Medium Voltage Distribution: N-Series Three-Phase Recloser With ADVC Controller

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Medium Voltage Distribution

N-Series Three-Phase Recloser


with ADVC Controller

Make the most of your energy SM


Applications
Smart Grid Ready
With the increasing push for advanced monitoring, reduction of
outages, and the need to facilitate two-way communications
between supply and the distribution network, the N-Series
Automatic Circuit Recloser is ready to be integrated into your
smart grid solution.

Loop Automation
Restoring power to your customers in the shortest possible time is
the focus of Recloser Solutions’ Loop Automation Scheme.

The Loop Automation Scheme reconfigures protection settings,


sectionalizes faults, minimizes affected areas, and restores network
supply without the need for communications or operator
intervention, using standard recloser features.

Automatic Changeover (ACO)


The Automatic Changeover (ACO) System uses primary and
alternative supplies, master and slave reclosers, and fast
communications to ensure that supply is always available for a
critical load in the event of a power failure.

Using a number of different setups, including break-before-make and


make-before-break, allows the system to be configured to the exact
specifications required for the critical load. The system can even be
set up for one-way or two-way switching to ensure power is always
available to your critical systems.

Operation as a Sectionalizer
Reclosers and sectionalizers work together to further improve feeder
reliability. Using a separate RL-Series LBS/Sectionalizer, as part of
a feeder automation network, detects fault passage and
automatically isolates faulty sections of a network in conjunction with
upstream recloser operation. To accomplish this it senses the
three-phase current and voltage to count the number of recloser trip
operations. When the preprogrammed number of recloser
operations is reached, the controller opens the sectionalizer during
the recloser dead time to isolate the downstream fault.

2 | N-Series Three-Phase Automatic Circuit Recloser


Introduction and Features
The N-Series Automatic Circuit Recloser (ACR) Reduced Purchase Cost
represents the commitment of Schneider Electric™ > Fully integrated: No requirement for additional Remote Terminal Units (RTU), power
to improve products and invest in ongoing product supplies, batteries, or enclosures. The RTU and a range of communication ports are
development. Providing the features of a traditional included in the standard equipment.

recloser, plus the benefits of up-to-date design > A 630 A cable connection kit is provided as part of the standard package. Optional 250 A,
400 A, and 800 A cable kits are also available.
optimized for automation, remote control, and
monitoring, now or in the future, the N-Series ACR
Reduced Installation Costs
is a complete scalable solution.
> Simple Commissioning: Configuration of the unit is from the WSOS Software or the
operator interface.
The N-Series development was driven by customer
> All key components required for installation are included.
demand for improved return on capital investment in
the distribution network. After careful evaluation of
> Lightning arrester mounting, cable tail kit, and pole-mounting brackets are provided in the
standard package. An optional voltage transformer (VT) for auxiliary supply is available.
customer needs, the N-Series was developed to
> Schneider Electric ACRs are ideally suited as low-cost feeder circuit breakers in outdoor
achieve optimum performance and reliability, making primary substations. In this application, connection into the substation control system is
use of the latest available technology in vacuum simple and low cost.
interruption and microelectronics.
Reduced Operating Costs
In the past, distribution equipment such as reclosers > Reduce equipment damage through the integral protection relay, which provides fast
isolation of faults.
have been purchased only to support load growth.
Today, your customers, the electricity consumers, > The recloser constantly monitors line current and voltage without the need for additional
measurement devices. This data can then be used for forward planning and optimization of
are demanding reduced outages and lower prices. existing feeders.
At Schneider Electric, we are continually working to
> Reliable lifetime, low maintenance equipment reduces operational costs.
provide the advanced equipment needed for
tomorrow’s competitive electricity distribution system. DSA/SCADA Compatibility
When used with a compatible DSA or SCADA system, Schneider Electric ACRs support remote
By using our technologically advanced equipment, control and monitoring to provide the following advantages:
operating costs will be reduced and capital works
can be deferred through better management of
> Reduced travel time for line crews: information on fault current and recloser status values
transmitted to system control allows fast location of the faulted line section.
the existing plant. There will be a reduction in the
> This same information allows informed remote switching, reducing the affected area and
outage area; reductions can cause lost revenue. quickly restoring supply.
> ACRs can be configured and settings managed from system control without technicians
In addition to ACRs, the Schneider Electric family of having to visit each individual recloser in the field, with a consequent reduction in travelling
switchgear includes remotely controlled and monitored time and improved system integrity.
pole-mounted load break switches and sectionalizers,
as well as remote control and monitoring software. Increased Customer Satisfaction
> Reduced Customer Minutes Lost: Supply can be quickly restored to fault-free areas.
The Schneider Electric Switchgear and Controller
product ranges create a complete solution for
Deferred Capital Expenditures
distribution system automation (DSA). > Remotely controlled and monitored reclosers give an improved knowledge of a system and
provide better system control. Feeder and substation load can then be remotely managed,
improving utilization of your existing plant. Purchase of new plant can then most likely be
deferred for a considerable period of time.

