Gforce Chilled Water: 7 To211 KW

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

gForce Chilled Water

7 to211 kW

by
Model Number Identification

GF C D 008 3 2

gForce Series 2 — 208 or 230


4 — 460
C — Chilled Water
3 — Three Phase
D — Downflow
U — Upflow
Nominal kilowatts
007-211 kW

2
Building on more than 50 years of experience, Data Aire produces innovative
solutions to meet the developing demands of critical spaces. We are a
solutions-driven organization with a passion for finding creative answers by
working with our customers through a consultative process.

Known for products that are designed utilizing high levels of technology,
Data Aire engineers are experienced visionaries who adapt processes and
design proprietary unit enhancements which reflect the constant needs of
today’s mission critical spaces.

Data Aire combines extensive expertise in control logic with world-


class manufacturing capability recognized by key international quality
certifications. For those seeking reliable, scalable, customized technology,
we provide the solutions of choice. Our precision air control equipment
and intelligent energy management technology serve customers in diverse
applications worldwide.

3
Overview

MISSION CRITICAL COOLING


gForce by Data Aire are efficient and economical while complying with strict
environmental requirements. Incorporating backward curved plenum fans with
electronically commutated (EC) motors, these units supply radially dispersed cooling
air at lower speeds allowing for more uniform static pressure across the room. These
fans provide more net cooling from the computer room air conditioning (CRAC) system.
DC motors are more energy efficient, providing an on-going savings year after year.
Each unit is factory run tested and put through a vigorous quality control procedure.

IMPROVED PERFORMANCE AND REDUCED MAINTENANCE


Backward curved fans discharge air radially, allowing for uniform static pressure across
the raised floor. Traditional forward curved fans prohibit optimal airflow through the
raised floor close to the CRAC. One of the key features of backward curved fans,
commonly referred to as plug fans, is that the motor and fan are integrated into a
single unit, and includes a separate speed controller. This eliminates the need for
monthly maintenance, belt replacement and all belt dust.

IMPROVED AIRFLOW DESIGN


The increased capacity of the gForce internal cabinet allows for less restrictive airflow.
When additional options are added to smaller cabinets, the static pressure within
the unit increases, making airflow more difficult. The advanced design of the bigger
interior and the product’s quality construction ensures the highest level of efficiency in
a precision air system.

DATA AIRE DELIVERS


Standard lead time for a standard unit is 30 days from date of order. With an optional
premium “quick ship” units can be expedited to ship in as little as one week. All units
are built to your specific order and specification. Not only does Data Aire deliver
standard products in short lead times, our consultative process helps you meet your
specific requirements.

4
Design Features

DESIGN
gForce CW units feature a specially designed compact tubular steel frame which allows for minimum space
requirement of air conditioning equipment in the controlled area. Although compact, all parts are easily accessible
providing excellent serviceability. The heart of the system is the Data Alarm Processor (dap4), a microprocessor
based controller. The dap4 not only controls and monitors temperature, humidity, airflow, and cleanliness, it provides
component runtimes, alarm history, and automatic self-test.

FRAME AND CABINET


The heliarc welded tubular steel frame provides for maximum strength and ease of access. Side and front doors
can be easily opened and removed with quarter-turn fasteners allowing full access to all unit components. All doors
include one inch thick, 1-1/2 pound density insulation for thermal performance, protection, and sound attenuation.

COIL SECTION
Designed for draw-through application, the computer-selected, rifle-tubbing dual circuited A-frame coil has an
interwoven surface that increases unit efficiency at low load conditions. Air is drawn through both circuits of the coil at
low velocity providing effective surface exposure with minimum turbulence. The coil sits in a stainless steel drain pan.

FAN SECTION
Backward curved plenum fans with electronically commutated motors are used to provide the most efficient fan/
motor combination available in the market today. Electronically commutated motors are DC motors connected to
standard AC power. DC motors are more efficient that AC motors and can be programmed to run at various speeds.
With the fan blades directly connected to the motor, there is no need for periodic maintenance. In the unlikely event
of a fan failure, replacement is simple; remove four bolts, disconnect the power and remove the fan. Reverse the
process for installation of a new fan.

