Teh 1096 PDF
Teh 1096 PDF
Teh 1096 PDF
TEH-1096
NOTICE: The information contained in this book is based upon generally accepted engineering principles. However, it is the individual designer's responsibility to make certain that the final design conforms to all applicable federal, state and local codes.
Reprinted by permission from the ASHRAE Guide and Data Book 1967, Chapter 66 Figure 1.2 and Figure 1.3.
Price $25.00
PAGE 2
SECTION 1
DETERMINING BUILDING FLOW REQUIREMENTS HOW MUCH FLOW DOES MY BUILDING NEED?
System flow requirements are determined by the number of plumbing fixtures in the building. A plumbing fixture is defined as any device which requires domestic water. Washing machines, urinals, sinks and showers are examples of plumbing fixtures. Take a look at the flow calculation sheet in Figure 1.1 (page 4). Notice that each type of plumbing fixture has been assigned a fixture unit count in column A. This number reflects the typical GPM requirements of the respective fixture. Since these are estimates, it is always advisable to use actual fixture ratings when available from the manufacturer. You may occasionally run across a fixture or two that are not listed on our sheet. In this case, it will be up to your best judgment to estimate the maximum GPM requirements of these units. The first step in determining flow requirements is to count the total of each type of plumbing fixture. It is a good idea to also consider fixtures which may be added during future expansion. These totals should be recorded in column B. Then multiply columns A&B and record this value in the Total Fixture Unit Count column. After you have completed this for all fixtures, add up the totals and put this number in the space marked 'Total building fixture count'' This number will be used to calculate our demand GPM and to size the main pipe prior to the split into separate cold and hot water risers. Ignore columns C and D. They will be used to size individual hot and cold water piping in Chapter 3. Now we know what our building flow requirements are. Or do we? Experience and common sense tell us that it is nearly impossible for every fixture in a building to be in operation at the same time. Somehow, we must estimate a usage factor for our building. The usage factor is defined as the percentage of fixtures that will be in use at any given time.
PAGE 3
WC/Public - Flush Valve WC/Public - Flush Tank Pedestal Urinal/Public Stall - Wall Urinal/Public Stall - Wall Urinal/Private Lavatory/Public Bathtub/Public Shower Head/Public Service Sink/Office Kitchen Sink/Hotel, etc. WC/Private Flush Valve WC/Private Flush Tank Lavatory/Private Bathtub/Private Shower Head/Private Bathroom Group/Private Flush Valve Bathroom Group/Private Flush Tank Separate Shower/Private Kitchen Sink/Private Dishwasher/Private - Public Washing Machine/Private Washing Machine/Hospital Bidet/Private Ice Maker/Private - Public Lawn Hoses/Public Lawn Hoses/Commercial Equipment Fill Valves/Commercial OTHER FIXTURES OTHER FIXTURES OTHER FIXTURES OTHER FIXTURES
Total building fixture unit count Total building CW fixture units Total building HW fixture units *Used for building pipe sizing only
Source: ASPE Data Book, Chapter 3: Cold Water Systems (Nov. 1988)
PAGE 4
400
DEMAND G.P.M.
300
200
100
1 2
500
1000
1500
2000
2500
3000
FIXTURE UNITS
DEMAND G.P.M.
1 2
60 40 20
20
40
60
80
100
120
140
160
180
200
220
240
FIXTURE UNITS
The charts shown in Figures 1.2 and 1.3 (above) are used to determine the building's usage factor. If you look closely at both charts, you'll see that they are actually the same graph but on different scales. Curve #1 is used for buildings with flush valve toilets and curve #2 is used for those with flush tank toilets. Use Figure 1.2 for large buildings and Figure 1.3 for smaller buildings. Figure 1.4 (page 6) on the following page can be used for extremely large buildings or campus type applications. To determine the GPM requirements of the building, recall the total building fixture count from the Flow Calculation Sheet. Locate this value on the horizontal axis and trace upwards to the intersection with the appropriate curve. At the intersection, trace left to the vertical axis. The point at which you intersect the vertical axis is the GPM requirement of the building. With a little practice, you will find this procedure quick and accurate. The curves shown in Figures 1.2, 1.3 and 1.4 are based on National Bureau of Standards Report BMS79 by R.B. Hunter. Those in the know often refer to this simply as Hunter's curve. It is not the only way to determine GPM requirements but it is the most widely accepted and is utilized by the American Society of Plumbing Engineers (ASPE). Recently, there has been discussion of various new methods of determining building GPM requirements. Several of these methods look quite promising and are being studied by ASPE committees. It is very possible that Hunter's curve will be replaced or, at least, augmented by one or more of the new methods in the not too distant future. Nonetheless, at this time, R.B. Hunter's method remains as the most widely used and accepted procedure.