N-Series Three-Phase Automatic Circuit Recloser | 3


ACR Overview
N-SeriesACR
The N-Series ACRisisdesigned
designedaround
aroundvacuum
vacuum The
The N-Series
N-Seriescircuit
circuitbreaker
breakerisiscontrolled
controlledand
andmonitored
monitoredbyby
either thethe
either COMPACT™ or™ULTRA
COMPACT or ULTRA
containedininaafully
interrupters contained fullywelded
weldedand
andsealed
sealed
316 ADVCController
ADVC Controller(ADVC).
(ADVC).
316 marine-grade
marine stainless
grade stainless steel enclosure.
steel enclosure. Enclosed
Enclosedininaa304
304(COMPACT)
(COMPACT)oror316316(ULTRA)
(ULTRA)grade
gradestainless
stainlesssteel enclosure,
steel thethe
enclosure, ADVC
ADVC
provides
providesananelectronic
electroniccontroller
controllerwith
withoperator
operatorinterface
interfacethat
(OI)monitors the circuit
that monitors the breaker
circuit breaker
and
and provides
providesprotection,
protection,measurement,
measurement,control, and
control, communication
and communication functions. Connected
functions. Connectedvia via
The enclosure is filled with sulphur hexafluoride (SF6 )
aa control
controlcable,
cable,the
theSwitchgear
SwitchgearandandADVC
ADVCcan
can form
form a remotely
a remotely controlled
controlled and and monitored
monitored ACR.
ACR.
gas or dry air (‘N-green’ option), which both have
excellent electrical insulating properties, resulting in a The
The circuit
circuitbreaker
breakerisisoperated
operatedby bysending
sendinga acontrolled
controlled pulse
pulseof of
current from
current froma storage
a storage
capacitor
capacitorininthe
theADVC
ADVCthrough
througha asolenoid.
solenoid.This
Thisattracts thethe
attracts mechanism
mechanism plate, which
plate in turn
which in turn
compact and low-maintenance device. closes
closes the
thecontacts
contactsininthe
thevacuum
vacuuminterrupter. The
interrupter. Thecontacts
contactsareare
held in the
held in theclosed position
closed by by
position
latch
latch tongues
tonguesresting
restingononthe
thetrip
tripbar.
bar.

Opening
Openingof ofthe
thecontacts
contactsisisachieved
achievedbybyreleasing aa
releasing controlled
controlledpulse
pulseof of
current from
current froma capacitor
a capacitor
through
throughthe thetrip
tripcoil.
coil.This
Thisattracts
attractsthe
thetrip
tripbar
bararmature,
armature, turning thethe
turning triptrip
barbar
andandreleasing thethe
releasing
1 12
latch.
latch.The
Theopening
openingspringspringand
andthe
thecontact
contactpressure
pressuresprings
springs accelerate
accelerate thethe
contacts
contacts open. A A
open.
flflexible
exible connection
connectionisisprovided
providedtotoallow
allowmovement
movement of of
thethe
contacts
contactsto to
occur.
occur.

Epoxy
Epoxy bushings
bushingsinsulate
insulatethe
themain
maincircuit
circuitconductors
conductors from thethe
from tank
tankand provide
and a double
provide a doubleO-ring
O-ring
2 seal.
seal. They
Theyalso
alsoprovide
providethe
thenecessary
necessaryinsulation
insulationandandsupport
support forfor
thethe
embedded
embedded capacitive
capacitive
13
voltage
voltagetransformers
transformers(CVT)
(CVT)andandfor
forthe
thecurrent
currenttransformers
transformers (CT).
(CT).The bushings
The areare
bushings DINDIN
47 47
636636
(threaded
(threadedoption)
option)and
andallow
allowthe
theconnection
connectionofof alternative
alternativecable
cableconnection
connectionelbows if desired.
elbows if desired.
Lightning
Lightningarrester
arrestermounting
mountingisisprovided
providedforforinstallation
installationconvenience.
convenience.
14
AA standard
standardkit kitfor
forfifield
eld fifitting
tting isissupplied
suppliedwith
withthe
thecircuit
circuitbreaker.
breaker.It It
contains
containssilicone
silicone bushing
bushing
boots
bootsand and9.85
9.85ft.ft.(3(3m)
m)lengths
lengthsofof.372
.372in.² (240
in.² (240mm²) aluminium
mm²) aluminiuminsulated water-tight
insulated water-tight cable
cable
tails
tails rated
ratedatat630
630A. A.This
Thisarrangement
arrangementresults
resultsinina arecloser
reclosersuitable
suitable forfor
connection
connection into an an
into
15 insulated
insulatedconductor
conductorsystem,system,orora abare
bareconductor
conductor system,
system, as as
appropriate.
appropriate. TheThefullyfully
insulated
insulated
systemprovides
system providesfreedom
freedomfrom fromfaults
faultscaused
causedbyby birds
birds andand other
other wildlife.
wildlife.
3
16 An
An auxiliary
auxiliary voltage
voltagesupply
supplyofof110,
110,220, oror
220, 240 volts
240 ACAC
volts is required to power
is required thethe
to power unitunit
and,and,
if if
4 necessary,
necessary, aa VT can be
voltage provided as
transformer a purchase
can option.
be provided as aThe ADVC is
purchase connected
option. by a control
The ADVC is
17 cable to the by
connected bottom of the
a control circuit
cable to breaker through
the bottom a rubber
of the covered through
circuit breaker plug/socket arrangement.
a rubber covered
5 plug/socket arrangement.
A clearly visible external pointer shows the contact position. The recloser can be tripped from
18 the ground
A clearly by a hookstick.
visible It can shows
external pointer then bethe
locked out by
contact opening
position. therecloser
The isolatingcan
switches located
be tripped from
6 on
thethe operator
ground by acontrol panel.
hookstick. These
It can switches
then are physically
be locked connected
out by opening in seriesswitches
the isolating with bothlocated
the
trip andoperator
on the close solenoids.
control panel. These switches are physically connected in series with both the
7 19 trip and close solenoids.
The ADVC interfaces to the recloser via the control cable and connects to the switch cable
20 entry module
The ADVC (SCEM) in
interfaces tothe
thebase of the
recloser viatank. The SCEM
the control cableuses
andnonvolatile
connectsmemory to store
to the switch all
cable
8 relevant calibration
entry module (SCEM) data,
in ratings,
the baseand number
of the tank.ofTheoperations.
SCEM usesThe non-volatile
SCEM also provides
memory the first all
to store
21 stage of electrical
relevant calibration isolation and shorting
data, ratings, electronics
and number to short theThe
of operations. CTsSCEM
and CVTs
alsoinprovides
the eventthe thefirst
9 control
stage ofcable is disconnected
electrical isolation and while current
shorting is flowing through
electronics to short the
the recloser.
CTs and CVTs in the event the
22 control cable is disconnected while current is flowing through the recloser.
10

