TW30HQ2B4D
TW30HQ2B4D
TW30HQ2B4D
Service Manual
Table of Contents
Table of contents
Service Manual
9. Troubleshooting...................................................................................................32
9.1 Flashing LED of Indoor/Outdoor Unit and Primary Judgement.......................................32
9.2 How to Check Simply the Main Part................................................................................40
9.3 Troubleshooting for Normal Malfunction..........................................................................56
10. Exploded View and Parts List...............................................................58
10.1 Indoor Unit.....................................................................................................................58
10.2 Outdoor Unit..................................................................................................................62
11. Removal Procedure........................................................................................64
11.1 Removal Procedure of Indoor Unit................................................................................64
11.2 Removal Procedure of Outdoor Unit.............................................................................73
Appendix:.........................................................................................................................79
Appendix 1: Reference Sheet of Celsius and Fahrenheit.....................................................79
Appendix 2: Configuration of Connection Pipe......................................................................79
Appendix 3: Pipe Expanding Method....................................................................................80
Appendix 4: List of Resistance for Temperature Sensor.......................................................81
Table of contents
Service Manual
TW30HQ2B4DI TW36HQ2B4DI
TW30HQ2B4DO
TW36HQ2B4DO YAN1F6F(WiFi)
Model List:
Remote
No Model Product code Indoor model Indoor product code Outdoor model Outdoor product code
Controller
1 TW30HQ2B4D(WIFI) CB434004801_L87641 TW30HQ2B4DI CB434N04801_L87641 TW30HQ2B4DO CB171W10600_L87641 YAN1F6F
2 TW36HQ2B4D(WIFI) CB432008101_L87641 TW36HQ2B4DI CB432N08101_L87641 TW36HQ2B4DO CB432W08100_L87641 (WiFi)
Technical Information 1
Service Manual
2. Specifications
2.1 Specification Sheet
Model TW30HQ2B4D(WIFI) TW36HQ2B4D(WIFI)
Product Code CB434004801_L87641 CB432008101_L87641
Rated Voltage V~ 208/230 208/230
Power Supply Rated Frequency Hz 60 60
Phases 1 1
Power Supply Mode Outdoor Outdoor
Cooling Capacity(Min~Max) Btu/h 28000(9485~30026) 33600(7404~35997)
Heating Capacity(Min~Max) Btu/h 28400(9997~32994) 34600(14979~35997)
Cooling Power Input(Min~Max) W 2705(600~3900) 4100(450~4300)
Heating Power Input(Min~Max) W 2800(650~4000) 3800(560~4300)
Cooling Power Current A 11.5 17
Heating Power Current A 12 16.5
Rated Input W 4000 4300
Rated Current A 17 20
Rated Heating Current A 17.5 20
Air Flow Volume(SH/H/M/L) CFM 706/618/530/412 883/765/647/559
Dehumidifying Volume Pint/h 6.34 7.4
EER (Btu/h)/W 10.36 8.2
COP (Btu/h)/W 10.14 9.11
SEER 18 18
HSPF 9 9
2
Application Area yd 41.86-62.19 55.01-83.72
Model of indoor unit TW30HQ2B4DI TW36HQ2B4DI
Indoor Unit Product Code CB434N04801_L87641 CB432N08101_L87641
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) inch Φ4 1/4X20 9/16X2 Φ4 1/4X20 9/16X2
Fan Motor Cooling Speed (SH/H/M/L) r/min 1350/1150/950/850 1400/1250/1000/800
Fan Motor Heating Speed (SH/H/M/L) r/min 1350/1200/1000/800 1400/1250/1050/850
Output of Fan Motor W 70 70
Fan Motor RLA A 0.4 0.4
Fan Motor Capacitor μF / /
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter inch Φ9/32 Φ9/32
Indoor Unit Row-fin Gap inch 2-1/16 2-1/16
Coil Length (LXDXW) inch 42 9/32X1X15 42 9/32X1X15X2
Swing Motor Model MP24BA MP24BA
Output of Swing Motor W 1.5 1.5
Fuse A 3.15 5
Sound Pressure Level (SH/H/M/L) dB (A) 51/45/41/37 54/49/44/37
Sound Power Level (SH/H/M/L) dB (A) 61/55/51/47 64/59/54/47
Dimension (WXHXD) inch 53 9/64X12 53/64X9 61/64 53 9/64X12 53/64X9 61/64
Dimension of Carton Box (LXWXH) inch 56 39/64X16 29/64X13 55/64 56 39/64X16 29/64X13 55/64
Dimension of Package (LXWXH) inch 56 47/64X16 37/64X14 7/16 56 47/64X16 37/64X14 7/16
Net Weight Ib 41.9 41.9
Gross Weight Ib 51.8 51.8
2 Technical Information
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
Technical Information 3
Service Manual
Cooling Heating
105 110
100
100
95
Capacity ratio (%)
75 70
70
Conditions 60 Conditions
65 Indoor: DB 80°F WB66 °F Indoor:DB 70°F
60 Indoor air flow: Super High Indoor air flow:Super High
Pipe length : 24.6ft 50 Pipe length: 24.6ft
55
50 40
90 95 100 105 109 -4 5 14 23 32 41 50
Cooling Heating
105 110
100
100
95
Capacity ratio (%)
90 90
85
80 80
75 70
70
Conditions 60 Conditions
65 Indoor: DB 80°F WB66 °F Indoor:DB 70°F
60 Indoor air flow: Super High Indoor air flow:Super High
Pipe length : 24.6ft 50 Pipe length: 24.6ft
55
50 40
90 95 100 105 109 -13 5 14 23 32 41 50
140
120 140
100 120
Capacity ratio (%)
100
80
80
60
60
40
40
20 20
0 0
0 14 23 32 59 68 77 86 95 104 109 115 -31 -22 -13 -4 5 18 35 45 50 59 68 75
4 Technical Information
Service Manual
75
36K
70
Noise/dB(A)
50
Noise dB(A)
65 36K
60
30K
40 30K
55
50
30 45
L M H SH 20 30 40 50 60 70 80 90 100
80/66 95/- 36K 130~145 46.8 to 52.8 127 to 96.8 Super High High 37
Heating:
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 24.6ft.
