PRM DesignGuideComplete v1
PRM DesignGuideComplete v1
PRM DesignGuideComplete v1
Introduction
With the increasing sophistication of modern power systems, it is easy to overlook the fact that the basic function
of a power distribution system has been the same for over 100 years the safe, reliable distribution of power from
a source to the connected loads. This basic function has not changed, although the complexity of the loads
themselves, along with today's reliability and efficiency requirements, do make its realization more complex.
This guide discusses the basic considerations which must be taken into account in order to obtain an optimal
system design. Because the characteristics of each load, process, etc., served are unique, so too will each design
be unique in order to match the requirements imposed.
Illumination Whether for providing light for an office environment or a manufacturing shop floor, illumination is
one of the most important applications of electric power, and the oldest.
Environmental systems Electric heating, ventilation, and air-conditioning are a large application for electric
power, and also an area in which electric power receives direct competition from other energy sources such as
natural gas.
Industrial processes Industrial processes account for a large percentage of the global use of electric power.
Typical process applications are listed as follows. These are not all-inclusive but do cover the majority of
process applications:
N Pumping
[1]
Chemical Processes
Furnaces
Standard Handbook for Electrical Engineers, New York: McGraw-Hill, 2001, pp. 21-1 - 21-99.
Smelting
Rolling Mills
Welding
Refrigeration
Drying
Well Drilling
Materials Handling
Computers and Data Centers With the advent of large computer networks the need also arisen for reliable
power for these.
Health Care Reliable power has always been a requirement of the health care industry, but added to this is
the need for power quality due to the nature of the equipment used.
Safety Systems Systems such as fire alarm and smoke detection systems, sprinkler systems and fire pumps
are vital to any commercial or industrial facility.
Communication Systems Systems such as telephone and intrusion detection and monitoring are
critically important.
Basic Safety: The power system must be able to perform all of its basic functions, and withstand basic
abnormal conditions, without damage to the system or to personnel.
B a s i c F u n c t i o n a l i t y : The power system must be able to distribute power from the source to the connected
loads in a reliable manner under normal conditions.
Reasonable Cost: The power system cost to obtain basic safety and functionality should be reasonable.
Above and beyond the basics are a multitude of considerations, some of which will apply to each particular
system design:
Enhanced Safety: The ability to withstand extremely abnormal conditions with a minimum of risk to personnel.
E n h a n c e d M a i n t a i n a b i l i t y : The system can be maintained with minimum interruption to service and with
minimum personnel protective equipment.
E n h a n c e d F l e x i b i l i t y : The ability to add future loads to the system, and with loads of a different nature than
currently exist on the system.
Enhanced Space Economy: The power system takes up the smallest possible physical space.
Reduced Cost: The power system costs, both first cost and operating cost, are low.
Enhanced Power Quality: The power system currents and voltages are sinusoidal, without large amounts of
harmonics present. System voltage magnitudes do not change appreciably.
Enhanced Tr a n s p a r e n c y : The power system data at all levels is easily acquired and interpreted, and the power
system is easily interfaced with other building systems. Enhanced control of the system is also possible.
While it should be the goal of every power system design to meet the above basic considerations, no system
design can yield all of the enhanced characteristics listed. The relationship between the considerations listed is
shown in figure 1-1.
As can be seen, some of the enhanced characteristics mentioned are mutually exclusive, and to obtain a
combination of several enhanced characteristics requires a significant increase in cost. The design engineer,
therefore, must take into account the balance between the performance requirements of the system and the cost,
while not compromising the basic safety elements, functionality, and code compliance.
Section 2:
Introduction
An understanding of the fundamentals of electric power is vital to successful power system design. It is assumed
that the reader has a degree in electrical engineering or electrical engineering technology, however the following
discussion is presented as review and reference material for completeness.
Basic Concepts
Commercial electric power in the United States is generated and delivered as alternating current, abbreviated as
AC. AC power consists of sinusoidal voltages and currents. Mathematically, an ac voltage or current can be
expressed as follows:
(2-1)
(2-2)
where
v(t)
i(t)
Vmax
Imax
f
v
i
t
is an AC voltage
is an AC current
is the voltage amplitude
is the current amplitude
is the system frequency
is the voltage phase shift in degrees
is the current phase shift in degrees
is the time in ms
The voltages from (2-3) - (2-5) are shown graphically in figure 2-1:
Vmax
12
24
t (ms)
Va
Vb
Vc
The peaks of the voltage waveforms are 120 (5.5 ms at 60 Hz) apart. Note that the peak of phase A occurs
before the peak of phase B, which in turn occurs before the peak of phase C. This is referred to as an ABC phase
sequence or ABC phase rotation. If any two phase labels are swapped, the result will be CBA phase rotation.
Both are encountered in practice. Also note that the definition of time = 0 is arbitrary due to the periodic nature of
the waveforms.
Because the full mathematical representation of AC voltages and currents is not practical, a shorthand notation is
usually used. This shorthand notation treats the sinusoids as complex quantities based upon the following
mathematical relationship:
(2-6)
The voltage quantities from (2-3) - (2-5) can therefore be rewritten as follows:
(2-7)
(2-8)
(2-9)
To further develop this shorthand notation, it must be recognized that the use of the RMS (root-mean-square)
quantity, rather than the amplitude, is advantageous in power calculations (discussed below). The RMS quantity
for a periodic function f(t) is defined as follows:
(2-10)
where
Frms
T
Using (2-10), the RMS value of each of the sinusoidal voltages from (2-3) - (2-5) are calculated as:
(2-11)
Because the RMS value is so useful in the calculation of power-related quantities, any time an AC voltage or
current value is given it is assumed to be an RMS value unless otherwise stated.
Assuming that only the real part of eje is kept, the voltages from (2-7) - (2-9) can be written as complex quantities
known as phasors:
V a = Vrms e j 21600t
(2-12)
(2-13)
(2-14)
Assuming a frequency of 60 Hz, the commonly-used shorthand notation for (2-12) - (2-14) is:
(2-15)
(2-16)
(2-17)
The phasor quantities in (2-15) - (2-17) can be treated as complex quantities for the purposes of manipulation and
calculation, but with the understanding that, if required, the basic time-domain voltage relationships (2-3) - (2-5)
can easily be obtained. The phasors can be plotted, as shown in figure 2-2:
In most instances the Re and Im axes are omitted since the definition of time zero (and thus angle zero) is
arbitrary; the important information conveyed is the angular relationships between the phasors themselves.
Note that the real part of a phasor is its projection on the Re axis; if the phasors are imagined to rotate in a
counter-clockwise direction about the 0,0 point it can be seen that the peak of va(t), represented by the tip of
phasor Va crossing the Re axis, occurs first, followed by the peak of vb(t), followed in turn by the peak of vc(t).
Thus for angles defined as positive in the counter-clockwise direction the ABC phase sequence is indicated by a
counter-clockwise phasor rotation. If angles are defined as positive in the clockwise direction a clockwise phasor
rotation would indicate an ABC phase sequence. Both are encountered in practice. In this guide all angles in
phasor diagrams will be assumed to be positive in the counter-clockwise direction.
In figure 2-3 the three phases A, B, and C have been labeled, along with the neutral (N) and ground (G).
The neutral is optional, however the ground always exists. The AC voltages Va, Vb and Vc per the discussion
above could represent phase-to-phase voltages (Vab, Vbc,Vca), phase-to-neutral voltages (Van,Vbn, Vcn) or
phase-to-ground voltages (Vag, Vbg, Vcg). The existence of the neutral, and the relationship between the phases
and ground, is dependent upon the system grounding and is discussed in section 6 of this guide. Note
that a ground current is not defined; this is because the ground is not intended to carry load current, only ground
fault current as discussed in subsequent sections of this guide. In practice, when 3 voltages are discussed, they
are assumed to be phase-to-phase voltages unless otherwise noted.
AC power
With the basic concepts per above, AC electrical power can be described.
Consider the following DC circuit element:
is the DC voltage across the circuit element under consideration, with polarity as shown
is the DC current through the circuit element under consideration, considered positive for
the direction shown
is the power generated by, or dissipated through, the circuit element under consideration
The sign of P in (2-18) is dependent upon the direction of current flow with respect to the DC voltage. A positive
value for P indicates power dissipated, while a negative value for P indicates power generated. DC power is
measured in Watts, where one Watt is 1V x 1A.
With AC voltages and currents the expression for power is more complex. Assume that one phase is taken under
consideration, with and AC current and voltage as defined by (1-1) and (1-2) respectively. The expression for the
instantaneous power, after some manipulation, is:
(2-19)
Thus, the instantaneous power consists of two parts: A DC component and an AC component with a frequency
twice that of the system frequency. The quantity (v - i) is defined as the power angle or power factor angle and
is the angle by which the current peak lags behind the voltage peak on their respective waveforms. The quantity
P= cos(v-i) is known as the power factor of the circuit.
The average value of p(t) is of concern in AC circuits. The average value of p(t) is:
(2-20)
Recall that Vmax can be expressed in terms of Vrms per (2-11); substituting Vrms per (2-11) into (2-20) yields:
(2-21)
However, the absolute value of the product VrmsIrms cos(v-j) will always be less than VrmsIrms unless (v-j) = 0.
Further, if (v-j) = 90 , as is the case with a purely inductive or capacitive load, VrmsIrms cos(v-j) = 0.
Because energy is required to force current to flow, and energy is always conserved, AC power must have
another component. This component is most easily defined if AC power is treated as a complex quantity. To do
this, Complex Power S is defined as follows:
(2-22)
The quantities V and I are the AC current and voltage in their complex forms per (2-15) above, with the
*operator denoting the complex conjugate, or angle negation, of the current. This conjugation of the current is
done to yield the correct value for the power angle as described below. Real Power P and Reactive Power Q
are defined as follows:
(2-23)
(2-24)
(2-25)
(2-26)
P is expressed in Watts. Q has the same units but to differentiate it from P it is expressed in Voltamperes. rather
than Watts. S is the Apparent Power and is also expressed in Voltamperes.
The depiction in figure 2-5 is referred to as the power triangle since P, Q and S form a right triangle. It is also
important to note that the power factor angle is the same as the load impedance angle of the circuit. The power
factor is referred to as a lagging power factor if the current lags the voltage (i.e., (v-l) is positive up to 90)
and as a leading power factor if the current leads the voltage (i.e., (v-l) is negative down to -90). For a lagging
power factor, the real and reactive power flow in the same direction; for a lagging power factor they flow in
opposite directions. Of the passive circuit elements, resistors exhibit a unity power factor, inductors exhibit a zero
power factor lagging, and capacitors exhibit a zero power factor leading.
The foregoing discussion considers only single-phase circuits. For 3 circuits the power quantities for all three
phases must be added together, i.e.,
(2-27)
(2-28)
(2-29)
(2-30)
If the voltage magnitudes and power factor angles for each phase are equal, the power quantities per phase can
be represented as S1, S1, P1, and Q1; equations (2-27) - (2-30) can then be simplified as:
(2-31)
(2-32)
(2-33)
(2-34)
Transformers
Transformers are vital components for AC power systems. They are used to change the voltage and current
magnitudes to suit the application.
d
dt
(2-35)
where is the voltage induced in a coil of N turns that is linked by a magnetic flux .
In turn, the magnetic flux for a coil of N turns which through which a current I passes and linked by a magnetic
path with reluctance can be expressed as:
(2-36)
Consider the simple transformer shown in the following figure:
(2-40)
(2-41)
Dividing (2-40) by (2-41),
(2-42)
Equations (2-38) and (2-42) are the basic equations for a single-phase transformer. The voltage ratio (V1/V2) is
equal to the turns ratio (N1/N2), and the current ratio is equal to the inverse of the turns ratio. By re-writing (2-38)
in terms of the turns ratio (N1/N2) an substituting into (2-42), the following is obtained:
(2-43)
This is to be expected, since the apparent flowing into the transformer should ideally equal the apparent power
flowing out of the transformer.
The usefulness of the transformer lies in the fact that it can adjust the voltage and current to the application. For
example, on a transmission line it is advantageous to keep the voltage high in order to be able to transmit the
power with as small a current as possible, in order to minimize line losses and voltage drop. At utilization
equipment, it is advantageous to work with low voltages that are more conducive to equipment design and
personnel safety.
Another important aspect of the transformer is that it changes the impedance of the circuit. For example, if an
impedance Z2 is connected to winding 2 of the ideal transformer in figure 2-6 it can be stated by definition that
(2-44)
Using (2-38) and (2-42), (2-44) can be written in terms of V1 and I1:
(2-45)
By definition,
(2-46)
Therefore, (2-45) can be re-written as
(2-47)
As can be seen, the impedance as seen through the transformer is the load impedance at the transformer output
winding multiplied by the square of the turns ratio.
The resistance Rc represents the core losses due to hysteresis, and inductance Lc represents the magnetizing
inductance. Resistances R1 and R2 represent the winding resistances of winding 1 and winding 2, respectively.
Inductances L1 and L2 represent the leakage inductances of windings 1 and 2, respectively. For quick
calculations, the core losses and magnetizing inductance are often ignored, and the model is treated as an
impedance in series with an ideal transformer.
To insure the proper polarity, the circuit representation for a transformer includes polarity marks as shown in figure
2-8. If the current for one winding flows into its terminal with the polarity mark, the current for the other winding
flow out of its terminal with the polarity mark. In addition, the ANSI polarity markings per [1] are shown; H
denotes the higher voltage winding, and X denotes the lower voltage winding.
If a three-phase transformer is used, the wye-wye connection has the disadvantage of requiring a four-legged
core to allow for a magnetic flux imbalance. Further, the solidly-grounded neutrals allow for ground currents to flow
that can create interference in communications circuits [2]. Both the primary and secondary neutrals terminals
must be solidly-grounded to allow for triplen-harmonic currents to flow; if the neutrals are allowed to float harmonic
overvoltages will be developed from phase to neutral on each winding. These overvoltages can damage the
transformer insulation. Wye-wye transformers are often used on systems above 25 kV to minimize a problem
known as ferroresonance. Ferroresonance is a condition which results from the transformer magnetizing
impedance resonating with the upstream cable charging capacitance, resulting in destructive overvoltages as the
transformer core moves into and out of saturation in a non-linear manner. Single-phase switching is usually the
cause of ferroresonance.
The delta-delta connection is shown in figure 2-10. Note that there is no neutral on the delta-delta connection.
A unique feature of this connection is that if one transformer is taken out of service, the two remaining
transformers can still provide three-phase service at a reduced capacity (57.7% of the capacity with all three
transformers in service).
The delta-wye connection is shown in figure 2-11. Note that for the given turns ratios of 1:1 that the magnitude
of the phase-to-phase output voltage is equal to the magnitude of the phase-to-phase input voltage multiplied
by 3 . The input and output voltages of 3 transformers and 3 banks of single-phase transformers are always
referenced as the phase-to-phase magnitude. Therefore, for a delta-wye transformer the winding turns ratios for
each set of windings must be compensated by (1/3 ) to produce the desired input-to-output voltage ratio.
Note also that the phase-to-phase voltages on the lower voltage side of the transformer lag the phase-to-phase
voltages on the high voltage side by 30. This is dictated by [1].
The delta-wye transformer connection is by far the most popular choice for commercial and industrial applications.
3 transformers do not require a four-legged core like the wye-wye connection, but the advantages of a wye
secondary winding (elaborated on in section 6 of this guide) are obtained. Further, the secondary neutral can be
left unconnected in this arrangement, unlike the wye-wye arrangement.
10
The wye-delta connection is shown in figure 2-12. This connection is seldom used in commercial and industrial
applications. Note that the delta is arranged differently from the delta-wye connection, in order to satisfy the
requirement from [1] to have the phase-to-phase voltages on the low-voltage side of the transformer lag the
corresponding voltages on the primary side by 30.
A.) DC Circuits
(2-48)
(2-49)
(2-50)
where
Vdc
Idc
Rdc
P
11
is an AC voltage
is an AC current
is the voltage amplitude
is the current amplitude
is the system frequency
is the voltage phase shift in degrees
is the current phase shift in degrees
is the time in ms
12
13
= -1
f
C
L
14
References
Because the subject matter for this section is basic and general to the subject of electrical engineering, it is
included in most undergraduate textbooks on basic circuit analysis and electric machines. Where material is
considered so basic as to be axiomatic no attempt has been made to cite a particular source for it.
For material not covered per the above, references specifically cited in this section are:
[1]
IEEE Standard Terminal Markings and Connections for Distribution and Power Transformers,
IEEE Std. C57.12.70-2000.
[2]
Turan Gonen, Electric Power Distribution System Design, New York: McGraw-Hill, 1986, p.137.
15
Section 3:
Load Planning
Basic Principles
The most vital, but often the last to be acquired, pieces of information for power system design are the load
details. An important concept in load planning is that due to non-coincident timing, some equipment operating
at less than rated load, and some equipment operating intermittently rather than continuously, the total demand
upon the power source is always less than the total connected load [1]. This concept is known as load diversity.
The following standard definitions are given in [1] and [2] and are tools to quantify it:
Demand: The electric load at the receiving terminals averaged over a specified demand interval. of time, usually
15 min., 30 min., or 1 hour based upon the particular utilitys demand interval. Demand may be expressed in
amperes, kiloamperes, kilowatts, kilovars, or kilovoltamperes.
Demand Interval: The period over which the load is averaged, usually 15 min., 30 min., or 1 hour.
Peak Load: The maximum load consumed or produced by a group of units in a stated period of time. It may be
the maximum instantaneous load or the maximum average load over a designated period of time.
Maximum Demand: The greatest of all demands that have occurred during a specified period of time such as
one-quarter, one-half, or one hour. For utility billing purposes the period of time is generally one month.
Coincident Demand: Any demand that occurs simultaneously with any other demand.
Demand Factor: The ratio of the maximum coincident demand of a system, or part of a system, to the total
connected load of the system, or part of the system, under consideration, i.e.,
(3-1)
Diversity Factor: The ratio of the sum of the individual maximum demands of the various subdivisions of a
system to the maximum demand of the whole system, i.e.,
(3-2)
where
Di
DG
Using (1), the relationship between the diversity factor and the demand factor is
(3-3)
where
TCLi
DFi
Load Factor: The ratio of the average load over a designated period of time to the peak load occurring
in that period, i.e.,
(3-4)
If T is the designated period of time, an alternate formula for the load factor may be obtained by manipulating
(3-4) as follows:
(3-5)
These quantities must be used with each type of load to develop a realistic picture of the actual load requirements
if the economical sizing of equipment is to be achieved. Further, they are important to the utility rate structure
(and thus the utility bill).
As stated in [2], the following must be taken into account in this process:
I
Load Profile Load magnitude and power factor variations expected during low-load, average load,
and peak load conditions
Special or unusual loads such as resistance welding, arc welding, induction melting, induction heating, etc.
Reference [4] and individual engineering experience on previous projects are both useful in determining demand
factors for different types of loads. In addition, the National Electrical Code [3] gives minimum requirements for
the computation of branch circuit, feeder, and service loads.
Receptacle: A receptacle is a contact device installed at the outlet for the connection of an attachment plug.
A single receptacle is a single contact device with no other contact device on the same yoke. A multiple receptacle
is two or more contact devices on the same yoke.
Continuous Load: A load where the maximum current is expected to continue for three hours or more.
The NEC definition of Demand Factor is essentially the same as given above.
I
Minimum lighting load (Article 220.12): Minimum lighting load must not be less than as specified in table 3-1
(NEC Table 220.12):
Table 3-1: General lighting loads by occupancy (NEC [3] table 220.12)
Type of Occupancy
Unit Load
Volt-Amperes
Per quare Meter
Unit Load
Volt-Amperes
per Square Foot
11
Banks
39
3.5b
33
Churches
11
Clubs
22
22
Dwelling Units
33
0.5
Hospitals
22
22
22
Lodge rooms
17
1.5
Office buildings
39
3.5b
Restaurants
22
Schools
33
Stores
33
Warehouses (storage)
0.25
11
0.5
Storage Spaces
0.25
Court Rooms
a
a
b
Motor Loads (Article 220.14(C)): Motor loads must be calculated in accordance with Articles 430.22,
430.24, and 440.6, summarized as follows:):
N The full load current rating for a single motor used in a continuous duty application is 125% of the motors
full-load current rating as determined by Article 430.6, which refers to horsepower/ampacity tables 430.247,
430.248, 430.249, or 430.250 as appropriate (Article 430.22).
N
The load calculation for several motors, or a motor(s) and other loads, is 125% of the full load current rating
of the highest rated motor per a.) above plus the sum of the full-load current ratings of all the other motors in
the group, plus the ampacity required for the other loads (Article 430.24).
Luminaires (lighting fixtures) (Article 220.14(D)): An outlet supplying luminaire(s) shall be calculated based upon
the maximum volt-ampere rating of the equipment and lamps for which the luminaire(s) is rated.
Heavy-Duty Lampholders (Article 220.14(E)): Loads f for heavy-duty lampholders must be calculated at a
minimum of 600 volt-amperes.
Sign and outline lighting (Article 220.14(F)): Sign and outline lighting loads shall be calculated at a minimum of
1200 volt-amperes for each required branch circuit specified in article 600.5(A).
Show windows (Article 220.14(G)): Show windows can be calculated in accordance with either:
N The unit load per outlet as required in other provisions of article 220.14.
N
Loads for fixed multioutlet assemblies in other than dwelling units or the guest rooms and guest suites of hotels
or motels must be calculated as follows (Article 220.14(H)):
N Where appliances are unlikely to be used simultaneously, each 1.5m (5 ft.) or fraction thereof of each
separate and continuous length must be considered as one outlet of 180 volt-amperes.
N
For hermetic refrigerant motor compressors or multi-motor equipment employed as part of air conditioning or
refrigerating equipment, the equipment nameplate rated load current should be used instead of the motor
horsepower rating (Article 440.6).
Where appliances are likely to be used simultaneously, each 300mm (1 ft.) or fraction thereof must be
considered as an outlet of 180 volt-amperes.
Receptacle outlets (Articles 220.14(I), 220.14(J), 220.14(K), 220.14(L)): Loads for these are calculated
as follows:
N Dwelling occupancies (Article 220.14(J)): In one-family, two-family, and multifamily dwellings and in guest
rooms or guest suites of hotels and motels, general-use receptacle outlets of 20A rating or less are included
in the general lighting load per above. No additional load calculations are required for these.
N
Banks and office buildings (Article 220.14(K)): Receptacle outlets must be calculated to be the larger of
either the calculated value per c.) below or 11 volt-amperes/square meter (1 volt-ampere per square ft.).
All other receptacle outlets (Article 220.14(I)): Each receptacle on one yoke must be calculated as
180 volt-amperes. A multiple receptacle consisting of four or more receptacles must be calculated at
90 volt-amperes per receptacle.
Sufficient branch circuits must be incorporated into the system design to serve the loads per Article 220.10
(summarized 1.) 8.) above), along with branch circuits for any specific loads not covered in Article 220.10.
The total number of branch circuits must be determined from the calculated load and the size or rating of the
branch circuits used. The load must be evenly proportioned among the branch circuits (Article 210.11(C)).
In addition, Article 210.11(C) requires several dedicated branch circuits as follows for dwelling units:
N Two or more 20A small-appliance branch circuits (Article 210.11(C)(1)).
N
Continuous Loads (Article 210.20): The rating of the overcurrent protection for a branch circuit must be at least
the sum of the non-continuous load +125% of the continuous load unless the overcurrent device is 100%-rated.
Because the rating of the overcurrent protection determines the rating of the branch circuit (Article 210.3), the
branch circuit must be sized for the non-continuous load +125% of the continuous load. In load calculations,
continuous loads should therefore be multiplied by 1.25 unless the circuit overcurrent device is 100% rated.
Note that motor loads are not included in this calculation as the 125% factor is already included in the applicable
sizing per above.
General Lighting Loads (Article 220.42): The feeder general lighting load can be calculated by multiplying the
branch circuit general lighting load calculated per B.) 1.) above, for those branch circuits supplied by the feeder,
by a demand factor per table 3-2 (NEC table 220.42).
Table 3-2: Lighting load feeder demand factors (NEC [3] table 220.42)
Type of Occupancy
Demand Factor
(Percent)
Dwelling units
100
35
25
Hospitals*
40
20
50
40
30
Warehouses (storage)
100
50
All others
Total volt-amperes
100
* The demand factors of this table shall not apply to the calculated load of feeders or services supplying areas in hospitals, hotels,
and motels where the entire lighting is likely to be used at one time, as in operating rooms, ballrooms, or dining rooms.
Show window or track lighting (Article 220.43): Show windows must use a calculated value of 660 voltamperes per linear meter (200 volt-amperes per linear foot), measured horizontally along its base. Track
lighting in other than dwelling units must be calculated at an 150 volt-amperes per 660mm (2 ft.) of lighting
track or fraction thereof.
Receptacles in other than dwelling units (Article 220.44): Demand factors for non-dwelling receptacle loads
are given in table 3-3 (NEC table 220.44).
Table 3-3: Demand factors for non-dwelling receptacle loads (NEC [3] table 220.44)
Portion of Receptacle Load to Which Demand Factor Applies (Volt-Amperes)
100
50
Motors (Article 220.50): The feeder demands for these are calculated as follows:
N The load calculation for several motors, or a motor(s) and other loads, is 125% of the full load current rating
of the highest rated motor per II.) B.) ii.) above plus the sum of the full-load current ratings of all the other
motors in the group, plus the ampacity required for the other loads (Article 430.24).
N
The load calculation for factory-wired multimotor and combination-load equipment should be based upon the
minimum circuit ampacity marked on the equipment (Article 430.25) instead of the motor horsepower rating.
Where allowed by the Authority Having Jurisdiction, feeder demand factors may be applied based upon the
duty cycles of the motors. No demand factors are given in the NEC for this situation.
Fixed Electric Space Heating (Article 220.51): The feeder loads for these must be calculated at 100% of
the connected load.
Noncoincident Loads (Article 220.60): Where it is unlikely that two or more noncoincident loads will be in use
simultaneously, it is permissible to use only the largest loads that will be used at one time to be used in
calculating the feeder demand.
Feeder neutral load (Article 220.61): The feeder neutral load is defined as the maximum load imbalance on the
feeder. The maximum load imbalance for three-phase four-wire systems is the maximum net calculated load
between the neutral and any one ungrounded conductor. A demand factor of 70% may be applied to this
calculated load imbalance. Refer to NEC article 220.61 for neutral reductions in systems other than
three-phase, four-wire systems. This demand factor does not apply to non-linear loads; in fact, it may be
necessary to oversize the neutral due to current flow from non-linear load triplen harmonics.
Continuous Loads (Article 215.3): The rating of the overcurrent protection for a feeder circuit must be at least
the sum of the non-continuous load +125% of the continuous load, unless the overcurrent device is 100%-rated.
Because the rating of the overcurrent protection determines the rating of the branch circuit (Article 210.3),
the branch circuit must be sized for the non-continuous load +125% of the continuous load. In the final feeder
circuit load calculation, the continuous portion of the load should therefore be multiplied by 1.25 unless the
overcurrent device for the circuit is 100%-rated. Note that motor loads are not included in this calculation as the
125% factor is already included in the applicable sizing per above.
Additional calculation data is given in NEC Article 220 for dwelling units, restaurants, schools, and farms. This
data is not repeated here. Refer to NEC Article 220 for details.
As this guide only presents the basic NEC requirements for load calculations, it is imperative to refer to the NEC
itself when in doubt about a specific load sizing application. Computer programs are commercially available to
automate the calculation of feeder and branch circuit loads per the NEC methodology described above.
References
Because the subject matter for this section is basic and general to the subject of electrical engineering, it is
included in most undergraduate textbooks on basic circuit analysis and electric machines. Where material is
considered so basic as to be axiomatic no attempt has been made to cite a particular source for it.
For material not covered per the above, references specifically cited in this section are:
[1]
IEEE Recommended Practice for Electric Power Distribution for Industrial Plants,
IEEE Standard 141-1993, December 1993.
[2]
Turan Gonen, Electric Power Distribution System Design, New York: McGraw-Hill, 1986, pp. 37-51.
[3]
The National Electrical Code, NFPA 70, The National Fire Protection Association, Inc., 2005 Edition.
[4]
Section 4:
Basic Principles
The selection of system voltages is crucial to successful power system design. Reference [1] lists the standard
voltages for the United States and their ranges. The nominal voltages from [1] are given in table 4-1.
As can be seen, ANSI C84.1-1989 divides system voltages into voltage classes. Voltages 600 V and below are
referred to as low voltage, voltages from 600 V-69 kV are referred to as medium voltage, voltages from
69 kV-230 kV are referred to as high voltage and voltages 230 kV-1,100 kV are referred to as extra high
voltage, with 1,100 kV also referred to as ultra high voltage. The emphasis of this guide is on low and
medium voltage distribution systems.
Table 4-1: Standard nominal three-phase system voltages per ANSI C84.1-1989
Voltage Class
Three-wire
Low Voltage
240
480
600
Medium Voltage
2,400
4,160
4,800
6,900
13,800
Four-wire
208 Y/120
240/120
480 Y/277
4,160 Y/2400
8,320 Y/4800
12,000 Y/6,930
12,470 Y/7,200
13,200 Y/7,620
13,800 Y/7,970
20,780 Y/12,000
22,860 Y/13,200
23,000
34,500
46,000
69,000
High Voltage
115,000
138,000
161,000
230,000
Extra-High Voltage
345,000
500,000
765,000
Ultra-High Voltage
1,100,000
24,940 Y/14,400
34,500 Y/19,920
The choice of service voltage is limited to those voltages which the serving utility provides. In most cases only one
choice of electrical utility is available, and thus only one choice of service voltage. As the power requirements
increase, so too does the likelihood that the utility will require a higher service voltage for a given installation.
In some cases a choice may be given by the utility as to the service voltage desired, in which case an analysis of
the various options would be required to arrive at the correct choice. In general, the higher the service voltage the
more expensive the equipment required to accommodate it will be. Maintenance and installation costs also
increase with increasing service voltage. However, equipment such as large motors may require a service voltage
of 4160 V or higher, and, further, service reliability tends to increase at higher service voltages.
Another factor to consider regarding service voltage is the voltage regulation of the utility system. Voltages defined
by the utility as distribution should, in most cases, have adequate voltage regulation for the loads served.
Voltages defined as subtransmission or transmission, however, often require the use of voltage regulators or
load-tap changing transformers at the service equipment to give adequate voltage regulation. This situation
typically only occurs for service voltages above 34.5 kV, however it can occur on voltages between 20 kV and
34.5 kV. When in doubt the serving utility should be consulted.
The utilization voltage is determined by the requirements of the served loads. For most industrial and commercial
facilities this will be 480 Y/277 V, although 208 Y/120 V is also required for convenience receptacles and small
machinery. Large motors may require 4160 V or higher. Distribution within a facility may be 480 Y/277 V or, for
large distribution systems, medium voltage distribution may be required. Medium voltage distribution implies a
medium voltage (or higher) service voltage, and will result in higher costs of equipment, installation, and
maintenance than low voltage distribution. However, this must be considered along with the fact that medium
voltage distribution will generally result in smaller conductor sizes and will make control of voltage drop easier.
Power equipment ampacity limitations impose practical limits upon the available service voltage to serve a given
load requirement for a single service, as shown in table 4-2.
is the voltage drop along a length of conductor or across a piece of equipment in volts
is the load current in amperes
is the conductor or equipment impedance, in ohms
Thus, the larger the load current and larger the conductor impedance, the larger the voltage drop.
Unbalanced loads will, of course, give an unbalanced voltage drop, which will lead to an unbalanced voltage
at the utilization equipment.
A voltage drop of 5% or less from the utility service to the most remotely-located load is recommended by NEC
article 210.19(A)(1), FPN No. 4. Because this is a note only, it is not a requirement per se but is the commonly
accepted guideline.
Table 4-2: Power equipment design limits to service voltage vs. load requirements,
for a single service
Voltage (V)
Equipment Type
Maximum Equipment
Ampacity (A)
5000
1,800
4,157
5,196
208
480
600
2,400
4,160
4,800
Metal-Enclosed Switchgear,
w/Fuses 69,000
6,900
8,320
12,000
12,470
13,200
13,800
Metal-Enclosed Switchgear,
w/Fuses
720
8,605
10,376
14,965
15,551
16,461
17,210
20,780
22,860
23,000
24,940
Metal-Enclosed Switchgear,
w/Fuses
175
6,299
6,929
6,972
7,560
34,500
Metal-Enclosed Switchgear,
w/Fuses
115
6,872
2,400
4,160
4,800
6,900
8,320
12,000
12,470
13,200
13,800
Metal-Clad Switchgear
3000
12,471
21,616
24,942
38,853
43,232
62,354
64,796
68,589
71,707
20,780
22,860
23,000
24,940
Metal-Clad Switchgear
2000
71,984
79,189
79,674
86,395
1080
4,489
7,782
8,979
Because conductor impedance increases with the length of the conductor, it can be seen that unless the power
source is close to the center of the load the voltage will vary across the system, and, further, it can be more costly
to maintain the maximum voltage drop across the system to within 5% of the service voltage since larger
conductors must be used to offset longer conductor lengths.
Also from equation (4-1) it can be seen that as load changes, so does the voltage drop. For a given maximum
load, a measure of this change at a given point is the voltage regulation, defined as
(4-2)
where
Vno load
Vload
is the voltage, at a given point in the system, with no load current flowing from that point to the load.
is the voltage, at the same point in the system, with full load current flowing from that point to the load.
Another source of concern when planning for voltage drop is the use of power-factor correction capacitors.
Because these serve to reduce the reactive component of the load current they will also reduce the voltage drop
per equation (4-1).
Both low and high voltage conditions, and voltage imbalance, have an adverse effect on utilization equipment (see
[2] for additional information). Voltage drop must therefore be taken into account during power system design to
avoid future problems.
References
[1]
American National Standard Preferred Voltage Ratings for Electric Power Systems and Equipment (60 Hz),
ANSI C84.1-1989.
[2]
IEEE Recommended Practice for Electric Power Distribution for Industrial Plants, IEEE Standard 141-1993,
December 1993.
Section 5:
System Arrangements
Introduction
The selection of system arrangement has a profound impact upon the reliability and maintainability of the system.
Several commonly-used system topologies are presented here, along with the pros and cons of each. The figures
for each of these assume that the distribution and utilization voltage are the same, and that the service voltage
differs from the distribution/utilization voltage. The symbology (low voltage circuit breaker, low voltage drawout
circuit breaker, medium voltage switch, medium voltage breaker) reflects the most commonly-used equipment for
each arrangement. The symbology used throughout this section is shown in figure 5-1:
Radial system
The radial system is the simplest system topology, and is shown in figure 5-2. It is the least expensive in terms of
equipment first-cost. However, it is also the least reliable since it incorporates only one utility source and the loss
of the utility source, transformer, or the service or distribution equipment will result in a loss of service. Further, the
loads must be shut down in order to perform maintenance on the system. This arrangement is most commonly
used where the need for low first-cost, simplicity, and space economy outweigh the need for enhanced reliability.
Typical equipment for this system arrangement is a single unit substation consisting of a fused primary switch,
a transformer of sufficient size to supply the loads, and a low voltage switchboard.
An automatic transfer scheme may optionally be provided between the two primary switches to
automatically switch from a failed utility source to an available source. Most often metal-clad circuit
breakers are used, rather than metal-enclosed switches, if this is the case. More about typical
equipment application guidelines follows in a subsequent section of this guide.
Figure 5-4: Expanded Radial System with one utility source and a single primary feeder
A more reliable and maintainable arrangement utilizing multiple primary feeders is shown in figure 5-5. In the
system of figure 5-5, each unit substation is supplied by a dedicated feeder from the service entrance switchgear.
Each substation is also equipped with a primary disconnect switch to allow isolation of each feeder on both ends
for maintenance purposes.
Typical service entrance equipment consists of a metal-clad switchgear main circuit breaker and metal-enclosed
fused feeder switches. Metal-Clad circuit breakers may be used instead of metal-enclosed feeder switches
if required.
Figure 5-5: Expanded Radial System with one utility source and multiple primary feeders
Figure 5-6 shows an expanded radial system utilizing multiple substations and two utility sources, again with
metal-clad primary switchgear but with a duplex metal-enclosed switchgear for utility source selection:
Figure 5-6: Expanded Radial System with two utility sources and multiple primary feeders
Of the arrangements discussed this far, the arrangement of figure 5-6 is the most reliable it does not depend
upon a single utility source for system availability, nor does the failure of one transformer or feeder cause a loss of
service to the entire facility. However, the loss of a transformer or feeder will result in the loss of service to a part
of the facility. More reliable system arrangements are required if this is to be avoided.
Loop system
The loop system arrangement is one of several arrangements that can allow one system component, such as a
transformer or feeder cable, to fail without causing a loss of service to a part of the facility.
Figure 5-7 shows a primary loop arrangement. The advantages of this arrangement over previously-mentioned
arrangements are that a failure of one feeder cable will not cause one part of the facility to experience a loss of
service and that one feeder cable can be maintained without causing a loss of service (note that an outage to part
of the system will be experienced after the failure of a feeder cable until the loop is switched to accommodate the
loss of the cable).
In figure 5-7 metal-clad circuit breakers are used as the feeder protective devices. Fused metal-enclosed-feeder
switches could be utilized for this, but caution must be used if this is considered since the feeder fuses would
have to be able to serve both transformers and the feeder and transformer fuses would have to coordinate for
maximum selectivity.
It must be noted that the system arrangement of figure 5-7 is designed to be operated with the loop open, i.e., one
of the four loop switches shown would be normally-open. If closed-loop operation were required, metal-clad circuit
breakers should be used instead to provide maximum selectivity (this arrangement is discussed further below).
Momentary paralleling to allow maintenance of one section of the loop without causing an outage to one part of
the facility can be accomplished with metal-enclosed loop switches, however, if caution is used in the system
design and maintenance.
Secondary-Selective system
Another method of allowing the system to remain in service after the failure of one component is the secondaryselective system. Figure 5-8 shows such an arrangement.
The system arrangement of figure 5-8 has the advantage of allowing one transformer to fail without causing a loss
of service to one part of the plant. This is a characteristic none of the previously-mentioned system arrangements
exhibit. The system can be run with the secondary bus tie breaker normally-open or normally-closed. If the bus tie
breaker is normally-closed the failure of one transformer, if directional overcurrent relays are supplied on the
transformer secondary main circuit breakers, will not cause an outage, however care must be taken in the system
design as the available fault current at the secondary switchgear can be doubled in this case.
Typical equipment for this arrangement is low voltage power circuit-breaker switchgear with drawout circuit
breakers, both for reasons of coordination and maintenance. However, a low voltage switchboard may be utilized
also if care is taken in the system design and the system coordination is achievable. For a normally-closed bus tie
breaker, low voltage power switchgear is essential since the breakers lend themselves more readily external
protective relaying.
Note that if one transformer fails the other transformer and its associated secondary main circuit must carry the
entire load. This must be taken into account in sizing the transformer and secondary switchgear for this type of
system to be effective.
A larger-scale version of the secondary selective system is the transformer sparing scheme, as shown in figure 9.
This type of system allows good flexibility in switching. The system is usually operated with all of the secondary tie
breakers except one (the sparing transformer secondary main/tie breaker) normally-open. The sparing transformer
5
secondary main/tie breaker) normally-open. The sparing transformer supplies one load bus if a transformer fails or
is taken off-line for maintenance. A transformer is switched out of the circuit by opening its secondary main
breaker and closing the tie breaker to allow the sparing transformer to feed its loads. The sparing transformer may
be allowed to feed multiple load busses if it is sized properly. Care must be used when allowing multiple
transformers to be paralleled as the fault current is increased with each transformer that is paralleled, and
directional relaying is required on the secondary main circuit breakers to selectively isolate a faulted transformer.
An electrical or key interlock scheme is required to enforce the proper operating modes of this type of system,
especially in light of the fact that the switching is carried out over several pieces of equipment that can be in
different locations from one another. A properly-designed interlocking system will allow for the addition of future
substations without modification of the existing interlocking.
With both types of secondary-selective system, an automatic transfer scheme may be utilized to switch between a
failed transformer and an available transformer.
Primary-Selective system
A selective system arrangement may also utilize the primary system equipment. Such an arrangement is shown in
figure 5-10.
As with the secondary selective system, an automatic transfer scheme may be used to automatically perform
the required transfer operations, should a utility source become unavailable. The bus tie circuit breaker may be
normally-closed or normally-open, depending upon utility allowances. If the bus tie circuit breaker is
normally-closed care must be taken in the protective relaying to insure that a fault on one utility line does not
cause the entire system to be taken off-line. The available fault current with the tie breaker normally closed
increases with each utility service added to the system.
Metal-Clad switchgear is most commonly used with this type of arrangement, due to the limitations of
metal-enclosed load interrupter switches.
Composite systems
The above system arrangements are the basic building blocks of power distribution system topologies, but are
rarely used alone for a given system. To increase system reliability it is usually necessary to combine two or more
of these arrangements. For example, one commonly-used arrangement is shown in figure 5-13.
As can be seen, a fault on a primary loop cable or the failure of one transformer can be accommodated without
loss of service to either load bus (but with an outage to part of the system until the system is switched to
accommodate the failure). In addition, a single section of the primary loop or one transformer can be taken out of
service while maintaining service to the loads.
The system of figure 5-13 can be expanded by the addition of an additional utility source and a primary bus tie
breaker to form an even more reliable system, as shown in figure 5-14. With this arrangement, the failure of a
single utility source, a single primary circuit breaker, a single loop feeder cable, or a single transformer can be
accommodated without loss of service. And, any one primary circuit breaker, any one section of the primary
distribution loop, or any one transformer can be taken out of service without loss of service to the loads.
However, the cost of a second utility service and two additional metal-clad breakers must be taken into account.
A logical expansion of this system, resulting in a further increase in system reliability, can be had by replacing the
primary distribution loop with dedicated feeder circuit breakers from each primary bus, as shown in figure 5-15. In
this system arrangement multiple primary feeder cable failures can be accommodated without jeopardizing service
to the loads (an outage will be taken until the system is switched to accommodate the failures, however).
An example of an extremely reliable system arrangement is given in figure 16. Note that figure 5-16 is a
re-arrangement of the primary ring-bus configuration shown in figure 5-12, along with the primary source-selective
configuration shown in figure 5-3 and a variant of the transformer sparing scheme given in figure 5-9. This system
arrangement gives good flexibility in switching for maintenance purposes, and also allows any one utility, primary
switchgear bus, or transformer fail without loss of service to any of the loads (again, an outage may be taken until
the system is switched to accommodate the failure, depending upon the failure under consideration). It also allows
any three primary feeders to be faulted without loss of service to any of the loads. Other composite arrangements
are possible.
Summary
Various system arrangements have been presented in this section, starting with the least complex and
progressing to a very complex, robust system arrangement. In general, as reliability increases so does complexity
and cost. It must be remembered that economic considerations will usually dictate how complex a system
arrangement can be used, and thus will have a great deal of impact on how reliable the system is. Tables 5-6 and
5-7 show the features of each system arrangement given in this section.
