Installation Guide
No-load Shutdown
The UPS will shut down to conserve energy if while operating on battery power the UPS detects
that connected equipment is using less than 15 W of energy for more than 15 minutes.
No-load shutdown can be enabled or disabled through Program mode described below.
55a
If the Back-UPS switches to battery power too frequently or too infrequently, adjust the transfer
voltage and sensitivity settings:
1. Verify that the Back-UPS battery is connected. Connect the Back-UPS to a wall outlet. The
Back-UPS should be turned off.
2. Press and hold the POWER ON/OFF button for 10 seconds. The LEDs will illuminate amber,
to indicate that the Back-UPS is in Program mode.
3. The LEDs will flash either green, red or amber to indicate the current sensitivity level. The
Back-UPS will beep to indicate that No-load Shutdown is enabled. Refer to the table for an
explanation of the transfer voltage sensitivity levels.
4. To select LOW sensitivity, press the <KEY>ON/OFF button until the LED flashes green.
5. To select MEDIUM sensitivity, press the <KEY>ON/OFF button until the LED flashes red.
6. To select HIGH sensitivity, press the <KEY>ON/OFF button until the LED flashes amber.
7. To exit Program mode wait for five seconds and both LEDs will extinguish.
Status Indicators
Audible
Indicator
Voltage
Sensitivity
Setting
Green
None
Low
150-300
Disabled
Green
4 beeps per
second
Low
150-300
Enabled
Red
None
Medium
155-290
Disabled
Red
4 beeps per
second
Medium
(factory
default)
155-290
Enabled
Amber
None
High
165-280
Disabled
Amber
4 beeps per
second
High
165-280
Enabled
LED
Flashes
Status
Power On
The Back-UPS is supplying
utility power to connected
equipment.
On Battery
Back-UPS supplying battery
power to battery backup outlets.
LED Indicator
The green LED
illuminates.
The green LED
illuminates. The
LED is not
illuminated during
the beeps.
The green LED
illuminates with
rapid green flashes.
Audible Indicator
On
None
Audible Indicator
Terminates
No-load
Shutdown
N/A
Constant tone
Back-UPS is turned
off.
The Back-UPS
beeps once every
four seconds.
Input
Voltage
Range
Specifications
Input
Warranty
Register your product on-line. http://warranty.apc.com
The standard warranty is two (2) years from the date of purchase. SEIT standard procedure
is to replace the original unit with a factory reconditioned unit. Customers who must have
the original unit back due to the assignment of asset tags and set depreciation schedules
must declare such a need at first contact with an SEIT Technical Support representative.
SEIT will ship the replacement unit once the defective unit has been received by the repair
department, or cross-ship upon the receipt of a valid credit card number. The customer
pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship
the replacement unit to the customer.
Output
Protection and
Filtering
Battery
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the Troubleshooting section of the manual to eliminate common problems.
2. If the problem persists, contact Schneider Electric IT (SEIT) Customer Support
through the APC by Schneider Electric Web site, www.apc.com.
a. Note the model number and serial number and the date of purchase. The model
and serial numbers are located on the rear panel of the unit and are available
through the LCD display on select models.
b. Call SEIT Customer Support and a technician will attempt to solve the problem
over the phone. If this is not possible, the technician will issue a Returned
Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the APC by
Schneider Electric Web site for country specific instructions.
3. Pack the unit in the original packaging whenever possible to avoid damage in transit.
Never use foam beads for packaging. Damage sustained in transit is not covered
under warranty.
4. Always DISCONNECT THE UPS BATTERIES before shipping. The United
States Department of Transportation (DOT), and the International Air
Transport Association (IATA) regulations require that UPS batteries be
disconnected before shipping. The internal batteries may remain in the UPS.
5. Write the RMA# provided by Customer Support on the outside of the package.
6. Return the unit by insured, pre-paid carrier to the address provided by Customer
Support.
Recommended Use
Physical
Voltage
Frequency
47-63 Hz
Brownout Transfers
Over-voltage Transfer
UPS Capacity
(3 battery backup outlets)
Voltage - On Battery
230 Vac 8%
Frequency - On Battery
50 or 60 Hz + 1 (auto-sensing)
Transfer Time
6 ms Typical, 10 ms maximum
AC Surge Protection
EMI/RFI Filter
Full time
AC Input
Type
Average Life
Net Weight
5 kg.
Dimensions
Length x Width x Height
27.85 cm x 16 cm x 8.85 cm
Operating Temperature
32 F to 104 F (0 C to 40 C)
Storage Temperature
5 F to 113 F (15 C to 45 C)
Operating Elevation
0 to 10,000 ft (0 to 3000 m)
Battery Replacement
The battery in the Back-UPS 625 is not user-replaceable. Contact Schneider Electric Sales and
Technical Support for a list of authorized service centers near you.