430a 2gs01c22e01 00en - 031
430a 2gs01c22e01 00en - 031
430a 2gs01c22e01 00en - 031
■ STANDARD SPECIFICATIONS
Refer to GS 01C22T02-00E for Fieldbus communication
type marked with “䉫.”
Measurement Ranges:
All Rights Reserved. Copyright © 1994, Yokogawa Electric Corporation GS 01C22E01-00E April 01, 2013-00
<<Contents>> <<Index>> 3
100{750} Atmospheric
600 pressure
Working
E-10.5 pressure
R=
0.0236 Digital KPa abs
Communication {mmHg abs}
External
load range Applicable range
resistance BRAIN and HART
10{75}
250
R (⍀)
2.7{20}
1{7.5}
10.5 16.4 24.7 42 -40 0 40 80 120
Power supply voltage E (V DC) Process temperature (⬚C)
F02E.EPS F02E.EPS
Figure 1. Relationship Between Power Supply Voltage and Figure 2. Working Pressure and Process Temperature
External Load Resistance
0.2
Accuracy
0.1
%
0
Value of 'x'
A capsule 0 0.1{1} 0.3{3} 3 MPa{30 kgf/cm2}
B capsule 0 0.46{4.6} 1.4{14} 14 MPa{140 kgf/cm2}
(Pref)
F03E.EPS
Figure 3. Accuracy
All Rights Reserved. Copyright © 1994, Yokogawa Electric Corporation GS 01C22E01-00E April 01, 2013-00
<<Contents>> <<Index>> 4
■ MODEL AND SUFFIX CODES
Model Suffix Codes Description
EJA430 ............................. Gauge pressure transmitter
Output Signal -D . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
-E . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol) *1
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol) *7
Measurement span A........................ 0.06 to 3 MPa{0.6 to 30 kgf/cm2}
(capsule) B........................ 0.46 to 14 MPa{4.6 to 140 kgf/cm2}
Wetted parts material*11 [Body] *4 [Capsule] [Vent plug]
S# . . . . . . . . . . . . . . . . . . . . . . . JIS SCS14A JIS SUS316L *2 JIS SUS316 *13
H# . . . . . . . . . . . . . . . . . . . . . . . JIS SCS14A Hastelloy C-276 *3 *12 JIS SUS316 *13
M# . . . . . . . . . . . . . . . . . . . . . . . JIS SCS14A Monel *3 JIS SUS316 *13
T....................... JIS SCS14A Tantalum *3 JIS SUS316 *13
A# . . . . . . . . . . . . . . . . . . . . . . . Hastelloy C-276 equivalent*8 Hastelloy C-276 *3 *12 Hastelloy C-276 *12
D....................... Hastelloy C-276 equivalent*8 Tantalum *3 Hastelloy C-276 *12
B# . . . . . . . . . . . . . . . . . . . . . . . Monel equivalent *9 Monel *3 Monel
Process connection 0...................... without process connector (Rc1/4 female on the cover flanges)
1...................... with Rc1/4 female process connector
2...................... with Rc1/2 female process connector
3...................... with 1/4 NPT female process connector
4...................... with 1/2 NPT female process connector
夽 5...................... without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts material [Maximum working pressure]
(A capsule) (B capsule)
夽 A.................... JIS SCM435 3 MPa {30 kgf/cm2} 14 MPa {140 kgf/cm2}
B.................... JIS SUS630 3 MPa {30 kgf/cm2} 14 MPa {140 kgf/cm2}
Installation -2 . . . . . . . . . . . . . . . . . Vertical impulse piping type, right side high pressure, process connector upside *5
-3 . . . . . . . . . . . . . . . . . Vertical impulse piping type, right side high pressure, process connector downside *5
-6 . . . . . . . . . . . . . . . . . Vertical impulse piping type, left side high pressure, process connector upside *5
-7 . . . . . . . . . . . . . . . . . Vertical impulse piping type, left side high pressure, process connector downside *5
-8 . . . . . . . . . . . . . . . . . Horizontal impulse piping type, right side high pressure *6
夽 -9 . . . . . . . . . . . . . . . . . Horizontal impulse piping type, left side high pressure *6
Electrical connection 0............... G1/2 female, one electrical connection
夽 2............... 1/2 NPT female, two electrical connections without blind plug
3............... Pg 13.5 female, two electrical connections without blind plug
4............... M20 female, two electrical connections without blind plug
