GST IFP8 Prezentare 2015 1
GST IFP8 Prezentare 2015 1
GST IFP8 Prezentare 2015 1
1
8-Loop Fire Panel
2
Addressable Fire Panel
LCIFP8
GST IFP8 Loop Card
Specification :
3
Addressable Fire Panel
P-9935
GST IFP8 communication card
Specification :
4
Addressable Fire Panel
P-9945A
GST IFP8 RS485 Class A network card
Specification :
5
Addressable Fire Panel
P-9965
GST IFP8 CAN network card (Class B)
Specification :
6
Addressable Fire Panel
P-9965A
GST IFP8 CAN network card (Class A)
Specification :
7
Panel Overview GST-IFP8 Structure
Structures
8
Panel Overview GST-IFP8 Fascia
Fascia
LED indicator
Control Buttons
2 x 70 Zone Indication
9
Panel Overview GST-IFP8 Internal Parts Overview
XS 8
F7.820.1238V2 XS 1
FAULT
INDICAT OR BOARD
COM BOARD
XS 9 XS 2
COM NC
XS15
OUTPUT
FEED
NO
MAIN BOARD
REPEATER
B
OUTPUT TO ALARM
A
XS5
TO MAINBOARD
F1
XS 1 0 XS 3
BACK
F2
GND +5V
-
ROUTING
OUTPUT
+
LOOP BOARD
-
SOUNDER
+
XS 1 1 XS 4
-
XS1
TO FPE
+ I-
LOOP 01
LOOP BOARD
0-
I+
TO MAINBOARD
0+
I-
+5V GND
LOOP 01
XS 1 2 XS 5
0-
I+
RP1
0+
I-
LOOP 01
0-
I+
LOOP BOARD
0+
I-
LOOP 01
0-
I+
0+
I-
XS 1 3 XS 6
LOOP 01
0-
I+
IO ZONE
0+
I-
LOOP 01
0-
I+
LOOP BOARD
0+
TO PRINT
I-
LOOP 01
F7.820.1238V2
0-
XS3
I+
XS6
0+
I-
XS 1 4 XS 7
LOOP 01
0-
I+
0+
I-
0-
LOOP 01
I+
LOOP BOARD
0+
GND 5V TX RX GND 24V
I-
0-
LOOP 01
I+
0+
24V
+5V GND
+ + + + + + HL
HL HL HL HL HL HL HL
HL +HL +HL +HL +HL +HL +
+ + + + + +
HL HL HL HL HL
+ HL
+ +HL +HL +HL +HL +HL
+ +HL
+ + + +
HL + + +
HL HL HL HL
HL HL HL HL
+HL HL
+ + HL
+ +HL +HL +HL +HL
+ HL HL + + + +
HL HL
27V GND
HL HL HL
+HL
+ F7.820.1312V2
+
+ +HL +HL
+
+HL
+
+HL
+
BT1
ZONE INDICATOR BOARD
BAT+ BAT-
HL
HL
HL
HL
HL HL HL HL HL HL 90V/260/12V
HL HL HL HL
+ + + + + + +
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
ZS2 +
HL
+HL +HL +HL +HL +HL +HL +HL
+ + + + + + +
HL HL HL HL
+HL +HL
HL HL
XP1 HL
DC Output 27V 11.7A +V AJD L
+HL +HL +HL +HL +HL
+ + + + + + +
HL HL HL HL HL HL HL
+HL +HL +HL HL +HL +HL +HL
+ + HL + + +
HL HL HL HL HL HL
+HL +HL +
+ + +HL +HL +HL
+ + +
+ + HL HL +
HL HL HL
HL HL HL HL HL
HL
+HL +HL +HL +HL + + +HL
+ + + + + + HL
HL HL HL HL HL HL HL
+HL +HL +HL +HL +HL +HL +
+ + + +
V+
+ + +
HL HL HL HL HL HL HL
+HL +HL + +HL +HL +HL +HL +HL
+ HL HL + + + + +
HL HL HL HL HL HL
+HL HL +HL +HL +HL +HL
+
HL
+ +
HL
+
HL + + + + Fuse
HL HL HL HL
+HL
F7.820.1312V2
V-
2A AC Input
AC220V
N
PRINT ER
AC/DC POW ER
CONVERT ER AC FILT ER POW ER SW IT CH
+ - + -
12
Panel Overview GST-IFP8 External Wiring
next panel A2
next panel B2
XS8
F7.820.1238V2 XS1
sA
next panel B1
NO COM NC
System Connections
XT18
next panel A1
OUTPUT
FAULT
next panel A
COM BOARD
next panel B
REPEATER
B
XT14
B
Output to Repeater or
Mimic Panel
XS9 XS2 A ss B
A
XS15
F2 F1
XT19
FEED
EOL
BACK
Fitted
470 ohms
4.7Kohms
MAIN BOARD
XT13
_
ALARM
EOL
