Matushima Servicemanual Uk
Matushima Servicemanual Uk
Matushima Servicemanual Uk
TCL
WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS
Models
TAC-07CHSA/R TAC-09CHSA/R
TAC-12CHSA/R TAC-18CHSA/R
TAC-24CHSA/R
CONTENTS
IMPORTANT NOTICE
2
TCL Air Conditioner Service Manual
Technical Specifications
Model No. TAC-07CHSA/R TAC-09CHSA/R TAC-12CHSA/R TAC-18CHSA/R
Type Heat Pump Heat Pump Heat Pump Heat Pump
Control type Remote Remote Remote Remote
Rated cooling capacity Btu/h 7000 9000 12000 18000
Rated heating capacity Btu/h 7700 9500 12500 19000
EER for cooling Btu/h.w 10.4 10.4 10.5 10.27
COP for heating W/W 3.49 3.49 3.21 3.37
Moisture removal Liters/h 0.8 0.8 1.0 1.0
High dB(A) 36 36 38 36
Indoor noise level at
Med. dB(A) 32 32 34 32
cooling
Low dB(A) 29 29 32 29
Outdoor noise level dB(A) 55 55 55 55
Electrical Data
Power supply 220V~/50Hz
Voltage Range V
Cooling A 3.0 3.9 5.2 8.0
Rated current
Heating A 2.9 3.6 5.2 7.5
Cooling W 670 850 1140 1750
Rated input
Heating W 630 790 1140 1650
Refrigerating System
Refrigerant/Charge Gram R410A/480g R410A/480g R410A/730g R410A/1400g
Type Rotary Rotary Rotary Rotary
Model ---- ---- ---- ----
Compressor LRA A ---- ---- ---- ----
MFG ---- ---- ---- ----
Evaporator Louver fin and grooved tube type ( ϕ 7)
Condenser Corrugated fin and grooved tube type ( ϕ 9.52)
Expansion device Capillary tube
Defrosting system Microcomputer controlled reverse system
Fan System
Indoor air circulation/Hi Cooling m3/h 430 430 530 800
Indoor fan type Cross flow Cross flow Cross flow Cross flow
Cooling rpm 1150/1050/950 1150/1050/950 1270/1170/1000 1060/970/880
Indoor fan speed Heating rpm 1150/1050/950 1150/1050/950 1250/1150/1000 1060/970/880
H/M/L Dry rpm 950 950 950 880
Sleep rpm 950 950 950 880
Indoor fan motor output W 12 12 12 22
Outdoor air circulation m3/h
Outdoor fan type Propeller fan Propeller fan Propeller fan Propeller fan
Outdoor fan speed rpm 895 860 860 850
Outdoor fan motor output W 25 31 31 45
Connections
Refrigerant coupling Flare type
Gas Inches 3/8 3/8 1/2 1/2
Connecting Pipe
Liquid Inches 1/4 1/4 1/4 1/4
Connecting Wiring Size x Core number
Drainage Pipe O.D 16mm
Others
Suitable area m2 9~15 12~19 16~28 30~40
Net dimensions Indoor mm 710x240x179 710x240x179 770x240x179 1033x313x202
(W x H x D) Outdoor mm 600x232x500 700x255x540 760x252x552 760x252x552
Indoor kg 8 8 8 14
Net weight
Outdoor kg 25 26 32 43
Packing dimensions Indoor mm 805x325x270 790x310x252 863x325x270 1088x380x263
(W x H x D) Outdoor mm 745x352x542 803x380x595 863x405x605 838x361x600
Indoor kg 10 10 10 19
Gross weight
Outdoor kg 28 34 34 45
Loading Capacity 40’/40’HC 132/280/318 111/238/276 106/236/248 90/188/218
3
TCL Air Conditioner Service Manual
Technical Specifications
Model No. TAC-24CHSA/R
Type Heat Pump
Control type Remote
Rated cooling capacity Btu/h 24000
Rated heating capacity Btu/h 26000
EER for cooling Btu/h.w 10.8
COP for heating W/W 3.46
Moisture removal Liters/h 2.2
High dB(A) 49
Indoor noise level at
Med. dB(A) 46
cooling
Low dB(A) 43
Outdoor noise level dB(A) 58
Electrical Data
Power supply 220V~/50Hz
Voltage Range V
Cooling A 10.1
Rated current
Heating A 10
Cooling W 2220
Rated input
Heating W 2200
Refrigerating System
Refrigerant/Charge Gram R410A/1900g
Type Rotary
Model ----
Compressor LRA A ----
MFG ----
Evaporator Louver fin and grooved tube type ( ϕ 7)
Condenser Corrugated fin and grooved tube type ( ϕ 9.52)
Expansion device Capillary tube
Defrosting system Microcomputer controlled reverse system
Fan System
Indoor air circulation/Hi Cooling m3/h 1100
Indoor fan type Cross flow