5............... G1/2 female, two electrical connections and a blind plug
7............... 1/2 NPT female, two electrical connections and a blind plug
8............... Pg 13.5 female, two electrical connections and a blind plug
9............... M20 female, two electrical connections and a blind plug
A............... G1/2 female, two electrical connections and a SUS316 blind plug
C............... 1/2 NPT female, two electrical connections and a SUS316 blind plug
Integral indicator D............. Digital indicator
E............. Digital indicator with the range setting switch *10
夽 N............. (None)
Mounting bracket 夽 A............ JIS SECC 2-inch pipe mounting (flat type)
B............ JIS SUS304 2-inch pipe mounting (flat type)
J............ JIS SUS316 2-inch pipe mounting (flat type)
C............ JIS SECC 2-inch pipe mounting (L type)
D............ JIS SUS304 2-inch pipe mounting (L type)
K............ JIS SUS316 2-inch pipe mounting (L type)
N............ (None)
Optional codes /■ Optional specification
T08E.EPS
The ‘夽’ marks indicate the most typical selection for each specification. Example: EJA430-DAS5A-92NA/䊐
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of
SUS316 material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.
All Rights Reserved. Copyright © 1994, Yokogawa Electric Corporation GS 01C22E01-00E April 01, 2013-00
<<Contents>> <<Index>> 5
*9: Indicated material is equivalent to ASTM M35-2.
*10: Not applicable for Output signal code F.
*11: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to
plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the
fill fluid can contaminate the user's process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium
hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted
parts material.
*12: Hastelloy C-276 or ASTM N10276.
*13: JIS SUS316 or ASTM grade 316.
All Rights Reserved. Copyright © 1994, Yokogawa Electric Corporation GS 01C22E01-00E Jul. 08, 2009-00
<<Contents>> <<Index>> 6
■ OPTIONAL SPECIFICATIONS (For Explosion Protected types “䉫”)
For FOUNDATION Fieldbus explosion protected type, see GS 01C22T02-00E.
Item Description Code
FM Explosionproof Approval *1 *3
Applicable standard: FM3600, FM3615, FM3810, ANSI/NEMA250
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
FF1
Hazardous (classified) locations, indoors and outdoors (NEMA 4X)
Division 2, 'SEALS NOT REQUIRED',
Temp. Class: T6
Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F)
FM Intrinsically safe Approval *1 *3
Applicable standard: FM3600, FM3610, FM3611, FM3810, ANSI/NEMA250
Factory Mutual (FM) Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1 Hazardous Locations.
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
Groups E, F & G, and Class III, Division 1 Hazardous Locations.
FS1
Enclosure: “NEMA 4X”, Temp. Class: T4, Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F)
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 H
[Groups C, D, E, F and G]
Vmax=30 V, Imax=225 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 H
Combined FF1 and FS1 *1 *3 FU1
ATEX Flameproof Approval *2
Applicable standard: EN60079-0, EN60079-1
Certificate: KEMA 02ATEX2148
II 2G Ex d IIC T4, T5, T6 KF21
Amb. Temp.: T5; –40 to 80⬚C ( –40 to 176⬚F), T4 and T6; –40 to 75⬚C ( –40 to 167⬚F)
ATEX Max. process Temp.: T4; 120⬚C (248⬚F), T5; 100⬚C (212⬚F), T6; 85⬚C (185⬚F)
ATEX Intrinsically safe Approval *2 *3
Applicable standard: EN50014, EN50020, EN500284, EN50281-1-1
Certificate: KEMA 02ATEX1030X KS2
II 1G EEx ia IIC T4, Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F)
Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 H
T11E.EPS
*1: Applicable for Electrical connection code 2, 7 and C (1/2 NPT female).
*2: Applicable for Electrical connection code 2, 4, 7, 9 and C(1/2 NPT and M20 female).
