Uninterruptible Power Systems
1/2/3KVA
4256-5110 B
Operation Manual
All rights reserved.
The information in this document is subject to change without notice.
Publish statement
Thank you for purchasing this series UPS.
This series UPS is an intelligent, single phase in single phase out, high frequency
online UPS designed by our R&D team who is with years of designing experiences
on UPS. With excellent electrical performance, perfect intelligent monitoring and
network functions, smart appearance, complying with EMC and safety standards,
The UPS meets the world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment.
1
Table of Contents
1. Important Safety Warning.................................................................................................................. 3
3. Operations .............................................................................................................................................. 13
4. Troubleshooting ................................................................................................................................... 19
6. Options .................................................................................................................................................... 21
7. Specification .......................................................................................................................................... 23
2
1. Important Safety Warning
Important safety instructions – Save these instructions
Please comply with all warnings and operating instructions in this manual strictly.
Save this manual properly and read carefully the following instructions before
installing the unit. Do not operate this unit before reading through all safety
information and operating instructions carefully
There exists dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety instructions
and relative laws, otherwise it will result in personnel injury or equipment damage.
Safety instructions in this manual act as a supplementary for the local safety
instructions. Our company will not assume the liability that caused by
disobeyingsafety instructions.
1-1 Transportation
Please transport the UPS system only in the original package to protect against
shock and impact.
1-2 Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed.
Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or
near heater.
Do not block ventilation holes in the UPS housing.
1-3 Installation
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
The UPS can be operated by any individuals with no previous experience.
Connect the UPS system only to an earthed shockproof outlet which must be
easily accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof
outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
When installing the equipment, it should ensure that the sum of the leakage
current of the UPS and the connected devices does not exceed 3.5mA.
3
1-4 Operation
Do not disconnect the mains cable on the UPS system or the building wiring
outlet (shockproof socket outlet) during operations since this would cancel the
protective earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS
output sockets or output terminals block may be electrically live even if the UPS
system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
Riskofelectricshock
CAUTION!
Readthisinformationtoavoidequipmentdamage
2. Installationand setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. Please keep the original package in a safe place for future use.
Check the appearance to see if the UPS is damaged or not during the
transportation, do not switch on the UPS if any damage found. Please contact the
dealer right away.
Check the accessories according to the packing list and contact the dealer in case
of missing parts.
It includes:
5
2-2 Real panel view
1KVA(S):
1KVA(H):
2KVA(S):
2KVA(H)/3KVA(H)
6
2KVA(S)-6batt /3KVA(S):
1. AC input
2. Network /Fax/Modem Surge Protection(option)
3. Input circuit breaker
4. EPO(option)
5. USB communication port(option)
6. RS-232 communication port
7. SNMP intelligent slot (option)
8. Output receptacles
9. Battery Terminal
10. Output Terminal
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or Relay card. When
installing either SNMP or Relay card in the UPS, it will provide advanced communication
and monitoring options.
NOTE: USB port and RS-232 port can’t work at the same time.
Step 4: Turn on the UPS
Press the ON button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not
expect full battery run capability during this initial charge period.
Step 5: Install software
For optimal computer system protection, install UPS monitoring software to fully
configure UPS shutdown. You may insert provided CD into CD-ROM to install the
monitoring software.
Step 6: External battery connection
If your UPS is not including batteries. Please connect external batteries as below chart.
8
2-4 UPSstartup and turn off
Startup operation
(1) Turn on the UPS in line mode
NOTE Verify that the total equipment ratings do not exceed the UPS
capacity to prevent an overload alarm.
a) Once mains power is plugged in, the UPS will charge the battery, at the moment,
the LCD shows that the output voltage is 220, which means the UPS automatic ally
tart the inverter. If it is expected to change to bypassmodel, you can Press “OFF”
key.
b) Press and hold the ON key for more than three seconds to start the UPS, then it will
start the inverter.
c) Once started, the UPS will perform a self-test function, LED will light and go out
circularly and orderly. When the self-test finishes, it will come to line mode, the
corresponding LED lights, the UPS is working in line mode.
(2) Turn on the UPS by DC without mains power
a) When mains power is disconnected, press and hold the ON key for more than half a
second to start UPS.
b) The operation of the UPS in the process of start is almost the same as that when
mains power is in. After finishing the self-test, the corresponding LED lights and the
UPS is working in battery mode.
9
LCD control panel introduction
LED Indicator
Indicator Description
Yellow
NOTE When power on or startup , these indicators will turn on and off sequentially.
10
Function Keys
Function Key Description
UP To go to previous selection
Icon Functiondescription
InputSourceInformation
IndicatestheACinput.
Indicatesthesettingprograms.
Indicatesthewarningand faultcodes.
Warning: flashingwithwarningcode.
11
OutputInformation
Indicate output voltage, output frequency, load percent, load in VA,
load in
Watt and discharging current.
Battery Information
Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in
battery mode and charging status in line mode.
Load Information
Indicatesoverload.
Indicatestheloadlevelby 0-24%,25-50%,50-74%and75-100%.
Indicatesunitconnectstothemains.
Indicatesloadissuppliedbyutilitypower.
Indicatestheutilitychargercircuitis working.
