FCPS-24FS6(C/E)
6 Amp, 24 Volt
Remote Power Supply
Power Supplies
The Fire•Lite FCPS-24FS6(C/E) is a compact, cost-effective,
6-amp remote power supplies with battery charger. The FCPS-
24FS6(C/E) may be connected to any 12 or 24 volt fire alarm control
panel (FACP) or may stand-alone. Primary applications include noti-
fication appliance (bell) circuit (NAC) expansion (to support ADA
requirements and NAC synchronization) or auxiliary power to sup-
port 24 volt system accessories. The FCPS provides regulated and
filtered 24 VDC power to four notification appliance circuits config-
ured as either two Class B (Style Y) and Class A (Style Z, with
ZNAC-4 option module) or four class B only. Alternately, the four out-
puts may be configured as any combination of resettable/non-reset-
table power outputs (optimal for powering four-wire smoke
detectors. The FCPS-24FS6(C/E) also contains a battery charger
capable of charging up to 7.0 AH batteries. The FCPS-24FS6C is
ULC-listed.
NOTE: Unless otherwise specified, the term FCPS-24FS6 used in this
document refers to the FCPS-24FS6, FCPS-24FS6C, and FCPS-
24FS6E.
Features
• UL-Listed Notification Appliance Circuit (NAC) synchronization
using System Sensor®, Wheelock®, or Gentex® “Commander2”
appliances
• Operates as a “sync-follower” or as a “sync-generator” (default)
See note on page 2.
• Contains two fully-isolated input/control circuits - triggered from
FACP NAC (NAC expander mode) or jumped permanently “ON”
(stand-alone mode)
Specifications
• Two Class B (Style Y) or Class A (Style Z, with ZNAC-4 module)
NACs (circuits 1 & 3) Primary (AC) Power:
• 6-amp full load output, with 3 amps maximum/circuit, in NAC • FCPS-24FS6/C: 120 VAC, 60 Hz, 3.2A maximum
expander mode (UL 864) • FCPS-24FS6E: 240 VAC, 50 Hz, 1.6A maximum
• 4-amp continuous output in stand-alone mode (UL 1481) • Wire Size: minimum #14 AWG (2.0mm2) with 600 V insulation
• Compatible with coded inputs; signals passed through Control Input Circuit:
• Optional power-supervision relay (EOLR-1) • Trigger Input Voltage: 9 to 32 VDC
• In stand-alone mode, output power circuits may be configured as: • Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9 - 16 V)
resettable, (reset line from FACP required), non-resettable, or a
Trouble Contact Rating: 5 A at 24 VDC
mix of two and two
• Fully regulated and filtered power output - optimal for powering Auxiliary Power Output: Special application power 500 mA maxi-
four-wire smoke detectors, annunciators, and other system mum
peripherals requiring regulated/filtered power Output Circuits:
• Power-limiting technology meets UL power-limiting requirements • +24 VDC filtered, regulated
• Form-C normally-closed trouble relay • 3.0 A maximum for any one circuit
• Fully supervised power supply, battery, and NACs • Total continuous current for all outputs (stand-alone mode):
• Selectable earth fault detection 4.0 A maximum
• AC trouble report selectable for immediate 2-hour delay • Total short-term current for all outputs (NAC expander mode):
• Works with virtually any UL 864 fire alarm control which utilizes 6.0 A maximum
an industry-standard reverse-polarity notification circuit (including Secondary Power (Battery) Charging Circuit:
unfiltered and unregulated bell power) • Supports lead-acid batteries only
• Requires input trigger voltage of 9 - 32 VDC • Float-charge voltage: 27.6 VDC
• Self-contained in compact, locking cabinet - 15”H x 14.5”W x • Maximum current charge: 250 mA
2.75”D (cm: 38.1H x 36.83W x 6.985D)
• Maximum battery capacity: 7.0 AH
• Includes integral battery charger capable of charging up to 18 AH
batteries. Cabinet capable of housing 7.0 AH batteries
• Battery charger may be disabled via DIP switch for applications
requiring larger batteries
• Fixed, clamp-type terminal blocks accommodate up to 12 AWG
(3.1mm2) wire