Ehc 500MW
Ehc 500MW
Ehc 500MW
07.03.2020
K.V.Prathapan
NTPL, Tuticorin
TURBINE CONTROL LOOPS
100%
+
+
hrSC
SC_O/P M
hrLC A M
I
LC_O/P X N M
1 I hr
hrPC N
PC_O/P 2
MHG_O/P ASO
SPEED CONTROLLER LOGICS:
Raise
Speed NR Speed NRTD hrSC
Reference Reference
Limiter Speed
Setter Controller
Lower
SGC Turb
Auto Synch.
Dn/dt optd
DCS OR NR (lower)
Back Panel P.B.
GCD if pact < stn.load
dN/dt LOGIC:
GCB Open OR
A
N
HPSV 1&2 Not closed D
dn /dt
Operated
SPEED REFERENCE (NR) LOGICS
Speed raise
Speed lower SR NR NRTD
(Tur.Trip) Track to (Nact – 130 rpm) setter
SR
Limiter
Track to Nact + 15 rpm
Nact -1
Nact
Nact -2
& MV3
Nact -3
Nrtd PDT
hrsc
Controller O/P
Nact
Gain = 24
5% droop
LOAD CONTROLLER
Load Reference :-
Raise Command :-
i) From DCS
ii) From Panel
iii) SGCT
Lower Command :-
i) From DCS
ii) From Panel
iii) SGCT
Both Raise and Lower commands are issued provided ‘CMC is not ON ‘
Push button
Raise
CRT >1
SGC Turb. &
1
PR PR
S
E PR
‘ CMC not ON’ Lower
L
PR LRL
INT.
PRTD
TSE Margins Time
Constant
Fast follow
Pact< Pstn
A
GCB ON N Fast follow .
D
LC error > 5%
Controller un-stable
LOAD REF TRACKING SIGNAL
LC input < - 2% A
Over freq Unloading Load ref Tracking signal.
N PRTD tracks PR.
in LC active
D
Pact. < 30 %
M +
ΣPR I Error
N
PRMAX
PAct.
_
SUM OF PR( ΣPR) LOGIC
i) PR = PRTD + PR△f + Pressure correction.
ii) P R△f = 0 MW if:
i) Freq. Influence is OFF
OR ii) CMC is not “ON”
OR iii) Turbine Follow Boiler (IP mode)
iii) PR△f is active provided above conditions are not there and Pact>PStn
iv) Pressure correction is active, if :-
a) Pact > PStn
AND b) LC is in action.
AND c) LP Mode is selected.
Load controller ‘ON’ & ‘OFF’
Load controller can be switched ‘ON’ or ‘OFF’ from CRT/P.B. only and only when
speed controller is active ,and speed Controller out put is more than load controller output.
***
ΣPR LOGIC
Pressure Correction
PRTD + ΣP R
+
PRΔ f
Pressure Correction Signal 1
0% 2 Pressure
Correction
SEL-2
Freq. Inf. OFF
CMC OFF OR
IP mode Selected
STOP REFERENCE LIMITER LOGICS:-
It is a PID Controller
Logics :-
i. During PC in action, the output follows the PC output + 2%.
ii. If LC is switched off, then the output is equal to – 10%.
iii. During LC not stable, the output will track SC output – 1.5 %.
PRESSURE CONTROLLER
Logics :-
LP Mode :- ( Limit Pressure Mode ).
+
Set Pressure + P
-
I
-10 Kg -1
+ R
0 Kg 2
IP Mode Sel 2
Limit between 50 to 120 %
LP Mode
A LP reached.
N Alarm
ΔP is +ve
D
CONTOLLER SELECTION LOGIC
The Logic:
Speed controller, load controller O/P are fed to a
MAX selector . The O/P of MAX and the inverted
speed controller O/P are fed to a MIN1 selector ,
whose O/P along with the pressure controller O/P
are fed to another MIN2 selector . The final output of
this MIN2 gate is fed as reference (hr) to the position
controller.
CONT. SELECTION
100% +A
D
SC_O/P +D
M
M
I
A
LC_O/P N
X M
1 hr
I
N
Position
2
reference
PC_O/P
TRACKING DEVICE LOGICS:
It is made ‘ON’ by :-
i) Manual command from DCS
ii) SGCT It is made ’OFF’ by:-
Manual command from DCS
SLD/HSG position fault.
EHC position F/B fault.
Collins transmitter 1&2 deviation > 5%.
SGCT
Turbine Trip.
EHTC fault.
Speed signal 2/3 fault.
EHTC FAULT:-
All tracking device ’OFF’ commands are treated as EHTC fault conditions.
THANK YOU