Aurora Pumps
Aurora Pumps
Aurora Pumps
ENGINEERING SPECIFICATIONS
CENTRIFUGAL FIRE PUMPS
61
(A) AURORA MODEL 481 HORIZONTAL BASE MOUNTED size ____-481____ horizontal split case, bronze fitted, SINGLE STAGE, double suction
centrifugal pump.
(B) AURORA MODEL 485 HORIZONTAL BASE MOUNTED size ____-485____ horizontal split case, bronze fitted, TWO STAGE, single suction,
centrifugal pump.
The driver shall be a horizontal, foot mounted, open drip-proof (or T.E.F.C.),
ball bearing type, AC, induction, squirrel cage motor: wound for ____ volts,
3 phase, 60 (50) Hertz. The motor shall be of such capacity that 115% of the
full-load ampere rating shall not be exceeded at any condition of pump load.
Locked rotor current shall not exceed the values specified in NFPA Pamphlet
No.20.
62
_____
2.
_____
3.
_____
4.
Discharge tee
_____
5.
Base elbow
_____
6.
Hose valves
_____
7.
_____
8.
_____
9.
Blind flange
_____
X
_____
_____
X
_____
_____
X
_____
_____
_____
X
_____
63
than____degrees F.
The engine shall be of the self-contained open type mounted on a suitable
base with the following minimum accessories, plus any others that may be
necessary by local requirements.
1. Dual battery set sized to NFPA Pamphlet No.20 requirements with
X
electrolyte shipped in separate containers, rack and cables
_____
2. Dual battery charger of proper type for batteries used (included in U.L.
X
Listed/F.M. Approved controller)
_____
2. Circuit breaker - time delay type with trips in all phases set for 300% of
the motor full-load current. The interrupting capacity of circuit breaker shall
be____asymmetrical amperes.
X
3. Electric starter with suitable generator and voltage regulator _____
4. Engine water pump
X
_____
X
_____
X
_____
X
_____
8. Speed governor
X
_____
X
_____
X
_____
11. Stubshaft
X
_____
X
_____
X
_____
X
_____
15. Proper instrument panel complete with engine run warning light, water
temperature gauge, oil pressure gauge, ammeter, totalizing type tachometer
X
and hour meter
_____
X
_____
17. Cooling water line for the engine heat exchanger assembly
X
_____
X
_____
ENGINE DRIVE
The Fire Pump shall be driven by a U .L. Listed and F.M. Approved diesel
engine. The engine shall conform to the requirements of NFPA Pamphlet
No.20 and be approved for Fire Pump use. The rated speed shall not exceed
____RPM and shall develop ____ H.P. to drive the pump. Reserve H.P.
shall be as stipulated in Pamphlet No.20 when the unit is operating
at____ft. above sea level in an ambient temperature not greater
All engine wiring for automatic operation shall terminate in a proper junction
box to permit field connection to a separate control panel.
64
FUEL SYSTEM
A suitable fuel system for the diesel engine shall be furnished. It must be in
accordance with NFPA Pamphlet No.20, and shall include a____gallon
above surface storage tank. Flexible fuel connectors, combination vent-flash
arrestor and fill cap shall be included.
Starting the engine by a fire alarm relay, deluge valve relay, or remote pushbutton station shall be included in the controller circuit.
In the event the pump, engine and control are in an unattended area, a
remote alarm panel shall be furnished as per NFPA Pamphlet No.20.
TESTS
The pump and electric motor (or engine) shall be thoroughly shop-tested by
the respective manufacturers as required by NFPA Pamphlet No.20. The
control panel shall also be tested as a unit. All such tests shall be conducted
prior to shipment.
The pump, driver, controller and all accessories shall be purchased under a
unit contract. The pump shall be given a complete performance test with
POSITIVE SUCTION PRESSURE. A certified performance curve shall be
prepared and submitted. Pumps shall also be hydrostatically tested to twice
the shut off pressure, but in no case less than 250 lbs. per sq. inch.
In the case of diesel drives, the pump manufacturer shall perform a second
pump operational test as a unit with the job engine. Test data shall be
furnished.
The pump manufacturer shall assume unit responsibility and shall provide the
services a factory trained representative to supervise and/or be available to
conduct final field acceptance tests.
71
RATED
CAPACITY
G.P.M.