ELECTRIC REHEAT
Low-watt density finned tubular sheathed elements provide ample capacity to maintain room dry bulb conditions
during a call for dehumidification. Three stages of reheat are standard.

HUMIDIFICATION
gForce CW includes an electric steam generator humidifier with “quick change” disposable cylinders and an auto-
flush cycle. The steam generator humidifier, with its patented control system, optimizes cylinder life and energy
efficiency by concentrating incoming water to a predetermined conductivity much higher than that of any entering
water. The control system continuously monitors the conductivity in the cylinder through its electronics, which allows
water to be flushed as often as is necessary to maintain the capacity at this design conductivity. The high design
conductivity results in a minimum flushing of heated water, which saves energy. The humidifier is designed to allow all
units at any voltage to produce full rated steam output capacity at an optimum low water level based on this design
conductivity.

FILTER SECTION
Units are provided with 4 inch deep, MERV-8 pleated filters. The filter section is accessible from the top, front, or side
on downflow units, and the front and right hand side on upflow units.

5
System Control

SMART SYSTEM CONTROLS FOR MISSION CRITICAL ENVIRONMENTS


Incorporating advances based on years of control-logic experience, Data Aire system control products offer maximum
operational flexibility and growth potential. From a versatile microprocessor controller or a dependable relay
autochangeover unit, to accessories that help prevent hot spots in rack installations and compensate for short-term
power outages, Data Aire technology keeps you in command.
The gForce systems come equipped with dap4 touch for the dap4 control panel. dap4 supports the following
network protocols for integration with a Building Management System (BMS) for Computer Room Air Conditioning
(CRAC) system monitoring and control: Modbus RTU, TCP/IP, SNMP V1 or V2, BACnet IP or MS/TP and LonTalk SNVT.
Building Management System Interface: Unit(s) shall be furnished with an optional interface card to communicate
directly with the Building Automation System (BAS) through a RS-485, Ethernet or LonTalk port. All alarms, set points,
and operating parameters that are accessible from the unit mounted control panel shall also be made available
through the BAS.

CONTROLS
CONDITION AND DATA SWITCHING AND
AUTOMATIC CONTROL FUNCTIONS ROUTINELY DISPLAYED CONTROL FUNCTIONS
Humidity Anticipation Current Date and Time System On/Off/Esc Button
Auxiliary Chilled Water Operation* Unit Status Menu Selection Buttons
Sequential Load Activation Temperature Setpoint Menu Exit Button
Start Time Delay Humidity Setpoint Select Buttons
Automatic Reheat Element Rotation Current Temperature Alarm Silence Button
Temperature Anticipation Cooling 1, 2, 3, 4* Program Set Button
Energy Saver (Glycol Operation)* Current Humidity Manual Override for:
Hot Water Coil Flush Cycle* Dehumidification Cool 1, Cool 2, Heat 1,
Dehumidification Lockout Humidification Humidification, CW Valve
Chilled Water Coil Flush Cycle* Current Fan Speed* and Fan Speed
Energy Saver Coil Flush Cycle* Reheat 1, 2, 3Current
Selectable Water Under Floor Alarm Action Discharge Temperature*
Compressor Short Cycle Current Chilled Water Valve Position
Current Percent of Capacity Utilized

ALARMS

High Temperature Warning High Humidity Warning Local Alarm


Low Temperature Warning Low Humidity Warning Manual Override
Low Pressure Compressor 1 Low Pressure Compressor 2 Humidifier Problem
High Pressure Compressor 1 High Pressure Compressor 2 Custom Message*
Dirty Filter Under Floor Water Detection Power Failure Restart
Firestat Tripped Compressor Short Cycle Maintenance Required
Temperature Sensor Error Humidity Sensor Error Discharge Sensor Error*
No Water Flow* Smoke Detector* High Condensate Water Level*
Fan Motor Overload* Standby Pump On* Person to Contact on Alarm*

6
HISTORICAL DATA
High Temperature Last 24 Hours Low Temperature Last 24 Hours
High Humidity Last 24 Hours Low Humidity Last 24 Hours
Alarm History (Last 100 Alarms) Hourly Average of Duty
Equipment Runtimes for:
Blower, Compressor 1, Compressor 2, Reheat 1, 2, 3, Dehumidification,
Energy Saver*, Humidifier, Condenser and Chilled Water