Please note that the formulas given in these tables are for the systems as shown in the figures above. They will
hold true for expanded versions of these system arrangements where the expansion is made symmetrically
with respect to the configuration shown. They will not hold true when modifications are made to the system
arrangements with respect to symmetry, with altered numbers of switching/protective devices, or for concurrent
failures of different types of system components. When in doubt regarding a system which is derived from,
but not identical, to the systems shown in the figures above, double-check these numbers.
From a maintenance perspective, the number of system elements that can be taken down for maintenance is the
same as the number that can fail while maintaining service to the loads.
These tables do not attempt to address concurrent failures of different types of system components, nor are they
a guarantee of loss of service to a particular load after a component failure while the system is being switched to
an alternate configuration. However, they are a guide to the relative strengths and weaknesses of each of the
system arrangements presented.
Table 5-6: Power system arrangement summary for the basic arrangements as shown
in this section
U
PB
SF
T
SB
$
Arrangement
Utility
Failures
Allowed
Pri. Bkr
Failures
Allowed
Pri. Feeder
Failures
Allowed
Transformer
Failures
Allowed
Sec.
Main/Tie
Bkr
Failures
Allowed
U-1 O
$+
Expanded Radial,
Single Primary Feeder
$$
Expanded Radial,
Multiple Primary Feeders
$$
Expanded Radial,
Multiple Utility Sources,
Multiple Primary Feeders
U-1 O
$$+
$$$
Secondary-Selective System
$$$
Varies;
Maximum of T-1
TL
$$$$
U-1 O,N
PB-F-U O,N,
$$$$$
U-1 O,N,$,
PB-1 O,N,$,
F-1 O,N,$,
T-1 O,N,$,
SB-1 O,N,$,
$$$$$
U-1 O,N,M
U O,N,,M
$$$$$$
Radial
Radial w/ Primary Selectivity
Primary Selective
Assumes that each utility source has sufficient capacity to supply the entire system.
Assumes that all secondary circuit breakers, including feeder breakers, are interchangeable.
N Assumes that each primary main and bus tie (if applicable) circuit breakers has sufficient capacity to
supply the entire system.
Assumes that all primary circuit breakers, including feeder breakers, are interchangeable.
$ Assumes that each primary feeder has sufficient capacity to supply the entire system.
Assumes that each transformer, secondary main and bus tie (if applicable) circuit breaker have sufficient
capacity to supply the entire system.
M Assumes that the ring bus has sufficient capacity to supply the entire system.
L
10
Cost
Table 7:
Arrangement
Utility
Failures
Allowed
Pri. Bkr
Failures
Allowed
Pri. Feeder
Failures
Allowed
Transformer
Failures
Allowed
Sec.
Main/Tie
Bkr
Failures
Allowed
Primary Double-Selective /
Secondary-Selective
U-1 O,N
PB-F/2-U
F/2
T-1
T-1 ,L
$$$$$$$$
F/2
T-1
T ,L
$$$$$$$$+
Cost
O,N,
U-1 O,N,M
PB-F/2-U+1
O,N,,M
Assumes that each utility source has sufficient capacity to supply the entire system.
Assumes that all secondary circuit breakers, including feeder breakers, are interchangeable.
N Assumes that each primary main and bus tie (if applicable) circuit breakers has sufficient capacity to
supply the entire system.
Assumes that all primary circuit breakers, including feeder breakers, are interchangeable.
$ Assumes that each primary feeder has sufficient capacity to supply the entire system.
Assumes that each transformer, secondary main and bus tie (if applicable) circuit breaker have sufficient
capacity to supply the entire system.
M Assumes that the ring bus has sufficient capacity to supply the entire system.
L
11
Section 6:
System Grounding
Introduction
The topic of system grounding is extremely important, as it affects the susceptibility of the system to voltage
transients, determines the types of loads the system can accommodate, and helps to determine the system
protection requirements.
The system grounding arrangement is determined by the grounding of the power source. For commercial and
industrial systems, the types of power sources generally fall into four broad categories:
A Utility Service The system grounding is usually determined by the secondary winding configuration of the
upstream utility substation transformer.
B Generator The system grounding is determined by the stator winding configuration.
C Transformer The system grounding on the system fed by the transformer is determined by the transformer
secondary winding configuration.
D Static Power Converter For devices such as rectifiers and inverters, the system grounding is determined by
the grounding of the output stage of the converter.
Categories A to D fall under the NEC definition for a separately-derived system. The recognition of a separatelyderived system is important when applying NEC requirements to system grounding, as discussed below.
All of the power sources mentioned above except D are magnetically-operated devices with windings.
To understand the system voltage relationships with respect to system grounding, it must be recognized that there
are two common ways of connecting device windings: wye and delta. These two arrangements, with their system
voltage relationships, are shown in figure 6-1. As can be seen from the figure, in the wye-connected arrangement
there are four terminals, with the phase-to-neutral voltage for each phase set by the winding voltage and the
resulting phase-to-phase voltage set by the vector relationships between the voltages. The delta configuration
has only three terminals, with the phase-to-phase voltage set by the winding voltages and the neutral terminal
not defined.
Neither of these arrangements is inherently associated with any particular system grounding arrangement,
although some arrangements more commonly use one arrangement vs. the other for reasons that will be
explained further below.
Figure 6-1: Wye and delta winding configurations and system voltage relationships
Solidly-grounded systems
The solidly-grounded system is the most common system arrangement, and one of the most versatile. The
most commonly-used configuration is the solidly-grounded wye, because it will support single-phase phase-toneutral loads.
The solidly-grounded wye system arrangement can be shown by considering the neutral terminal from the
wye system arrangement in figure 6-1 to be grounded. This is shown in figure 6-2:
The delta arrangement can be configured in another manner, however, that does have merits as a solidlygrounded system. This arrangement is shown in figure 6-4. While the arrangement of figure 6-4 may not appear at
first glance to have merit, it can be seen that this system is suitable both for three-phase and single-phase loads,
so long as the single-phase and three-phase load cables are kept separate from each other. This is commonly
2
used for small services which require both 240 VAC three-phase and 120/240 VAC single-phase. Note that the
phase A voltage to ground is 173% of the phase B and C voltages to ground. This arrangement requires the BC
winding to have a center tap.
A common characteristic of all three solidly-grounded system shown here, and of solidly-grounded systems in
general, is that a short-circuit to ground will cause a large amount of short-circuit current to flow. This condition is
known as a ground fault and is illustrated in figure 6-5. As can be seen from figure 6-5, the voltage on the faulted
phase is depressed, and a large current flows in the faulted phase since the phase and fault impedance are small.
The voltage and current on the other two phases are not affected. The fact that a solidly-grounded system will
support a large ground fault current is an important characteristic of this type of system grounding and does affect
the system design. Statistically, 90-95% of all system short-circuits are ground faults so this is an important topic.
The practices used in ground-fault protection are described in a later section of this guide.
The occurrence of a ground fault on a solidly-grounded system necessitates the removal of the fault as quickly
as possible. This is the major disadvantage of the solidly-grounded system as compared to other types of
system grounding.
A solidly-grounded system is very effective at reducing the possibility of line-to-ground voltage transients.
However, to do this the system must be effectively grounded. One measure of the effectiveness of the
system grounding is the ratio of the available ground-fault current to the available three-phase fault current.
For effectively-grounded systems this ratio is usually at least 60% [2].
Most utility systems which supply service for commercial and industrial systems are solidly grounded. Typical
utility practice is to ground the neutral at many points, usually at every line pole, creating a multi-grounded neutral
system. Because a separate grounding conductor is not run with the utility line, the resistance of the earth limits
the circulating ground currents that can be caused by this type of grounding. Because separate grounding
conductors are used inside a commercial or industrial facility, multi-grounded neutrals not preferred for power
systems in these facilities due to the possibility of circulating ground currents. As will be explained later in this
section, multi-grounded neutrals in NEC jurisdictions, such as commercial or industrial facilities, are actually
prohibited in most cases by the NEC [1]. Instead, a single point of grounding is preferred for this type of system,
creating a uni-grounded or single-point grounded system.
In general, the solidly-grounded system is the most popular, is required where single-phase phase-to-neutral loads
must be supplied, and has the most stable phase-to-ground voltage characteristics. However, the large ground
fault currents this type of system can support, and the equipment that this necessitates, are a disadvantage and
can be hindrance to system reliability.
Ungrounded systems
This system grounding arrangement is at the other end of the spectrum from solidly-grounded systems.
An ungrounded system is a system where there is no intentional connection of the system to ground.
The term ungrounded system is actually a misnomer, since every system is grounded through its inherent
charging capacitance to ground. To illustrate this point and its effect on the system voltages to ground, the delta
winding configuration introduced in figure 6-3 is re-drawn in figure 6-6 to show these system capacitances.
If all of the system voltages in figure 6-6 are multiplied by 3 and all of the phase angles are shifted by 30 (both
are reasonable operations since the voltage magnitudes and phase angles for the phase-to-phase voltage were
arbitrarily chosen), the results are the same voltage relationships as shown in figure 6-4 for the solidly-grounded
wye system. The differences between the ungrounded delta system and the solidly-grounded wye system, then,
are that there is no intentional connection to ground, and that there is no phase-to-neutral driving voltage on the
ungrounded delta system. This becomes important when the effects of a ground fault are considered. The lack of
a grounded system neutral also makes this type of system unsuitable for single-phase phase-to-neutral loads.
Figure 6-6: Ungrounded Delta System winding arrangement and voltage relationships
In figure 6-7, the effects of a single phase to ground fault are shown. The equations in figure 6-7 are not
immediately practical for use, however if the fault impedance is assumed to be zero and the system capacitive
charging impedance is assumed to be much larger than the phase impedances, these equations reduce into a
workable form. Figure 6-8 shows the resulting equations, and shows the current and voltage phase relationships.
As can be seen from figure 6-8, the net result of a ground fault on one phase of an ungrounded delta system is a
change in the system phase-to-ground voltages. The phase-to-ground voltage on the faulted phase is zero, and
the phase-to-ground voltage on the unfaulted phases are 173% of their nominal values. This has implications for
power equipment the phase-to-ground voltage rating for equipment on an ungrounded system must be at least
equal the phase-to-phase voltage rating. This also has implications for the methods used for ground detection, as
explained later in this guide.
4
Figure 6-8: Ungrounded Delta System simplified ground fault voltage and current relationships
The ground currents with one phase is faulted to ground are essentially negligible. Because of this fact, from an
operational standpoint ungrounded systems have the advantage of being able to remain in service if one phase is
faulted to ground. However, suitable ground detection must be provided to alarm this condition (and is required in
most cases by the NEC [1] as described below). In some older facilities, it has been reported that this type of
system has remained in place for 40 years or more with one phase grounded! This condition is not dangerous in
and of itself (other than due to the increased phase-to-ground voltage on the unfaulted phases), however if a
ground fault occurs on one of the ungrounded phases the result is a phase-to-phase fault with its characteristic
large fault current magnitude.
Another important consideration for an ungrounded system is its susceptibility to large transient overvoltages.
These can result from a resonant or near-resonant condition during ground faults, or from arcing [2]. A resonant
ground fault condition occurs when the inductive reactance of the ground-fault path approximately equals the
system capacitive reactance to ground. Arcing introduces the phenomenon of current-chopping, which can cause
excessive overvoltages due to the system capacitance to ground.
The ground detection mentioned above can be accomplished through the use of voltage transformers connected
in wye-broken delta, as illustrated in figure 6-9.
A
VT
LT A
VT
LT B
LT M
VT
LT C
GROUND
FAULT
LOCATION
LTA
LTB
LTC
NONE
DIM
DIM
DIM
OFF
PHASE A
OFF
BRIGHT
BRIGHT
BRIGHT
PHASE B
BRIGHT
OFF
BRIGHT
BRIGHT
PHASE C
BRIGHT
BRIGHT
DIM
BRIGHT
LTM
In figure 6-9, three ground detection lights LTA, LTB and LTC are connected so that they indicate the A, B and
C phase-to-ground voltages, respectively. A master ground detection light LTM indicates a ground fault on any
phase. With no ground fault on the system LTA, LTB and LTB will glow dimly. If a ground fault occurs on one
phase, the light for that phase will be extinguished and LTM will glow brightly along with the lights for the other
two phases. Control relays may be substituted for the lights if necessary. Resistor R is connected across the
broken-delta voltage transformer secondaries to minimize the possibility of ferroresonance. Most ground detection
schemes for ungrounded systems use this system or a variant thereof.
Note that the ground detection per figure 6-10 indicates on which phase the ground fault occurs, but not
where in the system the ground fault occurs. This, along with the disadvantages of ungrounded systems
due to susceptibility to voltage transients, was the main impetus for the development of other ground
system arrangements.
Modern power systems are rarely ungrounded due to the advent of high-resistance grounded systems as
discussed below. However, older ungrounded systems are occasionally encountered.
The resistor is sized to be less than or equal to the magnitude of the system charging capacitance to ground. If
the resistor is thus sized, the high-resistance grounded system is usually not susceptible to the large transient
overvoltages that an ungrounded system can experience. The ground resistor is usually provided with taps to
allow field adjustment of the resistance during commissioning.
If no ground fault current is present, the phasor diagram for the system is the same as for a solidly-grounded wye
system, as shown in figure 6-10. However, if a ground fault occurs on one phase the system response is as
shown in figure 6-11. As can be seen from figure 6-11, the ground fault current is limited by the grounding resistor.
If the approximation is made that ZA and ZF are very small compared to the ground resistor resistance value R,
which is a good approximation if the fault is a bolted ground fault, then the ground fault current is approximately
equal to the phase-to-neutral voltage of the faulted phase divided by R. The faulted phase voltage to ground in
that case would be zero and the unfaulted phase voltages to ground would be 173% of their values without a
ground fault present. This is the same phenomenon exhibited by the ungrounded system arrangement, except
that the ground fault current is larger and approximately in-phase with the phase-to-neutral voltage on the faulted
phase. The limitation of the ground fault current to such a low level, along with the absence of a solidly-grounded
system neutral, has the effect of making this system ground arrangement unsuitable for single-phase line-toneutral loads.
Figure 6-11: High-Resistance Grounded System with a ground fault on one phase
The ground fault current is not large enough to force its removal by taking the system off-line. Therefore, the
high-resistance grounded system has the same operational advantage in this respect as the ungrounded system.
However, in addition to the improved voltage transient response as discussed above, the high-resistance
grounded system has the advantage of allowing the location of a ground fault to be tracked.
A typical ground detection system for a high-resistance grounded system is illustrated in figure 6-12. The ground
resistor is shown with a tap between two resistor sections R1 and R2. When a ground fault occurs, relay 59 (the
ANSI standard for an overvoltage relay, as discussed later in this guide) detects the increased voltage across the
resistor. It sends a signal to the control circuitry to initiate a ground fault alarm by energizing the alarm indicator.
When the operator turns the pulse control selector to the ON position, the control circuit causes pulsing contact
P to close and re-open approximately once per second. When P closes R2 is shorted and the pulse indicator is
energized. R1 and R2 are sized so that approximately 5-7 times the resistor continuous ground fault current flows
when R2 is shorted. The result is a pulsing ground fault current that can be detected using a clamp-on ammeter
(an analog ammeter is most convenient). By tracing the circuit with the ammeter, the ground fault location can be
determined. Once the ground fault has been removed from the system pressing the alarm reset button will
de-energize the alarm indicator.
This type of system is known as a pulsing ground detection system and is very effective in locating ground
faults, but is generally more expensive than the ungrounded system ground fault indicator in figure 6-10.
For medium voltage systems, high-resistance grounding is usually implemented using a low voltage resistor and
a neutral transformer, as shown in figure 6-13.
Reactance grounding
In industrial and commercial facilities, reactance grounding is commonly used in the neutrals of generators. In
most generators, solid grounding may permit the level of ground-fault current available from the generator to
exceed the three-phase value for which its windings are braced [2]. For these cases, grounding of the generator
neutral through an air-core reactance is the standard solution for lowering the ground fault level. This reactance
ideally limits the ground-fault current to the three-phase available fault current and will allow the system to operate
with phase-to-neutral loads.
The solution is a grounding transformer. Although several different configurations exist, by far the most popular in
commercial and industrial system is the zig-zag transformer arrangement. It uses transformers connected as
shown in figure 6-14:
The zig-zag transformer will only pass ground current. Its typical implementation on an ungrounded system, in
order to convert the system to a high-resistance grounded system, is shown in figure 6-15. The zig-zag
transformer distributes the ground current IG equally between the three phases. For all practical purposes the
system, from a grounding standpoint, behaves as a high-resistance grounded system.
The solidly-grounded and low-resistance grounded systems can also be implemented by using a grounding
transformer, depending upon the amount of impedance connected in the neutral.
10
With these terms defined, several of the major components of the grounding system can be illustrated by
redrawing the system of figure 6-2 and labeling the components:
Several key design constraints for grounding systems from the NEC [1] are as follows. These are paraphrased
from the code text (Note: This guide is not intended as a substitute for familiarity with the NEC, nor is it intended
as an authoritative interpretation of every aspect of the NEC articles mentioned.):
I
Electrical systems that are grounded must be grounded in such a manner as to limit the voltage imposed by
lightning, line surges, or unintentional contact with higher voltage lines and that will stabilize the voltage to earth
during normal operation [Article 250.4(A)(1)]. In other words, if a system is considered solidly grounded the
ground impedance must be low.
If the system can be solidly grounded at 150 V to ground or less, it must be solidly grounded [Article 250.20(B)].
There is therefore no such system as a 120 V Ungrounded Delta in use, even though such a system is
physically possible.
If the system neutral carries current it must be solidly grounded [Article 250.20(B)]. This is indicative of
single-phase loading and is typical for a 4-wire wye (such as figure 6-2) or center-tapped 4-wire delta
(such as figure 6-4) system.
Certain systems are permitted, but not required, to be solidly grounded. They are listed as electric systems used
exclusively to supply industrial electric furnaces for melting, refining, tempering, and the like, separately derived
systems used exclusively for rectifiers that supply only adjustable-speed industrial drives, and separately
derived systems supplied by transformers that have a primary voltage rating less than 1000 volts provided that
certain conditions are met [Article 250.21].
If a system 50-1000 VAC is not solidly-grounded, ground detectors must be installed on the system unless the
voltage to ground is less than 120 V [Article 250.21].
Certain systems cannot be grounded. They are listed as circuits for electric cranes operating over combustible
fibers in Class III locations as provided in Article 503.155, circuits within hazardous (classified) anesthetizing
locations and other isolated power systems in health care facilities as provided in 517.61 and 517.160, circuits
for equipment within electrolytic cell working zone as provided in Article 668, and secondary circuits of lighting
systems as provided in 411.5(A) [Article 250.22]. Some of the requirements for hazardous locations and health
care facilities are covered in section XVI.
For solidly-grounded systems, an unspliced main bonding jumper must be used to connect the equipment
grounding conductor(s) and the service disconnect enclosure to the grounded conductor within the enclosure
for each utility service disconnect [Article 250.24(B)].
For solidly-grounded systems, an unspliced system bonding jumper must be used to connect the equipment
grounding conductor of a separately derived system to the grounded conductor. This connection must be made
at any single point on the separately derived system from the source to the first system disconnecting means or
overcurrent device [250.30(A)(1)]
A grounding connection on the load side of the main bonding or system bonding jumper on a solidly-grounded
system is not permitted [Articles 240.24(A)(5), 250.30(A)]. The reasons for this are explained in below and in
section VIII.
11
Ground fault protection of equipment must be provided for solidly grounded wye electrical services, feeder
disconnects on solidly-grounded wye systems, and building or structure disconnects on solidly-grounded wye
systems under the following conditions:
N The voltage is greater than 150 V to ground, but does not exceed 600 V phase-to-phase.
N
The utility service, feeder, or building or structure disconnect is rated 1000 A or more.
The disconnect in question does not supply a fire pump or continuous industrial process.
Where ground fault protection is required per Article 215.10 or 230.95 for a health care facility, an additional step
of ground fault protection is required in the next downstream device toward the load, with the exception of
circuits on the load side of an essential electrical system transfer switch and between on-site generating units for
the essential electrical system and the essential electrical system transfer switches [Article 517.17]. Specific
requirements for health-care systems are described in a later section of this guide.
The alternate source for an emergency or legally-required standby system is not required to have ground fault
protection. For an emergency system, ground-fault indication is required [Articles 700.26, 701.17]. A later
section of this guide describes the requirements for Emergency and Standby Power Systems.
All electrical equipment, wiring, and other electrically conductive material must be installed in a manner that
creates a permanent, low-impedance path facilitating the operation of the overcurrent device. This circuit must
be able to safely carry the ground fault current imposed upon it. [Article 250.4(A)(5)]. The intent of this
requirement is to allow ground fault current magnitudes to be sufficient for the ground fault protection/detection
to detect (and for ground fault protection to clear) the fault, and for a ground fault not to cause damage to the
grounding system.
[Article 250.36]
I
The system neutral derived from a grounding transformer may be used for grounding [Article 250.182].
The minimum insulation level for the neutral of a solidly-grounded system is 600 V. A bare neutral is
permissible under certain conditions [Article 250.184 (A) (1)].
Impedance grounded neutral systems may be used where conditions 1, 3, and 4 for the use of highimpedance grounding on systems 480-1000 V above are met [Article 250.186].
The neutral conductor must be identified and fully insulated with the same phase insulation as the phase
conductors [Article 250.186 (B)].
Zig-zag grounding transformers must not be installed on the load side of any system grounding connection
[Article 450.5].
When a grounding transformer is used to provide the grounding for a 3 phase 4 wire system, the grounding
transformer must not be provided with overcurrent protection independent of the main switch and common-trip
overcurrent protection for the 3 phase, 4 wire system [Article 450.5 (A) (1)]. An overcurrent sensing device must
be provided that will cause the main switch or common-trip overcurrent protection to open if the load on the
grounding transformer exceeds 125% of its continuous current rating [Article 450.5 (A) (2)].
Again, these points are not intended to be an all-inclusive reference for NEC grounding requirements. They do,
however, summarize many of the major requirements. When in doubt, consult the NEC.
12
References
[1]
The National Electrical Code, NFPA 70, The National Fire Protection Association, Inc., 2005 Edition.
[2]
IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems, IEEE Std.
142-1991, December 1991.
13
Section 7:
System Protection
Introduction
An important consideration in power system design is system protection. Without system protection, the power
system itself, which is intended to be of benefit to the facility in question, would itself become a hazard.
The major concern for system protection is protection against the effects of destructive, abnormally high currents.
These abnormal currents, if left unchecked, could cause fires or explosions resulting in risk to personnel and
damage to equipment. Other concerns, such as transient overvoltages, are also considered when designing
power system protection although they are generally considered only after protection against abnormal currents
has been designed.
V th = V ln
I f 3 =
V ln
Z th
The Thevenin impedance for a power system at a given point in the system is referred to as the short-circuit
impedance. In the great majority of power systems the short-circuit impedance is predominately inductive,
therefore one simplification that is often made is to treat the impedance purely as inductance. This has the
effect of causing the fault current to lag the system line-to-neutral voltage by 90. If the system is an ungrounded
delta system the equivalent line-to-neutral voltage can be obtained by performing a delta-wye conversion of
the source voltage.
The phase-to-phase fault value can be calculated from the three-phase fault value if it is remembered that the
line-to-line voltage magnitude is equal to the line-to-neutral voltage magnitude multiplied by 3, and that there will
be twice the impedance in the circuit since the return path must be considered. These two facts, taken together,
allow computation of the line-to-line fault current magnitude I f l l as:
I
f l l
3 I
f 3
(7-1)
This, however, is as far as this simplified analysis method will take us. In order to further characterize fault
currents, a method for calculating unbalanced faults must be used. The universally-accepted method for this is
a method known as the method of symmetrical components.
In the method of symmetrical components, unbalanced currents and voltages are broken into three distinct
components: positive sequence, negative sequence, and zero sequence.These sequence components can be
thought of as independent sets of rotating balanced phasors. The positive sequence set rotates in the standard
A-B-C phase rotation. The negative sequence set rotates in the negative or C-B-A phase rotation. In the zero
sequence set all three phase components are in phase with one another. The positive, negative and zero
sequence components can be further simplified by referring only to the A-phase phasor of each set; these are
referred to as V1 for the positive sequence set, V2 for the negative sequence set and V0 for the zero-sequence
set. For a given set of phase voltages Va, Vb and Vc, the sequence components are related to the phase voltages
as follows:
V1 =
(7-2)
V2
(7-3)
V0
1
V a + aV b + a 2 V c
3
1
=
V a + a 2 V b + aV c
3
1
=
V a +V b +V c
3
(7-4)
V a =V 1 +V 2 +V 0
(7-5)
V b = a 2 V 1 + aV 2 + V 0
(7-6)
V c = aV 1 + a 2 V 2 + V 0
(7-7)
where
a
= 1<120
The system may be separated into positive, negative, and zero-sequence networks depending upon the fault type
and the resulting sequence quantities then combined per (7-5), (7-6), and (7-7) to yield the phase values.
Modern short-circuit analysis is performed using the computer. Even large systems can be quickly analyzed
via short-circuit analysis software. Even so, some heuristic benefit can be gained by knowing how the method
of symmetrical components works. For example, certain protective relays are often set in terms of negativesequence values and ground currents are often referred to as zero-sequence quantities in the literature.
Another factor that must be taken into account is the existence of DC quantities in fault currents. Because of
the system inductance the current cannot change instantaneously, therefore upon initiation of a fault the system
must go through a transient condition which bridges the gap between the faulted and unfaulted conditions.
This transition involves DC currents. For a generic single-phase AC circuit with an open-circuit voltage
v ( t ) = Vm sin( t + ) and a short-circuit impedance consisting of resistance R and inductance L, the fault
i( t ) =
t
sin( t + ) sin( )e L
R 2 + ( L ) 2
Vm
(7-5)
where
L
= tan 1
The angle can be recognized to be the angle of the Thevenin impedance. Several key points can be
taken from (7-5):
I
When the fault occurs such that ( - )= 0 no transient will occur. For a purely inductive circuit this would mean
that = 90 and thus the fault is initiated when the voltage is at its peak.
When the fault occurs such that ( - ) = 90 the maximum transient will occur. For a purely inductive circuit
this would mean that = 0 and thus the fault is initiated when the voltage is zero.
The time constant of the circuit is (L/R) and thus the higher the value of L/R the longer the transient will last.
Instead of (L/R) power systems typically are defined in terms of (X/R), where (X/R) is the ratio of the inductive
reactance of the short-circuit impedance to its resistance. Thus the higher (X/R) or the X/R ratio, the longer the
short-circuit transient will last. This has great implications on the rating of equipment.
A typical plot of fault current on a distribution system with a low X/R ratio and closing angle such that a small
transient is produced is shown in figure 7-2. In contrast with this is the plot shown in figure 7-3, which is the fault
current for a system with a high X/R ratio and closing angle of 0 such that there is a large transient.
1.5
1
i(t)
0.5
0
0.0005
-0.5
0.009
0.0175
0.026
0.0345
0.043
-1
-1.5
t(s)
Figure 7-2: Fault current for system with low X/R ratio and small-transient closing angle, normalized
to a steady-state magnitude of 1
2
1.5
i(t)
1
0.5
0
0.0005
-0.5
0.009
0.0175
0.026
0.0345
0.043
-1
t(s)
Figure 7-3: Fault current for system with higher X/R ratio and closing angle of 0, normalized
to a steady-state magnitude of 1
Figure 7-4 shows only the steady-state component of the waveform of figure 7-3, and figure 7-5 shows only the
transient component.
1.5
1
ss i(t)
0.5
0
0.0005
-0.5
0.009
0.0175
0.026
0.0345
0.043
-1
-1.5
t(s)
tran i(t)
0.009
0.0175
0.026
0.0345
0.043
t(s)
The fault current is often described in terms of its RMS Symmetrical and RMS Asymmetrical values. The RMS
symmetrical value is the RMS value considering the steady-state component only. The RMS asymmetrical value is
the RMS value over the first cycle considering both the steady-state and transient components at the worst-case
closing angle. As a simplification of (7-5) an approximate asymmetry factor can be calculated as [3]
2
Asymmetry factor = 1+ 2e
X
R
(7-9)
For example, this asymmetry factor for an X/R ratio of 25 is 1.6, meaning that the approximate worst-case RMS
asymmetrical value over the first cycle for the fault current at an X/R ratio of 25 will be no greater than the RMS
symmetrical value multiplied by 1.6.
For motors and generators, which have a high X/R ratios, calculations for the transient performance during a fault
are simplified by representing the short-circuit impedances differently for different time periods after the fault
initiation. The reactive component of the short-circuit impedance for the first half-cycle into the fault is the
subtransient reactance (X"d). For the first several cycles into the fault the reactance is larger and is termed the
transient reactance (X'd). For the long-term fault currents (up to 30 cycles or so into the fault) the reactance is
even larger and is termed the synchronous reactance (Xd). The synchronous reactance is much larger than either
the transient or subtransient reactance and models the phenomenon of AC decrement; after the DC component
decays the AC component continues to decay, eventually reaching a value that can be less than the generator
rated load current.
In general, the closer the fault is to a generator or generators the higher the X/R ratio and thus the larger the DC
offset. The AC decrement of the fault from generator sources is pronounced. Faults from most utility services are
sufficiently far removed from generation and have enough resistance in the distribution lines that there is less DC
offset and essentially no AC decrement. The fault current contribution from induction motors has a high DC offset
but also decays rapidly to zero over the first few cycles since there is no applied field excitation. The fault current
contribution from synchronous motors has a large DC component and decays to zero but at a slower rate than for
4
induction motors due to the applied field excitation. For a given point in the system, the fault current is the sum of
the contributions from all of these sources and the DC offset, DC decay, and AC decrement are all dependent
upon the relative location of the fault with respect to these sources.
The existence of the transient is of vital importance to selecting the proper equipment for system protection.
Because standards for equipment short-circuit ratings vary (more will be stated regarding this in subsequent
sections of this guide), all the more speed and efficiency is gained by using the computer for short circuit
calculations; the various equipment rating standards can be taken into account to produce accurate results for
comparison with the equipment ratings.
CA
CB
CC
Plug Fuses
Type C or
Type S
Voltage
Ratings
Ampere
Ratings
Interrupting
Ratings
(RMS)
Current
Limiting?
Standards
Notes
Varies
UL 248-3-2000,
CSA C22.2 NO.
248.2-2000
Plug-style
UL 248-3-2000,
CSA C22.2 NO.
248-3-2000
No mounting holes
UL 248-3-2000,
CSA C22.2 NO.
248-3-2000
Mounting holes in
end blades
600 Vac
0-12000 A
200,000 A
0-600 Vdc
Varies
Varies
600 Vac
0-30A
200,000A
Yes
0-600 Vdc
Varies
Varies
Yes
600 Vac
0-60 A
200,000 A
Yes
0-600 Vdc
Varies
Varies
Yes
600 Vac
0-30 A
200,000 A
Yes
Rejection-style;
0-600 Vdc
Varies
Varies
UL 248-4-2000 ,
CSA C22.2 NO.
248.4-2000
480 Vac
25-60 A
100,000 A
Yes
UL 248-5-2000,
CSA C22.2 NO.
248.5-2000
6000 V
0-20 A
100,000 A
Yes
480 Vdc
Varies
Varies
Yes
250 Vac
0-600 A
10,000 A
No
No
600 Vac
0-600 A
10,000 A
0-600 Vdc
Varies
Varies
600 Vac
0-600 A
200,000 A
Yes
0-600 Vdc
Varies
Varies
Yes
250 Vac
0-600A
50,000 A
Yes*
250 Vac
0-600A
100,000 A
Yes*
250 Vac
0-600A
200,000 A
Yes*
600 Vac
0-600A
50,000 A
Yes*
600 Vac
0-600A
100,000 A
Yes
600 Vac
0-600A
200,000 A
Yes*
0-600 Vdc
Varies
Varies
600 Vac
601-6000 A
200,000 A
0-600 Vdc
Varies
Varies
250 Vac
0-600 A
600 Vac
UL 248-6-2000,
CSA C22.2 NO.
248.6-2000
UL 248-8-2000,
CSA C22.2 NO.
248.8-2000
UL 248-9-2000,
CSA C22.2 NO.
248-9-2000
Yes
UL 248-10-2000,
CSA C22.2 NO.
248.10-2000
Bolt-on construction
200,000 A
Yes
0-600 A
200,000 A
Yes
UL 248-12-2000,
CSA C22.2 NO.
248.12-2000
0-600 Vdc
Varies
Varies
300 Vac
0-1200 A
200,000 A
Yes
600 Vdc
0-1200 A
200,000 A
Yes
UL 248-15-2000,
CSA C22.2 NO
248.15-2000
Similar to Class J,
but dimension-ally
smaller
0-600 Vdc
Varies
Varies
125 Vac
0-30 A
10,000 A
125 Vdc
0-30 A
10,000 A
UL 248-11-2000,
CSA NO. 248.112000
No
* Because of their interchangeability with Class H fuses, class K-1, K-5, and K-9 fuses cannot be marked as current-limiting.
100K
10K
1K
100
C UR R E NT IN AMP E R E S
1000
100
100
10
10
100K
0.01
10K
0.01
1K
0.10
100
0.10
T IME IN S E C ONDS
1000
In some cases the fuse average melting time only is given. This can be treated as the fuse opening time
with a tolerance of 15%. The -15% boundary is the minimum melting time and the +15% boundary is the
total clearing time.
Note that the time-current characteristic does not extend below .01 seconds. This is due to the fact that below
.01 seconds the fuse is operating in its current-limiting region and the fuse I2t is of increasing importance.
The time-current characteristic curves are used to demonstrate the coordination between protective devices in
series. The basic principle of system protection is that for a given fault current ideally only the device nearest the
fault opens, minimizing the effect of the fault on the rest of the system. This principle is known as selective
coordination and can be analyzed with the use of the device time-current characteristic curves.
As an example, consider a 480 V system with two sets of fuses in series, with a system available fault current of
30,000 A. Bus A is protected using 400 A class J fuses which supply, among others, bus B. Bus B is protected
using 100 A class J fuses. Coordination between the 400 A and 100 A fuses can is shown via the time-current
curves of figure 7-7, along with a one-line diagram of the part of the system under consideration. Because the
time bands for the two fuses do not overlap, these are coordinated for all operating times above .01 seconds.
It can also be stated that these two sets of fuses are coordinated through approximately 4200 A, since at 4200 A
Fuse A has the potential to begin operating in its current-limiting region. Fuse B has the potential to begin
operating its current-limiting region at 1100 A. For currents above approximately 4000 A, therefore, both sets of
fuses have the potential to be operating in the current-limiting region. When both sets of fuses are operating the
current-limiting region the time-current curves cannot be used to the determine coordination between them.
Instead, for a given fault current the minimum melting I2t for Fuse A must be greater than the maximum clearing I2t
for Fuse B. In practice, instead of publishing I2t data fuse manufacturers typically publish ratio tables showing the
minimum ratios of fuses of a given type that will coordinate with each other.
100K
10K
C UR R E NT IN AMP E R E S
1K
100
10
1000
1000
FUSE A
100
100
FUSE B
10
10
BUS A
FUSE A
400 .0 A
T IME IN S E C ONDS
UTILITY SOURCE
480 V
300 00.00A Available Fau lt
BUS B
FUSE B
100 .0 A
0.10
0.10
BUS C
100K
1K
10K
0.01
10
100
0.01
Low voltage fuse AC interrupting ratings are based upon a maximum power factor of .2, corresponding to a
maximum X/R ratio of 4.899. In order to evaluate a low voltage fuses interrupting rating on a system with a higher
X/R ratio the system symmetrical fault current must be multiplied by a multiplying factor [3]:
MULT =
1+ e
X
R actual
X
1+ e R
(7-10)
test
where
X
R actual
X
R test
The available symmetrical fault current multiplied by the multiplying factor per (7-10) can be compared to the fuse
interrupting rating.
The use of fuses requires a holder and a switching device in addition to the fuses themselves. Because they are
single-phase devices, a single blown fuse from a three-phase set will cause a single-phasing condition, which can
lead to motor damage. Replacing fuses typically requires opening equipment doors and/or removing cover panels.
Also, replacement fuses must be stocked to get a circuit with a blown fuse back on-line quickly. For these
reasons, the use of low voltage fuses in modern power systems is generally discouraged. For circuit breakers that
have a short-time rating
Thermal-magnetic circuit breaker: This type of circuit breaker contains a thermal element to trip the circuit
breaker for overloads and a faster magnetic instantaneous element to trip the circuit breaker for short circuits.
On many larger thermal-magnetic circuit breakers the instantaneous element is adjustable.
Electronic trip circuit breaker: An electronic circuit breaker contains a solid-state adjustable trip unit. These
circuit breakers are extremely flexible in coordination with other devices.
Sensor: An electronic-trip circuit breakers sensor is usually an air-core current transformer (CT) designed
specifically to work with that circuit breakers trip unit. The sensor size, in conjunction with the rating plug,
determines the electronic-trip circuit breakers continuous current rating.
Rating plug: An electronic trip circuit breakers rating plug can vary the circuit breakers continuous current rating
as a function of its sensor size.
Typical molded-case circuit breakers are shown in figure 7-8. In figure 7-8 on the left is a thermal-magnetic circuit
breaker, and on the right is an electronic-trip circuit breaker. The thermal-magnetic circuit breaker is designed for
cable connections and the electronic circuit breaker is designed for bus connections, but neither type is inherently
suited for one connection type over another. Note the prominently-mounted operating handle on each circuit
breaker.
Circuit breakers may be mounted in stand-alone enclosures, in switchboards, or in panelboards (more information
on switchboards and panelboards is given in a later section of this guide).
A typical thermal-magnetic circuit breaker time-current characteristic is shown in figure 7-9. Note the two distinct
parts of the characteristic curve: The thermal or long-time characteristic is used for overload protection and the
magnetic or instantaneous characteristic is used for short-circuit protection. Note also that there is a band of
operating times for a given fault current. The lower boundary represents the lowest possible trip time and the
upper boundary represents the highest possible trip time for a given current.
10
100K
10K
1K
100
C UR R E NT IN AMP E R E S
1000
1000
100
100
10
10
0.01
10K
100K
0.01
1K
0.10
100
0.10
T IME IN S E C ONDS
10K
100K
C UR R E NT IN AMP E R E S
1K
100
The time-current characteristic for an electronic-trip circuit breaker is shown in figure 7-10. The characteristic for
an electronic trip circuit breaker consists of the long time pickup, long-time delay, short-time pickup, short time
delay, and instantaneous pickup parameters, all of which are adjustable over a given range. This adjustability
makes the electronic-trip circuit breaker very flexible when coordinating with other devices. The adjustable
parameters for an electronic trip circuit breaker are features of the trip unit. In many cases the trip unit is also
available without the short-time function. In catalog data the long-time characteristic is listed as L, the short-time is
listed as S, and the instantaneous as I. Therefore an LSI trip unit has long-time, short-time, and instantaneous
characteristics, whereas an LI trip unit has only the long-time and instantaneous characteristics. For circuit
breakers that have a short-time rating, the instantaneous feature may be disabled, enhancing coordination with
downstream devices.
1000
1000
100
10
T IME IN S E C ONDS
Instantaneous Pickup
100K
0.01
10K
0.01
1K
0.10
100
0.10
11
If the instantaneous feature has been disabled one must still be cognizant of any instantaneous override feature
the breaker has, which will engage the instantaneous function above a given level of current even if it has been
disabled in order to protect the circuit breaker from damage.
Another feature available on electronic-trip circuit breakers is ground-fault protection, which is discussed in detail
later in this section.
100K
C UR R E NT IN AMP E R E S
10K
10
1000
1K
100
Typical coordination between an electronic and a thermal magnetic circuit breaker is shown in figure 7-11.
Because the time bands do not overlap, these two devices are considered to be coordinated.
1000
CB A
100
100
CB B
10
10
BUS A
CB A
250 0.0 A
T IME IN S E C ONDS
UTILITY SOURCE
480 V
300 00.00A Available Fau lt
BUS B
CB B
400 .0 A
0.10
0.10
BUS C
100K
10K
1K
0.01
10
100
0.01
A further reduction in the let-through energy for a fault in the region between two electronic-trip circuit breakers
can be accomplished through zone-selective interlocking. This consists of wiring the two trip units such that if the
downstream circuit breaker senses the fault (typically this will be based upon the short-time pickup) it sends a
restraining signal to the upstream circuit breaker. The upstream circuit breaker will then continue to time out as
specified on its characteristic curve, tripping if the downstream device does not clear the fault. However, if the
downstream device does not sense the fault and the upstream devices does, the upstream device will not have
the restraining signal from the downstream device and will trip with no intentional delay. For example, if zone
selective interlocking were present in the system of figure 7-11 and fault occurs on bus C circuit breaker B will
sense the fault and send a restraining signal to circuit breaker A. Circuit breaker A is coordinated with circuit
breaker B, so circuit breaker B will trip first. If circuit breaker B fails to clear the fault, circuit breaker A will time out
on its time-current characteristic per figure 7-11 and trip. If the fault occurs at bus B, circuit breaker B will not
detect the fault and thus will not send the restraining signal to circuit breaker A. Circuit breaker A will sense the
fault and will trip with no intentional delay, which is faster than dictated by its time-current characteristic per figure
7-11. Care must be used when applying zone-selective interlocking where there are multiple sources of power and
fault currents can flow in either direction through a circuit breaker.
Table 7-2 shows typical characteristics of molded-case circuit breakers [3]. This table is for reference only; when
specifying circuit breakers manufacturers actual catalog data should be used.
12
Table 7-2: Typical characteristics of molded case circuit breakers for commercial and
industrial applications (Largely same as [3] table 7-1)
Frame Size (A)
Number of
Poles
100
100, 150
225, 250
400, 600
800, 1000
1200
1600, 2000
3000, 4000
240 V
277 V
10
14
65
65
480 V
600 V
2,3
18
14
14
2,3
65
25
18
2,3
100
65
25
2,3
25
22
22
2,3
65
25
22
2,3
100
65
25
2,3
42
30
22
2,3
65
65
25
2,3
100
42
30
22
65
50
25
200
100
65
42
30
22
65
50
25
200
100
65
65
50
42
125
100
65
100
100
85
200
150
100
35
Note that the continuous current rating is set by the sensor and rating plug sizes for a given electronic-trip circuit
breaker. This can be smaller than the frame size. As can be seen from table 7-2, more than one interrupting rating
can be available for a given frame size.
Molded-case circuit breakers are tested for interrupting capabilities with test X/R ratios as shown in table 7-3 [4].
As with fuses, when a circuit breaker is applied in a circuit with an X/R ratio larger than its test X/R then the
available RMS symmetrical fault current should be multiplied by the multiplying factor per equation (7-10) in order
to be compared with the circuit breaker interrupting rating.
