Precommissioning Test Format
Precommissioning Test Format
Precommissioning Test Format
PRECOMMISSIONINGOFTRANSFORMER
COMMISSIONINGFORMATS DOCNO: SUBSTATION: EQUIPMENTIDENTIFICATIONNO:
2Winding
ICT
220/132/11
400/220/33
Current(Tertiary):
Sl.No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
NameofTests Insulationresistancemeasurement Vectorgrouptest&polaritycheck Shortcircuitimpedancetest Magneticbalancetest Floatingneutralvoltagemeasurement Magnetisationcurrenttest Voltageratiotest InsulationresistancemeasurementsofbushingCT ContinuityTestofBushingCTs SecondarywindingresistanceofbushingCT PolarityTestofBushingCTs CurrentRatiotest Magnetisingcurvesperformance
Page1of72
N2Pressure
DewPoint
AmbientTemp
Remarks
NOTE: N2 pressure and dew point should be within permissible range as per graph provided by manufacturer. During storage at site, dew point has to be measured whenever any drop in N2 pressure is observed. During storage at site before commissioning, N2 pressure has to be measured dailyandrecordtobemaintainedinaseparatesheet. b.IMPACTRECORERANALYSIS RECEIVEDIN STATUS HEALTHY Yes CONDITIONATSITE Yes Analysisreport Receivedfrom Manufacturer Before starting of erection BRIEFANALYSIS
No No
Note: Impact Recorder should be detached from the Transformer/ Reactor preferably when the mainunithasbeenplacedonitsfoundation. c.COREINSULATIONCHECK INSULATIONVALUE BetweenCCG BetweenCLG BetweenCCCL (Recommendedvalue>10MOhms)' Note:ShortinglinkbetweenCC,CL&GtoberemovedandIRvaluetobetakenbetweenCCG,CLG &CCCL.
Page2of72
C.CHECKS/PRECAUTIONSDURINGERECTION i)Activepartoftransformershouldminimumexposedtoatmosphere ii)Duringexposureofactivepartoftransformertoatmosphere: DRY AIR GENERATOR/ Yes DRY AIR CYLINDERS USED: No Remarks
iii)WHILEENTERINGINTRANSFORMERTANK,CHECKAVAILABILITYOFPROPEROXYGEN TRANSFORMER KEPT Yes SEALED WITH N2 IN BETWEEN DIFFERENT ERECTION ACTIVITIES D.PRECOMMISSIONINGCHECKS: Sl DESCRIPTION No 1. Transformer and its auxiliaries are free from visible defects on physical inspection 2. All fittings as per out line general arrangementdrawing. 3. Check main tank has been provided with doubleearthing 4. Check neutral is grounded through separate connections. Ensure metallic requirements as per specification in earthingstripsused 5. Check that Marshalling box, OLTC driving gear, Diverter, Radiator bank, Pump & Fanmotoretchasbeenearthed 6. All nuts and bolts are tightened correctly as per specified torque (as per manufacturersrecommendation) 7. Checktightnessofterminalconnectors 8. Check levelling of transformer and its accessories 9. Erectioncompletioncertificatealongwith listofoutstandingactivitiesreviewed 10. Any paint removed / scratched in transit hasbeentouchedup 11. Bushings are clean and free from physical damages 12. Oilleveliscorrectonallbushings STATUS Yes No REMARKS RECORDDEFICIENCIES,IFANY No Remarks
Page3of72
13. Check hermetically sealing is intact in all bushings 14. Check oil leakage through any joints / valvesetc. 15. Check oil drain valves are properly closed andlocked. 16. Check oil level in Main / OLTC conservatortank 17. Check oil level at conservator matches withoiltemperatureoftransformer 18. CheckgearboxoillevelinOLTC 19. Check OTI and WTI pockets and replenish theoil,ifrequired 20. check all valves for their opening & closingsequence 21. Check the colour of breather silica gel ( bluewhendry) 22. Check availability of oil in the breather cup 23. Check all rollers are locked and tack welded with rails ( where ever applicable ) 24. Checkbushingtesttapisgrounded 25. Check no debris , loose T & P and oil strainsonandaroundthetransformer 26. Check door seals of marshalling box is intact and all cable gland plates unused holesaresealed 27. Check that pressure relief valve is correctlymounted 28. Ensure unused secondary cores of bushingCT's,ifany,hasbeenshorted 29. Check star point has been formed properlyandgroundedatoneendonlyas perscheme 30. Check that permanent and adequate lightningarrangementsareready 31. Check that labelling and identification is permanentandsatisfactory 32. Check that buchholz relay is correctly mounted with arrow pointing towards conservator 33. Check cables are properly fixed and ensurecableentryatthebottom 34. Ensure all power and control cable terminalsaretightened 35. Checkallcablesandferrulesareprovided with number as per cable schedule (cross ferulingtobeChecked) 36. Check that all cables are correctly glanded
Page4of72
37. Check external cabling from junction box torelay/controlpanelcompleted 38. Checkthatairhasbeenreleasedfromthe radiators and their headers / OLTC buchholz relay /Main tank / tank/ bushingturretsetc. 39. Checkfireprotectionsystem&is adequate&ready 40. CheckthatCCCL&Gareshorted 41. Check that all radiator bank valves on top andbottomheadersareopen 42. Change over operation of ac supply from SourceitoSourceiichecked 43. Checktheflangesofbushing& OLTCforanycrackafterfixing 44. Check various interlocks provided with fire fighting as per the schematic ref. Drg no:__________ DESCRIPTIONOFINTERLOCKS CHECKED
E.MEASUREMENT OF EARTH RESISTANCE OF ELECTRODE LOCATION VALUE (Before connection to grid) VALUE (After connection to grid) NOTE:ValueofEarthResistance<1.0OHM F.CALIBRATIONOFOTI&WTIPERFORMEDASPERPROCEDURE: Yes No 1 2 3 4
G.DETAILSOFRELAYS/CONTACTORSUSED:SCHEMATICDRAWINGNO.:__________________ Circuit Reference Make SerialNo. Type Number of NO & Number of AI, BI & NCcontacts BO NO NC AI BI+BO
H.EVACUATINGANDOILFILLING: a) Before filling oil, each drum has been physically checked for free moisture and appearance: Yes No b)OILFILTERMACHINE: Page5of72
: :
d)OILSTORAGETANK: i). ii). iii). iv). v). Insidepaintedornot : Silicagelbreatherprovidedornot : Anyopeningleftuncovered : CapacityofStoragetank(KL) : Cleanlinessofinsideofpipes/hosestothestoragetank:
e)EXPOSUREDURINGERECTION: i). ExposurehoursduringFirstday,NumberofHours: a. N2filledpressure(PSIorBar) b. NumberofHoursunderN2 c. Ambienttemperature d. RelativeHumidity e. Weather(sunny/cloudy/stormy/rainy) ii). ExposurehoursduringSecondday,NumberofHours: a. N2filledpressure(PSIorBar) b. NumberofHoursunderN2 c. Ambienttemperature d. RelativeHumidity e. Weather(sunny/cloudy/stormy/rainy) iii). ExposurehoursduringThirdday,NumberofHours: a. N2filledpressure(PSIorBar) b. NumberofHoursunderN2 c. Ambienttemperature d. RelativeHumidity e. Weather(sunny/cloudy/stormy/rainy) f)N2SEALINGINCASEOFDELAYINOILFILLING: a. No.ofCylindersusedfordisplacingtheairinsidethetank: b. N2admittedfrombottomvalve Page6of72 : : : : : : : : : : : : : : : :
a. Valveatdiametricallyoppositeendattopkeptopen: b. No.ofCylindersusedforbuildingup2PSI(0.14kg/cm2) InspectionItem 1.Tightnesstest a.Startevacuatingoncompleteunit b.Stopevacuatingat3mbar c. Pressure P1 in kPa, 1 hour after stop evacuating d. Pressure P2 in kPa, 0.5 hrs after readingP1 e. Leakage = (P2P1)X V= If >3.6, continue evacuating, V is the volume of oil as per nameplate. 2.VACUUM a.Pressure0.13kPa(1.3mbar)reached b.Vacuumkeptfor Upto145kV,12Hour 145kV&upto220kV,24Hours 3.OILFILLING a.Oilfillingismade b.OilConservatorwithAirCell c.OLTC 4.STANDINGTIME Upto145kV,12Hours 145kV&upto220kV,48Hours G)RECORDOFDRYINGOUTPROCESS: Dryingoutstartedon: (Hourlyreadingtobetaken) Date Vacuumreading OTIOF Condensate Remarks & sign Vacuum Intransformer TANK Collected total ofsupervising readingin Tank /Rate Engineer Filtration machine Record of filtration and Dry out shall be kept in a register and shall be made a part of the Pre commissioningdocument. Time H)INSULATIONRESISTANCEMEASUREMENT:(USING500VMEGGER): Meggerdetails: ValidityofCalibration: Page7of72 Date: Time: AmbientTemp: Date Time Checked Remarks
Ambienttemperature: SlNo Status Yes A ControlWiring B TapCganger Motor Controlwiring C CoolingSystem FanMotor PumpMotor ControlWiring NOTE:IRvaluesshouldbe>50Mforcables Description Remarks,ifany No
I)INSULATIONRESISTANCEMEASUREMENT:(USING5000VMEGGER): Meggerdetails: ValidityofCalibration: Ambienttemperature: MainWinding AutoTransformer HV+IVtoLV HV+IVtoE LVtoE 2WindingTransformer HVtoE LVtoE HVtoLV TemperatureofOIL: AI=60ss/15s 600sec PI=600s/60s Temp.