11 23

24
Cross section of circuit breaker

Legend
1: Cable tails 13: DIN 47 636 bushings
2: Current transformer 14: Capacitive voltage
3: 316 grade stainless transformer (CVT)
steel tank 15: Lightning arrester
4: Air- or gas-filled tank and mountings
5: Flexible connection 16: Vacuum interrupter
6: Closing solenoid 17: Contacts
7: Opening spring 18: Pushrod
8: Mechanism plate 19: Contact pressure spring
9: Switch cable entry 20: Latch
module (SCEM) 21: Trip bar
10: Cable-entry cover 22: Trip bar armature
11: Cable to control cubicle 23: Trip coil
12: Silicone bushing boot 24: Manual trip lever
N-Series Automatic Circuit Recloser

4 | N-Series Three-Phase Automatic Circuit Recloser


ADVC Controller Series
Advanced protection, data logging, and With a cubicle designed
designedtotominimize
minimizetemperature
temperatureriserisefrom
fromsolar
solarheating,
heating, the
the 304
304 (COMPACT)
(COMPACT)
communications capabilities are made possible by 316 (ULTRA) grade stainless
or 316 stainlesssteel
steelenclosure
enclosureisisused
usedtotomount
mountthethecontrol and
control protection
and protection
enclosure (CAPE), power
power supply
supplyunit
unit(PSU),
(PSU),customer
customeraccessories,
accessories,andandoperator
operatorinterface.
interface.
the technology housed in the ADVC Controller.
The ADVC Controller
Controller Series
Seriesincorporates
incorporatesaamulti-function
multifunction protection
protectionrelay,
relay,aacircuit
circuitbreaker
breaker
controller, a metering
metering unit,
unit,and
andaan RTU. terminal unit.
remote
It has been designed especially for outdoor
pole-mounted operation and is typically mounted low Batteries are carefully
Batteries are carefullylocated
locatedunderneath
underneaththese
thesemodules
modulestotohelp
helpavoid
avoid overheating
overheating soso that
that a a
on the pole for ease of access by operation personnel. battery life of
of up
up to years11can
to55years canbe
beachieved.
achieved.AAtamper-resistant,
tamper-resistant,lockable
lockable stainless
stainless steel
steel door
door,
sealed with aa rubber
rubbergasket,
gasket provides
provides access
accessto tothe
theoperator
operatorinterface.
interface.Vents
Ventsare arescreened
screened
against vermin entry
entry and
andall
allelectronic
electronicparts
partsare
areenclosed
enclosed
in in a sealed
a sealed die-cast
die-cast enclosure,
enclosure, which
which
protects them fromfrom entry
entryof
ofmoisture
moistureand
andcondensation
condensationensuring
ensuringa long
a long lifetime.
lifetime.

The COMPACT Cubicle


Cubicle isissuitable
suitablefor
fortemperatures
temperaturesfrom
from-14
-14°F°F(-10
(-10°C)
°C)toto122
122°F°F(50
(50°C),
°C),
while the option of
of aa battery
batteryheater
heaterininthe
theULTRA Cubicle
ULTRACubicle extends
extends itsits operating
operating temperature
temperature
range from -40
-40 °F
°F (-40
(-40°C)
°C)toto122
122°F°F(50
(50°C).
°C).

A
A built-in
built-in microprocessor
microprocessor controlled
controlled power
power supply provides uninterrupted
supply provides uninterrupted operation
operation ofof not
not
only
only the
the circuit
circuit breaker and controller,
breaker and controller, but
but also
also the
the communications
communications radio
radio or
or modem.
modem. These
These
accessories are connected to a built-in user
user-programmable radio power
programmable radio power supply.
supply. Therefore
Therefore
no other power supplies are required for connection into into your SCADA
SCADA or distribution
distribution
automation
automation system.
system.

Due
Due toto careful
careful design
design,thetheefficiency
efficiencyofof
allall parts
parts is extremely
is extremely high,
high, allowing
allowing a battery
a battery holdhold-up
up timetime
hours.2.2 The
of up to 44 hours Thearchitecture
architectureused
usedhas hasthe
theadvantage
advantagethat that the
the circuit
circuit breaker
breaker operation
operation
is independent of of the
the high-voltage
high-voltagesupply,
supply,relying
relyingonona aset
setofof capacitors
capacitors charged
charged byby
thethe
auxiliary supply.
supply.