Table 7-3: AC test circuit characteristics for molded-case circuit breakers [4]
Interrupting rating
(RMS Symmetrical)
(X/R)test
10,000 or LESS
0.45 - 0.50
1.732
10,001-20,000
0.25-0.30
3.180
Over 20,000
0.15 - 0.20
4.899
Current-limiting circuit breakers are also available. Coordination between two current-limiting circuit breakers when
they are both operating in the current limiting range is typically determined by test.
13
By definition, low voltage molded case circuit breakers are not maintainable devices. Failure of a component
generally requires replacement of the entire circuit breaker unless the circuit breaker has been specifically
designed for maintainability.
Magnetic-only circuit breakers which have only magnetic tripping capability are available. These are often used
as short-circuit protection for motor circuits (discussed in more detail in a later section of this guide). For this
reason these are often referred to as motor circuit protectors.
Molded case switches are also available. These do not have a thermal element, however most have a magnetic
element which opens the switch above a specified current to protect the switch from damage due to lack of a
short-time rating.
Molded-case circuit breakers are available with several different options, such as stored-energy mechanisms, key
interlocks, motor operators, etc. Refer to specific manufacturers literature for details.
Because the switching means is included with the device, molded-case circuit breakers give inherent flexibility of
operation. This allows circuits to be reclosed without removing cover panels and exposing the operator to
hazardous voltages. For three-phase circuits three-pole circuit breakers are used, which alleviates single-phasing
concerns. And, circuit breakers are not one-time devices, eliminating need to store spares in the event of a fault.
These characteristics make molded-case circuit breakers very versatile protective devices.
14
Table 7-4: Preferred ratings for low voltage AC power circuit breakers with instantaneous
direct-acting phase trip elements (Same as [3] table 7-3)a
System
Nominal
Voltage (V)
Rated
Maximum
Voltage (V)
Insulation
(dielectric)
withstand (V)
Range of trip
device current
ratings (A)c
600
635
2,200
14,000
225
40-225
600
635
2,200
22,000
600
40-600
600
635
2,200
22,000
800
100-800
600
635
2,200
42,000
1,600
200-1,600
600
635
2,200
42,000
2,000
200-2,000
600
635
2,200
65,000
3,000
2,000-3000
600
635
2,200
65,000
3,200
2,000-3200
600
635
2,200
85,000
4,000
4,000
480
508
2,200
22,000
225
40-225
480
508
2,200
30,000
600
100-600
480
508
2,200
30,000
800
100-800
480
508
2,200
50,000
1,600
400-1,600
480
508
2,200
50,000
2,000
400-2,000
480
508
2,200
65,000
3,000
2,000-3,000
480
508
2,200
65,000
3,200
2,000-3,200
480
508
2,200
85,000
4,000
4,000
240
254
2,200
25,000
225
40-225
240
254
2,200
42,000
600
150-600
240
254
2,200
42,000
800
150-800
240
254
2,200
65,000
1,600
600-1,600
240
254
2,200
65,000
2,000
600-2,000
240
254
2,200
85,000
3,000
2,000-3,000
240
254
2,200
85,000
3,200
2,000-3,200
240
254
2,200
130,000
4,000
4,000
Ratings in this column are RMS symmetrical values for single-phase (two pole) circuit breakers and three-phase average RMS
symmetrical values of three-phase (three-pole) circuit breakers. When applied on systems where rated maximum voltage may
appear across a single pole, the short-circuit current ratings are 87% of these values. See 5.6 in IEEE Std C37.13-1990.
The continuous-current-carrying capability of some circuit-breaker-trip-device combinations may be higher than the trip-device
current rating. See 10.1.3 in IEEE Std C37.13-1990.
15
Table 7-5: Preferred ratings for low voltage AC power circuit breakers without instantaneous
direct-acting phase trip elements (Largely same as [3] table 7-4)a
Range of trip device current ratings (A)d
Rated Maximum
Voltage (V)
Inter-mediate
Time Band
Maximum
Time Band
635
225
100-225
125-225
150-225
635
600
175-600
200-600
250-600
635
800
175-800
200-800
250-800
635
1,600
360-1,600
400-1,600
500-1,600
635
2,000
250-2,000
400-2,000
500-2,000
635
3,000
2,000-3,000
2,000-3,000
2,000-3,000
635
3,200
2,000-3,200
2,000-3,200
2,000-3,200
635
4,000
4,000
4,000
4,000
508
225
100-225
125-225
150-225
508
600
175-600
200-600
250-600
508
800
175-800
200-800
250-800
508
1,600
350-1600
400-1,600
500-1,600
508
2,000
350-2,000
400-2,000
500-2,000
508
3,000
2,000-3,000
2,000-3,000
2,000-3,000
508
3,200
4,000
4,000
2,000-3,200
508
4,000
4,000
4,000
4,000
254
225
100-225
125-225
150-225
254
600
175-600
200-600
250-600
254
800
175-800
200-800
250-800
254
1,600
350-1,600
400-1,600
500-1,600
254
2,000
350-2,000
400-2,000
500-2,000
254
3,000
2,000-3,000
2,000-3,000
2,000-3,000
254
3,200
2,000-3,200
2,000-3,200
2,000-3,200
254
4,000
4,000
4,000
4,000
The continuous-current-carrying capability of some circuit-breaker-trip-device combinations may be higher than the tripdevice current rating. See 10.1.3 in IEEE Std C37.13-1990.
As with molded-case circuit breakers, low voltage power circuit breakers are tested at a given power factor. The
test power factor is 15% for unfused circuit breakers and 20% for fused circuit breakers. Table 7-6 shows the
multiplying factors for both fused and unfused circuit breakers for various short-circuit power factors. The
multiplying factors for unfused circuit breakers are calculated similarly to those for molded-case circuit breakers,
but those for fused circuit breakers are based upon RMS rather than peak current and differ slightly from the
multiplying factors obtained from equation (7-10) [5].
16
Table 7-6: Short-circuit multiplying factors for low voltage power circuit breakers
(Largely same as [5] table 3)
System Short-Circuit
Power Factor
Multiplying Factor x
RMS Symmetrical ShortCircuit Current, for
Unfused Power Circuit
Breakers
Multiplying Factor x
RMS Symmetrical ShortCircuit Current, for
Fused Power Circuit
Breakers
20
4.9
1.00
1.00
15
6.6
1.00
1.07
12
8.27
1.04
1.12
10
9.95
1.07
1.15
8.5
11.72
1.09
1.18
14.25
1.11
1.21
20.0
1.14
1.26
Use of low voltage power circuit breakers allows optimum flexibility in coordination, since the instantaneous
function may be disabled. Further, since these are designed for heavy-duty use in an industrial environment
they are most often configured as drawout circuit breakers with stored-energy mechanisms in ANSI low voltage
metal enclosed switchgear (described in a later section of this guide). This makes them ideal for low voltage
automatic transfer applications. Their inherent operational flexibility serves to make them the ideal device
for circuit protection in industrial applications where the ability to coordinate with downstream devices is a
premium consideration.
ANSI C37.42-1996
ANSI C37.44-1981
ANSI C37.46-1981
ANSI C37.47-1981
ANSI C37.53.1-1989
Those definitions in Low voltage fuses section above which do not specifically reference low voltage fuses are
also valid for medium voltage fuses. Generally, medium voltage fuses can be divided into two major categories:
Current-limiting and expulsion. Current-limiting fuses were defined in Low voltage fuses section above, and the
same basic definition applies to medium voltage fuses. Expulsion fuses are defined as follows [3]:
17
Expulsion fuse: A vented fuse in which the expulsion effect of the gases produced by internal arcing, either
alone or aided by other mechanisms, results in current interruption.
In addition, medium voltage fuses are further classified as power fuses or distribution fuses as follows [3]:
Power fuse: Defined by ANSI C37.42-1996 as having dielectric withstand (BIL) strengths at power levels, applied
primarily in stations and substations, with mechanical construction basically adapted to station and substation
mountings.
Distribution fuse: Defined by ANSI C37.42-1996 as having dielectric withstand (BIL) strengths at distribution
levels, applied primarily on distribution feeders and circuits, and with operating voltage limits corresponding to
distribution voltages. These are further subdivided into distribution current limiting fuses and distribution fuse
cutouts, as described below.
Current-limiting fuses interrupt in less than _ cycle when subjected to currents in their current-limiting range. This
is an advantage as it limits the peak fault current to a value less than the prospective fault current as described
above for low voltage fuses. This provides current-limiting fuses with high interrupting ratings and allows them to
protect downstream devices with lower short-circuit ratings in some cases. However, the same technologies that
combine to give medium voltage current-liming fuses their current-limiting characteristics can also produce thermal
issues when the fuses are loaded at lower current levels. For this reason, the following definitions apply to
current-limiting fuses [3]
Backup current-limiting fuse: A fuse capable of interrupting all currents from its maximum rated interrupting
current down to its rated minimum interrupting current.
General purpose current-limiting fuse: A fuse capable of interrupting all currents from the rated interrupting
current down to the current that causes melting of the fusible element in no less than 1h.
Full-range current-limiting fuse: A fuse capable of interrupting all currents from its rated interrupting current
down to the minimum continuous current that causes melting of the fusible elements.
Due to the limitations of backup and general purpose current limiting fuses, current-limiting power fuses have
melting characteristics defined as E or R, defined as follows:
E-Rating: The current-responsive element for ratings 100 A or below shall melt in 300 s at an RMS current within
the range of 200% to 240% of the continuous-current rating of the fuse unit, refill unit, or use link. The currentresponsive element for ratings above 100 A shall melt in 600 s at an RMS current within the range of 220% to
264% of the continuous-current rating of the fuse unit, refill unit, or fuse link.
R-Rating: The fuse shall melt in the range of 15 s to 35 s at a value of current equal to 100 times the R number.
Similarly, distribution current-limiting fuses are defined by given characteristic ratings, one of which is the C rating,
defined as follows:
C-Rating: The current-responsive element shall melt at 100 s at an RMS current within the range of 170% to
240% of the continuous-current rating of the fuse unit.
A typical time-current curve for an E-rated current-limiting power fuse is shown in figure 7-13. The fuse in figure
7-13 is a 125E-rated fuse. Note that the curve starts at approximately 250 A for a minimum melting time of 1000 s.
Care must be taken with backup and general-purpose current-limiting fuses so that the load current does not to
exceed the E- or R-rating of the fuse. Failure to do this can result in the development of a hot-spot and
subsequent failure of the fuse and its mounting. For fuses enclosed in equipment, this can have disastrous
consequences since failure of the fuse and/or its mounting can lead to an arcing fault in the equipment. Note that
the boundary of the characteristic, denoting the minimum-melting current, should be further derated to take into
account pre-loading of the fuse (consult the fuse manufacturer for details). Note that, as with low voltage fuses,
the current-limiting fuse characteristic does not extend below .01 seconds since the fuse would be in its currentlimiting range below this interrupting time.
18
100K
10K
C UR R E NT IN AMP E R E S
1K
100
10
1000
1000
100
10
10
0.10
T IME IN S E C ONDS
100
0.10
100K
10K
1K
0.01
10
100
0.01
A current-limiting power fuse consists of a fuse mounting (typically fuse clips) plus the fuse unit itself. These are
frequently mounted in metal-enclosed switchgear. A distribution current-limiting fuse may consist of a
disconnecting-style holder or clips, plus the fuse unit. Distribution current-limiting fuses may also be provided with
under-oil mountings for use with distribution transformers. They are frequently used for capacitor protection as
well, with clips designed to mount to the capacitor.
Current-limiting power fuses are typically used for short-circuit protection of instrument transformers, power
transformers, and capacitor banks. Table 7-7 gives maximum ratings for medium voltage current-limiting power
fuses from 2.75 through 38 kV.
19
Short-Circuit maximum
interrupting ratings
(kA RMS symmetrical)
2.75
225,450a,750a, 1350a
2.75/4.76
450a
50.0
5.5
225,400,750a,1350a
8.25
125,200a
50.0, 50.0
15.5
65,100,125a,200a
25.8
50,100a
35.0, 35.0
38.0
50,100a
35.0, 35.0
Parallel Fuses
During interruption current-limiting fuses produce significant arc voltages. These must be taken into account in
selecting equipment. They are typically compared to the BIL level of the equipment, including downstream
equipment at the same voltage level. The maximum permissible overvoltages for current-limiting power fuses are
shown in table 7-8 [3]:
Table 7-8: Maximum permissible overvoltages for current-limiting power fuses
(Same as [3] table 6-1)
Maximum Peak Overvoltages (kV, crest)
Rated Maximum Voltage (kV)
0.5A to 12A
Over 12A
2.8
13
5.5
25
18
8.3
38
26
15.0
68
47
15.5
70
49
22.0
117
70
25.8
117
81
27.0
123
84
38.0
173
119
In practice, the arc voltages for current-limiting fuses generally indicate the use of the smallest available fuse
voltage class for the given system voltage, for example, 5.5 kV fuses instead of 8.3kV fuses for a 4160 V system.
After a fault interruption, in a three-phase set of current-limiting fuses all three fuses will be replaced, even if
only one fuse interrupted the fault. This is due to the possibility of damage to the other two fuses due to the
fault, which could change their time-current characteristics and make them unsuitable to carry load current
without failure.
Because medium voltage current-limiting fuses interrupt short circuits without the expulsion of gas or flame,
they are widely utilized in a variety of applications.
20
Power expulsion fuses generally consist of an insulating mounting plus a fuse holder which accepts the fuse
refills. The fuse holder may be of the disconnecting or non-disconnecting type. Only the refill is replaced when a
fuse interrupts an overcurrent, and if only one phase of a three-phase set interrupted the fault only that fuse need
be replaced. Power expulsion fuses are typically used in substations and enclosed equipment.
Distribution expulsion fuses are generally distribution fuse cutouts, which are adapted to pole or cross arm
mounting. They consist of the fuse holder and refill unit. The fuse holder is usually of the disconnecting type.
These are typically used as pole-mounted fuses on utility distribution systems.
Expulsion fuses use the liberation of de-ionizing gasses to interrupt overcurrents. Boric acid is typically used as
the interrupting medium for power expulsion fuses and bone fiber is typically used for distribution fuse cutouts.
When an expulsion fuse interrupts an overcurrent the interrupting medium liberates de-ionizing gas, interrupting
the overcurrent. The exhaust gasses are then emitted from the fuse, accompanied by noise. The exhaust
gasses for a boric acid fuse may condensed by an exhaust control device (commonly called an exhaust filter,
silencer, or snuffler).
Unlike current-limiting fuses, expulsion-type fuses interrupt high overcurrents at natural current zeros. They are
therefore non-current-limiting, and as a result typically have lower interrupting ratings than current-limiting fuses.
Table 7-9 shows the maximum continuous current and short-circuit interrupting ratings for refill-type boric-acid
expulsion-type power fuses [3]. Because expulsion-type fuses are non-current-limiting, they do not produce the
significant arc voltages that current-limiting fuses produce, and thus it is permissible to use a fuse with a larger
voltage class than the system, for example, a 14.4 kV-rated fuse on a 4160 V system. This makes expulsion-type
fuses particularly useful on systems which may be upgraded in the future to a higher voltage. However, the lower
interrupting ratings of expulsion-type fuses are often an issue vs. current-limiting fuses in light of the fact that the
largest expulsion-type fuse interrupting ratings require larger physical dimensions which cannot always be easily
accommodated in enclosed equipment. Further, in some cases the expulsion-type fuses prohibit some spacesaving mounting configurations in enclosed equipment that are available with current-limiting fuses.
Table 7-9: Maximum continuous current and short circuit interrupting ratings for refill type
boric-acid expulsion-type power fuses (Same as [3] table 6-6)
Short-Circuit maximum
interrupting ratings
(kA, RMS symmetrical)
2.8
200,400,720a
4.8
200,400,720a
5.5
200,400,720a
8.3
200,400,720a
14.4
200,400,720a
15.5
200,400,720a
17.0
200,400,720a
25.8
200,300,540a
27.0
200,300
12.5, 20.0
38.0
200,300,540a
Parallel Fuses
21
100K
10K
C UR R E NT IN AMP E R E S
1K
10
1000
100
E-ratings are used for power expulsion fuses. A typical time-current characteristic for a 125E boric-acid fuse is
given in figure 7-15.
1000
100
10
10
0.10
T IME IN S E C ONDS
100
0.10
100K
10K
1K
0.01
10
100
0.01
Figure 7-15: Typical boric acid power expulsion fuse time-current characteristic
Note that the characteristic extends to the available fault current (in this case, 29.4 kA), unlike that of the
current-limiting fuse. It is common practice to treat these as current-limiting fuses so far as the E-rating is
concerned, i.e., the maximum load current is usually kept below the E-rating. However, the boric-acid fuse is
not subject to damage when loaded above its E-rating, and they are often referred to in the industry as
non-damageable due to this fact.
When applying medium voltage fuses, the voltage rating and the interrupting rating are of importance.
The maximum line-to-line voltage of the system should not exceed the fuse voltage rating. The published
interrupting rating for power fuses is typically for a test X/R ratio of 15, and for distribution fuses the test X/R ratio
is typically 8; the fuse manufacturer should be consulted for derating factors for X/R ratios above these values.
The manufacturer should also be consulted if the test X/R is in doubt.
Medium voltage fuses provide economical short-circuit protection when applied within their ratings, particularly for
transformers, cables, and capacitors. For more sophisticated protection at the medium voltage level, other means
must be employed.
22
Medium voltage circuit breakers are generally not equipped with integral trip units as low voltage circuit breakers
are. Instead, protective relays must be used to sense abnormal conditions and trip the circuit breaker accordingly.
Most modern medium voltage circuit breakers are rated on a symmetrical current basis. The following rating
definitions apply [6]:
Rated Maximum Voltage: The highest RMS phase-to-phase voltage for which the circuit breaker is designed.
Rated Power Frequency: The frequency at which the circuit breaker is designed to operate.
Figure 7-16: Medium voltage circuit breaker, for use In metal-clad switchgear
Rated Dry Withstand Voltage: The RMS voltage that the circuit breaker in new condition is capable of
withstanding for 1 minute under specified conditions.
Rated Wet Withstand Voltage: The RMS voltage that an outdoor circuit breaker or external components in new
condition are capable of withstanding for 10s.
Rated Lightning Impulse Withstand Voltage: The peak value of a standard 1.2 x 50 s wave, as defined in
IEEE Std 4-1978, that a circuit breaker in new condition is capable of withstanding.
Rated Continuous Current: The current in RMS symmetrical amperes that the circuit breaker is designed to
carry continuously.
Rated Interrupting Time: The maximum permissible interval between the energizing of the trip circuit at rated
control voltage and the interruption of the current in the main circuit in all poles.
Rated Short Circuit Current (Required Symmetrical Interrupting Capability): The value of the symmetrical
component of the short-circuit current in RMS amperes at the instant of arcing contact separation that the circuit
breaker shall be required to interrupt at a specified operating voltage, on the standard operating duty cycle, and
with a DC component of less than 20% of the current value of the symmetrical component.
Required Asymmetrical Interrupting Capability: The value of the total RMS short-circuit current at the instant
of arcing contact separation that the circuit breaker shall be required to interrupt at a specified operating voltage
and on the standard operating duty cycle. This is based upon a standard time constant of 45ms (X/R ratio =17 for
60 Hz and 14 for 50 Hz systems) and an assumed relay operating time of _ cycle.
Rated closing and latching capability: The circuit breaker shall be capable of closing and latching any power
frequency making current whose maximum peak is equal to or less than 2.6 (for 60 Hz power frequency; 2.5 for
50 Hz power frequency) times the rated short-circuit current.
23
Rated Short-Time Current: The maximum short-circuit current that the circuit breaker can carry without tripping
for a specified period of time.
Maximum Permissible Tripping Delay: The maximum delay time for protective relaying to trip the circuit
breaker during short-circuit conditions, based upon the rated short-time current and short-time current-carrying
time period.
Rated Transient Recovery Voltage (TRV): At its rated maximum voltage, a circuit breaker is capable of
interrupting three-phase grounded and ungrounded terminal faults at the rated short-circuit current in any circuit in
which the TRV does not exceed the rated TRV envelope. For a circuit breaker rated below 100kV, the rated TRV
is represented by a 1-cosine wave, with a magnitude and time-to-peak dependent upon the rated maximum
voltage of the circuit breaker.
Rated Voltage Range Factor K: Defined in earlier versions of [6] as the factor by which the rated maximum
voltage may be divided to determine the minimum voltage for which the interrupting rating varies linearly with the
interrupting rating at the rated maximum voltage by the following formula:
V
I vop = I v max max
Vop
(7-8)
where
Ivmax
Vmax
Vop
Ivop
For values of Vop below (Vmax K) the short-circuit interrupting capability was considered to be equal to
(Iv max x K). This model was more representative of older technologies such as air-blast interruption. Because
most modern circuit breakers employ vacuum technology, the current version of [6] assumes that K = 1., which
gives the same short circuit rating for all voltages below the rated voltage. However, in practice designs with K > 1
still exist and are in common use.
Table 7-10 shows the preferred ratings for circuit breakers from [7] where K=1. Table 7-11 shows the preferred
ratings for circuit breakers where K > 1.
24
Table 7-10: Preferred ratings for indoor circuit breakers with K=1.0
(Essentially same as [7] table 1)
Rated
Max.
Voltage,
(kV)
Rated
Voltage
Range
Factor K
Rated
Continuous
Current
(A RMS)
Rated
Rated TRV
ShortRated Peak Rated
Circuit and
Voltage E2 Time to
Short-Time
(kV peak) Peak T2,
Current
(s)
(kA RMS)
Rated
Interrupting
Time
(ms)
Rated Max.
Permissible
Tripping
Time Delay Y
(s)
4.76
1.0
1200, 2000
31.5
8.9
4.76
1.0
1200, 2000
40
8.9
4.76
1.0
50
8.25
1.0
15
1.0
1200, 2000
15
1.0
15
1.0
15
15
Rated
Closing
and
Latching
Current,
(kA Peak)
50
83
82
50
83
104
8.9
50
83
130
40
15.5
60
83
104
20
28
75
83
52
1200, 2000
25
28
75
83
65
1200, 2000
31.5
28
75
83
82
1.0
40
28
75
83
104
1.0
50
28
75
83
130
15
1.0
63
28
75
83
164
27
1.0
1200
16
51
105
83
42
27
1.0
1200,2000
25
51
105
83
65
38
1.0
1200
16
71
125
83
42
38
1.0
1200,2000x
25
71
125
83
65
38
1.0
31.5
71
125
83
82
38
1.0
40
71
125
83
104
It should be noted that although 83 ms or 5 cycles is the preferred value per [6] for the rated interrupting time,
3-cycle designs are common.
Other related preferred ratings, such as dielectric ratings and capacitance switching ratings, are also given in [7].
Table 7-11: Preferred ratings for indoor circuit breakers with voltage range factor K > 1.0
(Essentially same as [7] table A1)
Rated
Max.
Voltage,
(kV)
Rated
Voltage
Range
Factor K
Rated
Continuous
Current at
60Hz
(A RMS)
Rated ShortRated
Rated Max.
Max.
Closing and
Circuit
Interrupting
Voltage
Symmetrical
Latching
Current at
Time,
Divided by Interrupting
Capability
Rated Max.
Cycles
K, kV RMS Capability and 2.7K Times
kV
Rated Short- Rated Short(kA RMS)
Time Current
Circuit
(kA, RMS)
Current
(kA Crest)
4.76
1.36
1200
8.8
3.5
12
32
4.76
1.24
1200, 2000
29
3.85
36
97
4.76
1.19
41
4.0
49
132
8.25
1.25
1200, 2000
33
6.6
41
111
15.0
1.30
1200, 2000
18
11.5
23
62
15.0
1.30
1200, 2000
28
11.5
36
97
15.0
1.30
37
11.5
48
130
38.0
1.65
21
23.0
35
95
38.0
1.0
1200, 3000
40
38.0
40
108
In order to apply medium voltage circuit breakers, it is important to understand how the system X/R ratio affects
the circuit breaker interrupting rating. As stated above, for 60Hz systems the asymmetrical interrupting capability is
based upon an X/R ratio of 17. Thus, for systems where the X/R ratio is 17 or lower the circuit breaker will have
adequate asymmetrical interrupting capability so long as 100% of the symmetrical short-circuit current rating is
25
equal to or above the available RMS symmetrical fault current. For X/R ratios above 17, the available RMS
symmetrical fault current must be compared to the short-circuit current rating of the circuit breaker multiplied by a
multiplying factor determined from [8]. Because the multiplying factors from [8] do not usually exceed 1.25, the
fault current may be compared to 80% of the circuit breaker interrupting rating regardless of X/R ratio in most
cases. The close and latch rating is evaluated using equation (7-9) to obtain the asymmetrical fault current at the
circuit breaker. Reference [8] contains a full method for determining the suitability of a circuit breaker for duty on a
given system, and along with the requirements for low voltage short-circuit calculations from [5] forms the basis for
what the industry terms as ANSI short-circuit analysis. Capacitance switching and generator applications are also
areas of concern when applying medium voltage circuit breakers. Preferred capacitance switching values are
given in [7] and must not be exceeded. Generator applications, for generators rated above 3MVA, must be
approached with caution due to the high X/R ratios encountered. Often, breakers with longer interrupting times are
desirable in large generator applications in order to allow the fault current to decay to the point that there is a
natural current zero for interruption.
As stated above, medium voltage circuit breakers are typically provided without integral trip units. For this reason,
custom protection must be provide via protective relays, discussed in the next section. Circuit breakers are
equipped with tripping and closing coils to allow tripping and closing operations via protective relays, manual
control switches, PLCs, SCADA systems, etc. The circuit breaker internal control circuitry is arranged per IEEE
C37.11-1997. Circuit breakers are also equipped with a number of auxiliary contacts to allow interlocking and
external indication of breaker position.
For medium voltage protection applications, circuit breakers offer flexibility that cannot be obtained with fuses.
Further, they do not require a separate switching device as fuses do. These benefits are gained at a price: Circuit
breaker applications are more expensive than fuse applications, both due to the inherent cost of the circuit
breakers themselves and due to the protective relays required. For many applications, however, circuit breakers
are the only choice that offers the flexibility required. Large medium voltage services and distribution systems and
most applications involving medium voltage generation employ circuit breakers.
Protective relays
For medium voltage circuit breaker applications, protective relays serve as the brains that detect abnormal
system conditions and direct the circuit breakers to operate. They also serve to provide specialized protection in
low voltage power circuit breaker applications for functions not available in the circuit breaker trip units.
Most modern protective relays are solid-state electronic or microprocessor-based devices, although older
electromechanical devices are still available. Solid-state electronic or microprocessor-based relays offer more
flexibility and functionality than electromechanical relays, including the ability to interface with common
communications protocols such as MODBUS for integration into a SCADA environment. However, they do require
reliable control power to maintain operation during abnormal system conditions. This reliable control power is
most often provided by a DC battery system, although AC UPS-based systems are also encountered.
Electromechanical relays are typically single-phase devices. Solid-state electronic relays are typically available in
single-phase or three-phase versions. Microprocessor-based relays are typically three-phase devices. While
electromechanical and solid-state electronic relays typically incorporate one relay function per device,
microprocessor-based relays usually encompass many functions in one device, making a single microprocessorbased relay capable of performing the same functions that would require several electromechanical or solid-state
relays. This functionality usually makes microprocessor-based relays the best choice for new installations.
26
Protective relays are not rated for direct connection to the power system where they are applied. For this reason,
instrument transformers are used to reduce the currents and voltages to the levels for which the relays are
designed. Instrument transformers generally fall into one of two broad categories: Current Transformers (CTs)
and Voltage Transformers (VTs). The loads on instrument transformers, such as relays and meters, are known as
burdens to distinguish them from power system loads.
A current transformer consists of a coil toroidally-wound around a ferromagnetic core. The conductor for which the
current is to be measured is passed through the center of the toroid. The magnetic field generated by the current
through the conductor causes current to flow in the coil. In essence, a CT may be thought of as a conventional
transformer with one primary turn.
CTs in the United States typically have 5 A-rated secondaries, with primary ratings from 10 - 40,000 A and larger.
For relaying applications in industrial facilities, CT ratios are typically 50:5 - 4000:5. IEEE Std. C57.13-1993
designates certain ratios as standard, as well as a classification system for relaying performance. The
classification system consists of a letter and a number. The letter may be C, designating that the percent ratio
correction may be calculated, or T, denoting that the ratio correction has been determined by test. The number
denotes the voltage that the CT can deliver to a standard burden (as described in IEEE Std. C37.13-1993) at 20
times the rated secondary current without exceeding 10% ratio error. As a more accurate alternative,
manufacturer-published CT excitation curves may be used to determine the accuracy. For relaying application, the
issue at hand is the performance of the relay during worst-case short-circuit conditions, when the CT secondary
currents are the largest and may cause the secondary voltage to exceed the CTs rating due to the voltage
developed across the relay input coil. This condition will cause the CT to saturate, significantly changing the ratio
and thus the accuracy of the measurement. For cases of severe CT saturation the relay may respond in an
unpredictable manner, such as not operating or producing chatter of its output contacts.
CT's where the power conductor passes through the window formed by the toroidal CT winding are known as
window-type CTs. CTs which are designed with an integral bus bar running through device are known as bus-bar
type CTs. Other designs, such as wound primary CTs for metering applications and non-saturating air-core CTs,
are available. Additional information on CT application can be found in [3].
Quasi-Physical
Arrangement
Ip
Is
Circuit
Representation
Ip
Is
H1
X1
X2
H2
POWER
CONDUCTOR
Voltage transformers (VTs) are used to step the power system voltage down to a level that the relay can utilize.
The operation of voltage transformers is essentially the same as for conventional power transformers discussed in
section 2 of this guide, except that the design has been optimized for accuracy. Like current transformers, voltage
transformers are assigned accuracy classes by IEEE Std. C57.13-1996. VT accuracy classes are designated W,
X,M Y, Z, and ZZ in order of increasing burden requirements. Refer to [3] for more information regarding the
application of voltage transformers.
Protective relays are classified by function. To make circuit representations easier, each function has been defined
and assigned a number by IEEE Std. C37.2-1996. The IEEE standard function numbers are given in table 7-12.
Table 7-13 gives the commonly-used suffix letters to further designate protective functions [3].
These designations can be combined in various ways. For example, 87T denotes a transformer differential relay,
51N denotes a residual ground time-overcurrent relay, 87B denotes a bus differential relay, etc.
27
Table 7-12: Commonly used protective relay device function numbers (Same as [3] table 4-1)
Relay Device
Function Number
Protection Function
21
Distance
25
Synchronizing
27
Undervoltage
32
Directional Power
40
46
47
49
50
Instantaneous Overcurrent
51
Time-overcurrent
59
Overvoltage
60
67
Directional Overcurrent
81
86
Lockout
87
Differential
Table 7-13: Commonly used suffix letters applied to relay function numbers
(Same as [3] table 4-2)
Suffix Letter
Relay Application
Alarm only
Bus protection
Ground fault protection [relay current transformer (CT) in a system neutral circuit] or
generator protection]
GS
Line Protection
Motor Protection
Transformer protection
Voltage
Several commonly-used protective functions are described below. It must be noted that where a protective
function is described it may be a dedicated relay (electromechanical, solid-state electronic, or microprocessorbased) or a single protective function contained within a microprocessor-based relay. In some manufacturers
literature the individual functions are referred to as elements.
28
100K
1K
10K
C UR R E NT IN AMP E R E S
100
10
1000
1000
100
100
10
1
50
0.10
0.01
100K
10
1K
100
0.01
10K
0.10
T IME IN S E C ONDS
The pickup level is set by the tap setting, which is usually set in CT secondary amperes but may be set in primary
amperes on some microprocessor-based relays.
Each relay curve has a time dial setting which allows the curve to be shifted up or down on the time-current
characteristic curve. In figure 7-19, the time dial settings are different to give enough space between the curves to
show their differences.
The above are IEEE-standard curves; others are available, depending upon the relay make and model. A solidstate electronic or microprocessor-based relay will have all of these curves available on one unit;
electromechanical relays must be ordered with a given characteristic that cannot be changed.
The 50 instantaneous function is only provided with a pickup setting. The 30ms delay shown in figure 7-19 for the
50 function is typical and takes into account both the relay logic operation and the output contact closing time.
Most microprocessor-based units will also have an adjustable delay for the 50 function; when an intentional time
delay is added the 50 is referred to as a definite-time overcurrent function. On solid-state electronic and
microprocessor-based relays, the 50 function may be enabled or disabled. On electromechanical relays, the 50
function can be added as an instantaneous attachment to a 51 time-overcurrent relay. If a relay has both 50 and
51 functions present and enabled is referred to as a 50/51 relay.
Typically, overcurrent relays are employed as one per phase. In solidly-grounded medium voltage systems, the
most common choice for ground fault protection is to add a fourth relay in the residual connection of the CTs to
monitor the sum of all three phase currents. This relay is referred to as a residual ground overcurrent or 51N (or
50/51N) relay.
The CT arrangement for 50/51 and 50/51N relays for a solidly-grounded system is shown in figure 7-20.
SOURCE
A
50/51-B
50/51-C
50/51-N
LOAD
29
For a low-resistance-grounded system, the use of an overcurrent relay connected to a CT in the service
transformer or generator neutral is usually the best option. This CT should have a ratio smaller than the phase
CTs, and the relay pickup range in conjunction with the neutral CT should allow a pickup as low as 10% of the
neutral resistor rating. For a feeder circuit downstream from the service transformer, a zero-sequence CT is
recommended, again with a ratio small enough to allow a pickup as low as 10% of the neutral resistor rating.
When an overcurrent relay is utilized with a zero-sequence CT it is referred to as a 50G, 51G or 50/51G relay
depending upon relay type used. Figure 7-21 shows typical arrangements for both these applications.
TRANSFORMER NEUTRAL
C
51N
ZERO-SEQUENCE
A
Figure 7-21: Transformer neutral and zero-sequence ground relaying applications for
resistance-grounded systems
For ungrounded systems, the ground detection methods in Section 6 are recommended since little ground current
will flow during a single phase-to-ground fault. Low voltage solidly-grounded systems are discussed below.
The typical application of phase and residual neutral ground overcurrent relays in one-line diagram form is
shown in figure 7-22.
[3]
CT
600:5
[3]
51
51N
52
In figure 7-22, the designation 52 is the IEEE Std. C37.2-1996 designation for a circuit breaker. The phase
relays are designated 51 and the residual ground overcurrent relay is designated 51N (both without instantaneous
function). The bracketed [3] denotes that there are three phase overcurrent relays and three CTs. The dotted
line from the relays to the circuit breaker denotes that the relays are wired to trip the circuit breaker on an
overcurrent condition.
Another type of overcurrent relay is the voltage-restrained overcurrent relay 51 V and the voltage-controlled relay
51C. Both are used in generator applications to allow the relay to be set below the generator full-load current due
to the fact that the fault contribution from a generator will decay to a value less than the full-load current of the
generator. The 51C relay does not operate on overcurrent unless the voltage is below a preset value. The 51 V
relay pickup current shifts as the voltage changes, allowing it to only respond to overcurrents at reduced voltage.
Both require voltage inputs, and thus require voltage transformers for operation.
30
UTILITY
FEED
#2
VT [3]
FAULT
CURRENT
FLOW
VT [3]
FAULT
FAULT
CURRENT
FLOW
[3]
CT
600:5
[3]
AUX
VT.
[3]
AUX
VT.
[3]
FAULT
CURRENT
FLOW
[3]
51
51
51N
51N
52-M1
CT
600:5
[3]
52-M2
67, 67N
TRIP
DIRECTION
67, 67N
TRIP
DIRECTION
FAULT
CURRENT
FLOW
CT
600:5
[3]
FAULT
CURRENT
FLOW
67N
52-T
N.C.
67
[3]
67N
67
CT
600:5
[3]
[3]
[3]
51
51N
Figure 7-23: Example protective relaying arrangement for closed-transition primary-selective system
In figure 7-23 the bus tie circuit breaker is normally-closed, paralleling the two utility feeds. Each main circuit
breaker and the bus tie circuit breaker are protected via 51 and 51N relays. The mains also have 67 and 67N
relays. Note that the 67 relays are polarized via the line voltage transformers, and auxiliary voltage transformers
connected in wye-broken delta are supplied for polarization of the 67N relays. The polarization results in the
indicated tripping directions for these relays. The need for the 67 and 67N relays can be demonstrated by
considering a fault on one of the utility feeds. Should utility feed #2, for example, experience a fault, the fault
current will be supplied both from the upstream system feeding utility feed #2 and from utility feed #1 through
circuit breakers 52-M1, 52-T, and 52-M2. Because the 51 and 51N relays for 52-M1 and 52-M2 are likely set
identically, they will both respond to the fault at the same time, tripping 52-M1 and 52-M2 and de-energizing the
entire downstream system. To avoid this, the 67 and 67N relays are set to coordinate with the 51 and 51N relays,
respectively, so that the 67 and 67N relays trip first. For a fault on utility feed #2, the 67 and 67N relays for 52-M1
31
will not trip due to the fact that the current is flowing in the direction opposite to the tripping direction. However, the
67 and 67N relays on 52-M2 will sense current in the tripping direction and trip 52-M2. The downstream system is
still energized by 52-M1 and 52-T after 52-M2 trips.
32
33
SOURCE
A
A-PHASE
R
R
O
B-PHASE
R
R
O
C-PHASE
R
R
O
LOAD
Figure 7-24: Typical application of current-differential relays for delta-wye transformer protection
87T ZONE OF
PROTECTION
CT
[3]
52
[3]
86T
87T
CT
[3]
Figure 7-25: Transformer differential relay application from figure 7-24 in one-line diagram format
Note that the secondary protective device is shown as a low voltage power circuit breaker. It is important that the
protective devices on both sides of the transformer be capable of fault-interrupting duty and suitable for relay
tripping.
In figure 7-25 a lockout relay is used to trip both the primary and secondary overcurrent devices. The lockout relay
is designated 86T since it is used for transformer tripping, and the differential relay is denoted 87T since it is
protecting the transformer. The wye and delta CT connections are also noted.
34
An important concept in protective relaying is the zone of protection; a zone of protection is the area that a given
protective relay and/or overcurrent device(s) are to protect. While the zone of protection concept applies to any
type of protection (note the term zone selective interlocking as described earlier in this section), it is especially
important in the application of differential relays because the zone of protection is strictly defined by the CT
locations. In figure 7-25 the zone of protection for the 87T relay is shown by the dashed-line box around the
transformer. For faults within the zone of protection, the currents in the CTs will not sum to zero at the relay
operating windings and the relays will operate. Outside the zone of protection the operating winding currents
should sum to zero (or be low enough that the percentage restraint is not exceeded), and therefore the relays
will not operate.
The other major category of differential relays, high-impedance differential relays, use a different principle for
operation. A high-impedance differential relay has a high-impedance operating element, across which the voltage
is measured. CTs are connected such that during normal load or external fault conditions the current through the
impedance is essentially zero. But, for a fault inside the differential zone of protection, the current through the
high-impedance input is non-zero and causes a rapid rise in the voltage across the input, resulting in relay
operation. A simplified schematic of a high-impedance differential relay is shown in figure 7-26 to illustrate the
concept. Note that the relay only has one set of input terminals, without restraint windings. This means that any
number of CTs may be connected to the relay as needed to extend zone of protection, so long as the CT currents
sum to zero during normal conditions. Also note that a voltage-limiting MOV connected across the high-impedance
input is shown. This is to keep the voltage across the input during a fault from damaging the input.
ZONE OF PROTECTION
HIGH-IMPEDANCE
DIFFERENTIAL RELAY
MOV
Z
High-impedance differential relays are typically used for bus protection. Bus protection is an application that
demands many sets of CTs be connected to the relays. It is also an application that demands that that relay be
able to operate with unequal CT performance, since external fault magnitudes can be quite large. The highimpedance differential relay meets both requirements.
Figure 7-27 shows the application of bus differential relays to a primary-selective system. Note that in figure 7-27
the zones of protection for Bus #1 and Bus #2 overlap. Here the 86 relay is extremely useful due to the large
number of circuit breakers to be tripped. Note that all circuit breakers attached to the protected busses are
equipped with differential CTs and are tripped by that busses respective 86 relay. The 87 relays are denoted 87B
since they are protecting busses. The same applies for the 86B relays. Note also that the protective zones
overlap; this is typical practice to insure that all parts of the bus work are protected.
The high-impedance differential relay is typically set in terms of voltage across the input. The voltage setting is
typically set so that if one CT is fully saturated and the others are not the relay will not operate. By its nature, the
high-impedance differential relay is less sensitive than the current-differential relay, but since it is typically applied
to protect bussing, where fault magnitudes are typically high, the additional sensitivity is not required.
35
BUS #1 ZONE OF
PROTECTION
CT
[3]
52-M1
BUS #2 ZONE OF
PROTECTION
[3]
[3]
87B
87B
86B
86B
CT
[3]
52-T
N.C.
BUS #1
CT
[3]
CT
[3]
CT
[3]
52-M2
BUS #2
CT
[3]
CT
[3]
CT
[3]
CT
[3]
CT
[3]
N
IF
ELECTRONIC-TRIP
CIRCUIT BREAKER
MAIN OR SYSTEM
BONDING
JUMPER
TRIP
UNIT W/
GFT
(LSG,
LSIG)
CB CURRENT
SENSORS
IF
NEUTRAL SENSOR
OR CT
IF
GROUND
FAULT
IF
LOAD
Figure 7-28: Low voltage ground fault protection for 4-wire radial system with electronic-trip circuit breaker
36
In figure 7-28 the neutral sensor may be an air-core CT or a conventional iron-core CT. Note that the ground
fault current is diverted around the neutral sensor when it is placed on the load-side of the main or system
bonding jumper (see Section 6 for the definition of main and system bonding jumpers and related discussion).
Under normal unbalanced-load conditions the neutral sensor will detect the neutral current and prevent the
circuit breaker from tripping. Note that if the system is a 3-wire system without a system neutral the neutral
CT is omitted.
If the circuit breaker is not equipped with an electronic trip system, an external ground fault relay may be used
with a zero-sequence sensor to trip the circuit breaker. The circuit breaker must be equipped with a shunt trip
attachment in this case. Figure 7-29 shows an example of this arrangement. In figure 7-29 the external ground
fault relay is noted as GS. In low voltage systems this is the typical notation rather than 51G, although 51G
could be used also. Note that in a 3-wire system the neutral is omitted, and the zero-sequence sensor includes
the phase conductors only.
SOURCE
A
N
IF
BONDING
JUMPER
IF
Circuit Breaker
without Electronic Trip
ST
ZEROSEQUENCE
SENSOR
OR CT
GS
IF
GROUND
FAULT
IF
LOAD
Figure 7-29: Low voltage ground fault protection for 4-wire radial system without electronic trip
circuit breaker
These methods provide sensitive ground fault protection for solidly-grounded radial systems. However, if multiple
sources are involved a more involved system is required in order to obtain reliable ground-fault protection.