J)VECTORGROUPTEST&POLARITYCKECKING CONNECT NEUTRAL POINT WITH EARTH, JOIN 1RI AND 3 RI TERMINALS, APPLY 415V, 3PHASE SUPPLYTOHVTERMINALS Terminal 1R11Y1 1Y11B1 1B11R1 3B11B1 3B11Y1 3R1N 3Y1N 1R1N 2R1N 2Y1N 2B1N VoltageMeasured Page8of72 Remarks
ENSURE2R1N=2Y1N=2B1N=CONSTANT AS3R1N>3B1N>3Y1N,AND3Y11B1>3B11B1 VECTORGROUPYnaod1ISCONFIRMEDANDPOLARITYVERIFIED K)MEASUREMENTOFWINDINGRESISTANCE(INOHM) WindingResistancemeterdetail: Validityofcalibration: AmbientTemperature: i). HVSideMeasurement Tap positi on 1 2 3 4 5 6 7 8 9b 10 11 12 13 14 15 16 17 Wdg.Resistance,HVN 1R12R1 1Y12Y1 1B12B1 Resistanceat750C R Y B Factory Value at 750C R Y B Remarks OTIreading: WTIreading:
FactoryTestReportRef.NO: ii). INTERMEDIATEVOLTAGESIDE: BetweenWinding Resistance AtSite 2R1N 2Y1N 2B1N iii). LOWVOLTAGESIDE: Page9of72 Resistanceat750C Factory Remarks
Site
Site
Resistanceat750C Factory
Remarks
NOTE: LV WINDING RESISTANCE AT FACTORY MEASURED WITHOUT FORMATION OF DELTA. HOWEVER MEASUREMENTS CARRIED OUT AT SITE ARE AFTER FORMATION OF DELTA. HENCE A CORRECTIONFACTOROF1.5TIMESTOBEAPPLIEDINSITERESULTS. L)MAGNETICBALANCETEST: Applysinglephase230VacrossonephaseofHVwindingterminalandneutralthenmeasurevoltage inothertwoHVterminalsacrossneutral.Repeatthetestforeachofthethreephases. Apply 1ph, 230V AC VoltagemeasuredinVolts across(1) Between(2) Between(3) 2R1N 2Y1N 2B1N 2Y1N 2R1N 2B1N 2B1N 2Y1N 2R1N M)FLOATINGNEUTRALVOLTAGEMEASUREMENT Disconnectthetransformerneutralfromtheground Apply 3 phase 415 volts to the high voltage winding and make the measurement in the IV winding withrespecttoneutralandneutralpointtoground. TapPosition Normal() Normal() Normal() HVWinding 1RN 1YN 1BN Voltage Applied IVWinding 2RN 2YN 2BN NEarth Voltage Measured Remarks, any if Remarks
Apply 3 phase 415 volts to the intermediate voltage winding and make the measurement in the tertiarywindingwithrespecttoneutralandneutralpointtoground. IVWinding 2RN 2YN 2BN VoltageApplied LVWinding 3RN 3YN 3BN NEarth Voltage Measured Yes/No Remarks,ifany
Check:Afterthetest,neutralreconnectedtoGround: N)MAGNETISATIONCURRENTTEST:
Page10of72
TestingInstrumentdetail: TestingInstrumentCalibrationvalidornot: Ambienttemperatureatthetimeoftest: TemperatureofOIL: i). APPLY1PHASEACSUPPLYONHVTERMINALSANDKEEPIV&LVOPEN TapPosition Voltage Current Factory test Remarks Applied(V) Measured(mA) value Lowest() RN Rph YN Yph BN Bph Normal() RN Rph YN Yph BN Bph Highest() RN Rph YN Yph BN Bph ii). APPLY1PHASEACSUPPLYONIVTERMINALSANDKEEPHV&LVOPEN TapPosition Voltage applied Currentmeasured Remarks (Volts) inLVside(mAmps) Normal() 2RN 2YN 2BN P)VOLTAGERATIOTEST: TestingInstrument(TRM)detail: TestingInstrumentCalibrationvalidornot: Ambienttemperatureatthetimeoftest: TemperatureofOIL: i). RatioHV/IV Tap Pos 1 2 3 4 5 6 7 8 9 10 11 12 Voltageapplied 1RN 1YN 1BN Voltagemeasured 2RN 2YN 2BN Page11of72 Ratio R FactoryRatio R Y
13 14 15 16 17
ii). RATIO:HV/LV Tap Voltageapplied Position 1RN 1YN 1BN Lowest Normal Highest iii). RATIO:IV/LV Voltagemeasured 3RN 3YN 3BN Ratio R Y FactoryRatio R Y
Tap Voltageapplied Voltagemeasured Ratio Position 2RN 2YN 2BN 3RN 3YN 3BN R Y Lowest Q)OILCHARACTERISTICS: Date: OTIreading: Time: AmbientTemp: WTIreading:
FactoryRatio R Y B
SampletobecollectedbeforeCharging&followingvaluetobeachieved: BDV:Min70kV MoistureinPPM:Min10 Tandelta(900C):Max0.1 Resistivity:Min6x1012Ohmcm InterfacialTensionat270C:Min0.035N/m OILSample BDV(kV) Moisture (PPM) Tandelta Resistivity (Ohmcm) Inter facial tension (N/m) Remarks
GASES
Before Charging
S)TestonOLTC: Sl No 1 2 3 4 5 6 7 8 9 10 11 12 T)OPERATIONALTESTOFOTHEREQUIPMENTS i). CHECKINGOFCOOLINGEQUIPMENTS a) RotationDirectionofPumps: OK b) RotationDirectionofFans: OK ii). PROTECTIONCHECKS Eqpt. SettingValue FanNo 1 2 3 4 5 6 Status OK NotOK Visualinspectionofequipment Manual operation on all taps ( local ) with confirmation oftheno.ofrevolutionsandLockingatextremetaps Overloaddeviceofdrivingmotor Localoperation(Electrical) Remoteoperation(Electrical) Tappositionindicator CheckoperationwithMasterFollowerscheme(parallel operation) Outofsteprelay StepbyStepContactor LimitSwitch Windingresistanceatalltaps Continuity test of winding during one Complete cycle of operation Description Remarks
Page13of72
7 8 9 10 11 12 PumpNo 1 2 3 4
U)INSULATIONRESISTANCEMEASUREMENTOFBUSHINGCTs:(USING500VMEGGER) Between EarthCoreI EarthCoreII EarthCoreIII EarthCoreIV CoreICoreII CoreICoreIII CoreICoreIV CoreIICoreIII CoreIICoreIV CoreIIICoreIV HV Rph IV Rph Neutral Yph Bph Rph LV Yph
Yph
Bph
Bph
V)CONTINUITYTESTOFBUSHINGCT's Core CoreI CoreII CoreIII CoreIV Between Terminal 1S11S2 2S12S2 3S13S2 4S14S2 HV Rph IV Rph Neutral Yph Bph Rph LV Yph
Yph
Bph
Bph
W)SECONDARYWINDINGRESISTANCEOFBUSHINGCT's(INOHM) i). HVSIDE Core COREI COREII COREIII COREIV Between Terminal 1S11S2 2S12S2 3S13S2 4S14S2 RPhase() Factory Site YPhase() Factory BPhase() Factory
Site
Site
Page14of72
ii). IVSIDE Core Between Terminal COREI 1S11S2 COREII 2S12S2 COREIII 3S13S2 COREIV 4S14S2 iii). LVSIDE Core COREI COREII COREIII COREIV Between Terminal 1S11S2 2S12S2 3S13S2 4S14S2 RPhase() Factory Site YPhase() Factory BPhase() Factory
Site
Site
YPhase() Factory
Site
BPhase() Factory
Site
iv). NEUTRALSIDE Core COREI Between Terminal 1S11S2 NEUTRAL() Factory Site
RPH COREI 1S1(+ve) 1S2(ve) COREII 2S1(+ve) 2S2(ve) COREIII 3S1(+ve) 3S2(ve) COREIV 4S1(+ve) 4S2(ve) ii). POLARITYOFLV&NeutralBCT CORE COREI COREII COREIII COREIV Between 1S1(+ve) 2S1(+ve) 3S1(+ve) 4S1(+ve) 1S2(ve) 2S2(ve) 3S2(ve) 4S2(ve) RPH
BPH
RPH
BPH
LV YPH
Neutral BPH
Page15of72
CORE S1S2 COREI (1S11S2) COREII (2S12S2) COREIII (3S13S2) COREIV (4S14S2)
Primary % 20% 40% 80% 20% 40% 80% 20% 40% 80% 20% 40% 80%
Current Actual
Secondary Current
Theoretical Ratio
Actual Ratio
% Error
ii). YPHASE:HVSIDE CORE S1S2 COREI (1S11S2) COREII (2S12S2) COREIII (3S13S2) COREIV (4S14S2) iii). BPHASE:HVSIDE CORE S1S2 COREI (1S11S2) COREII (2S12S2) COREIII (3S13S2) COREIV (4S14S2) Primary % 20% 40% 80% 20% 40% 80% 20% 40% 80% 20% 40% 80% Current Actual Page16of72 Secondary Current Theoretical Ratio Actual Ratio % Error Primary % 20% 40% 80% 20% 40% 80% 20% 40% 80% 20% 40% 80% Current Actual Secondary Current Theoretical Ratio Actual Ratio % Error