PROGRAMMABLE FUNCTIONS
Temperature Setpoint Temperature Deadband Fan Control Mode
System Start Delay Low Temperature Alarm Limit Humidity Deadband
Humidity Setpoint High Humidity Alarm Limit Low Humidity Alarm Limit
Define Password Reset Equipment Runtimes Audio Alarm Mode
Reverse Acting Water Valve Compressor Short Cycle Alarm Humidity Anticipation
Compressors(s) Analog Module Sensor Setup* Calibrate Temperature Sensor
Temperature Scale High Temperature Alarm Limit Fan Speed Settings
Water Valve Voltage Range Delay for Optional Alarm 1, 2, 3, 4 Firestat Temperature Alarm Limit
Manual Diagnosis Remote Alarm 1, 2, 3, 4 Selection Calibrate Discharge Air Sensor*
Person to contact on Alarm Compressor Lead/Lag Sequence Dehumidification Mode
Humidifier Autoflush Timer* Power Problem or Restart Mode Scheduled Normal Maintenance
Reheat Stages Water Valve Mode Calibrate Humidity
Humidifier Network Protocol
Compressor Supplements to Energy Saver*
Low Discharge Temperature Alarm Limit*
Calibrate Chilled Water Temperature Sensor*

ACCESSORIES
RackSense 32
dap4 Smart Power Capacitor
dap4 Power Meter

* Some of the programmable selections, displays or alarms may require additional components or sensors

7
Options

REMOTE TEMPERATURE AND HUMIDITY SENSORS


Temperature and humidity sensors may be ordered for remote wall mounting in lieu of the standard return air
sensors. Sensors are provided in a wall mounted plastic case for remote sensing of temperature and humidity. 35
feet of shielded cable is provided for field wiring. Other lengths available as well.

SMOKE DETECTOR
A unit mounted smoke detector will shut down the unit if smoke is sensed. The microprocessor will sound an
alarm and display a “SMOKE DETECTED” message. The smoke detector is mounted in the return air stream and is
provided with auxiliary contacts.

UNIT MOUNTED DISCONNECT


A unit mounted nonautomatic disconnect switch is installed in the high voltage electrical section. The operating
mechanism allows access to the high voltage electrical components when switched to the “OFF” position. The
operating mechanism (handle) protrudes through the decorative door.

CONDENSATE PUMP
Condensate pumps may be ordered as factory installed or for field installation. Condensate pumps are complete
with sump, motor, and automatic control. The pumps are rated for 145 GPH at 40 feet (460v) or 168 GPM at 40 feet
(230v) maximum. Pumps shipped loose are available in 115, 230, or 460 volt.

FLOORSTAND
Floorstands are adjustable -1/+3 inches and are available with seismic construction.

HIGH EFFICIENCY FILTERS


Standard filters are rated at MERV 8 based on ASHRAE 52.2. Higher efficiency filters are available (consult factory
regarding efficiency and unit static pressure).

STEAM GENERATOR HUMIDIFIER WITH MODULATING CONTROL


Modulating control may be added to the steam generator humidifier. Modulating control will allow the humidifier
to automatically adjust steam output to match changing room conditions. Self-regulating auto flush is included.

8
HOT WATER REHEAT
Where hot water is available, a unit installed reheat coil can use hot water reheat. The system is designed for 150
psi maximum water pressure and includes a 2-way valve (a 3-way valve is optional). Units with the hot water reheat
do not include electric reheat. Supplemental reheat may be ordered.

2-WAY CHILLED WATER VALVE


A 2-way chilled water valve is available to replace the standard 3-way valve where required.

