Application
The Model AFS-222 is a general pur-
pose proving switch designed for
HVAC and Energy Management ap-
plications. It may be used to sense
positive, negative, or differential air
pressure.
Bulletin AFS222.05 1
(Figure 3) TWO POSITIVE SAMPLES: Con- Specifications
nect the higher positive sample to in-
let H. Connect the lower positive
Model AFS-222 Air Flow Switch
sample to inlet L.
Mounting Position: Mount with the
ONE POSITIVE AND ONE NEGA-
diaphragm in any vertical plane.
TIVE SAMPLE: Connect the posi-
Set Point Range: 0.05 0.02" w.c. to
tive sample to inlet H. Connect the
12.0"w.c.
negative sample to inlet L.
Field Adjustable Operate Range:
0.07"w.c. to 12.0" w.c.
Electrical Connections(see Field Adjustable Release Range:
Figure 3) 0.04"w.c. to 11.2" w.c.
Approximate Switching Differential:
(Figure 4) Before pressure is applied to the dia- Progressive, increasing from 0.02 0.01
phragm, the switch contacts will be "w.c. at minimum set point to approxi-
in the normally closed (NC) posi- mately 0.8 " w.c. at maximum set point.
tion.The snap switch has screw top Measured Media: Air, or combustion
terminals with cup washers. Wire by-products that will not degrade silicon.
alarm and control applications as Maximum Pressure: psi
shown in Figure 4. (0.03 bar)
Operating Temperature Range:
-40F to 180F (-40 to 82C)
Field Adjustment
Life: 100,000 cycles minimum at 1/2 psi
The adjustment range of an AFS-222 maximum pressure each cycle and at
Air Switch is 0.05 .02" w.c. to 12.0" maximum rated electrical load.
w.c.. To adjust the set point, t urn the Electrical Rating:
POSITIVE PRESSURE ONLY: adjusting screw counterclockwise un- 300 VA pilot duty at 115 to 277 VAC,
Connect the sample line to inlet H; til motion has stopped. Next, turn the 15 amps noninductive to 277 VAC,
inlet L remains open to the atmo- adjusting screw 4 complete turns in 60 Hz.
sphere. a clockwise direction to engage the Contact Arrangement: SPDT
spring. From this point, the next ten Electrical Connections: Screw-type
NEGATIVE PRESSURE ONLY: terminals with cup washers.
turns will be used for the actual cali-
Connect the sample line to inlet L; Conduit Opening: 7/8" diameter
bration. Each full turn represents
inlet H remains open to the atmo- opening accepts " conduit.
approximately 1.2" w.c.
sphere. Sample Line Connectors: Male,
Please note: To properly cali- externally threaded 7/16" 24 UNS 2A
TWO NEGATIVE SAMPLES:
brate an air switch, a digital manom- thread, complete with nuts and self-
Connect the higher negative sample
eter or other measuring device should aligning ferrules.
to inlet L. Connect the lower nega-
be used to confirm the actual set Sample Line Connections: Connec-
tive sample to inlet H.
point. tors will accept " OD rigid or semi-rigid
tubing.
Approval: UL, FM, CSA
Shipping Weight: 1.2 lbs.
Accessories
Location of Sample Lines for Typical Applications P/N 18311 Slip-on " OD Tubing Adapter,
suitable for slipping on flexible plastic
tubing. Sample line probes. Orifice plugs
(pulsation dampers).
Bulletin AFS222.05
Cleveland Controls Model
Division of UniControl Inc.
AFS262
Air Pressure Sensing Switch with Adjustable Set Point Range
Application
The Model AFS-262 is a general pur-
pose proving switch designed for
HVAC and Energy Management ap-
plications. It may be used to sense
positive, negative, or differential air
pressure.
Bulletin AFS262.05 1
(Figure 3) TWO POSITIVE SAMPLES: Con- Specifications
nect the higher positive sample to in-
let H. Connect the lower positive
sample to inlet L. Model AFS-262 Air Flow Switch
ONE POSITIVE AND ONE NEGA- Mounting Position: Mount with the
TIVE SAMPLE: Connect the posi- diaphragm in any vertical plane.
tive sample to inlet H. Connect the Set Point Range: 0.05 0.02" w.c. to
negative sample to inlet L. 2.0"w.c.
Field Adjustable Operate Range:
0.07"w.c. to 2.0" w.c.
Electrical Connections(see Field Adjustable Release Range:
Figure 3) 0.04"w.c. to 1.9" w.c.
(Figure 4) Approximate Switching Differential:
Before pressure is applied to the dia- Progressive, increasing from 0.02 0.01
phragm, the switch contacts will be "w.c. at minimum set point to approxi-
in the normally closed (NC) posi- mately 0.1 " w.c. at maximum set point.
tion.The snap switch has screw top Measured Media: Air, or combustion
terminals with cup washers. Wire by-products that will not degrade
alarm and control applications as silicone.
shown in Figure 4. Maximum Pressure:
psi (0.03 bar)
Field Adjustment Operating Temperature Range:
-40F to 180F (-40 to 82C)
The adjustment range of an AFS-262 Life: 100,000 cycles minimum at 1/2 psi
Air Switch is 0.05 .02" w.c. to 2.0" maximum pressure each cycle and at
w.c.. To adjust the set point, t urn the maximum rated electrical load.