PAGE 5
30
25
GPM (Hundreds)
20
15
10
10
15
20
25
30
PAGE 6
SECTION 2
DETERMINING BUILDING PRESSURE REQUIREMENTS HOW MUCH PRESSURE DOES MY BUILDING NEED?
Now that we know our GPM requirements, it is time to calculate the pressure boost required to maintain flow and pressure at all fixtures. Keep in mind that water, like people, tends to follow the path of least resistance. Therefore, if we satisfy the fixture at the end of the path of greatest resistance, it seems reasonable that we will satisfy all other fixtures in our system. When calculating this resistance, or pressure drop, it is important to totalize piping pressure drop and the pressure drop of the far-end fixture. The path of greatest pressure drop could be a long piping run to a unit with a very small pressure drop. Conversely, it may be a very short piping run to a unit with a very high pressure drop. To calculate the pressure drop, we must take into account several factors including piping friction losses (including fittings), elevation of highest fixture and individual fixture pressure drop. While this can be a time consuming task, it is an important step in properly determining our final boost requirements. This publication includes several worksheets to assist you in maintaining records and performing the necessary calculations. Our first step will be to determine the pressure drop across the various fittings (tees, ells, etc) in each piping branch. The worksheet and chart shown in Figures 2.1 (page 9) and 2.2 (page 10) respectively, will be our tools for this job. Step one is to trace the piping from the proposed booster location to the fixture at the farthest end of the piping branch. We must record the quantity of each type of fitting in column A of Figure 2.1 worksheet. Note that you will need one work sheet for each pipe size and flow rate in the piping run. After recording this data refer to the chart shown in Figure 2.2. This chart converts each fitting to an equivalent length of straight pipe. Record the equivalent length in the appropriate spaces in column B of Figure 2.1. After entering all data, multiply column A by column B and record your answer in column C. Add the figures in column C and move on to the next step. It is now time to determine the total pressure drop of the piping run. For this, we will use the path pressure drop worksheet shown in Figure 2.3 (page 11). You will also need a tool to determine pressure drop per 100' of pipe based on various flow rates. Ideally, you should use a Bell & Gossett System SyzerTM Calculator (Now available on computer disc). If you do not have this helpful tool, you can refer to the hydraulic Institute data book. Record pipe size and flow rate in the first two columns. The actual length of straight pipe (less fittings) goes into column A. Record your total equivalent length of straight pipe (fittings only, from Figure 2.1) in column B. Remember that you will have a different value for each pipe size and flow rate. Now add columns A & B, record the sum in column C, Total Length of Pipe. Now refer to your System SyzerTM or Hydraulic Institute book to determine the pressure drop per 100 of pipe for each size and GPM. Record this value in column D. After you have completed this exercise for the entire piping run, multiply column C by column D and divide by 100. Enter this value in column D. Now multiply column C by column D and divide the total by 100. Record the answer in column E. This is the total pressure drop for a pipe run of specific length, size and flow rate. Add the values in column E and record your answer in the appropriate space.
PAGE 7
PAGE 8
PAGE 9
Coupling or Straight Run of Tee 0.3 0.6 0.8 0.9 1.2 1.5 2 2.5 3 4 5 6
/8
1 1 1 2 2 3 4 5 6
Equivalent Length of Valves and Fittings - Figure 2.2 EQUIVALENT LENGTH OF PIPE FOR VARIOUS VALVES (feet)*
Valve Size (Inches)
3
Gate Valve 0.2 0.4 0.5 0.6 0.8 1 1.3 1.6 2 2.7 3.3 4
Angle Valve 4 8 12 15 18 22 28 34 40 55 70 80
/8
1 1 1 2 2 3 4 5 6
EXAMPLE: A two inch, 45 standard elbow has a friction loss equal to four feet of straight two inch pipe. * Allowances based on non-recessed threaded fittings. Use one-half the allowances for recessed fittings or streamline solder fittings. Source: ASPE Data Book, Chapter 3: Cold Water Systems (Nov. 1988)
PAGE 10
Total Head Loss for Piping Run (Add column "E"):____________________ Elevation of Highest Texture in Relation to Booster Location:____________________ Total Pressure Requirement for Piping Run:____________________ Conversion from Feet to PSIG: /2.31 Pressure Drop of greatest Pressure Drop Fixture:____________________ Pressure Requirement in PSIG:____________________
* From Figure 2.1 (page 9) ** From B&G System Syzer or Hydraulic Institute Data Book
PAGE 11
PAGE 12
ft
+ +
ft ft
Gross Suction Pressure (A) - Negative Effects (B) = Net Minimum Suction (feet)/2.31= Net Minimum Suction (PSIG)
PAGE 13
Duty Point Calculation Worksheet - Figure 2.6 PRESSURE BOOSTER DUTY POINT CALCULATION
Required discharge pressure (from Figure 2.3)*: Minimum net suction pressure (from Figure 2.5): = Pressure required of booster system: PSIG PSIG PSI
* This number must be from the Figure 2.3 worksheet which has the highest total pressure requirement. Using a lower figure will result in an undersized booster and some very unhappy tenants on the upper floors of your building.