SOUNDER ROUTING
O/P
4.7Kohms
+
MAINBOARD
TO
GST-IFP8
Sounder with Output Device with
built-in diode fitted diode
OUTPUT TO
XT12
XS10 XS3
_
O/P EOL
4.7Kohms
+
+
Sounder with Output Device with
built-in diode fitted diode
XT11
OUTPUT
_
EOL
TO FPE
FPE FPE
4.7Kohms
+
+
LOOP BOARD
+
FPE with
fitted diode
XS11 XS4
I+ I-
10 O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+
A1
XT10
O-
Out to
LOOP 01 LOOP 02 LOOP 03 LOOP 04 LOOP 05 LOOP 06 LOOP 07 LOOP 08 LOOP 09 LOOP
LOOP 10
O+
Out to
B1
I+ I-
XT10
XT9
Network Terminal - Clas
LOOP BOARD B2 In from
I+
+5V GND
I+ I-
XS12 XS5
XT8
In from
I-
A2
I+ I-
A
O-
Out to
XT7
LOOP 10
O+
LOOP BOARD B
Out to
I+ I-
XT10
XT6
Network Terminal - Cla
I+
XS13 XS6
I+ I-
No connection
XT5
I-
I+ I-
XT4
LOOP BOARD Out to first device
O-
I+ I-
Loop Out
XT3
LOOP 01
O+
XS14 XS7
XT1
I+ I-
XT2
I+
Loop In
O-I+ I-
LOOP BOARD
I-
GND 5V TX RX GND 24V In from last device
XT1
24V
13
Panel Overview GST-IFP8 External Wiring
O-
out to first device
O+ Loop Out
LOOP
XT1
Loop Wiring
01
I+
Loop In
I-
XT1
A2
14
Panel Overview GST-IFP8 External Wiring
Output Condition Device Alarm Disable CE Mode Delay Time Stop – via
Number (Default) Program Silence Button
Alarm Routing A 00000083 Immediate Yes No Yes No
Routing
Output to Sounder A 00000082 Immediate Yes Yes Yes Yes
Sounder
Output to FPE A 00000081 Immediate Yes Yes No No
FPE
Note: For output dry contact use C-9302C (output capacity 5A/220VAC or 5A/24VDC)
15
Panel Overview GST-IFP8 Mother Board
16
Panel Overview GST-IFP8 Card Configuration
Card addressing
Each card (except main board) must be set
unique number (via onboard rotary switch) before
install it on motherboard,
Addressing sequence :loop card network card,
repeater card and RS232 communication card,
The number must start from No.1, and
continuously
Installation: recommend the card No.1 installed
on the lowest slot. Then card No.2 on the upper
slot, one by one till last card
CARD SUM:04 LOOP SUM:06 DEVICE SUM:614
*************************************************************
1 Loop 01: Loop Card, Devices Sum:184
2 Loop 02: Loop Card, Devices Sum:160
3 Loop 03: Loop Card, Devices Sum:150
4 Loop 04: Loop Card, Devices Sum:120
5 Loop 05: Net Unit
6 Loop 06: Color CRT
17
Panel Overview GST-IFP8 Card Configuration
Card Configuration
10 Loops + Repeater
10 Loops + Communication
8 Loops + Communication + Repeater
8 Loops + Communication+ Network 8
Loops + Network + Repeater
6 Loops + Communication + Network + Repeater
18
Panel Overview GST-IFP8 Card Configuration
Card Configuration
XS1
XS8 A1 Loop 11 - CRT Card 01
P-9935- Communication Card
9 01 HL1
8 2 HL2
7 3
6 5 4
XS2
XS9
Main Card
XS3
XS10 LED HL2
9 01
LED HL1
9 01
LED HL1
9 01
LED HL1
9 01
LED HL1
XS7
XS17 LED HL2
9 01
LED HL1
19
Panel Overview GST-IFP8 Card Configuration
