Nothing Special   »   [go: up one dir, main page]

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 28

SIPROTEC 5/

DIGSI 5 BASIC-Course
03 Hardware Overview
www.siemens.com/poweracademy Copyright © Siemens AG 2012. All rights reserved.
SIPROTEC 5: Modular Hardware Design

Content

 Overview: Look from the outside


 Types of IO-Modules

Copyright © Siemens AG 2012. All rights reserved.


 Rear view, Principle of terminal naming
 Typical Devices
 A closer look to the inside
 Summary

03 Hardware Overview
Version: D_02_Page 2 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Wath are new ?

Modular device concept, freely configurable


Delivered devices can be expanded with 1/6-moduls

Copyright © Siemens AG 2012. All rights reserved.


without problems
Customers can configure their individual device for
specific applications
Up to 40 analog input channels (U, I)

03 Hardware Overview
Version: D_02_Page 3 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Base Module with Expansion Modules

Copyright © Siemens AG 2012. All rights reserved.


03 Hardware Overview
Version: D_02_Page 4 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Mounting of an expansion module

Copyright © Siemens AG 2012. All rights reserved.


03 Hardware Overview
Version: D_02_Page 5 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Detailed view on module connections


 Robust and stable

connection
between parts

Copyright © Siemens AG 2012. All rights reserved.


03 Hardware Overview
Version: D_02_Page 6 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Different Types of Operator Panels for Base Module

Dual Color

Copyright © Siemens AG 2012. All rights reserved.


LEDs
(settable to
green or red)

No Display Small Display Large Display


03 Hardware Overview
Version: D_02_Page 7 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Operator Panels for expansion modules

Single

Copyright © Siemens AG 2012. All rights reserved.


Color
LEDs
(red)

Without LED With LED With LED and key switches


03 Hardware Overview
Version: D_02_Page 8 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Surface mounted device – front view

Copyright © Siemens AG 2012. All rights reserved.


03 Hardware Overview
Version: D_02_Page 9 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Operating Elements Base Module Expansion Module


of HMI
Description Field
for LEDs

16 LEDs (red)

Copyright © Siemens AG 2012. All rights reserved.


16 LEDs (green or Description Field
red, selectable) for LEDs

Context Sensitive Keys


LED Acknowledge
and Reset of Cursor Keys
latched
information

Numerical Keys Key Switch S5


and Function Keys „Remote/Local“
Key Switch S1
USB plug-in
„Interlocking Off / Normal“
Description Field
Control of Switching Elements
for Function Keys

03 Hardware Overview
Version: D_02_Page 10 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Change of Current Transformer

Copyright © Siemens AG 2012. All rights reserved.


03 Hardware Overview
Version: D_02_Page 11 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Current Transformer is inside of Current Terminal

Voltage terminal
(for voltage measurement, BI, BO)

Copyright © Siemens AG 2012. All rights reserved.


Current
transformer

Current terminal

03 Hardware Overview
Version: D_02_Page 12 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Change of modules

Copyright © Siemens AG 2012. All rights reserved.


03 Hardware Overview
Version: D_02_Page 13 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Types of IO-Boards

Properties of IO-Boards

14 different IO boards have been designed to meet the requirements for


the possible applications.
Elements to be combined on the different IO boards:

Copyright © Siemens AG 2012. All rights reserved.


 Binary Inputs (with and without common potentials)
 Relay: Relay Standard 9 ms (Make contact, normally open)
 Relay Standard (Change over contact)
 Relay Fast 6 ms (Make contact, normally open)
 Relay Fast (Change over contact)
 Power-Relay
 High-Speed Relay 0,2 ms (semi-conductor speed-up)
 Current Transducer Input (Protection or Measurement)
 Voltage Transducer Input
 Measurement transducer input (20mA)
 Plug-In-Modules (Communication, 20mA Input, Memory,…)

03 Hardware Overview
Version: D_02_Page 14 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Board Types (1)


PS201 IO201

Copyright © Siemens AG 2012. All rights reserved.


Life Contact

03 Hardware Overview
Version: D_02_Page 15 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Board Types (2)


IO202 IO203

Copyright © Siemens AG 2012. All rights reserved.


03 Hardware Overview
Version: D_02_Page 16 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Board Types (3)


IO205 IO206

Copyright © Siemens AG 2012. All rights reserved.


Variant of IO205
03 Hardware Overview
Version: D_02_Page 17 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Board Types (4)


IO207

Copyright © Siemens AG 2012. All rights reserved.