37
SOURCE
#1
A
SOURCE
#1
N
IF
MAIN OR SYSTEM
BONDING
JUMPER
B x IF
A x IF
CB-M1
B x IF
CB-M2
B x IF
IF
GROUND
FAULT
IF
CB-T
B x IF
SOURCE
#1
LOADS
SOURCE
#2
LOADS
Figure 7-30: Secondary-selective system with radial ground-fault protection of figure 7-28 applied
The solution is the modified-differential ground fault system. A typical example of such a system is shown in
figure 7-31:
SOURCE
#1
A
SOURCE
#1
N
IF
MAIN OR SYSTEM
BONDING
JUMPER
B x IF
A x IF
A x IF
GT
IF
B x IF
A x IF
CB-M1
GM1
B x IF
IF
IF
B x IF
B x IF
CB-M2
GM2
B x IF
B x IF
GROUND
FAULT
IF
CB-T
B x IF
SOURCE
#1
LOADS
SOURCE
#2
LOADS
In figure 7-31 the breaker internal sensors are shown, but the trip units are omitted for clarity. The ground-fault
function for CB-M1 is noted as GM1, for CB-M2 is noted as GM2, and for CB-T is noted as GT. In this
arrangement, regardless of the ground current dividing factors A and B the correct circuit breakers will sense the
ground fault and trip. Note that this system works regardless of whether CB-T is normally-open or normally-closed.
Non-electronic circuit breakers could also be used, but external CTs and ground relays would have to be utilized.
For unusual system arrangements or arrangements with more then two sources, the system of figure 7-31 can be
expanded. These are usually custom-engineered solutions.
38
10
100
C UR R E NT IN AMP E R E S
1
10K
Figure 7-32 shows typical time-current characteristics for the ground fault function of an electronic-trip circuit breaker.
1000
100
100
10
10
0.10
0.10
10K
10
1K
0.01
1
100
0.01
0.5
T IME IN S E C ONDS
1000
Figure 7-32: Typical electronic-trip circuit breaker ground-fault protection time-current characteristic
This characteristic is adjustable both for pickup and time delay. Discrete relays for use with non-electronic circuit
breakers are also available with similar characteristics.
Care must be taken when coordinating ground-fault protection if multiple levels of ground-fault protection do not exist
downstream from the service or source of a separately-derived system. The NEC Article 230.95 (A) service-entrance
requirement [1] for a maximum of 1200 A pickup and maximum 1-second delay at 3000 A ground-fault current can
lead to a lack of coordination for downstream feeder and branch-circuit ground faults. This is one of the reasons for
the use of other than solidly-grounded systems where maximum system reliability is to be achieved.
Surge protection
Surge protection is protection of conductors and equipment against the effects of voltage surges. These are
usually due to lightning, although switching transients can also cause damaging overvoltages. Unlike overvoltage
relaying, surge protection is directly connected to the power circuit, and for the best protection is usually located
as close as physically practical to the protected equipment.
39
surge arrestor can absorb without damage, in ascending order as listed. Table 7-14 gives commonly-applied MOV
surge arrestor ratings vs. the system voltage. In general, use of surge arrestors with the lowest MCOV exceeding
the anticipated line-to-ground voltage provides the best protection. Detailed insulation coordination studies can
also be performed with the use of transient analysis software. For low-resistance-grounded systems, selection of
the lowest acceptable surge arrestor rating involves comparing the overvoltage vs. time characteristic of the surge
arrestor to the maximum time a ground fault will remain on the system prior to tripping.
For motor circuits, surge capacitors are also often employed. These provide dV/dt protection for the motor
windings. Care must be used when sizing surge capacitors and the effects of harmonic currents must be
evaluated to insure the capacitors will not rupture.
Both surge capacitors and surge arresters are applied without dedicated overcurrent protection. For this reason,
failure of these devices will result in some equipment damage. In the case of surge arresters, use of polymer
housings will result in minimal damage should the arrester fail; the housing will simply split to relieve the internal
overpressure. Use of porcelain housings which can sustain large internal overpressures can result in severe
damage should the arrester fail. In the case of surge capacitors, since they are typically filled with dielectric fluid
and have steel housings they can sustain high internal overpressures, and failure of the housing due to internal
overpressure can result in catastrophic equipment damage and risk to personnel.
Applicable standards include IEEE Std. C62.11 and IEEE Std. C62.22.
Table 7-14: Commonly-applied ratings for metal-oxide surge arrestors
Duty-Cycle Voltage (kV)`
MCOV (kV)
2.6
4160 Y/2400
2400
5.1
8320 Y/4800
4160
4800
7.7
12000 Y/6930
6900
12470 Y/7200
10
8.4
12
10.2
15
12.7
13200 Y/7620
13800Y/7970
20780 Y/12000
12000
12470
18
40
15.3
22860 Y/13200
13200
24940 Y/14400
13800
34500 Y/19920
20780
21
17.0
24
19.5
27
22.0
30
24.4
22860
36
29.0
24940
Use of this system category requires a solid ground conductor (non-earth) path back to the upstream transformer
or generator neutral.
Includes grounded-wye systems where the path to the upstream transformer neutral includes an earth path
41
100
100K
10K
C UR R E NT IN AMP E R E S
1K
100
10
1000
1000
100
10
0.10
T IME IN S E C ONDS
10
0.10
100K
10K
1K
0.01
10
100
0.01
Short-circuit protection involves comparison of the transformer damage curve per IEEE Std. C57.109-1993 with
the primary overcurrent device time-current characteristic. In general, the damage curve must be to the right and
above the primary overcurrent device characteristic. Another constraint on the primary overcurrent device is that it
must be capable of withstanding the inrush of the transformer without tripping (and without damage for currentlimiting fuses). An example time-current characteristic showing protection for a 1000 kVA 13.2 kV Delta:
480 Y/277 V, 5.75%Z dry-type transformer is shown in figure 7-34. The transformer is protected with a 65E
current-limiting primary fuses and a 1200 A electronic-trip secondary circuit breaker. As can be seen from the
figure, the fuses do withstand the inrush without damage since the inrush point is to the left and below the fuse
minimum melt curve. The transformer is protected from short-circuits by the primary fuses. The secondary circuit
breaker provides overload protection at the full-load current of the transformer. Note that the primary fuse and
secondary circuit-breaker characteristics overlap for high fault currents; this is unavoidable and is considered
acceptable. Note also that the fuse curve and the transformer damage curve overlap; this is unavoidable but these
should overlap at the lowest current possible. For currents below the fuse/transformer damage curve overlap the
secondary circuit breaker must protect the transformer; the lower the point of overlap, the more likely the fault is
an external fault on the load side of the secondary circuit breaker and therefore greater chance the secondary
circuit breaker will effectively protect the transformer for faults in this region.
Also note that the transformer damage characteristic is shown twice. Because transformer is a delta-wye
transformer, a ground-fault on the secondary side of the transformer will result in only 57.7% of the maximum
three-phase primary fault current while one secondary winding experiences the full fault current. This is illustrated
in Figure 7-35, as well as the corollary for delta-delta transformers. The damage characteristic has therefore been
shifted to 57.7% of its published value to account for secondary line-to-ground faults. Also, the shifted curve has
another, more conservative curve shown; this is the frequent-fault curve and is applicable only to the secondary
overcurrent device since faults between the transformer secondary and the secondary overcurrent protective
device should not be frequent.
Additional devices, such as thermal overload alarms/relays and sudden-pressure relays, are also available for
protection of transformers. These are typically specified with the transformer itself and can provide very good
protection. However, even if these devices are installed the primary and secondary overcurrent devices must be
coordinated with the transformer as described above.
42
1000
10K
10
1K
100
C UR R E NT IN AMP E R E S
1
1000
XFMR
PRI. FUSE
100
100
XFMR
SEC. CB
10
TX Inrush
0.10
0.10
10K
10
1K
0.01
1
100
0.01
0.5
T IME IN S E C ONDS
10
Figure 7-34: Example protection for a 1000 kVA, 13.2 kV Delta: 480 Y/277V, 5.75%Z dry-type transformer
Differential protection for transformers, as described above, is very effective for transformer internal faults.
If differential protection is supplied it is the primary protection for internal faults and will operate before the
primary overcurrent device. The primary overcurrent device serves as a backup protective device for internal
faults in this case.
Figure 7-35: Fault-current flow for delta-wye transformer L-N faults and delta-delta transformer L-L faults
43
Protection selectivity
The selectivity of protection refers to its ability to isolate an abnormal condition to the smallest portion of the
system possible. In most cases selectivity is a function of how well-coordinated the overcurrent protective devices
in the system are. As an example, consider the system of figure 7-36:
UTILITY SERVICE
A
B
C
D
E
F
G
Figure 7-36 shows a small radial system with a medium voltage utility service, a service substation consisting of a
primary switch step-down transformer protected by a primary fuse, and a secondary switchboard. One of the
switchboard feeder circuit breakers is shown feeding al lighting panel and other loads.
For optimum selectivity, a fault at point G should only cause its lighting panel feeder circuit breaker to trip. The
panel main circuit breaker and all devices upstream should not be affected. If the lighting panel feeder circuit
breaker time-current characteristic does not coordinate with that of the lighting panel main, the main may trip, deenergizing the entire panelboard.
Going upstream, a fault at point F should only cause the panelboard main circuit breaker to trip and a fault at point
E should only cause the switchboard main circuit breaker to trip. A fault at point D may cause the switchboard
main circuit breaker to trip or the primary fuse to blow, but the effect on the system is the same since all of the
loads will be de-energized in either event. A fault at point C should only cause the transformer primary fuse to blow.
Lack of selectivity causes more of the system to be de-energized for a fault in a given location. The severity of the
outage increases as the fault location is considered farther and farther upstream. In this example, if the
transformer primary fuses and the upstream utility recloser, protective relays, or fuses are not coordinated the
entire utility distribution line, or a segment of the line, could be de-energized, affecting other customers.
To analyze system selectivity, a time-current coordination study must be performed. This study analyzes the
time-current coordination characteristics of the protective devices in the system and plots them on time current
curves such as those illustrated in this section. Coordination is considered to be achieved between two devices if
their time-current bands show sufficient clear space between them on the time-current curve or, in the case of
protective relays, if sufficient margin for overtravel, manufacturing tolerances, circuit breaker speed, and safety are
achieved.
44
Coordination is not always possible to maintain in the high fault-current ranges. However, in most cases an
acceptable compromise can be reached since high-level faults are a rare occurrence.
Another important concept is that of backup protection. In this case, for a fault at point G if the lighting panel
feeder circuit breaker fails to trip the panelboard main circuit breaker should trip as dictated by its time-current
curve. If selective coordination exists between the panelboard main circuit breaker and the switchboard feeder
circuit breaker, then the switchboard feeder circuit breaker will not trip. So, backup protection must consider one
level upstream vs. primary protection unless additional backup protective devices are installed.
References
[1]
The National Electrical Code, NFPA 70, The National Fire Protection Association, Inc., 2005 Edition.
[2]
Alan Greenwood, Electrical Transients in Power Systems, New York, John Wiley and Sons Inc., 1971.
[3]
IEEE Recommended Practice for Protection and Coordination of Industrial Power Systems, IEEE Std. 2422001, December 2001.
[4]
Molded-Case Circuit Breakers, Molded Case Switches and Circuit-Breaker Enclosures, UL 489, Underwriters
Laboratories Inc., April 25, 2002.
[5]
IEEE Standard for Low Voltage AC Power Circuit Breakers Used in Enclosures, ANSI/IEEE Standard C37.131990, October 1990, Reaff. April 8, 1996.
[6]
IEEE Standard Rating Structure for AC High Voltage Circuit Breakers, ANSI/IEEE Standard C37.04-1999, June
1999.
[7]
AC High Voltage Circuit Breakers Rated on a Symmetrical Current Basis Preferred Ratings and Related
Required Capabilities, ANSI Standard C37.06-2000, May 2000.
[8]
IEEE Application Guide for AC High Voltage Circuit Breakers Rated on a Symmetrical Current Basis, IEEE Std
C37.010-1999, September 1999.
[9]
Swindler, D.L., Fredericks, C.J., Modified Differential Ground Fault Protection for Systems Having Multiple
Sources and Grounds, Industry Applications, IEEE Transactions on, Volume 30, Issue 6, Nov. 1994.
45
Section 8:
Introduction
Electric motors are an important part of any electrical system. Because they convert electrical energy to
mechanical energy, they are the interface between the electrical and mechanical systems of a facility.
This creates unique challenges for control and protection which have, in turn, led to unique solutions.
This section gives background on various AC motor types, and the control and protection practices commonly
used for these.
AC motor types
Motors generally consist of two basic assemblies: The stator, or stationary part, and the rotor, or rotating part.
Motors have two sets of windings: armature windings, to which the power is applied, and field windings , which
produce a magnetic field that interacts with the magnetic field from the armature windings to produce torque on
the rotor. This torque causes the rotor to rotate. For most AC motors, the armature windings are located on the
stator, and the field windings are located on the rotor (one exception is the field exciter for a brushless
synchronous motor, as described below). For this reason, in most cases the armature windings are known
synonymously as the stator windings.
AC motors in common use today may be divided into two broad categories: Induction (asynchronous) or
synchronous. These two types of motors differ in how the rotor field excitation is supplied. For induction motors,
there is no externally-applied rotor excitation, and current is instead induced into the rotor windings due to the
rotating stator magnetic field. For synchronous motors, a field excitation is applied to the rotor windings. This
difference in field excitation leads to differences in motor characteristics, which leads in turn to different protection
and control requirements for each motor type.
For an induction motor, the speed will always be less than synchronous speed by a factor known as the slip of the
motor. The motor speed can be expressed as:
(8-2)
where
n
s
ns
Induction motors are classified by application with a design letter which gives an indication of key performance
characteristics of the motor. Table 8-1 gives typical design letter characteristics for induction motors. These are
typical characteristics only for further details consult the specific performance standards for the complete
requirements [2,3].
Slip
(%)
Typical Applications
Relative
Efficiency
Design A
Normal locked
rotor torque and
high locked-rotor
current
70-275a
65-190a
175-300
Not
Defined
0.5-5
Medium
or High
Design B
Normal lockedrotor torque and
normal lockedrotor current
70-275a
65-190a
175-300a
600-800
0.5-5
Medium
or High
Design C
High locked-rotor
torque and
normal lockedrotor current
200-285a
140-195a
190-225a
600-800
1-5
Medium
Design D
High locked-rotor
torque and
high slip
275
Not
defined
275
600-800
Medium
IEC Design H
High locked rotor
torque and high
locked rotor
current
200-285a
140-195a
190-225a
800-1000
1-5
Medium
IEC Design N
Normal lockedrotor torque and
high locked rotor
current
70-190a
60-140a
160-200a
800-1000
0.5-3
Medium
or High
Synchronous motors may be further classified as brush or brushless type. The field exciter for a brush-type motor
is typically a DC generator with its rotor mounted on the motor shaft. The output of the DC generator is fed via
brushes and slip rings to the motor field windings. The field exciter for a brushless synchronous motor typically
consists of an AC generator with the field windings on its stator, armature windings on its rotor, and with its rotor
mounted on the motor shaft. The output of the generator is rectified by solid-state rectifier elements also mounted
on the rotor shaft and fed directly to the motor field windings without the need for brushes or slip rings. Because of
the proliferation of solid-state power electronic technology, and because the brushless-type motors require less
maintenance almost all new synchronous motors are brushless-type [1], although many existing installations do
have older brush-type motors in service. In either design the field excitation to the exciter may be varied to vary
the power-factor operation of the motor, and in fact power factor correction is one common use of synchronous
motors since they can be made to operate at leading power factors.
C.) Enclosure types, cooling methods and other general application information
Please refer to [3] for more information on motor enclosure types and cooling methods, as well as additional
general application information for motors.
Further, the shaft rotational acceleration is related to the output torque and the inertia of the load as follows:
(8-4)
where
T
J
Because a= dn/dt, the speed of the motor shaft can be written as:
(8-5)
The inertia of the load (and rotor), then, is crucial to the acceleration rate of the motor shaft (and the load) and
thus to the output speed of the shaft. A typical design B induction motor torque-speed characteristic is as shown in
figure 8-1, along with pertinent characteristics from table 8-1 labeled:
1.2
1
0.8
0.6
0.4
LockedRotor
Torque
0.2
0.
06
0.
12
0.
18
0.
24
0.
3
0.
36
0.
42
0.
48
0.
54
0.
6
0.
66
0.
72
0.
78
0.
84
0.
9
0.
96
Breakdown
Torque
Pull-Up
Torque
Figure 8-1 shows the motor output torque as a function of shaft speed with full rated voltage applied to the motor.
To show the performance of a motor when connected to a load, a typical speed-torque-characteristic for a fan is
plotted along with the motor speed-torque characteristic in figure 8-2. The load speed-torque characteristic is a
plot of the torque required to drive a load at a given speed. Several points can be made regarding the motor and
load of figure 8-2:
I
The motor locked-rotor torque is greater than the load torque at zero speed. This means the motor can start with
the load connected.
The motor pull-up torque is greater than the load torque during the acceleration period. This means that the
motor can successfully accelerate the load.
The steady-state speed of the motor is where the motor-torque and load-torque curves cross the steady-state
operating point approximately 98.5% synchronous speed. The motor slip is therefore approximately 1.5%
The difference between the motor output torque and the load torque is the accelerating torque for the motor-load
system. The accelerating torque is the same as given in eq. (8-1) above. A plot of the accelerating torque is given
in figure 8-3.
1.2
1
Steady-State Operating
Point
0.8
Motor
Torque
0.6
0.4
0.2
Load
Torque
Accelerating Torque
0.98
0.91
0.84
0.7
0.77
0.63
0.56
0.49
0.42
0.35
0.28
0.21
0.14
0.07
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.
06
0.
12
0.
18
0.
24
0.
3
0.
36
0.
42
0.
48
0.
54
0.
6
0.
66
0.
72
0.
78
0.
84
0.
9
0.
96
Figure 8-3: Accelerating torque for motor and load of figure 8-2
With the accelerating torque known, the motor (and load) shaft speed can be calculated from eq. (8-4) and (8-5).
In practice, this is best left to computer simulation. A typical plot of the approximate shaft speed, is shown in
figure 8-4.
As can be seen from figure 8-4, for the example shown the motor accelerates to steady-state speed in
approximately 14 seconds. The motor breakdown torque and load and motor moments of inertia (typically
referred to as motor wk2 and load wk2, respectively) must be known to obtain this speed vs. time characteristic.
1.2
1
0.8
0.6
0.4
0.2
72
63
67
.5
54
58
.5
45
49
.5
36
40
.5
27
31
.5
18
22
.5
9
13
.5
4.
5
0
0
The importance of the above analysis lies in the fact that for successful motor starting the motor must be able to
successfully support the load torque during acceleration. If the motor cannot do this, it will stall during starting.
Proper motor selection, considering both the HP and torque characteristics, is essential for proper starting.
Further, for an induction motor the slip is determined by the torque characteristics of the motor and load.
Time (s)
Figure 8-4: Typical motor speed vs. time for the example above
For a synchronous motor, starting analysis is similar since the damper windings of the motor give a speed-torque
characteristic similar to that of an induction motor. For a synchronous motor the steady-state speed is the
synchronous speed of the motor, which is achieved by applying the field excitation once the motor has
accelerated to a speed close to synchronous speed on the damper windings.
Class B: Class B controllers are DC air-break manual or magnetic controllers for service on 600 V or less. They
are capable of interrupting operating overloads but not short circuits or faults beyond operating overloads.
Class V: Class V controllers are AC vacuum-break magnetic controllers for service on 1500 V or less, and
capable of interrupting operating overloads but not short circuit or faults beyond operating overloads.
Low voltage NEMA-rated contactors are designated in sizes 00 (smallest) through 9 (largest) for various duty
applications per [5]. Figure 8-5 shows a NEMA-rated low voltage contactor along with a manual motor starting
switch, a starter, and a combination starter.
a.)
b.)
c.)
d.)
Figure 8-5:
a.) Motor starting contactor,
b.) Manual motor starter,
c.) Motor starter with contactor and overload relay,
d.) Combination starter with magnetic-only circuit breaker, contactor, thermal overload relay and
pilot devices
Control of contactors using maintained-contact devices is referred to as two-wire control. Use of momentarycontact devices in the control of contactors is referred to as three-wire control. Three-wire control has the
advantage of allowing the contactor to open and remain open if the line voltage should fail; this arrangement is
typical to provide undervoltage protection for motors and prevent inadvertent re-energization after a power failure.
Two-wire and three-wire control are shown in figure 8-6.
Figure 8-6: Low voltage contactor control: (full-voltage non-reversing control shown):
a.) Contactor nomenclature,
b.) Two-wire control,
c.) Three wire control
Medium voltage contactors are typically use vacuum as the interrupting means. Unlike a circuit breaker, a medium
voltage vacuum contactor is specifically designed for long life in load-interrupting duty rather than for short-circuit
interrupting duty. However, unlike their low voltage counterparts a medium voltage contactor may be able to
interrupt short-circuit currents beyond operating overloads.
Medium voltage air-break, vacuum, or oil-immersed controllers are classified by [7] as class E. Class E controllers
are further divided into class E1 and E2 as follows:
Class E1: Class E1 controllers employ their contacts for both starting and stopping the motor and interrupting
short circuits or faults exceeding operating overloads.
Class E2: Class E2 controllers employ their contacts for starting and stopping the motor and employ fuses for
short circuits or faults exceeding operating overloads.
Above 7200 V, motor control is generally accomplished using circuit breakers.
Another form of across-the-line starting is full voltage reversing starting, in which the motor may be made to turn
in either direction. This arrangement utilizes a full voltage reversing contactor with six poles, interlocked so that
only one set of contacts may be closed at a given time. The contacts are connected so that in the reverse
direction the motor has two phases swapped, forcing it to run in the opposite direction.
Across-the-line starting is the least expensive method, but it has the disadvantage that the full locked-rotor current
will be drawn during starting. This can cause voltage sags. Also, since the motor acceleration is dependent only
upon the motor output torque and load torque characteristics (along with the line voltage level), the acceleration is
not as smooth as can be attained with other starting methods.
is the motor output torque at reduced voltage when the autotransformer is in the circuit
is the motor output torque with full voltage applied
Therefore, the motor output torque at the 80% autotransformer tap is 64% of the full-voltage torque value, at 65%
tap the torque is 42.25% of the full-voltage torque, and at 50% tap the torque is 25% of the full-voltage value.
Care must be taken to insure that the motor can be started at the tap value selected. Also, the thermal duty
capabilities of the autotransformer per NEMA ICS-9 must be taken into account; these will generally limit the
lowest tap to which the motor may be connected without damage to the autotransformer during starting.
A typical low voltage implementation of the reduced-voltage autotransformer starter is shown in figure 8-8.
In figure 8-8 there are three contactors, labeled R, 1S, and 2S. The control scheme is designed so that the first
contactor to close is 1S, connecting the two autotransformers in open-delta. Once contactor 1S is closed,
contactor 2S closes, connecting the motor to the output of the autotransformer, in this case set to 50%. After a
pre-set time delay or current transition level, contactor 1S opens, leaving the motor energized through the noncommon autotransformer windings. Once contactor 1S is open, contactor R closes, energizing the motor at full
voltage. This is a closed-transition scheme; open transition schemes exist also.
The soft-start controller can also decelerate the motor in the same manner using the SCRs.
Because the SCRs dissipate heat, the equipment heat dissipation and the ambient temperature are concerns
when applying soft-start controllers and must be considered carefully.
Dedicated motor power factor correction capacitors must be switched out of the circuit during starting when
adjustable-speed drives are employed, due to the harmonic voltage interactions that could cause them to fail.
Surge capacitors should not be used at motors which are soft-started for the same reason.
Because soft-starters are microprocessor-based devices, they are typically supplied with communications and
internal diagnostic capabilities, making them a truly cutting-edge motor starting (and stopping) solution.
9
10
So, for these types of processes the torque required to turn them is proportional to the square of the speed. But,
the power required to turn them is proportional to the cube of the speed, and this is what makes motor speed
control economically attractive [3]. To further this argument, consider the energy wasted when mechanical means
such as the throttling valves or dampers are used to control a process which is being driven from a motor running
at full speed. It is clear that motor speed control can be used to save energy by reducing wasted energy used to
mechanically control the process.
Advantages
Disadvantages
Across-the -Line
Simple
Cost-Effective
Reduced-voltage
autotransformer
Reduced-Voltage
Resistor or
Reactor
Wye-Delta
Some Flexibility in starting characteristics due adjustable Large equipment size due to autotransformers
taps on autotransformers
Limited duty cycle
Limited flexibility in starting characteristics
Higher inrush current than with reduced-voltage
autotransformer
Large equipment size due to resistors/reactors
Part-Winding
Smooth Acceleration
Relatively Expensive
Smooth Acceleration
11
overspeed operation can result in safety issues. Further, pulse-width modulated (PWM) drive outputs can cause
repetitive voltage overshoots referred to as ringing, which can reduce the life expectancy of a general-purpose
motor. As per [3], the motor manufacturer should be consulted before applying a general-purpose motor in an
adjustable-speed drive application.
Various designs exist for adjustable-speed drives, however for low voltage drives the most prevalent is the
voltage-source pulse-width modulated design. As its name implies, the output is pulse-width modulated to reduce
the output harmonic and noise content. The AC input to the drive is typically a diode rectifier. A simplified circuit
topology for al voltage-source PWM drive is given in figure 8-11.
Figure 8-11: Voltage-source PWM adjustable-speed drive: simplified circuit topology for low voltage
implementation
The output stage for the circuit in figure 8-11 consists of Insulated-Gate Bipolar Transistors (IGBTs), which are
commonly used in low voltage PWM adjustable-speed drives instead of SCRs due to their superior switching rate
capability.
Adjustable speed drives offer superior speed control for motors through 10,000hp, depending upon the system
voltage [1]. They usually incorporate protection for the motor as well, allowing the omission of separate motor
protective relays if desired. Due to the high switching frequencies involved and their interaction with the cable
capacitance, the length of the cable runs between the output of the drive and the motor are limited, and, as
mentioned above for soft-starters, power factor correction capacitors and surge capacitors should not be used at
the output of an adjustable speed drive. Also due to the high switching frequencies, common-mode noise on the
grounding conductors can be an issue when these drives are employed.
On the incoming line, adjustable speed drives produce harmonics which must be taken into account in the over-all
system design. This topic is addressed in a later section of this guide.
Adjustable speed drives, like soft-starters, are microprocessor-based devices. Therefore, they can interface with
the automation infrastructure of a facility.
With the exception of a few isolated cases, for most industrial and commercial facilities adjustable speed drives
are the speed control of choice for AC motors.
Rotor-resistance speed control similar to rotor-resistance starting, this method consists of varying the effective
resistance in the rotor of a wound-rotor induction motor to vary the speed. Variants of this method include rotor
power recovery systems using a second machine or an auxiliary solid-state rectifier and converter.
Multi-speed motor This type of motor is typically a squirrel-cage motor which has up to four fixed speeds.
Primary voltage adjustment using saturable reactors This method is only applicable to NEMA Design D motors
and offers a very narrow range of speed control.
Because of the limitations of these methods and the fact that they do not fit a wide range of motors, the adjustable
speed drive is typically the solution of choice for most commercial and industrial facilities.
12
B.) Plugging
Plugging is the reversal of the phase sequence on an induction motor via switching two phase connections to the
motor, which will cause the motor to come to a very rapid stop due to torque developed on the rotor in the
opposite direction from the current running direction. A zero-speed switch should be used to prevent reversal of
the motor.
Motor protection
Motor protection involves protection of a motor from abnormal conditions. The most common abnormal condition
is an overload, which can produce damaging heating effects in the motor. For this reason, overload relays are the
primary means of motor protection. However, short-circuit protection is also required to minimize damage to the
motor from an internal short-circuit. Other protective devices are also available, their use depending upon the size
of the motor and the cost of protection vs. the cost of the motor.
14
100K
C UR R E NT IN AMP E R E S
10K
10
1000
1K
100
The resulting time-current coordination is shown in figure 8-13. Note that in figure 8-13 the purple curve to the
right of the overload relay curve is the motor thermal damage curve, obtained from the motor manufacturer. If this
curve is not available the relay or motor manufacturers selection tables should be used for selection of the
overload relay. The thermal overload relay protects the motor from overloads, while at the same time not opening
the motor inrush current or full-load current, as denoted by the purple MOTOR current curve to its left. Note the
high-current region (with current equal to the motor locked-rotor current) with an acceleration time of
approximately 9 seconds; this curve is dependent upon the connected load and must also obtained from the
motor manufacturer unless the motor acceleration time can be determined. In many cases the motor starting
current curve will not be available; for most cases a Class 10 overload relay will clear the locked-rotor current,
with Class 20 relays applied for higher service-factor motors such as NEMA design T-frame motors and Class 30
applied for high-inertial loads [2]. The magnetic-only circuit breaker protects the cable for short-circuits, as
denoted by the red CABLE short-circuit characteristic to the right of the circuit breaker characteristic. Finally,
while it is not shown on the curve the contactor can break up to 10 x its motor FLA rating, or 5400A, up to 10
times without servicing per [5] which is more than the maximum trip current of the circuit breaker; the contactor is
therefore adequately protected. The motor and its branch circuit is, therefore, adequately protected.
1000
CB
100
100
O.L.
10
CABLE
10
MOTOR
0.10
T IME IN S E C ONDS
0.10
100K
10K
1K
0.01
10
100
0.01
For larger motors on solidly-grounded systems low voltage ground-fault protective devices may also be required to
allow coordination with upstream ground-fault protective devices. The application of these falls under the same
guidelines as given in System protection scetion (section 7 in this guide).
15
In addition to the overload protection described above, thermostats are commonly installed in three-phase
industrial-service 460 V motors from 11 kW through 150 kW (14-200hp) [2]. These are bimetallic devices that
operate at one fixed temperature and serve to de-energize the motor if the temperature setpoint is exceeded.
Low voltage motors are also occasionally provided with undervoltage relays, either to trip or prevent energization
when an undervoltage condition exists.
RTDs Resistance Temperature Detectors are typically made of platinum, nickel, or copper and exhibit an
increasing resistance with increasing temperature. The RTD resistance is used to monitor the temperature at
various points in the motor, typically in the stator windings. The temperature is used to provide precise overload
protection for the motor. Per [2], RTDs should be specified for all motors 370 kW (500 hp) and above.
Negative-Sequence Overcurrent (Device 46) This is used to protect against damaging negative-sequence
currents, which can be caused by unbalanced voltages.
Phase sequence (Device 47) This is used to prevent the single-phasing of three-phase motors, which can
cause thermal damage if not detected.
Differential (Device 87) This is used to provide sensitive, high-speed protection for motor internal faults.
Typically only larger motors are provided with differential protection. In addition to traditional differential
protection, motors can also be equipped with self-balancing differential protection in which only one CT is used
for each phase, with both ends of each winding passing through that phases CT. Both are shown in figure 8-14.
Note that both ends of each stator winding must be brought to terminals to utilize differential protection.
Traditional differential protection may utilize either percentage differential (preferred) or high-impedance
differential relays. Self-balancing differential protection typically utilizes a standard overcurrent relay element.
Ground Fault Protection (Device 50G): Almost all medium voltage motors on solidly-grounded or low-resistancegrounded systems are provided with ground-fault protection. This is accomplished with a zero-sequence CT and
is almost always instantaneous.
87M
87M
87M
87M
87M
87M
a.)
Figure 8-14: Motor differential protection:
a.) Traditional
b.) Self-balancing
16
b.)
Typical overload and short-circuit protection for a medium voltage motor may be illustrated by considering the
following: A 750 hp, 4160 V motor is to be protected. The motor has a nameplate full-load current value of 96 A
and a locked-rotor current of 576 A, and a service factor of 1.15. A microprocessor-based motor protection relay is
to be utilized. The motor is to be provided with R-rated fuses for short-circuit protection. NEC Article 430.224 [6]
states that for motors over 600V the conductors shall have an ampacity no less than that at which the motor
overload protective device(s) are to trip. The pickup value for the overload protection is to be set equal to the
service factor times the nameplate full-load current, which is 110.4 A; the cables are copper in underground
conduit, therefore the cable size selected is #2AWG, with an ampacity of 145A per NEC table 310.77 [6]. The CT
primary ratings for the motor protection relay are typically selected as no less than 1.5 times the motor full load
current to avoid saturation (must be checked!) in this case 200:5. To coordinate with the overload protection and
protect the motor branch circuit cables and motor, a 6R fuse is chosen (note that per NEC Article 430.225 [6] the
motor overcurrent protection must be coordinated to automatically interrupt overload and fault currents in the
motor, but there is not specific constraint given for the short-circuit protection, unlike the requirements for motors
under 600 V per above). The motor switching device is a vacuum contactor rated 5.5 kV with an interrupting
rating of 5000A. A one-line representation of the motor branch circuit is shown in figure 8-15, excluding
ground-fault protection.
Figure 8-15: Example medium voltage motor circuit, excluding ground-fault protection
The resulting time-current coordination for this circuit is shown in figure 8-16. Note that the purple MV MOTOR
load current curve is to the left and below the green overload relay characteristic, therefore the motor inrush and
full-load current does not trip the overload relay. Unlike the case for a low voltage motor, this is typically available
from the manufacturer, who has analyzed the motors performance when connected to the driven load. Note also
that the purple motor thermal damage curve is to the left and above the relay overload curve, indicating the motor
is protected for overloads. The same applies for the red MV CABLE rated full-load current marker at the top of
the plot. The motor thermal damage curve is obtained from the motor manufacturer; if the entire curve is not
available, the motor hot safe-stall time provides one point on the curve. The red MV CABLE short-circuit
damage curve is to the right and above the blue MV FUSE characteristic, therefore the cable is protected for
short-circuits by the fuses. Finally, note that the fuse total clearing and overload relay curves cross at
approximately 900 A; this is well above the inrush of 576 A, but well below the contactor rating of 5000 A. The
fuse will therefore clear faults above the contactors 5000 A rating before the contactor opens.
A.) General
The NEC basic requirements for motors, motor circuits, and controllers are given in NEC Article 430 [6], and are
supplemented by additional articles for specific motor-driven equipment. Article 430 is divided into 14 parts. The
requirements which apply to each part of a motor circuit are illustrated in figure 8-17.
17
100
100K
10K
C UR R E NT IN AMP E R E S
1K
100
10
1000
1000
MV CABLE
RELAY
MV CABLE
100
MV FUSE
RELAY
10
MV MOTOR
10
10K
0.01
1K
0.10
100
0.10
T IME IN S E C ONDS
0.01
100K
10
One of the main premises of Article 430 is the fact that the hp or kW rating of a motor is the output rating, as
discussed above. The motor electrical input characteristics will vary based upon the motor design. The
requirements in Article 430 are designed around this fact, as will be illustrated below.
Several definitions are given in Article 430 for terms unique or have meanings unique to that article:
Adjustable Speed Drive: A combination of the power converter, motor, and motor mounted auxiliary devices
such as encoders, tachometers, thermal switches, and detectors, air blowers, heaters, and vibration sensors.
18
19
Conductors that supply several motors or a motor(s) and other loads must have an ampacity not less than 125%
of the full-load current rating of the largest motor in the group plus the sum of all the full-load currents of all other
motors in the group, plus the ampacity required for other loads. Various exceptions apply, and the authority having
jurisdiction may grant permission for a lower ampacity, provided the conductors have the ampacity for the
maximum load determined in accordance with the sizes and number of motors supplied and the character of their
loads and duties. [430.24, 430.25]
Where a motor installation includes a capacitor connected on the load side of the motor overload device, the
effect of the capacitor must be disregarded in sizing the motor circuit conductor. [460.9, referenced in 430.27]
E.) Motor branch circuit short-circuit and ground fault protection (Part IV.)
Motor branch circuit short-circuit and ground fault protective devices must comply with Table 430.52, which gives
maximum ratings, in percentage of the motor full-load current, which can be used for various motor and protective
device types. If the value for the protective device rating does not correspond with a standard size for a fuses,
nonadjustable circuit breakers, thermal protective devices, or possible settings of adjustable circuit breakers, the
next higher standard size is permitted. If the value for the protective device rating is no sufficient for the starting
current of the motor, various exceptions apply depending upon the protective device type. [430.52 (C) (1)].
Where maximum branch-circuit short-circuit and ground-fault protective device ratings are shown in the
manufacturers overload relay table for use with a motor controller or are otherwise marked on equipment, they
must not be exceeded even if otherwise permitted by Table 430.52. [Table 430.52 (C) (2)]
Instantaneous-trip circuit breakers may only be used if adjustable and if part of a listed combination motor
controller having coordinated motor overload and short-circuit and ground-fault protection in each conductor.
Exceptions apply. [Table 430.52 (C) (3)]
For a multi-speed motor, a single short-circuit and ground-fault protective device is permitted for two or more
windings, so long as the rating of the protective device does not exceed the percentage per Table 430.52 of the
smallest winding protected. Exceptions apply. [430.52 (C) (4)]
So long as the replacement fuse size is marked adjacent to the fuses, suitable fuses are permitted in lieu of the
devices listed in Table 430.52 for power electronic devices in a solid state motor control system. [430.52 (C) (5)]
A listed self-protected combination controller is permitted in lieu of the devices specified in Table 430.52 so long
as the adjustable instantaneous trip settings do not exceed 1300% of full-load motor current for other than Design
B energy-efficient motors and 1700% of full-load current for Design B energy-efficient motors. The same applies
for a motor short-circuit protector, so long as it is part of a listed motor controller having coordinate motor overload
protection and short-circuit and ground-fault protection. [430.52 (C) (6), 430.52 (C) (7)]
Torque motors must be protected at the motor nameplate current rating in accordance with 240.4 (B). [430.52 (D)]
Two or more motors or one or more motors and other loads are permitted to be connected to the same
branch circuit if:
I
The motors are not over 1hp, the branch circuit is 120 V and protected at not over 20 A 600 V or less protected
at not over 15 A, the full-load rating of each motor does not exceed 6 A, the rating of the branch-circuit shortcircuit and ground-fault protective device marked on any of the controllers is not exceeded, and individual
overload protection confirms to 430.32, OR,
If the branch circuit short-circuit and ground-fault protective device is selected not to exceed the requirements of
430.52 for the smallest rated motor, each motor has individual overload protection, and it can be determined that
the branch-circuit short-circuit and ground-fault protective device will not open under the most severe normal
conditions of service that might be encountered, OR,
The motors are part of a group installation complying with 430.52 (C) and (D).
[430.53]
For multimotor and combination load equipment, the rating of the branch-circuit and ground-fault protective device
must not exceed the rating marked on the equipment. [430.54]
Motor branch circuit and ground-fault protection may be combined into a single protective device where the rating
or setting of the device provides the overload protection specified in 430.32. [430.55]
21
group of coordinated controllers that drive several parts of a single machine or piece of apparatus. In this case the
disconnecting means must be located in sight from the controllers, and both the disconnecting means and the
controllers must be located in sight from the machine or apparatus. [430.102]
A motor disconnecting means must be located in sight from the motor location and the driven machinery location
unless the controller disconnecting means is individually capable of being locked in the open position and either
a.) such a location of the disconnecting means is impracticable or introduces additional or increased hazards to
persons or property, or b.) the motor is in an industrial installation where conditions of maintenance and
supervision ensure that only qualified persons service the equipment. The controller disconnecting means per
above may be permitted to serve as the disconnecting means for the motor if it is located in sight from the motor
location and the driven machinery location. [430.102]
The disconnecting means must open all ungrounded supply conductors and must be designed so that no pole can
be operated independently. The disconnecting means is permitted to be in the same enclosure with the controller.
The disconnecting means must clearly indicate whether it is in the open (off) or closed (on) position. The
disconnecting means may be a listed motor circuit switch rated in horsepower, a listed molded case circuit
breaker, a listed molded case switch, or an instantaneous trip circuit breaker that is part of a listed combination
controller. Listed manual motor controllers additionally marked as suitable as motor disconnect are permitted as
a disconnecting means where installed between the final motor branch-circuit short-circuit protective device and
the motor. [430.103, 430.104, 430.109 (A)]
System isolation equipment must be listed for disconnection purposes. Where system isolation equipment is used
it must be installed on the load side of the overcurrent protection and its disconnecting means. The disconnecting
means must be a listed motor-circuit switch rated in horsepower, a listed molded case circuit breaker, or a listed
molded-case switch. [430.109 (A) (7)]
Stationary motors of 1/8 hp or less may use the branch-circuit overcurrent device as the disconnecting means.
Stationary motors rated 2hp or less and 300V or less may use a general-purpose switch with an ampere rating not
less than twice the full-load current rating of the motor, a general-use AC snap switch for use only on AC, or a
listed manual motor controller with a hp rating not less than the motor hp and marked suitable as motor
disconnect as the motor disconnecting means. [430.109 (B), 430.109 (C)]
For stationary motors rated at more than 40hp up to and including 100hp, the disconnecting means is permitted to
be a general-use or isolating switch where plainly marked do not operate under load. [430.109(E)]
Cord-and-plug connected motors with a horsepower-rated attachment plug and receptacle having ratings no loess
than the motor ratings may use the attachment plug and receptacle and the disconnecting means. Cord-and-plug
connected appliances per 422.32, room air conditioners per 440.63, or a portable motor rated 1/3 hp or less do
not require the hp-rated attachment plug and receptacle. [430.109 (F)]
The ampere rating of the disconnecting means must not be less than 115% of the full load current rating of the
motor, unless it is rated in hp and has a hp rating not less than the hp of the motor. For torque motors the
disconnecting means must have a an ampere rating of at least 115% of the motor nameplate current. A method
for determining the required disconnect rating for combination loads is given in 430.110 (C). [430.110]
Each motor must be provided with its own disconnecting means, unless a number of motors drive several parts of
a single machine or piece of apparatus, a group of motors is under the protection one set of branch-circuit
protective devices as permitted by 430.53 (A), or where a group of motors is in a single room within sight from the
location of the disconnecting means. [430.112]
Where a motor or motor-operated equipment receive electrical energy from more than one source, each source
must be provided with a disconnecting means from each source of electrical energy immediately adjacent to the
equipment served. The disconnecting means for the main power supply to the motor is not required to be
immediately adjacent of the controller disconnecting means can be locked in the open position.
22
position that will render the overload device in the circuit inoperative. Motor starting rheostats must be designed
so that the contact arm cannot be left on intermediate segments. [430.82]
Stationary motors of 1/8 hp or less which are normally left running and is constructed so that it cannot be
damaged by overload or failure to start, the branch-circuit protective device is permitted to serve as the controller.
Portable motors rated 1/3 hp or less may have an attachment plug and receptacle serve as the controller. [430.81]
Controllers, other than inverse time circuit breakers and molded case switches, must have horsepower ratings at
the application voltage not lower than the horsepower rating of the motor. A branch circuit inverse time circuit
breaker or molded case switch is permitted as a controller for all motors. For stationary motors 2hp or less and
300 V or less, a general-use switch having an ampere rating not less than twice the full-load current rating of the
motor or an AC only snap switch where the motor full-load current rating is not more than 80% of the ampere
rating of the switch may serve as the controller. For torque motors, the controller must have a continuous-duty,
full-load current rating not less than the nameplate current rating of the motor. [430.83]
A controller with a straight voltage rating, for example 240 V or 480 V, is permitted to be applied in a circuit in
which the nominal voltage between any two conductors does not exceed the controllers voltage rating.