Technical Information 5
Service Manual
12 53/64
53 9/64 9 61/34
13 25/32 29 3/8 10
Φ2 3/4 Φ2 3/4
1 37/64
14 37/64 36 2/9
31 7/64
39 1/2 16 13/16
24
15 9/16
Unit:inch
6 Technical Information
Service Manual
Gas pipe
side
Valve
Discharge
Heat
exchanger
(evaporator) Suction Accumlator
Compressor
Heat
exchanger
Liquid pipe (condenser)
side
Valve Electron Capillary Strainer
expansion
valve
COOLING
Gas pipe
side
Valve
4-Way valve
Discharge
Technical Information 7
Service Manual
36K
Gas pipe
side
Valve
Discharge
Heat
exchanger
(evaporator) Suction Accumlator
Compressor
Heat
exchanger
Liquid pipe (condenser)
side
Valve Electron Strainer
expansion
valve
COOLING
Gas pipe
side
Valve
4-Way valve
Discharge
8 Technical Information
Service Manual
5. Electrical Part
5.1 Wiring Diagram
● Instruction
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
● Indoor Unit
:,5(' :$51,1*
52207(03
78%(7(03
&21752//(5 3OHDVHGRQ
WWRXFKDQ\
5(&(,9(5$1' HOHFWURQLFFRPSRQHQWRU
6(1625
6(1625
0
0
$3
6:,1* )$102725 63610000431
02725 :,),02'8/(
Technical Information 9
Service Manual
● Outdoor Unit
TW30HQ2B4DO TW36HQ2B4DO
:$51,1*
(;3$16,219$/9(
29(5/2$'3527(&725
%$1'+($7(5
%$1'+($7(5
7(036(1625
7(036(1625
7(036(1625
3OHDVHGRQ
WWRXFKDQ\
&2035(6625
HOHFWURQLFFRPSRQHQWRU 6$7 &203
(/(&7521,&
28778%(
2875220
(;+$867
WHUPLQDOZKHQWKHPDFKLQHLV <(*1 8 &203 *
%27720
UXQQLQJVWRSSLQJRUKDVEHHQ
SRZHUHGRIIIRUOHVVWKDQ 9 : <(*1
PLQXWHVWRSUHYHQWWKHULVN * 0$*1(7,&
RIHOHFWULFVKRFN 57 57 57 5,1*
/ / / *
/ (.9 (+ (+
*1<(*1 . . . 5' 5'
%8 <( 5'
,1'22581,7
* 7(50,1$/
0$*1(7,& ( 8 9 :
%/2&.
:+%8 %8 5,1* (9 &1 +($7/ +($7/ 29&&203
1
%. / / %.
&20
5'%1
$3
%.%1 %1 / /
%1
/ $&/ 35,17('&,5&8,7%2$5'
:+%8 / /
/ %8
$&1
*1<(*1
*
+33 +33 :$< 2)$1'&
;7 /3
<(*1 /1 /1
*
/ / :+ :+ 2* 2*
97 97 %8 <( %1 :+ 0 *
32:(5 3 3
+3 +3 / / / / <(*1
)$1
<9 / /
+,*+ +,*+ 02725 *
:$<
35(6685( 35(6685(
6:,7&+ 6:,7&+ 9$/9( 5($&725 5($&725 127(
03D 03D 0RWRUJURXQGRQO\
60000706049303 RU03D DSSOLHVWRWKH
LURQVKHOOPRWRU
10 Technical Information
Service Manual
Top View
4 5 6 7 8 9 10
1 Grounding wire
2 DC motor needle stand
Communication terminal for
3
outdoor unit
Interface of health function(only
4
11 for the mode with this function)
5 Interface of neutral wire
6 Fuse
3 7 Interface of live wire
8 Needle stand for jumper cap
2 12 9 Auto button
1 10 up&down swing interface
13 11 Left&right swing interface
12
14 Interface of ambient temperature
13
sensor
Interface of tube temperature
14
sensor
15 15 Display interface
Bottom View
Technical Information 11
Service Manual
Outdoor Unit
TW30HQ2B4DO TW36HQ2B4DO
● Top view
1 2 3 4 5 6
8
9
10
11
12
13
15 14
● Bottom view
12 Technical Information
Service Manual
2 MODE button
3 FAN button
4 SWING button
1 5 TURBO button
3
2
6 ▲/ button
▲
5
4
6 7 SLEEP button
7
8 8 TEMP button
9
11 10 9 WIFI button
10 LIGHT button
12
11 CLOCK button
● This is a general use remote controller, it could be used for the air conditioners with multifunction; For some function,
which the model doesn't have, if press the corresponding button on the remote controller that the unit will keep the
original running status.
● After putting through the power, the air conditioner will give out a sound. Operation indicator " " is ON (red indicator,
the colour is different for different models). After that, you can operate the air conditioner by using remote controller.
● Under on status, pressing the button on the remote controller, the signal icon " " on the display of remote controller
will blink once and the air conditioner will give out a “de” sound, which means the signal has been sent to the air
conditioner.
● Under off status, set temperature and clock icon will be displayed on the display of remote controller (If timer on, timer
off and light functions are set, the corre- sponding icons will be displayed on the display of remote controller at the same
time); Under on status, the display will show the corresponding set function icons.
Technical Information 13
Service Manual
1. ON/OFF button
Press this button to turn on the unit. Press this button again to turn off the unit.
2. MODE button
Press this button to select your required operation mode.
AUTO COOL DRY FAN HEAT
● When selecting auto mode, air conditioner will operate automatically according to ex-factory setting. Set temperature can’t be adjusted and
will not be displayed as well. Press "FAN" button can adjust fan speed. Press "SWING" button can adjust fan blowing angle.
● After selecting cool mode, air conditioner will operate under cool mode. Cool indicator on indoor unit is ON(This indicator is not available for
some models). Press "▲" or " " button to adjust set temperature. Press "FAN" button to adjust fan speed. Press "SWING" button to adjust fan
blowing angle.
● When selecting dry mode, the air conditioner operates at low speed under dry mode. Dry indicator on indoor unit is ON(This indicator is not
available for some models). Under dry mode, fan speed can’t be adjusted. Press "SWING" button to adjust fan blowing angle.
● When selecting fan mode, the air conditioner will only blow fan, no cooling and no heating. Press "FAN" button to adjust fan speed. Press
"SWING" button to adjust fan blowing angle.
● When selecting heating mode, the air conditioner operates under heat mode. Heat indicator on indoor unit is ON(This indicator is not
available for some models).Press "▲" or " " button to adjust set temperature. Press "FAN" button to adjust fan speed. Press "SWING" button
to adjust fan blowing angle. (Cooling only unit won’t receive heating mode signal. If setting heat mode with remote controller, press ON/OFF
button can’t start up the unit).
Note:
● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5 minutes to blow air (actual delay time is depend on indoor
ambient temperature).
● Set temperature range from remote controller: 16~30 ; Fan speed: auto, low speed, medium speed, high speed.
3. FAN button
Pressing this button can set fan speed circularly as: auto (AUTO), low( ) ,medium( ), high( ).
Auto
Note:
● Under AUTO speed, air conditioner will select proper fan speed automatically according to ex-factory setting.
● Fan speed under dry mode is low speed.
● X-FAN function:Hold fan speed button for 2s in COOL or DRY mode, the icon “ ” is displayed and the indoor fan will continue operation
for a few minutes in order to dry the indoor unit even though you have turned off the unit. After energization, X-FAN OFF is defaulted. X-FAN
is not available in AUTO, FAN or HEAT mode.