250
250
250
250
250
250
250
250
250
250
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
750
750
750
750
750
750
750
750
750
750
750
750
750
750
750
750
750
750
750
750
750
750
MODEL
DESIGNATION
2-1/2-481-10B
2-1/2-483-10B
2-1/2-481-10B
2-1/2-483-10B
3-481-10
3-481-10/DI
3-483-10
3-481-10
3-481-10/DI
3-483-10
3-481-10
3-481-10/DI
3-483-10
4-481-11A
4-483-11A
4-481-11C
4-481-11C/DI
4-483-11C
4-481-11C
4-481-11C/DI
4-481-15
4-483-15
4-485-15
5-485-12
5-485-12
5-485-12
5-485-15
4-481-11A
4-483-11A
4-481-11C
4-481-11C/DI
4-481-11C
4-481-11C/DI
4-483-11C
4-481-15
4-483-15
5-481-11C
5-481-11C/DI
5-483-11C
5-481-15
5-483-15
6-458-12
6-485-12
6-485-12
6-485-12
6-485-17A
6-485-17A/DI
6-485-17A
6-485-17A/DI
RATED HEAD
PRESSURE RANGE
P.S.I.
51-115
51-115
52-167
52-167
40-120
40-120
40-120
40-100
40-100
40-100
50-150
50-150
50-150
40-55
40-55
55-134
55-134
55-134
75-180
75-180
60-80
60-180
150-210
182-319
188-330
288-476
68-144
40-50
40-50
66-164
66-164
65-192
65-192
65-192
71-95
71-95
105-154
105-154
105-154
50-70
50-70
193-255
197-340
205-352
310-506
80-175
80-175
140-245
140-245
APPROXIMATE
SPEED
R.P.M.
2950/3000
2950
3550/3560
3560
2950/3000
2950/3000
2950
3550/3560
3550/3560
3560
3550/3560
3550/3560
3560
1750/1770
1770
2950/3000
2950/3000
2950
3300
3300
1750/1770
1770
1750/1770
2950
3000
3560
1460/1480
1750/1770
1770
3300
3300
3550/3560
3550/3560
3560
1750/1770
1770
2950/3000
2950/3000
2950
1750/1770
1770
2600
2950
3000
3560
1460/1480
1460/1480
1750/1770
1750/1770
MAXIMUM ALLOWABLE
WORKING PRESSURE
P.S.I.
250
250
250
250
210
450
210
210
450
210
210
450
210
270
270
275
500
275
275
500
200
200
270
625
625
625
270
270
270
275
500
275
500
275
200
200
325
450
325
210
210
625
625
625
625
330
400
330
400
1. The data shown above is listed in the current Fire Protection Equipment Directory of U.L. and is consistent with the requirements of F.M.
2. Maximum Working Pressure (PSI) is defined by U.L. as the maximum pressure that can be developed at the discharge flange under any operating
condition. Applications where working pressures exceed these limits must be referred to the factory. Maximum pressure at the discharge flange = maximum
suction pressure plus maximum total developed head.
3. In determining Maximum Allowable Working Pressure, both agencies require initial hydrostatic testing approval at twice the values shown above.
DI = Ductile Iron construction
RATED
MODEL
RATED HEAD
CAPACITY
DESIGNATION
5-481-11B
5-481-11B/DI
5-481-11B
5-481-11B/DI
5-483-11B
5-481-11C
5-481-11C/DI
5-483-11C
5-481-11C
5-481-11C/DI
5-481-11C
5-481-11C/DI
5-483-11C
5-481-15
5-483-15
5-481-17
5-483-17
6-481-11
6-483-11
6-481-11HH
6-481-11HH
6-481-11HH
6-481-11HH
6-481-14HH
6-481-14HH
6-481-14HH
6-481-14HH
6-481-14HH
6-481-14HH
6-485-17A
6-485-17A/DI
6-481-18C
6-481-18C/DI
6-483-18C
6-481-11HH
6-481-11HH
6-481-11HH
6-481-11HH
6-481-14HH
6-481-14HH
6-481-14HH
6-481-14HH
6-481-14HH
6-481-14HH
G.P.M.
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
APPROXIMATE
MAXIMUM ALLOWABLE
PRESSURE RANGE
SPEED
WORKING PRESSURE
P.S.I.
145-165
145-165
165-200
165-200
165-200
97-146
97-146
97-146
90-135
90-135
90-160
90-160
90-160
50-90
50-90
90-125
90-125
40-50
40-50
69-115
93-155
74-186
188-219
77-133
96-160
75-203
102-287
130-248
154-287
130-240
130-240
81-108
81-108
81-108
96-110
98-151
111-182
132-216
94-130
87-156
122-301
110-287
122-247
145-287
R.P.M.