Card Configuration
XS8 A1
9 01 HL1
HL2
Loop 10 - CRT Card 01
8 2
7 3 P-9935- Communication Card
654
XS2
XS9
Main Card
XS3
Loop 9-Net Unit - Wired on Loop 10 terminal
Sample…
XS10 LED HL2
9 01
LED HL1
8 2
7 3 P-9945A - Network Card
654
A1 8 Loops + Network + Communication card
XS4
XS11 LED HL2
9 01
LED HL1
9 01
LED HL1
9 01
LED HL1
XS7
XS17 LED HL2
9 01
LED HL1
20
Panel Overview GST-IFP8 Card Configuration
Card Configuration
XS8 A1
9 01 HL1
HL2
Loop 9 - Repeater Card 01
8 2
7 3 P-9945RP - Repeater Card
65 4
XS2
XS9
Main Card
XS3 9 01 Loop 8-Net Unit - Wired on Loop 10 terminal
LED HL2 LED HL1
XS10 8 2
7 3
P-9945A - Network Card - 01
65 4
A1
Sample…
XS4
XS11 LED HL2
8
9 01
2
LED HL1
XS5
XS12 LED HL2
9 01
LED HL1
XS6
XS13 LED HL2
9 01
LED HL1
XS7
XS17 LED HL2
9 01
LED HL1
21
Panel Overview GST-IFP8 System Diagram
Stand-alone Architecture
IFP8 Capacities
•LCIFP8 –dual loop
•Loop 10 -2420 devices
•1.0 km max loop length
•1.5mm2 UTP fire cable
22
Panel Overview GST-IFP8 Repeater and GMC connection
• GSTGMC-up to 8 users
• Required P-9935
•RS232- 15 meters
23
Panels Networking
24
Panels Networking
Network
25
Panels Networking
RS 232 Card
26
Panels Networking
RS 232 Card
27
Panels Networking
P-9960 P-9960
P-9965
Total Cable Length 3.5 Km (max)
P-9965
CAN HUB
CAN100H-4/8/12/16
P-9960 P-9965 P-9965
P-9960 28
Panels Networking
•Maximum 99 FACP
Fiber Optic Network
•Recommend 32 FACP
RS485 Class B Fiber Optic Network
Fibre Optic
+ +
P-9940A P-9945A
(For Single-Mode-25KM)
Interface FIB485S01
Optic
Optic
Fibre
Fibre
(For Multi Mode -4.5km)
Interface FIB485M01
+ +
P-9940A P-9940A
29
Panels Networking
(For Single-Mode-25KM)
Interface FIB485S01
Fibre Optic
Fibre Optic
Fibre Optic
+ +
P-9940A P-9940A
30
Panels Networking
TCP/IP Network
+ +
TCP/IP
+
+
NPort5230 + P-9930TCP/IP
P-9935 TCPIP + NPort5230
31
Product Overview
32
Initiating Device
DB-01 C-9314P
Standard Base Remote Indicator
33
Initiating Device
DB-01 C-9314P
Standard Base Remote Indicator
34
Initiating Device
DB-01 C-9314P
Standard Base Remote Indicator
35
Initiating Device
Beam Detector
Infrared beam detector
Detection range 8 to 100 meters
Path width 7 meters each side
1 to 4 reflectors for different path length
Standard EN54-12
Electronically addressed by programmer
Additional Fire and Fault dry contact relay output
24VDC supply required
I-9105R
Reflective Beam Detector
36
Initiating Device
D-92FC D-92WPB
37
Notification Device
C-94DB
Optional deep base for I-9403
38
Notification Device
C-94DB
Optional deep base for I-9404
39
Notification Device
DI-9405 Addressable
“sandwich” structure
Sounder Base
Termination suitable for “DI” range detectors
Loop powered
Maximum 30 pieces per loop
Three working modes settable (Mode I, II, III,
and the latter two available with pre-alarm state).
