Uninterruptible Power Systems
1/2/3KVA

4256-5110 B

Operation Manual
All rights reserved.
The information in this document is subject to change without notice.

Publish statement
Thank you for purchasing this series UPS.
This series UPS is an intelligent, single phase in single phase out, high frequency
online UPS designed by our R&D team who is with years of designing experiences
on UPS. With excellent electrical performance, perfect intelligent monitoring and
network functions, smart appearance, complying with EMC and safety standards,
The UPS meets the world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment.

1
Table of Contents
1. Important Safety Warning.................................................................................................................. 3

1-1 Transportation ............................................................................................................................ 3

1-2 Preparation ................................................................................................................................... 3

1-3 Installation .................................................................................................................................... 3

1-4 Operation ...................................................................................................................................... 4

1-5 Maintenance, service and faults ........................................................................................... 4

1-6 Symbols used in this guide..................................................................................................... 5

2. Installationand setup ............................................................................................................................ 5

2-1 Unpack checking ........................................................................................................................ 5

2-2 Real panel view ........................................................................................................................... 6

2-3 Setup the UPS.............................................................................................................................. 7

2-4 UPSstartup and turn off .......................................................................................................... 9

3. Operations .............................................................................................................................................. 13

3-1 Button operation ...................................................................................................................... 13

3-2 LCD display ................................................................................................................................. 13

3-3 UPS setting ................................................................................................................................. 15

3-4 Operational Status and Mode(s) ........................................................................................ 18

3-5 Alarm or Fault reference code ............................................................................................. 18

4. Troubleshooting ................................................................................................................................... 19

5. Storage and Maintenance ................................................................................................................. 21

6. Options .................................................................................................................................................... 21

7. Specification .......................................................................................................................................... 23

2
1. Important Safety Warning
Important safety instructions – Save these instructions
Please comply with all warnings and operating instructions in this manual strictly.
Save this manual properly and read carefully the following instructions before
installing the unit. Do not operate this unit before reading through all safety
information and operating instructions carefully
There exists dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety instructions
and relative laws, otherwise it will result in personnel injury or equipment damage.
Safety instructions in this manual act as a supplementary for the local safety
instructions. Our company will not assume the liability that caused by
disobeyingsafety instructions.

1-1 Transportation
 Please transport the UPS system only in the original package to protect against
shock and impact.

1-2 Preparation
 Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed.
Please allow at least two hours for the UPS system to acclimate the environment.
 Do not install the UPS system near water or in moist environments.
 Do not install the UPS system where it would be exposed to direct sunlight or
near heater.
 Do not block ventilation holes in the UPS housing.

1-3 Installation
 Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
 Place cables in such a way that no one can step on or trip over them.
 Do not connect domestic appliances such as hair dryers to UPS output sockets.
 The UPS can be operated by any individuals with no previous experience.
 Connect the UPS system only to an earthed shockproof outlet which must be
easily accessible and close to the UPS system.
 Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof
outlet).
 Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
 When installing the equipment, it should ensure that the sum of the leakage
current of the UPS and the connected devices does not exceed 3.5mA.
3
1-4 Operation
 Do not disconnect the mains cable on the UPS system or the building wiring
outlet (shockproof socket outlet) during operations since this would cancel the
protective earthing of the UPS system and of all connected loads.
 The UPS system features its own, internal current source (batteries). The UPS
output sockets or output terminals block may be electrically live even if the UPS
system is not connected to the building wiring outlet.
 In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
 Prevent no fluids or other foreign objects from inside of the UPS system.