A controller with a slash rating, for example, 480 Y/277 V, may only be applied on a solidly-grounded circuit where
the nominal voltage to ground from any conductor does not exceed the lower of the two values of the controllers
voltage rating and the nominal voltage between any two conductors does not exceed the higher value of the
controllers voltage rating. [430.83 (E)]
A controller need not open all conductors to the motor, unless it also serves as a disconnecting means [430.84].
The controller must only open enough conductors as is necessary to stop the motor.
A controller is permitted to disconnect the grounded conductor, so long as the controller is designed so that the
pole which disconnects the grounded conductor cannot open without simultaneously opening all conductors of the
circuit. [430.85]
Each motor must have its own individual controller, unless a number of motors drive several parts of a single
machine or piece of apparatus, a group of motors is under the protection one overcurrent device as permitted by
430.53 (A), or where a group of motors is in a single room within sight from the location of the disconnecting
means. An air-break switch, inverse time circuit breaker, or oil switch may be permitted to serve as the controller
and disconnecting means if it complies with the requirements for controllers in 430.83, opens all ungrounded
conductors to the motor, and is protected by an overcurrent device in each ungrounded conductor. An
autotransformer type controller must be provided with a separate disconnecting means. Inverse-time circuit
breakers and oil switches are permitted to be both hand and manually operable. [430.111]
Motor control circuits must be provided with overcurrent protection in accordance with 430.72. [430.72]
Motor control circuits must be arranged so that they will be disconnected from all sources of supply when the
disconnecting means is in the open position. The disconnecting means may be two separate adjacent devices,
one to disconnect the motor circuit, the other to disconnect the control circuit. Various exceptions apply to the
requirement to the need for the two disconnecting means to be adjacent to each other. Control transformers in
controller enclosures must be connected to the load side of the disconnecting means for the motor control
circuit. [430.74]
Where damage to a motor control circuit would constitute a hazard, all conductors of such a remote motor control
circuit that are outside the control device itself must be installed in a raceway or otherwise suitably protected from
physical damage. Where one side of the motor control circuit is grounded, the motor control circuit must be
arranged so that an accidental ground in the control circuit remote from the motor controller will not start the motor
or bypass manually operated shutdown devices. [430.73]
23
Where the power conversion equipment is marked to indicate that motor overload protection is included, additional
overload protection is not required. If a bypass circuit is utilized, motor overload protection as described in part III
(see above) must be provided in the bypass circuit. For multiple-motor applications individual motor overload
protection per part III is required. [430.124]
Adjustable speed drive systems must protect the motor against overtemperature conditions by means of a motor
thermal protector per 430.32, an adjustable speed drive controller with load and speed-sensitive overload
protection and thermal memory retention upon power loss, overtemperature protection relay utilizing thermal
sensors embedded in the motor and meeting the requirements of 430.32 (A)(2) or (B)(2), or a thermal sensor
embedded in the motor that is received and acted upon by an adjustable speed drive. Motors that utilize external
forced-air or liquid cooling systems must be provided with protection that will be continuously enabled or enabled
automatically if the cooling system fails. For multiple motor applications, individual motor overtemperature
protection must be provided. The provisions of 430.43 and 430.44 apply to motor overtemperature protection
means. [430.24]
The disconnecting means is permitted to be in the incoming line conversion equipment and must have a rating of
not less than 115% of the rated input current of the conversion unit. [430.128]
24
operate to failure if necessary to prevent a greater hazard to persons, the sensing device(s) are permitted to be
connected to a supervised annunciator or alarm instead of interrupting the motor circuit [430.225]
Fault current protection must be provided by either a circuit breaker, arranged so that it can be serviced without
hazard, or fuses. A circuit breaker must open each ungrounded conductor. Fuses must be placed in each
ungrounded conductor and must be furnished with a disconnecting means (or be of the type that can serve as the
disconnecting means) and arranged so that they cannot be serviced while energized. Automatic reclosing of the
fault-current interrupting device is not permitted unless the circuit is exposed to transient faults and such
automatic reclosing does not create a hazard to persons. Overload and fault-current protection may be provided
by the same device. [430.225]
The ultimate trip current of overload relays or other motor-protective devices must not exceed 115% of the
controllers continuous current rating. Where the motor branch-circuit disconnecting means is separate from the
controller, the disconnecting means current rating must not be less than the ultimate trip setting of the overcurrent
relays in the circuit.
The controller disconnecting means must be capable of being locked in the open position.
References
[1]
Donald G. Fink, F. Wayne Beaty, Standard Handbook for Electrical Engineers, New York: McGraw-Hill, 2000.
[2]
IEEE Recommended Practice for Protection and Coordination of Industrial Power Systems, IEEE Std. 242-2001,
December 2001.
[3]
Safety Standard and Guide for Selection, Installation, and Use of Electric Motors and Generators, NEMA
Standards Publication MG 2-2001
[4]
Industrial Controls and System: General Requirements, NEMA Standards Publication ICS 1-2000.
[5]
Industrial Control and Systems: Controllers, Contactors, and Overload Relays Rated 600 Volts, NEMA
Standards Publication ICS 2-2000.
[6]
The National Electrical Code, NFPA 70, The National Fire Protection Association, Inc., 2005 Edition.
[7]
Industrial Control and Systems: Medium Voltage Controllers Rated 2001 to 7200V AC.
[8]
P.C. Sen, Principles of Electric Machines and Power Electronics, New York: John Wiley & Sons, 1989.
25
Section 9:
Introduction
Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,
transmission, distribution, or control of electrical energy. This section concentrates upon commonly-used power
distribution equipment: Panelboards, Switchboards, Low Voltage Motor Control Centers, Low Voltage Switchgear,
Medium Voltage Power and Distribution Transformers, Medium Voltage Metal Enclosed Switchgear, Medium
Voltage Motor Control Centers, and Medium Voltage Metal-Clad switchgear. Each has its own unique standards
and application guidelines, and one facet of good power system design is the knowledge of when to apply each
type of equipment and the limitations of each type of equipment. All of these equipment described herein are
typically custom-engineered on a per-order basis.
Panelboards
Table 9-1: Quick reference Panelboards
120-600 V
30-1200 A
Through 200 kA
UL 50, UL 67, CSA C22.2 No. 29, CSA C22.2 No. 94,
NEMA PB 1, Federal Specification W-P-115C, NEC
1, 3R, 5, 12
Article 408
Panelboards are the most common type of power distribution equipment. A panelboard is defined as a single
panel or group of panel units designed for assembly in the form of a single panel, including buses and automatic
overcurrent devices, and equipped with or without switches for the control of light, heat, or power circuits;
designed to be placed in a cabinet or cutout box placed in or against a wall, partition, or other support; and
accessible only from the front [2]. It typically consists of low voltage molded-case circuit breakers arranged
with connections to a common bus, with or without a main circuit breaker. Figure 9-1 shows typical examples
of panelboards.
Panelboards are used to group the overcurrent protection devices for several circuits together into a single piece
of equipment. In small installations they may serve as the service equipment. The NEC [2] divides panelboards
into two categories:
Lighting and Appliance Branch-Circuit Panelboard: A panelboard having more than 10 percent of its
overcurrent devices protecting lighting and appliance branch circuits.
Power Panelboard: A panelboard having 10 percent or fewer of its overcurrent devices protecting lighting and
appliance branch circuits.
Lighting and appliance branch-circuit panelboards are limited to a maximum of 42 overcurrent devices, excluding
mains. UL 67 [3] designates Class CTL Panelboard as the marking for appliance and branch circuit panelboards;
CTL stands for circuit limiting. In some manufacturers literature lighting and appliance branch-circuit
panelboards for residential or light commercial use are referred to as loadcenters.
Panelboards are available with built-in main devices or as main lugs only (MLO). The NEC [2] requires appliance
and branch circuit panelboards to be individually protected on the supply side by not more than two main circuit
breakers or two sets of fuses having a combined rating no greater than the rating of the panelboard. Lighting and
appliance branch circuit panelboards are not required to have individual protection if the feeder overcurrent device
is no greater than the rating of the panelboard. Power panelboards must be protected by an overcurrent device
with a rating not greater than that of the panelboard [2].
Various methods for attaching the circuit breakers to the panelboard bus are available, such as plug-on, bolt on,
etc. The circuit breakers are typically purchased separately. Often, the enclosure, interior, and trim assemblies for
the panelboard itself are purchased separately as well. This is typically true of larger panelboards and gives a
great deal of flexibility with regard to use of the same interior with different enclosures and trims.
Panelboards are available with a number of accessories. Subfeed lugs allow taps directly from the panelboard
bus without the need for overcurrent devices. Circuit breaker locking devices allow locking of circuit breakers in
the open or closed position (note that the breakers will still trip on an overcurrent condition). Various types of trims
are available, with various locking means available for trims that are equipped with doors.
Switchboards
Table 9-2: Quick reference Switchboards
120-600 V
800-5000 A
Through 200 kA
1, 3R
Article 408
The definition of a switchboard is a large single panel, frame, or assembly of panels on which are mounted on
the face, back, or both, switches, overcurrent and other protective devices, buses, and usually instruments [2].
Switchboards are free-standing equipment, unlike panelboards, and are generally accessible from the rear as well
as from the front. They may consist of multiple sections, connected by a common through-bus. Unlike
panelboards, the number of overcurrent devices in a switchboard is not limited.
Switchboards generally house molded case circuit breakers or fused switches. They are generally the next level
upstream from panelboards in the electrical system, and in some small to medium-size electrical systems they
serve as the service equipment. Figure 9-2 shows an example of a switchboard.
Switchboards are available with a main circuit breaker or fusible switch, or as main-lugs only. The available
ampacities and multi-section availability makes them more flexible than panelboards. They are generally available
utilizing either copper or aluminum bussing, and with a variety of bus plating options. Custom bussing for retrofit
applications is also possible.
Switchboard circuit breakers may be stationary-mounted (also referred to as fixed-mounted), where they can be
removed only by unbolting of electrical connections and mounting supports, or drawout-mounted, where they can
be without the necessity of removing connections or mounting supports. It is possible to insert and remove
drawout devices with the main bus energized. The section which contains the main circuit breaker(s) or service
disconnect devices is referred to as a main section. A section containing branch or feeder circuit breakers is
referred to as a distribution section.
Devices mounted in the switchboard may be either panel mounted (also referred to as group mounted), where
they are mounted on a common base or mounting surface, or individually mounted, where they do not share a
common base or mounting surface. Individually mounted devices may or may not be in their own compartments.
A device which is segregated from other devices by metal or insulating barriers and which is not readily accessible
to personnel unless special means for access are used is referred to an isolated device. Figure 9-3 shows
examples of sections with group-mounted individually-mounted device.
The main through-bus is often referred to as the horizontal bus. The bussing in a section which connects to the
through-bus is referred to as the section bus (also known as vertical bus). The bussing that connects the section
bus to the overcurrent devices is referred to as the branch bus. Section and branch busses may be smaller than
the main through-bus; if this is the case UL 891 [2] gives the required section bus size as a function of the number
of overcurrent devices connected to it.
a.)
b.)
Figure 9-3:
a.) Group-mounted devices
b.) Individually-mounted devices
Switchboards are available with a number of accessories, including custom-engineered options such as utility
metering compartments, automatic transfer schemes, and modified-differential ground fault for switchboards with
multiple mains. However, the internal barriering requirements are minimal.
120-600 V
600-2500 A
Through 100 kA
1, 3R, 12
Article 430
A motor control center (MCC) is defined as a floor-mounted assembly of one or more enclosed vertical sections
typically having a common power bus and typically containing combination motor control units [5].
Motor control centers are used to group a number of combination motor controllers together at a given location
with a common power bus. Figure 9-4 shows an example of a motor control center.
120-600 V
1600-5000 A
Through 200 kA
1, 3R
Low voltage switchgear, more properly termed metal enclosed low voltage power circuit breaker switchgear,
is defined per [7] as LV switchgear of multiple or individual enclosures, including the following equipment
as required:
I
Low voltage power circuit breakers (fused or unfused) in accordance with IEEE Std. C37.13-1990 or
IEEE C37.14-1999
Low voltage power switchgear is the preferred equipment for medium to large industrial systems where the
advantages of low voltage power circuit breakers, discussed in Section 7, can be utilized to enhance coordination
and reliability. It is typically used as the highest level of low voltage equipment in a facility of this type and, if the
utility service is a low voltage service, the service entrance switchgear as well. Figure 9-5 shows an example of
low voltage switchgear.
Low voltage switchgear, although it performs the same functions and has comparable availability of voltage and
ampacity ratings as switchboards, represents a different mode of development from switchboards and is, in
general, more robust, both due to the construction of the switchgear itself and due to the characteristics of
low voltage power circuit breakers vs. molded-case circuit breakers. For this reason it is preferred over
switchboards where coordination, reliability, and maintenance are a primary concern.
Low voltage switchgear is compartmentalized to reduce the possibility of internal fault propagation. ANSI C37.20.1
[7] requires each breaker to be provided with its own metal-enclosed compartment. Optional barriers are usually
available to separate the main bus from the cable terminations, forming separate bus and cable compartments
within a section, as well as side barriers to separate adjacent cable and bus compartments.
All low voltage switchgear is required to pass an AC withstand test of 2.2 kV for one minute [7].
As with switchboards, low voltage switchgear is available with many options. The options are generally more
numerous than those for switchboards due to the nature of switchgear service conditions.
2400 - 38 kV
120 - 15 kV
1, 3R
Medium voltage power and distribution transformers are used for the transformation of voltages for the distribution
of electric power. They can be generally classified into two different types:
Dry-Type: The windings of this type of transformer are cooled via the circulation of ventilating air. The windings
may be one of several types, including Vacuum Pressure Impregnated (VPI), Vacuum Pressure Encapsulated
(VPE), and Cast-Resin. The Cast-Resin types generally are more durable and less likely to absorb moisture in the
windings than the VPI or VPE types. In some cases the primary windings are cast-resin and the secondary
windings are VPI or VPE.
Liquid-Filled: The windings of this type of transformer are cooled via a liquid medium, usually mineral oil,
silicone, or paraffinic petroleum-based fluids.
Liquid-filled units have a generally low in first-cost, but the requirements in NEC [2] Article 450 must be reviewed
to insure that installation requirements can be adequately met, and maintenance must be taken under
consideration since fluid levels should be monitored and the condition of the fluid examined on a regular basis.
They have an expected service life of around 20 years. VPE and VPI dry-type transformers also generally have
low first-costs, have longer lifetimes than liquid-filled units, and are much easier than liquid-filled types to install
indoors; however, consideration should be given to the absorption of moisture by the windings if these are used
outdoors. Installed indoors, these have expected service lifetimes of around 30 years. Cast-resin, dry-type
transformers have generally high first-costs compared to the other types, but have the same installation
requirements as dry-type transformers and have the longest expected service life (around 40 years).
Enclosure styles may also be divided into two basic types: pad-mounted, which is a totally-enclosed type
generally mounted outdoors and with specific tamper-resistance features to prevent inadvertent access by the
general public, and unit substation type, which is an industrial-type enclosure suitable for close-coupling into an
integrated unit substation lineup with primary and secondary equipment (note that unit substation-style
transformers may also be equipped with cable termination compartments as well).
Figure 9-6 shows typical examples of medium voltage power and distribution transformers.
Medium voltage power and distribution transformer capacities may be increased with the addition of fans. Cooling
types are listed as AA (ambient air) for dry-type transformers without fans, and AA/FA (ambient air/forced air) for
dry-type transformers with fans, for an increase of 33% in kVA capacity. The cooling type for a liquid-filled
transformer is listed as OA for units without fans, OA/FA for units with fans, with an increase of 15% kVA capacity
for units 225-2000 kVA, and 25% for units 2,500-10,000 kVA. FFA (future forced air) options are usually
available for both dry and liquid-filled types, although experience has shown that the fans are almost never added
in the field.
a.)
b.)
d.)
c.)
Table 9-6 gives typical BIL levels for medium voltage power and distribution transformers. These apply to both the
primary and secondary windings. Table 9-7 gives typical design temperature rises.
Table 9-6: Typical BIL levels for medium voltage power and distribution transformers
kV class
1.2
10
30
2.5
20
45
5.0
30
60
7.2
30
60
8.7
45
75
15.0
60
95
25.0
110
125
35.0
N/A*
150
VPI/VPE dry-type transformers are typically not available above 25.0 kV Class
Table 9-7: Typical design temperature rises for medium voltage power and distribution
transformers (over A 30C average/ 40C maximum ambient)
Transformer type
VPI/VPE dry-type
Cast-coil dry-type
80 or 115
Liquid-filled
55/65 or 65
Impedance levels vary; the manufacturer must be consulted for the design impedance of a specific transformer.
In general, units 1000-5000 kVA typically have 5.75% impedance 7.5% tolerance.
Medium voltage power and distribution transformers are typically available with several types of accessories,
including connections to primary and secondary equipment, temperature controllers and fan packages, integral
fuses for transformers with padmount-style enclosures, etc.
8
2400 V - 38 kV
600 - 2000 A
Through 65 kA
ANSI/IEEE C37.20.3
1, 3R
Metal-enclosed power switchgear is defined by [8] as a switchgear assembly enclosed on all sides and top with
sheet metal (except for ventilating openings and inspection windows) containing primary power circuit switching or
interrupting devices, or both, with buses and connections and possibly including control and auxiliary devices.
Access to the interior of the enclosure is provided by doors or removable covers. Metal-enclosed interrupter
switchgear is defined by [8] as metal-enclosed power switchgear including the following equipment as required:
I
Interrupter switches
Instrument Transformers
Metal-enclosed interrupter switchgear is typically used for the protection of unit substation transformers and as
service-entrance equipment in small- to medium- size facilities. Figure 9-7 shows an example of metal-enclosed
interrupter switchgear.
As with all fusible equipment, overcurrent protection flexibility is limited, however with current-limiting fuses this
equipment has high (up to 65 kA rms symmetrical) short-circuit interrupting capability. The load interrupter
switches in this class of switchgear are designed to interrupt load currents only, and may use air as the
interrupting medium or SF6. They may be arranged in many configurations of mains, but ties, and feeders as
required by the application.
This type of switchgear is frequently used as the primary equipment of a unit substation line-up incorporating
primary equipment, a transformer, and secondary equipment.
Table 9-9 shows the BIL levels of metal-enclosed interrupter switchgear, per [8]. The power frequency withstand
is a one-minute test value. Momentary (10 cycle) and short-time (2s) current ratings are also assigned for this
type of switchgear.
Table 9-9: Voltage withstand levels for metal-enclosed interrupter switchgear, per [8]
Rated Maximum Voltage (kV)
4.76
19
60
8.25
36
95
15.0
36
95
27.0
60
125
38.0
80
150
Internal barriering requirements for medium voltage areas within the switchgear are minimal. All low voltage
components are required to be separated by grounded metal barriers from all medium voltage components.
Interlocks are required to prevent access to medium voltage fuses while their respective switch is open and to
prevent closing their respective switch while they are accessible. In the rare case that this type of switchgear
contains drawout devices, shutters must be provided to prevent accidental contact with live parts when the
drawout element is withdrawn.
Available options for this type of switchgear include shunt trip devices for the switches, motor operators for the
switches, blown fuse indication, etc. Relaying of any type, including voltage relaying, must be carefully reviewed to
avoid exceeding the limits of the switches. The application of overcurrent relaying to this type of switchgear is not
recommended unless a short-circuit interrupting element is included, such as a vacuum interrupter.
2400 V 7.2 kV
Through 3000 A
Through 50 kA
1, 3R
Medium voltage motor controllers are used to control the starting and protection for medium voltage motors. They
generally utilize vacuum contactors rated up to 400 A continuous, in series with a non-load-break isolation switch
and R-rated fuses, fed from a common power bus. The motor starting methods in Section 8 are all generally
supported, including soft-start capabilities. Class E2 units per [9], which employ fuses for short-circuit protection,
are generally the most common. Figure 9-8 shows a typical example of a medium voltage MCC.
Medium voltage MCCs are generally available with a number of options depending upon the manufacturer,
including customized control and multi-function microprocessor-based motor protection relays. The contactors are
generally of roll-out design to allow quick replacement.
Above 7200, metal-clad switchgear is generally used for motor starting.
10
2400 V 38 kV
Through 3000 A
Through 50 kA
ANSI/IEEE C37.20.2
1, 3R
Metal-clad switchgear is defined by [10] as metal-enclosed power switchgear characterized by the following
necessary features:
I
The main switching and interrupting device is of the removable (drawout type) arranged with a mechanism
for moving it physically between connected and disconnected positions and equipped with self-aligning and
self-coupling primary disconnecting devices and disconnectable control wiring connections.
Major parts of the primary circuit, that is, the circuit switching or interrupting devices, buses, voltage
transformers, and control power transformers, are completely enclosed by grounded metal barriers that have no
intentional openings between compartments. Specifically included is a metal barrier in front of, or a part of, the
circuit interrupting device to ensure that, when in the connected position, no primary circuit components are
exposed by the opening of a door.
Automatic shutters that cover primary circuit elements when the removable element is in the disconnected, test,
or removed position.
Primary bus conductors and connections are covered with insulating material throughout.
Mechanical interlocks are provided for proper operating sequence under normal operating conditions.
Instruments, meters, relays, secondary control devices, and their wiring are isolated by grounded metal barriers
from all primary circuit elements with the exception of short lengths of wire such as at instrument transformer
terminals.
The door through which the circuit interrupting device is inserted into the housing may serve as an instrument or
relay panel and may also provide access to a secondary or control compartment within the housing
Medium voltage metal-clad switchgear is generally used as the high-level distribution switchgear for medium- to
large-sized facilities. It is also the preferred choice for service entrance equipment for these types of facilities.
Figure 9-9 shows an example of metal-clad switchgear.
11
Metal-clad switchgear uses high-voltage circuit breakers, as described in Section 7, fed from a common power
bus. It is configurable in many different arrangements of main, bus tie, and feeder devices to suit the application.
Relays are usually required since the circuit breakers generally do not have integral trip units. This type of
switchgear is the preferred means for accomplishing automatic transfer control and complex generator paralleling
applications; the control may be placed in the switchgear itself or in a separate panel, depending upon the
application and specific end-user preferences.
The construction requirements per [10] insure that metal-clad switchgear is the safest type of switchgear in terms
of operator safety.
The BIL and withstand voltage requirements for this switchgear are the same as for metal-enclosed switchgear as
given in table 9-9 above.
This type of switchgear has many options available to suit the application, such as electric racking for circuit
breakers, ground and test units that allow the grounding/testing of stationary contacts with a circuit breaker
withdrawn, etc.
References
12
[1]
Enclosures for Electrical Equipment (1000 Volts Maximum), NEMA Standards Publication 250-2003.
[2]
The National Electrical Code, NFPA 70, The National Fire Protection Association, Inc., 2005 Edition.
[3]
UL Standard for Safety for Panelboards, UL 67, Underwriters Laboratory, Inc., November 2003.
[4]
UL Standard for Safety for Switchboards, UL 891, Underwriters Laboratories, Inc., February 2003.
[5]
UL Standard for Safety for Motor Control Centers, UL 845, Underwriters Laboratories, Inc., August 2005.
[6]
[7]
IEEE Standard for Metal-Enclosed Low Voltage Power Circuit Breaker Switchgear, IEEE Std. C37.20.1-2001,
October 2002.
[8]
IEEE Standard for Metal-Enclosed Interrupter Switchgear, IEEE Std. C37.20.3-2001, August 2001.
[9]
Industrial Control and Systems: Medium Voltage Controllers Rated 2001 to 7200 Volts AC, NEMA Standards
Publication ICS 3-1993.
[10]
IEEE Standard for Metal-Clad Switchgear, IEEE Std. C37.20.2-1999, July 2000.
Section 10:
Introduction
Emergency and standby power systems are designed to provide an alternate source of power if the normal source
of power, most often the serving utility, should fail. As such, reliability of these types of systems is critical and good
design practices are essential.
10
10 sec
60
60 sec
120
120 sec
The Class of an emergency power system refers to the minimum time, in hours, for which the system is designed
to operate at its rated load without being refueled or recharged. The Classes for emergency power systems are
shown in table 10-2 [3]:
Table 10-2: NFPA 110 emergency power system classes (essentially the same as [3]
table 4.1(B))
Class
0.083
0.25
2 hr.
6 hr.
48
48 hr.
The Level of an emergency power system refers to the level of equipment installation, performance, and
maintenance requirements. The Levels for emergency power systems are shown in table 10-3 [3]:
Table 10-3: NFPA emergency power system levels
Level
When Installed
When failure of the equipment to perform could result in loss of human life or serious injuries
When failure of the equipment to perform is less critical to human life and safety and where
the authority having jurisdiction shall permit a higher degree of flexibility than that provided by
a level 1 system
F.) NFPA 99
NFPA 99 defines establishes criteria to minimize the hazards of fire, explosion, and electricity in health care
facilities. It defines several specific features of electric power systems for these facilities.
Legal Requirements As required by the NEC [2] NFPA 101 [4], NFPA 99 [5], and other local, state, and federal
codes and requirements. These are concerned with the safety of human life, protection of the environment, etc.
Economic Considerations Continuous process applications often require a continuous source of electrical
power to avoid significant economic loss. In some cases even a momentary loss of power can be disastrous.
Co-generation systems which are used to sell power back to the utility as part of an energy management strategy
are not discussed in this section.
Power sources
Generators are by far the most prevalent source of power for emergency and standby power systems. For most
commercial and industrial power systems these will be engine-generator sets, with the prime-mover and the
generator built into a single unit. For reciprocating engines, diesel engines are the most popular choice of primemover for generators, due to the cost of the diesel engines as compared to other forms of power and the relative
ease of application. Gasoline engine generator sets are also available and are generally less expensive than
diesel generator sets, but suffer from the disadvantages of higher operating costs, greater fuel storage hazards,
and shorter fuel storage life as compared to diesel. Diesel engines can also run on natural gas, although for
maximum efficiency specially-tuned engines for natural gas use are available.
The other alternative for generators is the turbine generator, typically powered by natural gas. Gas-turbine
generator sets are generally lighter in weight than diesel engine-generator sets, run more quietly, and generally
require less cooling and combustion air, leading to lower installation costs. However, gas-turbine generator sets
are more expensive than diesel engine-generator sets, and require more starting time (normally around 30 s
compared to the 10-15 seconds for diesels). The long starting-time requirement and lack of available small sizes
(< 500 kW) makes the gas-turbine generators infeasible in many applications.
Generator installations must consider the combustion and cooling air required by the generator and prime mover,
as well as the provisions for the removal of exhaust gasses. Noise abatement must also be considered.
These considerations increase the installation costs, especially for reciprocating-engine units such as diesel or
gasoline engines. Further, the fuel supply must be considered; building code and insurance considerations may
force the fuel storage tank to be well removed from the generator(s), usually forcing the addition of a fuel transfer
tank near the generator(s).
Care must be taken when sizing engine-generator sets for a given application since several ratings exist for the
output capability of a given machine. The continuous rating is typically the output rating of the engine-generator
set on a continuous basis with a non-varying load. The prime power rating is typically the continuous output
rating with varying load. The standby rating is typically the output rating for a limited period of time with varying
load. The manufacturer must be consulted to define the capabilities of a given unit.
A second alternative for emergency or standby system power is a second utility source. However, the
procurement of a second utility source which is sufficiently independent from the normal service may be
economically infeasible.
Solid-state converters that invert DC voltage from a battery system are another alternative, although they can be
difficult to apply and generally are not available in the larger sizes that may be needed for a medium to large
emergency or standby system.
Because motor starting and block loading can have a big effect on the output voltage and frequency of a small
generator such as the engine-generator sets described above, and also because power is not available during the
engine starting period, a buffer between the generators and sensitive load equipment is generally required. The
Uninterruptible Power Supply (UPS) is usually the buffer of choice for these applications. UPSs are available in
several different topologies, but the operational goals are the same regardless of topology: The supply of
uninterrupted power to sensitive, critical loads. The most popular topology for a UPS is the double conversion
topology, as shown in figure 10-1:
So long as the batteries are properly maintained, the AC output should not be affected by change in frequency
or voltage, or even a complete loss, at the input, so long as backup time of the UPS is not exceeded. Other
topologies exist, including the line interactive, double-conversion rotary, hybrid rotary, and line-interactive
rotary topologies, each with advantages and disadvantages of application. UPS systems do not alleviate the need
for a generator or second utility service power source, but they do serve to buffer critical loads from the effects of
generator starting time and voltage and frequency variations.
Switching devices
A means must be provided to switch the critical loads from the normal utility source to the standby power source.
Several types of device are available for this.
An automatic transfer switch is defined as self-acting equipment for transferring one or more load conductor
connections from one power source to another [1]. The automatic transfer switch is the most common means of
transferring critical loads to the emergency/standby power supply. An automatic transfer switch consists of a
switching means and a control system capable of sensing the normal supply voltage and switching over to the
alternate source should the normal source fail. Automatic transfer switches are available in ratings from 30-50 A,
and up to 600V [1]. Because automatic transfer switches are designed to continuously carry the loads they serve,
even under normal conditions, care must be used in sizing these so that the potential for failure is minimized.
Automatic test switches with adjustable pickup and dropout setpoints and integral testing capability are generally
preferred. An automatic transfer switch is generally an open-transition device that will not allow paralleling of the
two sources. Manual versions of transfer switches are also available. A one-line representation of an automatic
transfer switch is shown in figure 10-2.
Other options for transferring devices include electrically-operated circuit breakers, as described in System
protection section (section7 in this guide). For medium voltage transfers, medium voltage circuit breakers are
generally used. Manual versions of circuit-breaker transferring schemes are, of course, also available.
Bypass/isolation switches, as their name suggests, are used to bypass an automatic transfer switch (or other
switching means) and connect the source directly to the load and allow isolation of the transfer switch for
maintenance. Figure 10-3 shows a typical bypass/isolation switch arrangement along with the transfer switch:
In figure 10-3 the bypass blade B serves to bypass the automatic transfer switch, and isolating contacts I
serve to isolate the automatic transfer switch. Bypass/isolation switches are typically manually-operated devices.
Bypass/isolation switches are available with a test position in which only the ATS-to-load isolation contact
(marked with an asterisk [*] in figure 10-3) is open, allowing the transfer switch to be operated without
disconnecting the load.
Static Transfer Switches are typically used when high-speed (~4ms) operation is required. The most common
application is to bypass a UPS so that a UPS failure will not result in interruption of service to the load.
System arrangements
Various ways of arranging emergency and standby power systems exist. The most common arrangements
are given here.
In figure 10-5, the emergency/standby load at the bottom of the figure will always be supplied by one of the
normal sources if possible, and by the generator(s) if not. This will avoid the generator starting time for this load if
one utility source were to fail. The two emergency/standby loads in the middle of the figure will be supplied by
their respective switchboard busses or by the emergency source.
Emergency/standby systems are not limited to the low voltage level. For example, the primary selective/primary
loop/secondary selective system shown in figure 5-14 can be expanded to include an emergency system, as
shown in figure 10-6:
In figure 10-6 there is a great deal of flexibility in the system operation. However, instead of automatic transfer
switches metal-clad switchgear is used increasing the complexity of the system.
Figure 10-7: Minimum requirement per NEC [2] and NFPA 99 [5] for essential electrical system for
hospitals 150 kVA or Less (same as [2] FPN figure 517.30 No.2)
Figure 10-7: Minimum Requirement per NEC [2] and NFPA 99 [5] for Essential Electrical system for
Hospitals over 150 kVA (same as [2] FNP figure 517.30 No. 1)
The essential electrical system supplies the equipment system, defined as a system of circuits and equipment
arranged for delayed, automatic, or manual connection to the alternate power source and that serves primarily 3phase power equipment [2]. The emergency system supplies, which itself part of the essential electrical system,
supplies the life safety branch, which is a subsystem of the emergency system consisting of feeders and branch
circuitsintended to provide adequate power needs to insure safety to patients and personnel [2]. The
emergency system also supplies the critical branch, which is a subsystem of the emergency system consisting of
feeders and branch circuits supplying energy to task illumination, special power circuits, and selected receptacles
serving areas and functions related to patient care [2]. For hospitals of 150 kVA and less the equipment system,
life safety branch, and critical branch may be on the same transfer switch. Note that the transfer switch(es) for the
equipment system above 150 kVA is required to be delayed.
NEC requirements
The following are highlights from the NEC [2] requirements for emergency and standby power systems. This is not
intended to list all NEC requirements for these systems, but to illustrate the major points that apply in the most
common installations and affect the power system design. For the full text of the complete NEC requirements for
these systems, consult the NEC.
Witness Test: The authority having jurisdiction must conduct or witness a test of the complete system and
periodically afterward. [700.4 (A)]
Emergency systems must be tested periodically on a schedule acceptable to the authority having jurisdiction to
ensure the systems are maintained in proper operating condition. A written record must be kept of these tests.
[700.4 (B), (C), and (D)]
Battery systems that are part of the emergency system must be periodically maintained. [700.4 (B)]
A means for testing all emergency lighting and power systems during maximum anticipated load conditions must
be provided. [700.4 (E)]
The alternate power source is required to be sized to supply all emergency loads simultaneously. [700.5 (A)]
The alternate power source is permitted to supply emergency, legally required standby, and optional standby
system loads where the source has adequate capacity or where automatic selective load pickup or load
shedding is provided to insure adequate power to the emergency, legally required standby, and optional standby
system loads. If these requirements are met the system may also be used for peak load shaving. Peak load
shaving operation may satisfy the requirement for periodic testing if acceptable to the authority having
jurisdiction. A portable or temporary alternate source must be available if the emergency generator is out of
service for repair. [700.5 (B)]
Transfer equipment must be automatic, identified for emergency use, and approved by the authority
having jurisdiction. Automatic transfer switches must be electrically operated and mechanically held.
[700.6 (A) and (C)]
Audible and visual signal devices must be provided for indication of derangement of the emergency source, that
the battery is carrying load, that the battery is not functioning, and to indicate a ground fault in solidly-grounded
wye systems of more than 150 V to ground and over 1000 A. The sensor for ground-fault indication must be
located at or ahead of the main system disconnecting means for the emergency source. [700.7]
A sign must be placed at the service entrance equipment, indicating the type and location of on-site emergency
power sources. A sign is also required where the grounded circuit conductor connected to the emergency
source is connected to a grounding electrode conductor at a location remote from the emergency source.
[700.8]
All boxes and enclosures for emergency circuits must be permanently marked so that they will be readily
identified as a component of an emergency circuit or system. [700.9 (A)]
Wiring from an emergency source or emergency source distribution overcurrent protection to emergency loads
must be kept entirely independent of all other wiring and equipment. Exceptions apply where load equipment
must have wiring from two sources. [700.9 (B)]
For occupancies of not less than 1000 persons or in buildings above 75 ft. in height with assembly, educational,
residential, detention/correctional, business, or mercantile occupancy class the feeder circuit wiring must be 1.)
installed in spaces or areas that are fully protected by an approved automatic fire suppression system, or 2.) be
a listed electrical circuit protective system with a 1-hour fire rating, or 3.) be protected by a listed thermal barrier
system for electrical system components, or 4.) be protected by a fire-rated assembly listed to achieve a
minimum fire rating of 1 hour, or 5.) be embedded in not less than 50mm of concrete. Feeder circuit equipment
must be either in spaces fully protected by a approved automatic fire suppression systems or in spaces with
a 1-hour fire resistance rating. [700.9 (D)]
In the event of failure of the normal supply to, or within, the building or group of buildings concerned, emergency
lighting, power, or both, must be available within the time required by the application but not to exceed 10
seconds.
The alternate source of power must be a storage battery, generator set, UPS, separate service, or fuel cell
system, each with restrictions on its use. [700.12 (A), (B), (C), (D), and (E)].
Storage batteries must have sufficient capacity to supply and maintain the total load for a minimum period of one
hours, without the voltage applied to the load falling below 87% of nominal. The battery charging means must be
automatic. [700.12 (A)]
Generator sets must have a prime-mover acceptable to the authority having jurisdiction, and means of
automatically starting the prime mover on failure of the normal service. If the prime-mover is an internal
combustion engine, an on-premises fuel supply must be provided to allow not less than 2 hours full-demand
operation of the system. If power is required for operation of fuel transfer pump to deliver fuel to a generator set
day tank, this pump must be connected to the emergency power system. Generator sets must not be solely
dependent on a public utility gas system for their fuel supply for a municipal water supply for their cooling
systems. If dual supplies for these are used, means must be provided to automatically transfer from one supply
to the other. If a storage battery is used for control or signal power or as the means of starting the prime mover, it
must be equipped with an automatic charging means independent of the generator set. Where power is required
for the operation of the dampers used to ventilate the generator set, the dampers must be connected to the
emergency system. [700.12 (B) (1), (2), (3), and (4)]
10
If a generator set requires more than 10 seconds to develop power, an auxiliary power supply that energizes the
emergency system until the generator can pick up the load is permitted. [700.12 (B) (5)]
Outdoor generator sets do not require an additional disconnecting means where the ungrounded conductors
serve or pass through the building or structure, so long as they are equipped with a readily-accessible
disconnecting means located within sight of the building or structure supplied. [700.12 (B)(6)]
UPSs used to provide power for emergency systems must comply with the applicable provisions for battery
systems and generators.
An additional utility service is permitted to be the power source for the emergency system, if acceptable to the
authority having jurisdiction. A separate service drop or service lateral and service conductors sufficiently remote
electrically and physically from other service conductors to minimize the possibility of simultaneous interruption
of supply must be supplied. [700.12 (D)]
Fuel cell systems must be capable of supplying and maintaining the total load for not less then two hours of fulldemand operation. Fuel cell systems must meet the requirements of Parts II through VIII of Article 692 (Fuel Cell
Systems). A single fuel cell that serves as the normal source for the building or group of buildings concerned
cannot serve as the alternate source. [700.12(E)]
Individual unit equipment for emergency illumination must have a rechargeable battery, a battery charging
means, provisions for one or more lamps mounted on the equipment or terminals for remote lamps, and a
relaying device arranged to energize the lamps automatically upon failure of the supply to the unit equipment.
The battery must be capable of supplying the lamps for no less than one hours at not less than 60% of the initial
illumination level. [700.12 (F)]
Individual unit equipment for emergency illumination must be fixed in place. Flexible cord-and-plug installation is
permitted if the cord is no more than 3ft. in length. The branch circuit feeding the unit equipment must be the
same as that serving normal lighting in the area and connected ahead of any local switches, and must be clearly
identified at the distribution panel. Alternatively, for areas with at least three normal lighting branch circuits the
emergency illumination unit equipment may be supplied by a separate branch circuit with a lock-on feature.
[700.12 (F)]
No appliances or lamps, other than those specified for emergency use, are allowed on emergency
lighting circuits. [700.15]
Emergency illumination must include all required means of egress lighting, illuminated exit signs, and all other
lights specified as necessary to provide required illumination. Failure of any individual lighting element must not
leave in total darkness any space that requires emergency illumination. If HID lighting is used as emergency
illumination, it must operate until normal illumination has been restored. [700.16]
Emergency lighting must have either an emergency lighting supply, with provisions for automatically transferring
the emergency lights upon the event of failure of the general lighting system supply, or two or more separate
and complete systems with independent power supplies, each providing sufficient current for emergency lighting
purposes. If two systems are used, means must be provided for automatically energizing either system upon
failure of the other unless they are both kept lighted. [700.17]
All branch circuits that supply equipment classed as emergency equipment must have an emergency supply
source to which the load will be transferred upon the failure of the normal supply. [700.18]
Emergency lighting circuits must be arranged so that only authorized persons have control of emergency
lighting. Exceptions apply. [700.20]
Switches in series or 3- and 4-way switches cannot be used in emergency lighting circuits. [700.20]
Control switches for emergency lighting must be in convenient locations for authorized persons. In assembly
occupancies or theaters, audience areas of motion picture studios, and performance areas, a switch
for controlling emergency lighting systems must be in the lobby or at a place conveniently accessible
thereto. [700.21]
Emergency lighting on the exterior of a building that is not required for illumination when there is sufficient
daylight may be controlled by an automatic light-actuated device. [700.22]
The branch-circuit overcurrent devices in emergency circuit must be accessible to authorized persons
only. [700.25]
The alternate source for emergency systems is not required to have ground-fault protection of equipment.
Ground-fault indication is required. [700.26]
Emergency system(s) overcurrent devices must be selectively coordinated with all supply-side overcurrent
protective devices. [700.27]
System periodic testing and maintenance requirements are essentially the same as for emergency systems,
except that the authority having jurisdiction is only required to witness the test upon installation. [701.5]
The legally required standby system alternate power source is permitted to supply both legally required standby
system and optional standby system loads, provided that it either has enough capacity to handle all connected
loads or that automatic selective load pickup and load shedding is provided that will ensure adequate power to
the legally required standby circuits. [701.6]
Requirements for transfer equipment are essentially the same as for emergency systems, except that no
restriction is placed upon the use of transfer equipment use for other systems in addition to the legally required
standby system. [701.7]
Audible and visual signal devices must be provided for indication of derangement of the standby source, that the
standby source is carrying load, and that the battery charger is not functioning. [701.8]
Signage requirements are essentially the same as for emergency systems. [701.9]
Wiring for legally required standby systems is permitted to occupy the same raceways, cables, boxes, and
cabinets with other general wiring. [701.10]
In the event of failure of the normal supply to, or within, the building or group of buildings concerned,
legally required standby power must be available within the time required by the application but not to exceed
60 seconds.
The alternate source of power must be a storage battery, generator set, UPS, separate service, connection
ahead of the service disconnecting means, or fuel cell system, each with restrictions on its use.