*3: Applicable for Output signal code D and E. For intrinsically safe approval, use the safety barrier certified by the testing laboratories
(BARD-400 is not applicable).
All Rights Reserved. Copyright © 1994, Yokogawa Electric Corporation GS 01C22E01-00E April 01, 2013-00
<<Contents>> <<Index>> 7
Item Description Code
CSA Explosionproof Approval *1 *3
Applicable standard: C22.2 No. 0, No. 0.4, No. 25, No. 30, No. 94, No. 142
Certificate: 1089598
Explosionproof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
Division2 ‘SEALS NOT REQUIRED’ , Temp. Class: T4, T5, T6 Encl Type 4x CF1
Max. Process Temp.: T4; 120⬚C (248⬚F), T5; 100⬚C (212⬚F), T6; 85⬚C (185⬚F)
Amb. Temp.: –40 to 80⬚C (–40 to 176⬚F)
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
Canadian Standards No additional sealing required. Primary seal failure annunciation: at the zero adjustment screw
Association (CSA)
CSA Intrinsically safe Approval *1 *3
Applicable standard: C22.2 No. 0, No. 0.4, No. 25, No. 30, No. 94, No. 142, No. 157, No. 213
Certificate: 1053843
Class I, Groups A, B, C and D Class II and III, Groups E, F and G
Encl Type 4x, Temp. Class: T4, Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F) CS1
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 H
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required. Primary seal failure annunciation: at the zero adjustment screw
Combined CF1 and CS1 *1 *3 CU1
IECEx Intrinsically safe, type n and Flameproof Approval *3 *9
Intrinsically safe and type n
Applicable Standard: IEC 60079-0:2004, IEC 60079-11:1999, IEC 60079-15:2005,
IEC 60079-26:2005
Certificate: IECEx KEM 06.0007X
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP67
Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F), Max. Process Temp.: 120⬚C (248⬚F)
IECEx Electrical Parameters: [Ex ia] Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 H
SU2
[Ex nL] Ui=30 V, Ci=22.5 nF, Li=730 H
Flameproof
Applicable Standard: IEC 60079-0:2004, IEC60079-1:2003
Certificate: IECEx KEM 06.0005
Ex d IIC T6...T4 Enclosure: IP67
Max.Process Temp.: T4;120⬚C (248⬚F), T5;100⬚C (212⬚F), T6; 85⬚C (185⬚F)
Amb.Temp.: –40 to 75⬚C (–40 to 167⬚F) for T4, –40 to 80⬚C (–40 to 176⬚F) for T5,
–40 to 75⬚C (–40 to 167⬚F) for T6
TIIS Flameproof Approval, Ex do IIC T4X *3 *4 *5 *7 *8
JF3
Amb. Temp.: –20 to 60⬚C, Process Temp.: –20 to 120⬚C
TIIS certification TIIS Intrinsically safe Approval, Ex ia IIC T4 *6 *8
Certificate: TC14632 JS3
Amb. Temp.: –20 to 60⬚C, Process Temp.: –20 to 120⬚C
Attached flameproof Electrical connection: G1/2 female 1 pc. G11
packing adapter *5 Applicable cable: O. D. 8 to 12 mm 2 pcs. G12
T12E.EPS
*1: Applicable for Electrical connection code 2, 7 and C (1/2 NPT female).
*2: Applicable for Electrical connection code 2, 4, 7, 9 and C (1/2 NPT and M20 female).
*3: Applicable for Output signal code D and E. For intrinsically safe approval, use the safety barrier certified by the testing laboratories
(BARD-400 is not applicable).
*4: Not applicable for Electrical connection code A and C.
*5: If cable wiring is to be used to a TIIS flameproof type transmitter, add the YOKOGAWA-assured flameproof packing adapter.
*6: Applicable for Output signal code D. See <Safety Barrier for TIIS Intrinsically Safe Type>.
*7: In case that the ambient temperature exceeds 50°C or that the ambient temperature exceeds 45°C with the process temperature of
90°C or above, use heat-resistant cables with maximum allowable temperature of 75°C or above.
*8: TIIS (The Technology Institution of Industrial Safety) Certification is a new notation for the explosionproof approval in Japan
instead of JIS.