iv). RPHASE:IVSIDE CORE S1S2 COREI (1S11S2) COREII (2S12S2) COREIII (3S13S2) COREIV (4S14S2) Primary % 20% 40% 80% 20% 40% 80% 20% 40% 80% 20% 40% 80% Current Actual Secondary Current Theoretical Ratio Actual Ratio % Error
v). YPHASE:IVSIDE CORE S1S2 COREI (1S11S2) COREII (2S12S2) COREIII (3S13S2) COREIV (4S14S2) vi). BPHASE:IVSIDE CORE S1S2 COREI (1S11S2) COREII (2S12S2) COREIII (3S13S2) Primary % 20% 40% 80% 20% 40% 80% 20% 40% 80% Current Actual Page17of72 Secondary Current Theoretical Ratio Actual Ratio % Error Primary % 20% 40% 80% 20% 40% 80% 20% 40% 80% 20% 40% 80% Current Actual Secondary Current Theoretical Ratio Actual Ratio % Error
COREIV (4S14S2)
(NOTTOBEDONEFORMETERINGCORE) KNEEPOINTVOLTAGE(KVP)= i). RPHASE:HVSIDE VOLTAGE Tobeapplied Actual Value 0.25xKVP 0.50xKVP 0.75xKVP 1.00xKVP 1.10xKVP ii). YPHASE:HVSIDE VOLTAGE Tobeapplied Actual Value 0.25xKVP 0.50xKVP 0.75xKVP 1.00xKVP 1.10xKVP iii). BPHASE:HVSIDE VOLTAGE Tobeapplied Actual Value 0.25xKVP 0.50xKVP 0.75xKVP 1.00xKVP 1.10xKVP iv). RPHASE:IVSIDE VOLTAGE Tobeapplied Actual Value 0.25xKVP 0.50xKVP 0.75xKVP 1.00xKVP 1.10xKVP
COREIV 4S14S2
COREIV 4S14S2
COREIV 4S14S2
COREIV 4S14S2
v). YPHASE:IVSIDE VOLTAGE Tobeapplied Actual Value 0.25xKVP 0.50xKVP 0.75xKVP 1.00xKVP 1.10xKVP vi). BPHASE:IVSIDE VOLTAGE Tobeapplied Actual Value 0.25xKVP 0.50xKVP 0.75xKVP 1.00xKVP 1.10xKVP AA)CONTACTRESISTANCEMEASUREMENT:At100AMPS NOTE:THEVALUEOFCONTACTRESISTANCESHOULDNOTBEMORETHAN10PERJOINT/ CONNECTOR CONTACTRESISTANCE AcrossHVBushingTerminalBushing AcrossIVBushingTerminalBushing AcrossLVBushingTerminalBushing AcrossNeutralBushingTerminalBushing AcrossSurgeArrestorConnection AB)BUSHINGDETAILS: DrawingNo.__________________________________ Details Make Type Sl.No Rph HVSide Yph IVSide Yph LVSide Yph Neutral Bph RPH() YPH() BPH()
COREIV 4S14S2
COREIV 4S14S2
Bph
Rph
Bph
Rph
TestingInstrumentCalibrationvalidornot: Ambienttemperatureatthetimeoftest: TemperatureofOIL: i). HVSIDE VOLTAGE RPHASE SITE CAPACITANCE(MeasuredValue) YPHASE BPHASE FACTORY SITE FACTORY SITE FACTORY TANDELTA(MeasuredValue) YPHASE BPHASE FACTORY SITE FACTORY SITE FACTORY Remarks
Remarks
RPHASE SITE
RPHASE SITE
Remarks
RPHASE SITE
Remarks
AD)TANDELTAANDCAPACITANCEMEASUREMENTOFWINDINGS TestingInstrumentdetail:____________________________________________________ TestingInstrumentCalibrationvalidornot:___________________ Ambienttemperatureatthetimeoftest:_______________ TemperatureofOIL:__________________ Voltage 2kV 10kV Winding Test Combination Mode HVIV/LV UST CAPACITANCE Site Factory Page20of72 TANDELTA Site Factory Remarks
AD)SHORTCIRCUITIMPEDANCETEST TestingInstrumentdetail:____________________________________________________ TestingInstrumentCalibrationvalidornot:___________________ Ambienttemperatureatthetimeoftest:_______________ TemperatureofOIL:__________________ i). HVTOIV TapNo. 1U1(R) (IV OF R AND N SHORTED,LVOPEN) Voltage(V) Current(A) 1V1(Y) (IV OF Y AND N SHORTED,LVOPEN) Voltage(V) Current(A) 1W1(B) (IV OF B AND N SHORTED,LVOPEN) Voltage(V) Current(A)
LOWEST NORMAL HIGHEST ii). IVTOLV(NORMALTAP) SUPPLY SHORT ALL 3 LV BUSHINGS,HVOPEN 2U1N ____________A 2V1N 2W1N iii). HVTOLV(NORMALTAP) SUPPLY SHORT ALL 3 LV BUSHINGS,HVOPEN 1U1N ____________A 1V1N 1W1N ATLOWESTTAP SUPPLY SHORT ALL 3 LV BUSHINGS,HVOPEN 1U1N ____________A 1V1N 1W1N ATHIGHESTTAP
Page21of72
SUPPLY
1U1N 1V1N 1W1N AE)PROTECTIONANDALARMS SL Device No 1. ExcessiveWindingTemperature 2. ExcessiveOilTemperature 3. OilFlowFailure 4. PressureReliefValve 5. MainTankBuchholzrelay 6. OLTCBuchholzrelay 7. FanFailure 8. LowOilLevelGauge(MOLG) 9. Differentialrelay 10. OverloadRelay 11. REF 12. OverCurrent 13. Intertrip,ifany 14. TripFreeCheck 15. BackupOverCurrent 16. OverFlux AF)DETALSOFPROTECTIONSETTINGS: i). DIFFERENTIALPROTECTION:
OverexcitationInhibitFunction
Enabled
Page22of72
e. TDMultiplier f. TReset
______
_________
__________
______
_________
______
_________
d. EarthFaultSettings: OK/NotOK AG)STABILITYTESTOFDIFFERENTIAL&REFPROTECTION: NOTE : Prove the tripping of associated breakers by actual operation of the various devices and relaysaspertheschemes. AH)FREQUENCYRESPONSEANALYSIS(FRA) Page23of72 PS TMS HS
__________
______
_________
AI)allelectricaltestresultscomparedwithFactorytestresultsandfoundtobeinorder:Yes/No CHECKSAFTERCHARGINGOFTRANSFORMER AK)RECORDTHEFOLLOWINGAFTERCHARGING: i). Anyabnormalsoundemanatingfromthetransformer:Yes/No/Remarks ii). Noloadcurrentatrelayterminal: RPhase:______________A YPhase:__________________A BPhase:___________________A CTR:______________________ iii). TemperatureatthetimeofCharging: OTI WTI :_____________0C :_____________0C
Ambienttemperature:______________0C iv). MAXIMUMTEMPERATUREAFTER24HOURS:___________0C v). OLTC electrical operation checked in idle charged condition from min position to max positionandbacktonormalposition: YES/NO vi). Thermovisionscanningdoneatleastafter24hours ofloadingandrepeatedafteroneweek: YES/NO. AL)FINALDOCUMENTATIONREVIEW i). FACTORYTESTRESULTSAREAVAILABLE: YES/NO
Page24of72
iii). DOCUMENTSREGARDINGSPARES,EQUIPMENT,O&M MANNUALSETCAVAILABLEATSITEFORO&MPURPOSE: iv). AFTERMODIFICATION,IFANY,"ASBUILTDRAWINGS" AREAVAILABLEATSITE: Signature: Name: Designation: (SupplierRep) Signature: Name: Designation: ErectionAgency:
YES/NO
YES/NO
Page25of72
Voltagelevel,kV
CurrentCarryingCapacity:___________A TypeofOperatingMechanism: ControlVoltage:______________VoltDC 1) DETAILS: SL No YES 1. Equipment is free from dirt/dust Foreign materials etc. 2. Equipment is free from all visible defects on physical inspection 3. Support structures, marshalling box Has been providedwithtwoearthingPads/points 4. All nuts and bolts are tightened correctly as per specifiedtorque 5. Equipment erection is complete in all respect as per instruction manual (attach remaining activities, if any) 6. Permanent isolator levelling and identification is done 7. Levelling and alignment of structure and base frame ischecked NO DESCRIPTION STATUS REMARKS, ANY IF
Page26of72
8.