1-5 Maintenance, service and faults


 The UPS system operates with hazardous voltages. Repairs may be carried out
only by qualified maintenance personnel.
 Caution - risk of electric shock. Even after the unit is disconnected from the
mains (building wiring outlet), components inside the UPS system are still
connected to the battery and electrically live and dangerous.
 Before carrying out any kind of service and/or maintenance, disconnect the
batteries and verify that no current is present and no hazardous voltage exists in
the terminals of high capability capacitor such as BUS-capacitors.
 Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations.
Unauthorized persons must be kept well away from the batteries.
 Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Before touching, please verify that no voltage is present!
 Batteries may cause electric shock and have a high short-circuit current. Please
take the precautionary measures specified below and any other measures
necessary when working with batteries:
-remove wristwatches, rings and other metal objects
-use only tools with insulated grips and handles.
 When changing batteries, install the same number and same type of batteries.
 Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
 Do not open or destroy batteries. Escaping electrolyte can cause injury to the
skin and eyes. It may be toxic.
 Please replace the fuse only with the same type and amperage in order to avoid
fire hazards.
 Do not dismantle the UPS system.
4
1-6 Symbols used in this guide
WARNING!

Riskofelectricshock

CAUTION!

Readthisinformationtoavoidequipmentdamage

2. Installationand setup

NOTE: Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. Please keep the original package in a safe place for future use.

2-1 Unpack checking


 Don’t lean the UPS when moving it out from the packaging.

 Check the appearance to see if the UPS is damaged or not during the
transportation, do not switch on the UPS if any damage found. Please contact the
dealer right away.

 Check the accessories according to the packing list and contact the dealer in case
of missing parts.

It includes:

(1) UPS user's guide

(2) Software Suite CD

(3) USB cable

(4) Power cord (Input and output)

(5) RS232 cable

5
2-2 Real panel view
1KVA(S):

1KVA(H):

2KVA(S):

2KVA(H)/3KVA(H)

6
2KVA(S)-6batt /3KVA(S):

1. AC input
2. Network /Fax/Modem Surge Protection(option)
3. Input circuit breaker
4. EPO(option)
5. USB communication port(option)
6. RS-232 communication port
7. SNMP intelligent slot (option)
8. Output receptacles
9. Battery Terminal
10. Output Terminal

2-3 Setup the UPS


Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension
cords.
 For 200/208/220/230/240VAC models: The power cord is supplied in the UPS package.
Step 2: UPS output connection
7
 For socket-type outputs, simply connect devices to the outlets.
 For terminal-type input or outputs, please follow below steps for the wiring
configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm2 power cords for 3KVA (200/208/220/230/240VAC
models).
c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
Step 3 Communication connection
Communication port:

To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or Relay card. When
installing either SNMP or Relay card in the UPS, it will provide advanced communication
and monitoring options.
NOTE: USB port and RS-232 port can’t work at the same time.
Step 4: Turn on the UPS
Press the ON button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not
expect full battery run capability during this initial charge period.
Step 5: Install software
For optimal computer system protection, install UPS monitoring software to fully
configure UPS shutdown. You may insert provided CD into CD-ROM to install the
monitoring software.
Step 6: External battery connection
If your UPS is not including batteries. Please connect external batteries as below chart.

8
2-4 UPSstartup and turn off
 Startup operation
(1) Turn on the UPS in line mode

NOTE Verify that the total equipment ratings do not exceed the UPS
capacity to prevent an overload alarm.
a) Once mains power is plugged in, the UPS will charge the battery, at the moment,
the LCD shows that the output voltage is 220, which means the UPS automatic ally
tart the inverter. If it is expected to change to bypassmodel, you can Press “OFF”
key.
b) Press and hold the ON key for more than three seconds to start the UPS, then it will
start the inverter.
c) Once started, the UPS will perform a self-test function, LED will light and go out
circularly and orderly. When the self-test finishes, it will come to line mode, the
corresponding LED lights, the UPS is working in line mode.
(2) Turn on the UPS by DC without mains power
a) When mains power is disconnected, press and hold the ON key for more than half a
second to start UPS.
b) The operation of the UPS in the process of start is almost the same as that when
mains power is in. After finishing the self-test, the corresponding LED lights and the
UPS is working in battery mode.

 Turn off operation


(1) Turn off the UPS in line mode
a) Press and hold the OFF key for more than half a second to turn off the UPS and
inverter.
b) After the UPS shutdown, the LEDs go out and there is no output. If output is
needed, you can set bps “ON” onthe LCD setting menu.
(1) Turn off the UPS by DC without mains power
a) Press and hold the OFF key for more than half a second to turn off the UPS.
b) When turning off the UPS, it will do self-testing firstly. The LEDs light and go out
circularly and orderly until there is no display on the cover.