16 tones of sound.
Electronically addressed. The address and
tones can be modified in field.
Tone 14 and 16 are certified by EN54-3.
40
Notification Device
DI-9406 Addressable
Sounder Beacon Base “sandwich” structure
Termination suitable for “DI” range detectors
16 selectable tone
Loop powered
Maximum 30 pieces per loop
Three working modes settable (Mode I, II, III, and
the latter two available with pre-alarm state).
41
Interface
Input Interface
Intelligent single input module
Monitors switch contacts of remote equipment
Loop Powered
Cable monitored
Standard EN54-18
Electronically addressed by handheld
programmer
I-9300 Input Module LED status indicator
42
Interface
Input Interface
Intelligent zone monitor module
Interface with conventional fire devices
24VDC required
Cable monitored
Standard EN54-18
Electronically addressed by handheld
programmer
I-9319 Zone Interface Module LED status indicator
43
Interface
Output Interface
Intelligent single output module
24VDC/3A, 110VAC/3A dry contact output – Loop
Powered
Interface with conventional polarized sounders –
24VDC required
LED status indicator
Standard EN54-18
44
Isolator
Loop Isolator
45
Isolator
46
Programmer
Handheld Programmer
P-9910B Programmer
47
Repeater Panel
48
Repeater Panel
49
Repeater Panel
50
Graphic Station
51
Configuration, Operation and
Programming
2014 V1.2
Fire Alarm System Configuration
53
System Configuration
To configure a system
1. Decide panel type and quantity. If more than one panel is configured,
add network card to each panel.
2. Decide loop quantity. Remember leave at least 20% of loop quantity for
future expansion.
54
Addressable Fire Panel
55
System Configuration
Loop 1 1 2
Network Card NO NO NO
56
Addressable Fire Panel
Difference
GST100 GST200-2/2 GST-IFP8
Control)
Repeater Capacity 0 10 64
Checking function
57
System Configuration
58
System Loop Parameter
Loop
59
System Loop Parameter
60
System Loop Parameter
61
System Loop Parameter
62
GST-IFP8 Panel Operation
63
Panel Operation GST-IFP8
64
Panel Operation GST-IFP8
65
Panel Operation GST-IFP8
*BROWSE*
Local Output
D000 Group-000 Loop-00 F.P.E.
Local Output
D000 Group-000 Loop-00 ALARM ROUTING
Local Output
66
Panel Operation GST-IFP8
67
Panel Operation GST-IFP8
*CLOCK SETUP*
************************************************
Date (yy-mm-dd): [08]-[01]-[23]
Time (hh:mm:ss): [12]-[58]-[00]
Day ( week: 1-7): [3]
68
Panel Operation GST-IFP8
*PRINTER SETUP*
************************************************
1 DISABLE
2 ONLY FIRE
3 ALL HISTORY
69
Panel Operation GST-IFP8
70
Panel Operation GST-IFP8
*ACKNOWLEGE TIMER*
***********************************************
Please input the Pre-Alarm ACK time
Stage1 (Default 30S): [00]M-[30]S
71
Panel Operation GST-IFP8
72
Panel Operation GST-IFP8
73
Panel Operation GST-IFP8
*START/STOP DEVICE*
***********************************************
1 START DEVICE
2 STOP DEVICE
Start-> Stop->
Zone:002 Dev:001 Type: 03-BEAM DETECTOR Zone:002 Dev:001 Type: 03-BEAM DETECTOR
74
Panel Operation GST-IFP8
*DISABLE/ENABLE DEVICE*
***********************************************
1.DIS/ENABLE DEVICE-BY CODE
2.DIS/ENABLE DEVICE-BY ADDRESS
3.DIS/ENABLE ZONE
4.DIS/EANBLE SOUNDER
Disable-> Enable->
Zone:002 Dev:001 Type: 03-BEAM DETECTOR Zone:002 Dev:001 Type: 03-BEAM DETECTOR
75
Panel Operation GST-IFP8
*SYSTEM SETUP*
************************************************
1 PROGRAMMING *PROMRAMMING*
2 LOCAL OUTPUT SETUP ************************************************
3 WORKING STATE SETUP 1 DEVICE SETUP
4 COMMISSIONING 2 ZONE SETUP