3300
3300
3550/3560
3550/3560
3560
2950/3000
2950/3000
2950
3300
3300
3550/3560
3550/3560
3560
1750/1770
1770
1750/1770
1770
1750/1770
1770
2600
2950/3000
3300
3550/3560
2100
2300
2600
2950/3000
3300
3550-3560
1750/1770
1770
1460/1480
1460/1480
1480
2600
2950/3000
3300
3550/3560
2100
2300
2600
2950/3000
3300
3550-3560
P.S.I.
325
450
325
450
325
325
450
325
325
450
325
450
325
210
210
210
210
200
200
500
500
500
500
500
500
500
500
500
500
330
400
325
450
325
500
500
500
500
500
500
500
500
500
500
1. The data shown above is listed in the current Fire Protection Equipment Directory of U.L. and is consistent with the requirements of F.M.
2. Maximum Working Pressure (PSI) is defined by U.L. as the maximum pressure that can be developed at the discharge flange under any operating
condition. Applications where working pressures exceed these limits must be referred to the factory. Maximum pressure at the discharge flange = maximum
suction pressure plus maximum total developed head.
3. In determining Maximum Allowable Working Pressure, both agencies require initial hydrostatic testing approval at twice the values shown above.
DI = Ductile Iron construction
Pentair Water
RATED
CAPACITY
G.P.M.
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
MODEL
DESIGNATION
6-481-15
6-483-15
6-481-18B
6-481-18B/DI
6-483-18B
6-481-18C
6-481-18C/DI
6-483-18C
6-481-18C
6-481-18C/DI
6-483-18C
6-481-20
6-481-20/DI
6-483-20
8-481-12
8-483-12
8-481-21
8-481-21
5-481-11D
6-481-11HH
6-481-11HH
6-481-14HH
6-481-14HH
6-481-14HH
6-481-14HH
6-481-15
6-483-15
6-481-18B
6-481-18B/DI
6-483-18B
6-481-18C
6-481-18C/DI
6-483-18C
6-481-20
6-481-20/DI
6-483-20
8-481-12
8-483-12
8-481-21
8-481-21
RATED HEAD
PRESSURE RANGE
P.S.I.
55-96
55-96
100-140
100-140
100-140
78-105
78-105
78-105
81-108
81-108
81-108
84-168
84-168
84-168
43-52
43-52
90-142
136-200
90-120
121-144
142-209
142-196
153-285
137-240
158-283
50-90
50-90
95-134
95-134
95-134
75-102
75-102
75-102
80-165
80-165
80-165
40-50
40-50
88-141
135-200
APPROXIMATE
SPEED
R.P.M.
1750/1770
1770
1750/1770
1750/1770
1770
1750/1770
1750/1770
1770
1460/1480
1460/1480
1480
1750/1770
1750/1770
1770
1750/1770
1770
1460/1480
1750/1770
3300
2950/3000
3550-3560
2600
2950/3000
3300
3550/3560
1750/1770
1770
1750/1770
1750/1770
1770
1460/1480
1460/1480
1480
1750/1770
1750/1770
1770
1750/1770
1770
1460/1480
1750/1770
MAXIMUM ALLOWABLE
WORKING PRESSURE
P.S.I.
230
230
225
450
225
325
450
325
325
450
325
230
450
230
200
200
325
325
250
500
500
500
500
500
500
230
230
225
450
225
325
450
325
230
450
230
200
200
325
325
1. The data shown above is listed in the current Fire Protection Equipment Directory of U.L. and is consistent with the requirements of F.M.
2. Maximum Working Pressure (PSI) is defined by U.L. as the maximum pressure that can be developed at the discharge flange under any operating
condition. Applications where working pressures exceed these limits must be referred to the factory. Maximum pressure at the discharge flange = maximum
suction pressure plus maximum total developed head.
3. In determining Maximum Allowable Working Pressure, both agencies require initial hydrostatic testing approval at twice the values shown above.
DI = Ductile Iron construction
Pentair Water
RATED
CAPACITY
G.P.M.
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2500
2500
2500
2500
2500
2500
2500
3000
3000
3000
3000
3000
3500
3500
3500
3500
4000
4000
4000
4000
4500
5000
MODEL
DESIGNATION
6-481-15B
6-483-15B
6-481-15B
6-481-18C
6-481-18C/DI
6-481-18C
6-481-20
6-481-20/DI
6-483-20
8-481-17B
8-483-17B
8-481-17B
8-483-17B
8-481-21
8-481-21
8-481-17B
8-483-17B
8-481-17B
8-481-21A
8-481-21A
10-481-18
10-481-10D
10-481-15C
10-481-18
10-481-18
10-481-18D
10-481-18D
10-481-18
10-481-18
10-481-18D
10-481-18D
10-481-18
10-481-18D
10-481-18D
12-481-18A
10-481-18D
10-481-18D
RATED HEAD
PRESSURE RANGE
P.S.I.