[701.11 (A), (B), (C), (D), (E), and (F)]
The requirements for storage batteries, generator sets, UPSs, separate utility service, and fuels cells as the
standby power source are essentially the same as for emergency systems, except the requirements for fuel
transfer pumps and ventilation dampers to be connected to the system for generator sets. [701.11 (A)]
Where acceptable to the authority having jurisdiction, connections ahead of but not within the same cabinet,
enclosure, or vertical switchboard section as the service disconnecting means may serve as the standby power
source. This connection ahead of the normal service must be sufficiently separated from the normal main
service disconnecting means to prevent simultaneous interruption of supply. [701.11 (D)]
The requirements for individual unit equipment for legally required standby illumination are essentially the same
as for emergency illumination individual unit equipment. [701.11 (G)]
Legally-required standby system overcurrent protection requirements are essentially the same as for emergency
systems, except that ground-fault indication is not required. [701.15, 701.17, 701.18]
Transfer equipment is required, except in the case of temporary connection of a portable generator where
conditions of maintenance and supervision ensure that only qualified persons service the installation and
where normal supply is physically isolated by a lockable disconnect means or by disconnection of supply
conductors. [702.6]
Audible and visual signal devices must be provided for indication of derangement of the standby source and to
indicate that the optional standby source is carrying load. [702.7]
11
Signage requirements are essentially the same as for emergency and legally required standby systems. [702.8]
Wiring for optional standby systems is permitted to occupy the same raceways, cables, boxes, and cabinets with
other general wiring. [702.9]
Where a portable optional standby source is used as a separately derived system, it must be grounded to a
grounding electrode in accordance with Article 250.30. Where a portable optional standby source is used as a
non-seperately derived system, the equipment grounding conductor must be bonded to the system grounding
electrode. [702.10]
Outdoor generator sets do not require an additional disconnecting means where the ungrounded conductors
serve or pass through the building or structure, so long as they are equipped with a readily-accessible
disconnecting means located within sight of the building or structure supplied. [702.11]
D.) Health care facility essential electrical systems (Article 517 part III)
I
The essential electrical system is required to serve a limited amount of lighting and power service, which is
considered essential for life safety and orderly cessation of procedures during the time normal service is
interrupted for any reason. This includes clinics, medical and dental offices, outpatient facilities, nursing homes,
limited care facilities, hospitals, ad other health care facilities serving patients. [517.25]
The essential electrical system must meet the requirements of Article 700 (Emergency Systems), except as
amended by Article 517. [517.26]
N Hospitals (Articles 517.30 517.35)
12
The essential electrical systems for hospitals must comprised of two separate systems: The emergency
system and the equipment system. The emergency system must be limited to circuits essential to life
safety and to critical patient care, designated as the life safety branch and the critical branch. The
equipment system must supply major electrical equipment necessary for patient care and basic hospital
operation. [517.30 (B) (1), (2), and (3)]
The number of transfer switches used must be based on reliability, design, and load considerations.
One transfer switch is permitted to serve one or more branches or systems in a facility with a maximum
demand on the essential electrical system of 150 kVA. [517.30 (B) (4)]
Other loads not specifically mentioned in Article 517 must be served with their own transfer switches.
These loads must not be transferred to the essential electrical system generating equipment if the
transfer will overload the equipment, and they must be automatically shed upon generating equipment
overloading. [517.30 (B)(5)]
The life safety and critical branch circuit wiring must be kept independent of all of other wiring and
equipment and must not enter the same raceways, boxes, or cabinets with each other or other wiring.
Exceptions apply where transfer or load equipment must have wiring from two sources. Wiring for the
equipment system is permitted to occupy the same raceways boxes, or cabinets of other circuits that are
not part of the emergency system. [517.30 (C)]
All wiring of the emergency system must be mechanically protected. Nonflexible metal raceways, type MI
cable, or Schedule 80 rigid nonmetallic conduit are permitted, except that nonmetallic raceways cannot
be used for branch circuits that supply patient care areas. Schedule 40 rigid nonmetallic conduit, flexible
nonmetallic or jacketed metallic raceways, or jacketed metallic cable assemblies listed for installation in
concrete may be used if encased in no less than 2 in. of concrete. Listed flexible metal raceways and
listed metal sheathed cable assemblies may be used under certain conditions. Flexible power cords of
appliances or other utilization equipment and secondary circuits of Class 2 or Class 3 communications or
signaling systems are exempted from being run in metal raceways. [517.30 (C) (3)]
Generator sizing may be based upon demand calculations rather than on the entire load operating
simultaneously as required in 700.5. [517.30 (D)]
All receptacles supplied by the emergency system must have a distinctive color or marking. [517.30 (E)]
The life safety branch is permitted to supply only illumination of egress means, exit signs, alarm and
alerting systems, communications systems used during emergency conditions, task illumination at
the generator set location, elevator cab lighting, control, communications, and signal systems, and
automatic doors. [517.32]
The critical branch is permitted to supply task illumination and selected receptacles in critical care areas,
isolated power systems in special environments, task illumination and selected receptacles for selected
patient care areas, general care beds, selected labs, additional patient care task illumination and
receptacles as needed, nurse call systems, blood, bone, and tissue banks, telephone equipment rooms
and closets, etc. (complete list given in the NEC text). [517.33]
The critical branch may be subdivided into two or more branches. [517.33 (B)]
Delayed automatic connection to the equipment system must be provided for central suction systems,
sump pumps, compressed air systems, smoke control and stair pressurizing systems, kitchen hood
supply or exhaust systems, and supply, return, and exhaust ventilating systems for selected locations
(complete list given in NEC text). [517.34 (A)]
Delayed automatic or manual connection to the equipment system must be provided for selected heating
equipment, selected elevators, hyperbaric and hypobaric facilities, automatically operated doors, selected
electrically-heated autoclaving equipment, and other selected equipment. [complete list given in NEC text
and NFPA 99:4.2.2.2.3.5(9)] [517.34 (B)]
Generator accessories, such as the transfer fuel pump, electrically operated louvers, and other
accessories essential for generator operation, must be arranged for non-delayed automatic connection to
the alternate power source via the equipment system.
A minimum of two sources of power are required, one normal, one alternate. The alternate source may be
generator(s) on the premises, an external utility service if the normal service is a generator(s) on the
premises, or a battery system.
Applicability depends upon the type of care given at the facility. Specific exceptions are listed for certain
types of facilities (see NEC text for details). If a nursing home provides inpatient hospital care, it must
conform to the requirements for hospitals. Nursing homes and limited care facilities that are contiguous or
located on the same site with a hospital are permitted to have their essential electrical systems supplied
by the hospital. [517.40]
The essential electrical system must be comprised of two separate branches: The life safety branch and
the critical branch. [517.41 (A)]
Requirements for transfer switches are essentially the same as for hospitals. [517.41 (C)]
The life safety branch must be kept entirely independent of all other wiring and equipment and must not
enter the same raceways, boxes, or cabinets with other wiring. Exceptions apply where transfer or load
equipment must have wiring from two sources. [517.41 (D)]
Requirements for receptacle identification are essentially the same as for hospitals. [517.41 (E)]
The life safety branch must be automatically restored via the alternate power source within 10 seconds
after interruption of the normal source. [517.42]
The life safety branch must supply only illumination of means of egress, exit signs, alarm and alerting
systems, communications systems used during emergency conditions, dining and recreation areas,
task illumination at the generator set location, and elevator cab lighting, control, communications,
and signal systems.
Delayed automatic connection to the critical branch must be provided for task illumination and selected
receptacles in selected patient care areas, sump pumps and other equipment required to operate for the
safety of major apparatus and associated control systems and alarms, smoke control and stair
pressurization systems, kitchen hood supply and/or exhaust systems if required to operate during a fire in
or under the hood, and supply, return, and exhaust ventilating systems for airborne infections isolation
rooms (complete list given in NEC text). [517.43(A)]
13
Delayed automatic connection to the critical branch must be provided for heating equipment to provide
heating for patient rooms (exceptions apply), elevator service and additional illumination, receptacles,
and equipment. [517.43 (B)]
The alternate source of power must be a generator(s) located on the premises unless the normal source
is a generator(s) on the premises, in which case the alternate source may be either another generator set
or external utility service. In certain cases a battery system may be used (see NEC text). [517.44 (B)]
The essential electrical system must be a battery or generator system, if required per NFPA 99.
Where electrical life support equipment is required or critical care areas are present, the requirements
for hospitals apply.
The requirements of Article 700 apply to battery systems. Generator systems must be as described
for hospitals.
References
14
[1]
IEEE Recommended Practice for Emergency and Standby Power Systems for Industrial and Commercial
Applications, IEEE Std. 446-1995, December 1995.
[2]
The National Electrical Code, NFPA 70, The National Fire Protection Association, Inc., 2005 Edition.
[3]
Standard for Emergency and Standby Power Systems, NFPA 110, The National Fire Protection Association,
2005 Edition.
[4]
Life Safety Code, NFPA 101, The National Fire Protection Association, 2003 Edition.
[5]
Standard for Health Care Facilities, NFPA 99, The National Fire Protection Association, 2005 Edition.
Section 11:
Introduction
The term power quality may take on any one of several definitions. The strict definition of power quality is the
concept of powering and grounding electronic equipment in a manner that is suitable to the operation of that
equipment and compatible with the premises wiring system and other connected equipment [1]. In practice,
however, the term power quality is often used to denote the proximity of the system voltage to its sinusoidal form
at the nominal voltage level. Deviation from this sinusoidal norm therefore denotes a power quality issue. Strictly
speaking, this deviation is actually a power disturbance, defined as any deviation from the nominal value (or
from some selected thresholds based upon tolerance) of the AC input power characteristics [1]. The most
common power disturbances are, as defined by [1]:
Overvoltage: An RMS increase in the AC voltage, at the power frequency, for a period of time greater than 1 min.
Typical values are 110%-120% of nominal.
Undervoltage: An RMS decrease in the AC voltage, at the power frequency, for a period of time greater than
1 min. Typical values are 80-90% of nominal.
Swell: An increase in RMS voltage or current at the power frequency for durations from .5 cycle-1 min. Typical
values are 110%-180% of nominal.
Sag: An RMS reduction in the AC voltage, at the power frequency, for durations from _ cycle to a few seconds.
Interruption: The complete loss of voltage. A momentary interruption is a voltage loss (<10% of nominal) for a
time period between .5 cycles and 3 seconds). A temporary interruption is a voltage loss (<10% of nominal) for a
time period between 3 seconds and 1 min. A sustained interruption is the complete loss of voltage for a time
period greater than 1 min.
Notch: A switching (or other) disturbance of the normal power system voltage waveform, lasting less than _ cycle;
which is initially of opposite polarity to the waveform, and is thus subtractive from the normal waveform in terms of
the peak value of the disturbance voltage. This includes a complete loss of voltage for up to _ cycle.
Transient: A subcycle disturbance in the AC waveform that is evidenced by a sharp discontinuity of the
waveform. May be of either polarity and may be additive to, or subtractive from, the nominal waveform.
Flicker: A variation in input voltage, either magnitude or frequency, sufficient in duration to allow visual
observation of a change in electric light source intensity.
Harmonic Distortion: The mathematical representation of distortion of the pure sine waveform. This refers to
the distortion of the voltage and/or current waveform, due to the flow of non-sinusoidal currents.
Electrical Noise: Unwanted electrical signals that produce undesirable effects in the circuits of the control
systems in which they occur. Noise may be further categorized as transverse-mode noise, which is measurable
between phase conductors but not phase-to-ground, and common-mode noise, which is measurable phase-toground but not between phase conductors. This noise may be conducted or radiated. Also referred to as RFI
(radio-frequency interference) or EMI (electro-magnetic interference).
The causes of the common power disturbances listed can vary greatly. Common causes are listed in Table 11-1:
Common causes
Overvoltage
Undervoltage
Voltage Swell
Voltage Sag
Remote fault
Cold-load pickup (motor starting, transformer energization, etc.)
Large step loads
Transient
(Typically voltage surges)
Lightning strikes
Close-in switching (capacitors, etc.)
Complex circuit phenomena such as current chopping, restrikes, system resonance, etc.
Flicker
Notches and
Harmonic Distortion
Power electronic converter equipment such as rectifiers, inverters, drives, etc., which produce nonsinusoidal load current and commutation notches
Interruptions
Electrical Noise
Power disturbances can greatly affect utilization equipment. For example, sensitive electronic medical
equipment can malfunction, adjustable speed motor drives may trip off-line, etc. Interruptions can cause
microprocessor-based equipment such as computers to lose data. In extreme conditions, such as for voltage
surges caused by direct lightning strikes, both power equipment and utilization equipment may be subject to
failure. With the high reliability requirements imposed upon power systems, it is imperative that power system
disturbances, or potential disturbances, be mitigated to avoid down-time, equipment failure, and risk to human life.
(11-1)
where
Vh
V1
is the RMS harmonic voltage (or current) value at a frequency of n times the fundamental frequency
is the RMS fundamental-frequency voltage or current
Alternate forms for the distortion factor are given in [2] as percentages of the nominal voltage or demand load
current for the system under consideration, for use in evaluation of the harmonic content of the system voltage or
current. These are referred to as Total Harmonic Distortion (THDVn) and Total Demand Distortion (TDD), defined
as follows:
(11-2)
(11-3)
where
Vh
Vn
Ih
IL
Crest Factor: The ratio of the peak value of a periodic function to the RMS value, i.e.:
(11-4)
where
ypeak
yrms
Because power system voltages and currents are nominally sinusoidal, the nominal crest factor for these would
be 2, which is 1.414 (see Electric Power Fundamentals section (section 2) for details).
Notch Area: A notch in the power system voltage (or current) is illustrated in figure 11-1 [2]:
The notch area for the notch as illustrated in figure 11-1 is defined as:
(11-5)
where
An
t
d
Recovery time: This is the time needed for the output voltage or current to return to a value within the regulation
specification after a step load or line change.
Displacement Power Factor: The ratio of the active power of the fundamental wave, in watts, to the apparent
power of the fundamental wave, in volt-amperes. This is the traditional definition of power factor.
Total Power Factor: The ratio of the total input power, in watts, to the total volt-ampere input. This includes the
effects of harmonics.
K Factor: A measure of a transformers ability to serve non-sinusoidal loads. The K factor is defined as:
(11-6)
where
Ih
h
hmax
Voltage surges
The causes of voltage surges may be split into two major categories: Power system switching and environmental
[1]. Both exhibit decaying oscillatory transients. Capacitor switching close to the point under consideration is the
most common cause of switching surges, while lightning is the most common cause of environmentally-induced
voltage surges. Both can cause severe damage to unprotected power system components, with the potential for
lightning damage being the most severe; in the worst case, lightning damage can be catastrophic.
Surge arrestors, as described in Section 7, are typically used to protect against voltage surges. On low voltage
systems transient voltage surge suppressors (TVSS), also described in Section 7 are also used. For motors,
surge capacitors are an option. In severe cases, custom-designed R-C snubber circuits may be required as well.
Harmonic distortion
Harmonic distortion is a subject of great interest in modern power systems. Harmonic distortion results from
non-sinusoidal load currents. These currents are the result of non-linear loads, such as drives, which employ
power electronic devices to rectify the AC waveform. These devices draw non-sinusoidal currents which, in turn,
cause non-linear voltages to be developed in the system.
IEEE Standard 519-1992 [2] gives recommended limits for current distortion due to consumer loads and voltage
distortion in the utility supply voltage. Both are referenced at the point on the utility system where multiple
customers can be served, referred to as the Point of Common Coupling (PCC). The requirements from [2] for
current distortion limits on general distribution systems 120 V - 69 kV are given in table 11-2. Table 11-3 shows
the corresponding utility voltage distortion limits.
Note that the current limits are given both as limits on the individual harmonic levels and a limit on the TDD, and
that as the ratio Isc/IL increases the limits also increase. The reason for this is that the current distortion limits are
designed to limit the voltage distortion at the PCC, and the voltage distortion for a given current distortion worsens
with a larger source impedance (V - I Z).
Table 11-2: IEEE 519-1992 Harmonic current distortion limits for general distribution
systems 120 V through 69 kV (essentially same as [2] table 10-3)
Maximum harmonic current distortion in percent of IL
Individual harmonic order (Odd harmonics)
Isc/IL
<11
11<h<17
17h<23
23h<35
35h
TDD
<20*
4.0
2.0
1.5
0.6
0.3
5.0
20<50
7.0
3.5
2.5
1.0
0.5
8.0
50<100
10.0
4.5
4.0
1.5
0.7
12.0
100<1000
12.0
5.5
5.0
2.0
1.0
15.0
>1000
15.0
7.0
6.0
2.5
1.4
20.0
Even harmonics are limited to 25% of the odd harmonic limits above.
Current distortions that result in a DC offset, e.g. half-wave converters, are not allowed.
*All power generation equipment is limited to these values of current distortion, regardless of actual ISC/IL
where
ISC
IL
Table 11-3: IEEE 519-1992 Harmonic voltage distortion limits (essentially same as [2]
table 11-1)
Individual voltage distortion (%)
THDVn (%)
69 kV and below
3.0
5.0
1.5
2.5
1.0
1.5
Note: High voltage systems can have up to 2.0% THD where the cause is an HVDC terminal that will attenuate by the time
it is tapped for a user
Active filters
Passive tuned filters are simple series L-C filters. A single tuned passive filter can effectively mitigate one
harmonic frequency. They are generally tuned to a value below the harmonic frequency to be attenuated to avoid
a resonance condition at that frequency. These are custom-engineered solutions that must be designed
specifically for the circuit in question. Passive filters are also used for power factor correction. However, there is
5
a limit to their effectiveness and if higher-order harmonics must be attenuated their use is generally not
cost-effective. Care must be taken in all cases to balance the harmonic and power factor correction
considerations.
Phase multiplication operates on the principle that if m six-pulse rectifiers are shifted 60/m degrees from each
other, are controlled by the same delay angle, and are loaded equally, the only harmonics present will be:
(11-7)
where
h
q
k
Thus, for standard 6-pulse rectifiers the harmonic orders present will be 5, 7, 11, 13,, etc. 18-pulse rectifiers are
the current state-of-the-art; for an 18-pulse rectifier (m=3), the harmonic orders present are 17, 19, 35, 37, , etc.
For an 18-pulse converter, the lower-order harmonics are thus eliminated. For systems with large numbers of
phase-multiplied converters the harmonic current limits in table 10-3 are increased by the factor (q/6)1/2,
where q is the pulse-number of the predominate non-linear load on the system. In this case the limits for the
harmonic orders that do not fit equation (11-7) for the q of the predominate non-linear load are multiplied by a
factor of 0.25. Phase-shifting transformer connections are used to achieve the 60/m degree phase shift between
6-pulse rectifier units.
Active filtering technology is a still-evolving art. Current state-of-the-art designs measure the current, filter out the
fundamental frequency of the measured current, and inject current that is the negative of the result into the
system to cancel the harmonics up to a given harmonic order. These systems are generally used in existing
installations that have existing 6-pulse drives where replacing the drives is not a cost-effective solution, or where
multiple smaller 6-pulse drives are utilized since phase multiplication for a drive below 100hp is generally not costeffective. State-of-the-art units can also dynamically correct the power factor, and are advantageous vs. passive
filters both in their effectiveness and their flexibility in power factor correction.
References
[1]
IEEE Recommended Practice for Powering and Grounding Electronic Equipment, IEEE Std. 1100-1999,
March 1999.
[2]
IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems,
IEEE Std. 519-1992, June 1992.
[3]
IEEE Recommended Practice for Monitoring Electric Power Quality, IEEE Std. 1159-1995.
Introduction
The consideration of arc flash hazards is a relatively new concern for power system design. However, it is a
concern that is rapidly gaining momentum due to increasingly strict worker safety standards and system reliability
requirements that demand work on live electrical equipment.
Background
Electrical arcs form when a medium that is normally an insulator, such as air, is subjected to an electric field
strong enough to cause it to become ionized. This ionization causes the medium to become a conductor which
can carry current. The phenomenon of electrical arcing is as old as the world itself. Lightning is a natural form of
electrical arc. Man-made electrical arcs exist in devices such as arc furnaces. However, utilization of electrical
energy invariably requires equipment where unintentional arcing between conductors becomes a possibility.
Electric arcs in equipment liberate large amounts of uncontrolled energy in the form of intense heat and light.
Unintentional arcing in power equipment can impose several different types of hazards:
I
Heat from arc can cause severe flash burns many feet away (temperatures can reach 20,000 K, four times the
temperature at the surface of the sun!).
Byproducts from the arc, such as molten metal spatter, can cause severe injury.
Pressure wave effects caused by the rapid expansion of air and vaporization of metal can distort enclosures and
cause doors and cover panels to be ejected with severe force, injuring personnel.
Figure 12-1 gives an indication of the amount of uncontrolled energy an arc can contain, as seen by the amount
of damage to the equipment shown.
Electrical safety has traditionally been concerned only with electric shock hazards. The recognition of arc flash
hazards began formally in 1981 with a paper The Other Electrical Hazard: Arc Blast Burns [5] by Ralph Lee,
presented at the 1981 IEEE IAS Annual Meeting. This paper established theoretical modeling for the heat energy
incident upon a surface a given distance from the arc. Subsequent developments followed over the next 20 years,
including testing to develop more accurate empirical calculation methods and to evaluate protective clothing.
At the time of publication, there are two basic standards which establish requirements for arc flash hazards. The
first is NFPA 70E, Standard for Electrical Safety in the Workplace [1], which defines the basic practices to be
followed for electrical safety, including protective clothing levels which must be worn for given levels of arc flash
incident energy and what steps must be taken prior to live work on electrical equipment. The second is the IEEE
Guide for Performing Arc-Flash Hazard Calculations, IEEE 1584-2002 [2] which gives the engineer the methods
for calculating the severity of arc flash incident energy levels. The NEC [3] requires only that certain equipment
(switchboards, panelboards, industrial control panels, meter socket enclosures, and motor control centers in other
than dwelling occupancies and likely to require examination, adjustment, servicing, or maintenance while live) be
field marked to warn qualified persons of potential electric arc flash hazards.
electrically safe work condition prior to working on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational
limitations. In this case live work requires an Energized Electrical Work Permit, for which the requirements are
given in Article 130.1 (A) (2). Some exemptions are given to the requirement for an electrical work permit, such as
testing, troubleshooting, etc., performed by qualified persons.
The approach boundaries to live parts are defined above, and are illustrated in figure 12-2. These form a series of
boundaries from an exposed, energized electrical conductor(s) or circuit part(s). The requirements for crossing
these become increasingly restrictive as the worker moves closer to the exposed live part(s). The limited,
restricted, and prohibited approach boundaries are shock protection boundaries and are defined in NFPA 70E
table 130.2 (C) [1]. Qualified persons can approach live parts 50V or higher up to the restricted approach
boundary, and can only cross this boundary if they are insulated or guarded and no uninsulated part of the body
crosses the prohibited approach boundary, if the person is insulated from any other conductive object, or if the live
part is insulated from the person and from any other conductive objects at a different potential. Unqualified
persons must stay outside the limited approach boundary unless they are escorted by a qualified person.
Unqualified persons cannot cross the restricted approach boundary.
A flash hazard analysis must be performed in order to protect personnel from the possibility of injury due to arc
flash. This analysis must set the flash protection boundary, which for voltages below 600 V is equal to 4 ft. based
upon a clearing time of 0.1 second and a bolted fault current of 50 kA (5000 Ampere-seconds) or, where the
clearing time x bolted fault is greater than 5000 ampere seconds or under engineering supervision, may be
calculated with the equations given in the NFPA 70E text. For voltages over 600V, the flash protection boundary is
defined as the distance from the potential arc which has an incident energy of 1.2 cal/cm2, or 1.5 cal/cm2 if the
clearing time is 0.1 second or faster. The means of calculating the arc flash protection boundary for voltages 600V
or less is based upon the theoretical Lee method developed in [5]. The method for calculating the arc flash
incident energy for a given working distance from live parts is not specified in NFPA 70E code text itself; several
methods are given in Annex D of NFPA 70E. The preferred methods for performing these calculations are given in
IEEE 1584 [2], as detailed below. The option is also given to use pre-prepared tables given in NFPA 70E based
upon given levels of fault current and protective device clearing time to select personal protective equipment in
lieu of a formal arc flash study.
The classifications for personal protective equipment (PPE)for arc flash protection are given in NFPA table 130.7
(C)(11), reproduced below as table 12-1. PPE for arc flash protection is given an Arc Rating in cal/cm2, which
must be compared to the arc flash incident energy for the location in question to select the proper clothing.
Employees working within the flash protection boundary must wear nonconductive head protection wherever there
is a danger of head injury from electric shock or burns or from flying objects resulting from electrical explosion.
Face, neck, chin and eye protection must be worn wherever there is a danger of injury from electric arcs or
flashes or from flying objects resulting from electrical explosion. Body protection, in the form of flame-retardant
(FR) clothing as defined in table 11-1, must be worn where there is possible exposure to arc flash incident energy
levels above 1.2 cal/cm2; an exception allows Category 0 clothing to be worn for exposures 2 cal/cm2 or lower. An
example of a full flash suit is shown in figure 12-3.
Clothing description
N/A
25
40
IEEE 1584
IEEE 1584 [2] is the guide for determining arc flash incident energy levels and protection boundaries. It contains
an empirical calculation method based upon extensive test results using a Design-of-Experiments (DOE) method,
resulting in a 95% confidence level that the arcing fault current will be higher than calculated. In situations where
the empirical method does not apply, the Lee method from [5] is recommended, and is described in IEEE 1584.
IEEE 1584 only takes into account the heat of an arc, and not the secondary effects such as molten metal spatter
and pressure-wave effects.
Frequencies of 50 Hz or 60 Hz
Faults involving three phases in applying the empirical method it is assumed that a phase-to-ground fault will
escalate into a phase-to-phase fault
The first step in this method is to determine the predicted arcing fault current using the following equation for
system voltages less than 1000 V [2]:
(12-1)
For system voltages 1000 V or greater, the following equation is used [2]:
(12-2)
where
Ia
K
Ibf
V
G
The arcing fault current will typically be 40-60% of the bolted fault current for systems 1000 V or less, and 90-95%
of the bolted fault current for systems greater than 1000 V.
The arcing fault current is then used to find the clearing time for the overcurrent protective device which clears the
fault. Care must be taken to identify which device actually clears the fault. The clearing time then becomes the
arcing time for the purpose of finding the incident energy.
The normalized incident energy, referenced to a working distance of 610mm and an arcing time of 0.2 seconds,
is then calculated using the following equation [2]:
(12-3)
where
En
K1
K2
G
Now, using the actual working distance and arcing time, the incident energy is calculated as [2]:
(12-4)
where
Cf
En
t
D
x
= 1.0 for voltages above 1 kV, and 1.5 for voltages below 1 kV
is the incident energy in cal/cm2
is the arcing time per above
is the working distance in mm
is a distance exponent from [2] table 4
5
Table 4 in [2] gives the distance exponents, along with typical gaps between conductors, for different voltage
levels and equipment types.
The flash protection boundary may be found using the following equation [2]:
(12-5)
where
DB
EB
From [1] EB must be 1.2 cal/cm2 unless the voltage is above 600 V and the clearing time is 0.1 s or faster, in
which case it may be increased to 1.5 cal/cm2. However, equation (12-5) may be used to calculate the boundary
for any incident energy level, for example, to calculate the boundaries where different categories of PPE per table
11-1 may be worn. Note that the larger of the boundaries as calculated from IEEE 1584 or NFPA 70E should be
used in order to satisfy the NFPA 70E requirements.
Note that the incident energy is proportional to the arcing time, which is set by the overcurrent protective device
time-current characteristic and the arcing current level. Because overcurrent protective device tripping times are
lower for larger currents due to inverse time-current characteristics, this is an important point. Larger bolted fault
currents lead to larger predicted arcing fault currents, which lead to generally lower values of arc flash incident
energy. Lower bolted fault currents lead smaller predicted arcing fault currents, which lead to generally higher
values of incident energy.
For conservatism, a second predicted arcing fault current is calculated at 85% of the value per equation (11-1) or
(11-2), and the result is used to calculate a second value for the incident energy and flash protection boundary.
The larger of the incident energy/protection boundary values are used as the final result. If the overcurrent
protective device time-current characteristic is horizontal, such as for the instantaneous characteristic of an
electronic-trip circuit breaker, the two values will be equal since the arcing time will not change.
Application guidelines
A.) Arc flash calculations
The following guidelines are helpful when performing arc flash calculations [3]:
I
When choosing a calculation method, be sure the system conditions fall into the calculation methods range
of applicability.
Use the newest methods given in IEEE 1584-2002. Older methods given in previously-published papers are
superseded by this standard.
Use realistic fault current values. The actual minimum available fault current, rather than the worst-case values
typically used for short-circuit analysis, give more conservative (and realistic) results.
Consider the effects of arc fault propagation to the line side of the main overcurrent device when determining
which device should be used to calculate the arcing time. For example, for the electrical panel in figure 12-4,
device A would be used rather than device B for calculating the arcing time for a fault on the panelboard bus,
since the fault can propagate to the line side of device B. Similar considerations should be made for
switchboards, MCCs, etc.
Quantify the variables. The working distance, bus gap, equipment configuration, and system grounding are all
dependent upon the particular installation and must be accurately determined.
Be aware of motor contribution. Motor contribution can both increase and decrease the arc flash incident energy,
depending upon where in the system the arcing fault occurs.
Use a computer for analysis. This is the most efficient way to accurately calculate the incident energies and flash
protection boundaries where multiple sources, such as generation and motor contribution, must be taken into
account. Several commercial software packages are available for arc flash hazard analysis. Be aware, though,
what the user-configurable options for the software are and be sure they are set correctly for accurate results.
Use a dedicated main overcurrent device at transformer secondaries. The secondary of a transformer is one of
the most difficult places to achieve acceptable arc flash hazard levels. If multiple mains are used for transformer
secondaries, the arc flash hazard level downstream from the main but ahead of the feeders must be calculated
using the transformer primary device timing characteristics, significantly increasing the incident energy. If the
secondary main and feeders are in the same switchboard or panel, this will usually not be applicable due to arc
fault propagation to the line side of the main device as described above. For ANSI low voltage switchgear per
ANSI C37.20.1, however, this can be of real benefit, as well as in cases where the secondary overcurrent device
is remote from the feeders.
Closely coordinate devices where possible. The lower the clearing time for the predicted arcing current, the
lower the arc flash incident energy.
Use high-performance devices, such as low-arc-flash circuit breakers, where possible. These will significantly
reduce the arc flash incident energy.
Use bus differential protection and/or zone selective interlocking where possible. This is high-speed protection
that can significantly lower the arc flash incident energy.
References
[1]
Standard for Electrical Safety in the Workplace, NFPA 70E, The National Fire Protection Association,
2004 Edition.
[2]
IEEE Guide for Performing Arc Flash Hazard Calculations, IEEE 1584-2002, September 2002.
[3]
The National Electrical Code, NFPA 70, The National Fire Protection Association, Inc., 2005 Edition.
[4]
A. C. Parsons, Arc Flash Application Guide Arc Flash Energy Calculations for Circuit Breakers and Fuses,
Square D/Schneider Electric Engineering Services, August 2004.
[5]
Lee, R., The Other Electrical Hazard: Electrical Arc Blast Burns, IEEE Transactions on Industry Applications,
vol. 1A-18, no. 3, May/June 1982.
Section 13:
Introduction
The vast majority of industrial and commercial facilities are served from public utilities. However, the utility
interface is often the most neglected aspect of system design. This is especially true at the medium voltage level.
Often, the service equipment manufacturer is expected to resolve issues that severely impact the design of the
system. This can result in unexpected costs and project delays. These issues should be addressed during the
system design stage, where the impacts to system reliability and cost can be adequately managed; only by
knowing the utilitys requirements is this possible.
Restrictions on, or requirements for, normal and alternate services and transfer equipment between the two
Restrictions or requirements for the configuration of emergency and standby power systems
The most common requirement, which is applied to virtually every utility installation, is that the service
overcurrent device must coordinate with the upstream utility overcurrent device, typically a recloser or utility
substation circuit breaker. If there is standby power on the premises, the utility will typically require that
paralleling the alternate power source with the utility source not be possible unless stipulated in the rate
agreement for the service in question.
Requirements for restricted access to service cable termination and service disconnect compartments in the
service switchgear are another common. In some cases these must be in a dedicated switchgear or switchboard
section, increasing the service equipment footprint. In many cases grounding means must be provided with the
equipment to allow the utilitys preferred safety grounding equipment to be installed. In some cases, requirements
may be imposed on the entire service switchgear, such as electrical racking for circuit breakers or barriers that are
not standard for the equipment type used.
In some cases the control power for the service switchgear, such as a battery, must be designed to the
utilitys specifications.
Additional protective relaying may be required to prevent abnormal conditions which, although not harmful to the
system being served, affect the reliability of the utility system. In some cases the makes and models of protective
relays for the service overcurrent protection are restricted to those the utility has approved.
Data on the utilitys nearest upstream protective device (device type and ratings, relay type and
settings if applicable).
Contact information for utilitys system engineer or equivalent for the region in question.
All of these, except items 6 and 8, should be available from the serving utility. Item 6 should be available from the
regional Public Service Commission or similar governmental regulatory agency. Item 8 may not be available at the
outset, but should be taken into consideration as soon as it becomes available.
References
[1]
EUSERC Manual, Electric Utility Service Equipment Requirements Committee, 2005 Edition
Section 14:
Introduction
Electricity is a powerful form of energy that is essential to the operation of virtually every facility in the world.
It is also an expensive form of energy that can represent a significant portion of a manufacturing facilitys cost
of production.
This energy management primer is intended to introduce some electricity billing fundamentals, especially focusing
on the two major aspects of the electric bill, demand and energy. This section also highlights key aspects of
identifying energy-saving opportunities among major industrial processes and equipment.
Electricity metering: Electric utilities meter both the real and reactive power consumption of a facility. The real
power consumption, and its integral energy, usually comprise the largest portion of the electric bill. Reactive
power requirements, usually expressed in power factor, can also be a significant cost and will be discussed later.
Demand: Real power consumption, typically expressed in kilowatts or megawatts, varies instantaneously over
the course of a day as facility loads change. While instantaneous power fluctuations can be significant, electric
utilities have found that average power consumption over a time interval of 15, 30, or 60 minutes is a better
indicator of the demand on electrical distribution equipment.
Transformers, for example, can be selected based on average power requirements of the load. Short-duration
fluctuations in load current may cause corresponding drops in load voltage, but these drops are within the
normal operating tolerances of typical machines and within the design parameters of the transformer.
The demand rate, in $/kW, may also be referred to as a capacity charge, since it has historically been related to
the necessary construction of new generating stations, transmission lines, and other utility capital projects.
Demand charges often represent 40% or more of an industrial customers monthly bill.
INSTANTANEOUS
POWER
POWER (KILOWATTS)
DEMAND
INTERVAL
DEMAND
INTERVAL
DEMAND
INTERVAL
DEMAND
INTERVAL
TIME
Demand is the average instantaneous power consumption over a set time interval,
usually 15, 30, or 60 minutes.
I
Energy: The other major component of an electric bill is energy. The same metering equipment that measures
power demand also records customer energy consumption. Energy consumption is reported in kilowatt-hours or
megawatt-hours. Unlike power demand with its capacity relationship, customer energy consumption is
sometimes related to fuel requirements in electric utility generating stations. The cost per kilowatt-hour in a
given electric utility rate structure, therefore, is often influenced by the mix of generating plant types in the
utility system. Coal, fuel oil, natural gas, hydroelectric, and nuclear are typical fuel sources on which power
generation is based.
Load factor Demand/energy relationship: One useful parameter to calculate each month is the ratio of
the average demand to the peak demand. This unit-less number is a useful parameter that tracks the
effectiveness of demand management techniques. A load factor of 100% means that the facility operated at
the same demand the entire month, a so-called flat profile. This type of usage results in the lowest unit cost
of electricity.
Few facilities operate at a load factor of 100%, and that is not likely to represent an economical goal for most
facilities. But a facility can calculate its historical load factor, and seek to improve it by reducing usage at peak
times, moving batch processes to times of lower demand, and so forth. Load factor can be calculated from
values reported on practically every electric bill:
LF = kWh/(kW * days * 24);
Where LF is Load Factor, kWh is the total energy consumption for the billing period, kW is the peak demand set
during the billing period, and days is the number of billing days in the month (typically 28-32). 24, of course is
the number of hours in a day.
Time-of-Use customers may prefer to track load factor only during on-peak time periods. In that case, the kWh,
kW, days, and hours/day in the formula are changed to reflect the parameters established only during the onpeak periods.
Typical load factor for an industrial facility depends to a great degree on the number of shifts the plant operates.
One shift, five-day operations typical record a load factor of 20-30%, while two-shifts yield 40-50%, and three
shift, 24/7 facilities may reach load factors of 70-90%.
T hree S hifts
One S hift
Demand, kW
Demand, kW
Equal Energy
Unequal Demand
Graphical comparison of facilities with dramatically different load factors. The three shift facility produces an average demand that is nearly equal to its peak demand, while the average and peak
demand for the one shift facility is much less than one.
30%
50%
Peak Demand, kW
Load Factor:
1142
685
70%
489
250,000
250,000
250,000
Demand Cost
$11,420
$6,850
$4,890
Energy Cost
$10,000
$10,000
$10,000
$21,420
$16,850
$14,890
Average Cost/kWh
8.57
6.74
5.96
Demand Cost As
Percent of Total
53%
41%
33%
Power factor: The relationship of real, reactive, and total power has been introduced previously, and described
as the power triangle. For effective electricity cost reduction, it is important to understand how the customers
electric utility recoups its costs associated with reactive power requirements of its system. Many utilities include
power factor billing provisions in rate schedules, either directly in the form of penalties, or indirectly in the form of
real-power billing demand that is higher than the actual measured peak.
Even if a utility does not charge directly for poor power factor, there are at least three other reasons that a
customer may find it economical to install equipment to improve power factor within its facility, thereby reducing
the reactive power requirements of the utility. PowerLogic Solutions, volume 1, issue 4 (www.powerlogic.com)
describes each of these cost-reduction opportunities in considerable detail.
N Reduce power factor penalties
N
Reduce heating losses associated with power distribution (often called I2R losses)
Production
Equipment
9%
Compressed Air
8%
Packaging Lines
8%
Utility Systems
3%
HVAC
10%
Miscellaneous
6%
Cooling Tower
Fans
3%
Chilled Water
Pumps
9%
Condenser Water
Pumps
3%
Chillers
33%
The FEP is best developed using actual power measurements from existing facility-wide monitoring systems.
Some types of loads, lighting, for instance, may comprise part of the usage of every major circuit in the facility.
This fact would suggest that the meter measuring the power consumption of a feeder serving the buildings
centrifugal water chillers.
Circuit Monitors
Actual power monitoring data from existing circuit monitors measuring the power consumption
of individual feeders is the best basis for establishing the Facility Energy Profile.
The demand sort is produced by rearranging individual integrated demand readings for a given
billing period. Meters record demand readings chronologically, 3000 or so readings for a 30-day
billing period at 15-minute demand intervals; the demand sort utilizes a software tool to
distribute the readings from highest to lowest, so that times and values of peak usage are
easily analyzed.
The demand sort table facilitates demand analysis by depicting the number of intervals
(or hours) during which the plants peak electrical demand exceeded certain levels.
Using the demand sort table, the engineer is able to determine that a reduction in peak demand
to 2200 kW at this example facility would have required a demand reduction of 122 kW for 25
15-minute intervals, or 6.25 hours, in August of the sample year.
17000
16000
OffPeak
15000
Demand, kW
14000
13000
12000
Off-Peak
11000
On-Peak
2330
2245
2200
2115
2030
1945
1900
1645
1600
1515
1430
1345
1300
1215
1130
915
1045
1000
830
745
700
615
530
445
400
315
230
145
15
100
8000
ShoulderPeak
Shoulder-Peak
1815
9000
1730
10000
Peak-Day load profiles from actual power monitoring data can show consistency, or, as in
this case, a single-day aberration in peak demand that set the demand minimum billing level
(ratchet) for the remainder of the year.
Demand control
Demand controls systems are available that perform these basic functions:
I
Transmit signals to pre-determined equipment to turn off or curtail power usage if demand is predicted to
exceed target kW
These demand controls systems are intended to reduce peak demand for a facility to some predetermined level.
The design engineers foremost demand control system challenge is to identify loads in the facility that
can be controlled effectively. Ideal load candidates includes those machines or processes that are (1)
currently contributing to the facilitys load at peak times, and (2) whose function can be delayed or curtailed
at times of peak.
Most facilities lack equipment or processes that fit this ideal description, despite the numerous machines and
processes that may be operating at peak times. In fact, successful demand control is usually the exception
rather than the rule.
One common candidate for the demand control system is the air conditioning system. Buildings equipped with
multiple packaged direct-expansion air conditioning systems are typical targets of demand control sales efforts.
Unfortunately, demand control of air conditioning compressors usually leads to loss of temperature or humidity
control within the conditioned space, or lack of demand savings.
The reason for this paradox is twofold. One, natural diversity among multiple air conditioning compressors
ensures that all compressors are not operating at full load at the same time. Strangely, this fact is often
highlighted in the demand control system sales pitch: Not all compressors are running at the same time, so you
should turn some off for short periods of time.
Secondly, basic thermodynamic principles of moist air and vapor-compression refrigeration systems require
compressor power consumption to reduce air temperature and condense moisture. This process is controlled by
thermostats and humidistats within the facility. When cooling or dehumidification is removed or reduced at times
when these devices are calling for them, temperature and humidity will rise in the conditioned space.
So, if not air conditioning equipment, what loads have been successful demand control candidates?
An electrolysis process providing chemicals for a paper mill was able to reduce peak demand and flatten the
demand profile for the overall facility. A battery-charging system for forklift vehicles in an automotive facility was
capable of producing real demand savings during peak times. Finally, a large induction furnace melting scrap
metal proved to be an effective candidate for the rolling mill at a steel plant.
Chilled water supply and return temperatures increase over the course of a day due to
demand control of inlet guide vanes on a centrifugal water chiller. Space conditions
could not be maintained as a result of the demand control.
Costs of generated power: Onsite generators typically utilize natural gas, wood, fuel oil, or steam derived
from a fossil fuel or as a part of a production process. Unit fuel costs for fossil fuels are usually calculated based
on the fuels heating value, an estimated efficiency of the generator system, and the fuel cost.
Cost/kWh = fuel price/gal * 3413/HV/efficiency,
In this equation, HV is the heating value of fuel oil in BTU/gal, and 3413 is the conversion from BTU to kWh.
Internal combustion diesel generators typically range in efficiency from 25-30%.
For a typical example, #2 fuel oil may be burned in an IC engine. For a fuel-oil price of $2.00/gal, and a
generator efficiency of 25%, the fuel cost/kWh is:
Cost/kWh = $2.00 * 3413/108,000 BTU/gal/0.25
Cost/kWh = 25 /kWh.
Obviously, peak-shaving is much less attractive at a fuel cost of $2.00/gal, unless required generator operation
can be predicted accurately and electricity charges are comparably high as well.
Utility rates affecting peak-shaving generation: Electric utility rates must be analyzed carefully prior to
implementing peak shaving or cogeneration opportunities. Some utilities have special interconnection and
protective relaying requirements to ensure that onsite generation does not pose a safety hazard for utility
workers. In addition, many utility rate schedules impose standby charges for onsite generation.
These charges are intended to recoup the utilitys investment in transformers and other equipment necessary to
serve the facilitys entire load when the onsite generation equipment is not operating. Without this standby
equipment, utilities often reserve the right to replace service equipment with smaller facilities, at risk to the
facility of overloading the smaller equipment when onsite generation is not operating.
Plant Total Power Requirement
Plant Demand, kW
On-Peak
Period
Purchased Power
Facilities with onsite generation may be able to operate this equipment to reduce purchased power
requirements during periods of high demand, or high utility prices.
