HYDRANT
DRY BARREL
KEY FEATURES
Meet all applicable parts of ANSI/AWWA C502 standard.
250 PSIG working pressure, 1000 PSI test pressure as per UL246.
250 PSIG working pressure, 500 PSI test Pressure as per FM1510.
Secured by the stanless steell safety stem coupling, the hydrant prevents traffic
damage by pulling out if hit by a vehicle preventing damage to the main valve and stem.
Easily removable main valve from either the bonnet or ground line flange.
Field replaceable nozzles secured with external stainless steel lock screw.
{
SF-F-06 (1200) 1200 mm 4’ - 0” 183 kg. joint where mechanical
{
Note : Standard on flange
connection is available up
on request.
SF-F-06 (1350) 1300 mm 4’ - 6” 196 k g.
Requirement :
1.Make sure the smart and reliable of the control device when operation
2.All inspection should be according to the factory standard and relate inspection instruction.
3.Avoid the scratch after assembly the hydrant in order to keep good surface quality.
4.The drain water should be smooth when hydrants under the close status.
HYDRANT
DRY PILLAR
KEY FEATURES
LPCB Approved
Conforming to BS EN 14384: 2005, BS 1074-1, BS 1074-2 & BS 1074-6 Standards.
Shell material is of ductile iron.
Available with straight and 90 Deg Inlet connection.
Available with Different type of caps and out let landing valves.
Dry barrel design eliminates damage to the hydrant caused by freezing or corrosion of the upper part.
Automatic drain system drains the water in the upper part when the main valve is closed,
thus avoiding damage caused by freezing.
Externally sand blasted for smooth finish.
Hydrants are designed for high performance and easy to install, maintain and repair.
Break away design to prevent accidents to the hydrants, where only the upper part of the flange
would be broken upon impact, when broken, still able to maintain seal does not leak.
* Available with straight and 90Deg Horizantal inlet, with different dimension
Working Inlet/
Model Barrel Depth (A) Outlet Type
Pressure EN1092-2
DN100
100SFH1325-LPDI 800/1200/1445
with flange
Without break system
DN150
150SFH1080-LPDI 600/800/1200/1500/1700
with flange Two 2.5”BSP and one
16 Bar
DN100 4”BSP, coupling or valves
100SFH680-LPDIB 420/575/800*
with flange
With Break System
DN150
150SFH680-LPDIB 420/575/800*
with flange
Available in
4” and 6”
Available in
4” and 6”
Break Away Design to prevent accident to the hydrants where only the upper part of
the flange will be broken upon impact.
Designed as per AWWA C502, which applies for the wall thickness, loss head and hose
connection plugs.
SPECIFICATION
BURRIED
MODEL DIAMETER ATTACHMENTS
LENGTH
1 pc 4” Pumper
100SFH800-CI 800 mm 4” (100mm) Connection & 2 pcs of
2.5” Dia. Hose Outlet
1 pc 4” Pumper
100SFH1200-CI 1200 mm 4” (100mm) Connection & 2 pcs of
2.5” Dia. Hose Outlet
1 pc 4” Pumper
150SFH800-CI 800 mm 6” (150mm) Connection & 2 pcs of
2.5” Dia. Hose Outlet
1 pc 4” Pumper
150SFH1200-CI 1200 mm 6” (150mm) Connection & 2 pcs of
2.5” Dia. Hose Outlet
1 pc 4” Pumper
Connection & 2 pcs of
150SFH1200 1200 mm 6” (150mm) 2.5” Br ass Oblique
Landing V alv es with K ey
1 pc 4” Pumper
150SFH1200-CIV 1200 mm 6” (150mm) Connection & 2 pcs of
2.5” Dia. Hose Outlet
HYDRANT
WET BARREL
KEY FEATURES
Manufactured In accordance with AWWA C503 Standard. MODELS
UL Listed & FM Approved.
(1) 4.5" Pumper Nozzle, (2) 2.5" Hose Nozzles.
Nozzle Threads to NFPA 1963 Standard.
SFD-250-W H
Flange to ANSI B16.1 Class 125 (6").
Available with a 4 inch size Monitor Flange on top of the hydrant
Corrosion Protection
Interior and exterior is e-coated to a dry film thickness
of 0.6 mils minimum, then fusion bonded epoxy powder
coated ( FBE).
Working Pressure
250PSI for FM approval.
200PSI for UL/FM listed.
MATERIAL SPECIFICATION
Part Name Material ASTM Spec.
Body Ductile Iron A536 65-45-12
Pumper Nozzle Cap Cast Iron A126 Class B
Pumper Nozzle Bronze B62 C83600
Main Valve Rubber NBR
Main Valve Holder Stainless Steel AISI 304
Hose Nozzle Cap Cast Iron A126 Class B
Hose Nozzle Bronze B62 C83600
Stem Stainless Steel AISI 304
Stem Nut Bronze B62 C83600
Operating Nut Bronze B62 C83600
O-Ring Rubber NBR
Pumper Nozzle Gasket Rubber NBR
Hose Nozzle Gasket Rubber NBR
HYDRANT
WET BARREL
KEY FEATURES
The hydrant material is cast iron.
Two numbers of 2½" hydrant landing valves with cap and chain are provided with hydrants.
{
Wet fire hydrant is used in places where no
danger of Vehicle accidents or freezing
{
atmospheres. It is better to be used in malls,
shopping centers, colleges, hospitals, etc.
HYDRANT
CABINETS
SHC-800
Length Width Depth Leg Height
SHC-750 1500mm 800mm 250mm 100mm