This function indicates that moisture on evaporator of indoor unit will be blowed after the unit is stopped to avoid mould.
●Having set X-FAN function on:After turning off the unit by pressing ON/OFF button indoor fan will continue running for a few minutes.at low
speed.In this period,Hold fan speed button for 2s to stop indoor fan directly.
●Having set X-FAN function off: After turning off the unit by pressing ON/OFF button, the complete unit will be off directly.
4. SWING button
Press this button can select up&down swing angle. Fan blow angle can be selected circularly as below:
no display
(horizontal louvers stops at current position)
● When selecting " ", air conditioner is blowing fan automatically. Horizontal louver will automatically swing up & down at maximum angle.
● When selecting "
● When selecting "
● Hold " "button above 2s to set your required swing angle. When reaching your required angle, release the button.
Note:
●" " may not be available. When air conditioner receives this signal, the air conditioner will blow fan automatically.
5. TURBO button
Under COOL or HEAT mode, press this button to turn to quick COOL or quick HEAT mode. " " icon is displayed on remote controller.
Press this button again to exit turbo function and " " icon will disappear.
14 Technical Information
Service Manual
6. ▲/ button
▲
● Press "▲" or " " button once increase or decrease set temperature 1 (1°F) . Holding "▲" or " " button, 2s later, set temperature on
▲ ▲
remote controller will change quickly. On releasing button after setting is finished, temperature indica- tor on indoor unit will change
accordingly. (Temperature can’t be adjusted under auto mode)
● When setting TIMER ON, TIMER OFF or CLOCK, press "▲" or " " button to adjust time. (Refer to CLOCK, TIMER ON, TIMER OFF
▲
buttons)
7. SLEEP button
Under COOL, HEAT or DRY mode, press this button to start up sleep function. " " icon is displayed on remote controller. Press this button
again to cancel sleep function and " " icon will disappear.
8. TEMP button
By pressing this button, you can see indoor set temperature, indoor ambient temperature or outdoor ambient temperature on indoor units
display. The setting on remote controlleris selected circularly as below:
no display
● When selecting " " or no display with remote controller, temperature indicator on indoor unit displays set temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays indoor ambient temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays outdoor ambient temperature.
Note:
● Outdoor temperature display is not available for some models. At that time, indoor unit receives " "signal, while it displays indoor set
temperature.
● Its defaulted to display set temperature when turning on the unit.There is no display in the remote controller.
● Only for the models whose indoor unit has dual-8 display.
● When selecting displaying of indoor or outdoor ambient temperature, indoor temperature indicator displays corresponding temperature and
9. WIFI button
Press " WiFi " button to turn on or turn off WiFi function. When WiFi function is turned on, the " WiFi " icon will be displayed on remote
controller; Under status of remote controller off, press "MODE" and " WiFi " buttons simultaneously for 1s,WiFi modulewill restore to factory
default setting.
10. LIGHT button
Press this button to turn off display light on indoor unit. " " icon on remote controller disappears. Press this button again to turn on
display light. " " icon is displayed.
11. CLOCK button
Press this button to set clock time. " " icon on remote controller will blink. Press "▲" or " " button within 5s to set clock time. Each
▲
pressing of "▲" or " " button, clock time will increase or decrease 1 minute. If hold "▲" or " " button, 2s later, time will change quickly.
▲ ▲
" icon resumes displaying. Cancel TIMER ON: Under the condition that TIMER ON is
started up, press "TIMER ON" button to cancel it.
● TIMER OFF button
"TIMER OFF" button can set the time for timer off. After pressing this button," " icon disappears and the word "OFF" on remote
controller blinks. Press "▲" or " " button to adjust TIMER OFF setting. After each pressing "▲" or " " button,
▲ ▲
TIMER OFF setting will increase or decrease 1min. Hold "▲" or " " button, 2s later, the time will change quickly until reaching your
▲
required time. Press "TIMER OFF" word "OFF" will stop blinking. " " icon resumes displaying. Cancel TIMER OFF. Under the condition
that TIMER OFF is started up, press "TIMER OFF" button to cancel it.
Technical Information 15
Service Manual
Note:
● Under on and off status, you can set TIMER OFF or TIMER ON simultaneously.
● Before setting TIMER ON or TIMER OFF, please adjust the clock time.
● After starting up TIMER ON or TIMER OFF, set the constant circulating valid. After that, air conditioner will be turned on or turned off
according to setting time. ON/OFF button has no effect on setting. If you dont need this function, please use remote controller to cancel it.
2. 8 heating function
Under heating mode, press "TEMP" and "CLOCK" buttons simultaneously to start up or turn off 8 heating function. When this function is
started up, " " and "8 " will be shown on remote controller, and the air conditioner keep the heating status at 8 . Press "TEMP" and
"CLOCK" buttons simultaneously again to exit 8 heating function.
Note:
● Under 8 heating function, fan speed is defaulted at auto speed and it cant be adjusted.
● Under 8 heating function, set temperature cant be adjusted. Press "TURBO" button and the remote controller wont send signal.
● Sleep function and 8 heating function cant operate at the same time. If 8 heating function has been set under cooling mode, press
sleep button will cancel 8 heating function. If sleep function has been set under cooling mode, start up the 8 heating function will
cancel sleep function.
● Under temperature display, the remote controller will display 46 heating.
Press "▲" and "MODE" buttons simultaneously to start I FEEL function and " " will be displayed on the remote controller. After this function
is set, the remote controller will send the detected ambient temperature to the controller and the unitwill automatically adjust the indoor
temperature according to the detected tempera-ture. Press this two buttons simultaneously again to close I FEEL function and " " will
disappear.
● Please put the remote controller near user when this function is set. Do not put the remote controller near the object of high temperature
or low temperature in order to avoid detecting inaccurate ambient temperature.When I FEEL function is turned on, the remote controller
should be put within the area where indoor unit can receive the signal sent by the remote controller.
If “H1” is displayed on the remote controller while it’s not operated by the professional person/after-sales person, it belongs to the
misoperation.
Please operate it as below to cancel it.Under the OFF status of remote controller, hold the MODE button for 5s to cancel “H1” display.
Note:
● If remote controller displays “H1”, it belongs to the normal function reminder. If the unit is defrosting under heating mode, it operates
according to H1 defrosting mode. “H1” won’t be displayed on the panel of indoor unit;
● Once you set H1 mode, if you turn off unit by remote controller, H1 will display 3 times on the remote controller and then disappear;
● Also, when you set H1 mode, when you change to heating mode, H1 will display 3 times on the remote controller and then disappear.
Operation guide
1. After putting through the power, press "ON/OFF" button on remote controller to turn on the air conditioner.
2. Press "MODE" button to select your required mode: AUTO, COOL, DRY, FAN, HEAT.
3. Press "▲" or " " button to set your required temperature. (Temperature cant be adjusted under auto mode).
▲
4. Press "FAN" button to set your required fan speed: auto, low, medium and high speed.
5. Press "SWING" button to select fan blowing angle.
16 Technical Information
Service Manual
1. Press the back side of remote controller marked with " signal sender battery
out the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and make sure the position of "+" polar and "-" polar reinstall
are correct.
