502 Series DC Power System: Netsure™
502 Series DC Power System: Netsure™
502 Series DC Power System: Netsure™
502 SERIES
DC POWER SYSTEM
NetSure™ 502 SERIES
KEY FEATURES
yy Configuration file
capability – minimizes Efficiency eSure Rectifier
installation time and allows Efficiency Curve
planned network conformity. 98%
96%
94%
92%
90% Standard Rectifier
88% Efficiency Curve
86%
84%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Load
2
The NetSure™ 502 system is ideal for wireline and wireless applications such as switch sites, co-location,
huts and large vaults or enclosures, as well as FTTx electronics.
eSure™ Rectifiers
Ultra high efficiency of 96.5% is achieved with the eSure R48-2000e rectifier. eSure rectifiers from Vertiv deliver the most reliability
and highest efficiency in the industry, reducing power consumption and lowering operation cost.
The NetSure 502 Series supports eSure The modular design of these units
rectifiers. The R48-2000e is a modular, facilitates power plant sizing to
high frequency constant power rectifier application needs. Beyond reducing
designed with the latest patented operating costs, Vertiv has maximized
switch-mode technology using DSP the value of eSure rectifiers by making
(Digital Signal Processor) functionality. them backwards compatible with existing
Use of DSP technology results in fewer NetSure DC Power Systems. Both unit
components and optimized operation. types can be used in a system together.
Plug’n’play technology allows for easy
The eSure rectifier provides up to 100%
system configuration. System capacity
of rated power at 55°C. As the
can be increased by simply plugging an
temperature increases from 55°C to 80°C,
additional rectifier into an existing shelf
the thermal power limit circuit linearly
or a newly added expansion shelf — no
decreases power. In the typical operating
adjustments or setup are required. The
range, eSure rectifiers have a power factor
NetSure 502 rectifiers provide load power,
greater than .99, total harmonic distortion
battery float current and battery recharge
less than 5%, and efficiencies up to
current. The rectifiers are monitored and
96.5%. Each hot-swappable rectifier has
controlled by the SCU+, ACU+ or NCU.
an integral multi-speed cooling fan and
a tri-LED status indicator.
Environmental Endurance
3
NetSure™ 502 SERIES
As load demand grows, the system can be easily expanded with additional modular components.
4
NetSure™ 502 systems come in many different configurations
1. AC input wiring
3. ACU+ controller
1 2 3 4
4. Distribution panel
This highly flexible DC power system is available in bulk output shelves, integrated distribution shelves or externally mounted
distribution panel systems. These alternatives are optimal for rack-mounting in any building, shelter or cabinet installation.
NetSure 502 is easily integrated into any Vertiv outdoor enclosure when a pre-manufactured space-efficient outdoor solution is needed.
The system can also be shipped loose or mounted in a relay rack with battery trays. The three following core configurations define the
combination of rectifier and distribution shelves and determine the ultimate capacity of the system.
5
NetSure™ 502 SERIES
INPUT
19" integrated up to 80 A
23" integrated up to 120 A
19" rear bulk systems up to 365 A
Output Capacity 23" rear bulk systems up to 450 A
19" & 23" top bulk systems up to 400 A
19" & 23" externally mounted distribution panel systems up to 600 A
Rear bulk output shelves – Rear for installation, front for operation and maintenance
Top bulk output system – Top for installation, front for operation and maintenance
Access
Integrated distribution system – Front for installation, operation and maintenance
Externally mounted distribution system – Rear, front and top for installation, front for operation and maintenance
ENVIRONMENTAL
Temperature Range, Operating -40 °C to +80 °C (-40 °F to +176 °F) see rectifier specification for any derating
EMI/RFI Conforms to FCC rules Part 15, Subpart B, Class B and EN55022 Class B, radiated and conducted
UL 60950 Recognized (US & Canada) – Rear bulk distribution system and integrated distribution system
Safety Compliance UL 1801 Listed (US & Canada) – top bulk and external distribution panel system
NEBS Level 3
100 100
80 80
60 60
40 40
20 20
0 0
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 0 50 100 150 200 250 300 350
6
Rectifier Specifications, R48-2000e
AC INPUT RECTIFIER
Input Voltage, Nominal 120 VAC, 208 VAC, 240 VAC
Input Voltage, Operating Range 85 VAC to 300 VAC extended range to 300 VAC without damage
Frequency 45 Hz to 65 Hz
Power Factor (PF) 0.99 ≥ to 50% load
Total Harmonic Distortion <5% from 50% to 100% of rated load
Input Current, Maximum 13 A
Inrush Current Inrush current does not exceed 150% of the rated input steady state peak value.
Operating Efficiency 96.5%
DC OUTPUT
Output Voltage, Adjustment Range -42 VDC to -58 VDC
Constant Power Limiting Operation 2000 W @ -48 VDC
See derating chart for voltages less than 176 VDC or temperatures higher than 55 °C.
Output Current 41.7 A @ -48 VDC
Regulation Steady state output voltage remains within +/-1%
for any combination of input voltage and temperature from 5% to 100% load
Voice Band Noise Does not exceed 38 dBrnC output noise from 20% to 70% load
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 100 mv rms per Telcordia GR-947-CORE
Psophometric Noise <2 mV at 20% to 70% of rated load
Protection High Voltage shutdown fixed and selective capability. Fixed – requires manual restart.
Selective – If rectifier detects over voltage it will turn off. After 5 seconds it will restart;
if it encounters an over voltage within 5 minutes it will turn off and remain off until reset.
ENVIRONMENTAL
Temperature -40 °C to +80 °C (-40 °F to 176 °F )
Altitude 2000 m (6560 ft) at full power
British Thermal Unit (BTU) 326.9 BTU/hour
Ventilation Front to back with speed-controlled fan (field replaceable)
Audible Noise The rectifier does not produce sound levels above 50 dB(A), measured 0.6 m in front of the rectifier,
at the same horizontal line as the middle of the rectifier at 25 °C
STATUS /ALARM INDICATORS AND MONITORING
Visual Indicators Green LED: Normal Operation Yellow LED: Alarm
Red LED: Failure Flashing Red LED: Fan Failure
Status Settings Controller establishes rectifier settings
RECTIFIER PHYSICAL SPECIFICATIONS
Mounting Plug in installation
Dimensions (H x W x D) 86 x 84.5 x 272 mm (3.39" x 3.33" x 10.71")
Weight 2.4 kg (5.3 lbs)
Safety Compliance UL 60950 Recognized (US & Canada)
Additional Information
For additional specification, engineering and installation information, request specification number 582136700 (integrated distribution configuration) or 582136800 (bulk and external
distribution configurations) or 1R482000e (eSure rectifier).
For ordering information on the complete system, request SAG582136700 or SAG582136800.