9.
10. Auxiliary contacts and relays have been cleaned and freefromrust/damage 11. Coronaringsareprovidedandproperlyfixed
14. All the cable identification tags provided and all cores are provided with identification ferrules at M.B. 15. Allmovingpartsarelubricated
16. Alignment of isolator already made and locking bolt provided,ifany 17. FreenessofmanualoperationisOK
18. Greasing has been made on the main contacts accordingtothemanufacturersinstruction 19. Functional checking of auxiliary Contacts for indicationsandinterlocks 20. Erection completion certificate along with list of outstandingactivitiesreviewed 21. All spare wires to be kept with ferrules but not terminatedattheterminalblocks 22. Earth switch connected to earth through braided wires 23. Interlocks checked as per approved scheme with all combinations 24. CheckthatearthswitchbladealignmentIncondition isatsufficientdistantfromIsolator 25. Check that operation and positioning of the limit switch&theauxiliarycontactsassemblyareok 26. Check that all three phase isolators are Closing & Page27of72
28. Provision of bimetallic strips ensured wherever applicable 2) MOTORDETAILS: a) Make: b) Sl.No: c) Type: d) HP/KW: e) Volt: f) Ampere:
g) YearofManufacture: h) OverloadSettings: i) Insulation Resistance of Motor Winding (Winding to Earth): (By 500 V Megger):_____________M. 3) ISOLATOROPERATIONALCHECK: a) OperatetheIsolatorandrecordthemotorcurrent: a. Open:_________________A b. Close:_________________A b) OPERATIONOFISOLATORFROMLOCAL/REMOTE: IsolatorOperation LOCAL Open Close c) MEASUREMENTOFOPERATINGTIME OPERATION RPhase CLOSING(Sec) OPENING(Sec) d) AUXILLARYCONTACTSCHECKING Page28of72 PHASE YPhase BPhase CONTROLPANEL REMOTE OK/NOTOK
ISOLATOR
AUXILIARY RPHASE NO NC
INSULATIONRESISTANCETEST(USING5000VOLTMEGGER): ISOLATOROPENCONDITION BETWEEN RPhase MalesidetoGround FemalesidetoGround MalesidetoFemaleside PHASE YPhase BPhase
5)
CONTACTRESISTANCEMEASUREMENT: (TOBEMEASUREDAFTER50OPERATIONS) a) ISOLATORCLOSECONDITION (CONTACTRESISTANCESHOULDBELESSTHAN10/CONNECTOR) ACROSS PHASE RPhase() CONNECTOR(MALESIDE) CONNECTOR(FEMALESIDE) MAINCONTACT(MALE&FEMALE) b) ISOLATOROPENCONDITION&GROUNDSWITCHCLOSE (CONTACTRESISTANCESHOULDBELESSTHAN150/BREAK) Page29of72 YPhase() BPhase()
YES/NO
c)
Signature: Name: Designation: (SupplierRep) Signature: Name: Designation: ErectionAgency: Signature: Name: Designation: SiteI/C,AEGCL Signature Name: Designation: T&C,AEGCL
Page30of72
ASSAMELECTRICITYGRIDCORPORATIONLIMITED PRECOMMISSIONINGOFWAVETRAP
COMMISSIONINGFORMATS DOCNO: BAYNO: SUBSTATION: DATEOFTESTING:
Voltagelevel,kV
1. DETAILS:CHECKLIST/TESTING SL No YES 1. Equipment is free from dirt/dust Foreign materials etc. 2. Equipment is free from all visible defects on physical inspection 3. Support structures, has been provided with two earthingPads/points 4. All nuts and bolts are tightened correctly as per specifiedtorque 5. Permanent isolator levelling and identification is done 6. Levelling and alignment of structure and base frame ischecked 7. All insulators & line matching unit are free from any physicaldefects 8. Tightness of nuts / bolts of terminal connectors are checked Page31of72 NO DESCRIPTION STATUS REMARKS, ANY IF
9.
10. Check that the tuning unit and Arrestor are properly tightenedAndfreefromanydamage 2. INSULATIONRESISTANCEMEASUREMENT: SL NO Upper Terminal 5000V &Earth LA of the Wave 500V Trap 3. CONTACTRESISTANCEMEASUREMENT: THEVALUESHOULDNOTMORETHAN5PERCONNECTOR/JOINT SL No 1 2 4. FINALDOCUMENTATIONREVIEW: a) Finaldocumentofprecommissioningchecks ReviewedandApproved: Documentsregardingspares,equipment,O&M Manualsetc.availableatsiteforo&mpurpose: Aftermodification,ifany,"asbuiltdrawings" areavailableatsite: ACROSS UpperTerminal BottomTerminal RPhase() PHASE YPhase() BETWEEN MEGGER RPHASE PHASE YPHASE
1M
BPhase()
YES/NO
b)
YES/NO
c)
YES/NO
Page32of72
ASSAMELECTRICITYGRIDCORPORATIONLIMITED
PRECOMMISSIONINGOFSF6CIRCUITBREAKER
COMMISSIONINGFORMATS DOCNO: SUBSTATION:
BAYNAME/NO: DATEOFERECTION:
DATEOFENERZIZATION:
Voltagelevel,kV
RATEDBREAKINGCAPACITY:
DESCRIPTION
STATUS YES NO
REMARKS,RECORD DEFICIENCIES,IFANY
1. 2. 3. 4. 5.
6. 7. 8.
Equipment is free from dirt/dust Foreign materialsetc. Equipment is free from all visible defects on physicalinspection Support structures, has been provided with two earthingPads/points All nuts and bolts are tightened correctly as per specifiedtorque Equipment erection is complete in all respect & erectioncompletionCertificatealongwithlistof Outstandingactivitiesreviewed. (ATTACHREMAININGACTIVITIES,IFANY) Permanent pole levelling and Identification is done Levelling and alignment of structure and base frameischecked Control box / marshalling kiosk is free from any
Page33of72
physicaldefects 9. Tightness of nuts bolts of terminal connectors arechecked i) Auxiliary contacts and relays have been cleanedandfreefromrust/damage ii) All spare wires to be kept with ferrules but notterminatedattheterminalblocks iii) Check all the valves in the SF6 pipe line are tightened,dilocouplingaretightened. Slow and power closing operation and opening done.(whereverapplicable) OperatingSystem a) Closing
10.
11. 12.
i). Hydraulic ii). Spring iii). Pneumatic b) Opening i). Hydraulic ii). Spring iii). Pneumatic HYDRAULICSYSTEM ACCUMULATOR a) b) Make SerialNo: Rph: YPh BPh Type YearofManufacture
12.1.