PAGE 14
SECTION 3
DOMESTIC WATER PIPE SIZING
The first step in sizing domestic water pipe is to determine the individual flow requirements of both hot and cold water. We will also need to recall the total system GPM as calculated in Section 1. Below are Figures 3.1 and 3.2 from Section 1. By calculating the fixture unit counts for hot and cold water, we can determine the GPM requirements. These figures will then be used to determine pipe size.
400
DEMAND G.P.M.
300
200
100
1 2
500
1000
1500
2000
2500
3000
FIXTURE UNITS
DEMAND G.P.M.
1 2
60 40 20
20
40
60
80
100
120
140
160
180
200
220
240
FIXTURE UNITS
Use curve 1 for cold water flow estimation when using flush valve toilets. Use curve 2 for hot water flow estimation and cold water flow estimation when using flush tank toilets. The flow requirements we establish from fixture unit counts is related to pipe size by pressure drop and flow velocity considerations. The relationship is categorized by the type of pipe being used. Our good friend R.B. Hunter from Section 1 broke piping into four different groups: smooth copper tube, fairly smooth galvanized, fairly rough galvanized and rough galvanized. Bell & Gusset has merged Hunter's data into the graphs shown in Figures 3.3, 3.4, 3.5, and 3.6. These graphs represent the correlation of fixture units to pipe size, pressure drop, velocity and demand flow rate. The graphs illustrate these relationships in smooth copper tubing, fairly smooth, fairly rough and rough galvanized pipe.
PAGE 15
PAGE 16
25
20
K L
15/sec.
15
3/8 3/4
10
1/2
10/sec.
1.5
.8 .7 .6
2/sec.
5 6 7 8 9 10 12 15 20 30 18 25 40 50 60 100 150 250 350 500 800 1,500 3,000 5,000 9,000 80 125 200 300 400 600 1,000 2,000 4,000 6,000 10,000
Copper Tubing: Size, Pressure Drop and Velocity vs. Fixture Units* - Figure 3.3
.5
HOT WATER FIXTURE UNITS AND/OR COLD WATER FIXTURE UNITS WITH FLUSH TANKS
4 5 6 7 8 9 10 15 20 30 40 50 60 70 80 100 200 300 400 500 600 800 1,000
1.5
25
20
1/2 3/4
15
3/8
11/4
10
1.5
.8 .7 .6
2/sec.
5 6 7 8 9 10 12 15 20 30 18 25 40 50 60 100 150 250 350 500 800 1,500 3,000 5,000 9,000 80 125 200 300 400 600 1,000 2,000 4,000 6,000 10,000
Fairly Smooth Pipe: Size, Pressure Drop and Velocity vs. Fixture Units* - Figure 3.4
.5
HOT WATER FIXTURE UNITS AND/OR COLD WATER FIXTURE UNITS WITH FLUSH TANKS
4 5 6 7 8 9 10 15 20 30 40 50 60 70 80 100 200 300 400 500 600 800 1,000
1.5
PAGE 17
PAGE 18
25
20
3/8 3/4
15
1/2
1 8/sec. 4
11/4 3
11/2 21/2
10/sec. 2
10
1.5
.8 .7 .6 5 6 7 8 9 10 12 15 20 30 18 25 40 50
Fairly Rough Pipe: Size, Pressure Drop and Velocity vs. Fixture Units* - Figure 3.5
.5
60 100 150 250 350 500 800 1,500 3,000 5,000 9,000 80 125 200 300 400 600 1,000 2,000 4,000 6,000 10,000
HOT WATER FIXTURE UNITS AND/OR COLD WATER FIXTURE UNITS WITH FLUSH TANKS
4 5 6 7 8 9 10 15 20 30 40 50 60 70 80 100 200 300 400 500 600 800 1,000
1.5
25
20
3/8
10/sec. 8/sec.
