AUX TR-1
AUX TR-1
AUX TR-1
KPTCL, BALLARI
PROJECT : M/s. GROMA INFRASTRUCTURE LTD
APPLIED
VOLTAGE (DC) PHASE REF. IR VALUE
5000 HV-EARTH 30.8 GΩ
500 LV-EARTH 44.6 GΩ
2500 HV-LV 21.7 GΩ
3 Y CUT 72.9 267.8 405 5.3 16.4 11.0 1.9 7.2 9.1
B CUT 409 251.5 86.1 16.2 4.7 11.5 9.2 6.9 2.2
b) LV SIDE:
5. Ratio test:
6. Vector Group:
1. 1U2n + 2n1V=1U1V
9.3+ 402=411
2. 1W2W<1W2V
392>406
3. 1V2W=1U2V
395.8=396.7
Remarks:
Test Result Found Satisfactory.