IndicatestheDC/ACinvertercircuitis working.
Mute Operation
Indicatesunitalarmisdisabled.
12
3. Operations
13
Item Interface Description Content Displayed
Battery voltage&Backup
02
time& Battery capacity
Input frequency&
03
Output frequency
04 Load
Environment
05
Temperature
14
06 UPS model.
07 Firmware Version
Alarm Code(Warming
Message)
08 All alarm codes are
present when abnormal
behavior(s) occur(s)
After the UPS turn ON, press buttons “UP +Down” for 5 seconds and then goes into
the setting interface page.
Note: Press “Down”button to confirm selection and exit setting mode when LCD
display the last selection in UPS setting mode.
15
Item Settings Content display
Mode setting
Frequency setting
16
Battery EOD voltae
setting(Second)
17
3-4 Operational Status and Mode(s)
item Content Displayed
1 Initialized
2 Standby Mode
3 No Output
4 Bypass Mode
5 Utility Mode
6 Battery Mode
7 Battery Self-diagnostics
8 Inverter is starting up
9 ECO Mode
10 EPO Mode
11 Maintenance Bypass Mode
12 Fault Mode
4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table
below and theTrouble Shooting Chart.
20
5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years
at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this
case, please contact your dealer.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours
6. Options
SNMP card: internal SNMP
The relay card includes 6 output ports and one input port.Please refer to the following table for
detail.
22
7. Specification
MODEL 1KVA(S) 1KVA(H) 2KVA(S) 2KVA(H) 3KVA(S) 3KVA(H)
PHASE Single phase with ground
Capacity (VA/Watts) 1000VA / 1000W 2000VA / 2000W 3000VA / 3000W
INPUT
Nominal voltage 200/208/220/230/240VAC
160Vac±5% @100%-80% load;
140Vac±5% @80%-70% load;
Low line
120Vac±5% @70%-60% load;
transfer
110Vac±5% @60%-0% load;
(Ambient Temp. <35℃)
Operating 175Vac±5% @100%-80% load;
voltage 155Vac±5% @80%-70% load;
Low line
range 135Vac±5% @70%-60% load;
comeback
125Vac±5% @60%-0% load;
(Ambient Temp. <35℃)
High line
300Vac ±5%
transfer
High line
290Vac ±5%
comeback
Operating frequency
40-70Hz
range
Power factor 0.99@100% load(Nominal Input Voltage)
Bypass high voltage point
230-264: setting the high voltage point in LCD from 230Vac to 264Vac. (Default: 264Vac)
Bypass voltage range
Bypass low voltage point
170-220: setting the low voltage point in LCD from 170Vac to 220Vac. (Default: 170Vac)
Generator input Support
OUTPUT
Output voltage 200/208/220/230/240Vac
Power factor 1.0
Voltage regulation ±1%
Line Mode
(synchroni 47-53Hz or 57-63Hz
Frequency zed range)
23
Numbers 2 3 2 3 4 6 4 6 6 8 6 8
Backup time Long run unit depends on the capacity of external batteries
Typical recharge
4 hours recover to 90% capacity (Typical)
time(standard modle)
109.
27.4 41.0 27.4 41.0 54.7 82.1 54.7 82.1 82.1 109.4 82.1
4
Charging voltage VDC VDC VDC VDC VDC VDC VDC VDC VDC VDC VDC
VDC
±1% ±1% ±1% ±1% ±1% ±1% ±1% ±1% ±1% ±1% ±1%
±1%
12A max, 12A max,
12A max, can
can be can be
Charge current 1A or 2A be setting by 1A or 2A 1A or 2A
setting by setting by
LCD
LCD LCD
SYSTEM FEATURES
Ambient Temp.<35℃
105%~110%: UPS transfer to bypass after 10minuteswhen the utility is normal
110%~130%: UPS transfer to bypass after 1minute when the utility is normal
Line 130%~150%: UPS transfer to bypass after 5 seconds when the utility is normal
Overload Mode >150%:UPS transfer to bypass immediately when the utility is normal
@35℃ Battery
Mode 35℃<Ambient Temp.<40℃
105%~110%: UPS transfer to bypass after 1minute when the utility is normal
110%~130%: UPS transfer to bypass after 5 seconds when the utility is normal
>130%:UPS transfer to bypass immediately when the utility is normal
Short Circuit Hold Whole System
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
EPO (optional) Shut down UPS immediately
Audible & Visual alarms Line Failure, Battery Low, Overload, System Fault
Comunication interface USB(or RS232), SNMPcard(optional), Relay card (optional)
ENVIRONMENTAL
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20-90 % RH @ 0- 40°C (non-condensing)
Altitude < 1500m
Noise level Less than 50dBA at 1 Meter
PHYSICAL
144* 144* 144* 144* 144* 144* 144*
Dimension W×H×D 144*209 144*209 191*337 191*337 191*337
209* 209* 209* 209* 209* 209* 209*
(mm) *293 *399 *460 *460 *460
293 399 293 399 399 399 399
Net Weight (kg) 9.8 14.4 4 4.1 17 27.1 6.7 6.8 27.6 32.8 7.3 7.4
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
EMC
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8