80-100
80-100
100-125
100-140
100-140
100-140
123-150
123-150
123-150
52-94
52-94
53-127
53-127
82-135
130-195
75-130
75-130
115-144
123-190
100-125
65-100
63-96
100-110
61-99
99-145
61-95
90-138
60-97
98-140
59-94
88-135
95-110
64-92
85-134
67-102
81-132
91-130
APPROXIMATE
SPEED
R.P.M.
1750/1770
1770
2100
1750/1770
1750/1770
1770
1750/1770
1750/1770
1770
1460/1480
1480
1750/1770
1770
1460/1480
1750/1770
1750/1770
1770
2100
1750/1770
1460/1480
1460/1480
1460/1480
2300
1460/1480
1770
1460/1480
1750/1770
1460/1480
1750/1770
1460/1480
1750/1770
1750/1770
1460/1480
1750/1770
1460/1480
1750/1770
1750/1770
MAXIMUM ALLOWABLE
WORKING PRESSURE
P.S.I.
200
200
200
225
450
225
230
450
230
208
208
208
208
325
325
208
208
208
325
325
200
237
200
200
200
237
237
200
200
237
237
200
237
237
200
237
237
1. The data shown above is listed in the current Fire Protection Equipment Directory of U.L. and is consistent with the requirements of F.M.
2. Maximum Working Pressure (PSI) is defined by U.L. as the maximum pressure that can be developed at the discharge flange under any operating
condition. Applications where working pressures exceed these limits must be referred to the factory. Maximum pressure at the discharge flange = maximum
suction pressure plus maximum total developed head.
3. In determining Maximum Allowable Working Pressure, both agencies require initial hydrostatic testing approval at twice the values shown above.
DI = Ductile Iron construction
Pentair Water
75
FIRE PUMPS
REMOVABLE PANEL
Fire pumps for industrial plants and similar locations have a range of
capacities from 500 to 4,500 gallons per minute. Their principal use is to
make available large amounts of water for fire protection. They may take
suction from a public main simply to increase the pressure available from
such a source, but they are more often provided with their own reservoirs,
suction tanks or wells, making the plant independent of piped water from
public systems.
SCREEN RAISED
HIGH WATER
LOWEST STANDING
WATER LEVEL
BOTTOM OF
RESERVOIR
STRAINER
RACK
SCREENS
YARD
SYSTEM
76
PRIMING
The suction pipe and pump casing must be full of water for the pump to work.
The pump casing must be provided with an automatic air release valve or
umbrella cock to allow evacuation of air.
C. Note size and type of pump and arrangement of control devices. Note
size of suction and discharge connections and pipes. Give length of suction
pipe and the head in feet under which water is received by
the pump, or the lift in feet.
1
4
6
3
2
10
14
11
13
17
6
16
12
18
D. Ask for any records kept of weekly running tests made both to check
operation of the pump and the operation of manual and automatic starting,
stopping and general control equipment provided as part of the installation.
See the results of the last annual full capacity test.
18
15
E. Fire pumps are designed for relatively infrequent use, but must be able
to perform satisfactorily even after standing idle for some time. Note whether
the conditions generally make this possible. The pump should not be used for
any other pumping service. It should be possible for an excited and perhaps
unskilled person to start the pump. Note the extent to which employees show
familiarity with the operation of the pump.
CENTRIFUGAL FIRE PUMPS
Following are some of the important features to cover in an inspection.
There are many other details and for these consult CENTRIFUGAL FIRE PUMPS,
NFPA No.20, which covers the common method of driving; electric motors,
steam turbines, gasoline (installations prior to adoption of 1974 edition of
NFPA No.20) and diesel engines.
In general, pump and driver should be provided as a unit together with all
needed control equipment. There should be acceptable evidence available for
the inspector that the entire assembly is properly designed, such as listing of
the assembly by Underwriters Laboratories, Inc.. Underwriters Laboratories
of Canada or Factory Mutual Research Corporation.
500
5
750
6
1,000
6
1,500
8
2,000
10
2,500
10
3,000
12
3,500
12
4,000
12
4,500
14
5
3
2
6
4
3
8
4
4
8
6
6
10
6
6
10
6
8
12
8
12
12
8
12
14
8
16
16
8
16
77
D. Look for suitable disconnecting means for electric circuits and proper
overcurrent protection. Inspect the transformer installation.