UPFLOW PLENUM
Upflow plenums are fully insulated and have front discharge air grilles. Side grilles for both or one side are
available. Plenums are available in various heights and are painted to match the unit color.

by

9
Models & Capacities

GFCX-007XX thru GFCX-014XX


GFCX-007XX GFCX-011XX GFCX-014XX
@ 800 CFM, 6 GPM @ 1,200 CFM, 8 GPM @ 1,600 CFM, 11 GPM
EAT Net Total Net Sensible Net Total "Net Sensible Net Total Net Sensible
°F (DB/WB) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr)" kW (BTU/hr) kW (BTU/hr)
72/58.6 4.7 (16,100) 4.5 (15,400) 7.0 (23,900) 6.8 (23,300) 10.5 (35,800) 10.0 (34,000)
75/61 5.6 (19,000) 5.0 (17,000) 8.1 (27,700) 7.5 (25,600) 12.3 (41,900) 10.9 (37,200)
72/60 5.0 (17,200) 4.3 (14,700) 7.3 (25,000) 6.6 (22,400) 11.2 (38,200) 9.6 (32,800)
75/62.5 6.0 (20,600) 4.7 (16,200) 8.7 (29,600) 7.1 (24,400) 13.2 (45,200) 10.5 (35,800)
80/67 7.9 (27,100) 5.4 (18,400) 11.3 (38,400) 8.1 (27,500) 17.2 (58,700) 11.8 (40,400)

GFCX-018XX thru GFCX-032XX


GFCX-018XX GFCX-025XX GFCX-032XX
@ 2,000 CFM, 13 GPM @ 3,250 CFM, 18 GPM @ 3,500 CFM, 22 GPM
EAT Net Total Net Sensible Net Total Net Sensible Net Total Net Sensible
°F (DB/WB) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr)
72/58.6 12.8 (43,600) 12.3 (42,000) 15.6 (53,400) 15.6 (53,400) 20.4 (69,700) 20.1 (68,500)
75/61 14.9 (50,700) 13.4 (45,800) 17.8 (60,800) 17.5 (59,600) 23.7 (80,900) 22.0 (75,000)
72/60 13.5 (46,200) 11.8 (40,400) 15.9 (54,400) 15.2 (52,000) 21.4 (73,000) 19.3 (65,700)
75/62.5 15.9 (54,300) 12.9 (44,000) 18.6 (63,400) 16.7 (56,900) 25.2 (85,900) 21.0 (71,600)
80/67 20.5 (70,100) 14.5 (49,400) 23.9 (81,400) 18.6 (63,500) 32.5 (111,000) 23.5 (80,100)

GFCX-039XX thru GFCX-053XX


GFCX-039XX GFCX-046XX GFCX-053XX
@ 3,750 CFM, 27 GPM @ 4,000 CFM, 32 GPM @ 7,000 CFM, 42 GPM
EAT Net Total Net Sensible Net Total Net Sensible Net Total Net Sensible
°F (DB/WB) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr)
72/58.6 25.1 (85,500) 23.8 (81,100) 29.2 (99,600) 26.9 (91,800) 39.1 (133,600) 38.2 (130,300)
75/61 29.4 (100,300) 26.0 (88,600) 34.5 (117,900) 29.4 (100,500) 45.7 (156,000) 41.9 (143,100)
72/60 26.8 (91,300) 22.8 (77,900) 31.6 (107,800) 26.0 (88,700) 41.4 (141,200) 36.8 (125,500)
75/62.5 31.7 (108,100) 24.9 (85,100) 37.5 (128,100) 28.5 (97,200) 48.9 (166,900) 40.3 (137,400)
80/67 41.2 (140,500) 28.1 (95,900) 49.0 (167,300) 32.4 (110,500) 63.6 (217,100) 45.3 (154600)

GFCX-063XX thru GFCX-091XX


"GFCX-063XX "GFCX-077XX "GFCX-091XX
@ 8,000 CFM, 46 GPM" @ 9,000 CFM, 55 GPM" @ 9,500 CFM, 73 GPM"
EAT Net Total Net Sensible Net Total Net Sensible Net Total Net Sensible
°F (DB/WB) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr)
72/58.6 50.2 (171,200) 48.1 (164,300) 61.9 (211,200) 58.2 (198,700) 67.4 (230,000) 62.8 (214,300)
75/61 58.6 (200,000) 52.6 (179,600) 72.6 (247,700) 63.5 (216,800) 79.5 (271,300) 68.6 (234,200)
72/60 53.3 (181,800) 46.3 (158,000) 66.2 (226,000) 56.1 (191,300) 72.6 (247,800) 60.5 (206,500)
75/62.5 62.8 (214,300) 48.8 (166,500) 78.2 (266,800) 61.1 (208,700) 86.1 (294,000) 66.2 (226,100)
80/67 81.1 (276,900) 56.7 (193,600) 101.1 (345,200) 68.9 (235,100) 112.2 (383,100) 75.0 (256,000)

1. Performance data is based on ACFM and tested in compliance with ASHRAE Standard 127-2007 Standard Rating Conditions.
2. Net capacity data includes fan motor heat.

