valve suppprt

Remove the screws fixing valve support, then remove


the valve support. valve supprt

12. Remove 4-way valve assy

Unsolder the welding joints connecting the 4-way valve


assy, remove the 4-way valve.
Note:
4-way valve assy
Before unsoldering the welding joint, wrap the 4-way
valve with a wet cloth completely to avoid damage to
the valve caused by high temperature.

112 Installation and Maintenance


Step Procedure

13. Remove isolation sheet

electric expand
Remove the screws fixing the isolation
valve fitting
sheet and then remove the isolation
sheet. electric expansion
valve sub-Assy

welding joint

14. Remove clapboard assy

clapboard assy

Remove the screws fixing the clapboard assy and then


remove the clapboard assy.

15. Remove compressor

nut
Remove the 3 foot nuts on the compressor and then
remove the compressor.

compressor

Installation and Maintenance 113


GWH24AFE-K6DNA2I/O Caution: discharge the refrigerant
completely before removal.

Step Procedure

1. Before disassembly

2. Remove top cover

top cover

Remove the screws fixing top panel and then remove


the top panel.

3. Remove big handle and valve cover

Remove the screws fixing big handle, valve cover and big handle
then remove them.

valve cover

114 Installation and Maintenance


Step Procedure

4. Remove front panel assy

Remove connection screws connecting the front panel


assy with the chassis and the motor support, and then
remove the front panel assy.

front panel

5. Remove right side plate assy

Rescrew the ground screws, remove the ground wires,


loosen the screws fixing terminal board, remove the right side plate
terminal board, rescrew the screws fixing the right
plate, and remove the right side plate assy.

6. Remove gas valve and liquid valve

Remove the valve support bolck, remove the screws


fixing the gas valve and the liquid valve,unsolder the
welding joint connecting the gas valve and the liquid
valve, remove them.
Note:
Discharge the refrigerant completely befor unsoldering; welding joint
when unsoldering, wrap the gas valve with a wet cloth
completely to avoid damage to the valve caused by
high temperature. liquid valve

gas valve

Installation and Maintenance 115


Step Procedure

7. Remove valve suppprt

Remove the screws fixing valve support, then remove


the valve support.

valve supprt

8. Remove electronic expansion valve

Remove the terminals of the electronic expansion valve


coil and rotate to remove the electronic expansion valve
coil. electric expansion
Unsolder the welding joint connecting the electronic valve sub-Assy
expansion Valve and then remove the electronic
expansion valve.

welding joint

9. Remove electric box assy

Remove the terminals, lift up and rotate the electrical


box assy to the right so that the snaps on the clapboard
are removed and the electrical box assy are removed.

116 Installation and Maintenance


Step Procedure

10. Remove 4-way valve assy 4-way valve assy

Unsolder the welding joints connecting the 4-way valve


assy, remove the 4-way valve.
Note:
Before unsoldering the welding joint, wrap the 4-way
valve with a wet cloth completely to avoid damage to
the valve caused by high temperature.

11. Remove axial flow fan

Remove the nut on the fan and then remove the axial
flow fan.

axial flow fan

12. Remove motor

Remove the screws fixing the motor and then remove


the motor.

motor

Installation and Maintenance 117


Step Procedure

12. Remove motor support

Remove the screws fixing the motor support and lift the
motor support to remove it.

motor support

14. Remove clapboard assy clapboard assy

Remove the screws fixing the clapboard assy and then


remove the clapboard assy.

15. Remove compressor

nut

Remove the 3 foot nuts on the compressor and then


remove the compressor.

compressor

118 Installation and Maintenance


Appendix
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit display Fahrenheit Celsius Fahrenheit display Fahrenheit Celsius Fahrenheit display Fahrenheit Celsius
temperature(oF) (oF) (oC) temperature(oF) (oF) (oC) temperature(oF) (oF) (oC)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30

Ambient temperature
Fahrenheit display Fahrenheit Celsius Fahrenheit display Fahrenheit Celsius Fahrenheit display Fahrenheit Celsius
temperature(oF) (oF) (oC) temperature(oF) (oF) (oC) temperature(oF) (oF) (oC)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25

