NextEnergy NXE
NextEnergy NXE
NextEnergy NXE
DATACENTRE TRANSPORT
NextEnergy
ONLINE Tower
• Efficiency up to 97% in latest UPS series designed for mission continuous operation and premium
critical applications as data centres, protection for your customers’ business.
double conversion communication networks, commercial and
NXE NXE
LOAD
Input » Output »
Batteries
complete front access for all maintenance MAXIMUM RELIABILITY OPERATION MODES
activities, ensures maximum space for AND AVAILABILITY The UPS can operate in many Operation
installation and service; The NextEnergy architecture and features Modes, in order to grant always the
• NextEnergy includes top and bottom cable deliver significant cost savings thanks maximum level of protection and
entry (on NXE 250, NXE 500 and NXE 600 to an easy adapting to new or existing maximum level of efficiency, based on
top on option); installations without impacting power mains quality and load type.
• Operation without Neutral: NextEnergy can infrastructure. This is possible through
work with (4 wire) or without (3 wire) the scalability, granting minimized initial ON LINE
neutral line connection (see below picture). investment (CAPEX), adding power cores ON LINE Mode (Double Conversion)
as business demands grow: provides the highest level of power
• Parallel configuration up to 8 units conditioning and protects the load from all
L1-L2-L3-N L1-L2-L3-N NextEnergy UPS can be connected in electrical network disturbance in terms of
parallel with up to 8 units to increase voltage and frequency. The overall AC/AC
the capacity or add redundancy (N+1). efficiency is up to 97%.
Parallel configuration with common or
separated battery is possible. ECO Mode
DB LOAD • Efficiency Control Mode (ECM) The load is normally powered from the
Considering that a typical UPS load can bypass line while the rectifier keeps the
vary from 20% to 80%, the ECM function battery charged. When the mains exceeds
4-wire (L1-L2-L3-N) installation
optimises the operating efficiency of the limits the load is automatically
a parallel UPS configuration according transferred in ON LINE Mode in approx.
to the power absorbed by the load: in 2 msec. The efficiency is more than 99%.
L1-L2-L3 L1-L2-L3
case of low load, it sets some UPS in
“freeze” mode, ensuring redundancy and
a working point of the “live” UPS in the
higher efficiency working point, during all
DB LOAD load conditions (see below picture).
• Hot System Expansion (HSE) allows the
addition of further UPS into an existing
3-wire (L1-L2-L3) installation system, without the need to switch off
the operational units or transfer them to
bypass mode.
This is an important feature to reduce
the TCO of the distribution system, where
the neutral line cable is not distributed
- savings investment - and the neutral is
created by an isolation transformer close
to the load.
This is a typical infrastructure solution
adopted by modern Data Centre or for
installations where the neutral is not
used at all, allowing not only reduced
cost for the distribution arrangements
but also effortless replacement of legacy
equipments.
THE UPS WORKS IN A LOW EFFICIENCY WORKING POINT THE ACTIVE UPS WORKS IN A HIGHER EFFICIENCY WORKING POINT
30%
% Efficiency
% Efficiency
15%
15 100 30 100
% Load % Load
4 UNITS 2 UNITS
300 kVA 15% PN 300 kVA 30% PN
ACTIVE ECO applied to the mains supply. In case of SMART CAPACITY TEST (SCT)
In this mode the NXE works as Active mains failure the transfer time on Inverter Thanks to the Smart Capacity Test
Filter: the bypass line is the priory source is approximately 0 (classified VFD SS (SCT) functionality (Load Test mode) the
and supplies the active power while the 111). Power factor correction plays an system can be tested onsite during the
inverter only provides the reactive part active role in reducing the installation’s commissioning, before it is connected
of the load. This ensures that the UPS TCO: it means reduction of Joule losses to the real load, without using costly
input power factor remains close to unity, and voltage drop, for an optimum sizing temporary loads, cabling and breakers
regardless of the load power factor. In of electrical equipment such as power and without wasting energy from the
addition, the inverter operation reduces transformers, cables, busbars, switch power network. In this condition the UPS
significantly the harmonic content (THDi) and protection devices. The electric output supplies energy to the input in re-
distribution is more efficient and stable. circulating mode. In this mode NextEnergy
Also the current distortion (harmonics) is low consuming, just the energy due the
generated by non-linear loads such as internal losses.
inverters, computers, drives and so on
causes several problems in an electric
system. It is important to reduce it.