3 COMMUNICATION SETUP *COMMUNICATION SETUP*
4 DAY/NIGHT TIME SETUP ***********************************************
5 MODIFY PASSW ORD 1 MONITOR INTERFACE
6 C&E EQUATION SETUP 2 NETWORK INTERFACE
7 DEVICE TYPE SETUP
*MONITOR INTERFACE SETUP*
***************************************************
76
Panel Operation GST-IFP8
*SYSTEM SETUP*
******************************************************
1 PROGRAMMING *PROMRAMMING*
2 LOCAL OUTPUT SETUP ************************************************
3 WORKING STATE SETUP 1 DEVICE SETUP *COMMUNICATION SETUP*
4 COMMISSIONING 2 ZONE SETUP ************************************************
3 COMMUNICATION SETUP 1 MONITOR INTERFACE
4 DAY/NIGHT TIME SETUP 2 NETWORK INTERFACE
5 MODIFY PASSWORD
6 C&E EQUATION SETUP *NETWORK INTERFACE SETUP*
7 DEVICE TYPE SETUP *******************************************************
Please input loop No: 04
77
Panel Operation GST-IFP8
*SYSTEM SETUP*
******************************************************
1 PROGRAMMING *PROMRAMMING*
2 LOCAL OUTPUT SETUP ************************************************
3 WORKING STATE SETUP 1 DEVICE SETUP
4 COMMISSIONING 2 ZONE SETUP *DAY/NIGHT TIME SETUP*
3 COMMUNICATION SETUP ************************************************
4 DAY/NIGHT TIME SETUP Please input the start time of day mode
5 MODIFY PASSWORD Default at 08:00 (hh:mm) [08]:[00]
6 C&E EQUATION SETUP
7 DEVICE TYPE SETUP Please input the end time of day mode
Default at 18:00 (hh:mm) [18]:[00]
Please note: day/night mode will affect the Cause & Effect time delay and the Type A and Type B
dependency
Panel works in night mode, in case fire panel will active the output modules immediately according
to Cause & Effect , all time delay settings on Cause &Effect will be ignored.
78
Panel Operation GST-IFP8
*SYSTEM SETUP*
******************************************************
1 PROGRAMMING *PROMRAMMING*
2 LOCAL OUTPUT SETUP ************************************************
3 WORKING STATE SETUP 1 DEVICE SETUP
4 COMMISSIONING 2 ZONE SETUP *MODIFY PASSWORD*
3 COMMUNICATION SETUP ************************************************
4 DAY/NIGHT TIME SETUP 1.OPERATOR PASSWORD
5 MODIFY PASSWORD 2.MANAGER PASSWORD
6 C&E EQUATION SETUP
7 DEVICE TYPE SETUP
*MODIFY PASSWORD*
************************************************
********
*MODIFY PASSWORD*
************************************************
********
79
Panel Operation GST-IFP8
*SYSTEM SETUP*
********************************************************* LOCAL OUTPUT SETUP Commission Mode
1 PROGRAMMING (OTS) Output to Sounder A Mode (0-2)
2LOCAL OUTPUT SETUP
0-one fire
3 WORKING STATE SETUP
1 more fire
4 COMMISSIONING
2 On C&E (Note: use device number 00000082-Sounder A)
(FPE) Fire Protection Equipment A Mode (0-2)
0-one fire
1 more fire
2 On C&E(Note: use device number 00000081-FPE A)
(FAR)Fire Alarm Routing A mode (0-2)
0-one fire
1 more fire
2 On C&E (Note: use device number 00000083-Alarm Routing A)
*LOCAL OUTPUT SETUP*
*********************************************************
Delay Time: 00 (note: ratio 1:10)
•FPE no delay affect
SOUNDERA mode (0-2): 0-on one fire •OTS & FAR affect by delay settings
F.P.E. A mode (0-2):1-More fire
ALARM ROUTINGA mode (0-2): 2-on C&E
DELAY TIME:[00]*10SEC – IN DELAY MODE
80
Panel Operation GST-IFP8
81
GST-IFP8 Basic Software
Configuration
82
GST-IFP8 Panel Addressing
5.Press “User
8.Select Setup”, “Browse
7.Select 6.Press “System
“Communicate Devices” to check
“Programming Menu” Setup”
Setup” Menu Color Crt loop
number
Note : Address on panel must same as the panel address on GST definition program.