POSITIVE PRESSURE ONLY: adjusting screw counterclockwise un- Electrical Rating:
Connect the sample line to inlet H; til motion has stopped. Next, turn the 300 VA pilot duty at 115 to 277 VAC,
inlet L remains open to the atmo- adjusting screw 4 complete turns in 15 amps noninductive to 277 VAC,
sphere. a clockwise direction to engage the 60 Hz.
spring. From this point, the next ten Contact Arrangement: SPDT
NEGATIVE PRESSURE ONLY:
turns will be used for the actual cali- Electrical Connections: Screw-type
Connect the sample line to inlet L;
bration. Each full turn represents terminals with cup washers.
inlet H remains open to the atmo- Conduit Opening: 7/8" diameter
approximately 0.2" w.c.
sphere. opening accepts " conduit.
Please note: To properly cali- Sample Line Connectors: Male,
TWO NEGATIVE SAMPLES:
brate an air switch, a digital manom- externally threaded 7/16" 24 UNS 2A
Connect the higher negative sample
eter or other measuring device should thread, complete with nuts and self-
to inlet L. Connect the lower nega-
be used to confirm the actual set aligning ferrules.
tive sample to inlet H.
point. Sample Line Connections: Connec-
tors will accept " OD rigid or semi-rigid
tubing.
Approval: UL, FM, CSA, CE
Shipping Weight: 1.2 lbs.
Accessories
Location of Sample Lines for Typical Applications P/N 18311 Slip-on " OD Tubing Adapter,
suitable for slipping on flexible plastic
tubing. Sample line probes. Orifice plugs
(pulsation dampers).
Bulletin AFS262.05 2
Cleveland Controls Model
Division of UniControl Inc.
AFS460
ADJUSTABLE SET POINT AIR PRESSURE SENSING SWITCH WITH MANUAL RESET
APPLICATION
The Model AFS-460 is a general purpose
proving switch designed to require
manual operator reset following actuation.
It can be used to sense positive, nega-
tive, or differential air pressure in HVAC
and Energy Management applications
which require operator interface.
General Description & Operation
The plated housing contains a diaphragm,
a calibration spring and a snap-acting
SPSTNC switch with manual reset but-
ton.
The sample connections located on each
side of the diaphragm accept 0.25" OD
metallic tubing via the integral compres-
sion ferrule and nut.
An enclosure cover protects the operator
from accidental contact with the live
switch terminal screws and the set point
adjusting screw. The enclosure cover ac-
cepts a 0.5" conduit connection.
AIR SAMPLING CONNECTION
MOUNTING (SEE FIGURE 1)
(SEE FIGURE 2)
Select a mounting location which is free The AFS-460 is designed to accept firm- POSITIVE PRESSURE ONLY: Connect
from vibration. The AFS-460 must be wall sample lines of " OD tubing by the sample line to inlet H; inlet L remains
mounted with the diaphragm in any verti- means of ferrule and nut compression open to the atmosphere.
cal plane in order to obtain the lowest connections. An optional " adapter, suit- NEGATIVE PRESSURE ONLY: Connect
specified operating set point. Avoid able for slip-on flexible tubing is available: the sample line to inlet L; inlet H remains
mounting with the sample line connec- order part number 18311. For sample open to the atmosphere.
tions in the "up" position. Surface mount lines of up to 10 feet, " OD tubing is ac-
TWO NEGATIVE SAMPLES: Connect
via the two 3/16" diameter holes in the ceptable. For lines up to 20 feet, use "
the higher negative sample to inlet L. Con-
integral mounting bracket. The mounting ID tubing.
nect the lower negative sample to inlet
holes are 37/8" apart. For lines up to 60 feet, use " ID tubing. H.
(Figure 1) Locate the sampling probe a minimum
TWO POSITIVE SAMPLES: Connect the
of 1.5 duct diameters downstream from
higher positive sample to inlet H. Connect
the air source. Install the sampling probe
the lower positive sample to inlet L.
as close to the center of the airstream as
possible. Refer to Figure 2 to identify the ONE POSITIVE AND ONE NEGATIVE
high pressure inlet (H) and the low pres- SAMPLE: Connect the positive sample
sure inlet (L). Select one of the five appli- to inlet H. Connect the negative sample
cation options listed on page 2, and con- to inlet L.
nect the sample lines as recommended.
Are you
Cleveland Controls reading a FAX or a
COPY of this bulletin?
DIVISION OF UNICONTROL INC. Tel: 216-398-0330 DOWNLOAD the full-
1111 Brookpark Rd color PDF version of this
Fax: 216-398-8558 and other literature at
Cleveland OH 44109 our website!