3. Reinstall the cover of battery box. remove
Note:
Cover of battery box
● During operation, point the remote control signal sender at the receiving window on indoor unit.
● The distance between signal sender and receiving window should be no more than 8m, and there should be no obstacles between them.
Technical Information 17
Service Manual
Internet
Cloud
Operating Systems
Scan the QR code or search "Ewpe Smart" in the application market to download and install it. When "Ewpe Smart" App is installed,
register the account and add the device to achieve long-distance control and LAN control of smart home appliances.
For more information, please refer to "Help" in App.
18 Technical Information
Service Manual
Compressor
Outdoor fan
Technical Information 19
Service Manual
When duration of successive heating operation is more than 45 minutes, or accumulated heating time more than 90 minutes, andone of the
following conditions is reached, the unit will enter the defrost mode after 3 minutes.
a. Toutdoor amb. ≥ 41°F, Toutdoor pipe ≤ 28.4°F;
b. 28.4°F ≤ Toutdoor amb. ≤ 41°F,Toutdoor pipe - Tcompensation≤ 23°F
c. 23°F < Toutdoor amb. ≤ 28.4°F, Toutdoor pipe - Tcompensation≤ 17.6°F;
d. 14°F < Toutdoor amb. < 23°F, Toutdoor pipe- Tcompensation ≤ Toutdoor amb.+26.6°F;
e. Toutdoor amb. < 14°F, Toutdoor pipe- Tcompensation ≤ Toutdoor amb.+26.6°F;
After energization, when defrosting for the first time Tcompensation=0°F. If it is not the firstly time for defrosting, the Tcompensation is
determined by the Toutdoor pipe of last time quitting defrosting.
a.Toutdoor pipe > 35.6°F, Tcompensation=32°F; b. Toutdoor pipe ≤ 35.6°F, Tcompensation=33.8°F.
At that time, the indoor fan stops and the compressor stops, and after 60 seconds the outer fan will stop, and then after 30seconds, the four-
way valve will stop. After 30 seconds, the compressor is initiated for raising the frequency to defrost frequency.
When the compressor has operated under defrost mode for 10 minutes, or Touter tube ≥ 50°F, the compressor will be converted to 46Hz
operation.After 30 seconds, the compressor will stop. And after another 30 seconds, the four-way valve will be opened, and after60 seconds,
the compressor and the outer fan will be started, the indoor fan will run under preset cold air prevention conditions,and H1 will be displayed
at temperature display area on the display panel. Defrost frequency is 70 Hz.
3.Protection
Cold air prevention
The unit is started under heating mode (the compressor is ON):
① In the case of Tindoor amb. < 75°F: if T tube ≤ 104°F and the indoor fan is at stop state, the indoor fan will begin to run at low speed witha
time lag of 2 minutes. Within 2 minutes, if T tube > 104°F, the indoor fan also will run at low speed; and after 1 minute operation atlow speed,
the indoor fan will be converted to operation at preset speed. Within 1 minute low speed operation or 2 minute non-operation, if T tube >
108°F, the fan will run at present speed.
② In the case of Tindoor amb. < 75°F: if Ttube ≤ 108°F, the indoor fan will run at low speed, and after one minute, the indoor fan will
beconverted to preset speed. Within 1 minute low speed operation, if Ttube > 104°F, the indoor fan will be converted to preset speed.Note:
Tindoor amb. indicated in ① and ② refers to, under initially heating mode, the indoor ambient temperature before the command to start the
compressor is performed according to the program, or after the unit is withdrawn from defrost, the indoor ambient temperature before the
defrost symbol is cleared.
Total current up and frequency down protection
If the total current Itotal ≤ 16A, frequency rise will be allowed; if Itotal ≥ 17A,frequency rise will not be allowed; if Itotal18A,the compressorwill run
at reduced frequency; and if Itotal20A, the compressor will stop and the outdoor fan will stop with a time lag of 60s.
(4) Fan Mode
Under the mode, the indoor fan will run at preset speed and the compressor, the outdoor fan, the four-way valve and the electricheater will
stop.
Under the mode, temperature can be set within a range of 61°F~86°F.
(5) AUTO Mode
① Working conditions and process of AUTO mode
Under AUTO mode, standard cooling temperature Tpreset is 77°F and standard heating temperature Tpreset is 68°F.
a. Once energized, if Tamb. ≤ 71.6°F, the unit will be started under heating mode; if 71.6°F < Tamb.< 78.8°F, the unit will run under fanmode
and the run indicator will be bright; and if Tamb. ≥ 78.8°F, the unit will be started under cooling mode.
b.Under AUTO mode,if Tamb. ≥ Tpreset +1.8ºF is detected,the unit will select to run under cooling mode,in which case implicit
presettemperature is 77°F; if Tamb. ≤ Tpreset-1.8°F, the compressor will stop, the outdoor fan will stop with a time lag of 1 minute,
andtheindoor fan will run at preset speed; and if Tpreset-1.8°F < Tamb. < Tpreset+1.8ºF, the unit will remain at its original state.
c.Under AUTO mode, if Tamb. ≤ Tpreset+3.6°F is detected, the unit will select to run under heating mode, in which case implicit preset
temperature is 64°F; if Tamb. ≥ Tpreset+9°F, the compressor will stop, the outdoor fan will stop with a time lag of 1 minute,and the indoor
fan will run under the mode of residue heat blowing; and if Tpreset+3.6°F < Tamb.< Tpreset+41°F, the unit will remainatits original state. The
cooling-only unit will run under fan mode.
d.Under AUTO mode, if 71.6°F < Tamb.< 78.8°F, the unit will remain at its original state.
② Protection
a. In cooling operation, protection is the same as that under the cooling mode;
b. In heating operation, protection is the same as that under the heating mode;
c. When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor willremain unchanged
for at least 6 minutes.
(6) Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
① Overload protection
Ttube:measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat ex-changer under
heating mode.
1) Cooling overloada.
a. If Ttube ≤ 126°F, the unit will return to its original operation state.
b. If Ttube ≥ 131°F, frequency rise is not allowed.
20 Technical Information
Service Manual
Technical Information 21
Service Manual
Warnings
cient fixing bolt must be installed; make sure the installation
support is firm.
4. Ware safety belt if the height of working is above 78 3/4
inch.
5. Use equipped components or appointed components dur-
Electrical Safety Precautions: ing installation.
6. Make sure no foreign objects are left in the unit after fin-
1. Cut off the power supply of air conditioner before ishing installation.
checking and maintenance.
2. The air condition must apply specialized circuit and Refrigerant Safety Precautions:
prohibit share the same circuit with other appliances.