Due to sophisticated
Due to sophisticated power-supply-management
power-supply-managementtechniques,
techniques,aacircuit
circuitbreaker
breakeroperation
operation is is
always
always guaranteed when attempted
guaranteed when attemptedand
andalarms
alarmsare
areraised
raisedover
overthe
thetelemetry
telemetry when
when auxiliary
auxiliary
power is lost.

Communications equipment can


Communications equipment canbe
bemounted
mountedwithin
withinthe
theADVC
ADVCController
Controllercubicle.
cubicle.AA
V23V23 FSK
FSK
modem, RS232, RS485,
modem, RS232, RS485, and
and Ethernet
Ethernet TCP/IP
TCP/IP are
areprovided
providedas
asstandard
standardtotosupport
supportallall
ofof your
your
ADVC ULTRA (with flexVUE) communications needs.
communications needs.

The ADVC Controller Series is available in two models:

> ULTRA
> COMPACT

The table below outlines some of the differences between the two models.

ULTRA COMPACT
Enclosure 316 stainless steel 304 stainless steel
Door locking Three-point Two-point
Customer Side tray Side tray only
accessory tray Upper tray
Input/Output modules 8 inputs, 8 outputs N/A
Optional
Battery heater Optional N/A
Battery 7 Ah or 12 Ah 7 Ah
ADVC COMPACT (with setVUE) Temperature
Temperature range
Range -40 °F (-40 °C) to 122 °F (50 °C) -14 °F (-10 °C) to 122 °F (50 °C)
(with battery heater option)

Auxiliary power supply 120/240 VAC 120/240 VAC


Dual AC power supply Optional N/A
VT supply via switchgear Optional Optional
DC power supply Optional N/A

1 Battery replacement interval


interval is
is influenced
influencedbybyenvironmental
environmentaltemperature.
temperature.
2 With optional 12 Ah Battery, panel
panel off off,and
andwithout
withoutcommunications
communicationsdevices
devicesoperating.
operating.

N-Series Three-Phase Automatic Circuit Recloser | 5


ADVC Block Diagram
Electric automatic
Schneider Electric ACRs provide many
circuit outstanding
reclosers provide
advantages
many to the advantages
outstanding user. to the user.

New and innovative features


features have
have been
been made
madepossible
possible
by the way the pole-mounted circuit breaker
pole-mounted circuit breakerandand
control cubicle work closely
closely together.
together. The
The block
block
diagram on this page shows how the the two
two items
items
are interfaced.

Special extended range CTs provide


current a range from
transformers provide a
1 A to from
range 16,0001 AAtofor16,000
measurement and protection.
A for measurement and
Embedded Embedded
protection. voltage screens accurately
voltage screensimage the
accurately
primarythe
image voltage value
primary and phase
voltage relationship
value and at
phase relationship
thethe
at analogue
analoguefront
frontend, allowing
end, allowingmeasurement
measurement of
of voltage,
voltage, current,
current, power
power factor,
factor, andand frequency
frequency in the
in the electronic
electronic module. module.

ADVC Controller block diagram

6 | N-Series Three-Phase Automatic Circuit Recloser


ADVC Features
Each recloser is provided with an operator interface. From here a user can access and
program the many measurement and protection features available. The two following operator
interfaces are available:

> setVUE Operator Interface


t Based on the field-proven operator panels in the previous controllers, this menu-driven
interface with large LCD display offers a familiar look and feel.

setVUE Operator Interface

> flexVUE Operator Interface


t 20 Status Lights provide a quick snapshot of the protection and controller status.
t 12 Quick Action Keys are available to execute frequently used actions such as «Remote
control» ON/OFF, «Reclose» ON/OFF, etc. Each key has its own status light to indicate
the ON/OFF state.
t All Status Lights and Quick Action Keys are customizable.
t It is possible to access event and measurement data and change settings.

flexVUE Operator Interface

Telemetry Interface
The Schneider Electric ACR can be interfaced to your SCADA system either through its built-in
V23 modem and a radio, or its RS232 ports and a modem of your choice. RS485 and Ethernet
TCP/IP are also available. A variable-voltage uninterruptible power supply is included for the
radio or modem, which can be mounted inside the communications cubicle. Many telemetry
protocols can be supported such as DNP3 and IEC 60870-5-101.

Computer Interface
WSOS isis an
WSOS an advanced
advanced personal-computer-based
personal-computer-basedsoftware
softwarepackage
packagetotoallow
allowoffl
off-line andonline
ine and on-line
programming,monitoring,
programming, monitoring,and
andcontrol
control of
of aa recloser
recloser via a USB port, RS232
RS232 port, or
or Ethernet.
Ethernet.

