Schneider PLC Module Bmxdra1605 PDF
Schneider PLC Module Bmxdra1605 PDF
Schneider PLC Module Bmxdra1605 PDF
Main
Range of product Modicon M340 automation platform
Product or component Discrete output module
type
Electrical connection 20-way connector
Discrete output number 16 conforming to EN/IEC 61131-2
Discrete output type Relay
Discrete output voltage 240 V 200...264 V AC
24 V 19...30 V DC
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Complementary
[Ith] conventional free air thermal current 2A
Insulation resistance > 10 MOhm 500 V DC
Power dissipation in W <= 3 W
Response time on output <= 12 ms deactivation
<= 10 ms activation
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
Typical current consumption 100 mA 3.3 V DC
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
MTBF reliability 2463296 H
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Protection type External short-circuit protection
External overload protection
DC inductive overvoltage protection
AC inductive overvoltage protection
Output overload protection Use 1 fast blow fuse per channel or group of channel
Output overvoltage protection Use ZNO surge limiter on each output AC
Use RC circuit on each output AC
Use discharge diode on each output DC
Output short-circuit protection Use 1 fast blow fuse per channel or group of channel
Minimum switching current 1 mA 5 V DC
Electrical durability 300000 cycles DC-13 7.2 W 24 V
300000 cycles DC-13 3 W 100 V
300000 cycles AC-15 60 VA 200 V 0.35
300000 cycles AC-15 36 VA 240 V 0.35
300000 cycles AC-14 80 VA 200 V 0.7
300000 cycles AC-14 72 VA 240 V 0.7
100000 cycles DC-13 24 W 24 V
100000 cycles DC-13 10 W 100 V
100000 cycles AC-15 200 VA 200 V 0.35
100000 cycles AC-15 120 VA 240 V 0.35
100000 cycles AC-14 300 VA 200 V 0.7
100000 cycles AC-14 240 VA 240 V 0.7
Status LED 1 LED red I/O
1 LED red ERR
1 LED per channel green channel diagnostic
1 LED green RUN
Product weight 0.15 kg
Mar 9, 2013
1
Environment
IP degree of protection IP20
Standards CSA 22-2 No 142
IEC 1131-2
IEC 664
NF C 63-850
UL 508
UL 746C
Dielectric strength 2000 V AC at 50/60 Hz 1 min
Ambient air temperature for operation 0...60 C
Relative humidity 10...95 % without condensation
Protective treatment TC
2
Product data sheet BMXDRA1605
Dimensions Drawings
Dimensions
3
Product data sheet BMXDRA1605
Connections and Schema
Module Connection
power24VDC or 24...240VAC
supply
fuse 1 fast blow fuse of 12A for each 8-channel group