3. The air conditioner should be installed in suitable 1. Avoid contact between refrigerant and fire as it generates
location and ensure the power plug is touchable. poisonous gas; Prohibit prolong the connection pipe by
4. Make sure each wiring terminal is connected firmly welding.
during installation and maintenance. 2. Apply specified refrigerant only. Never have it mixed with
5. Have the unit adequately grounded. The grounding wire any other refrigerant. Never have air remain in the refrigerant
cant be used for other purposes. line as it may lead to rupture or other hazards.
6. Must apply protective accessories such as protective 3. Make sure no refrigerant gas is leaking out when installation
boards, cable-cross loop and wire clip. is completed.
7. The live wire, neutral wire and grounding wire of power 4. If there is refrigerant leakage, please take sufficient measure
supply must be corresponding to the live wire, neutral to minimize the density of refrigerant.
wire and grounding wire of the air conditioner. 5. Never touch the refrigerant piping or compressor without
8. The power cord and power connection wires cant be wearing glove to avoid scald or frostbite.
pressed by hard objects.
9. If power cord or connection wire is broken, it must be Improper installation may lead to fire hazard, explosion,
replaced by a qualified person. electric shock or injury.
Warnings
1. When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the
specified refrigerant.
Any presence of air or other foreign substance in the refrigerant circuit will cause system pressure rise or compressor rupture, resulting
in injury.
2.When installing or moving this unit, do not charge the refrigerant which is not comply with that on the nameplate or
unqualified refrigerant.
Otherwise, it may cause abnormal operation, wrong action, mechanical malfunction or even series safety accident.
3.When refrigerant needs to be recovered during relocating or repairing the unit, be sure that the unit is running in cooling
mode.Then, fully close the valve at high pressure side (liquid valve).About 30-40 seconds later, fully close the valve at low
pressure side (gas valve), immediately stop the unit and disconnect power. Please note that the time for refrigerant recovery
should not exceed 1 minute.
If refrigerant recovery takes too much time, air may be sucked in and cause pressure rise or compressor rupture, resulting in injury.
4.During refrigerant recovery, make sure that liquid valve and gas valve are fully closed and power is disconnected before
detaching the connection pipe.
If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure
rise or compressor rupture, resulting in injury.
5.When installing the unit, make sure that connection pipe is securely connected before the compressor starts running.
If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure
rise or compressor rupture, resulting in injury.
6.Prohibit installing the unit at the place where there may be leaked corrosive gas or flammable gas.
If there leaked gas around the unit, it may cause explosion and other accidents.
7.Do not use extension cords for electrical connections. If the electric wire is not long enough, please contact a local service
center authorized and ask for a proper electric wire.
Poor connections may lead to electric shock or fire.
8.Use the specified types of wires for electrical connections between the indoor and outdoor units. Firmly clamp the wires so
that their terminals receive no external stresses.
Electric wires with insufficient capacity, wrong wire connections and insecure wire terminals may cause electric shock or fire.
10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container
8. Installation
8.1 Installation Dimension Diagram
ch
str
8 in
ob
t 11
he
eas
ot
At l
et
ac
Sp
n
ctio
s tru
ob
the
to
Sp ac
e inch
ac Sp 7/8
et 11
ot e ast
he
wa At l
At l
eas ll
t 11
7/8
inch
Drainage pipe
o
u cti h
str inc
ob 3/4 Sp
the t 7 8 ac
et
o le as At et
ot
pa
c At lea
st 1 he
S 91 ob
1/1 str
6 in uc
ch tio
n
Installation procedures
Start installation
Finish installation
Note: this flow is only for reference; please find the more detailed installation steps in this section.
(4) Properly connect the live wire, neutral wire and grounding
8.3 Selection of Installation Location wire of power socket.
1. Basic Requirement: (5) Be sure to cut off the power supply before proceeding any
Installing the unit in the following places may cause work related to electricity and safety.
(6) Do not put through the power before finishing installation.
malfunction. If it is unavoidable, please consult the local dealer:
(7) If the supply cord is damaged,it must be replaced by the
(1) The place with strong heat sources, vapors, flammable or
manufacturer,its service agent or similarly qualified persons in
explosive gas, or volatile objects spread in the air. order to avoid a hazard.
(2) The place with high-frequency devices (such as welding (8) The temperature of refrigerant circuit will be high, please
machine, medical equipment). keep the interconnection cable away from the copper tube.
(3) The place near coast area. (9) The appliance shall be installed in accordance with national
(4) The place with oil or fumes in the air. wiring regulations.
(5) The place with sulfureted gas. (10)Installation must be performed in accordance with the
(6) Other places with special circumstances. requirement of NEC and CEC by authorized personnel only.
(7) Do not use the unit in the immediate surroundings of a
2. Grounding Requirement:
laundry a bath a shower or a swimming pool.
(1) The air conditioner is first class electric appliance. It must
2. Indoor Unit: be properly grounding with specialized grounding device
(1) There should be no obstruction near air inlet and air outlet. by a professional. Please make sure it is always grounded
effectively, otherwise it may cause electric shock.
(2) Select a location where the condensation water can be
(2) The yellow-green wire in air conditioner is grounding wire,
dispersed easily and wont affect other people. which cant be used for other purposes.
(3) Select a location which is convenient to connect the (3) The grounding resistance should comply with national
outdoor unit and near the power socket. electric safety regulations.
(4) Select a location which is out of reach for children. (4) The appliance must be positioned so that the plug is
accessible.
(5) The location should be able to withstand the weight of
(5) An all-pole disconnection switch having a contact separation
indoor unit and wont increase noise and vibration. of at least 1/8 inch in all poles should be connected in fixed
(6) The appliance must be installed 98 7/16 inch above floor. wiring.
(7) Dont install the indoor unit right above the electric (6) Including an air switch with suitable capacity, please note
appliance. the following table. Air switch should be included magnet
buckle and heating buckle function, it can protect the circuit-
(8) The appliance shall not be installed in the laundry.
short and overload. (Caution: please do not use the fuse only
for protect the circuit)
3. Outdoor Unit:
(1) Select a location where the noise and outflow air emitted by
the outdoor unit will not affect neighborhood. 8.5 Installation of Indoor Unit
(2) The location should be well ventilated and dry, in which
1. Choosing Installation Iocation
the outdoor unit wont be exposed directly to sunlight or strong
Recommend the installation location to the client and then
wind.
confirm it with the client.