Appendix 2: Configuration of Connection Pipe


1.Standard length of connection pipe(More details please refer to the specifications.)
2.Min. length of connection pipe is 3m.
3.Max. length of connection pipe and max. high difference.(More details please refer to the specifications.)
4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe
● After the length of connection pipe is prolonged for 10m at the basis of standard length, you should add 5ml of refrigerant oil for each
additional 5m of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):
● Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional refrigerant
charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter

Additional refrigerant charging amount for R32

Piping size Indoor unit throttle Outdoor unit throttle


Cooling only,
Liquid pipe Gas pipe cooling and heating Cooling only(g/m) Cooling and heating(g/m)
(g / m)
1/4” 3/8” or 1/2” 14 12 16
1/4” or 3/8” 5/8” or 3/4” 40 12 40
1/2” 3/4” or 7/8” 80 24 96
5/8” 1" or 1 1/4” 136 48 96
3/4'' / 200 200 200
7/8'' / 280 280 280

Installation and Maintenance 119


Appendix 3: Pipe Expanding Method
Pipe
Note:
Improper pipe expanding is the main cause of refrigerant leakage.Please expand Pipe cutter
the pipe according to the following steps:
A:Cut the pip Leaning Uneven Burr
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.

Pipe
B:Remove the burrs Shaper
● Remove the burrs with shaper and prevent the burrs from getting into the pipe.
Downwards
C:Put on suitable insulating pipe.

Union pipe
D:Put on the union nut
● Remove the union nut on the indoor connection pipe and outdoor valve; install
the union nut on the pipe. Pipe

E:Expand the port


● Expand the port with expander.
Note: Hard
mold
● "A" is different according to the diameter, please refer to the sheet below: Expander

A(mm)
Outer diameter(mm)
Max Min Pipe
Ф6 - 6.35 (1/4") 1.3 0.7
Ф9 - Ф9.52 (3/8”) 1.6 1.0
Ф12 - 12.70 (1/2”) 1.8 1.0
Ф16 - 15.88 (5/8”) 2.4 2.2

Smooth surface

F:Inspection Improper expanding


● Check the quality of expanding port. If there is any blemish, expand the port
again according to the steps above.
leaning damaged crack uneven
surface thickness
The length is equal

120 Installation and Maintenance


Appendix 4: List of Resistance for Temperature Sensor
Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units(15K)

Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)

-19 138.10 0 49.02 20 18.75 40 7.97

-18 128.60 2 44.31 22 17.14 42 7.35

-16 115.00 4 40.09 24 15.68 44 6.79

-14 102.90 6 36.32 26 14.36 46 6.28

-12 92.22 8 32.94 28 13.16 48 5.81

-10 82.75 10 29.90 30 12.07 50 5.38

-8 74.35 12 27.18 32 11.09 52 4.99

-6 66.88 14 24.73 34 10.20 54 4.63

-4 60.23 16 22.53 36 9.38 56 4.29

-2 54.31 18 20.54 38 8.64 58 3.99

Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)

Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)

-19 181.40 20 25.01 60 4.95 100 1.35

-15 145.00 25 20.00 65 4.14 105 1.16

-10 110.30 30 16.10 70 3.48 110 1.01

-5 84.61 35 13.04 75 2.94 115 0.88

0 65.37 40 10.62 80 2.50 120 0.77

5 50.87 45 8.71 85 2.13 125 0.67

10 39.87 50 7.17 90 1.82 130 0.59

15 31.47 55 5.94 95 1.56 135 0.52

Resistance Table of Discharge Temperature Sensor for Outdoor(50K)

Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)

-30 911.400 10 98 50 17.65 90 4.469

-25 660.8 15 77.35 55 14.62 95 3.841

-20 486.5 20 61.48 60 12.17 100 3.315

-15 362.9 25 49.19 65 10.18 105 2.872

-10 274 30 39.61 70 8.555 110 2.498

-5 209 35 32.09 75 7.224 115 2.182

0 161 40 26.15 80 6.129 120 1.912

5 125.1 45 21.43 85 5.222 125 1.682

Installation and Maintenance 121


JF00304636

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI


Add: West Jinji Rd, Qianshan, Zhuhai,Guangdong, China, 519070
Tel: (+86-756) 8522219
Fax: (+86-756) 8669426
E-mail: global@cn.gree.com
For product improvement, specifications and appearance in this manual are subject to change without prior notice.

You might also like