DESCRIPTION
Models AFS-222, AFS-262, and AFS-460 Differential
Pressure Switches are general-purpose, airflow-proving switches designed for HVAC and building automation
applications. They may be used to sense positive, negative, or differential air pressure. The AFS-460 models
have a manual reset push button; the N.C. switch will
open upon pressure rise to setpoint but will not close
until the reset button is pushed.
AFS-222
AFS-460
FM
APPROVED
FEATURES
APPLICATIONS
Two-year warranty
Adjustable setpoint
For static or differential pressure
UL, CSA, FM approved
Manual reset (Model AFS-460)
SPECIFICATIONS
Setpoint range
AFS-222
AFS-262
AFS-460
AFS-460-DSS
Switch differential,
AFS-222, 202 only Progressive, increasing from
approximately 0.02" W.C.
(5.0 Pa) @ min setpoint to
approximately 0.8" W.C.
(199 Pa) @ max setpoint
Contacts
AFS-222, -202
AFS-460
AFS-460-DSS
SPDT
SPST N.C.
2-SPST N.C.
Electrical rating
AFS-222, -202
AFS-460
Overpressure
Operating temp
Pressure
connections
Connections
Agency approvals
Weight
Life
AFS-222, -202
AFS-460
DIMENSIONS
in
(cm)
2.81
(7.14)
6.13
(15.57)
Low Pressure Inlet (B)
3.25
(8.23)
3.88
(9.86)
3.25
(8.23)
C NO NC
0.710
(1.80)
1.38
(3.50)
1.63
(4.14)
1.94
(4.93)
High Pressure Inlet (A)
0.44
(1.12)
0.78
(1.98)
OPERATION
Select a mounting location that is free from vibration. The switch
must be mounted with the diaphragm in any vertical plane in order to
obtain the lowest specified operating setpoint. Avoid mounting with
the sample line connections in the up position. Surface mount via
the two 3/16" diameter holes in the integral mounting bracket.
The Model AFS-460-DSS has a lead switch (A) and a lag switch (B).
The lead switch trips according to the setpoint knob and the lag
switch trips after the lead switch. If dual-switch simultaneous operation is required, order (not stocked at Kele) AFS-460-136 (120 VAC
power) or AFS-460-137 (24 VAC power).
Locate sampling probe a minimum of 1-1/2 duct diameters downstream from the air source. Install the sampling probe as close to the
center of the airstream as possible.
WIRING
NO
Opens on a
rise in
differential
pressure
NC
NC
AFS-222, -262
AFS-460
A
Lead
NC
B
Lag
NC
AFS-460-DSS
ORDERING INFORMATION
MODEL
AFS-222
AFS-222-C
AFS-262
AFS-262-C
AFS-460
AFS-460-C
AFS-460-DSS
AFS-400-DSS-C
DESCRIPTION
0.05" to 12" W.C. (12.5 to 2989 Pa)
Kele calibrated for your application (specify setpoint)
0.05" to 2" W.C. (12.5 to 498 Pa)
Kele calibrated for your application (specify setpoint)
Manual reset differential pressure switch
Kele calibrated for your application (specify setpoint)
Manual reset differential pressure switch with two SPST switches
Kele calibrated for your application (specify setpoint)