Operation and Display Panel


The operation and display panel, shown in below chart, is on the front panel of the
inverter. It includes three indicators, four function keys and a LCD display, indicating the
operating status and input/output power information.

9
LCD control panel introduction

(1)LED(fromright to left: “alarm”, “bypass”, “battery”, “inverter”);

(2)On-Line UPS LCD display;(3)Function keys

LED Indicator
Indicator Description

OnThe UPS has an active alarm or fault.


Red

The UPS is in Bypass mode.


OnThe UPS is operating normally
Yellow onbypassduring High Efficiency operation.

OnThe UPS is in Battery mode.

Yellow

OnThe UPS is operating normally.


Green

NOTE When power on or startup , these indicators will turn on and off sequentially.

NOTE On different operation modes , these indicators will indicate differently.

10
Function Keys
Function Key Description

ESC/OFF To exit setting mode Or turn off the ups

UP To go to previous selection

Down To go to next selection

To confirm the selection in setting mode or enter setting mode


ENTER/ON
or turn on the UPS.

LCD Display Icons

Icon Functiondescription

InputSourceInformation

IndicatestheACinput.

Indicateinputvoltage,inputfrequency ,batteryvoltageand Temp

Configuration Program and Fault Information

Indicatesthesettingprograms.

Indicatesthewarningand faultcodes.

Warning: flashingwithwarningcode.

Fault: lighting withfaultcode

11
OutputInformation
Indicate output voltage, output frequency, load percent, load in VA,
load in
Watt and discharging current.

Battery Information
Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in
battery mode and charging status in line mode.

In AC mode, it will present battery charging status.

Status Battery capacity LCD Display

0-24% 4 bars will flash in turns

Bottom bar will be on and the other three


25-49%
bars will flash in turns
Constant
Bottom two bar will be on and the other two
Curren mode 50-74%
bars will flash in turns

Bottom three bar will be on and thetop bars


75-100%
will flash

Load Information
Indicatesoverload.

Indicatestheloadlevelby 0-24%,25-50%,50-74%and75-100%.

0%~25% 25%~50% 50%~75% 75%~100%

Mode Operation Information

Indicatesunitconnectstothemains.

Indicatesloadissuppliedbyutilitypower.

Indicatestheutilitychargercircuitis working.

IndicatestheDC/ACinvertercircuitis working.

Mute Operation

Indicatesunitalarmisdisabled.

12
3. Operations

3-1 Button operation


Button Function
 Turn on the UPS: Press and hold ON button for
at least 2 seconds to turn on the UPS.
 Confirm current settings:When the UPS
entersthe setting mode, must press this button
to confirm the settings value what you
ON /ENTER Button
want,nest press up/down button to change
settings information.
 Out off bypass mode:when the UPS enter to
bypass mode, press and hold this button it will
switch to normal mode.
 Turn off the UPS: Press and hold this button at
least 2 seconds to turn off the UPS in battery
mode. UPS will be in standby mode under
power normal or transfer to Bypass mode if the
OFF/ESC Button
Bypass enable setting by pressing this button.
 Exit setting mode:Press this button to confirm
selection and exit setting mode when LCD
display the last selection in UPS setting mode.
 Up key: Press this button to display previous
UP Button
selection in UPS setting mode.
 Down key: Press this button to display next
DOWN Button
selection in UPS setting mode.
 Setting mode: Press and hold this button for 5
UP + DOWN Button
seconds to enter UPS setting mode.

3-2 LCD display


Part one: Rack display
There are 9 interfaces available in the LCD display.

13
Item Interface Description Content Displayed

Input voltage& Output


01
voltage

Battery voltage&Backup
02
time& Battery capacity

Input frequency&
03
Output frequency

04 Load

Environment
05
Temperature

14
06 UPS model.