Email:saleshvac@unicontrolinc.com
Web page: http://www.clevelandcontrols.com
Bulletin AFS460.06
(Figure 2)
ELECTRICAL SPECIFICATIONS
CONNECTIONS
MODEL AFS-460 AIR
(SEE FIGURE 3) PRESSURE SENSING
Before pressure is applied to the dia-
SWITCH WITH MANUAL
phragm, the switch contacts will be in the RESET FEATURE
normally closed (NC) position.
Mounting Position (in order to meet
(Figure 3) The snap switch has screw top terminals
lowest operating specifications): Mount
with cup washers. Wire alarm and con-
trol applications as shown in Figure 4. with the diaphragm in any vertical plane.
Set Point Range:
FIELD ADJUSTMENT 0.40 0.06"w.c. to 12.0"w.c.
Field Adjustable Operate Range:
The adjustment range of an AFS-460 0.46"w.c. to 12.0" w.c.
Air Switch is 0.4" 0.02" w.c. to 12.0" Field Adjustable Release Range:
w.c. To adjust the set point, turn the ad-
0.46"w.c. to 11.2" w.c.
justing screw counterclockwise until mo-
tion has stopped. Next, turn the adjust- Approximate Switch Differential:
ing screw four complete turns in a clock- Progressive, increasing from approxi-
wise direction to engage the spring. From mately
this point, the next ten turns will be used 0.06 0.01"w.c. at minimum set point, to
(Figure 4) for the actual calibration. Each full turn approximately 0.8"w.c. at maximum set
represents approximately 1.16" w.c. point.
Please note: To properly calibrate an Measured Media: Air, or combustion
air switch, a digital manometer or other by-products that will not degrade
measuring device should be used to con- silicone.
firm the actual set point. Maximum Pressure: psi (0.03 bar)
Life: Exceeds UL-recognized mechani-
cal endurance test of 6,000 cycles
minimum at 0.5 psi maximum pressure
each cycle and at maximum electrical
load.
Electrical Rating: @ 60 Hz.
15 amp 125, 250, or 277 VAC
hp 125 V AC, Hp 250 VAC,
amp 125 V DC,
amp 250 V DC .
Contact Arrangement:
SPSTNC (manual reset).
Electrical Connections:
Screw top terminals with cup washers.
Conduit Opening: 7/8" diameter
opening accepts " conduit.
Sample Line Connectors: Male,
externally threaded 7/16" 24 UNS 2A
thread, complete with nuts and self-
aligning ferrules.
Sample Line Connections: Connec-
tors will accept " OD rigid or semi-rigid
tubing.
Approval and Recognition:
UL, CSA, CE.
Shipping Weight:
1.2 lbs.
Accessories:
P/N 18311 Slip-on " OD Tubing
Adapter, suitable for slipping on flexible
plastic tubing.
Sample line probes.
Orifice plugs (pulsation dampers).
Nominal Dimensions in Inches (Millimeters)
Cleveland Controls Model
Division of UniControl Inc. AFS-460-DSS
ADJUSTABLE SET POINT AIR PRESSURE SENSING SWITCH WITH DUAL MANUAL RESET
APPLICATION
The Model AFS-460DSS is a general
purpose airflow proving switch designed
for 120 VAC HVAC and Energy Manage-
ment applications where dual manual re-
set switches with SPST contacts are
needed. It may be used to sense posi-
tive, negative, or differential air pressure.
Part Number
Dimension B
Part Number
Dimension A
Dimension B
Part Number
Dimension B
Part Number
Dimension A
Barbed End
Smooth OD
Barbed End
1.5 1.0 21397 1.75 21397-112 1.5 Smooth OD
1.0 21401 1.75 21401-112
2.0 .5 21116 1.25 21116-112 2.0 .5 21120 1.25 21120-112
3.5 1.0 21398 1.75 21398-112 3.5 1.0 21402 1.75 21402-112
4.0 .5 21117 1.25 21117-112 4.0 .5 21121 1.25 21121-112
5.5 1.0 21399 1.75 21399-112 5.5 1.0 21403 1.75 21403-112
7.5 1.0 21400 1.75 21400-112 7.5 1.0 21404 1.75 21404-112
8.0 .5 21123 1.25 21123-112
8.0 .5 21119 1.25 21119-112
10.0 .5 28527 1.25 28527-112
12.0 .5 28528 1.25 28528-112
1. Position 5 to 8 diameters downstream from elbows, ob- 1. Positive static pressure increases as the lter gets dirty.
structions, or signicant change in duct area. 2. Differential across lter changes as lter gets dirty.
2. Insert probe into duct perdendicular to airstream so that: 3. Flow is reduced as lter gets dirty.
Aspiration (static) probe tip opens parallel with airstream. 4. Fan operation or true air ow with little or no static pressure.
Impact (total pressure) probe tip opens directly into the airstream. 5. Negative pressure increases as the lter gets dirty.
6. Fan operation and true air ow: varying amounts of static
pressure. Probes must be perpendicular to air ow.