If panel not in commissioning mode, press “System Setup” Button, then “Working
State” setup. Change panel t o “commissioning state”, then back to ‘Commissioning
Menu” select“1.Device learn” panel will re-learn all hardware and devices
83
Basic Software Configuration GST-IFP8
2.Connect download
1. Power On 3.Run GST
card USB cable to 4.Select Com Port
GST-IFP8 panel Definition Software
computer USB port
84
Basic Software Configuration GST-IFP8
The device code is the device unique ID on standalone FACP or whole FACP network. So before addressing and
programming devices, below points should be noted:
1. In same zone, in case the devices from different loop or different panel, the device address + device type can not be
same as other device’s. for example: in zone No.1 already has smoke detector address No.1 from loop1, and in this
zone has another smoke detector from other loop or other panel, the device address can not be No.1 again. Or if use
address No.1, can not given to smoke detector.
3. Fire alarm signal from network can be use as the local Cause & Effect condition.
4. Local panel can send activation command to network (if sending command option set as enable)
85
Basic Software Configuration GST-IFP8
86
Basic Software Configuration GST-IFP8
87
Basic Software Configuration GST-IFP8
2. Number of Loop
88
Basic Software Configuration GST-IFP8
3. Zone Configuration
Adding a zone
1.Click the “FACP Zone” icon
2.Right-click “Panel that will add zone” and select “Add Zone”
3.Or Click the “New” icon
Note: Max number of zone is 999
Zone ID : Zone
number Zone Mode:
1 Off: Panel display Fire immediately- No Pre-alarm feature (Default Setting)
2 Type A: Enable Pre-alarm/ The system shall response to a second alarm from any device in the same zone as the system alarm (Type A)
3 Type B: Enable Pre-alarm/ The system shall response to a second alarm from any device in the same or other zone as the system alarm (Type B)
89
Basic Software Configuration GST-IFP8
4. Device Detailed
Device Configuration per Loop
1.Click the “FACP Net” icon
2.Click “Panel to be programmed”
3.Click the “Loop 1”
Address: 1-242
Loop Number: Loop Number
Zone: Zone assignment
Device Type: Selection of device
type.
Properties: For output- 0-on/off ;
1-continoues
Location: Device location
information Note:
IFP8 character 40 max Registered:
Once the data is uploaded from the
panel, it will indicate TRUE
if the particular device is being found
or registered in the panel otherwise it
will indicate False.