07 Firmware Version

Alarm Code(Warming
Message)
08 All alarm codes are
present when abnormal
behavior(s) occur(s)

3-3 UPS setting


The UPS has setting functions. This user settings can be done under any kind of UPS
working mode. The setting will take effect under certain condition. Below table
describes how to set the UPS.

The setting function is controlled by 4buttons (Up , Down, ON/Enter,OFF/ESC):

“Up ▲+ Down▼”---goes into the setting page;

ON/Enter --- - confirm the settings option;

Up ▲ & Down ▼--- value adjustment for choosing different pages;

OFF/ESC--- Exit setting mode;

After the UPS turn ON, press buttons “UP +Down” for 5 seconds and then goes into
the setting interface page.

Note: Press “Down”button to confirm selection and exit setting mode when LCD
display the last selection in UPS setting mode.

15
Item Settings Content display

Mode setting

Press Enter button to change the


01 setting (ECO or NOR or CF).
Press UP ▲button to select the
previous setting.
Press DOWN▼ button to select
the next setting.

Output voltage setting

Press Enter button to change the


02 setting(200,208,220, 230, 240).
Press UP▲ button to select the
previous setting.
Press DOWN▼ button to select
the next setting.

Frequency setting

Press Enter button to change


03 the setting (50 or 60Hz).
Press UP button▲ to select the
previous setting.
Press DOWN button ▼ to select
the next setting.
Battery capacity setting

Press Enter button to change


the setting (Battery capacity
04 range is 1-200Ah).
Press UP button ▲ to select the
previous setting.
Press DOWN button ▼ to select
the next setting.
Battery EOD voltae setting(Once)

Press Enter button to change


the setting (1.75/1.84/1.92).
05
Press UP button ▲ to select the
previous setting.
Press DOWN button ▼ to select
the next setting.

16
Battery EOD voltae
setting(Second)

Press Enter button to change


06 the setting (1.60/1.70/1.75/1.80).
Press UP button ▲ to select the
previous setting.
Press DOWN button ▼ to select
the next setting.
Bypass voltage upper limit setting

Press Enter button to change


the setting(The bypass voltage
07 upper limit range is 230-264Vac ).
Press UP button ▲ to select the
previous setting.
Press DOWN button ▼ to select
the next setting.
Bypass voltage lower limit setting

Press Enter button to change the


setting(The bypass voltage lower
08 limit range is 170-220Vac).
Press UP button to select the
previous setting.
Press DOWN button to select
the next setting.
Mute setting

Press Enter button to change the


setting(ON or OFF).
09
Press UP button to select the
previous setting.
Press DOWN button to save and
exit the setup.

BYPASS enable/disable setting

Press Enter button to change the


setting(ON or OFF).
10
Press UP button ▲ to select the
previous setting.
Press DOWN button ▼ to save
and exit the setup.

17
3-4 Operational Status and Mode(s)
item Content Displayed
1 Initialized
2 Standby Mode
3 No Output
4 Bypass Mode
5 Utility Mode
6 Battery Mode
7 Battery Self-diagnostics
8 Inverter is starting up
9 ECO Mode
10 EPO Mode
11 Maintenance Bypass Mode
12 Fault Mode

3-5 Alarm or Fault reference code


Event log UPS Alarm Warning Buzzer LED
1 Rectifier Fault Beep continuously Fault LED lit
Inverter fault(Including Inverter
2 Beep continuously Fault LED lit
bridge is shorted)
9 Fan fault Beep continuously Fault LED lit
12 Selftest fault Beep continuously Fault LED lit
13 Battery Charger fault Beep continuously Fault LED lit
15 DC Bus over voltage Beep continuously Fault LED lit
16 DC Bus below voltage Beep continuously Fault LED lit
17 DC bus unbalance Beep continuously Fault LED lit
18 Soft start failed Beep continuously Fault LED lit
19 UPS Inside Over Temperature Twice per second Fault LED lit
20 Heatsink Over Temperature Twice per second Fault LED lit
26 Battery over voltage Once per second Fault LED blinking
29 Output Short-circuit Once per second Fault LED blinking
30 Input current limit Once per second Fault LED blinking
31 Bypass over current Once per second BPS LED blinking
INV or BPS LED
32 Overload Once per second
blinking
33 No battery Once per second Battery LED blinking
34 Battery under voltage Once per second Battery LED blinking
35 Battery low pre-warning Once per second Battery LED blinking
36 Over load time out Once per 2 seconds Fault LED blinking
18
37 DC component over limit. Once per 2 seconds INV LED blinking
39 Mains volt. Abnormal Once per 2 seconds Battery LED lit
40 Mains freq. abnormal Once per 2 seconds Battery LED lit
41 Bypass Not Available BPS LED blinking