3/4
1/2
15
11/4 11/2
2 3
21/2
10
3/sec. 8 2/sec.
1.5
Rough Pipe: Size, Pressure Drop and Velocity vs. Fixture Units* - Figure 3.6
.8 .7 .6
1.5/sec.
5 6 7 8 9 10 12 15 20 30 18 25 40 50 60 100 150 250 350 500 800 1,500 3,000 5,000 9,000 80 125 200 300 400 600 1,000 2,000 4,000 6,000 10,000
.5
HOT WATER FIXTURE UNITS AND/OR COLD WATER FIXTURE UNITS WITH FLUSH TANKS
4 5 6 7 8 9 10 15 20 30 40 50 60 70 80 100 200 300 400 500 600 800 1,000
1.5
PAGE 19
PAGE 20
Rough Pipe - Figure 3.8 MAXIMUM FLOW DEMAND / FIXTURE COUNT @ 5 PSI / 100 FRICTION LOSS WITH ROUGH PIPE
No. Fixture Units (Flush Tank)* 0-1 1-4.5 4.5-11 11-20 20-35 35-120 120-275 275-520 520-1400 1400-3200 3200-6200 GPM Demand 0-1.5 1.5-4 4-8.5 8.5-15 15-23 23-46 46-85 85-130 130-260 260-450 450-720 Rough Pipe Size (Inches) Based on 5 PSI / 100' Pressure Loss 0.5 .075 1 1.25 1.5 2 2.5 3 4 5 6 No. Fixture Units (Flush Valve)** *** *** *** *** *** 10-42 42-170 170-400 400-1400 1400-3200 3200-6200
* Always applies to hot water distribution ** Should be confirmed by flush valve manufacturer *** Consult flush valve manufacturer.
PAGE 21
TOTAL FIXTURE UNIT 7.5 15.0 22.5 30.0 37.5 45.0 52.5 60.0 67.5 75.0
TOTAL FIXTURE UNIT 13.5 27.0 40.5 54.0 67.5 81.0 94.5 108.0 121.5 135.0
6.75 Fixture Unit/APT. 13.5 Fixture Unit/ FLOOR
PAGE 22
225 F.U. = 2
150 F.U. = 2
75 F.U. = 2
135 F.U.
135 F.U.
135 F.U.
135 F.U.
135 F.U.
675 F.U. = 3
Figure 3.10
135 F.U. = 3
PAGE 23
SECTION 4
PRESSURE BOOSTER SELECTION PROCEDURE
SYSTEM SPLITS Every building has what is commonly referred to as a load profile. This profile is a representation of building demand throughout the course of a typical day. Remember, very few buildings have full demand 24 hours per day. The exceptions to this rule are process systems which could have steady demand around the clock. A sample load profile is shown in Figure 4.1.
200
150
100
50
12:00 AM
2:24 AM
4:48 AM
7:12 AM
9:36 AM
12:00 PM
2:24 PM
4:48 PM
7:12 PM
9:36 PM
12:00 AM
The chart shows that demand varies significantly during the course of a day. This varying profile should lead us to select a system with 2 or more pumps to share demand. This will allow us to use less horsepower when demand is low enough to be satisfied by one pump. Lets assume that in the above example, the peak demand is 225 GPM. Upon closer inspection, we see that for a significant percentage of the day, we are below 50% of design capacity. Therefore, it is to our advantage to design a booster system with a small lead pump to handle low demand periods and larger lag pump(s) to handle high demand. The small lead, or jockey pump will use considerably less energy than a pump sized for 50% capacity and to reduce our utility bill, we should use as little horsepower as possible to satisfy demand. Had we simply gone with a 50% pump split, the horsepower requirements of the lead pump would equal that of the lag and for a good portion of the day we would be wasting energy. A one pump system may have a lower initial cost but will operate well below its design point for the vast majority of the day. Another disadvantage of a simplex type system is a lack of redundancy. The following factors should be considered when determining system splits: 1. Reduce operating costs by minimizing total horsepower required to meet operating point below full demand. Study the buildings load profile and select a jockey pump that covers the greatest percentage of load at the lowest possible horsepower. 2. Account for planned future expansions and additions. 3. Provide the appropriate amount of back-up capability based on the criticality of the application.