4. Click Save icon to save
90
Basic Software Configuration GST-IFP8
91
Basic Software Configuration GST-IFP8
92
Basic Software Configuration GST-IFP8
Action
Cause: Cause Mode Effect
Devices Description:
Each deice include 3 digit zone number + 3 digit address + 2 digit device type (Valid number 0-9 and *
means any number)
Example 001002 03 means Zone 001 Address 002 Device Type 03 (Smoke Detector)
001*** 03 means Zone 001 Address Any Device Type 03 (Smoke Detector)
****** 03 means Any zone Any Address Device Type 03 (Smoke Detector)
Relation:
“+” means “OR” logic “x” means “AND” logic
Action Mode:
“=“ means “START” “x=“ means “STOP” Note: Stop action not affected by any defined time delay
Effect :
Devices Description:
Each deice include 3 digit zone number + 3 digit address + 2 digit device type (Valid number 0-9 and *
means any number)
Delay time number x 10 is the real time (by seconds) 01 means 10 seconds 02 means 20 seconds
93
Basic Software Configuration GST-IFP8
001010 12 x= ****** 13 00
Once voice alarm module 001010 be started, all sounder s will be stopped
94
Basic Software Configuration GST-IFP8
95
Basic Software Configuration GST-IFP8
Note:
•Com Board (XS8-XS1) – Used only for Repeater/ Mimic Card P-9946 or Communication Card P-9935 (USB and serial connection)
•Communication Card P-9935 can be placed in any Loop Board using only serial port connection, USB is not accessible
96
GST-IFP8 Basic Keypad
Configuration
97
Basic Keypad Configuration GST-IFP8
1. Zone Setup
2. Device Type Setup
3. Point Setup
4. C&E Set-up
98
Basic Keypad Configuration GST-IFP8
Zone Setup
*SYSTEM SETUP* **********
*PROMRAMMING* ***
******************************************** ********************************************* *ZONE SETUP*
1 PROGRAMMING 1 DEVICE SETUP
2 LOCAL OUTPUT SETUP Zone (1-999):001
2 ZONE SETUP
3 WORKING STATE SETUP *****************************************************
3 COMMUNICATION SETUP
4 COMMISSIONING Dependency Type(0-2): 1-Type A
4 DAY/NIGHT TIME SETUP
Sounder Mode (0-1):0-sound by zone fire
5 MODIFY PASSWORD
Resound mode:(0-1):0- no resound
6 C&E EQUATION SETUP
Zone Led: (1-140):001
7 DEVICE TYPE SETUP
Text (40 Bytes): Ground Floor
99
Basic Keypad Configuration GST-IFP8
Zone Setup
*SYSTEM SETUP*
******************************************************
1 PROGRAMMING
2 LOCAL OUTPUT SETUP *PROMRAMMING*
3 WORKING STATE SETUP ************************************************
4 COMMISSIONING 1 DEVICE SETUP *ZONE SETUP*
2 ZONE SETUP
3 COMMUNICATION SETUP Zone (1-999):001
4 DAY/NIGHT TIME SETUP *****************************************************
5 MODIFY PASSWORD Dependency Type(0-2): 1-Type A
6 C&E EQUATION SETUP Sounder Mode (0-1):0-sound by zone fire
7 DEVICE TYPE SETUP Resound mode:(0-1):0- no resound
Zone Led: (1-140):001
Text (40 Bytes): Ground Floor
Sounder Mode :
1 sound by zone fire: the zonal sounder will be auto active by the fire signal from same zone
2 On E&C: the programming zone sounder activation will depend on the Cause & Effect programming
Resound Mode:
1 No resound : The sounder will not resound on fire alarm from other zones after being silenced.
2 Resound by new fire : The sounder will resound on fire alarm from other zones after being silenced.
Zone Led :
select the prefer Led number as the programming zone fire fault/disable indication.
10
Basic Keypad Configuration GST-IFP8
10
Basic Keypad Configuration GST-IFP8
Device Setup
*SYSTEM SETUP* *PROMRAMMING* *DEVICE SETUP*
************************************************ ************************************************
1 PROGRAMMING 1 DEVICE SETUP Loop 01 Address (1-242):001
2 LOCAL OUTPUT SETUP 2 ZONE SETUP **************************************************
3 WORKING STATE SETUP 3 COMMUNICATION SETUP Zone (1-999): 001
4 COMMISSIONING 4 DAY/NIGHT TIME SETUP Device Type –OPTICAL SMOKE