(3) The location should be able to withstand the weight of
outdoor unit. 2. Install Wall-mounting Frame
(4) Make sure that the installation follows the requirement of (1) Hang the wall-mounting frame on the wall; adjust it in
installation dimension diagram. horizontal position with the level meter and then point out the
(5)Select a location which is out of reach for children and far screw fixing holes on the wall.
away from animals or plants.If it is unavoidable, please add (2) Drill the screw fixing holes on the wall with impact drill (the
fence for safety purpose. specification of drill head should be the same as the plastic
expansion particle) and then fill the plastic expansion particles
in the holes.
torque wrench.(As show in Fig.6)
(3) Fix the wall-mounting frame on the wall with tapping screws
(4) Wrap the indoor pipe and joint of connection pipe with
(ST4.2X25TA) and then check if the frame is firmly installed by
insulating pipe, and then wrap it with tape.(As show in Fig.7)
pulling the frame. If the plastic expansion particle is loose,
please drill another fixing hole nearby. Open-end
wrench
Left Right
Insulating pipe
Fig.10
(2) Fix the wire crossing board on connection wire sleeve at 8. Bind up Pipe
the bottom case; let the connection wire sleeve go through the (1) Bind up the connection pipe, power cord and drain hose
wire crossing hole at the back of indoor unit, and then pull it out with the band.(As show in Fig.14)
from the front.(As show in Fig.12) (2) Reserve a certain length of drain hose and power cord
for installation when binding them. When binding to a certain
degree, separate the indoor power and then separate the drain
hose.(As show in Fig.15)
(3) Bind them evenly.
(4) The liquid pipe and gas pipe should be bound separately at
connection wire sleeve the end.
Fig.12
Indoor and
(3) Remove the wire clip; connect the power connection wire outdoor power cord
to the wiring terminal according to the color; tighten the screw Indoor unit Gas
pipe
and then fix the power connection wire with wire clip.(As show
in Fig.13)
Liquid
Fig.14 Band pipe
N(1) 2 3 Drain hose
white black red green
(blue) (brown) (yellow-
green)
Note: the wiring board is for reference only,please refer to the actual one.
(4) Put wiring cover back and then tighten the screw. Fig.15
(5) Close the panel. Indoor power cord
(6) Install the Conduit assy.
a. Fix the conduit assy on the conduit board and then let the Note:
connection wire between indoor unit and outdoor unit go
(1) The power cord and control wire cant be crossed or
through the conduit.
winding.
b. Fix the conduit assy on the chassis with 3 screws.
(2) The drain hose should be bound at the bottom.
● Conduit assy consists of conduit, conduit connector and
lock nut.(Not the standard part, which should be purchased by
9. Hang the Indoor Unit
customer.)
(1) Put the bound pipes in the wall pipe and then make them
● The length of conduit can be calculated according to the
pass through the wall hole.
length of connection wire.
(2) Hang the indoor unit on the wall-mounting frame.
(3) Stuff the gap between pipes and wall hole with sealing gum.
(4) Fix the wall pipe.(As show in Fig.16)
(5) Check if the indoor unit is installed firmly and closed to the
wall.(As show in Fig.17)
Foot holes
Fig.20 Fig.22
4. Connect Indoor and Outdoor Pipes The drain hos
can't raise
(1) Remove the screw cap of valve and aim the pipe joint at the Wall upwards
bellmouth of pipe.(As show in Fig.21)
(2) Pretightening the union nut with hand..(As show in Fig.22)
U-shaped curve
Drain hose
Liquid pipe Pipe joint
Liquid gas pipe
valve Fig.24 Fig.25
Union nut
gas valve Note:
Fig.21 (1) The through-wall height of drain hose shouldnt be higher
than the outlet pipe hole of indoor unit.(As show in Fig.25)
(3) Tighten the union nut with torque wrench by referring to the (2) Slant the drain hose slightly downwards. The drain hose
sheet below. cant be curved, raised and fluctuant, etc.(As show in Fig.26)
9. Troubleshooting
9.1 Flashing LED of Indoor/Outdoor Unit and Primary Judgement
(during (during
Compressor blinking, blinking,
Min ON ON Showing during min. cooling or
23 P0
frequence in 0.25s 0.25s min. heating test
test state and OFF and OFF
0.25s) 0.25s)
(during (during
Compressor blinking, blinking,
rated ON ON Showing during nominal cooling or
24 P1
frequence in 0.25s 0.25s nominal heating test
test state and OFF and OFF
0.25s) 0.25s)
(during (during
Compressor blinking, blinking,
maximum ON ON Showing during max. cooling or
25 P2
frequence in 0.25s 0.25s max. heating test
test state and OFF and OFF
0.25s) 0.25s)
Static OFF 3S
32 dedusting H2 and blink
protection twice
Indoor unit
OFF 3S
and outdoor compressor and Outdoor fan Indoor unit and outdoor unit doesn't
42 LP and blink
unit doesn't motor can’t work match
19 times
match
During cooling and drying
operation, compressor will stop
OFF 3S
Failure start- while indoor fan will operate;
43 LC and blink Refer to the malfunction analysis
up During heating operation, the
11 times
complete unit will stop
operation.
once heating
(during
49 Defrosting mode. Compressor will Its the normal state
blinking,
ON 10s operate
and OFF while indoor fan will stop
1. Outdoor ambient
temperature exceeds the
operation range of unit (eg: less
Cool: compressor
than-20oC or more than 60oC
and outdoor fan stops
for cooling; more than 30oC for
Undefined operation, while indoor
heating);
50 outdoor unit oE fan operates; Heat:
2. Failure startup of
error compressor, outdoor
compressor?
fan and indoor fan stop
3. Are wires of compressor not
operation.
connected tightly?
4. Is compressor damaged?
5. Is main board damaged?
No
No Is malfunction
eliminated
No
No Is malfunction Yes
eliminated
Replace it with a
temperature sensor with
the same model
Yes
No Is malfunction
eliminated
Yes
End
Start
Turn unit on
Yes to check whether the
No malfunction is
eliminated.
Turn unit on
No No to check whether the Yes
malfunction is
eliminated.
Connect power and restart the unit. It's the malfunction of main board.
Test whether the voltage between terminal 1 and terminal 2 No Replace a new main board that is
of motor interface is within 280~310VDC. of the same model.
Yes
Yes
Then check whether the voltage It's the malfunction of main board.
between terminal 2 and terminal 3 No Replace a new main board that is
of the same model.
of the motor interface is 15VDC.
Yes
Then check whether there is voltage It's the malfunction of main board.
between terminal 2 and terminal 4 No Replace a new main board that is
of the motor interface. of the same model.
Yes
Start
No Appearance of the
Is there jumper cap on the mainboard?
jumper cap
No Is malfunction
eliminated
No Is malfunction Yes
eliminated
Is malfunction Yes
eliminated
Yes
No
End
Start
No No
Is the supply voltage too low Yes Adjust the supply voltage to maintain it Is malfunction Yes
with overload? within normal range eliminated
No No
Is the indoor / outdoor Yes Clean the indoor and outdoor heat Is malfunction Yes
heat exchanger dirty,or are the air inlet exchangers and remove the blockage eliminated
and outlet blocked? of air inlet and outlet
No
No
The fan is abnormal? Fan Yes Check the motor and reinstall the Is malfunction Yes
speed is too low or fan doesnt rotate motor to have the fan run normally eliminated
No No
Yes No
Is there blockage inside the system? Yes Flush the heat exchangers with high
(Filth blockage, ice plug, greasy Is malfunction Yes
blockage, the cut off valve hasnt been pressure nitrogen eliminated
opened completely)
No No
No
End
Start
Yes
End
6.Malfunction of communication E6
Main detection points:
● Check if the connection wire and the built-in wiring of indoor and outdoor unit are connected well and without damage;
● If the communication circuit of indoor mainboard is damaged? If the communication circuit of outdoor mainboard (AP1) is
damaged?