12.1.1.
c) d)
Page34of72
Autoreclosinglockout Generallockout
____________________ _____________________
VentingofHydraulicSystemisdone: a) b) c) d) PREFILLINGPRESSUREOFN2 INACCUMULATOR(BARatDeg.C) Pumprunningtimeforcharging Hydraulicsystemfrominitialpressure toworkingpressure CHECKINGSAFETYVALVE(OPEN/CLOSE) HYDRAULICPRESSUREDROPFOR1HR BREAKERONPOSITION BREAKEROFFPOSITION OILPRESSUREMONITOR PUMPON/OFFBAR PUMPRUNNINGTIME AUTORECLOSINGLOCKOUT(OIL) Page35of72 _________ _________ BAR SEC _______ _______ _________ BAR _______ _________ BAR _______ _________ BAR ________ _________ MIN ________ FACTORYTEST _______at C
0
Pump
PilotValve Accumulator
HydraulicMechanism
SITETEST ______at0C
FACTORYTEST PRESSURECONTACT__________MAKE/BREAK_________ CLOSINGLOCKOUT(OIL) PRESSURECONTACT__________MAKE/BREAK_________ GENERALLOCKOUT(OIL) PRESSURECONTACT__________MAKE/BREAK_________ CHECKINGANTIPUMPINGCONTACTOR PRESSURECONTACT__________MAKE/BREAK CHECKINGLOSSOFNITROGEN PRESSURECONTACT__________MAKE/BREAK BAR BAR BAR
SITETEST _______
_______
_______
OK/NOTOK
OK/NOTOK
12.1.5. OILPRESSUREDROPDURINGOPERATIONSANDPUMPRUNNINGTIMEINSECONDS Sl No 1 Pressurebeforeoperation,BAR PressureafterClosingoperation,BAR Pumprunningtime,Sec 2 Pressurebeforeoperation,BAR PressureafterOpeningoperation,BAR Pumprunningtime,Sec 3 Pressurebeforeoperation,BAR PressureafterClose/Openoperation,BAR Pumprunningtime,Sec 4 Pressurebeforeoperation,BAR PressureafterOpenCloseOpenoperation,BAR Pumprunningtime,Sec 12.2. SPRINGOPERATINGSYSTEM Description FactoryTest Value SiteTest Value
Page36of72
ThermalOverloadSetting: DCcurrenttakenbyMotorforchargingtheSpring_______________Amp 12.2.2. DETAILSOFRELAYS/CONTACTORSUSED:SCHEMATICDRAWINGNO:____________ CIRCUITREFERENCE OilPressuremonitor Closinglockout Autoreclosinglockout Generallockout MAKE SerialNo. TYPE NO+NC
TIMETAKENBYTHESPRINGTOCHARGEFULLYAFTERCLOSINGOFBREAKER DETAILS RPHASE Factory Site Chargingtime 13. SF6DENSITYMONITORDETAILS Make Model SerialNo Rph: Yph: BPh: 13.1. SF6DENSITYMONITORSETTINGS PHASE DETAILS BLOCKING Factory RPH RefillAlarm OperationBlock Site DEBLOCKING Factory Site SF6GASFILLEDAT __________BAR AT_________0CON ____/_____/_____ QuantityofSF6GasFilled ACTUAL RPh YPh BPh ASPERSPEC RPh YPh BPh Remark YPHASE Factory Site BPHASE Factory Site
Page37of72
YPH
RefillAlarm OperationBlock
BPH
RefillAlarm OperationBlock
13.2. MEASUREMENTOFDEWPOINTOFSF6GAS: SLNO NOTE: Dew point measurement of SF6 gas needs to be done pole wise in close loop method withoutanywastageofsf6gas. 13.3. LEAKAGECHECK: SlNo Description RPhase A InitialfillingofSF6Gasat_____0C (ASperTemp.correctionchart) DropinSF6GasPressurein24Hrs Fillingpressureat________0C (Afteralltesting) Additionalleakagetestbycovering IndividualjointwithPolythene _____BAR _____BAR _____BAR Yes/No PHASE YPhase _____BAR _____BAR _____BAR Yes/No BPhase _____BAR _____BAR _____BAR Yes/No Description MeasuredValue
B C D
14. COILRESISTANCEMEASUREMENT: SLNO A PHASE RPhase COIL TRIPCOILI TRIPCOILII CLOSECOIL TRIPCOILI TRIPCOILII CLOSECOIL TRIPCOILI TRIPCOILII CLOSECOIL MEASURED VALUE() SERIES RESISTOR() TOTAL ()
YPhase
BPhase
15. CIRCUITARY/OPEARTIONALCHECKS:
Page38of72
SLNO A B C D E F G H I J
CIRCUITREFERENCE TrippingthroughTCI TrippingthroughTCII Closingcircuit ANTIPUMPINGOPERATION (CloseOpenoperation) POLEDiscrepancyfeature BreakerPositionIndication HeaterinSwitchCubicle HeaterinControlCubicle IlluminationinSwitchCubicle IlluminationinControlCubicle
NOTE : In case wiring for remote operation is not ready, please indicate terminal number along with wire ferrule number in switch cubicle where remote cables shall be terminated. Remote operationcanbecheckedfromtheseterminals. 16. OPERATINGTIME(INMILLISECONDS): PHASE RPHMainContact RPHPIR AUXILIARYContact RPHMainContact RPHPIR AUXILIARYContact YPHMainContact YPHPIR AUXILIARYContact YPHMainContact YPHPIR AUXILIARYContact BPHMainContact BPHPIR AUXILIARYContact BPHMainContact BPHPIR AUXILIARYContact BREAK BREAKI BREAKII BREAKI BREAKII BREAKI BREAKII CLOSE OPEN TRIPI TRIPII CLOSEOPENUSING TRIPI TRIPII
18. IRVALUEWITHBREAKEROPEN:(Using5000VMegger) ACROSSOPENCONTACT RPhaseBreakI RPhaseBreakII YPhaseBreakI YPhaseBreakII BPhaseBreakI BPhaseBreakII MEASUREMENTVALUE(M)
19. IR VALUE WITH RESPECT TO EARTH WITH BREAKER CLOSED, EARTH SWITCH AND ISOLATOR OPEN:(USING5000VOLTMEGGER) BETWEEN RPHASEandEARTH YPHASEandEARTH BPHASEandEARTH 20. MINIMUMPICKUPVOLTAGEOFCOILS: COILDETAILS RPhaseTripCoilI RPhaseTripCoilII RPhaseClosingCoil YPhaseTripCoilI YPhaseTripCoilII YPhaseClosingCoil BPhaseTripCoilI BPhaseTripCoilII BPhaseClosingCoil 21. GRADINGCAPACITOR: 21.1. DETAILS MEASUREMENTVALUE(V) MEASUREMENTVALUE(M)
Page40of72
DETAILS
INTERRUPTER1 R Y B
INTERRUPTER2 R Y B
CAPACITANCEANDTANDELTAMEASUREMENT:(TobedoneonUSTmode) DESCRIPTION R CAPACITANCE: SITE FACTORY TANDELTA: FACTORY SITE INTERRUPTER1 Y B R INTERRUPTER2 Y B
22. CONTACTRESISTANCEMEASUREMENT: SL NO 1 2 3 23. BREAKEROPERATIONCOUNTERREADING: Sl No 1 2 3 PHASE COUNTER TYPE ELECTRICAL READING DATE MECHANICAL RPhase YPhase BPhase PHASE ACROSSEACHPOLE FACTORY SITE INTERRUPTER1 FACTORY SITE INTERRUPTER2 FACTORY SITE
Sl DESCRIPTION NO TEST 1
RESULT OK NOT OK Source I/II DC Switch off the DC Control source in control cubicle DC Fail,ACFail Switch cubicle ON/OFF Source I/II DC Switch off the AC Control source in control cubicle AC Fail,ACFail cubicle Switch ON/OFF ShorttheALARMcontactsofSF6GASDensityMonitor RPhase DENSITY SF6 GAS DENSITY MONITOR LOW YPhase DENSITY SF6 GAS DENSITY MONITOR LOW BPhase DENSITY SF6 GAS DENSITY MONITOR LOW RemovethecableconnectedtoDensityMonitor RPhase DENSITY OPERATION/CLOS MONITOR INGLOCKOUT YPhase DENSITY OPERATION/CLOS MONITOR INGLOCKOUT BPhase DENSITY OPERATION/CLOS MONITOR INGLOCKOUT Pole Give Tripping PD Relay at Breaker Discrepancy command to RPh CBCubicle only and check the operation of Pole DiscrepancyRelay Pole Give Tripping PD Relay at Breaker Discrepancy command to YPh CBCubicle only and check the operation of Pole DiscrepancyRelay Pole Give Tripping PD Relay at Breaker Discrepancy command to YPh CBCubicle only and check the operation of Pole DiscrepancyRelay BreakerAutoTrip Close the breaker Protection and Trip through relay as per Protection which scheme areapplicable