Remote Control
The ADVC offers an impressive list of communication ports for use in remote control applications:

> 4 x RS232 > 1 x Ethernet


> 1 x RS485 > 1 x V23

N-Series Three-Phase Automatic Circuit Recloser | 7


WSOS Version 5
Customizing the operator interface to suit your unique The flexVUE operator interface uses light-emitting
light emitting diodes (LEDs) and an LCD display
applications has never been easier. to communicate
communicate the
the system
system status
status to
to aalocal
localoperator.
operator.Operator
Operatoractions
actionsthat
thatare
are
performed on a regular basis can be mapped to 12 12 dedicated
dedicated buttons
buttons on
on the
the interface.
interface.
Each of
Each of these
these buttons
buttons also
also has
has aa light
light to
to indicate
indicate the
the ON/OFF
ON/OFFstatestateof
ofeach
eachaction.
action.
Together with
Together with the
the 20
20 Status
Status Lights
Lights thethe panel
panel provides
provides no
no less
less than
than 32
32 three-color
three-color LEDs
LEDs
that display
that display the
the state
state of
of the
the controller
controllerand andoverhead
overheadsystem.
system.On Onthe
theinterface,
interface,the
theaction
action
buttons are
buttons are grouped
grouped together
together and
and referred
referred toto as
as Quick
Quick Action
Action Keys.
Keys.The
Thestatus
statusLEDs
LEDs
are also
are also grouped
grouped together
together and
and referred
referred to to as
as Status
Status Lights.
Lights.

Every controller
controller is
is programmed
programmed with with aa standard
standard confi guration of
configuration ofStatus
StatusLights
Lightsand
and
Quick Action
Action Keys
Keys — — text
text labels
labels are
are used
used to
to mark
mark the
the function
function of
of each.
each. These
These labels
labels are
are inserted
inserted intointo special
special pockets
pockets within
within thethe flexVUE
flexVUE operator
operator interface
interface andand
cancan
be be
changed in the fifield
eld if required.

A
A graphical panel configuration
graphical panel configuration tool
tool isis provided
providedas aspart
partofofthe
theWSOS
WSOS55software
softwarepackage
package
that
that will allow full
will allow full customization
customization ofof the
the flexVUE operatorinterface,
flexVUEoperator interface,ififrequired.
required.With
Withthe
the
tool
tool you
you can create your
can create your own
own logic
logicfunctions
functionsdriving
drivingthe
theStatus
StatusLights,
Lights,as aswell
wellasaschange
change
the
the actions linked to
actions linked to each
each Quick
Quick Action
ActionKey. Key.New
Newlabels
labelscan
canbebeprinted
printedfrom
fromthe
theWSOS
WSOS
template
template using standard office
using standard office paper,
paper,cut cutto
tosize,
size,and
andinserted
insertedinto
intothethecontroller.
controller.

Example of building the logic function for a Status Light

Inserting custom labels into the interface

WSOS
WSOS Version
Version 55 integrates
integrates the
theSchneider
SchneiderElectric
Electricfifield-proven, Windows®®-based
eld-proven, Windows -based
switchgear
switchgear operating
operatingsystem
systemandandits
itspowerful
powerfulfeatures
featuresand
andtools,
tools,developed
developedover overmany
many
years,
years, into
into aa modern
modern desktop.
desktop.The
The desktop
desktopincludes
includesthe
theSwitchgear
SwitchgearExplorer
Explorerto to
organize
organize your
your switchgear
switchgearthetheway
wayyou
youlike
likeititand
andthe
theLaunch
LaunchPadPadfor
forhandy
handylinks
linkstoto
Example of setting the Quick Action Keys
online
online help,
help, getting
getting started,
started,updates,
updates,andandmuch
muchmore.more.Controlling,
Controlling,confi guring, and
configuring, and
accessing
accessing valuable
valuable switchgear
switchgeardata
datafrom
fromlocal
a localor or
remote
remotelocations is now
locations even
is now eveneasier
easier
than
than before.
before.

Local and Remote Control


> Switchgear operation
> Protection group selection
> Protection group copy
> NPS on/off/alarm control
> Auto reclose, ground protection, and SGF on/off control
> Hot line tag, low gas, and dead lockout on/off control
> Configurable input/output expander (IOEX)
> Configurable quick keys
> Configurable delay for local open and close operations (“hit and run”)
> Configurable SCADA protocols (e.g., DNP3, 101/104, modbus, MITS)

8 | N-Series Three-Phase Automatic Circuit Recloser


WSOS Version 5 (continued)
Windows Switchgear Communication Options
Operating System > Local USB port (for connection to WSOS only)
> Local RS232 port connection
WSOS is the Schneider Electric Switchgear Operating > Radio modem
System software. It provides easy access to all
> GSM/PSTN modem
switchgear functions from opening/closing, through
configuring protection and communication parameters > DNP3 virtual terminal object
to accessing measurement and analytical data. > TCP/IP
> Communications output capture
By using a PC, engineers can manage a large number
of reclosers, either remotely via a communications link Measurement Screens
or locally via USB, serial port, or Ethernet connection. > Three-phase, ground, and sequence current
> Phase voltages:
t Phase to phase
t Phase to ground
t Sequence voltages
> Phase live/dead indication
> Apparent, reactive, and real power:
t Total
t Per phase
> Power factor
> Signed or unsigned power
> Frequency
> Power quality toolkit:
t Waveform capture
t Harmonics
Example of the WSOS5 desktop
Interface Configuration
> Status Lights:
t Logic function to indicate, separate true/false state color configuration
> Quick Action Keys:
t Customize actions assigned to each key
t Custom logic functions for light indication
t Separate true/false color configuration
> Print labels to insert into operator interface

Panel Configuration Tool

N-Series Three-Phase Automatic Circuit Recloser | 9


General Protection Features
Operating Sequence
Reclose times are individually selectable. The operating sequence is defined by:
O – 1st rt – CO – 2nd rt – CO – 3rd rt – CO where rt = reclose time
where O = open
where C = close

Reclose Times
> First reclose time range: 0.5 – 180 sec.
> Second reclose time range: 2.0 – 180 sec.
> Third reclose time range: 2.0 – 180 sec.
> Timing resolution: 0.1 sec.

