Special contactors
Special contactors LC1 DpK are designed for switching 3-phase, single or
multiple-step capacitor banks (up to 6 steps). Over 6 steps, it is recommanded
to use chokes in order to limit the inrush current and thus improve the lifetime
of the installation. The contactors are conform to standards IEC 60070 and 60831,
UL and CSA.
Contactor applications
Specification
Contactors fitted with a block of early make poles and damping resistors, limiting
the value of the current on closing to 60 In max.
This current limitation increases the life of all the components of the installation,
in particular that of the fuses and capacitors.
The patented design of the add-on block (n° 90 119-20) ensures safety and long life
of the installation.
Operating conditions
There is no need to use choke inductors for either single or multiple-step capacitor
banks. Short-circuit protection must be provided by gI type fuses rated at 1.7…2 In.
Maximum operational power
The power values given in the selection table below are for the following operating
conditions:
PF511555.eps
Dimensions, schemes :
page 5/103
Dimensions
LC1 DFK, DGK LC1 DLK, DMK
DB402404.eps
DB402405.eps
103
91
77
77
121 45 127 45
DB402407.eps
180
166
113
127
156 55 5
154 85
Schemes
LC1 DpK
-R
DB402403.eps
13 21 31
NO NC NC
1/L1
3/L2
5/L3
A1
4/T2
6/T3
2/T1
A2
-R
14 22 32
References :
page 5/102