Cooling rpm 1330/1230/1150
Indoor fan speed Heating rpm 1330/1230/1150
H/M/L Dry rpm 1150
Sleep rpm 1150
Indoor fan motor output W 35
Outdoor air circulation m3/h
Outdoor fan type Propeller fan
Outdoor fan speed rpm 850
Outdoor fan motor output W 76
Connections
Refrigerant coupling Flare type
Gas Inches 5/8
Connecting Pipe
Liquid Inches 3/8
Connecting Wiring Size x Core number
Drainage Pipe O.D 16mm
Others
Suitable area m2 35~48
Net dimensions Indoor mm 1033X313X202
(W x H x D) Outdoor mm 890 X 307 X 660
Indoor kg 16
Net weight
Outdoor kg 57
Packing dimensions Indoor mm 1103x395x280
(W x H x D) Outdoor mm 990x415x715
Indoor kg 18
Gross weight
Outdoor kg 59
Loading Capacity 40’/40’HC 63/135/157
4
TCL Air Conditioner Service Manual
Operation Details
1 Remote controller
Remote controller
1 ON/OFF button
Used to start and stop operation
when pressed.
FEEL
SLEEP TIMER ON TMIER OFF
AUTO 2 TIMER button
COOL HIGH
DRY MID Used to select TIMER operation.
FAN LOW
HEAT SWING
3 UP button (TOO COOL button)
3 Used to increase the set room temperature
and time.
5 SLEEP FAN 7
4 DOWN button (TOO WARM button)
2 TIMER SWING 6 Used to decrease the set room temperature
and time.
8 MODE ON/OFF 1 5 SLEEP button
Used to set or cancel sleep mode operation.
4
6 VANE control button
Used to adjust airflow direction.
Note: Each mode and relevant function will be further specified in following pages.
Remote Control
The remote controller is not presetted as Cooling Only Air Conditioner or Heat Pump by manufacturer.
Each time after the remote controller replace batteries or is energized, the arrowhead will flashes on the front of
Heat or Cool on LCD of the remote controller.
User can preset the remote controller type depending on the air conditioner type you have purchased as
follows:
Press any button when the arrowhead flashes on the front of Cool , Cooling Only is set.
Press any button when the arrowhead flashes on the front of Heat , Heat Pump is set.
If you don t press any button within 10 seconds, the remote controller is preset as Heat Pump automatically.
Note :
If the air conditioner you purchased is a Cooling Only one, but you preset the remote controller as Heat Pump, it
doesn t bring any matter. But if the air conditioner you purchased is a Heat Pump one, and you preset the
remote controller as Cooling Only, then you CAN NOT preset the Heating operation with the remote controller.
5
TCL Air Conditioner Service Manual
REMOTE CONTROLLER
6
TCL Air Conditioner Service Manual
Electronic Controller
1. Safety Control
(1) Time Delay Safety Control
3 minutes delay for compressor---The compressor is ceased for 3minutes to balance the pressure in the
refrigeration cycle in order to protect the compressor.
2 minutes delay for 4-way valve---The 4-way valve is ceased for 2 minutes to prevent the
refrigerant-gas abnormal noise when the HEATING operation is OFF or switch to the other operation
mode.
(2) Indoor Pipe Temperature Sensor Frost Prevention Control
When the indoor pipe temperature sensor reads 0℃ or below for 5 minutes, the indoor pipe temperature
sensor frost prevention control starts. The compressor and outdoor fan stop and indoor fan operates at high
speed for 3 minutes. After that, if the indoor pipe temperature sensor reads less than 5℃ this control
prolonged until the indoor pipe temperature sensor reads 5℃ or more.
(3) High Temperature Protection Control
During HEATING operation, the outdoor fan motor and compressor are controlled by the indoor pipe
temperature to prevent the high temperature of compressor.