03 Hardware Overview
Version: D_02_Page 18 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Board Types (5)


IO208 IO209

Copyright © Siemens AG 2012. All rights reserved.


03 Hardware Overview
Version: D_02_Page 19 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Board Types (6)


IO214 CB202

Copyright © Siemens AG 2012. All rights reserved.


Variant of IO202
03 Hardware Overview
Version: D_02_Page 20 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Label: Position
and type of IO

Copyright © Siemens AG 2012. All rights reserved.


Battery

03 Hardware Overview
Version: D_02_Page 21 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Rear view, Principle of Terminal Naming

Copyright © Siemens AG 2012. All rights reserved.


03 Hardware Overview
Version: D_02_Page 22 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Example of Typical Devices (1/2)

 Basic protection relay for Base Module with IO202


directional measuring 4xI, 4xU, 11BI, 8BO,
1 Life Contact

Copyright © Siemens AG 2012. All rights reserved.


 Protection relay for two Base Module with
measuring points IO208 and Extension
Module with IO202
(1,5 circuit breaker method) 8xI, 8xU, 15BI, 19BO,

1 Life Contact

03 Hardware Overview
Version: D_02_Page 23 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Example of Typical Devices (2/2)

 Bay Controller for double

Copyright © Siemens AG 2012. All rights reserved.


bus feeder with large
number of IO signals

Base Module with


IO202 and Extension
Modules with IO202 and
3xIO207
4xI, 4xU, 67BI, 38BO,
1 Life Contact

03 Hardware Overview
Version: D_02_Page 24 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Look to the inside (1/2)


Highlights of Power Supply
PS201 IO20x IO20x
 Distributed Power Supply
1,5V 5V for high availability and high

Copyright © Siemens AG 2012. All rights reserved.


EMC resistance
 Thermal load is distributed
3,3V -5V
 All voltages are supervised
 detailed diagnostic
11V  Wide Range PS (24/48 V DC,
60-220V AC/DC)
24/48V range will not be
damaged if connected to
higher voltage

Local power bus 28V

03 Hardware Overview
Version: D_02_Page 25 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Look to the inside (2/2)


Highlights of A/D sampling
I
U

5 Ranges
 Cross-wiring of Current and
Current Clamp 8 pol.

I
U
5 Ranges A Voltage Groups to different
A/D Converters

Copyright © Siemens AG 2012. All rights reserved.


D
I
U 4 channel

 Fast error detection for


Sigma
5 Ranges
Delta 1

I
U

5 Ranges
A/D converters
EEPROM

 A/D converter 24 Bit


U
(SIPROTEC4: 22 Bit)
 better accuracy
U
Voltage Clamp 14 pol.

U
U A
D  Calibration factor on current
transformer terminal
4 channel
Sigma
U Delta 2
U

U
U

03 Hardware Overview
Version: D_02_Page 26 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Summary and Highlights (1/2)  Modular device concept, freely configurable


 Delivered devices can be expanded with 1/6-moduls
without problems
 Customers can configure their individual device for specific
applications
 Up to 40 analog input channels (U, I)

 Devices without Jumpers – no more opening

Copyright © Siemens AG 2012. All rights reserved.


of device
 1A/5A-rated current will be set electronically.
 Three thresholds of binary inputs (15V, 71V, 154V) can be
set individually using software

 Powerful signal processing


 Sampling rate up to 16 kHz (protection 1kHz)
 Maximum 40 analog channels (24 for protection)
 Prepared for PMU functionality

 Draw out of terminal blocks


 Simple exchange of current transformers
 Pre-Wiring is possible
 Change to sensitive ground fault CT input is possible after
ordering

 Service-friendly
 Opening of device not necessary (battery, modules,… can
be changed without opening)

03 Hardware Overview
Version: D_02_Page 27 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5: Modular Hardware Design

Summary and Highlights (2/2)  On-Site operation panel, visualization


 9 freely configurable function keys
 Option of small and large display for all devices
 Up to 16 multicolor LEDs + the option of 4*16 red LEDs

 IEC61508 Certification

Copyright © Siemens AG 2012. All rights reserved.


 Safety standard, certificate scheduled for step 2
 all necessary developments are available in step 1

 Memory module 8 GB (step 2)


 For long-time fault records
 For power quality data

 Identical Wiring for panel-mounted and


surface-mounted device
 Standardization saves time
 Standardization prevents from errors

03 Hardware Overview
Version: D_02_Page 28 Siemens Power Academy TD