10
GFCX-106XX thru GFCX-158XX
GFCX-106XX GFCX-141XX GFCX-158XX
@ 11,700 CFM, 83 GPM @ 16,000 CFM, 95 GPM @ 17,500 CFM, 105 GPM
EAT "Net Total Net Sensible Net Total Net Sensible Net Total Net Sensible
°F (DB/WB) kW (BTU/hr)" kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr)
72/58.6 83.7 (285,700) 77.6 (264,700) 97.6 (333,000) 94.7 (323,200) 113.3 (386,600) 107.2 (365,700)
75/61 98.9 (337,400) 84.8 (289,400) 113.4 (387,000) 103.5 (353,300) 133.3 (454,900) 117.3 (400,300)
72/60 90.3 (308,200) 74.8 (255,300) 103.0 (351,600) 91.1 (311,000) 121.1 (413,300) 102.9 (351,300)
75/62.5 107.1 (365,600) 81.9 (279,600) 121.1 (413,300) 99.3 (338,800) 143.5 (489,900) 112.6 (384,400)
80/67 139.5 (476,100) 92.8 (316,600) 156.1 (532,800) 111.2 (379,600) 186.6 (637,000) 127.1 (433,900)

GFCX-0176XX thru GFCX-211XX


GFCX-176XX GFCX-211XX -
@ 19,000 CFM, 110 GPM @ 20,000 CFM, 144 GPM -
EAT Net Total Net Sensible Net Total Net Sensible Net Total Net Sensible
°F (DB/WB) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr) kW (BTU/hr)
72/58.6 128.4 (438,100) 120.7 (412,000) 154.1 (526,000) 138.6 (473,100) - -
75/61 150.8 (514,600) 131.8 (449,900) 184.3 (629,100) 152.5 (520,500) - -
72/60 137.1 (467,900) 115.8 (395,300) 169.1 (577,100) 134.9 (460,400) - -
75/62.5 162.1 (553,400) 126.5 (431,700) 202.1 (689,700) 148.6 (507,300) - -
80/67 209.8 (716,200) 142.4 (486,100) 265.1 (904,900) 170.1 (580,400) - -

GFCX-XXXXX @ STANDARD AIRFLOW


Standard EC Plug Fans Standard Cabinet Dimensions
Capacity, kW Number of Fans Fan Size, mm Fan Motor, kW Depth, in. Length, in. Height, in.
7 1 450mm 1.0 40.5 36.0 78.0
11 1 450mm 1.0 40.5 36.0 78.0
14 1 450mm 1.0 40.5 36.0 78.0
18 1 450mm 1.0 40.5 36.0 78.0
25 1 500mm 2.7 40.5 49.5 78.0
32 1 500mm 2.7 40.5 49.5 78.0
39 1 500mm 2.7 40.5 49.5 78.0
46 1 500mm 2.7 40.5 49.5 78.0
53 2 500mm 2.7 40.5 83.0 78.0
63 2 500mm 2.7 40.5 83.0 78.0
77 2 500mm 2.7 40.5 83.0 78.0
91 2 560mm 3.0 40.5 83.0 78.0
106 3 500mm 2.7 40.5 106.0 78.0
141 3 560mm 3.0 40.5 120.0 84.0
158 3 560mm 5.0 40.5 120.0 84.0
176 3 560mm 5.0 40.5 120.0 84.0
211 3 560mm 5.0 46.0 120.0 99.0

3. Performance data based on an entering temperature of 45° F.


4. Consult factory for alternate operating conditions or options as these may impact unit performance.

11
www.DataAire.com
800-347-2473 | sales@DataAire.com A member of the
230 W. Blueridge Avenue C/S Group of Companies
Orange, CA 92865 Making Building Better®

©2019 Data Aire, Inc. | REV 07/2019