CLIENT : M/s.

KPTCL, BALLARI
PROJECT : M/s. GROMA INFRASTRUCTURE LTD

PAGE No. : PRE-COMMISSIONING TEST

TEST REPORT FOR AUXILLARY TRANSFORMER

Location : 11KV SWITCH YARD


Designation : AUXILLARY TRANSFORMER
Name Plate Details:
Make : VIJAY ELECTRIC CO
Serial No : VEC/250/L201-01
Rating : 250 MVA
Voltage : HV : 11 KV LV : 433V
Current : HV :13.12 A LV : 3333.4 A
Vector Group : Dyn11
Type of cooling : ONAN
Normal Tap : 3
Total Tap : 7
Year of Make 02-2024
Date of Testing : 01/07/2024

1. Insulation Resistance Test :

APPLIED
VOLTAGE (DC) PHASE REF. IR VALUE
5000 HV-EARTH 30.8 GΩ
500 LV-EARTH 44.6 GΩ
2500 HV-LV 21.7 GΩ

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : M/s. KPTCL, BALLARI
PROJECT : M/s. GROMA INFRASTRUCTURE LTD

PAGE No. : PRE-COMMISSIONING TEST

2. Magnetizing Current Test:

MEASURED CURRENT IN HV (mA)


TAP NO
1U(mA) 1V(mA) 1W(mA)
1 1.3 2.1 2.1
2 1.3 1.0 1.9
3 1.4 1.6 1.7
4 1.6 1.6 1.9
5 1.5 1.7 2.0
6 1.8 1.9 2.1
7 1.5 2.0 2.0

3. Magnetic Balance Test:

APPLIED HV SIDE VOLTAGE


MEASURED LV SIDE VOLTAGE (V)
TAP REF (V)
1U1V 1V1W 1W1U 2U2V 2V2W 2W2U 2U2N 2V2N 2W2N
R CUT 170.9 407 187.2 13.5 14.0 0.5 4.3 9.1 4.8

3 Y CUT 72.9 267.8 405 5.3 16.4 11.0 1.9 7.2 9.1

B CUT 409 251.5 86.1 16.2 4.7 11.5 9.2 6.9 2.2

4. Winding Resistance Test:


A) HV SIDE:

TAP NO. 1U1V(mΩ) 1V1W(mΩ) 1W1U(mΩ)


1 6.4 6.5 6.4
2 6.2 6.2 6.3
3 6.0 6.1 6.1
4 5.9 6.0 5.9
5 5.8 5.7 5.7
6 5.6 5.7 5.7
7 5.3 5.5 5.5

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : M/s. KPTCL, BALLARI
PROJECT : M/s. GROMA INFRASTRUCTURE LTD

PAGE No. : PRE-COMMISSIONING TEST

b) LV SIDE:

MEASURED RESISTANCE VALUE (mΩ)


TAP NO
2U2N 2V2N 2W2N
3 0.1 0.2 0.1

5. Ratio test:

APPLIED HV SIDE VOLTAGE MEASURED LV SIDE VOLTAGE (V)


TAP NO.
(V)
1U1V 1V1W 1W1U 2U2V 2V2W 2W2U 2U2N 2V2N 2W2N
1 409 403 412 14.9 15.2 15.4 8.8 8.8 8.8

2 413 408 409 15.8 15.6 15.8 9.1 9.0 9.0

3 412 410 410 16.1 16.0 16.1 9.3 9.2 9.2

4 405 404 405 16.2 16.2 16.3 9.4 9.3 9.4

5 405 404 405 16.6 16.6 16.7 9.6 9.6 9.6

6 408 397 404 17.0 16.9 17.2 9.9 9.9 9.8

7 410 406 404 17.8 17.6 17.7 10.2 10.1 10.1

6. Vector Group:

Conditions for Dyn11,

1. 1U2n + 2n1V=1U1V
9.3+ 402=411
2. 1W2W<1W2V
392>406
3. 1V2W=1U2V
395.8=396.7

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : M/s. KPTCL, BALLARI
PROJECT : M/s. GROMA INFRASTRUCTURE LTD

PAGE No. : PRE-COMMISSIONING TEST

Remarks:
Test Result Found Satisfactory.

TESTED BY VERIFIED BY WITNESSED BY