Outdoor fan OFF: when the indoor pipe temperature is ≥50℃
Outdoor fan ON: when the indoor pipe temperature is ≤48℃
Compressor OFF: when the indoor pipe temperature is ≥62℃
Compressor ON: when the indoor pipe temperature is ≤48℃
2. “I Feel” Mode Operation
(1) When the “I Feel” mode is selected, the operation mode and initial set temperature are determined by the
initial room temperature at start-up of the operation except to turn off the air conditioner and operates it
again.
(2) If the mode is change to “I Feel” mode from other mode, the “I Feel” mode doesn’t operate until compressor
stop for more than 3 minutes.
In the “I Feel” mode , when the controller receives the up or down single of temperature, the set
temperature can adjust by 1℃ upper or lower. The biggest you can adjust by 2℃ upper or lower.
3. “COOLING” Mode Operation
(1) When the COOLING mode is selected without setting temperature, the system will set the set temperature at
26℃ automatically with the AUTO FAN speed.
(2) When selecting the COOLING mode operation, the system will operate according to the setting by the
remote controller and the operation is as following:
7
TCL Air Conditioner Service Manual
Room Temp.
Set TEMP. +1℃
Set TEMP. -1℃
Time More than 2 min More than 2 min More than 2 min More than 2 min More than 2 min
Indoor Fan Set Speed Set Speed Set Speed Set Speed Set Speed
Compressor ON OFF ON OFF ON
Outdoor Fan ON OFF ON OFF ON
(3) In HEATING mode, the indoor fan motor speed is controlled by Cold Air Prevention Control.
(4) Cold Air Prevention Control
The function is intend to prevent cold air from being discharged when the heating operation starts or
when defrosting.
The indoor fan speed will be controlled as following.
The vane angle is at the angle C(100°).
Temperature drop
34℃
Low Speed
27℃
Low Speed
25℃
Stop the fan
23℃
Stop the fan
During the heating operation, if the compressor stops that it will adjust the indoor fan speed, after 30
seconds to stop the fan.
8
TCL Air Conditioner Service Manual
(5) Defrost
Defrosting of the outdoor heat exchange is controlled by the microprocessor with detection by the indoor
pipe temperature sensor.
Defrost control type is according to the JC on the PCB whether is connected.
When the JC is connect on the PCB
When one of the conditions of A, Band C is satisfy, the defrosting operation stars.
A. IPT--- indoor pipe temperature
In the condition A, it must satisfy the conditions a), b)and c) then into defrosting operation.
a) IPT1 satisfy IPT1=IPTMAX-△IPT(8℃)
b) t5≥50minutes(the compressor cumulative operation time≥50 minutes, t5 is permitted move
and lower than t1 too).
c) IPT<40℃,and keep 2 minutes.
According to the condition A enter the defrosting operation, the first defrosting operation time is
8minutes; After defrosting operation one cycle, and then judge and regulate the defrosting operation
time.
B. After the compressor cumulative operation time exceeds 120 minutes and the temperature of the IPT
is less then 35℃ for 2 minutes. When the defrosting operation time on this condition exceeds
8minutes, it will terminate.
C. After the compressor operation continuously for 20 minutes and the IPT is less than 23℃ or from
the last time of defrosting operation is 50 minutes or more interval. When the defrosting operation
time on this condition exceeds 10 minutes, it will terminal.
When the JC isn’t connected on the PCB
When the conditions of a) or b) is satisfy, the defrosting operation starts.
a) Under the heating operation, the compressor cumulative operation time exceeds 50 minutes and the
temperature of the outdoor pipe temperature sensor reads lower than -8℃
b) Under the heating operation, the compressor cumulative operation time exceeds 50 minutes, if the
indoor pipe temperature sensor reads lower than 40℃ continuously for 2minutes.
Note: If haven’t the outdoor pipe temperature sensor that use the condition b) to defrost, against
use the condition a).
Defrost terminating conditions
When the condition c) or d) is satisfy, the defrosting operation will terminal.
c) The outdoor defrost sensor reads 20℃ or more.
d) The defrosting time exceeds 10 minutes.