PAGE 24
2 21/2
21/2 3 3 4
4 6
6 8
10
12 14 16 24
10 12 14 16
30 20
10 8 6 4 3 2
PAGE 25
__________ PSIG
x 2.31= _______ FT
(B)
(C) (D)
REQUIRED PUMP TOTAL DYNAMIC HEAD = A + B + C - D _______ FT + ______FT + ______ FT - ______ FT = ______ FT NOTE: If designing a multiple pump system with unequal flow rates per pump, this calculation must be performed for each pump / PRV combination. NET POSITIVE SUCTION HEAD REQUIREMENT In order to pump water, a centrifugal pump must have a positive suction pressure at the eye of the impeller. This pressure is called net positive suction head required or NPSHR. Every centrifugal pump has a NPSHR curve associated with it. NPSHR is measured in pounds per square Inch absolute (PSIA) in order to account for effects of atmospheric pressure. PIPE SIZING FOR PRESSURE BOOSTER PACKAGES It is usually acceptable to size pressure booster suction and discharge headers for a maximum velocity of 10 feet per second. Since the booster is typically located in an equipment room, velocity noise is usually not a major concern. If the booster is located adjacent to occupied spaces, a maximum velocity of 8 feet per second would be a better choice. CONSTANT SPEED PRESSURE BOOSTER DESIGN CONSIDERATIONS The construction of the package should allow for servicing of the pumps and PRVs while the unit is in operation. To achieve this, service valves must be installed around each pump PRV set. This allows a set to be isolated while the other pumps continue to operate. A high temperature relief valve should be installed to prevent the possibility of excessive heating of water during low or no flow conditions. Use one valve per pump or pipe a single valve in a manner which allows it to provide relief for all pumps. The control panel should provide a means of staging and destaging pumps based on system demand. There are several methods of staging pumps in constant speed booster systems. When pumps are staged based on flow rate, this is typically done with a combination of flow switches. As GPM increases, each switch engages its respective pump in sequence. As demand decreases, the pumps are destaged in the same manner. If a microprocessor based controller is used, it is possible to stage pumps based on an analog input from a flow sensor.
PAGE 26
POWER
CURRENT
MOTOR LOAD
MOTOR LOAD
As you can see, the Power vs. Load curve depicts a much more linear relationship than does the Current vs. Load curve. The linearity of the relationship between Power and Load allows the controller to stage and restage pumps with greater accuracy and improved efficiency at low load conditions. TYPICAL PRESSURE BOOSTER OPTIONS ALTERNATION: Pump alternation on multiple pump systems can be either manual or automatic. The intention on alternating pumps is to equalize wear on the equipment. If you have a jockey pump on your package, only the lag pumps should be alternated. The purpose of a jockey pump is to minimize energy consumption. If a lag pump is alternated into the lead pump position, we are defeating the purpose of a jockey pump. AUDIO - ALARM: This option will provide audible as well as visual indication of an alarm condition. This is ideal for critical operations where downtime is a premium. This alarm may also include a dry contact for remote indication of the alarm. AQUASTAT: This feature works as a back up to the thermal relief system. When water temperature exceeds a preset point, the unit stops all pumps. Reset should be automatic upon return to an acceptable operating temperature. LOW SUCTION PRESSURE CUT OUT: AII pressure boosters should be equipped with a means of shutting the pumps down in the event of a loss of supply pressure to the booster. This is typically activated by a pressure sensor (switch or transducer) located in the suction header. Reset should be automatic upon a return to acceptable supply pressure.
PAGE 27
SECTION 5
HYDROPNEUMATIC TANK SIZING
Hydropneumatic tanks are primarily used in a domestic water system for draw down purposes when the pressure booster system is off on no-flow shutdown (NFSD). The NFSD circuitry turns the lead pump off when there is no demand on the system. While the system is off in this condition, the hydropneumatic tank will satisfy small demands on the system. Without the tank, the booster would restart upon the slightest call for flow such as a single toilet being flushed or even a minute leak in the piping system. Hydropneumatic tank sizing is dependent on two factors: 1. Length of time you wish the pumps to remain off in a no-flow situation. 2. The tank location in relation to the pressure booster. Any given building will have a low demand rate for various times of the day. Leaky faucets or someone getting a glass of water in the middle of the night are factors which prevent this low demand period from being a no demand period. It is not often that a system will have periods of zero demand. The estimated low demand GPM should be multiplied by the minimum number of minutes you want your booster to stay off on no-flow shutdown to determine draw down volume of the tank. Due to the time delays built into most no-flow shutdown circuits, three minutes is generally the minimum off time considered. Typically, the maximum amount of time is 30 minutes. The longer the unit is off the more energy we save but the larger our tank must be. Therefore, a compromise must be made between tank size and minimum shutdown time.