Sequence Reset Time


> Sequence reset
Resettime:
Time: 3 – 180 sec.
> Timing resolution: 1 sec.

Trips to Lockout
Overcurrent and fault trips to lockout are selectable between 1 and 4. A separate setting is
available for sensitive ground fault and negative phase sequence.

Inverse Time Protection Curves


The ADVC offers a total of 48 user-selectable inverse time protection curves. These are:
100

Standard inverse > Three IEC60255 curves: Inverse


Very inverse Very inverse
Time (s)

Extremely inverse
Extremely inverse
> Three IEEE C37.112 inverse time curves: Moderately inverse
Very inverse
10

Extremely inverse
> 42 nonstandard
non-standardinverse
inversetime
timecurves:
curves: Refer to the Operating
Manual for a full listing

Instantaneous Protection
Instantaneous protection works by tripping the recloser if the line current exceeds the
1

Instantaneous Multiplier x Setting Current.


100 % Setting current
> Multiplier range: 1 – 30
Inverse time curves
> Resolution of setting: 0.1
> Max effective setting: 16 kA

Definite Time Protection


Definite time protection is an alternative to inverse time protection. It works by tripping the
100

recloser at a fixed time after pick-up.


IDMT curve
> Setting current range: 10 – 1,260 A
Time (s)

Threshold
Maximum time
> Definite time resolution: 0.1 sec.

Minimum time > Definite time range: 0.01 – 100 sec.


10

Instantaneous > Setting current resolution: 1A

Modified curve Sensitive Ground Fault (SGF)


SGF causes the recloser to trip when the ground current rises above a set level for longer than
the set time.
1

> SGF trip current range: 4 – 20 A


100 % Setting current > SGF operating time range: 0.1 – 999 sec.

Modified curve
> SGF trip current setting resolution: 1A
> SGF operating time resolution: 0.1 sec.

10 | N-Series Three-Phase Automatic Circuit Recloser


General Protection Features (continued)
Inrush Restraint
Inrush restraint raises the phase and ground threshold currents for a short period of time to
allow for short duration inrush currents when closing onto a load.

> Multiplier range: 1 – 30


> Multiplier resolution: 0.1
> Time range: 0.05 – 30 sec.
> Time resolution: 0.05 sec.

Cold Load Pick-Up


Cold load pick-up allows for a loss of diversity when a load has been without supply for a
period of time.

> Multiplier range: 1–5


> Multiplier resolution: 0.1
> Time constant
Constantrange:
range: 1 – 480 min.
> Time constant resolution: 1 min.

Multiple Protection Groups


The ADVC supports up to 10 protection groups, each of which can be configured with
completely separate protection characteristics with different inverse time curves and setting
currents. The number of protection groups available to the operator can be configured using
WSOS, thereby restricting or enabling access to protection settings as required.

Automatic Protection Group Selection


Automatic protection group selection (APGS) is used to change the protection group
depending on the direction of power flow. This allows the recloser to be correctly graded with
devices downstream regardless of the power flow direction.

Loss of Phase
WSOS offers a quick, easy way to configure the protection groups.
Loss of phase protection trips the recloser if phase-ground voltage on one or two phases falls
below a set voltage threshold for a set length of time.

> Threshold voltage range: 2 – 15 kV


> Voltage resolution: 1V
> Time range: 0.1 – 100 sec.
> Time resolution: 0.1 sec.

Live Load Blocking


Live load blocking prevents a recloser from closing if any of the load side terminals are live.

> Live load threshold voltage range: 2 – 15 kV

Dead Lockout
Dead lockout prevents a reclose unless one or more of the source side or load side terminals
are live. If all terminals are dead then the controller goes to lockout.

N-Series Three-Phase Automatic Circuit Recloser | 11


Advanced Protection Features
Directional Blocking
Directional blocking is a protection feature that restricts tripping on faults to a designated side
of the recloser. It prevents nuisance tripping if particular network conditions are causing “false”
ground faults. In radial systems, directional blocking prevents nuisance tripping by blocking
faults in the source direction and only responding to faults in the load direction.

Directional Protection
Directional
Distinct protection
protection for is distinct
faults protection
in the for faults
forward and in the
reverse forwardAand
direction. reverse
forward faultdirection.
may use a
A forward
different fault may use
time-current a different
curve time-current
and settings curvefault
to a reverse and (i.e.,
settings
thesetoare
a reverse fault
individually
(i.e., these are
selectable). individually
Both the forwardselectable).
protectionBoth
and the forward
reverse protection
protection areand reverseat
operating protection
the same time.
are operating
This at the same
is an additional time.This
protection is an additional protection feature.
feature.

Sequence Components
Negative-, positive-, and zero-phase sequence currents and voltages can be monitored
and logged.

In addition, the negative-phase sequence current protection can be used for detection of
low-level phase-to-phase faults in the presence of high-level, three-phase loads. Inverse time,
definite time, and instantaneous operation is available.

> Setting current range: 10 – 1,260 A


Sequence Coordination
Sequence coordination
Sequence coordination allows
allows aa recloser
recloser to
to coordinate
coordinate its
it’strip
tripsequence
sequencewith
withanother
another
recloser downstream.
recloser downstream.