OF SOURCEOF INITIATION
WINDOW/HMI DESCRIPTION
REMARKS
27. FINALDOCUMENTATIONREVIEW: a) b) FactoryTestresultsareavailable Finaldocumentofprecommissioningchecks ReviewedandApproved: Documentsregardingspares,equipment,O&M Manualsetc.availableatsiteforo&mpurpose: Aftermodification,ifany,"asbuiltdrawings" areavailableatsite: YES/NO YES/NO
c)
YES/NO
d)
YES/NO
Page43of72
ASSAMELECTRICITYGRIDCORPORATIONLIMITED
PRECOMMISSIONINGOFCURRENTTRANSFORMER
COMMISSIONINGFORMATS DOCNO: SUBSTATION:
BAYNAME/NO: DATEOFERECTION:
DATEOFENERZIZATION:
RATIOSELECTION: Voltagelevel,kV
YEAROFMANUFACTURE: PURCHASEORDERNO: RATEDDATA&CLASSOFACCURACY: CORE WINDINGI WINDINGII WINDINGIII WINDINGIV WINDINGV 1.0 SL No i). ii). iii). iv). v). vi). DETAIL: DESCRIPTION STATUS YES NO REMARKS RECORD DEFICENCIES, IFANY RATIO BURDEN ACCURACY CLASS KNEE POINT VOLTAGE(KVP)
Equipmentiscleanedandfreefrom Dust/Dirtforeignmaterialsetc. Equipmentisfreefromallvisible defectsonphysicalinspection Checkcttankhasbeenprovided Withdoubleearthing(deadtankCTs) CheckthatCTjunctionboxisearthed Allnutsandboltsaretightened correctlyasperspecifiedtorque Checktightnessofterminalconnector
Page44of72
AllfittingsasperOutline GeneralArrangementdrawing. Levellingandalignmentofstructure andbaseframeischecked Erectioncompletioncertificatealong withlistofoutstandingactivities Reviewed Anypaintremoved/scratchedin transithasbeentouchedup CheckprimarypolarityofCT,s erectedasperrelevantdrawing. Checkhermeticallysealingisintact Checktheoillevelandleakage throughanyjoints/Sec.Terminals Checkoildrainvalveisproperly Closedandlocked. OilLevel&Oilsampling N2pressurechecked(whereverapplicable) Oillevelontopchambergaugeglass
xviii). BDVofoilsampletakenfromtank bottomdrainvalve(onlyifNitrogen Pressureismeasuredzero) xix). Allthecableidentificationtags providedandallcoresareprovided withidentificationferrulesatM.B. xx). Checksecondarycableendboxis properlyfixedandensurecableentry atthebottomandunusedholessealed xxi). Ensureinterpolecablingiscompleted Andcheckthecontinuity. xxii). ChecktheIRvalueofsecondarycable xxiii). Check external cabling from junction box to relay/controlpanelcompleted xxiv). Ensureunusedsecondarycores, ifany,hasbeenshorted xxv). Checkstarpointhasbeenformed properlyandgroundedatoneendonly xxvi). ChecksparkgapsettinginP1terminal (whereverprovided/possible) Permanentpolelevellingand identificationmarkingsmade xxvii). CheckTANDELTAtesttapisproperly earthed xxviii). Check that lugs used in secondary circuit are ofringtype xxix). Check direction of PRIMARY (P1/ P2) w.r.t.
Page45of72
xxx). 2.0
INSULATIONRESISTANCEMEASUREMENT:(USING5KVMEGGER) SlNo.ofMegger: Make: Calibrationvalidupto:_____/______/______ Ambienttemperature:_______0C RelativeHumidity: NOTE: A)RemovetheconnectedearthingtosysteminvolvingCTundertest B)DisconnecttheconnectedterminalsofCTM.Box C)Permissiblevaluesis1000M.
SL No 1 2 3 4 5 6 CORE PRIMARYCOREI PRIMARYCOREII PRIMARYCOREIII PRIMARYCOREIV PRIMARYCOREV PRIMARYEARTH RPhase(M) PHASE YPhase(M) BPhase(M)
3.0 INSULATIONRESISTANCEMEASUREMENT:(Using500VMegger) SlNo.ofMegger: Make: Calibrationvalidupto:_____/______/______ Ambienttemperature:_______0C a) SL No 1 2 3 4 5 6 b) SL No CORE RPhase(M) Page46of72 PHASE YPhase(M) BPhase(M) CORE COREIEarth COREIIEarth COREIIIEarth COREIVEarth COREVEarth EARTHEarth RPhase(M) PHASE YPhase(M) BPhase(M)
1 2 3 4 5 6 7 8 9 10 4.0
COREICOREII COREICOREIII COREICOREIV COREICOREV COREIICOREIII COREIICOREIV COREIICOREV COREIIICOREIV COREIIICOREV COREIVCOREV
5.0
Calibrationvalidupto:_____/______/______ Ambienttemperature:_______0C CORE TERMINAL RPHASE Factory COREI 1S11S2 1S11S3 1S11S4 COREII 2S12S2 2S12S3 2S12S4 COREIII 3S13S2 3S13S3 3S13S4 COREIV 4S14S2 4S14S3 4S14S4 COREV 5S15S2 5S15S3 Site YPHASE Factory Site BPHASE Factory Site
Page47of72
COREI
1S2(Ve) 1S3(Ve) 1S4(Ve) 2S2(Ve) 2S3(Ve) 2S4(Ve) 3S2(Ve) 3S3(Ve) 3S4(Ve) 4S2(Ve) 4S3(Ve) 4S4(Ve) 5S2(Ve) 5S3(Ve) 5S4(Ve)
COREII
COREIII
COREIV
COREV
7.0 TANDELTAANDCAPACITANCEMEASUREMENT SlNo.ofTestKit: Make: Calibrationvalidupto:_____/______/______ DateofTesting:______/______/______ Ambienttemperature:_______0C a) CAPACITANCEMEASRUEMENT VOLTAGE CAPACITANCE(MEASUREDVALUE) RPhase FACTORY SITE 2kV YPhase FACTORY SITE BPhase FACTORY SITE REMARKS
Page48of72
10kV b)
TANDELTAMEASUREMENT VOLTAGE TANDELTA(MEASUREDVALUE) RPhase FACTORY SITE 2kV 10kV YPhase FACTORY SITE BPhase FACTORY SITE REMARKS
8.0
Calibrationvalidupto:_____/______/______ DateofTesting:______/______/______ Ambienttemperature:_______0C a) RPHASE CORE PRIMARYCURRENT % ACTUAL COREI 20% (1S11S2) 40% 80% COREII 20% (2S12S2) 40% 80% COREIII 20% (3S13S2) 40% 80% COREIV 20% (4S14S2) 40% 80% COREV 20% (5S15S2) 40% 80% COREI 20% (1S11S3) 40% 80% COREII 20% (2S12S3) 40% 80% COREIII 20% (3S13S3) 40% SECONDARY CURRENT
THERITICAL RATIO
ACTUAL RATIO
% OF ERROR
Page49of72
80% COREIV 20% (4S14S3) 40% 80% COREV 20% (5S15S3) 40% 80% COREI 20% (1S11S4) 40% 80% COREII 20% (2S12S4) 40% 80% COREIII 20% (3S13S4) 40% 80% COREIV 20% (4S14S4) 40% 80% COREV 20% (5S15S4) 40% 80% b) YPHASE CORE
PRIMARYCURRENT % ACTUAL COREI 20% (1S11S2) 40% 80% COREII 20% (2S12S2) 40% 80% COREIII 20% (3S13S2) 40% 80% COREIV 20% (4S14S2) 40% 80% COREV 20% (5S15S2) 40% 80% COREI 20% (1S11S3) 40% 80% COREII 20% (2S12S3) 40% 80% COREIII 20% (3S13S3) 40%
SECONDARY CURRENT
THERITICAL RATIO
ACTUAL RATIO
% OF ERROR
Page50of72
80% COREIV 20% (4S14S3) 40% 80% COREV 20% (5S15S3) 40% 80% COREI 20% (1S11S4) 40% 80% COREII 20% (2S12S4) 40% 80% COREIII 20% (3S13S4) 40% 80% COREIV 20% (4S14S4) 40% 80% COREV 20% (5S15S4) 40% 80% c) BPHASE CORE