5 MODIFY PASSW ORD Attribute (1-6):1
6 C&E EQUATION SETUP Text (40 Byte):
7 DEVICE TYPE SETUP
10
Basic Keypad Configuration GST-IFP8
Equation Setup
*SYSTEM SETUP*
**************************************** **************
1 PROGRAMMING *PROMRAMMING*
2 LOCAL OUTPUT SETUP ************************************************
3 WORKING STATE SETUP 1 DEVICE SETUP *C&E EQUATION SETUP*
4 COMMISSIONING 2 ZONE SETUP ************************************************
3 COMMUNICATION SETUP 1 CREATE
4 DAY/NIGHT TIME SETUP 2 MODIFY
5 MODIFY PASSWORD 3 DELETE ON *CREATE C&E*
6 C&E EQUATION SETUP 4 INITIALIZATI ************************************************
7 DEVICE TYPE SETUP C&E Quantity 000
No.001
001***03 + 001*** 02 = 001*** 13 00
NOTE:
Condition: INPUT DEVICES- 8 digits
Effect: OUTPUT DEVICES – 10 digits
Delay Time Ratio: 1:10 seconds
Number Arrangement:
999 242 99 = 999 242 99 99
Zone Address Device Type Zone Address Device Type Delay Time
10
Basic Keypad Configuration GST-IFP8
Equation Setup
Types of logic
Condition:
001 020 03 meaning Address 20 Optical smoke in Zone 1 (By Point)
001 *** 03 meaning At least 1(any address) Optical smoke in Zone 1 (By Zone)
*** *** 02 meaning At least 1(any address) Heat det. in the entire area (Global)
Effect:
*** *** 13 03 means sounder global alarm after 30 seconds (Global)
Sample:
001 *** 11 + 001 *** 03 + 001 *** 02 = 001*** 13 00, *** *** 13 06
Note:
Logic: AND Logic (x), OR Logic (+)
Fuzzy Logic: Asterisk (* value 1-9)
10
Basic Keypad Configuration GST-IFP8
Commissioning Menu
1. Device Learn
2. Duplicate Address Check
3. Modify Address
4. Modify Device Sensitivity
5. Commission Analog
6. Commission Digital
7. System Initialization
10
Basic Keypad Configuration GST-IFP8
10
Basic Keypad Configuration GST-IFP8
Duplicate Check
DUPLICATED ADDRESS CHECKING
*SYSTEM SETUP* *COMMISSIONING*
*********************************************** ************************************************* Please wait……
1 PROGRAMMING 1 DEVICE LEARN Press [Cancel] to Exit!
2 LOCAL OUTPUT SETUP 2DUPLICATED ADDRESS CHECK
3 W ORKING STATE SETUP 3 MODIFY ADDRESS
4COMMISSIONING 4 MODIFY DEVICE SENSITIVITY
5 COMMISSION IN ANALOGUE MODE DUPLICATED ADDRESS CHECKE OK
6 COMMISSION IN DIGITAL MODE Duplicated Address Sum: 001
7 SYSTEM INITIALIZATION
10
Basic Keypad Configuration GST-IFP8
Modify Address
*SYSTEM SETUP* *COMMISSIONING* *MODIFY ADDRESS*
*********************************************** ************************************************* Loop: 01 Address(1-242) : 001
1 PROGRAMMING 1 DEVICE LEARN ************************************************
2 LOCAL OUTPUT SETUP 2 DUPLICATED ADDRESS CHECK USER CODE : 00100115
3 W ORKING STATE SETUP 3MODIFY ADDRESS SERIAL NO.: 0000BB40
4COMMISSIONING 4 MODIFY DEVICE SENSITIVITY NEW CODE: 002
5 COMMISSION IN ANALOGUE MODE
6 COMMISSION IN DIGITAL MODE
7 SYSTEM INITIALIZATION
Note:
The panel must be set to “Commissioning Mode”
10
Basic Keypad Configuration GST-IFP8
Note:
The panel must be set to “Commissioning Mode”
10
Basic Keypad Configuration GST-IFP8
Note:
The panel must be set to “Commissioning Mode”
11
Basic Keypad Configuration GST-IFP8
Initialization Mode
*SYSTEM SETUP* *COMMISSIONING* Detector: Analog Mode
*********************************************** *************************************************
1 PROGRAMMING 1 DEVICE LEARN Press [1] Initialize detector in digital mode
2 LOCAL OUTPUT SETUP 2 DUPLICATED ADDRESS CHECK Press [2] Initialize detector in analog mode
3 W ORKING STATE SETUP 3 MODIFY ADDRESS Press [3] To Initialize the system
4 COMMISSIONING 4 MODIFY DEVICE SENSITIVITY
Press [4] To disable the battery resistance
5 COMMISSION IN ANALOGUE MODE
6 COMMISSION IN DIGITAL MODE
Press [5] To hide sounder plant item
7 SYSTEM INITIALIZATION
Note:
1.The panel must be set to “Commissioning Mode”
2. Required Initialization password:
11