Malfunction diagnosis process:
Start
yes
no
yes
no
Replace
Communication cord is damaged? yes communication Malfunction eliminated? yes
cord
no
no
Replace IDU's
main board
yes
Replace ODU's
Malfunction eliminated? no
main board.
yes
End
Start
Yes
Is malfunction
eliminated
The end
Outdoor unit
(1) Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main Check Points:
Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC~240VAC.
If the reactor (L) is correctly connected? If the connection is loose or fallen? If the reactor (L) is damaged?
Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
End
(2)
5. IPM protection, phase current overcurrent (the control board as below indicates the control board
of outdoor unit) H5/P5
Mainly detect:
(1) Compressor COMP terminal (2) voltage of power supply (3) compressor
(4) Refrigerant-charging volume (5) air outlet and air inlet of outdoor/indoor unit
Troubleshooting:
1. Whether the heat exchangers of indoor unit and outdoor unit are Measure the resistance
dirty? Whether the radiation is affected because the unit is between three terminals (UVW)
covered by the objects? of compressor and the copper pipe
2. When indoor fan and outdoor unit are operate normally? with resistance measuring meter
3. Whether the system pressure is too high?
4. Whether the pressure is because there's too much refrigerant?
Whether the
resistance value is more than
500ohm?
Whether there's Correct it one by one
abnormal phenomenons according to the Service
described as above? Manual, and then turn on
the unit. Replace the
compressor
Replace control
board
End
(3)High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
Is outdoor ambient temperature in normal range?
Are the outdoor and indoor fans operating normally?
Is the heat dissipation environment inside and outside the unit is good?
N
1. Check if the fan terminal OFAN
is connected correctly
Replace the Y
control panel AP1 N
Replace the
outdoor fan
End
(4) Start-up failure (following AP1 for outdoor unit control board)
Mainly detect:
Whether the compressor wiring is connected correct?
Is compressor broken?
Is time for compressor stopping enough?
Replace the
compressor
End
(5) Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
Whether the system pressure is too high?
Whether the input voltage is too low?
Disconnect
the needle stand of
Is stop time of the Is the outdoor fan working fan and measure the resistance
compressor longer than normally? between two terminals of fan with
3 minutes? ohmmeter. The resistance shall
be less than 1K Ohm.
Replace the
outdoor fan
Is the outdoor unit blocked Remove foreign
by foreign objects? objects
Are the wires for the compressor connected
correctly? Is connection sequence right?
Is the connection made in clockwise
direction?
Replace the
control panel AP1
Connect the
wires correctly
Replace the
compressor
Replace the
compressor
End
End
(6)Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)
Mainly detect:
Wether the PMV is connected well or not? Is PMV damaged?
Is refrigerant leaked?
Replace the
control panel
AP1
End
High-pressure protection
no
yes
yes
yes
yes
yes
yes
no
Check if the indoor swing Measure the swing motor and
louver is fully open ? signal input
yes
yes
no
Check if the indoor/ outdoor Replace the blocked parts or
filters or radiating fins are dirty or The system pipe is blocked
pipe
blocked ?
no
(8) Communication malfunction: (following AP1 for outdoor unit control board)
Mainly detect:
Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged?
Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not, if is
there any damage?
Start
N
If the fault is eliminated?
N
Replace the main board
of the indoor unit
Y
Y End
Start
N
If the fault is eliminated?
N
Replace the main board of
the indoor unit
Y End Y
21
46
WIFI
MODE
FAN
TIMER ON CLOCK
ON/OFF
SWING
TIMER OFF
20
19
TURBO TEMP SLEEP
IFEEL X-FAN
18
17
16
15 23
14
13 24
12 25
11
10
9
8 26
7
6
5
27
4 28
3 29
2 30
31
36 32
33
37 34
35
1 38
39
42
41
40
The component picture is only for reference; please refer to the actual product.
Part Code
Description
NO. TW30HQ2B4DI Qty
Product Code CB434N04801_L87641
1 Receiver Window / /
2 Front Panel 27230006890 1
3 Stand bar 2421212001 1
4 Filter Sub-Assy 11122106 2
5 Front Case Sub-Assy 20900700005 1
6 Upper Guide Louver 1051216601 1
7 Lower guide louver 1051216701 1
8 Axile Bush 10542704 6
9 Air Louver 2 1051216902 2
10 Air Louver 1 1051216802 16
11 Connecting Rod 10582086 2
12 Louver Clamp 26112158 9
13 Water Tray 2018213802 1
14 Screw Cover 2425200506 4
15 Rubber Plug (Water Tray) 76712012 1
16 Rear Case Sub-Assy 00000100113 1
17 Cross Flow Fan 1 10352039 1
18 Bearing Holder sub-assy 26152028 1
19 Cross Flow Fan 2 10352040 1
20 O-Gasket sub-assy of Bearing 76512051 1
21 Left Evaporator Support 24212041 1
22 Evaporator Assy 01002000027 1
23 Wall Mounting Frame 01252398 1
24 Right Support of Evaporator 2421204201 1
25 Fan Motor 1501213401 1
26 Pipe Clamp 26112071 1
27 Drainage hose 0523001404 1
28 Fixed Clip (Evaporator) 02112009 1
29 Cover Plate 2012212402 1
30 Motor Fixed Clip 26112324 1
31 Step Motor 1521210701 1
32 Press plate (crank) 26112070 1
33 Crank-guide 10582041 1
34 Upper Crank 10562004 1
35 Lower crank 10562005 1
36 Electric Box Assy 10000204113 1
37 Electric Box 201022502 1
38 Terminal Board 42011233 1
39 Main Board 30138001017 1
40 Display Board 30565277 1
41 Electric Box Cover 201022523 1
42 Electric Box Cover 2011204404S 1
43 Remote Controller 305001000085_TOSOT 1
44 Tube Sensor 390000453 1
45 Ambient Temperature Sensor 390000592 1
46 Detecting plate(WIFI) 30070077 1
Above data is subject to change without notice.
TW36HQ2B4DI
21
20
43 42 41 40
WIFI
MODE ON/OFF
19
FAN SWING
18
IFEEL X-FAN
17
16
15
14
13
12
11
10 22
9
8
7
6 23
5
4
24
3
25
2
26
1 27
28
33 29
30
34 31
32
35
36
39
38
37
The component picture is only for reference; please refer to the actual product.