4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table
below and theTrouble Shooting Chart.

Symptom Possible cause Remedy


Check if input power cord
The AC input power is
firmly connected to the
not connected well.
No indication and alarm even mains.
though the mains is normal. The AC input is
Plug AC input power cord
connected to the UPS
to AC input correctly.
output.

Alarm code is shown as“33” The external or


Check if all batteries are
and battery led blinking. internal battery is
connected well.
incorrectly connected.
Alarm code is shown as “26” Battery voltage is too
and battery led blinking. high or the charger is Contact your dealer.
fault.
Alarm code is shown as “34” Battery voltage is too
low or the charger is Contact your dealer.
and battery led blinking
fault.
Alarm code is shown as “32”
UPS is overload Remove excess loads from
and INV or BYPASS led
UPS output.
blinking.
The UPS shut down
Alarm code is shown as “29” Check output wiring and if
automatically because
and FAULT led light. connected devices are in
short circuit occurs on
short circuit status.
the UPS output.
Alarm code is shown as “9” Contact your dealer.
Fan fault.
and FAULT led light.

Alarm code is shown as A UPS internal fault Contact your dealer.


“01,02, 15,16,17,18” has occurred.
Charge the batteries for at
least 5 hours and then
Batteries are not fully
check capacity. If the
Battery backup time is shorter charged
problem still persists,
than nominal value consult your dealer.
Contact your dealer to
Batteries defect
replace the battery.
19
Trouble Shooting Chart

20
5. Storage and Maintenance
 Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years
at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this
case, please contact your dealer.

Be sure to deliver the spent battery to a recycling facility or


ship it to your dealer in the replacement battery packing material.

 Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours

6. Options
SNMP card: internal SNMP

◆Loosen the 2 torquescrews (on each side of thecard).


◆Carefully insert the SNMP card and lock the screws
The slot called SNMP supports the MEGAtec protocol.We advise that Net AgentII-3 port is
also a tool to remotely monitorand manage any UPS system
NetAgentII-3Ports supports the Modem Dial-in(PPP) function to enable the remote
control via the internet when the network is unavailable.
In addition to the features of a standard NetAgent Mini,NetAgent II has the option to
add Net Feeler Lite to detect temperature,humidity,smoke andsecurity sensors.Thus,making
NetAgent II aversatile management tool. NetAgent II also supports multiple languages and is
set up for web-based auto language detection.

Typical topologyof the UPS NetworkManagement


21
Relaycard
Mini dry contact card is used foproviding the interface for UPS peripheral monitoring. The
contact signals canreflect UPS running status.The card is connected to peripheral monitoring
devices via terminal board to facilitate the effective monitoring of the real-timestatus of UPS
and timely feedback the statusto monitor when abnormal situation occurs(suchas UPS failure,
mains interruption,UPS bypassand ect.). It is installed in the intelligent slotof the UPS.

The relay card includes 6 output ports and one input port.Please refer to the following table for
detail.