4%
2%
0%
6000
5800
5600
5400
5200
5000
4800
-2%
-4%
-6%
$0.60/gal
$0.80/gal
$1.00/gal
-8%
-10%
-12%
-14%
-16%
-18%
Generator Setpoint, kW
Process
Steam
Turbines
Electricity
Boilers
Condenser
Condensate
Return
Electricity generation and peak shaving can also be accomplished with steam cogeneration
systems typical of paper mills, refineries, and other large industrial processes.
Lighting control
Lighting systems in industrial facilities can represent an attractive savings opportunity, especially if lighting
systems have not been upgraded or maintained in the past five years. The most cost-effective approach for
lighting energy savings is to address the following three issues, in order:
I
Turn off lights during times when they are not needed
Reduce light levels to match the requirements for the tasks being performed in the area
Replace less efficient lamps, ballasts, or fixtures with more efficient sources
The second priority in lighting conservation involves light level reductions. The Illuminating Engineering Society of
North America (www.iesna.org) has established recommended light levels for different types of work tasks and
area usage types. In addition, it offers design guidance in laying out lighting systems, estimating light levels by
zonal cavity and point-by-point lighting design methodologies.
These light level recommendations are typically described as ranges of footcandles, the footcandle being a
quantity of light measured at a horizontal or vertical surface. Light output of a fixture is usually published in
lumens. Many manufacturers of lamps and lighting systems offer software tools to aid in designing new systems,
or in evaluating changes to existing systems.
I
Light levels are also adversely affect by dirt and the accumulation of dust on the light fixture. Luminaire Dirt
Depreciation, or LDD, also a factor less than 1.0, is a function of the type of light fixture as well as the
environment in which the fixture operates.
Ballast Factor, or BF, is yet another commonly used factor. BF is also a published value that is a function of
the type of ballast used to control the arc characteristics of fluorescent and HID lighting systems.
The designer usually applies these factors to the rated light level output of a lighting system, in order to
estimate the number of fixtures required to provide the desired light level not at initial installation, rather at
some designated point in the future. For example,
# fixtures = total required lumens/initial lumens/fixture/(LLD * LDD * BF).
N
Electric motors
Three-phase squirrel-cage induction motors comprise a considerable percentage of the electrical load in the
United States. Design, operation, and maintenance of these machines is well described in other references; this
document focuses on their energy efficiency aspects.
Induction motors typically range in full load efficiency from about 87% to 94%. This efficiency is very difficult to
measure accurately in the field, requiring a dynamometer and other specialized equipment. Fortunately, energy
saving projects associated with electric motors do not require actual efficiency of a given motor to be established.
One of the foremost opportunities for energy savings is to implement a program of replacing rather than
rewinding induction motors at failure. Rewinding a damaged induction motor is a common practice in industry,
but studies have proven that rewinding an induction motor drops its efficiency by a couple percentage points.
Multiple rewinds can further reduce the efficiency of the rewound motor.
While a drop in efficiency from 89% to 88% seems insignificant, a quick estimate reveals that this reduction can
be costly. A standard efficiency 20 hp motor operating 8000 hours annually, for example, costs about $7000 per
10
year to operate at an average electricity rate of 7 /kWh. Once this motor fails, the least-cost option for returning it
to service is typically rewinding.
The incremental cost of replacing this failed motor with an energy-efficient motor, however, is only $430. This
amount assumes considers the rewound cost, and the labor necessary to perform the motor change-out,
as sunk costs.
The annual energy savings associated with replacing the failed motor with an energy-efficient model, at a
new efficiency of 92.9%, is approximately $510. The simple payback for the replacement, therefore, is less
than one year.
Energy-efficient motor programs are applicable to any AC motor installations utilizing NEMA Design B induction
motors. Since the programs are based on replacement at failure, the full savings potential is realized after three
years or more.
HP
Rewound
Efficiency
Standard
Efficiency
Energy
Efficient
Efficiency
1
2
3
5
8
10
15
20
25
30
40
50
60
75
100
125
150
69.7%
79.5%
79.4%
81.4%
83.1%
85.1%
85.5%
87.3%
88.0%
88.1%
88.7%
90.0%
89.9%
90.4%
90.4%
90.6%
91.5%
70.7%
80.5%
80.4%
82.4%
84.1%
86.1%
86.5%
88.3%
89.0%
89.1%
89.7%
91.0%
90.9%
91.4%
91.4%
91.6%
92.5%
82.6%
83.4%
86.6%
88.3%
90.0%
91.1%
92.0%
92.9%
93.5%
93.7%
94.2%
94.4%
94.7%
94.9%
95.4%
95.3%
95.7%
11
Variable-speed drives
There are many devices used to provide AC motor control starting, stopping, changing speed, varying torque,
providing protection from voltage and current anomalies. This section will focus, however, on variable-frequency
control devices designed to reduce energy consumption and improve operation of three-phase AC induction
motors. See www.squared.com for technical publications that describe these devices in greater detail.
AC motor loads are typically grouped in four major categories:
Type of Load
Typical Examples
Variable torque
Constant torque
Constant horsepower
Grinders
Impact
Punch press
Energy-saving opportunities commonly focus on the variable-torque category, because the energy saving potential
is large even with small changes in pump or fan speed control.
This opportunity is driven by the power and speed characteristics of the variable-torque load. The capacity
of a pump or fan is directly proportional to the speed. A change in speed of 10% yields a change in pump gpm
or fan CFM of 10%.
Brake horsepower, however, is proportionally to the cube of the speed, meaning that a 10% reduction in pump
or fan speed can yield a 27% reduction in power consumption.
In addition, pumps and fans are often controlled by mechanical devices in the fluid flow stream, such as dampers,
control valves, and guide vanes. These devices are typically much less efficient means of varying pump volume or
fan delivery than changing the speed of the pump or fan.
Since most pumps and fans are driven by fixed-speed electric motors, where speed of the driven load is
determined by the number of motor poles, AC frequency, and motor slip, varying the speed of a motor requires an
external device. This external device is commonly referred to as an adjustable-speed drive, variable-frequency
drive, inverter, vector drive, or adjustable-frequency controller.
Variable-torque loads, such as centrifugal pumps and fans, exhibit a cubic relationship
between brake horsepower and speed.
12
Compressed air
Compressed air systems can consume a significant amount of electric energy in an industrial facility. Many textile,
automotive, chemical, and petroleum facilities operate large, multi-stage air compressors driven by electric motors
representing hundreds, thousands, or even ten-thousands of horsepower in capacity. One chemical plant
providing raw materials for synthetic textile manufacturing operated one 22,000 hp, and two 8,000 hp
compressors in a portion of its process.
While the 22,000 hp compressor is rare, significant energy reduction opportunities associated with compressed
are available.
Power consumption of a typical air compressor is a function of the air volume required (V),
the inlet air temperature (Tin), and the required pressure rise (Pout/Pin).
Reduce outlet pressure compressor discharge pressure in some facilities is set too high. Since the pressure
rise across a compressor is a key factor in its power consumption, reducing outlet pressure can offer significant
savings. Some reasons for excessive pressure may be straightforward; eg, production equipment with lower
requirements has replaced older machines without a corresponding reduction in compressed air setpoint. Other
reasons may be more complex; eg, piping system losses or leaks may force higher setpoints at the compressors
in order to provide adequate air pressure at production equipment.
Reduce air volume (CFM) requirements compressed air leaks usually offer the most attractive opportunity for
reducing compressed air volume. Some facilities have ignored leaks to the point that one compressor is
effectively operating 24/7 simply to serve air leaks.
Reduce inlet temperature warm air is less dense than cold air. As the compressed air work equation above
indicates, reducing inlet air temperature can reduce the work associated with a compressor. The usual method
of reducing air temperature is to provide outside air intakes for the compressor, rather than allowing the
compressor to utilize air from a hot equipment room.
Increase inlet pressure Its common to assume that inlet pressure to a compressor is fixed at atmospheric
pressure, but this is a misconception. Air compressor inlet systems, especially air filters, need to be kept clean
and free of obstructions. Pressure drop across dirty or blocked intakes serves to reduce the pressure at the
compressor and increase power consumption.
13
0.95
0.9
Chiller Efficiency
0.85
0.8
0.75
0.7
0.65
0.6
0.55
0.5
20%
30%
40%
50%
60%
70%
80%
90%
100%
140.0%
120.0%
%loaded CHILLER1_KWD
100.0%
80.0%
%loaded CHILLER2_KWD
60.0%
%loaded CHILLER5_KWD
40.0%
3/30/98 20:01
3/28/98 22:16
3/27/98 0:31
3/25/98 2:46
3/23/98 5:01
3/21/98 7:16
3/19/98 23:19
3/13/98 9:57
3/16/98 16:52
3/8/98 5:31
0.0%
3/10/98 15:17
20.0%
3/6/98 7:58
Operating three chillers at partial loads is less efficient that operating two chillers
at or near their rated capacity.
14
Chilled water reset this strategy involves increasing the chilled water supply temperature setpoint to match
the requirements of the cooling load. Reset is often performed as part of the control routines in an automatic
chiller controller. Chilled water reset can reduce compressor power consumption by 1.5%-2% per degree.
Reduce condenser water temperature similar to raising the chilled water setpoint, reducing the condenser
water temperature serves to reduce the compressor power requirements. Condenser water temperature
reduction of one degree can reduce compressor power consumption by 0.5%-1%.
Monitor and maintain chiller approach temperatures chiller condensers and evaporators are shell-and-tube
heat exchangers that require periodic maintenance to maintain optimum heat transfer characteristics. Since
water travels through the condenser and evaporator tubes, solids have a tendency to accumulate on internal
tube surfaces, requiring annual rodding to remove the scale and restore heat transfer coefficients.
145%
140%
135%
130%
125%
120%
115%
110%
Est'd FF = 0.0034
105%
100%
Clean
0.001
0.002
0.003
0.004
WAGES
WAGES is the acronym for the complete power and energy monitoring system in a typical industrial facility.
Industrials are concerned about the costs of Water, Air (compressed), Gas (natural gas), Electricity, and Steam.
These systems are often interrelated to the degree that reductions in one utility can increase usage in another.
The power monitoring system used by industrials has to have the capability of monitoring each of these
parameters accurately, and of posting this information in a common, preferably web-based, format for use by the
local site and by remote engineers and managers.
Web-based power monitoring systems allows energy managers to monitor the results
of their demand and energy reduction techniques through the internet, and facilitate
identification of new opportunities.
15
Induction motors
1. Motors operating 75%+ full load, more than 6,000 hours per year.
N Replace with energy efficient motors at failure.
2. Standard V-belts on pumps or fans.
N Convert to cog V-belts.
3. Fans or pumps that are throttled with dampers or control valves.
N Consider variable speed drives.
Demand management
1. Sharp demand peaks of short duration (low load factor)?
N Identify loads to shed or reschedule to off-peak.
2. Batch processes?
N Shift to off-peak.
3. Consider Time-of-Use savings opportunities.
16
Cooling towers
1. Consider variable speed drives for fan motors.
2. Consider PVC fill to replace wood fill material.
3. Consider velocity recovery stacks.
Boilers
1. Stack gas temperature > 400 F? (Ideal temperature: 100 degrees plus saturation temperature of the steam)
N Consider economizer to preheat feedwater or combustion air.
2. Manual or intermittent blowdown?
N Consider automatic blowdown system.
3. Continuous blowdown?
N Consider blowdown heat recovery system.
4. Excess air high or unburned combustibles?
N Consider boiling tuning.
5. Large amounts of high pressure condensate?
N Consider high pressure condensate receiver.
6. Increase amount of condensate returned.
7. Improve boiler chemical treatment.
8. Maintain steam traps.
17
Heat recovery
1. Waste water streams > 100 F?
N Consider heat exchanger and/or heat pump.
2. Waste air or gas stream > 300 F?
N Consider heat exchanger.
Cogeneration
1. Boiler rated pressure 100 psi greater than pressure required by process?
2. Concurrent steam and electrical demands?
N Consider back-pressure turbine.
Refrigeration
1. Consider hot gas heat recovery.
2. Consider thermal storage.
Compressed air
1. Provide additional small air compressor for loads.
2. Provide outside air intake.
3.
18
Section 15:
Project Coordination
Introduction
With all of the technical details that must be considered, project coordination is often given a low priority or,
worse, left to chance. However, this often-overlooked aspect of power system design is vital to insure the
success of any project.
Coordination with the Serving Utility: Coordination with the serving electric utility is vital if a clear understanding
is to be achieved between both parties. Often, additional requirements are uncovered that affect the design of
the project and its cost.
Coordination with the Local Planning/Regulatory/Codes Authorities: This is vital to the success of the
project. Additional requirements can be uncovered that affect the project, saving time and money vs.
identifying them later.
Coordination with equipment manufacturers: If this is possible prior to bidding, it can make the project run
smoother later in the process, especially for difficult equipment application situations, since a clear
understanding can be gained regarding the characteristics of the equipment in question and the best
alternatives can be evaluated.
Coordination with the installing contractor, if the actual construction is under your purview, can save time and
frustrating delays by making your installation requirements clear.
Post-bid/approval process
Once the bid process is complete, further details must be coordinated with the equipment manufacturers.
This is vital for two reasons:
1. To understand the details of the equipment proposed, and
2. To insure that the manufacturer understands the requirements of the equipment, including delivery
requirements. The time taken at this stage will save time and money later in the process.
Once shop drawings are received, it is important to review them in a timely manner, with any changes marked
clearly. Blanket statements to adhere to the specifications, without details, can lead to frustrating project delays.
This is also the time to submit the manufacturers shop drawings to the serving utility and/or local
planning/codes/regulatory authorities, if required. The equipment manufacturer will typically submit to the serving
utility if required, but this should be double-checked to avoid confusion. Also, it is good practice to obtain the
equipment submittal markups from the serving utility in order to be aware of any changes they request.
Equipment inspections
If you require an inspection of the equipment, be sure that the manufacturer clearly understands your
expectations. Make sure the manufacturer contacts you well in advance of the equipment availability date to allow
for adequate trip planning time.
1
Commissioning
When the equipment begins to arrive on site, it is a good idea to coordinate frequently with the installing
contractor. Arrange for the local sales representatives for the major equipment to be on-site periodically during
construction so that problems can be quickly resolved. If the manufacturers service technicians are responsible
for commissioning, make sure your expectations for the scope of their work are clear.
If the serving utility requires witness testing of any equipment or system, make sure they are notified at least two
weeks in advance to allow for proper planning.
Final acceptance
Once system commissioning is complete, arrange a walk-through with the client to show the completed
installation. Also, obtain all equipment operation and maintenance manuals, including field and factory test
reports, and store them in a secure area for future use.
Document Number
0100DB0603
1. Introduction
2. Background
Document Number
0100DB0603
A
CB M1
CB F1
C
LIGHTING PANEL
"LP1"
CB PM1
CB B1
E
Fault location
A
B
C
D
E
Document Number
0100DB0603
CB M1
CB M1 PRIMARY
PROTECTIVE
ZONE
CB F1
CB F1 PRIMARY
PROTECTIVE
ZONE
CB PM1
CB B1
CB B1 PRIMARY PROTECTIVE ZONE
Document Number
0100DB0603
Document Number
0100DB0603
CB M1
UTILITY PROTECTION
BACKUP PROTECTIVE ZONE
CB M1 BACKUP
PROTECTIVE
ZONE
CB F1
CB PM1
CB B1
CB PM1 BACKUP
PROTECTIVE ZONE
CB PM1 BACKUP
PROTECTIVE ZONE
Document Number
0100DB0603
10K
1K
100
CURRENT IN AMPERES
10
1000
1000
CB M1
100
100
CB F1
10
0.10
TIME IN SECONDS
10
0.10
100K
10K
1K
0.01
10
100
0.01
Document Number
0100DB0603
Overcurrent
30kA
Available
Fault
CB M1
CB M1 PRIMARY
PROTECTIVE
ZONE
CB F1
CB F1 PRIMARY
PROTECTIVE
ZONE
CB PM1
CB B1
CB B1 PRIMARY PROTECTIVE ZONE
Document Number
0100DB0603
where the available fault current is 2kA. It can be readily seen that the
primary protective zones in Fig. 7 are not the ideal primary protective
zones per Fig. 2.
Fig. 6: Time-Current Plot showing lack of selective
coordination between CB F1 and CB PM1
100K
10K
1K
100
CURRENT IN AMPERES
10
1000
1000
CB M1
CB F1
100
100
CB PM1
10
CB B1
10
TIME IN SECONDS
0.10
0.10
100K
10K
1K
0.01
10
100
0.01
CB M1
CB M1 PRIMARY
PROTECTIVE
ZONE
CB F1
30kA
Available
Fault
CB F1 PRIMARY
PROTECTIVE
ZONE
25kA
Available
Fault
CB PM1
CB B1
CB B1 PRIMARY
PROTECTIVE ZONE
Document Number
0100DB0603
Document Number
0100DB0603
10
Document Number
0100DB0603
11
Document Number
0100DB0603
12
Document Number
0100DB0603
Note that NEC 517.17 applies to hospitals and other buildings with
critical care areas or utilizing electrical life support equipment, and
buildings that provide the required essential utilities or services for the
operation of critical care areas or electrical life support equipment.
NEC 517.17 (B) requires an additional level of ground-fault protection
for health care facilities where a service or feeder disconnecting
means is equipped with ground-fault protection. This additional level
of ground-fault protection must be at the next level of protective
devices downstream from the service or feeder. In NEC 517.17 (C),
not only is it stated that selectivity must be achieved, but the amount
of selectivity (6 cycles) is specified.
Note that NEC 517.17(B) effectively prohibits the use of ground-fault
protection on the essential electrical system. The result is a conflict
between NEC 517.17(B) and NEC 700.27 and NEC 701.18. This will
be discussed in further detail below.
13
Document Number
0100DB0603
3. Protective Device
Characteristics
3.1. Fuses
Melting Time
Overcurrent is cleared.
Arcing Time
For all low-voltage fuse classes, the basic timing characteristics can
be classified in the same manner. Fuses are typically assigned a
minimum melting characteristic and a total clearing characteristic by
their manufacturer. These define the boundaries of the fuse timecurrent characteristic band. For currents with time durations below
and to the left of the time current characteristic band, the fuse will not
blow or be damaged. For currents with time durations within the timecurrent characteristic band, the fuse may or may not blow or be
damaged. For currents with time durations above and to the right of
the time-current characteristic band, the fuse will blow with a minimum
melting time given by the minimum melting time characteristic and a
total clearing time given by the total-clearing time characteristic.
Alternatively, the fuse may be assigned an average melting time
14
Document Number
0100DB0603
10K
100
1K
CURRENT IN AMPERES
1000
1000
100
100
Total Clearing
Characteristic
10
10
TIME IN SECONDS
Minimum
Melting
Characteristic
0.10
0.10
100K
10K
0.01
100
1K
0.01
15
Document Number
0100DB0603
10K
10
1K
100
CURRENT IN AMPERES
1000
1000
FU 1
100
100
FU 2
10
UTILITY BUS
1
TIME IN SECONDS
10
FU 1
FU 2
0.10
0.10
100K
10K
1K
10
100
0.01
0.01
16
Document Number
0100DB0603
Tripping Type
Short-time Withstand
Capability2
Low-Voltage
Power
UL 489
ANSI C37.13
UL 1066
Electronic
Electronic
(insulated case)3
Often comparable to
interrupting rating
Electronic
Typically comparable
to interrupting rating
Other circuit breaker types, such as molded-case circuit breakers with instantaneous-only trip
units, are available for specific applications, such as short-circuit protection of motor circuits
Insulated-case circuit breakers exceed the UL 489 standard. The term insulated case is
not a UL term.
17
Document Number
0100DB0603
10K
1K
10
100
CURRENT IN AMPERES
1000
1000
100
100
10
10
Thermal
(long-time)
Characteristic
0.10
TIME IN SECONDS
Magnetic
(instantaneous)
Characteristic
0.10
100K
10K
1K
0.01
10
100
0.01
10K
1000
1000
100
100
10
10
0.10
0.10
18
Magnetic
(instantaneous)
Characteristic
HI setting
100K
10K
1K
0.01
10
100
0.01
TIME IN SECONDS
Magnetic
(instantaneous)
Characteristic
LO setting
1K
10
100
CURRENT IN AMPERES
Document Number
0100DB0603
19
Document Number
0100DB0603
1K
10
100K
1000
100
CURRENT IN AMPERES
1000
100
10
10
TIME IN SECONDS
Adjustable
Short-Time Pickup
Adjustable
Short-Time Delay
Adjustable
Instantaneous Pickup 0.10
0.10
Instantaneous Timing
is Non-Adjustable
Instantaneous Override
Timing is Non-Adjustable
100K
10K
1K
0.01
10
100
0.01
3.3. Current-Limiting
Circuit Breakers
20
Document Number
0100DB0603
10K
10
1K
100
CURRENT IN AMPERES
1000
1000
100
10
10
0.10
0.10
100K
10K
10
1K
0.01
1
100
0.01
0.5
TIME IN SECONDS
100
21
Document Number
0100DB0603
10K
1K
10
100
CURRENT IN AMPERES
1000
1000
CB M1
100
CB F1
100
CB PM1
10
10
0.10
TIME IN SECONDS
CB F1 and CB PM1
coordinate up to the
available fault
current of 25kA,
despite what
time-current bands
show, due to
dynamic impedance
effects (for one
specific
manufacturers
circuit breakers)
CB B1
0.10
CB PM1, CB B1
Coordinate through 2kA
100K
10K
1K
0.01
10
100
0.01
21.6kA
22
Document Number
0100DB0603
10K
10
1K
100
CURRENT IN AMPERES
1000
1000
100
100
GF CHAR (TYP)
10
10
0.10
0.10
100K
10K
10
1K
0.01
0.5 1
100
0.01
TIME IN SECONDS
23
Document Number
0100DB0603
Requirement/Comment
6.5 Protection
6.5.1* General. The overcurrent protective devices in the EPSS shall be coordinated to optimize
selective tripping of the circuit overcurrent protective devices when a short circuit occurs.
Annex A
A.6.5.1 It is important that the various overcurrent devices be coordinated, as far as practicable, to
isolate faulted circuits and to protect against cascading operation on short circuit faults. In many
systems, however, full coordination is not practicable without using equipment that could be
prohibitively costly or undesirable for other reasons. Primary consideration also should be given to
prevent overloading of equipment by limiting the possibilities of large current inrushes due to
instantaneous reestablishment of connections to heavy loads.
24
Chapter 6 Protection
6.2 Short Circuit Considerations
Careful planning is necessary to design a system that assures optimum selectivity and
coordination with both power sources
Document Number
0100DB0603
The wording of 2005 NEC 700.27 and NEC 701.18 leaves an open
issue. Although selective coordination is defined in NEC 100 as
localization of an overcurrent condition to restrict outages to the
circuit or equipment affected, accomplished by the choice of
overcurrent protective devices and their ratings or settings, NEC
700.27 and NEC 701.18 contain the wording shall be selectively
coordinated with all supply side overcurrent protective devices. What
about scenarios where two devices that are effectively in series
protect a given piece of equipment?
Such a scenario is given in Fig. 17. The transformer shown is
protected for short-circuits by the primary circuit breaker, and for
overloads by the secondary circuit breaker. For a fault where the
protective zones overlap, does it matter whether the primary or
secondary circuit breaker trips? The answer is, of course, no.
However, because of the wording of NEC 700.27 and NEC 701.18 the
two circuit breakers would need to be selectively coordinated with
25
Document Number
0100DB0603
PRIMARY CB
PRIMARY CB
PROTECTIVE ZONE
TRANSFORMER
SECONDARY CB
SECONDARY CB
PROTECTIVE ZONE
Note that for transformers, such as the transformer shown in Fig. 17,
removal of the secondary overcurrent protective device may not be
possible due to restrictions in NEC 450. Removal of this device may
also hinder transformer protection. For these and other scenarios in
which two overcurrent protective devices in series must be utilized,
the local Authority Having Jurisdiction should be consulted to provide
a waiver.
Other possible scenarios for this issue are given in Fig. 18. In both
cases, selective coordination of CB 1 and CB 2 is not required for
over-all system coordination, since there are no additional devices
between the two. Both devices could be the same size device with the
same settings.
26
Document Number
0100DB0603
CB 1
CB 1
PANEL 2
CB 2
SWITCHBOARD
CB 2
a.)
b.)
What can be done about this issue? For the short-term, the solution is
to minimize occurrences of overcurrent protective devices in series,
as discussed below. Long-term actions may include the submission of
change proposals for consideration in a future code cycle. The more
proposals that are made on this issue, the more likely the issue is to
be recognized and corrected.
4.2.2. Ground-Fault Protection in
Health-Care Facilities
27
Document Number
0100DB0603
Alternate
power source
Normal
system
Nonessential
loads
Automatic
switching
equipment
Delayed
automatic
switching
equipment
Equipment
system
Life safety
branch
Critical
branch
Emergency system
What can be done about this issue? For the short-term, bringing the
issue up to the local Authority Having Jurisdiction for resolution is the
only recourse. Long-term actions may include the submission of
change proposals for consideration in a future code cycle. The more
proposals that are made on this issue, the more likely the issue is to
be recognized and corrected.
28
Document Number
0100DB0603
As mentioned in 2.2 above, the frequency of occurrence of highmagnitude bolted faults is much lower than that of lower-magnitude
faults, such as arcing ground faults. Also, the higher the current level
to which two overcurrent protective devices are coordinated, the more
difficult the coordination effort becomes. The impact of this fact upon
system protection and selective coordination are twofold, namely:
1.) It diminishes the practical need for selective coordination up to the
available fault current in favor of practicable coordination to a
lower level of fault current.
2.) It reinforces the need for coordinated ground-fault protection.
The wording of the 2005 NEC ignores the statistical evidence of the
frequency of occurrence of high-level bolted faults. In reality, these
faults are most common during the commissioning phase of the
electrical system in a facility, when damage to cable insulation and
other application and installation issues are corrected. During the
normal lifetime of the system, these types of short-circuits are rare
indeed, especially at lower levels in the system. One practical way to
address selectivity in emergency and standby systems might be to set
an established limit of 50% of the bolted fault current as the level of
coordination for overcurrent devices below a given level (for example,
400A or below); this is an approximate worst-case for the calculated
value of the arcing fault current for a 480V system when calculated
per the empirical equations in IEEE-1584 IEEE Guide for Performing
Arc-Flash Hazard Calculations [8]. Selective coordination up to such a
limit would be justifiable on a practical basis. However, no code or
standard presently sets this limit.
Arc-flash performance of the system is also a factor. In some cases,
arc-flash performance, particularly at the lower levels of the system,
may be impaired by forcing selectivity up to the available bolted fault
current. The reason for this is that the arc-flash incident energy level
is directly proportional to the time duration of an arcing fault, which
is the clearing time for the overcurrent protective device which
clears the fault.
Also, as described above the NEC effectively prohibits coordinated
ground-fault protection in health care facility essential electrical
systems, even though ~95% of all system faults are ground faults.
29
Document Number
0100DB0603
CB 1
PANEL 2
SWITCHBOARD
CB 1
a.)
b.)
Care must be taken to insure that another NEC section is not violated
when this is done, and that adequate protection of system
components is maintained. For example, the panelboard PANEL 2 of
Fig. 20 b.) may be a main-lugs only panel because there is no NEC
requirement for a panelboard to have a local main disconnect, only
overcurrent protection; this applies in all cases, even when the
supplying panel is on a different floor. Overcurrent protection for the
feeder cables between PANEL 1 and PANEL 2, and for PANEL 2, is
provided by CB 1 in PANEL 1. For the generator of Fig. 20 a.),
however, the removal of the circuit breaker at the generator should be
verified with the local Authority Having Jurisdiction due to possible
conflicts in interpretation of NEC 445.18, which requires a generator
to be equipped with a disconnect by which the generator can be
disconnected from the circuits it supplies. From a protection
standpoint, the cables between the generator and CB 1 can typically
withstand more short-circuit current than the generator can provide,
and, further, the generator voltage regulators control system may
have inherent features to shut down the generator if the generator
supplies a fault for an extended period of time; this must, of course,
be double-checked before making the decision to remove the circuit
breaker at the generator. Overload protection for the generator and
generator load cables is provided by CB 1.
30
Document Number
0100DB0603
CB 1
CB 3
AUTOXFER
E
SW
TO NORMAL SOURCE
CB 2
CB 4
CB 5
AUTOXFER
N
E
SW
AUTOXFER
SW
CB 1
CB 2
CB 1 PROTECTIVE ZONE
CB 3
PROTECTIVE
ZONE
AUTOXFER
E
SW
CB 2 PROTECTIVE ZONE
CB 3
TO NORMAL SOURCE
CB 4
CB 5
AUTOXFER
SW
AUTOXFER
SW
CB 6
CB 6 PROTECTIVE ZONE
31
Document Number
0100DB0603
TO NORMAL SOURCE
CB 1 PROTECTIVE ZONE
CB 1
AUTOXFER E
SW
AUTOXFER
SW
AUTOXFER
SW
CB 6
CB 6 PROTECTIVE ZONE
TO NORMAL SOURCE
CB 1 PROTECTIVE ZONE
CB 2 PROTECTIVE ZONE
87 B
CB 2
CB 3
CB 3
PROTECTIVE
ZONE
AUTOXFER E
SW
CB 4
CB 5
AUTOXFER
SW
AUTOXFER
SW
CB 6
CB 6 PROTECTIVE ZONE
32
Document Number
0100DB0603
In Fig. 24, the differential relay 87B would typically be of the highimpedance type, and would trip CB 1, CB 2, CB 3, CB 4, and CB 5.
A fault between CB 1/CB 2 and CB 3/CB 4/CB 5 will cause this relay
to trip, and, if it is set appropriately, it will operate faster than the trip
unit settings of CB 1 or CB 2, providing short-circuit protection for the
generators in this protective zone as well as providing short-circuit
protection for the paralleling switchgear bus. Generator overload
protection would still be provided by CB 1 and CB 2. Note that
generator differential protection is not shown; it could be provided to
provide additional protection for the generator, but would not be an
aid to selectivity. Generator differential relays, if used, should be of
the percentage-differential type rather than impedance type. Note
also that lockout relays, while recommended, are not shown. The
circuit breakers which must be tripped by the differential relays must
be suitable for external relay tripping (suitable insulated case circuit
breakers or ANSI power circuit breakers are recommended, but are
typically used in this application anyway). Economic concerns (cost
of differential relays and CTs and the extra wiring required) must, of
course, be taken into account when considering this approach.
A more in-depth treatment of generator protection for emergency and
standby power systems is given in a separate paper, Protection of
Low-Voltage Generators Considerations for Emergency and
Standby Power Systems.
33
Document Number
0100DB0603
PANEL 1
CB 1
CB 1
PANEL 2
PANEL 2
CB 2
CB 2
PANEL 3
PANEL 3
CB 3
a.)
34
CB 3
b.)
Document Number
0100DB0603
Although the smaller the transformer, the lower the available fault
current at the secondary, there may be cases where transformers
must be up-sized in order to achieve selective coordination. This is
usually due to the frame size of the primary circuit breaker required to
coordinate with devices at the next level below the transformer
secondary main. A careful balance between the required frame size of
the primary circuit breaker and the available fault current at the
transformer secondary is usually required.
35
5. References
Document Number
0100DB0603
[1] The National Electrical Code, NFPA 70, The National Fire
Protection Association, Inc., 2005 Edition.
[2] IEEE Recommended Practice for Protection and Coordination of
Industrial Power Systems, IEEE Std. 242-2001, December 2001.
[3] Short Circuit Selective Coordination for Low Voltage Circuit
Breakers, Square D Data Bulletin 0100DB0501, October 2005.
[4] IEEE Recommended Practice for Electric Power Distribution for
Industrial Plants, IEEE Std. 141-1993, December 1993.
[5] IEEE Recommended Practice for Applying Low-Voltage Circuit
Breakers Used in Industrial and Commercial Power Systems,
IEEE Std.1015-1997, October 1997.
[6] Standard for Emergency and Standby Power Systems, NFPA 110,
The National Fire Protection Association, Inc., 2005 Edition.
[7] IEEE Recommended Practice for Emergency and Standby Power
Systems for Industrial and Commercial Applications, IEEE Std.
446-1995, July 1996.
[8] IEEE Guide for Performing Arc-Flash Hazard Calculations, IEEE
Std. 1584-2002, September 2002.
tk
Document Number
0100DB0604
Introduction
In this guide, the specific application of circuit breakers in Square D I-Line, NF,
and NQOD panelboards at the 480V and 208V levels are considered.
Information from Data Bulletin 0100DB0501 (Short Circuit Selective
Coordination for Low Voltage Circuit Breakers) is utilized, along with TCC
comparisons where necessary. The result is a set of tables which allow for
easy and efficient selection of Square D panelboards and their overcurrent
devices. Two specifications for selective coordination are considered:
coordination from 0.1 1000s and coordination from 0.01 - 1000s. The
specification that is used will depend upon the NEC and other code
requirements of the installation and the interpretation of these requirements
by the authority having jurisdiction.
The tables herein may be used to select feeder and branch circuit breakers
that will be selectively coordinated when NF and NQOD panelboards are used
in a configuration as illustrated below:
I-LINE (UPSTREAM)
PANELBOARD - 480Y/277V
or 208Y/120VV
FEEDER
CIRCUIT
BREAKER
BRANCH
CIRCUIT
BREAKER
FEEDER
NF (480Y/277V
208Y/120V) or
NQOD (208Y/120V)
MLO
(DOWNSTREAM)
PANELBOARD
Document Number
0100DB0604
Listing Of Tables
Upstream Panelboard Type: I-Line
480Y/277V
0.1 - 1000s
0.01 - 1000s
0.1 - 1000s
0.01 - 1000s
NF
Table IIA
Table IIB
Table IA
Table IB
NQOD
Table IIIA
Table IIIB
N/A
N/A
Assumptions
Document Number
0100DB0604
6. If results do not yield a branch circuit breaker size which is large enough,
repeat steps 4 and 5 using a different Upstream Panelboard Feeder
Circuit Breaker Type
7. If results do not yield a branch circuit breaker size which is large enough
(or an acceptable level of fault current at the downstream panelboard),
a larger feeder will be required. Go to the next larger Feeder
Size/Upstream Panelboard Circuit Breaker Size and repeat steps 1
through 6
8. Repeat steps 1 through 7 until the desired branch circuit breaker size
is obtained
Document Number
0100DB0604
Table IA
I-Line/NF Panelboard Selective Coordination At 480Y/277V
0.1s 1000s
FEEDER SIZE /
UPSTREAM (I-LINE)
PANELBOARD CIRCUIT
BREAKER SIZE
(A)
REQUIRED
DOWNSTREAM (NF)
PANELBOARD
AMPACITY
(A)
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
18
25
100
125
35
65
110
125
125
125
18
35
65
18
30
35
65
18
30
150
250
35
65
18
175
250
30
35
65
18
200
250
30
35
65
18
30
225
250
35
65
18
250
250
30
35
65
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
FA, HD, LX
PG
FH
HG
LX
PG
HJ, LX
PJ
HD
HG
HJ
HD, LA, LX
PG
LA
HG, LH, LX
PG
HJ, LX
PJ
HD
JD, LA
LX
PG
LA
HG
JG, LH
LX
PG
HJ
JJ
LX
PJ
JD, LA
LX, PG
LA
JG, LH
LX, PG
JJ
LX, PJ
JD, LA, LX,
PG
LA-MC
LA
LA-MC
JG, LH, LX
PG
LH-MC
JJ, LX
PJ
JD, LA, LX
PG
LA-MC
LA
LA-MC
JG, LH, LX
PG
LH-MC
JJ, LX
PJ
JD, LA
LA-MC
LX, PG
LA
LA-MC
JG, LH
LH-MC
LX, PG
JJ
LX, PJ
DOWNSTREAM (NF)
PANELBOARD BRANCH
CIRCUIT BREAKER
TYPE
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
ED
ED
EG
EG
EG
EG
EJ
EJ
ED
EG
EJ
ED
ED
EG
EG
EG
EJ
EJ
ED
ED
ED
ED
EG
EG
EG
EG
EG
EJ
EJ
EJ
EJ
ED
ED
EG
EG
EG
EJ
EJ
ED
ED
ED
EG
EG
EG
EG
EG
EJ
EJ
ED
ED
ED
EG
EG
EG
EG
EG
EJ
EJ
ED
ED
ED
EG
EG
EG
EG
EG
EJ
EJ
30
50
30
30
30
50
30
50
30
30
30
30
50
30
30
50
30
50
30
35
40
70
35
30
35
40
70
30
35
40
70
40
70
40
40
70
40
70
70
80
125
70
125
70
80
125
70
80
70
110
125
70
125
70
110
125
70
110
70
125
125
70
125
70
125
125
70
125
Document Number
0100DB0604
FEEDER SIZE /
UPSTREAM (I-LINE)
PANELBOARD CIRCUIT
BREAKER SIZE
(A)
REQUIRED
DOWNSTREAM (NF)
PANELBOARD
AMPACITY
(A)
300
400
350
400
400
400
450
600
500
600
600
600
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
18
30
35
65
18
30
35
65
18
800
800
800
DOWNSTREAM (NF)
PANELBOARD BRANCH
CIRCUIT BREAKER
TYPE
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
ED
EG
EG
EJ
ED
EG
EG
EJ
ED
125
125
125
125
125
125
125
125
125
EG
125
30
LA, LA-MC
35
EG
125
65
18
35
65
18
35
65
18
EJ
ED
EG
EJ
ED
EG
EJ
125
125
125
125
125
125
125
ED
125
EG
125
EJ
ED
EG
EJ
ED
EG
EJ
125
125
125
125
125
125
125
35
65
700
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
18
35
65
18
35
65
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See
the explanatory note below for additional information
2 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range
PG (ET1.0) = ET1.0 trip unit
PG = Micrologic 5.0/6.0 trip unit
3 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45,
800A: 1000A w/LTPU=0.625, 700A: 1000A w/LTPU= 0.7)
Test X/R
4.9
3.2
1.7
Note that this is a consideration for breaker fault duty rather than for
selective coordination.
Document Number
0100DB0604
Table IB
I-Line/NF Panelboard Selective Coordination At 480Y/277V
0.01s 1000s
FEEDER SIZE /
UPSTREAM (I-LINE)
PANELBOARD CIRCUIT
BREAKER SIZE
(A)
REQUIRED
DOWNSTREAM (NF)
PANELBOARD
AMPACITY
(A)
100
125
125
125
150
250
175
250
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
18
35
65
18
35
65
18
35
65
18
35
65
18
200
250
30
35
65
18
225
250
30
35
65
18
250
250
30
35
300
300
65
18
35
65
18
400
400
30
35
450
600
500
600
600
600
65
18
35
65
18
35
65
18
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
PG
PG
PJ
PG
PG
PJ
PG
PG
PJ
PG
PG
PJ
PG
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
PG
LH-MC
LH-MC
LH-MC
PJ
PG
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
PG
LH-MC
LH-MC
LH-MC
LH-MC
PJ
LA-MC
LA-MC
LA-MC
PG
LA-MC
LA-MC
LA-MC
LH-MC
LH-MC
LH-MC
PG
PJ
PG4
PG4
PJ4
LA-MC
LA-MC
PG
LA-MC
LA-MC
LH-MC
LH-MC
PG
PJ
PG4
PG4
PJ4
PG4
PG4
PJ4
PG (ET1.0)2, PG2
DOWNSTREAM (NF)
PANELBOARD BRANCH
CIRCUIT BREAKER
TYPE
ED
EG
EJ
ED
EG
EJ
ED
EG
EJ
ED
EG
EJ
ED
ED
ED
ED
EG
EG
EG
EG
EG
EG
EG
EJ
ED
ED
ED
ED
ED
EG
EG
EG
EG
EG
EG
EG
EG
EG
EJ
ED
ED
ED
ED
EG
EG
EG
EG
EG
EG
EG
EJ
ED
EG
EJ
ED
ED
ED
EG
EG
EG
EG
EG
EJ
ED
EG
EJ
ED
EG
EJ
ED
MAXIMUM AVAILABLE
FAULT CURRENT AT
DOWNSTREAM (NF)
PANELBOARD
(kA RMS Sym.)1,3
18
35
65
18
35
65
18
35
65
18
35
65
18
18
10
6
18
10
6
35
18
10
6
65
18
18
14
8
7
18
14
8
7
35
18
14
8
7
65
18
10
8
18
18
10
8
18
10
8
35
65
18
35
65
18
6
18
18
6
18
6
35
65
18
21.6
9
18
21.6
9
18
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
50
50
50
50
50
50
70
70
70
70
70
70
80
15
20
100
15
20
100
80
15
20
100
80
110
15
20
30
100
15
20
30
100
110
15
20
30
100
110
30
40
100
125
30
40
100
30
40
100
125
125
125
125
125
100
125
125
100
125
100
125
125
125
125
125
125
125
125
125
125
Document Number
0100DB0604
FEEDER SIZE /
UPSTREAM (I-LINE)
PANELBOARD CIRCUIT
BREAKER SIZE
(A)
REQUIRED
DOWNSTREAM (NF)
PANELBOARD
AMPACITY
(A)
700
800
800
800
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
35
65
18
35
65
18
35
65
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
DOWNSTREAM (NF)
PANELBOARD BRANCH
CIRCUIT BREAKER
TYPE
PG (ET1.0)2, PG2
PJ (ET1.0)2, PJ2
PG2,4
PG2,4
PJ2,4
PG (ET1.0)2, PG2
PG (ET1.0)2, PG2
PJ (ET1.0)2, PJ2
EG
EJ
ED
EG
EJ
ED
EG
EJ
MAXIMUM AVAILABLE
FAULT CURRENT AT
DOWNSTREAM (NF)
PANELBOARD
(kA RMS Sym.)1,3
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
35
65
18
21.6
9
18
21.6
9
125
125
125
125
125
125
125
125
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See the explanatory
note below for additional information
2 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range
PG (ET1.0) = ET1.0 trip unit
PG = Micrologic 5.0/6.0 trip unit
3 Values in red are taken from data bulletin 0100DB0501; all other values in this column generated via TCC comparison
4 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45, 800A: 1000A
w/LTPU=0.625, 700A: 1000A w/LTPU= 0.7)
Test X/R
4.9
3.2
1.7
Note that this is a consideration for breaker fault duty rather than for
selective coordination.