See certificate list of TIIS flameproof Approval below.
Without integral indicator With integral indicator
S TC15296 TC15297
Wetted parts H, A TC15298 TC15299
material code T, D TC15300 TC15301
M, B TC15302 TC15303
T13E.EPS
*9: Applicable for Electrical connection code 2, 4, 7 and C (1/2 NPT and M20 female).
All Rights Reserved. Copyright © 1994, Yokogawa Electric Corporation GS 01C22E01-00E April 23, 2012-00
<<Contents>> <<Index>> 8
■ OPTIONAL SPECIFICATIONS
Item Description Code
Amplifier cover only P
Color change
Painting Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Epoxy resin-baked coating *15 X1
Exterior parts on the amplifier housing(name plates, tag plate, zero-adjustment screw,
316 SST exterior parts HC
stopper screw) will become 316 SST *16
Transmitter power supply voltage : 10.5 to 32 V DC (10.5 to 28 V DC for TIIS intrinsically
safe type, 10.5 to 30 V DC for intrinsically safe type other than TIIS, or 9 to 32 V DC for
Lightning protector A
Fieldbus communication type.)
Allowable current : Max. 6000 A (1⫻40 s), Repeating 1000 A (1⫻40 s) 100 times
Degrease cleansing treatment K1
Oil-prohibited use *11 Degrease cleansing treatment with fluorinated oil
filled capsule. Operating temperature -20 to 80°C K2
Total length: 119 mm (standard: 34 mm); Total length when combining with Optional code
Long vent *2 K1, K2, K5, and K6: 130 mm. Material: SUS316 or ASTM grade 316. U
Surface of isolating diaphragms are gold plated, effective for hydrogen permeation.
Gold-plate *5 (The diaphragm for atmospheric side is not gold-plated) A1
Wired tag plate Stainless steel tag plate wired onto transmitter N4
Cover flange *6 M01
Mill Certificate
Cover flange, Process connector *7 M11
Test Pressure : 3 MPa{30 kgf/cm2} *8 Nitrogen (N2) Gas *10 T03
Pressure test/Leak test Certificate *14
Test Pressure : 14 MPa{140 kgf/cm2} *9 Retention time: 10 minutes T02
T09E.EPS
*1: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by Option code D1, D3, and
D4.
*2: Applicable for vertical impulse piping type (Installation codes 2, 3, 6, or 7) and Wetted parts material code S, H, M, and T.
*3: Applicable for Output signal code D and E. The hardware error indicates faulty amplifier or capsule.
When combining with Option code F1, output status for down-scale is –2.5%, 3.6 mA DC or less.
*4: Applicable for Electrical connection code 2, 3, 4, A and C. Not applicable for Option code P䊐, X1, and JF3.
*5: Applicable for Wetted parts material code S.
*6: Applicable for Process connection code 0 and 5.
*7: Applicable for Process connection code 1, 2, 3, and 4.
*8: Applicable for Capsule code A.
*9: Applicable for Capsule code B.
*10: Pure nitrogen gas is used for oil-prohibited use (Option code K1, K2, K5, and K6).
*11: Applicable for Wetted parts material code S, H, M, and T.
*12: Applicable for Output signal code D and E. Write protection switch is attached for output code E. Not applicable for Integral
indicator code E.
*13: Not applicable for Option code C1.
*14: The unit on the certificate is always MPa regardless of selection of option code D1, D3, or D4.
*15: Not applicable for color change option.
*16: 316 or 316L SST. The specification is included in option code /E1. Not applicable with option code /JF3.