PAGE 28
TANK
TO FIXTURES
PUMP PRV
The tank can also be located at the discharge of the pressure booster package as shown in Figure 5.2 (on page 30). In most buildings, it is considerably easier to install a tank in the equipment room than on an upper floor which makes this location the most common. If locating a tank at the bottom of the system, it is important to make sure that the static height of the building plus the discharge pressure of the package does not exceed the maximum allowable working pressure of the tank.
PAGE 29
TO FIXTURES
For an even higher final pressure, the tank can be connected prior to the lead pump PRV (Figure 5.3). This is a higher pressure point because the pump TDH and suction pressure have not yet been reduced by the PRV. This again helps us to reduce the size of the tank. If this approach is taken the tank must be connected to the discharge of the lead pump at all times. If your booster is equipped with pump alternation and the tank's pump is moved to the 2nd or 3rd in sequence, the tank will not charge. An uncharged tank cannot provide any draw down volume so it will be of no use during a low flow shut down condition. Since this location will see higher pressures than either of the first two examples, it is particularly important to make sure you don't exceed the maximum working pressure of the tank.
TO FIXTURES
TANK
PUMP PRV
PAGE 30
APARTMENT BUILDING
UNIVERSITY DORMITORIES
COMMERCIAL
HOSPITAL
SCHOOL
8 15 23 30 38 45 53 60 68 75
11 22 33 44 55 66 77 88 99 110
Use this table for estimating purposes only. Final determination of the acceptance volume is the responsibility of the design engineer. Remember to consult local codes! The thirty minute shut down time can be adjusted for different times by using the following formula: ACCEPTANCE VOLUME (from Figure 5.4) X DESIRED SHUTDOWN TIME / 30 MINUTES = ADJUSTED ACCEPTANCE VOLUME Once we have determined the required acceptance volume, we can calculate the tank size based on draw down capabilities. Consult your hydropneumatic tank supplier for information on draw down volume of their tanks. A typical data sheet is shown in Figure 5.6 on page 36. Since different manufacturers tanks have different draw down capabilities, it is imperative that you use the data supplied by the manufacturer whose tank you plan to use. The value in the intersection of initial pressure and final pressure is your draw down coefficient. Divide your acceptance volume by this coefficient to obtain the total tank volume.
PRISON
PAGE 31
HOTEL
PAGE 33
160
120
80
Head
40
CAPACITY, US GPM
4. Using Figure 5.6, we can determine that our draw down coefficient is .335 5. Divide the acceptance volume by the draw down coefficient to obtain the total tank volume that will give us 75 GPM during low flow shutdown. 37.5 GPM / .335 = 1 12 Therefore, we need a minimum tank volume of 112 gallons to meet our shutdown requirements. HYDROPNEUMATIC TANK CHARGING Most hydropneumatic tanks ship from the manufacturer pre-charged to a pressure that is usually well below the actual charging requirement for the system. In other words, the air volume in the tank is too small once the tank is installed in the system. Pumps short cycle, draw down is limited, and in some cases, the situation is so severe that the tank could be removed from the system and nobody would know the difference. So, if were going to spend the money for a tank, let's make sure it works by charging it correctly. The correct tank pre-charge pressure depends upon the following factors: 1) Minimum allowable system pressure 2) Tank elevation relative to the pressure booster package 3) Tank connection point in the system We will define these variables as follows for our pre-charge calculation: Let D = Desired system pressure in PSIG (PRV setting) Let M = Maximum allowable pressure depression below PRV setting (D) Let H = Tank elevation above pressure booster in PSIG (PSIG = Feet / 2.31) Let P = Tank pre-charge pressure (tank empty) in PSIG We will also estimate a 1 PSIG pressure drop across the PRV at very low flow rates encountered during a low demand period.
PAGE 34
PAGE 35
F I N A L T A N K P R E S S U R E P S I
65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200
*NOTE: initial tank pressure is equal to the minimum allowable pressure of the system (at the point of the tank) where the booster system will come back on line. Final tank pressure is equal to the maximum system discharge pressure (at the point of the tank) or, the pressure reducing valve setting if the tank is mounted on the booster system. Actual usable gallons may vary 10%.