Document Number
0100DB0604
Table IIA
I-Line/NF Panelboard Selective Coordination At 208Y/120V
0.1s 1000s
FEEDER SIZE /
UPSTREAM (I-LINE)
PANELBOARD CIRCUIT
BREAKER SIZE
(A)
REQUIRED
DOWNSTREAM (NF)
PANELBOARD
AMPACITY
(A)
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
25
100
125
65
100
110
125
125
125
25
65
100
25
42
65
100
25
42
150
250
65
100
25
175
250
42
65
100
25
42
200
250
65
100
25
42
225
250
65
100
25
42
250
250
65
100
300
400
25
42
65
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
DOWNSTREAM (NF)
PANELBOARD BRANCH
CIRCUIT BREAKER TYPE
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
FA2, HD, LX
PG
FH, HG, LX
PG
HJ, LX
PJ
HD
HG
HJ
HD, LA, LX
PG
LA
HG, LH, LX
PG
HJ, LX
PJ
HD
JD, LA
LX
PG
LA
HG
JG, LH
LX
PG
HJ
JJ
LX
PJ
JD, LA
LX, PG
LA
JG, LH
LX, PG
JJ
LX, PJ
JD, LA, LX,
PG
LA-MC
LA
LA-MC
JG, LH, LX
PG
LH-MC
JJ, LX
PJ
JD, LA, LX
PG
LA-MC
LA
LA-MC
JG, LH, LX
PG
LH-MC
JJ, LX
PJ
JD, LA
LA-MC
LX, PG
LA
LA-MC
JG, LH
LH-MC
LX, PG
JJ
LX, PJ
LA, MG, LX, PG5
LA
LH, MG, LX, PG5
ED
ED
EG3
EG3
EJ3
EJ3
ED
EG3
EJ3
ED
ED
EG3
EG3
EG3
EJ3
EJ3
ED
ED
ED
ED
EG3
EG3
EG3
EG3
EG3
EJ3
EJ3
EJ3
EJ3
ED
ED
EG3
EG3
EG3
EJ3
EJ3
ED
ED
ED
EG3
EG3
EG3
EG3
EG3
EJ3
EJ3
ED
ED
ED
EG3
EG3
EG3
EG3
EG3
EJ3
EJ3
ED
ED
ED
EG3
EG3
EG3
EG3
EG3
EJ3
EJ3
ED
EG3
EG3
30
50
30
50
30
50
30
30
30
30
50
30
30
50
30
50
30
35
40
70
35
30
35
40
70
30
35
40
70
40
70
40
40
70
40
70
70
80
125
70
125
70
80
125
70
80
70
110
125
70
125
70
110
125
70
110
70
125
125
70
125
70
125
125
70
125
125
125
125
Document Number
0100DB0604
FEEDER SIZE /
UPSTREAM (I-LINE)
PANELBOARD CIRCUIT
BREAKER SIZE
(A)
REQUIRED
DOWNSTREAM (NF)
PANELBOARD
AMPACITY
(A)
350
400
400
400
450
600
500
600
600
600
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
100
25
42
65
100
25
42
65
100
25
65
100
25
65
100
25
65
100
700
800
800
800
25
65
100
25
65
100
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
DOWNSTREAM (NF)
PANELBOARD BRANCH
CIRCUIT BREAKER
TYPE
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
EJ3
ED
EG3
EG3
EJ3
ED
EG3
EG3
EJ3
ED
EG3
EJ3
ED
EG3
EJ3
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
ED
125
3
EG
125
125
125
125
125
125
125
125
EJ
ED
EG3
EJ3
ED
EG3
EJ3
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See
the explanatory note below for additional information
2 480V-rated
3 2 Pole or 3 Pole 15 125A only. 1 Pole is available from 15 70A and has an AIR of 35kA for EG, 65kA for EJ
4 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range
PG (ET1.0) = ET1.0 trip unit
PG = Micrologic 5.0/6.0 trip unit
5 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45,
800A: 1000A w/LTPU=0.625, 700A: 1000A w/LTPU= 0.7)
Test X/R
4.9
3.2
1.7
Note that this is a consideration for breaker fault duty rather than for
selective coordination.
Document Number
0100DB0604
TABLE IIB
I-Line/NF Panelboard Selective Coordination At 208Y/120V
0.01s 1000s
FEEDER SIZE /
UPSTREAM (I-LINE)
PANELBOARD CIRCUIT
BREAKER SIZE
(A)
REQUIRED
DOWNSTREAM (NF)
PANELBOARD
AMPACITY
(A)
100
125
125
125
150
250
175
250
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
25
65
100
25
65
100
25
65
100
25
65
100
25
200
250
42
65
100
25
42
225
250
65
100
25
250
250
42
65
300
300
100
25
65
100
25
42
400
400
65
10
450
600
500
600
600
600
100
25
65
100
25
65
100
25
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
PG
PG
PJ
PG
PG
PJ
PG
PG
PJ
PG
PG
PJ
PG
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
PG
LH-MC
LH-MC
LH-MC
PJ
PG
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
PG
LH-MC
LH-MC
LH-MC
LH-MC
PJ
LA-MC
LA-MC
LA-MC
PG
LA-MC
LA-MC
LA-MC
LH-MC
LH-MC
LH-MC
PG
PJ
PG6
PG6
PJ6
LA-MC
LA-MC
PG
LA-MC
LA-MC
LH-MC
LH-MC
PG
PJ
PG6
PG6
PJ6
PG6
PG6
PJ6
PG (ET1.0)4, PG4
DOWNSTREAM (NF)
PANELBOARD BRANCH
CIRCUIT BREAKER TYPE
ED
EG3
EJ3
ED
EG3
EJ3
ED
EG3
EJ3
ED
EG3
EJ3
ED
ED
ED
ED
EG3
EG3
EG3
EG3
EG3
EG3
EG3
EJ3
ED
ED
ED
ED
ED
EG3
EG3
EG3
EG3
EG3
EG3
EG3
EG3
EG3
EJ3
ED
ED
ED
ED
EG3
EG3
EG3
EG3
EG3
EG3
EG3
EJ3
ED
EG3
EJ3
ED
ED
ED
EG3
EG3
EG3
EG3
EG3
EJ3
ED
EG3
EJ3
ED
EG3
EJ3
ED
MAXIMUM AVAILABLE
FAULT CURRENT AT
DOWNSTREAM (NF)
PANELBOARD
(kA RMS Sym.)1,5
21.6
65
100
21.6
65
100
21.6
65
100
21.6
65
100
21.6
18
10
6
18
10
6
65
18
10
6
100
21.6
18
14
8
7
18
14
8
7
65
18
14
8
7
100
18
10
8
21.6
18
10
8
18
10
8
65
100
21.6
65
100
18
6
21.6
18
6
18
6
65
100
21.6
21.6
9
21.6
65
100
21.6
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
50
50
50
50
50
50
70
70
70
70
70
70
80
15
20
100
15
20
100
80
15
20
100
80
110
15
20
30
100
15
20
30
100
110
15
20
30
100
110
30
40
100
125
30
40
100
30
40
100
125
125
125
125
125
100
125
125
100
125
100
125
125
125
125
125
125
125
125
125
125
Document Number
0100DB0604
FEEDER SIZE /
UPSTREAM (I-LINE)
PANELBOARD CIRCUIT
BREAKER SIZE
(A)
REQUIRED
DOWNSTREAM (NF)
PANELBOARD
AMPACITY
(A)
700
800
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
65
100
25
65
100
800
800
25
65
100
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
PG (ET1.0)4, PG4
PJ (ET1.0)4, PJ4
PG4 6
PG4,6
MG
PJ4,6
MJ
PG (ET1.0)4, PG4
MG, PG (ET1.0)4, PG4
MJ, PJ (ET1.0)4, PJ4
DOWNSTREAM (NF)
PANELBOARD BRANCH
CIRCUIT BREAKER
TYPE
MAXIMUM AVAILABLE
FAULT CURRENT AT
DOWNSTREAM (NF)
PANELBOARD
(kA RMS Sym.)1,5
EG3
EJ3
ED
EG3
EG3
EJ3
EJ3
ED
EG3
EJ3
65
100
21.6
21.6
65
9
100
21.6
65
100
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
125
125
125
125
125
125
125
125
125
125
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See the explanatory notes
below for additional information
2 480V-rated
3 2 Pole or 3 Pole 15 125A only. 1 Pole is available from 15 70A and has an AIR of 35kA for EG, 65kA for EJ
4 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range
PG (ET1.0) = ET1.0 trip unit
PG = Micrologic 5.0/6.0 trip unit
5 Values in red are taken from data bulletin 0100DB0501; all other values in this column generated via TCC comparison
6 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45,
800A: 1000A w/LTPU=0.625, 700A: 1000A w/LTPU= 0.7)
Test X/R
4.9
3.2
1.7
Note that this is a consideration for breaker fault duty rather than for
selective coordination.
11
Document Number
0100DB0604
TABLE IIIA
I-Line/NQOD Panelboard Selective Coordination At 208Y/120V
0.1s 1000s
FEEDER SIZE /
UPSTREAM (I-LINE)
PANELBOARD CIRCUIT
BREAKER SIZE
(A)
REQUIRED
DOWNSTREAM (NF)
PANELBOARD
AMPACITY
(A)
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
10
100
100
22
65
110
225
10
22
65
10
125
225
22
42
65
10
150
225
22
42
65
10
175
225
22
42
65
10
200
225
22
42
65
10
225
225
22
42
65
10
250
400
22
42
65
10
300
350
12
400
22
400
42
65
10
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
DOWNSTREAM (NF)
PANELBOARD
BRANCH CIRCUIT
BREAKER TYPE
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
HD
FA, LX
PG
HD
FA2, LX
PG
HG
FH, LX
PG
HD
HD
HG
HD, LA
LX
PG
HD, LA
LX
PG
LA
HG, LH
LX, PG
HD
JD, LA, LX, PG
HD
JD, LA
LX
PG
LA
HG
JG, LH, LX, PG
JD, LA, LX, PG
JD, LA
LX
PG
LA
JG, LH, LX, PG
JD, LA,
LX
LA-MC, PG
JD, LA, LX,
PG
LA-MC
LA, LA-MC
JG, LH, LH-MC, LX, PG
JD, LA, LX, PG
LA-MC
JD, LA
LX
PG
LA-MC
LA, LA-MC
JG, LH, LH-MC, LX, PG
JD, LA, LX, PG
LA-MC
JD, LA
LX
PG
LA-MC
LA, LA-MC
JG, LH, LH-MC, LX, PG
LA, MG, LX
PG5
LA
MG, LX
PG5
LA
LH, MG, LX, PG5
LA
QO
QO
QO
QO-VH
QO-VH
QO-VH
QH
QH
QH
QO
QO-VH
QH
QO
QO
QO
QO-VH
QO-VH
QO-VH
QH
QH
QH
QO
QO
QO-VH
QO-VH
QO-VH
QO-VH
QH
QH
QH
QO
QO-VH
QO-VH
QO-VH
QH
QH
QO
QO
QO
QO-VH
QO-VH
QO-VH
QH
QH
QO
QO
QO-VH
QO-VH
QO-VH
QO-VH
QH
QH
QO
QO
QO-VH
QO-VH
QO-VH
QO-VH
QH
QH
QO
QO
QO-VH
QO-VH
QO-VH
QH
QH
QO
20
25
40
20
25
403
20
25
30
25
25
25
25
40
70
25
30
603
25
25
30
25
70
25
30
403
703
30
25
30
70
403
503
703
30
30
70
806
1006
503
803
1003
30
30
1006
1257
503
603
803
1253
30
30
1006
1257
603
803
1103
1503
30
30
1006
1257
903
1003
1253
30
30
1006
Document Number
0100DB0604
FEEDER SIZE /
UPSTREAM (I-LINE)
PANELBOARD CIRCUIT
BREAKER SIZE
(A)
REQUIRED
DOWNSTREAM (NQOD)
PANELBOARD
AMPACITY
(A)
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
350
400
400
400
450
600
500
600
22
42
65
10
22
42
65
10
22
65
10
22
65
10
600
600
22
65
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
DOWNSTREAM (NQOD)
PANELBOARD
BRANCH CIRCUIT
BREAKER TYPE
MG, LX
LA, MG, LX
LA
LH, MG, LX
LA, LA-MC, MG, LX, PG
LA, LA-MC, MG, LX, PG
LA, LA-MC
LH, LH-MC, MG, LX, PG
LC, MG, LX, PG5
LC, MG, LX, PG5
LC, MG, LX, PG5
LC, MG, LX, PG5
LC, MG, LX, PG5
LC, MG, LX, PG5
LC, MG, LX, PG
(ET1.0)4, PG4
LC, MG, LX, PG
(ET1.0)4, PG4
LC, MG, LX, PG
(ET1.0)4, PG4
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
QO
QO-VH
QH
QH
QO
QO-VH
QH
QH
QO
QO-VH
QH
QO
QO-VH
QH
1257
1503
30
30
1257
1503
30
30
1257
1503
30
1257
1503
30
QO
1257
QO-VH
1503
QH
30
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See
the explanatory note below for additional information
2 480V-rated
3 2 Pole or 3 Pole only. QO-VH 1 Pole is available up to 30A (and coordinates up to 30A)
4 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range
PG (ET1.0) = ET1.0 trip unit
PG = Micrologic 5.0/6.0 trip unit
5 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45,
800A: 1000A w/LTPU=0.625)
6 2 Pole or 3 Pole only. QO 1 Pole is available up to 70A (and coordinates up to 70A)
7 2p only. QO 1P is available up to 70A (and coordinates up to 70A), QO 3 Pole is available up to 100A (and coordinates
up to 100A)
Test X/R
4.9
3.2
1.7
Note that this is a consideration for breaker fault duty rather than for
selective coordination.
13
Document Number
0100DB0604
Table IIIB
I-Line/NQOD Panelboard Selective Coordination At 208Y/120V
0.01s 1000s
FEEDER SIZE /
REQUIRED
UPSTREAM (I-LINE)
DOWNSTREAM (NQOD)
PANELBOARD CIRCUIT
PANELBOARD AMPACITY
BREAKER SIZE
(A)
(A)
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
10
100
100
22
65
110
225
125
225
10
22
65
10
22
65
10
150
225
22
65
10
22
175
225
65
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
DOWNSTREAM (NQOD)
PANELBOARD
BRANCH CIRCUIT
BREAKER TYPE
HD
PG
HD
PG
PJ
HG
FH
PG
HD
HD
HG
HD
PG
HD
LA
PG
PJ
HG
LH
PG
HD
JD
PG
HD
JD
LA
PG
PJ
HG
JG
LH
PG
JD
PG
JD
LA
PG
PJ
JG
LH
PG
JD
LA-MC
LA-MC
LA-MC
QO
QO
QO-VH
QO-VH
QO-VH
QH
QH
QH
QO
QO-VH
QH
QO
QO
QO-VH
QO-VH
QO-VH
QO-VH
QH
QH
QH
QO
QO
QO
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QH
QH
QH
QH
QO
QO
QO-VH
QO-VH
QO-VH
QO-VH
QH
QH
QH
QO
QO
QO
QO
LA-MC
LA-MC
LA-MC
LA-MC
PG
JD
LA
PG
PJ
LA-MC
LA-MC
LA-MC
QO
QO
QO
QO
QO
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
JG
LH
LH-MC
PG
JD
QO-VH
QO-VH
QO-VH
QO-VH
QH
QH
QH
QH
QH
QO
10
200
225
22
42
65
225
14
225
10
MAXIMUM AVAILABLE
FAULT CURRENT AT
DOWNSTREAM (NQOD)
PANELBOARD1.8
1.3
10
1.3
21.6
22
1.3
0.9
65
1.3
1.3
1.3
1.3
10
1.3
3.2 (2P ONLY)
21.6
22
1.3
65 (1P), 3.2 (2P, 3P)
65
1.3
2.3
10
1.3
2.3
3.2 (2P ONLY)
21.6
22
1.3
2.4
65 (1P), 3.2 (2P, 3P)
65
2.3
10
2.3
3.2 (2P ONLY)
21.6
22
2.4
65 (1P), 3.2 (2P, 3P)
65
2.3
18 (1P, 2P), 16 (3P)
18 (1P, 2P), 10 (3P)
7 (1P), 10 (2P), 6.5
(3P)
7 (1P, 2P), 6 (3P)
6 (1P, 2P), 5.5 (3P)
5 (1P, 3P), 6 (2P)
5
10
2.3
3.2 (2P ONLY)
21.6
22
22 (1P, 2P), 16 (3P)
22 (1P, 2P), 10 (3P)
7 (1P), 10 (2P), 6.5
(3P)
7 (2P), 6 (3P)
6 (2P), 5.5 (3P)
6 (2P), 5 (3P)
5
3.4
2.4
65 (1P), 3.2 (2P, 3P)
3.4
65
2.3
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
20
40
20
403
403
20
25
30
25
25
25
25
70
25
25
603
603
25
25
30
25
70
70
25
30
30
703
703
25
30
30
30
70
70
403
403
703
703
30
30
30
70
15
20
30
40
50
70
1006
1006
503
503
803
803
15
20
30
403
503
703
1003
30
30
30
30
30
1006
Document Number
0100DB0604
FEEDER SIZE /
REQUIRED
UPSTREAM (I-LINE)
DOWNSTREAM (NQOD)
PANELBOARD CIRCUIT
PANELBOARD AMPACITY
BREAKER SIZE
(A)
(A)
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
10
225
225
22
42
65
10
250
400
22
42
65
10
22
300
400
65
22
350
400
65
400
400
10
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
DOWNSTREAM (NQOD)
PANELBOARD
BRANCH CIRCUIT
BREAKER TYPE
PG
LA-MC
LA-MC
LA-MC
QO
QO
QO
QO
LA-MC
LA-MC
LA-MC
QO
QO
QO
LA-MC
QO
LA-MC
LA-MC
LA-MC
JD
LA
PG
PJ
LA-MC
LA-MC
LA-MC
QO
QO
QO
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
JG
LH
LH-MC
PG
JD
PG
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
JD
LA
PG
PJ
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
LA-MC
JG
LH
LH-MC
PG
PG5
LA
MG
PG5
LH
MG
PG5
LA
MG
LH
MG
LA-MC
LA-MC
LA-MC
PG
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QH
QH
QH
QH
QH
QO
QO
QO
QO
QO
QO
QO
QO
QO
QO
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QH
QH
QH
QH
QH
QO
QO-VH
QO-VH
QO-VH
QH
QH
QH
QO-VH
QO-VH
QH
QH
QO
QO
QO
QO
MAXIMUM AVAILABLE
FAULT CURRENT AT
DOWNSTREAM (NQOD)
1,8
PANELBOARD
10
18
18 (1P, 2P), 16 (3P)
11 (1P), 18 (2P), 8
(3P)
10 (1P, 2P), 7.5 (3P)
10 (1P, 2P), 7 (3P)
8 (1P), 10 (2P), 6.5
(3P)
7 (1P), 10 (2P), 6
(3P)
8 (2P), 6 (3P)
6
3.825
2.3
3.2 (2P ONLY)
21.6
22
22 (1P, 2P), 18 (3P)
22 (1P, 2P), 16 (3P)
11 (1P), 22 (2P), 8
(3P)
18 (2P), 7.5 (3P)
18 (2P), 7 (3P)
13 (2P), 6.5 (3P)
10 (2P), 6 (3P)
8 (2P), 6 (3P)
6
3.825
3.825
2.4
65 (1P), 3.2 (2P, 3P)
3.825
65
2.3
10
18
18 (1P, 2P), 14 (3P)
10
10 (1P, 2P), 9 (3P)
10 (1P, 2P), 8 (3P)
10 (1P, 2P), 7.5 (3P)
10 (2P), 7.5 (3P)
4.25
2.3
3.2 (2P ONLY)
21.6
22
22 (1P, 2P), 18 (3P)
22 (1P, 2P), 14 (3P)
18 (2P), 10 (3P)
18 (2P), 9 (3P)
13 (2P), 8 (3P)
11 (2P), 7.5 (3P)
10 (2P), 7.5 (3P)
4.25
4.25
2.4
65 (1P), 3.2 (2P, 3P)
4.25
65
10
3.2 (2P ONLY)
3.6 (3P ONLY)
21.6
65 (1P), 3.2 (2P, 3P)
65 (1P), 3.6 (2P, 3P)
65
3.2 (2P ONLY)
3.6 (3P ONLY)
65 (1P), 3.2 (2P, 3P)
65 (1P), 3.6 (2P, 3P)
18
10
6
10
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
1006
15
20
30
40
50
60
70
806
1006
1257
503
503
803
803
15
20
30
403
503
603
703
803
1003
1253
30
30
30
30
30
1006
1006
20
30
40
50
60
70
1006
1257
603
603
1103
1103
20
30
403
503
603
803
1003
1503
30
30
30
30
30
1257
903
1003
1253
30
30
30
1503
1503
30
30
30
1006
1257
1257
15
Document Number
0100DB0604
FEEDER SIZE /
REQUIRED
UPSTREAM (I-LINE)
DOWNSTREAM (NQOD)
PANELBOARD CIRCUIT
PANELBOARD AMPACITY
BREAKER SIZE
(A)
(A)
MAXIMUM AVAILABLE
FAULT CURRENT AT
UPSTREAM (I-LINE)
PANELBOARD
(kA RMS Sym.)1
22
400
400
42
65
10
22
450
600
65
10
22
500
500
65
10
22
600
600
65
UPSTREAM (I-LINE)
PANELBOARD
FEEDER CIRCUIT
BREAKER TYPE
LA
LA-MC
LA-MC
LA-MC
MG
PG
LA-MC
LH
LH-MC
MG
PG
PG5
MG
PG5
MG
PG5
PG5
MG
PG5
MG
PG5
PG (ET1.0)4, PG4
MG
PG (ET1.0)4, PG4
MG
PG (ET1.0)4, PG4
MAXIMUM AVAILABLE
FAULT CURRENT AT
DOWNSTREAM (NQOD)
PANELBOARD BRANCH DOWNSTREAM (NQOD)
PANELBOARD
CIRCUIT BREAKER TYPE
(kA RMS Sym.)1,8
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QO-VH
QH
QH
QH
QH
QH
QO
QO-VH
QO-VH
QH
QH
QO
QO-VH
QO-VH
QH
QH
QO
QO-VH
QO-VH
QH
QH
LARGEST POSSIBLE
BRANCH CIRCUIT
BREAKER
(A)
1503
30
1003
1503
1503
1503
30
30
30
30
30
1257
1503
1503
30
30
1257
1503
1503
30
30
1257
1503
1503
30
30
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See the explanatory note
below for additional information
2 480V-rated
3 2 Pole or 3 Pole only. QO-VH 1 Pole is available up to 30A (and coordinates up to 30A)
4 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range
PG (ET1.0) = ET1.0 trip unit
PG = Micrologic 5.0/6.0 trip unit
5 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45,
800A: 1000A w/LTPU=0.625)
6 2 Pole or 3 Pole only. QO 1 Pole is available up to 70A (and coordinates up to 70A)
7 2 Pole only. QO 1 Pole is available up to 70A (and coordinates up to 70A), QO 3 Pole is available up to 100A (and coordinates up to 100A)
8 Values in red are taken from data bulletin 0100DB0501; all other values in this column generated via TCC comparison
Test X/R
4.9
3.2
1.7
Note that this is a consideration for breaker fault duty rather than for
selective coordination.
16
0600DB0601
2/2007
Cedar Rapids, IA, USA
Data Bulletin
A Comparison of Circuit Breakers and Fuses for
Low-Voltage Applications
Tony Parsons, PhD, P.E.,
Square D / Schneider Electric Power Systems Engineering
I. Introduction
Recent claims by fuse manufacturers regarding the arc-flash and simplifiedcoordination benefits of fuses do not tell the entire story regarding which
type of device is best for a given power system. In reality, not only does
the wide range of available circuit breaker types allow them to be
successfully used on nearly any kind of power system, they can be applied
so as to provide selective coordination, arc-flash protection, advanced
monitoring and control features, all in a renewable device. This paper gives
a feature-by-feature comparison of the merits of circuit breakers vs. fuses,
discussing the relative merits of fuses and circuit breakers in each section.
While both circuit breakers and fuses are available for application in
systems that operate at higher voltage levels, the focus of this guide is on
low-voltage systems operating at 600 V or below.
Article 240 of the National Electrical Code (NEC) [1] provides the basic
requirements for overcurrent (i.e., overload, short-circuit, and/or ground
fault) protection in a power system. Special requirements for overcurrent
protection of certain types of equipment are also contained in other
articlesfor example, details on protection requirements for motors and
motor circuits are given in Article 430, while transformer protection
requirements are given in Article 450.
The NEC defines the two basic types of Overcurrent Protective Devices
(OCPDs):
fuseAn overcurrent protective device with a circuit-opening fusible
part that is heated and severed by the passage of overcurrent through it.
circuit breakerA device designed to open and close a circuit by
nonautomatic means and to open the circuit automatically on a
predetermined overcurrent without damage to itself when properly
applied within its rating.
The NEC also requires that circuits be provided with a disconnecting
means, defined as a device, or group of devices, or other means by which
the conductors of a circuit can be disconnected from their source of supply.
Since fuses are designed to open only when subjected to an overcurrent,
they generally are applied in conjunction with a separate disconnecting
means (NEC 240.40 requires this in many situations), typically some form of
a disconnect switch. Since circuit breakers are designed to open and close
under manual operation as well as in response to an overcurrent, a
separate disconnecting means is not required.
Both fuses and circuit breakers are available in a variety of sizes, ratings,
and with differing features and characteristics that allow the designer of an
electrical system to choose a device that is appropriate for the system under
consideration.
0600DB0601
2/2007
As discussed above, both circuit breakers and fuses meet the basic NEC
requirements for overcurrent protection of electric power distribution
systems and equipment. Any type of OCPD must be sized and installed
correctly after taking all derating factors and other considerations into
account. Particularly for overloads and phase faults, both circuit breakers
and fuses provide excellent protection and either is suitable for most
applications. A bit more consideration is warranted for some other aspects
of system protection, as discussed in the remainder of this section.
A. Ground-Fault Protection
Conventional wisdom states that the most common type of fault in a power
system (by far) is a single-phase-to-ground fault. On solidly-grounded power
systems, the available ground-fault current level can be significant. In some
situations, ground fault current levels that are even higher than the
maximum three-phase fault current level are theoretically possible.
However, many ground faults produce only relatively low levels of fault
current due to impedance in the fault path (due to arcing or to some other
0600DB0601
2/2007
source of impedance from phase to ground). While such faults can cause
significant equipment and facility damage if not cleared from the system
quickly, phase overcurrent protective devices may not respond quickly to
the lower fault levelsif they detect the fault at all. For example, an 800 A
ground fault might simply appear as an unbalanced load to a 4000 A fuse or
circuit breaker not equipped with ground-fault protection. Because of this,
NEC 230.95 requires supplementary ground-fault protection on service
disconnects rated 1000 A or more on solidly-grounded, wye systems
operating at more than 150 V to ground but not more than 600 V phase-tophase (e.g., 277/480 V systems). The NEC also defines special ground-fault
protection requirements for health care facilities and emergency systems.
See the appropriate NEC articles for more details.
Circuit breakers can be equipped with integral ground-fault protection
through addition of either electronic trip units that act as protective relaying
to detect the ground fault and initiate a trip, or through addition of add-on
ground-fault protection modules. Ground-fault trip units typically use the
current sensors internal to the circuit breaker to detect the ground fault
condition, though an external neutral sensor is normally required to monitor
current flowing on the neutral conductor in a 4-wire system. If desired,
external relaying and current transformers (CTs) can also be used for
ground-fault detection provided that the circuit breaker is equipped with a
shunt trip accessory that can be actuated by the external relay.
By themselves, fuses cannot provide ground-fault protection except for
relatively high-level ground faults. When ground-fault protection is required
in a fusible system, the disconnecting means (usually a switch, sometimes a
contactor) must be capable of tripping automatically, and external relaying
and a zero-sequence CT or set of residually-connected phase CTs must be
installed to detect the ground faults and send the trip signal to the
disconnecting means.
While either system can function well if installed properly, extra care must
be taken with a fusible system (or circuit breaker-based system with
external ground relaying) to ensure that all external sensors are oriented
correctly and that all sensor and relay wiring is installed correctly.
Performance testing of the ground-fault system, as required in NEC
230.95(C) when the system is installed, should allow for identification of any
installation issues.
0600DB0601
2/2007
Circuit breakers of all types are also available with interrupting ratings up to
200 kA. In the not-too-distant past, fused circuit breakers were required to
achieve the 200 kA interrupting ratings, but modern circuit breakers can
achieve this rating without fuses. Circuit breakers with lower ratings are also
available, typically at a lower cost. Circuit breakers have single-pole
interrupting ratings that are adequate for installation on the majority of power
systems, though special consideration may be required in some cases. See
[3] for additional information.
C. Motor Protection
Size motor circuit fuses closer to the full-load current rating of the motor.
One fuse manufacturer recommends sizing dual-element, time-delay fuses
at 100125% of the motor's actual load level (not the nameplate rating) to
provide better levels of protection against damage resulting from singlephasing [4]. Note that this does not eliminate the possibility of single-phasing
occurring, and could increase the possibility of nuisance fuse operation on
sustained overloads. In applications where loading on a particular motor
varies widely, or in new facilities where actual current draw of a motor may
not be known, sizing the fuses properly could be a challenge. Application of
external relaying at high-value loads may still be warranted.
2007 Schneider Electric All Rights Reserved
0600DB0601
2/2007
D. Component Protection
E. Arc-Flash Protection
0600DB0601
2/2007
With the increased interest in arc-flash hazards in recent years, the ability of
OCPDs to provide protection against arcing faults has received much
interest. The potential severity of an arc-flash event at a given location in a
power system depends primarily on the available fault current, the distance
of the worker away from the source of the arc, and the time that it takes the
upstream OCPD to clear the arcing fault from the system. In many cases,
little can be done about the first two factorsthe available fault current
levels depend on utility system contribution, transformer impedance values,
etc.; while the working distance is limited by the fact that a worker working
on a piece of equipment must, in most cases, be physically close to the
equipment.
Proper selection and application of OCPDs can have a great deal of impact
on the fault clearing time. Clearing the fault more quickly can provide a great
deal of protection for workers, as the available incident energy is directly
proportional to the duration of the arcing faulti.e., the incident energy can
be cut in half if the fault can be cleared twice as quickly. Equations
appearing in IEEE Standard 1584-2002 [5] provide the present state-ofthe-art methods for determining the arc-flash hazard levels in a system and
for evaluating the impact of potential arc-flash mitigation options.
For low-voltage systems, which OCPDs provide the best protection against
arc flash?
Circuit breakers, with adjustable trip units that can be set to strike a
balance between providing selective coordination and arc-flash
protection?
Current-limiting fuses, which can clear high-level faults very quickly and
minimize damage to both equipment and personnel?
The IEEE 1584 standard contains three basic calculation models that can
be used to determine arc-flash hazard levelsan empirically-derived,
general model; simplified equations based on testing of current-limiting
(class RK-1 and class L) low-voltage fuses; and simplified equations based
on calculations performed on typical low-voltage circuit breakers. The
general equations require information on available fault current levels in the
system as well as knowledge of the trip characteristics of OCPDs in the
circuit, but can provide accurate results for any type of OCPD and for a wide
range of system conditions. The simplified circuit breaker and fuse
equations require little to no knowledge of actual device trip characteristics,
but differences in the way these equations were developed mean that they
should not be used to conduct a direct apples-to-apples comparison of
specific protective devices.
2007 Schneider Electric All Rights Reserved
0600DB0601
2/2007
As discussed above, the simplified fuse equations are based on field testing
of specific types of fuses, the simplified circuit breaker equations are based
on classes of circuit breakers and on the assumption that the relevant trip
settings are maximized, and not on specific devices or actual trip settings.
The circuit breaker equations are meant to allow calculation of the worstcase arc-flash levels allowed by any example of a circuit breaker within a
given classe.g., 100400 A MCCBs. If the IEEE 1584 empirical equations
are used to calculate arc-flash levels downstream of such a circuit breaker,
the values should never be higher than (and in many cases will be well
below) those shown by the simplified circuit breaker equations. This is
particularly true when using the equations to analyze larger LVPCBsthe
simplified IEEE 1584 equations assume that the circuit breaker's
instantaneous and/or short-time pickup and delay settings are set to the
maximum levels, which can result in the calculation of very conservative
arc-flash levels if the circuit breakers are actually set differently. For
example, Figure 1 shows the incident energy levels vs. bolted fault current
values for 2000 A circuit breakers in a 480 V, solidly-grounded system.
Figure 1:
NW-LF
NW-L
LVPCB w/INST
LVPCB w/ST
120
90
60
30
0
0
20
40
60
80
100
120
The LVPCB w/ST and LVPCB w/INST curves are based on the IEEE
1584 simplified equations for low-voltage power circuit breakers with shorttime and instantaneous pickup, respectively. The NW-L and NW-LF
curves show arc-flash values based on actual devices (2000 A Masterpact
NW-L and NW-LF circuit breakers set to trip instantaneously for an arcing
fault, respectively).
As shown in the plot, the simplified equations (particularly for the LVPCB
w/ST curve) are well above the results calculated based on the actual
device characteristics. When possible, a comparison of the level of arc-flash
protection a given device can provide, should be based on actual device
characteristics, not generic equations.
0600DB0601
2/2007
400A LH
400A LC
2.0
1.6
1.2
0.8
0.4
0.0
0
20
40
60
80
100
120
0600DB0601
2/2007
Figure 3:
NW-LF
NW-H
1600L Fuse
30
25
20
15
10
5
0
0
20
40
60
80
100
120
For circuit breakers with adjustable trip settings, proper selection of setting
levels is important for both arc-flash protection and for system coordination.
The best protection will be provided when the circuit breakers can be set to
trip instantaneously. Little to no protection may be provided by a circuit
breaker when the settings are blindly set to maximum, as is sometimes
done after a nuisance trip of the device. Arc-flash studies can be
performed to determine optimum settings for circuit breakers and other
devices in a system, but even then, it may not be possible to reduce circuit
breaker settings below a certain level to provide additional arc-flash
protection if system coordination is to be maintained.
However, an adjustable circuit breaker still gives the flexibility to provide arcflash protection in such situations, if only on a temporary basis. For
example, the instantaneous pickup level of a circuit breaker feeding an MCC
can be turned down to the minimum setting when workers are present at the
MCC, then turned back up when work is complete. This could allow the
circuit breaker to trip instantaneously and provide the best possible level of
protection at the MCC when workers are present and exposed to the
hazard, while the normal setting allows for proper coordination during
normal operation. While this can provide an obvious benefit, it also has its
drawbacks, including:
0600DB0601
2/2007
Utility Transformer
Switchboard
Main
Switchboard
Feeder-A
Feeder-B
Panel-B
P
Transformer-A
S
Feeder-C
Chiller
Panel-A Main
Panel-A
Panel-C
Chiller Motor
Suppose that a foreign object produces a bus fault on the main switchboard.
The Switchboard Main circuit breaker will detect the fault, then open to clear
it from the systemand interrupt power to the entire facility in the process.
However, since there are no protective devices (not including those on the
utility system) upstream of the main circuit breaker, this device operates as
intended and coordination is not an issue. If the fault occurs at Panel-C
instead, then the Feeder-C circuit breakerand only the Feeder-C circuit
breakershould open to clear the fault. If so, then Feeder-C is said to be
selectively coordinated with both of the upstream OCPDs that would also
carry the fault current. If the switchboard main circuit breaker opens either
before or at the same time as Feeder-C, then power is unnecessarily
interrupted to other parts of the systemnamely, Panel-A, Panel-B, and the
Chiller Motorand the system is not selectively coordinated.
In some situations, even though individual devices are not coordinated, the
system may still be considered to be well-coordinated. Referring again to
Figure 4, consider a fault at Panel-A. The Feeder-A circuit breaker on the
primary side of the step-down transformer and the Panel-A Main circuit
breaker on the transformer secondary will typically not coordinate well with
each otherthat is, for a fault at the Panel-A main bus, either or both of the
panel main circuit breaker and the transformer feeder circuit breaker may
open to clear the fault. However, since the two devices are in series,
operation of either/both devices interrupts power to the exact same portion
10
0600DB0601
2/2007
In elevator circuits when more than one elevator motor is fed by a single
feeder. See NEC 620.62.
The requirements for selective coordination in emergency and legallyrequired standby systems, new in the 2005 edition of the NEC, call for each
overcurrent device to be selectively coordinated with all supply side
overcurrent protective devices.
This requirement can be problematic for system designers because it
recognizes only device coordination and not system coordination, and
because it means that special consideration must be given to circuit
breaker-based systems.
Normally, coordination between devices on a time-current plot is
demonstrated by white space on the plot between the devicesideally,
the upstream device's trip curve will appear above and to the right of the
downstream device with no overlap between the curves. This indicates that
the downstream device would trip first when both saw the same fault. Any
overlap between devices indicates an area (i.e., a range of fault currents)
where it cannot be conclusively determined, at least from examination of the
plot, which device would trip first. For circuit breakers and relays, this
graphical comparison of trip characteristics is the primary way that system
coordination is assessed.
For fuses, coordination down to 0.01 second can be assessed by a
comparison of trip curves, while fuse let-through characteristics must be
compared to verify coordination beyond this point. Alternatively, tables
produced by fuse manufacturers show minimum ampere ratios between
pairs of load-side/line-side fuses that will insure coordinationfor fuses with
a 2:1 ratio, for example, the amp rating of the line-side fuse must be at least
2X the size of the load-side fuse for them to be properly coordinated.
11
0600DB0601
2/2007
Fuse manufacturers assert that fuses are often the only type of OCPD that
can truly be coordinated over all ranges of fault current, and that the fuse
ratio tables make selective coordination of fuses a simple prospect. While
this is true in some cases, things are not always this simple. Let us return to
the example system of Figure 4. Figure 5 that shows the time-current trip
characteristics for the Feeder-A and Panel-A Main circuit breakers.
A 125 A circuit breaker feeds the 480 V primary of the 75 kVA transformer,
while a 250 A main on the 208 V panel is selected.
Figure 5:
1000
100
FDR 'A'
Time in Seconds
0.10
0.01
0.5 1
10
100
1K
10K
Current in Amperes
Figure 5 shows that the trip curves of the two circuit breakers overlap,
indicating a lack of coordination between them. If the fault current falls into
the range where the device curves overlap, it is unclear which will trip first.
However, as discussed above, since these devices are in series, system
coordination is preserved even though device coordination is not.
Unfortunately, a strict interpretation of NEC 700.27 and 701.18 does not
recognize system coordination, and so this series installation would be a
code violation if installed in an emergency or legally-required standby
system.
What if fuses were used instead? The fuse ratio tables do not address
coordination between devices operating at different voltage levels, as in this
case, so a graphical evaluation of coordination would be required. Selecting
a typical 125 A, class RK-1, 600 V fuse for the primary feeder, and a 250 A,
RK-1, 250 V fuse for the secondary main will result in overlap between the
two devices. The size of the primary fuse must be increased to 175 A for the
fuses to coordinate, at least for durations above 0.01 seconds. This still
meets the NEC requirements for transformer protection in NEC 450, but
could make coordination with upstream devices more difficult depending on
the system design.
12
0600DB0601
2/2007
Figure 6 shows the time-current characteristics of the Feeder-B and FeederC circuit breakers in Figure 4.
Figure 6:
1000
100
Time in Seconds
10
FDR 'B'
1 FDR 'C'
0.10
0.01
0.5 1
10
100
1K
10K
Current in Amperes
13
0600DB0601
2/2007
For example, see Figure 7, which shows the time-current characteristics for
two Square D thermal-magnetic circuit breakersan 800 A MJ and a
125 A EJB, both at 208 V.
Figure 7:
1000
100
800A MJ
Time in Seconds
10
125A EJB
0.10
0.01
0.5 1
10
100
1K
10K
Current in Amperes
While the curve shows mis-coordination between the circuit breakers in the
instantaneous trip region, the test results presented in Data Bulletin
0100DB0501, Short-Circuit Selective Coordination for Low Voltage Circuit
Breakers, [9] indicates that this particular combination does actually
coordinate all the way up to 100 kA, the full interrupting rating of both
devices. Not all circuit breaker combinations tested coordinated this well
and some testing remains to be completed, but the fact is that fused
systems are not the only ones that can meet the strictest NEC requirements
for selective coordination.
Selective coordination may also be enhanced through simply designing the
power system (whether fuses or circuit breakers are used) with selective
coordination in mind. As examples of the latter, situations where OCPDs are
applied in series should be avoided as should application of devices
upstream/downstream of one another that are close in size (e.g., 800 A
panelboard with 600 A circuit breaker feeding a sub-panel), neither of which
lends itself to easy selective coordination between those devices. See Data
Bulletin 0100DB0403, Enhancing Short Circuit Selective Coordination with
Low Voltage Circuit Breakers [10] and [11] for additional discussion of
selective coordination in circuit breaker systems.
14
0600DB0601
2/2007
V. Reliability
VI. Rerating
15
VII. Renewability
0600DB0601
2/2007
Fuses clear faults from the system by virtue of the melting of the fusible
element. Once that element has melted and current can no longer pass
through the fuse, the fault is removed from the system. This melting is a
one-way processthe fusible link can no longer carry current and must be
replaced. For non-renewable fuseson low-voltage systems, this
encompasses all but certain types of Class H fusesthis means that the old
fuse cartridge must be removed from the fuseholder and a new one installed
before the circuit can be re-energized. Even for renewable fuses, the fuse
link itself must be replaced. Stocking spare fuses can help keep potential
system downtime to a minimum, but can mean that a substantial inventory
of spare fuses must be maintained.
A circuit breaker, on the other hand, clears faults from the system through
opening of a set of contacts. As long as the circuit breaker does not sustain
damage in the process of clearing the overcurrent, the contacts can be reclosed and the circuit re-energized by manually closing the circuit breaker. A
circuit breaker should always be inspected after a high fault, and testing
may also be wiseparticularly if any damage or stress is seen when the
circuit breaker is inspectedto ensure that the device will function properly.
In many cases, and particularly if the circuit breaker is properly applied
within its ratings, the circuit can be re-energized after only minimal
downtime.
Fuse manufacturers have argued that the non-renewability of fuses is
actually an advantage over circuit breakers in some situations. OSHA
regulations state that:
After a circuit is de-energized by a circuit protective device, the circuit
may not be manually re-energized until it has been determined that the
equipment and circuit can be safely energized. The repetitive manual
reclosing of circuit breakers or reenergizing circuits through replaced
fuses is prohibited.
NOTE: When it can be determined from the design of the circuit and the
overcurrent devices involved that the automatic operation of a device
was caused by an overload rather than a fault condition, no examination
of the circuit or connected equipment is needed before the circuit is reenergized. (OSHA 1910.334(b)(2))
The argument is that since fuses must be replaced, the temptation for a
worker to simply reset a circuit breaker and re-energize the circuit (thereby
possibly violating OSHA regulations) is removed. Realistically, though, a
worker who is willing to bypass OSHA regulations and proper work practices
in order to quickly get a circuit back in service is just as likely to do this with
fused circuits as with circuits protected by circuit breakers. In the real
world, for better or for worse, installations have been found where a single
disconnect contains more than one type and/or size of fuse; fuses have
been jumpered out or replaced with solid copper or steel bars, etc. Likewise,
circuit breakers have been misapplied, bypassed, etc. The type of worker
who operates and maintains an electric power system can have just as
much, if not more, impact on its performance as the type of overcurrent
protective device that is used.
16
0600DB0601
2/2007
17
VIII. Flexibility
18
0600DB0601
2/2007
0600DB0601
2/2007
IX. References
19
0600DB0601
2/2007