9
TCL Air Conditioner Service Manual
HEATING ON
COOLING/DRY OFF
The 4-way valve reverses for 5 seconds right before start-up of the compressor as following chart:
COOLING/DRY TO HEATING HEATING TO COOLING/DRY
Compressor
4-way Valve
5s 2min
Outdoor Fan
8. “SLEEP” mode
When the SLEEP button is pressed, the SLEEP mode is selected as following:
The indoor fan speed is set at the low speed, the power lamp and the sleep lamp is on, the temperature off
after 5 minutes.
When selecting COOLING/DRY operation with SLEEP mode, the set temperature will be raised by 1℃ 1
hour later and by 2℃ 2 hour later.
When selecting HEATING operation with SLEEP mode, the set temperature will be dropped by 1℃ 1
hour later and 2℃ 2hour later.
After the System operates in SLEEP mode for 8 hours, it will stop automatically.
9. Fan motor control
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the
microprocessor to feedback the rotational frequency. Comparing the current rotational frequency with the
target rotational frequency, the microprocessor adjusts fan motor electric to make the current rotational
frequency close to the target rotational frequency. With this control, when the fan speed is switched, the
rotational frequency changes smoothly.
(2) When the rotational frequency feedback signal has not output for 5 seconds (or when the microprocessor
can’t detect the signal for 5 seconds), the fan motor is regarded locked-up. Then the electric current to the fan
10
TCL Air Conditioner Service Manual
motor is shut off. 10 seconds later, the electric current is applied to the fan motor again. During the fan motor
lock-up, the POWER indicator lamp flashes on and off 6times/cycle or E6 to show the fan motor
abnormality.
10. Auto Fan Speed Control
(1) When the auto fan speed is selected, the indoor fan motor speed is automatically controlled by the room
temperature and the set temperature.
(2) In COOLING mode, the indoor fan motor operates as following:
Fan Speed
Hi
Me
Lo
Room temperature minus set temperature: 1℃ 2℃ 4℃
(3) In HEATING mode, the indoor fan motor operates as following;
Fan Speed
Hi
Mi
Lo
Room temperature minus set temperature 1℃ 2℃ 4℃
11. Auto Vane Operation control
(1) Vane motor drive
The unit is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the
motor are controlled by pulse signal transmitted from indoor microprocessor.
(2) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the
desired angle. The positioning is decided as follows:
When the ON/OFF button is pressed.
When the vane control is change from AUTO to MANUAL.
When the SWING is finished.
When the test run starts.
When the power supply turns ON.
(3) The auto vane changes as follows by pressing the VANE CONTROL button.
(4) VANE AUTO mode
In vane auto mode, the microprocessor automatically determines the vane angle and operation to make the
optimum room-temperature distribution.
(5) SWING mode
When presses the SWING button, the vane swings.
12. TIMER Operation
(1) To activate the air conditioner at the desire time, follow the procedure specified below(the remote control
and air conditioner are switched off):
Press the Timer button.
Select the desired mode by pressing the Mode button.
Select the desired temperature by pressing the ▲ ▼ button(only possible when the ‘cool’ or ‘heat’
mode is selected).
Select the ventilator speed (low, medium or high) or automatic mode(only possible when the feel, Cool
or Heat mode is selected) by pressing the Fan button.
The ventilator always operates in the Auto mode when the Dry mode is selected.
Select Swing or no Swing by pressing the Swing button.
11
TCL Air Conditioner Service Manual
12
TCL Air Conditioner Service Manual
this, it displays the failure and the protection is failing. You must be given the electric again to operate
it. In the failure, you can operate the FAN mode.
When the outdoor protects in the COOLING or DRY, the outdoor unit stops, the indoor fan operates in
set speed ; and in the HEATING, the outdoor unit stops, the indoor fan operates in cold air prevention
control. The system doesn’t receive the signal of remoter controller except the signal of shut off it.
When the system check the voltage is 220V and the delay control is finished, it operates at normal
again.
When the indoor fan motor is failure, the compressor is stopped, the outdoor fan and indoor fan is
stopped and display the failure. The system doesn’t receive the signal of remoter controller except the
signal of shut off it.
d) Display Of The Control
In the display board the lamp from left is the POWER lamp(Red), the SLEEP lamp(Yellow), the TIMER
lamp(Yellow), the RUN lamp(Green).
g) When gives the control electric, the buzzer voices a long for 0.3 second per cycle.