PAGE 36
SECTION 6
DOES VARIABLE SPEED PUMPING MAKE CENTS?
The technological advancement in recent years of AC variable frequency drives has brought the marketplace new products that are both more reliable and lower in cost than ever before. We are witnessing much wider use of variable frequency drives on fan and pump applications in the HVAC market because of their ability to greatly reduce annual energy costs. It is not uncommon to see simple paybacks measured in months for HVAC equipment that is being retrofitted with the necessary controls for variable speed operation: pump logic controller, sensors, and variable frequency drives (refer to Figure 6.1). As the cost of electronic equipment continues to decline, more opportunities to apply cost saving variable speed pumping become worthwhile. This technology is now being applied in the plumbing market on domestic water pressure booster systems. Domestic water pressure boosting packages are an attractive application because these systems are significant energy consumers, have widely varying load demands, and are typically oversized.
Domestic water pressure boosting system with adjustable frequency pump drives - Figure 6.1
Maximum Total System Flow 400 GPM Required Discharge Pressure 74 PSIG 30 PSIG Residual Pressure 24 PSIG Static Pressure 20 PSIG Friction Head Loss Minimum Suction Pressure = 20 PSIG Required Boost = 54 PSIG
30 PSIG Adjustable frequency drive Adjustable frequency drive Remote Pressure Sensor
Pump controller
HW Water Heater
CW
HW Water Heater
CW
HW
CW
City Main
Pump 1
Pump 2
NOTE: Two sensors shown for example purposes only. Typically only one sensor is required. See Variable Head Losses (page 39) for details.
PAGE 37
166
90% speed
76
100
200
300
400
500
600
Capacity (GPM)
When the pressure sensor is installed locally (refer to Figure 6.1), nearly the entire variable head loss must be maintained by the variable speed boosting package at all times to ensure there will always be enough pressure at the top of the system if full flow demand ever occurs. The slight rise shown on the control curve in Figure 6.2 is due to the variable head loss in the valving and fittings between the pump outlet and the pressure sensor located downstream in the discharge manifold.
PAGE 39
166
136 125 ft (54 PSIG) Pressure Boost 125 ft (54 PSIG) Minimum Control Head
46
100
200
300
400
500
600
Capacity (GPM)
PAGE 40
It becomes obvious, looking at the control curves, that a piping system that has a higher ratio of variable head losses to fixed head elements will be a better candidate for variable speed controls than a system with a lower ratio. The type of building and application play an important role in determining the shape of the control curve and load profile of the system. A tall residential apartment building with its large static height requirement will have a very different fixed head/variable head ratio than a large sprawling one-story factory. PRESSURE REDUCING VALVE LOSSES A pressure reducing valve (PRV) is used on constant speed domestic water pressure booster systems as a means of pressure control by modulating open and closed to maintain a constant discharge pressure. Some of the benefits of the PRV are that it: 1. Maintains steady system pressure regardless of changes in demand or suction pressure. 2. Helps prevent system over-pressurization. 3. Allows the use of dissimilar pumps in parallel by preventing a higher head pump from closing the check valve of a pump with lower head. These major benefits can be summarized by the fact that the PRV absorbs the pump's excess energy. The drawback to the PRV is that the absorbed energy is wasted energy. Variable speed systems achieve proper pressure by changing the pump's speed and therefore do not waste the excess energy. Figure 6.4 examines the operating point of our example system at a reduced flow rate. On a constant speed system, variable flow is achieved by riding back and forth on the pump curve. At lower flow rates, the PRV chokes down to absorb the excess head produced by the pump as its head rises to shut-off.