Pins definition of connecting terminal on the board

22
7. Specification
MODEL 1KVA(S) 1KVA(H) 2KVA(S) 2KVA(H) 3KVA(S) 3KVA(H)
PHASE Single phase with ground
Capacity (VA/Watts) 1000VA / 1000W 2000VA / 2000W 3000VA / 3000W
INPUT
Nominal voltage 200/208/220/230/240VAC
160Vac±5% @100%-80% load;
140Vac±5% @80%-70% load;
Low line
120Vac±5% @70%-60% load;
transfer
110Vac±5% @60%-0% load;
(Ambient Temp. <35℃)
Operating 175Vac±5% @100%-80% load;
voltage 155Vac±5% @80%-70% load;
Low line
range 135Vac±5% @70%-60% load;
comeback
125Vac±5% @60%-0% load;
(Ambient Temp. <35℃)
High line
300Vac ±5%
transfer
High line
290Vac ±5%
comeback
Operating frequency
40-70Hz
range
Power factor 0.99@100% load(Nominal Input Voltage)
Bypass high voltage point
230-264: setting the high voltage point in LCD from 230Vac to 264Vac. (Default: 264Vac)
Bypass voltage range
Bypass low voltage point
170-220: setting the low voltage point in LCD from 170Vac to 220Vac. (Default: 170Vac)
Generator input Support
OUTPUT
Output voltage 200/208/220/230/240Vac
Power factor 1.0
Voltage regulation ±1%

Line Mode
(synchroni 47-53Hz or 57-63Hz
Frequency zed range)

Bat. Mode (50/60±0.1)Hz


Crest factor 3:1
Harmonic distortion ≤2% THDwith linear load
(THDv) ≤4% THD with non linear load
Waveform Pure Sinewave
AC mode
<->Batt. Zero
Transfer mode
time Inverter
<-> 4ms(Typical)
bypass
Line mode 88% 92% 92%
Efficiency
Batt mode 85% 86% 85% 86% 87% 88% 87% 88% 89% 90% 89% 90%
BATTERY
depends on
depends on depends on
the
the capacity the capacity
Battery Type 12V9AH 12V9AH capacity of 12V9AH
of external of external
external
batteries batteries
batteries

23
Numbers 2 3 2 3 4 6 4 6 6 8 6 8
Backup time Long run unit depends on the capacity of external batteries
Typical recharge
4 hours recover to 90% capacity (Typical)
time(standard modle)
109.
27.4 41.0 27.4 41.0 54.7 82.1 54.7 82.1 82.1 109.4 82.1
4
Charging voltage VDC VDC VDC VDC VDC VDC VDC VDC VDC VDC VDC
VDC
±1% ±1% ±1% ±1% ±1% ±1% ±1% ±1% ±1% ±1% ±1%
±1%
12A max, 12A max,
12A max, can
can be can be
Charge current 1A or 2A be setting by 1A or 2A 1A or 2A
setting by setting by
LCD
LCD LCD
SYSTEM FEATURES
Ambient Temp.<35℃
105%~110%: UPS transfer to bypass after 10minuteswhen the utility is normal
110%~130%: UPS transfer to bypass after 1minute when the utility is normal
Line 130%~150%: UPS transfer to bypass after 5 seconds when the utility is normal
Overload Mode >150%:UPS transfer to bypass immediately when the utility is normal
@35℃ Battery
Mode 35℃<Ambient Temp.<40℃
105%~110%: UPS transfer to bypass after 1minute when the utility is normal
110%~130%: UPS transfer to bypass after 5 seconds when the utility is normal
>130%:UPS transfer to bypass immediately when the utility is normal
Short Circuit Hold Whole System
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
EPO (optional) Shut down UPS immediately
Audible & Visual alarms Line Failure, Battery Low, Overload, System Fault
Comunication interface USB(or RS232), SNMPcard(optional), Relay card (optional)
ENVIRONMENTAL
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20-90 % RH @ 0- 40°C (non-condensing)
Altitude < 1500m
Noise level Less than 50dBA at 1 Meter
PHYSICAL
144* 144* 144* 144* 144* 144* 144*
Dimension W×H×D 144*209 144*209 191*337 191*337 191*337
209* 209* 209* 209* 209* 209* 209*
(mm) *293 *399 *460 *460 *460
293 399 293 399 399 399 399
Net Weight (kg) 9.8 14.4 4 4.1 17 27.1 6.7 6.8 27.6 32.8 7.3 7.4
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
EMC
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

* Derate to 80% of capacity when the output voltage is adjusted to200/208VAC


** Product specifications are subject to change without further notice.