PRIMARYCURRENT % ACTUAL COREI 20% (1S11S2) 40% 80% COREII 20% (2S12S2) 40% 80% COREIII 20% (3S13S2) 40% 80% COREIV 20% (4S14S2) 40% 80% COREV 20% (5S15S2) 40% 80% COREI 20% (1S11S3) 40% 80% COREII 20% (2S12S3) 40% 80% COREIII 20% (3S13S3) 40%
SECONDARY CURRENT
THERITICAL RATIO
ACTUAL RATIO
% OF ERROR
Page51of72
80% COREIV 20% (4S14S3) 40% 80% COREV 20% (5S15S3) 40% 80% COREI 20% (1S11S4) 40% 80% COREII 20% (2S12S4) 40% 80% COREIII 20% (3S13S4) 40% 80% COREIV 20% (4S14S4) 40% 80% COREV 20% (5S15S4) 40% 80% 9.0
MAGNETISINGCURVESPERFORMANCE KNEEPOINTVOLTAGE(KVp)_______________VOLT SlNo.ofTestKit: Make: Calibrationvalidupto:_____/______/______ DateofTesting:______/______/______ Ambienttemperature:_______0C a) RPHASE VOLTAGE To be Actual applied Value 0.25xKVP 0.5xKVP 0.75xKVP 1.00xKVP 1.10xKVP b) YPHASE VOLTAGE To be Actual applied Value 0.25xKVP CURRENTMEASUREMENT(mA) COREI COREII COREIII COREIV 1S11S2 2S12S2 3S13S2 4S14S2 Not to Page52of72 COREV 5S15S2 CURRENTMEASUREMENT(mA) COREI COREII COREIII COREIV 1S11S2 2S12S2 3S13S2 4S14S2 Not to apply for Metering Core COREV 5S15S2
VOLTAGE To be Actual applied Value 0.25xKVP 0.5xKVP 0.75xKVP 1.00xKVP 1.10xKVP NOTE:
CURRENTMEASUREMENT(mA) COREI COREII COREIII COREIV 1S11S2 2S12S2 3S13S2 4S14S2 Not to apply for Metering Core
COREV 5S15S2
1.0CTshouldnotsaturateat110%ofkneepointvoltage(KVp) 2.0 If knee point voltage is not mentioned then knee point current may be taken into consideration 10.0 CONTACTRESISTANCEMEASUREMENT DetailsofTestKit: CONTACTRESISTANCE AcrossterminalP1 AcrossterminalP2 NOTE : The value of contact resistance should not be more than 10 PER JOINT / CONNECTOR. 11.0 DGATESTOFCTOIL(AFTERONEMONTHOFCOMMISSIONING) (Sampletobetakenat250mlbottle) DISOLVEGAS TotalGas% H2 CH4 C2H4 C2H6 C2H2 CO CO2 O2 N2 RPHASE YPHASE BPHASE REMARKS RPhase() YPhase() BPhase()
Page53of72
b)
YES/NO
c)
YES/NO
Page54of72
ASSAMELECTRICITYGRIDCORPORATIONLIMITED
PRECOMMISSIONINGOFCAPACITORVOLTAGETRANSFORMER
COMMISSIONINGFORMATS DOCNO: 132 SUBSTATION:
DETAILSOFEQUIPMENT: DESCRIPTION PURCHASEORDERNO MAKE TYPE SERIALNO CAPACITANCE(pF) SECONDARYDETAILS: DESCRIPTION VOLTAGE(V) VABURDEN(VA) CLASS PURPOSE 1.0 SL No i). ii). iii). iv). v). vi). vii). DETAILSOFCHECKLIST: DESCRIPTION WINDINGI WINDINGII WINDINGIII RPHASE YPHASE BPHASE
STATUS YES NO
Equipmentiscleanedandfreefrom Dust/Dirtforeignmaterialsetc. Equipmentisfreefromallvisible defectsonphysicalinspection CheckCVTtankhasbeenprovided Withdoubleearthing CheckthatCVTMarshallingBoxisearthed Allnutsandboltsaretightened correctlyasperspecifiedtorque Checktightnessofterminalconnector AllfittingsasperOutline GeneralArrangementdrawing.
Page55of72
viii).
Levelling and Identification marking is carriedout. ix). Levellingandalignmentofstructure andbaseframeischecked x). Erectioncompletioncertificatealong withlistofoutstandingactivities Reviewed xi). Anypaintremoved/scratchedin transithasbeentouchedup xii). Sl.NoofHVCAPACITORidenticaltothe Sl.nomentionedonRATING&DIG.PLATE xiii). Ensure brass vent plug between stacks of CVT'sisremoved xiv). Checktheoillevelandleakage throughanyjoints/Sec.Terminals xv). Checkoildrainvalveisproperly Closedandlocked. xvi). OilLevelontankGaugeGlass xvii). BDVofoilsampletakenfromtank bottomdrainvalve xviii). Checksecondarycableendboxis properlyfixedandensurecableentry atthebottomandunusedholessealed xix). EnsureH.Fterminalofunusedphases hasbeenearthedandnoloadon H.Fterminalbushing xx). CheckRATING/HEALTHINESSofFuses atCVTM.BandCVTterminalbox. xxi). Checkthattheneutralpointisearthed xxii). Ensureinterpolecablingiscompleted andcheckthecontinuity xxiii). ChecktheIRvalueofsecondarycable xxiv). Check external cabling from junction box to relay/controlpanelcompleted xxv). All the cable identification tags provided and all cores are provided with identification ferrulesatM.B. 2.0
3.0
CONTINUITYOFWINDING: (AfterremovingEarthLink1,2&3) SlNo BETWEENTERMINAL OK NOTOK A 1a1n B 2a2n C 3a3n INSULATIONRESISTANCEMEASUREMENT:(Using5kVMegger) DetailsofMegger: Page56of72
SLNo:
Type:
Make:
4.0
i) PrimarySecondaryCORE1 ii) PrimarySecondaryCORE2 iii) PrimarySecondaryCORE3 iv) PrimaryEarth INSULATIONRESISTANCEMEASUREMENT:(Using500VMegger) DetailsofMegger: SlNo BETWEEN i) SecondaryCORE1Earth ii) SecondaryCORE2Earth iii) SecondaryCORE3Earth iv) CORE1CORE2 v) CORE1CORE3 vi) CORE2CORE3 VOLTAGERATIOTEST: DetailsofTestingInstruments: PHASE PRIMARY R Y B SECONDARYVOLTAGE Between Value 1a1n 2a2n 3a3n 1a1n 2a2n 3a3n 1a1n 2a2n 3a3n THEORITICAL RATIO
5.0
% ERROR
6.0
SerialNo: Calibrationvalidupto:_____/______/______ DateofTesting:______/______/______ Ambienttemperature:_______0C a) CAPACITANCEMEASRUEMENT VOLTAGE CAPACITANCE(MEASUREDVALUE) RPhase FACTORY SITE 2kV 10kV a) TANDELTAMEASUREMENT VOLTAGE TANDELTA(MEASUREDVALUE) RPhase FACTORY SITE 2kV 10kV 7.0 FINALDOCUMENTATIONREVIEW: d) Finaldocumentofprecommissioningchecks ReviewedandApproved: Documentsregardingspares,equipment,O&M Manualsetc.availableatsiteforo&mpurpose: Aftermodification,ifany,"asbuiltdrawings" areavailableatsite: YPhase FACTORY SITE BPhase FACTORY SITE REMARKS YPhase FACTORY SITE BPhase FACTORY SITE REMARKS
YES/NO
e)
YES/NO
f)
YES/NO
Page58of72
ASSAMELECTRICITYGRIDCORPORATIONLIMITED
PRECOMMISSIONINGOFSURGEARRESTER
COMMISSIONINGFORMATS DOCNO: 33 132 SUBSTATION:
DETAILSOFEQUIPMENT: DESCRIPTION PURCHASEORDERNO MAKE TYPE SERIALNO RATING 1.0 SL No i). ii). iii). iv). v). RPHASE YPHASE BPHASE
Equipmentiscleanedandfreefrom Dust/Dirtforeignmaterialsetc. Equipmentisfreefromallvisible defectsonphysicalinspection Support structures have been provided with doubleearth Allnutsandboltsaretightened correctlyasperspecifiedtorque Equipment erection is complete in all respect (ATTACHREMAININGACTIVITIES,IFANY) Levelling and Identification marking is carriedout. Levellingandalignmentofstructure andbaseframeischecked All insulators & Surge counter are free from anyphysicaldefects Check tightness of all nuts & bolts and terminalconnector Erection completion certificate along with listofoutstandingactivities
Page59of72
xi).
xii).
xiii).