PAGE 41
136 125 ft (54 PSIG) Pressure Boost 125 ft (54 PSIG) Minimum Control Head
106
76
46
100
200
300
400
500
600
Capacity (GPM)
Variable speed systems, however, track the control curve. Lower head and flow rates are the result of slowing down the pump. The energy saved by a variable speed pump for this one flow rate is calculated below: Constant Speed Brake Horsepower = (Flow * GPM ) / (3960 * Pump Eff) = (100 * 143) / (3960 * .72) = 5.0 BHP Constant Speed kW = (BHP / Motor Eff / 1.34 = (5.0 HP / .852) / 1.34 = 4.4 kW Variable Speed Brake Horsepower = (100 * 81.7 / 3960 * .57 = 3.6 BHP Variable Speed kW = (BHP / Motor & Drive Eff / 1 .34 = (3.6 HP / .83) / 1.34 = 3.2 kW Net Energy Savings = (4.4 - 3.2) = 1.2 kW (approximately 27%) As stated above, one of the reasons for utilizing pressure reducing valves on each constant speed pump is to protect against over-pressurizing the domestic water booster system. If a constant speed pump without a PRV on its discharge is turned on when there is little flow demand in the system and the actual suction pressure is much greater than design, the resulting pressure from that pump could possibly over-pressurize the system and create leaks and/or damage plumbing fixtures. This same scenario could occur on a variable speed control system that is supplied with an across-the-line VFD bypass. If an across-the-line VFD bypass is desired because of the critical nature of the domestic water system and greater redundancy is required, then each pump with this capability should also be supplied with a pressure reducing valve on its discharge or some other means of pressure control. This will protect the domestic water system against over-pressurization in the event the pump is needed to run through the constant speed VFD bypass.
PAGE 42
System control curve for remote sensor location with increased suction pressure - Figure 6.5
Set point = 30 PSIG/69 ft; minimum control head = 54 psiW125 ft.
Pump Total Developed Head and Suction Pressure (ft)
231 Constant Speed Operating Point
201
171
{
400
90 ft (39 PSIG) Pressure Boost 125 ft (54 PSIG) Minimum Control Head
141
59% speed
20 0
300
500
600
Capacity (GPM)
Note that when the suction pressure increases above the stated minimum, the control curve is lowered by an equal amount. Put simply, the pumps do not have to produce as much pressure. The revised energy savings for an increase in suction pressure looks like this: Variable Span, Brake Horsepower = (100 * 47.1) / 3960 * .57 = 2.1 HP Variable Speed kW = (BHP / Motor & Drive Eff / 1.34 = (2.1 HP / .77) / 1 .34 = 2.0 kW Net Energy Savings = (4.4 -2.0) = 2.4 kW (approximately 55%)
PAGE 43
Retrofitting Variable Speed controls to a Constant Speed Booster Converting a constant speed pressure booster to variable speed operation is a fairly straightforward task. There are a few factors that need to be addressed. If your system consists of identical pumps without pressure reducing valves, the conversion is quite simple. Simply remove the existing starter panel and install the variable frequency drives, controller and remote sensor. Remember the advantages of a remote sensor discussed a few pages ago. If you have pressure reducing valves on your system, they must either be removed, modified or set above the normal required discharge of the pump at design conditions. The purpose of a PRV on a constant speed system is to limit the discharge pressure of the pump when a suction pressure surge occurs or when the pump rides back on its curve. This action will cause the PRV to fight the variable speed controller. Since the PRV regulates the discharge pressure, it is difficult for the system to exceed set point. If we do not exceed the set point, the controller sees no reason to slow the AFD down or destage pumps. Therefore, if the PRV situation is not properly addressed, variable speed operation becomes a defacto constant speed system. Fortunately, it is relatively simple to avoid the PRV dilemma. The most straightforward option is to replace the PRV with a check valve. If this is not feasible, the PRVs pilot valve can be removed. This essentially converts the PRV to a check valve only. The drawback to this shortcut is that the PRV is going to have a greater pressure drop than a typical check valve of the same size. This additional pressure drop can be significant and causes our system to use additional horsepower to overcome the pressure drop. The decision to replace or modify the PRV must be approached on a case by case basis. Weigh the cost of replacing the valve against the additional energy cost that will be incurred by pumping through the modified PRV. Variable Speed Systems With Pressure Reducing Valves There is a situation where it is advisable to use PRVs in variable speed applications. If you plan to have a VFD bypass on your system, consider a means to avoid over-pressurizing the system when operating in bypass. Remember, in the bypass mode, the pump is running at full speed regardless of the process variable vs. set-point relationship. Set point is defined as the pressure we want to maintain at the sensor location and process variable is what the pressure actually is at that point. The controller's primary function is to control pump speed and staging sequence to keep process variable equal to set-point. If the dead head pressure of the pump plus maximum suction pressure is sufficient to generate a system pressure high enough to damage any fixtures, you need a pressure reducing valve.
PAGE 44
PAGE 45
PAGE 46
PAGE 47
Xylem, Inc. 8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries. 2011 Xylem, Inc. TEH-1096 Rev. 1 December 2011