GENERAL
The FCPS-24S6 (6-amp) and FCPS-24S8 (8-amp) are compact, cost-effective remote power supplies with battery charger.
The FCPS-24S6/-24S8 may be connected to any 12- or 24volt Fire Alarm Control Panel (FACP) or may be used as a
stand-alone supply. Primary applications include Notification
Appliance (bell) Circuit (NAC) expansion (to support ADA requirements and NAC synchronization) or auxiliary power to
support 24-volt system accessories. The FCPS-24S6/-24S8
provides regulated and filtered 24 VDC power to four notification appliance circuits configured as either four Class B (Style
Y) or Class A (Style Z, with ZNAC-4 option module). Alternately, the four outputs may be configured as all non-resettable,
all resettable, or two non-resettable and two resettable. The
FCPS-24S6/-24S8 also contains a battery charger capable of
charging up to 18 AH batteries.
California
State Fire
Marshal
7315-0028:225
MEA
S635
299-02-E
6827pho1.jpg
FEATURES
Battery charger may be disabled via DIP switch for applications requiring larger batteries.
Fixed, clamp-type terminal blocks accommodate up to 12
AWG (3.1 mm) wire.
SPECIFICATIONS
Primary (AC) power:
FCPS-24S6/-24S8: 120 VAC, 60 Hz, 3.2 A maximum.
Wire size: minimum #14 AWG (2.0 mm) with 600 V insulation.
Control input circuit:
Trigger input voltage: 9 to 32 VDC.
Trigger current: 2.0 mA (16 32 V). Per input: 1.0 mA (9
16 V).
Trouble contact rating: 5 amps at 24 VDC.
APPLICATIONS
Example 1: Expand notification appliance power an additional 6.0 amps (FCPS-24S6) or 8.0 amps (FCPS-24S8). Use
up to four Class B (Style Y) outputs or four Class A (Style Z)
outputs (using ZNAC-4). For example, the FACP notification
appliance circuits will activate the FCPS when reverse-polarity activation occurs. Trouble conditions on the FCPS are
sensed by the FACP through the notification appliance circuit.
Example 2: Use the FCPS to expand auxiliary regulated
24-volt system power up to 4.0 amps (FCPS-24S6) or up to
6.0 amps (FCPS-24S8). Both resettable and non-resettable
power options are available. Resettable outputs are created
by connecting the resettable output from the FACP to one or
both of the FCPS inputs.
Example 3: Use addressable control modules to activate
the FCPS instead of activating it through the FACP notification
appliance circuits. This typically allows for mounting the FCPS
at greater distances* away from the FACP while expanding
system architecture in various applications.
For example, an addressable control module is used to activate the FCPS, and an addressable monitor module is used to
sense FCPS trouble conditions. Local auxiliary power output from
the FCPS provides power to the
addressable control module.
AGENCY LISTINGS
AND APPROVALS
See the first page of this data
sheet for listing agencies and file
numbers. These listings and approvals apply to the FCPS-24S6
and the FCPS-24S8. In some
cases, certain modules or applications may not be listed by certain approval agencies, or listing
may be in process. Consult factory for latest listing status.
6827blok.wmf
SIMPLIFIED
BLOCK DIAGRAM
Page 2 of 3 DN-6927 07/20/04
BOARD LAYOUT
6827bord.wmf
Free Download
Daily Updated Database
100% Free Datasheet Search Site
100% Free IC Replacement Search Site
Convenient Electronic Dictionary
Fast Search System
www.EEworld.com.cn