Under/Over-Frequency Protection
Trip Delay
Normal Frequency
Frequency

Count
Close Time
Under/over-frequency protection
Under/over-frequency protectiontrips
tripsthe
therecloser
recloserwhen
whenthe
thesystem
systemfrequency
frequencyexceeds
exceedsthe
the
Over Frequency
Trip setting under-and
under andover-frequency
over-frequencytrip
tripthreshold
threshold values;
values; frequency
frequency tripping
tripping range:
range: 45 – 65
65 Hz
Hz
Over Frequency
Normal restore
Trip at
this time Close at
this time > Frequency calculation: Once per cycle over a two-cycle period
Time

Nominal
> Number of under/over-frequency
Frequency
Axis
cycles before tripping: 2 – 1,000
> Accuracy: ±0.05 Hz
Under/over-frequency protection
> Under/Overvoltage Protection
When selected, and a nominal phase-to-ground system operating voltage is set, the
under/overvoltage protection works within a defined threshold above and below the
specified voltage.

> Undervoltage
Under voltagelower
lowerthreshold
thresholdrange:
range: 50% – 88%
> Overvoltage
Over voltageupper
upperthreshold
thresholdrange:
range: 112% – 150%
> Trip range (after x sec.): 0 – 300 sec.
> Phase logic:
t AND: when ALL phases deviate beyond thresholds
t OR: when ANY phase voltage deviates beyond the thresholds
t AVERAGE: when the numerical AVERAGE of all phase voltages deviates
beyond the threshold

12 | N-Series Three-Phase Automatic Circuit Recloser


Measurement Features
RMS Voltage and Current
True root mean square (RMS) voltage is measured on all six terminals. A user-configured
threshold indicates a live terminal (accuracy ±2.5%). RMS current is measured on three
phases (reading 2 – 800 A).

Real Power (Signed or Unsigned)


Real power is determined by multiplying the line voltage and line current in real time and
averaging over 2 seconds (accuracy ±5% of reading, within limits of V and I above).

Power and Power Factor


The ADVC Controller measures kW, kVA, kVAr, and power factor on a per-phase basis. The
power factor of the line is determined from the line voltage and the line-current phase relationship
and the previously calculated real power (accuracy ±5% of reading, within limits of V and I above).

Default Historical Measurements


Power flow is integrated over 5-, 15-, 30-, or 60-minute intervals (kWh) and recorded for two
months at the default setting. This can be viewed on the operator control panel, computer, or
compatible SCADA system. Additionally, data can be uploaded into a portable computer or a
compatible SCADA system.

Configurable Historical Measurements


Average demand profiles may be configured using WSOS. Customized configuration enables
the user to specify only the parameters that are required, negating unnecessary information
capture. Parameters such as line voltages and currents, power, kWh, battery voltage, and
cubicle temperature can be recorded in intervals selectable between 1 and 1,440 min.

Event History
> Maximum number of typical events stored in the event history: 30,000 events
Gas Pressure Measurement (SF6 or Dry Air “N-green” Option)
> Gas pressure display resolution: .725 psi (5 kPa)
> Gas pressure display accuracy: ± 1.45 psi (±10 kPa)
> Gas low alarm setting: 9.427 psi gauge @ 68 °F (65 kPa gauge @ 20 °C)
> Gas low alarm/interlock accuracy: ±1.45 psi (±10 kPa)

Power Quality Toolkit


> Supply Outage Measurement
t The supply outage measurement feature utilizes built-in recloser features to record the
number and duration of outages. These statistics are recorded in the controller and are
available to the utility to help calculate system outage customer minutes.
> The Controller Records:
t Cumulative total number of outages
t Cumulative total outage duration
t The time and duration of each outage event in the event log
Harmonic analysis
t These records are accessible to the user and can be retrieved using the operator control
panel, WSOS, or a SCADA system
> Harmonic Analysis
t Harmonics 2 to 16 and the total harmonic distortion (THD) are calculated over an 80-ms
period for four currents, six line-line voltages and six line-ground voltages —
these harmonics are available via WSOS
> Waveform Capture:
t Based on a user
user-defi ned trigger, the ADVC captures and stores in nonvolatile
defined non-volatilememory,
memory,
scaled raw data (10
(10 xx 3,200
3,200 samples
samples per
per second)
second) ofof the
the six
six line-ground
line-ground voltages,
voltages,and
andfour
four
currents for a predefi ned time window either
predefined either side
side of
of a user-defi ned trigger
user-defined trigger
t The user can configure
configure a pre
pre-and
andpost-trigger
post-triggertime
timeratio
ratiofor
fordata
datato
tobe
bestored
stored —

to 50%
this defaults to 50% pre-trigger
pre-trigger and
and 50%
50% post-trigger
post-trigger
t The captured data can be uploaded at anytime in COMTRADE (IEEE Std C37.111-1999)
format via WSOS
Waveform capture

N-Series Three-Phase Automatic Circuit Recloser | 13


N-Series Recloser Pole Mounting Details

Customer supplied: Schneider Electric supplied:


t Insulated connectors t 9.85 ft. (3 m), 630 A cable tail standard
t Connecting cables t 250 A, 400 A, or 800 A by request
t Lightning arresters t Silicone bushing boots (see detail below)

Cable Terminated with


Two-hole Lug
B A
Silicon Grease

Optional radio
antenna (installed
by customer)

C Standard Lug
D
Torque both M10
Bolts to 32.5 lb./
ft. (44 Nm) using
ADVC Controller a .67 in (17 mm)
Socket

