Complementary Type 1 coordination

technical information (IEC 60947-4-1) 0

Merlin Gerin NS80 circuit breakers,


Telemecanique contactors and thermal relays
DB115219

Direct-on-line starting

Reverser
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.
Starting (1): normal LR2 class 10 A, LR9 class 10.

Motors Circuit breakers Contactors (3) Thermal relays


220/230 V 380 V 415 V 440 V (2) 500/525 V 660/690 V
P I P I P I P I P I P I Type Rating Type Type Irth (1)
(kW) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (A) (A)
0.37 1.2 0.37 1.1 0.37 1 0.55 1.2 0.75 1.2 NS80H-MA 2.5 LC1-D09 LRD-06 1/1.6
0.55 1.6 0.55 1.5 0.55 1.4 0.75 1.5 1 1.5 NS80H-MA 2.5 LC1-D09 LRD-06 1/1.6
0.37 1.8 0.75 3 0.75 1.8 0.75 1.7 NS80H-MA 2.5 LC1-D09 LRD-07 1.6/2.5
1.1 2.4 1.1 2 1.5 2 NS80H-MA 2.5 LC1-D09 LRD-07 1.6/2.5
0.55 2.8 1.1 2.8 1.1 2.5 1.5 2.6 2.2 2.8 NS80H-MA 6.3 LC1-D09 LRD-08 2.5/4
1.5 3.7 1.5 3.5 1.5 3.1 3 3.8 NS80H-MA 6.3 LC1-D09 LRD-08 2.5/4
1.1 4.4 2.2 5 2.2 4.8 2.2 4.5 3 5 4 4.9 NS80H-MA 6.3 LC1-D09 LRD-10 4/6
1.5 6.1 3 6.6 3 6.5 3 5.8 4 6.5 5.5 6.6 NS80H-MA 12.5 LC1-D09 LRD-12 5.5/8
2.2 8.7 4 8.5 4 8.2 4 7.9 5.5 9 NS80H-MA 12.5 LC1-D09 LRD-14 7/10
7.5 8.9 NS80H-MA 12.5 LC1-D12 LRD-14 7/10
3 11.5 5.5 11.5 5.5 11 5.5 10.4 7.5 12 NS80H-MA 12.5 LC1-D12 LRD-16 9/13
4 14.5 7.5 15.5 7.5 14 7.5 13.7 9 14 NS80H-MA 25 LC1-D18 LRD-21 12/18
9 17 9 16.9 10 15 NS80H-MA 25 LC1-D18 LRD-21 12/18
10 11.5 NS80H-MA 25 LC1-D18 LRD-16 9/13
5.5 20 11 22 11 21 11 20.1 11 18.4 NS80H-MA 25 LC1-D25 LRD-22 16/24
15 17 NS80H-MA 25 LC1-D25 LRD-21 12/18
18.5 21.3 NS80H-MA 50 LC1-D32 LRD-22 16/24
7.5 28 15 30 15 28 15 26.5 18.5 28.5 NS80H-MA 50 LC1-D32 LRD-32 23/32
22 33 30 34.6 NS80H-MA 50 LC1-D40 LRD-33 55 30/40
11 39 18.5 37 22 40 22 39 NS80H-MA 50 LC1-D40 LRD-33 57 37/50
22 44 25 47 30 45 33 39 NS80H-MA 50 LC1-D50 LRD-33 57 37/50
15 52 30 51.5 NS80H-MA 50 LC1-D50 LRD-33 59 48/65
37 42 NS80H-MA 50 LC1-D65 LRD-33 57 37/50
18.5 64 30 59 30 55 37 64 37 55 NS80H-MA 80 LC1-D65 LRD-33 59 48/65
37 66 NS80H-MA 80 LC1-D65 LRD-33 61 55/70
45 49 NS80H-MA 80 LC1-D80 LRD-33 57 37/50
22 75 37 72 45 80 45 76 55 80 NS80H-MA 80 LC1-D80 LRD-33 63 63/80
55 60 NS80H-MA 80 LC1-D115 LR9-D53 67 60/100
75 80 LC1-F115 LR9-F53 63 48/80
(1) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 by LC2.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.