Fire-Lite MS-2E Data Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DF-52211:B2 A2-250

MS-2(E)
2-Zone Fire Alarm Control Panels
Conventional Fire Alarm Control Panels

General
The FireLite MS-2 and MS-2E Fire Alarm Control Panels
(FACPs) bring the latest in microprocessor technology to conventional fire controls. The MS-2 is compatible with the i
smoke detectors from System Sensor with drift compensation,
maintenance alert, and freeze warning. Automatic synchronization of audio/visual devices with three selections for manufacturer protocol. The Notification Appliance Circuit (NAC) protocol
can silence audible devices while strobes continue to flash,
using a single pair of wires.
The MS-2 is compatible with conventional input devices such as
two- and four-wire smoke detectors, pull stations, waterflow
devices, tamper switches and other normally-open contact
devices. Refer to the FireLite Device Compatibility Document
PN 15384 for a complete list of compatible devices.
Note: Unless indicated otherwise, the term MS-2 refers to both
MS-2 and MS-2E models.

Features
Two Style B (Class B) Initiating Device Circuits (IDCs).
One Style Y (Class B) NAC.
24 VDC.
i Technology features:
Drift compensation automatically adjusts detector sensitivity and increases resistance to false alarms caused by dust
accumulation.
Maintenance Alert LEDs (per zone) warn of excessive dirt
accumulation, preventing false alarms (meets NFPA 72
requirements).
Detector sensitivity is automatically measured by the
detector, which automatically adjusts its sensitivity back to
the factory settings when it becomes more sensitive due to
contaminants settling in the chamber.
Wireless handheld sensitivity meter eliminates the need for
voltmeters, magnets, and a physical connection to the
detector. The reader displays sensitivity in terms of percent
per foot obscuration and provides text status indication.
Supervisory LED (per zone) provides warning if a detector
senses temperature approaching freezing.
Special test protocol and LED indication allows quick test of
all detectors without need for a ladder.
NAC synchronization features:
Synchronization of standard ANSI audible signals as
required by NFPA 72.
Synchronization of ADA compliant strobes per NFPA 72.
Selectable for System Sensor, Wheelock, and Gentex
protocols.
Selective Silence for manual silence of horns while
strobes continue to flash on the same NAC.
Alarm verification selectable for each zone.
Disable switches provided per zone.

NAC programmable for:


Silence Inhibit
Auto Silence
Strobe Synchronization
Selective Silence (horn-strobe mute)

MS2.jpg

Temporal or Steady signal


Silenceable or Nonsilenceable
Silent or audible Walk Test operation mode commanded from
the front keypad, with automatic return-to-normal after one
hour of inactivity.
Each zone may be programmed for supervisory or fire; each
zone has separate red and yellow LEDs.
Disable switches provided for each zone.
Form-C Alarm and Trouble relays.
3.0 amps total usable current.
Piezo sounder for alarm, trouble, supervisory and maintenance.
Control buttons:
ACK (Acknowledge)
Alarm Silence
Reset
Walk Test
Zone Enable/Disable (one per zone)
LED indicators:
Fire Alarm (one per zone)
Supervisory (one per zone)
Trouble (one per zone)
Maintenance (one per zone)
AC Power
NAC Disable
Zone Disable
NAC Fault
System Trouble
DF-52211:B2 12/21/11 Page 1 of 2

Power Trouble
Walk Test
Alarm Silence
Earth Fault (on circuit board)
Battery Fault (on circuit board)
Charger Fault (on circuit board)
Optional dress panel.

Operation
Activation of a compatible smoke detector or any normally-open
fire alarm initiating device activates audible and visual signaling
devices, illuminates an indicating LED, sounds the piezo
sounder at the FACP, activates the FACP alarm relay and operates an optional module used to notify a remote station or initiate an auxiliary control function.

Alarm Relay TB6.


Relay contact ratings: 2.0 A @ 30 VDC (resistive).

AUXILIARY OUTPUT: RESETTABLE POWER TB1


Operating voltage: nominal 24 VDC.
Maximum available current: 500 mA appropriate for powering four-wire smoke detectors (see notes).
Power-limited circuitry.
Notes: 1) Refer to the FireLite Device Compatibility Document
PN 15384 for a complete list of compatible devices.
2) Total current for resettable power and one NAC must not
exceed 3.0 A for MS-2.

CABINET DIMENSIONS
Door: 15.342 (38.97 cm) high x 14.667 (37.28 cm) wide x
0.375 (0.95 cm) deep.

Specifications

Backbox: 15.0 (38.10 cm) high x 14.5 (36.83 cm) wide x 3.0
(7.62 cm) deep.

AC POWER TB8

BACKBOX MOUNTING

MS-2: 120 VAC, 50/60 Hz, 2.3 A.


MS-2E: 240 VAC, 50 Hz, 1.15 A.
Wire Size: Minimum 14 AWG (2.0 mm) with 600 V insulation.

BATTERY (SEALED LEAD-ACID ONLY) J8


Maximum charging circuit: normal flat charge 27.6 VCD @
0.8 A.
Maximum battery charger capacity: 18.0 AH battery (two
7.0 AH batteries can be housed in the FACP cabinet. Larger
batteries require a separate battery box such as the FireLite
BB-17F).

The cabinet can be surface mounted. The door is removable


during installation by opening and lifting it off the hinges. The
cabinet mounts using two key slots at the top of the backbox and
two additional 0.25 diameter holes at the bottom.

Listings and Approvals


UL Listed: S624.
MEA: 297-01-E.
CSFM: 7165-0075:200.

Ordering Information

INITIATING DEVICE CIRCUIT TB3

MS-2: Two-zone conventional FACP. 120 VAC, 50/60 Hz, 2.3 A.

MS-2E: Same as above with 240 VAC, 50 Hz, 1.15 A operation.

Alarm zones 1 & 2.


Power-limited circuitry.
Operation: all zones Style B (Class B).
Normal operating voltage: nominal 20 VDC.
Alarm current: 15 mA minimum.
Short-circuit current: 40 mA maximum.
Maximum loop resistance: 100 ohms.
End-of-line resistor: 4.7K ohm, watt (P/N 71252).
Standby current: 4 mA.
Compatible devices: refer to the FireLite Device Compatibility Document PN 15384 for a complete list of compatible
devices.

BB-17F: Battery box, required to house two batteries greater


than 7 AH to a maximum of 18 AH.
DP-MS2/4: Optional dress panel.
MS-2RB: MS-2(E) replacement board.
TR-1-R: Optional trim ring for semi-flush mounting.
4XTMF: Transmitter Module provides a supervised output for a
local energy municipal box transmitter in addition to alarm and
trouble reverse polarity.
A 4-zone version of this panel is also available. See DF-52266.

NOTIFICATION APPLIANCE CIRCUIT TB2

One NAC.
Power-limited circuitry.
Normal operating voltage: nominal 24 VDC.
Maximum signalling current: 2.5 A total with standard transformer.
End-of-line resistor: 4.7K ohm, watt (P/N 71252).
Compatible devices: refer to the FireLite Device Compatibility Document PN 15384 for a complete list of compatible
devices.

FORM-C RELAYS

FireLite Alarms is a registered trademark of Honeywell International Inc.


2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

Trouble Relay TB5 (fail-safe).


This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact FireLite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
www.firelite.com
Page 2 of 2 DF-52211:B2 12/21/11