ACTIVE ECO Mode combines high level
Combine high levels of availability with important CAPEX and
of AVAILABILITY OPEX reduction. The efficiency is more
with reduced than 98.5% Main LOAD
OPERATION MODES
→ → → → LOAD
→ → → LOAD
→ → → LOAD
→
→
→
MAINS
SWITCH
OUTPUT BYPASS
SWITCH SWITCH
MAINTENANCE
BYPASS MAINTENANCE
SWITCH BYPASS
BYPASS SWITCH
SWITCH
OUTPUT
MAINS SWITCH SWITCH
OUTPUT
SWITCH
OUTPUT
SWITCH MAINTENANCE
BYPASS
SWITCH
MAINS MAINTENANCE
SWITCH BYPASS BYPASS
SWITCH SWITCH
BYPASS
SWITCH MAINS
SWITCH
DETAILS
OUTPUT
SWITCH
MAINTENANCE
BYPASS
SWITCH
MAINS
SWITCH
BYPASS
SWITCH
DIMENSION
1900
1900
1900
0 0 0 1600 0 2000
800 85 1200 85 1400 85 85 8
NXE 600
NXE 800 2SW NXE 800
1900
1900
2000 0
85 2400
0
85
OPTIONS
BATTERY CABINET
Dimensions
1900
BB
[mm]
86
0 0
80
Dimensions
1900
1900
1900
1900
1900
1900
[mm]
1
6 0 8 0 120 200 0100
0
64 40 080 80 00 080
0 80 0 80
0 100
MODELS NXE 250 NXE 300 NXE 400
INPUT
Rated voltage [V] 380 / 400 / 415 three-phase
Voltage tolerance [V] 400 ±20% @ full load1
Frequency tolerance [Hz] 40 - 70
Power factor 0.99
THDI <3%
Soft Start 0 - 100% in 120 sec. (selectable)
Standard equipment provided Back feed protection, separate bypass line
BATTERIES
Type VRLA AGM / GEL, NiCd, Supercaps, Li-ion, Flywheels
Ripple current Zero
Recharge voltage compensation -0.11% x V x °C
OUTPUT
Nominal Power [kVA] 250 300 400
Active Power [kW] 250 300 400
Number of phases 3+N
Rated voltage [V] 380 / 400 / 415 three-phase + N (selectable)
Static Stability ±1%
Dynamic Stability ±5% in 10 msec.
Voltage distortion <1% with linear load/<3% with non-linear load
Frequency stability on battery ± 0.05%
Frequency [Hz] 50 or 60 (selectable)
110% for 60 min.; 125% for 2 min.; 110% for 60 min.; 125% for 10 min.;
Overload
150% for 20 sec. 150% for 1 min.
BYPASS
Rated voltage [V] 380 / 400 / 415 three-phase + N
Rated Frequency [Hz] 50 or 60 (selectable)
Frequency tolerance ±2% (selectable from ±1% to ±5%)
OVERALL SPECIFICATIONS
Weight [kg] 634 880 1100
Dimension (WxDxH) [mm] 800x850x1900 1200x850x1900 1400x850x1900
Input cable Bottom Top and bottom Top and bottom
Remote signals Volt-free contact (configurable)
Remote controls EPO, bypass battery charge block (configurable)
Communications USB + Dry contacts + 2 slots for communications interface
Ambient temperature
0 °C - +40 °C
for the UPS
Recommended temperature
+20 °C - +25 °C
for battery life
Range of relative humidity 5-95% non-condensing
Colour Dark grey RAL 7016
IP rating IP20 (other on request)
Efficiency (AC-AC) – ON LINE
up to 97%
Mode
European directives: L V 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility
Standards Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant
Classification in accordance with IEC 62040-3 (Voltage frequency Independent) VFI - SS - 111
Classification in accordance
(Voltage Frequency Independent) VFI - SS - 111
with IEC 62040-3
Moving the UPS Pallet jack
1
For wider tolerance conditions apply.
MODELS NXE 500 NXE 600 NXE 800 2SW NXE 800
INPUT
Rated voltage [V] 380 / 400 / 415 three-phase
Voltage tolerance [V] 400 ±20% @ full load1
Frequency tolerance [Hz] 40 - 70
Power factor 0.99
THDI <3%
Soft Start 0 - 100% in 120 sec. (selectable)
Standard equipment provided Back feed protection, separate bypass line
BATTERIES
Type VRLA AGM / GEL, NiCd, Supercaps, Li-ion, Flywheels
Ripple current Zero
Recharge voltage compensation -0.11% x V x °C
OUTPUT
Nominal Power [kVA] 500 600 800 800
Active Power [kW] 500 600 800 800
Number of phases 3+N
Rated voltage [V] 380 / 400 / 415 three-phase + N (selectable)
Static Stability ±1%
Dynamic Stability ±5% in 10 msec.