Part Code
Description
NO. TW36HQ2B4DI Qty
Product Code CB432N08101_L87641
1 Front Panel 27230013668 1
2 Stand Bar 2421212001 1
3 Filter Sub-Assy 11122106 2
4 Front Case Sub-assy 20900700005 1
5 Upper Guide Louver 1051216601 1
6 Lower Guide Louver 1051216701 1
7 Axile Bush 10542704 6
8 Air Louver 2 1051216902 2
9 Air Louver 1 1051216802 16
10 Connecting Rod 10582086 2
11 Louver Clamp 26112158 9
12 Water Tray 2018213802 1
13 Screw Cover 2425200506 4
14 Rubber Plug (Water Tray) 76712012 1
15 Rear Case assy 00000100113 1
16 Cross Flow Fan 1 10352039 1
17 Bearing Holder Sub-assy 26152028 1
18 Cross Flow Fan 2 10352040 1
19 O-Gasket sub-assy of Bearing 76512051 1
20 Left Evaporator Support 24212041 1
21 Evaporator Assy 1002000027 1
22 Wall Mounting Frame 1252398 1
23 Fan Motor 1501213401 1
24 Pipe Clamp 26112071 1
25 Drainage Hose 523001404 1
26 Cover Plate 2012212402 1
27 Motor Fixed Clip 1 26112324 1
28 Stepping Motor 1521210701 1
29 Press Plate(Crank) 26112070 1
30 Crank-guide 10582041 1
31 Upper Crank 10562004 1
32 Lower crank 10562005 1
33 Electric Box Assy 100002001022 1
34 Electric Box 201022502 1
35 Terminal Board 42011233 1
36 Main Board 30138001017 1
37 Display Board 30565277 1
38 Electric Box Cover 2011204404S 1
39 Electric Box Cover 2011204404 1
40 Remote Controller 305001000085_TOSOT 1
41 Temperature Sensor 390000592 1
42 Temperature Sensor 390000453 1
43 Detecting plate(WIFI) 30070077 1
TW36HQ2B4DO TW30HQ2B4DO
28
35
29 27 26 25 24 23 22 21
36
30
37
31
38 32
39 33
40
34
20
41
19
18
17
1 16
2 3 4 5 6 7 8 9 10
11 12 13 14 15
The component picture is only for reference; please refer to the actual product.
Part Code
Description
NO. TW30HQ2B4DO TW36HQ2B4DO Qty
Product Code CB171W10600_L87641 CB432W08100_L87641
1 Front Grill 01473050 1473050 1
2 Cabinet 0143500401P 0143500401P 1
3 Front Side Plate 01303249P 01303249P 1
4 Axial Flow Fan 10335014 10335014 1
5 Drainage Plug 06813401 7671301802 1
6 Chassis Sub-assy 02803101P 0280319605 1
7 Drainage Connecter 06123401 06123401 1
8 Compressor Gasket 76715022 76713066 3
9 Compressor and fittings 00105051 205200003 1
10 Electrical heater 7651873209 7651000413 1
11 Magnet Coil 4300040029 4300040029 1
12 4-way Valve Assy 03123895 30152000213 1
13 Right Side Plate 0130504402P 0130504402P 1
14 Valve Support Sub-Assy 0171501201P 0171501201P 1
15 Cut-off Valve 07133157 07130239 1
16 Valve cover 22245003 22245003 1
17 Retaining plate 02115006P 02115006P 1
18 Handle assy 02113109 2113109 1
19 Wiring clamp 26115004 26115004 1
20 Electronic expansion valve Sub-Assy 07133688 07133684 1
21 Temperature Sensor 3900031001 3900031001 1
22 Rear Grill 01475013 01475013 1
23 Condenser Assy 01163509 01163491 1
24 Clapboard 01233134 01233134 1
25 Condenser support plate 01175092 01175037 1
26 Motor Support Sub-Assy 0180287601 01802876 1
27 Top Cover Sub-Assy 01255007 1255007 1
28 Electric Box Cover 01425279 01425281 1
29 Reactor 43130192 43130192 2
30 Electric Box Sub-Assy 02603620 02603620 1
31 Pass wire ring sub-assy 76614102 76614102 2
32 left handle 26233053 2113031 1
33 Left Side Plate 01305043P 01305043P 1
34 Fan Motor 15702802 1570280000405 1
35 Electric Box Cover 01425281 01425281 1
36 Main Board 30148338 300027000216 1
37 Electric Box 02603614 02603614 1
38 Radiator 49010252 49010252 1
39 Terminal Board 42200006001401 42200006001401 1
40 Electric Box Assy 02613050 100002001028 1
41 Electrical Heater (Chassis) 765100047 7651000413 1
Steps Procedure
2.Remove filter
panel
clasps
Steps Procedure
A3/A5 panel
Remove screws fixing display, and then remove display
the display.
horizontal louver
Steps Procedure
a Remove the screw fixing detecting plate and then Detecting plate
remove the detecting plate. screw
Note:The position of detection board(WIFI)
may be different for -different models.
screw
screw
front case
Steps Procedure
clasp
Steps Procedure
electric box
Steps Procedure
water tray
screw
pipe-stopping plate
Steps Procedure
16.Remove evaporator
screw
b Turn over the indoor unit and adjust the pipe line to
the position as shown by the broken line.
evaporator
Steps Procedure
Steps Procedure
cushion rubber
TW30HQ2B4DO TW36HQ2B4DO
Steps Procedure
valve cover
top panel
Remove the screws connecting the top
panel with the front panel and left&right
side plate, and then remove the top panel.
Steps Procedure
Steps Procedure
electric box
8.Remove motor
motor
Steps Procedure
motor support
isolation sheet
4-way valve
Steps Procedure
liquid valve
valve support
14.Remove compressor
compressor
Steps Procedure
condenser
chassis
Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25
1.Standard length of connection pipe (More details please refer to the specifications.)
2.Min. length of connection pipe is 9.84ft.
3.Max. length of connection pipe and max. high difference.(More details please refer to the specifications.)
4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe
● After the length of connection pipe is prolonged for 32.81ft at the basis of standard length, you should add 5ml of refrigerant oil
for each additional 16.40ft of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):
● When the length of connection pipe is above 16.40ft, add refrigerant according to the prolonged length of liquid pipe. The
additional refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter
Additional refrigerant charging amount for R22, R407C, R410A and R134a
Diameter of connection pipe Outdoor unit throttle
Liquid pipe(inch) Gas pipe(inch) Cooling only(oz/ft.) Cooling and heating(oz/ft.)
Ф1/4 Ф3/8or Ф1/2 0.2 0.2
Ф1/4 or Ф3/8 Ф5/8 or Ф3/4 0.2 0.2
Ф1/2 Ф3/4 or Ф7/8 0.3 1.3
Ф5/8 Ф1 or Ф1 1/4 0.7 1.3
Ф3/4 / 2.7 2.7
Ф7/8 / 3.8 3.8
Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper
Downwards
C:Put on suitable insulating pipe
Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.
Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)