reviewed Checkoneendofsurgecounterisconnected to the bottom of la stack and one end of surgecounterhasbeenearth Thedirectionoftheexhaustventports away from the protected equipment and other arresterpoles Clearance from the arrester to earthed objects and from the arrester pole to another arrester pole maintained as per Outline drawing and all erection has been doneasperapproveddrawing. Check the serial no. and sequence of LA partsforerectioninmultistackLA CheckthealignmentofCoronaRing Check on charging, the Surge Counter pointerisingreenzone
PHASE YPhase(M)
BPhase(M)
3.0
BPhase
4.0
CAPACITANCE&TANDELTAMEASUREMENT: Page60of72
SlNo.ofTestKit: Make: Calibrationvalidupto:_____/______/______ DateofTesting:______/______/______ Ambienttemperature:_______0C VOLTAGE 2kV STACK TOP MIDDLE1 MIDDLE2 BOTTOM TOP MIDDLE1 MIDDLE2 BOTTOM CAPACITANCE TANDELTA REMARKS
10kV
5.0 6.0 CHECKINGOFHEALTHINESSOFSURGEMONITOR: FINALDOCUMENTATIONREVIEW: g) Finaldocumentofprecommissioningchecks ReviewedandApproved: Documentsregardingspares,equipment,O&M Manualsetc.availableatsiteforo&mpurpose: Aftermodification,ifany,"asbuiltdrawings" areavailableatsite: OK/NOTOK
YES/NO
h)
YES/NO
i)
YES/NO
Page61of72
ASSAMELECTRICITYGRIDCORPORATIONLIMITED
PRECOMMISSIONINGOF220kVLINERELAY&CONTROLPANEL
COMMISSIONINGFORMATS DOCNO: 33 132 SUBSTATION:
PurchaseOrderNo: TypeofPanel:SwingSimplex/Simplex/Duplex PanelOverallDimensions: RelaySpecificationsDetails: Sl No RelayType Make Relay Ordering Code Relay Compatibility IEC 61850 Type&Nos.of No.of Communication Analogue Channel Ports Modbus RJ45 Serial Nos.of BI&BO BI BO DCAuxiliaryVoltage:
1 2 3 1.0
DETAILS:CHECKLIST/TESTING a. Wiring
Sl No 1 2 3 4 5
As per norms Wiring done using PVC insulated 650 grade singlecore multi strands annealed copper conductor flexible wire. 2.5 Sqmm Red, Yellow, Blue & Black for CT Circuit 2.5 Sqmm Red, Yellow, Blue & Black for PT Circuit 2.5 Sqmm for 240V AC circuits 1.5 Sqmm Grey for DC circuits
Page62of72
Yes
No
Remarks
6 7
1.5 Sqmm Black for AC circuits 2.5 Sqmm Green for Earthing Circuit
b. Sl No 1 2 3
EARTHING: As per norms 1 no. Copper Bar of size 25 x 6 mm will be run throughout the board Earthing between equipments will be looped & finally terminated in Earth bar Earth bar coupling link of copper will be provided between adjacent panels Yes No Remarks
c. Sl No 1 2 d.
DC DISTRIBUTION
Sl No 1 2 3 4
As per norms Checking of DC Supervision Relay Source-1 Source-2 Changeover between Sources a) Electro Mechanical switch b) Through changeover relays e. VOLTAGE SELECTION RELAYS As per norms 75 A 75 B Check VTSS (BPT-LPT)
Yes
No
Remarks
Sl No 1 2 3
Yes
No
Remarks
Page63of72
f. Sl No 1 2 3 4 5 g. Sl No 1 2
METERING CIRCUIT As per norms W Meter VAR Meter V Meter A Meter TVM Meter SYNCHRONISING CIRCUIT As per norms Bus PT Supply Circuit Line CVT Supply Circuit Yes No Remarks Yes No Remarks
h. Sl No 1
CT CIRCUIT As per norms Metering Circuit Star Point Continuity Earthing should be either at CT JB or at Panel end Main Protection Circuit Star Point Continuity Earthing should be either at CT JB or at Panel end B/U Protection Circuit Star Point Continuity Earthing should be either at CT JB or at Panel end BBP Protection Circuit Star Point Continuity Earthing should be either at CT JB or at Panel end Yes No Remarks
i.
Input Circuit
Page64of72
Sl No 1 2 3 4 5
As per norms Main/TBC CB R phase Open Main/TBC CB Y phase Open Main/TBC CB B phase Open Main/TBC CB Ready for A/R Carrier Out of Service
Yes
No
Remarks
Sl No 6
As per norms External LBB/ A/R Initiation R phase Y phase B phase A/R Switch ON Carrier Channel I Healthy Carrier Channel II Healthy Carrier Channel I Received SOTF Initiation A/R Block Main CB Open Status R phase Y phase B phase TBC CB Open Status R phase Y phase B phase Main CB Ready for A/R TBC CB Ready for A/R j. Carrier circuit As per norms Carrier Channel I Received Carrier Channel I Healthy Carrier Channel I Send Carrier Channel II Send Carrier Channel II Received Carrier Channel II Healthy Carrier Channel I Send Carrier Channel II Send Direct Trip Received Channel I
Page65of72
Yes
No
Remarks
7 8 9 10 11 12
13
14 15
Sl No 1 2 3 4 5 6 7
Yes
No
Remarks
8 9 10 k. Sl No 1 2 3
Single Phase/ Three Phase Initiation Circuit As per norms 1 Trip R- : 86 R1 1 Trip Y- : 86 Y1 1 Trip B- : 86 B1 1 Trip R- : 86 R2 1 Trip Y- : 86 Y2 1 Trip B- : 86 B2 Master Trip Relay : 86 A Optd Distance Prot Optd. B/U Protection Optd. DT Received Ch-I DT Received Ch-II Master Trip Relay : 86 B Optd Distance Prot Optd. B/U Protection Optd. DT Received Ch-I DT Received Ch-II Auxiliary Trip Relay: 86 X (RL-1) Optd. Auxiliary Trip Relay: 86 X (RL-2) Optd. Yes No Remarks
l. Sl No 1 2
LBB Trip Relay Circuit As per norms LBB -96 Realy Optd. Check all the Trip Extensions as per scheme i) ii) iii) iv) v) vi)
Page66of72
Yes
No
Remarks
vii)
m. Sl No 1 2 3
As per norms DC Supply-1 to CB DC Supply-2 to CB Auto Reclose/ Remote Close Manual Trip-1 (TC-1)/ (TC-2)
n.
CB TC-1 / TC 2 Circuit (Protection Trip/Post Close Supn) & Pre Close Supervision
Sl No 1 2
As per norms 1- Optd. From Main Prot. Relay Group A Trip Optd. Group B Trip Optd.
Yes
No
Remarks
LBB/ BB Optd.
o.
Sl No 1
Yes
No
Remarks
2 p. Sl No 1 TBC TRIPPING CIRCUIT As per norms 86 A Extension 86 B extension 1- Trip Optd. From Main Protection Relay R Y B 2 To LBB Initiation TBC 86 R1 86 Y1 86 B1 86 R2 86 Y2 86 B2
Yes
No
Remarks
q.
Sl No 1
Yes
No
Remarks
Page68of72
89 A Open 89 B Close 89 B Open 89 C Close 89 C Open 89 D Close 89 D Open r. Sl No 1 INDICATION CIRCUIT As per norms CB Open CB Close CB Auto Trip CB Spring Charged 89 A Open 89 B Close 89 B Open 89 BE Close 89 BE Open 89 C Close 89 C Open 89 D Close 89 D Open 89 DE1 Close 89 DE1 Open 89 DE2 Close 89 DE2 Open Line Hot R- Healthy Line Hot Y- Healthy Line Hot B- Healthy
Yes
No
Remarks
s. Sl No 1 2 3 4 5
ANNUNCIATION CIRCUIT As per norms DC Fail AC Fail Main Dist Prot. Optd. O/C & E/F Optd. DEF/ SOTF Optd.
Page69of72
Yes
No
Remarks
6 7 8 9 10 11 12 13 14 15 16 t.
Carrier CH-I & II Fail A/R Optd. Power Swing Detected Panel AC Supply Fail LBB/BB Optd. Numerical Relay Faulty DT Received Ch-I & II CB TC-1 faulty CB TC-2 faulty SF6 Low Alarm SF6 Lock Out Main Distance Protection Relay
Sl No 1 2 3
As per norms Check CT Circuit (If any Mismatch) Check PT Circuit (If any Mismatch) Zone Reach Test
Yes
No
Remarks
4 5 6 7
ii) iii) 8 9 10 11
u.
Sl No 12 13 14 15 16 17
As per norms Under Frequency Optd. Over Voltage Optd. Directional B/U Relay Check CT Circuit (If any Mismatch) Check PT Circuit (If any Mismatch) Directionality Test i) Operating Zone ii) Non Operating Zone
Yes
No
Remarks
18 19
Page71of72
20
High Set
v. Sl No 1 2 3 4 5 6 7
ISOLATOR INTERLOCK CIRCUIT As per norms 89 A Interlock 89 B Interlock 89 BE Interlock 89 DE1 Interlock 89 DE2 Interlock 89 D Interlock 89 C Interlock Yes No Remarks
Page72of72