Voltage distortion <1% with linear load/<3% with non-linear load
Frequency stability on battery ± 0.05%
Frequency [Hz] 50 or 60 (selectable)
110% for 60 min.; 110% for 60 min.;
Overload 125% for 2 min.; 125% for 10 min.;
150% for 20 sec. 150% for 1 min.
BYPASS
Rated voltage [V] 380 / 400 / 415 three-phase + N
Rated Frequency [Hz] 50 or 60 (selectable)
Frequency tolerance ±2% (selectable from ±1% to ±5%)
OVERALL SPECIFICATIONS
Weight [kg] 1300 1600 1800 1985
Dimension (WxDxH) [mm] 1600x850x1900 2000x850x1900 2000x850x1900 2400x850x1900
Input cable Bottom Bottom Bottom Top and bottom
Remote signals Volt-free contact (configurable)
Remote controls EPO, bypass battery charge block (configurable)
Communications USB + Dry contacts + 2 slots for communications interface
Ambient temperature
0 °C - +40 °C
for the UPS
Recommended temperature
+20 °C - +25 °C
for battery life
Range of relative humidity 5-95% non-condensing
Colour Dark grey RAL 7016
IP rating IP20 (other on request)
Efficiency (AC-AC) – ON LINE
up to 97%
Mode
European directives: L V 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility
Standards Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant
Classification in accordance with IEC 62040-3 (Voltage frequency Independent) VFI - SS - 111
Classification in accordance
(Voltage Frequency Independent) VFI - SS - 111
with IEC 62040-3
Moving the UPS Pallet jack
1
For wider tolerance conditions apply.
NXE EMBEDDED PROTOCOLS
1 NextEnergy UPS
2 PowerShield3
3 Mail Server
2 1 4 Ethernet Switch
Ethernet
1 NextEnergy UPS
4
2 NetMan 204 board
3 Modbus/TCP Manager
4 SNMP Manager
5 Ethernet Switch
Ethernet
SNMP Protocol
Modbus/TCP Protocol
RPS S.p.A.
ITALY
The information in this document is subject to change without notice. Riello UPS assumes no responsibility for any errors that may appear in this document.
LEGNAGO (VR) CORMANO (MI) Visit www.riello-ups.com/bases
Head Office Sales Office for contact details.
Viale Europa, 7 Via Somalia, 20
37045 LEGNAGO (Verona) 20032 CORMANO (Milano)
Tel +39 0442 635811 Tel +39 02 663271
RPS America, Inc. RIELLO ENERDATA s.l. RIELLO UPS AUSTRALIA Pty. Ltd.
8808 Beckett Rd C/ Labradores, 11 Unit 4, 60-68 Box Road
West Chester, OH 45069 Parque Empresarial Taren Point - Sydney
Prado del Espino
28660 Boadilla del Monte
UNITED KINGDOM Madrid ASIA PACIFIC
RIELLO UPS Ltd. RIELLO TDL s.l. RIELLO UPS SINGAPORE Pte Ltd.
Unit 50 Clywedog Road North C/Berguedà, 6 bis No. 506 Chai Chee Lane,
Wrexham Industrial Estate Pol. Ind. Plà de la Bruguera #07-01, Singapore 469026
Wrexham LL13 9XN 08211 Castellar del Vallès, Barcelona
DATNXEG3Y21LREN
21509 Glinde
RIELLO DELTA POWER Sp. z o.o. RIELLO POWER INDIA Pvt. Ltd.
RIELLO POWER SYSTEMS GmbH ul. Krasnowolska 82 R Plot no. 213A, Sector-4,
Neufahrner Str. 12b 02-849 Warszawa IMT Manesar, 122050 Gurgaon (HR)
85375 Neufahrn/Grüneck
ARABIAN PENINSULA
FRANCE
RIELLO UPS Middle East FZ-LLC
RIELLO ONDULEURS S.a.r.l. Dubai Science Park
4 Rue du Bois Chaland, North Tower, 8th Floor, Office 801N
ZAC du Bois Chaland Al Barsha South, 500767
91090 Lisses
RIELLO ELETTRONICA