All Rights Reserved. Copyright © 1994, Yokogawa Electric Corporation GS 01C22E01-00E July 01, 2011-00
<<Contents>> <<Index>> 9
■ DIMENSIONS
● Vertical Impulse Piping Type
Process connector upside (INSTALLATION CODE '6' )
External indicator Unit : mm (approx.inch)
Process connection conduit connection
259(10.20) (Optional)
197 (7.76)
110 (4.33)
97 146 (5.75) High Low
(3.82) pressure 27 pressure
Process side *1 (1.06) side
connector
(Optional) Internal
indicator
(2.83)
72
(1.81)
(Optional)
148 *2
46
(5.83)
(3.07)
ø78
234(9.21)
Terminal
(4.02)
side
102
Conduit
Ground connection
terminal
Zero
( 2.09)
(0.47)
*3
Mounting bracket Shrouding bolt
(L-type, Optional) 2-inch pipe
(O.D. 60.5mm)
Process connector downside (INSTALLATION CODE '7' )
( 2.09)
53
Vent/Drain plug
(4.02)
102
(2.83)
72
High Low
pressure pressure
side (Note) side
Process
connections
(Optional) Terminal
ø78
External indicator
conduit connection side
(7.76)
197
(Optional)
(5.75)
(6.38)
146
Ground
162
terminal
High Low
pressure pressure
side *1 side
Process
connection
Process Vent plug 27 (1.06)
(4.88)
46 connector
124
Mounting bracket
2-inch pipe (O.D. 60.5mm)
(Flat-type, Optional)
F04E.EPS
*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on above figure are reversed.
(i.e. High pressure side is on the right side.)
*2: When Optional code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
*3: Applicable only for ATEX, IECEx, and TIIS Flameproof type.
All Rights Reserved. Copyright © 1994, Yokogawa Electric Corporation GS 01C22E01-00E Oct. 01, 2008-00
<<Contents>> <<Index>> 10
● Terminal Configuration ● Terminal Wiring
+
SUPPLY Power supply and output terminal
–
< Ordering Information > “䉫” < Safety Barrier for TIIS Intrinsically Safe Type >
Specify the following when ordering
1. Model, suffix codes, and optional codes Supplier Type Model
2. Calibration range and units: MTL3046B
1) Calibration range can be specified with range value MTL
MTL4041B
Isolator
specifications up to 5 digits KFD2-STC3-Ex 1
(excluding any decimal point) for low or high range limits P+F
KFD2-STV3-Ex 1-1, 2, 3
within the range of -32000 to 32000. T001E.EPS
2) Specify only one unit from the table, ‘Settings when
shipped.’ Note: Requirements of capacitance and inductance for cable
3. Select linear or square root for output mode and display wiring.
mode. Cw ≤ Co – 11[nF]
Lw ≤ Lo – 730[µH]
Note: If not specified, the instrument is shipped set for
(Co: Max. external capacitance)
linear mode.
(Lo: Max. external inductance)
4. Select normal or reverse for operation mode
Note: If not specified, the instrument is shipped in normal
operation mode.
< Reference >
5. Display scale and units (for transmitters equipped with
integral indicator only) 1. JIS SUS316L stainless steel; Equivalent to AISI 316L.
Specify either 0 to 100 % or engineering unit scale and 2. JIS SUS316 stainless steel; Equivalent to AISI 316.
‘Range and Unit’ for engineering units scale: 3. JIS SUS304 stainless steel; Equivalent to AISI 304.
Scale range can be specified with range limit specifications 4. JIS SECC Carbon steel.
up to 5 digits (excluding any decimal point) for low or 5. Teflon; Trademark of E.I. DuPont de Nemours & Co.
high range limits within the range of -19999 to 19999. 6. JIS SUS630 stainless steel; Equivalent to ASTM 630.
6. Tag Number (if required) 7. Hastelloy; Trademark of Haynes International Inc.
8. Monel; Trademark of Inco Alloys International, Inc.
< Related Instruments > “䉫” 9. JIS SCS14A stainless steel; Equivalent to JIS SUS316
Power Distributor: Refer to GS 01B04T01-02E or cast stainless steel or ASTM CF-8M.
GS 01B04T02-02E 10. HART; Trademark of the HART Communication
BRAIN TERMINAL: Refer to GS 01C00A11-00E Foundation.
11. FOUNDATION; Trademark of Fieldbus Foundation.
12. Other company names and product names used in this
material are registered trademarks or trademarks of their
respective owners.
All Rights Reserved. Copyright © 1994, Yokogawa Electric Corporation GS 01C22E01-00E Mar. 23, 2006-00
Subject to change without notice.