Boot

Control Cable

Bushing Palm
(Factory Fitted)

Bushing

N-Series Model Rated Voltage A (in./mm) B (in./mm) C (in./mm) D (in./mm)


N15 15.5 kV 54.9/1,370 35.3/898 22.1/525 33.6/880
N27 27 kV 54.9/1,370 35.3/898 22.1/525 33.6/880
N38 38 kV 55.5/1,410 35.3/898 22.1/525 37.5/955
N38 (“N-green”) 38 kV 55.5 /1,410 35.3/898 22.1/525 37.5/955

Notes
(1) Details given in this illustration are subject to change without notice. For full details see the Installation Manual.
(2) Grounding connections are not shown and are to be in accordance with the Installation Manual.
(3) Recloser can be mounted closer to pole if lightning arresters are pole-mounted.
(4) Optional substation mounting frame available on request.

14 | N-Series Three-Phase Automatic Circuit Recloser


N-Series Recloser Specifications

N-Series “N-green”
option
15 kV 27 kV 38 kV 38 kV 38 kV
12.5 kA 12.5 kA 12.5 kA 16 kA 16 kA
Ratings
Rated Maximum Voltage 15.5 kV 27 kV 38 kV 38 kV 38 kV
Rated Nominal Voltage (Phase to Ground)
Rated Continuous Current 800 A 800 A 800 A 800 A 800 A
Emergency Current (8 Hours) 850 A 850 A 850 A 850 A 850 A
Fault Make Capacity (RMS) 12.5 kA 12.5 kA 12.5 kA 16 kA 16 kA
Fault Make Capacity (Peak) 31.5 kA 31.5 kA 31.5 kA 40 kA 40 kA
Power Operating Time (Close/Open) 0.1/0.05 s 0.1/0.05 s 0.1/0.05 s 0.1/0.05 s 0.1/0.05 s
Mechanical Operations 10,000 10,000 10,000 10,000 10,000
Rated Full Load Operations 10,000 10,000 10,000 10,000 10,000
Short Time Current 12.5 kA 12.5 kA 12.5 kA 16 kA 16 kA
Breaking Capacity
Mainly Active (0.7pf) 800 A 800 A 800 A 800 A 800 A
Fault Break Capacity 12.5 kA 12.5 kA 12.5 kA 16 kA 16 kA
Cable Charging 25 A 40 A 40 A 40 A 40 A
Line Charging
Transformer Magnetizing 22 A 22 A 22 A 22 A 22 A
Capacitor Bank 250 A
Lightning Impulse Withstand Level
Phase to Phase
Phase to Ground 110 kV 150 kV 170 kV 170 kV 170 kV
Across Interrupter 110 kV 150 kV 170 kV 170 kV 170 kV
On Loss of SF6 /Dry Air 60 kV 70 kV 70 kV 70 kV 70 kV
Power Frequency Withstand Voltage
Phase to Ground 50 kV 60 kV 70 kV 70 kV 70 kV
Across Interrupter 50 kV 60 kV 70 kV 70 kV 70 kV
Service Conditions
Ambient Temperaturea (OF) -40 to 122 -40 to 122 -40 to 122 -40 to 122 -40 to 122
Ambient Temperaturea (OC) -40 to 50 -40 to 50 -40 to 50 -40 to 50 -40 to 50
Radiation (Max.) 1.1 kW/m 2
1.1 kW/m 2
1.1 kW/m 2
1.1 kW/m 2
1.1 kW/m2
Humidity 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100%
b
Altitude Feet (Max.) 9,840 9,840 9,840 9,840 9,840
Altitude Meters (Max.) b 3,000 3,000 3,000 3,000 3,000
Net Weights
Circuit Breaker with Pole-Mount Bracket (lb./kg) 549/249 549/249 549/249 549/249 549/249
Control Cubicle with Control Cable (lb./kg) 90/41 90/41 90/41 90/41 90/41
Gross Weight of Crate (lb./kg) 891/404 891/404 891/404 891/404 891/404
External VT (lb./kg) 132/60 132/60 132/60 132/60 132/60
Crate Dimensions
Width (in./mm) 45.7/1,160 45.7/1,160 45.7/1,160 45.7/1,160 45.7/1,160
Depth (in./mm) 28.7/730 28.7/730 28.7/730 28.7/730 28.7/730
Height (in./mm) 64.6/1,640 64.6/1,640 64.6/1,640 64.6/1,640 64.6/1,640

a. Option when cubicle battery heater is fitted (-14 °F to 122 °F {-10 °C to 50 °C} without heater)
b. For altitudes above 1,000 m (3,280 feet), derate in accordance with ANSI C37.60 for reclosers (ANSI C37.63 for LBS)

N-Series Three-Phase Automatic Circuit Recloser | 15


©2014 Schneider Electric. All Rights Reserved. Schneider Electric, Compact, and Make the most of your energy are trademarks owned by Schneider Electric Industries
SAS or its affiliated companies. All other trademarks are the property of their respective owners. • www.schneider-electric.com • 998-1221746_US
For More Information ...
Scan the QR code to email one of our subject matter experts
about our reclosers or visit us at http://goo.gl/XVwg1T.

Schneider Electric USA, Inc.


1415 S. Roselle Road
Palatine, IL 60067
Tel: 847-397-2600
Fax: 847-925-7500
www.schneider-electric.us/go/utility

Document Number 0110DB1301 October 2014