13
TCL Air Conditioner Service Manual
WIRING DIAGRAM
MODEL: TAC-07CHSA/R, TAC-09CHSA/R, TAC-12CHSA/R
INDOOR UNIT:
Outdoor
Room Temp. sensor CN6
Unit
TH2 Power Supply
CN5 CN4 CN3
Pipe Temp. sensor
Evaporator
θ Protecter
M
M Fan Motor
Vane Motor
Indoor Unit
OUTDOOR UNIT
Compressor
4-way Vane
CM
C R(M)
S
Blue
Blue
Red Blue
θ
Brown(White) White Protecter Compressor
1 Capacitor
Red Black
2
Yellow 3
Blue N Blue
Yellow/Green Blue Fan Capaciter
Orange
Yellow/Green Blue
M Yellow/Green
14
TCL Air Conditioner Service Manual
WIRING DIAGRAM
MODEL: TAC-18CHSA/R
INDOOR UNIT:
To The Outdoor Unit
White
Brown
Red
Red CN2
P4 PCB CN1 Transformer
Yellow P3
Relay
Yellow P5 CN3
Blue AC(N) P1 P9-1 FM
Blue P9-2
P2-1 Fan Motor
Yellow/Green Yellow/Green
CN5-1 SM
Yellow/Green Yellow/Green
CN5-2 SM
Blue Blue CN8 CN7 CN6
Vane Motor
Brown Brown
Room Temp. Sensor
To O.P.T Display PCB
Pipe Temp. Sensor
OUTDOOR UNIT:
Compressor
Valve Coil
CM
C R(M)
S
Blue
Blue
Red Blue
θ
Brown(White) White Inside/Outside Compressor
1 Protecter Capacitor
Red Black
2
Yellow 3
Blue N Blue
Yellow/Green Blue Fan Capaciter
Orange
Yellow/Green Blue
15
TCL Air Conditioner Service Manuel
WIRING DIAGRM
MODEL: TAC-24CHSN/R
INDOOR UNIT:
FM
SM
SM
OUTDOOR UNIT:
YLW/GRN
Red Red C1
2 Compressor
Yellow
3
Blue
Blue White
Red
N Blue
Brown Valve Coil
L Brown
YLW/GRN
YLW/GRN YLW/GRN CS R
To Power Supply
FM FM
Brown
L
Blue Compressor
N Blue Fan Motor
Motor
Relay
Brown Blue
O.P.T
Junction
16
TCL Air Conditioner Service Manual
EXPLOSION VIEW
Model: TAC-07CHSA/R, TAC-09CHS/R, TAC-12CHS/R
INDOOR UNIT
2
3
4 28
5
27
6
26
7 25
24
8
23
9 22
10 21
11 20
19
12
18
17
13
16
15
14
5
TCL Air Conditioner Service Manual
EXPLOSION VIEW
MODEL: TAC-18CHSA/R, TAC-24CHSA/R
INDOOR UNIT:
2 29
3
4 28
5
27
6
6 2
7 25
24
8
23
9 22
10 21
11 20
9
12 1
18
13 17
16
14 15
9
TCL Air Conditioner Service Manual
EXPLOSION VIEW
Mode:TAC-07CHSA/R
OUTDOOR UNIT:
7 6 5 4 3 2 1
29
8
28
27
9 26
25
24
23
22
21
20
10 11 12 13 14 15 16 17 18 19
19
TCL Air Conditioner Service Manual
EXPLOSION VIEW
MODEL: TAC-09CHSA/R, TAC-12CHSA/R, TAC-18CHSA/R
INDOOR UNIT:
8 7 6 5 4 3 2 1
30
9
29
28
10 27
26
25
24
23
22
21
11 12 13 14 15 16 17 18 19 20
20
TCL Air Conditioner Service Manual
EXPLOSION VIEW
MODEL: TAC-24CHSA/R
OUTDOOR UNIT:
8 7 6 5 4 3 2 1
29
9
28
27
26
25
24
23
22
21
20
10 11 12 13 14 15 16 17 18 19
21
TCL Air Conditioner Service Manual
22
TCL Air Conditioner Service Manual
23
TCL Air Conditioner Service Manual
24
TCL Air Conditioner Service Manual
25
TCL Air Conditioner Service Manual
Part List
26
TCL Air Conditioner Service Manual
27
TCL Air Conditioner Service Manual
28
TCL Air Conditioner Service Manual
29
TCL Air Conditioner Service Manual
Part List
30