VENT
HAND PUMP
FOR FILLING
GRAVITY TANK
END OF PIPE
2-QUART
GRAVITY TANK
12 FT MINIMUM
12"
ELEVATION
OF ENGINE
FUEl PUMP
3/8"
SUCTION
PIPES
IN TANK
FILL
PIPE
1-1/2"
1/2"
OVERFLOW
PIPE
VENT
STRAINER
TO
CARBURETOR
ENGINE
PUMP
CHECK VALVE
STORAGE
TANK
3 FT MINIMUM
STICK
GAUGE
ELEVATION OF ENGINE
FUEL PUMP NOT TO BE
OVER 6 FT ABOVE BOTTOM
OF GASOLINE STORAGE TANK
78
In even a brief or routine inspection the inspector should request that pumps
be operated a few minutes at rated speed with water discharging through
some convenient opening. Steam reciprocating pumps may run until water is
discharging freely through the relief valve. The management of a property
with a fire pump should make similar running tests weekly. It
should have employees to make tests for the inspector. The inspector should
not operate equipment.
E. Observe stuffing boxes of pump. With water seal supplied with water a
small leak at stuffing box glands is necessary.
I. Be specific and complete when ordering Fire Pumps and accessories so that
the necessary and correct items can be supplied.
2. Trouble can not be tolerated on the day of the field acceptance test,
therefore
G. Have all outlets closed, including relief valve, and note that pump shuts
off at the proper pressure (for horizontal shaft pumps usually not over 120
percent of rated pressure; for vertical shaft pumps 140 percent)
A. Visit the jobsite after the equipment has been delivered and check for
completeness and correctness and answer any questions the contractor may
have.
B. Visit the jobsite after installation and check for correctness of
installation.
79
3. After the installation is complete and the Fire Pump System is pressurized
and checked by the contractor an initial test should be conducted. This is
to check the controller and motor. The test should be conducted (with
contractor present if possible on engine drive systems, engine
representative will be present for start-up) as follows:
C. Tachometer.
D. Pitot tube and gauge.
E. *Calibrated suction and discharge gauges with a range accuracy of
1/4%. (First three items are in your APCO-MATIC kit)
A. Close all valves on discharge outlets. Check pump and motor alignment.
B. Open suction valve.
C. Check motor controller service manual and perform any necessary steps
outlined, in the manual, prior to putting controller into operation. Also, read
manual to understand how to operate the controller. Set controller to manual
position.
*The gauges furnished with the pump are 3% accurate and could lead to
problems if used for the field acceptance test. Equipment which is necessary
for the test and should be supplied by the local authorities:
1) 50 ft. of 2-1/2' hose for each hose connection on the outside hose
header.
2) Play pipe with 1-3/4" nozzle for each hose.
6. Field acceptance tests will vary in all locations. The following steps are
general and for electric drives. You will have to add any other requirements
which might be particular to your territory:
A. Hose and play pipe should be connected to each opening of outside hose
header.
B. Close discharge valve leading to building fire system.
C. Open discharge valve leading to outside hose header.
D. Suction valve should be open.
E. Close all relief valves.
G. Using pitot tube and gauge with 1-3/4" nozzle, valve should be
adjusted until gauge on pitot tube reads 30 PSI, this is equal to 500 GPM.
By opening additional valves and measuring the flow to equal 500 GPM, the
proper flow (500, 1000, 1500, 2000, 2500, 3000, 3500, 4000 or 4500) can
be obtained. Chart 1 lists nozzle pressures and flows for various nozzle sizes.
H. Open the necessary hose valves to obtain the rated flow. Check all
nozzles making sure the correct flow is maintained. Changing one valve
usually changes the flow in the other hoses. When the proper flow is assured,
check and record the following data:
A. Calibrated ammeter.
1) Suction gauge pressure.
B. Volt meter.
80
NOZZLE
PRESS.
10
20
30
35
40
45
50
55
60
62
64
66
68
70
72
74
76
78
80
85
90
95
100
105
110
115
120
1-1/8
l00
160
206
222
238
252
266
279
291
296
301
305
310
315
319
323
328
332
336
347
357
366
376
385
394
403
412
Q. Data obtained should match the certified performance test from the
factory (at 0 GPM, rate GPM, and 150% rated GPM). Average value of the
highest amps recorded should not exceed the nameplate amps of motor by
more than 115% (due to normal variations of test equipment, 120% may be
considered acceptable).
R. If data does not agree with test, recheck your data and if necessary,
retest pump. Be sure you figure total dynamic head correctly.
1-3/4
285
410
498
538
575
610
643
675
705
716
728
739
750
761
772
783
793
803
814
839
863
887
910
932
954
976
997