MS-2(E)
2-Zone Fire Alarm Control Panels
Conventional Fire Alarm Control Panels
General
The FireLite MS-2 and MS-2E Fire Alarm Control Panels
(FACPs) bring the latest in microprocessor technology to conventional fire controls. The MS-2 is compatible with the i
smoke detectors from System Sensor with drift compensation,
maintenance alert, and freeze warning. Automatic synchronization of audio/visual devices with three selections for manufacturer protocol. The Notification Appliance Circuit (NAC) protocol
can silence audible devices while strobes continue to flash,
using a single pair of wires.
The MS-2 is compatible with conventional input devices such as
two- and four-wire smoke detectors, pull stations, waterflow
devices, tamper switches and other normally-open contact
devices. Refer to the FireLite Device Compatibility Document
PN 15384 for a complete list of compatible devices.
Note: Unless indicated otherwise, the term MS-2 refers to both
MS-2 and MS-2E models.
Features
Two Style B (Class B) Initiating Device Circuits (IDCs).
One Style Y (Class B) NAC.
24 VDC.
i Technology features:
Drift compensation automatically adjusts detector sensitivity and increases resistance to false alarms caused by dust
accumulation.
Maintenance Alert LEDs (per zone) warn of excessive dirt
accumulation, preventing false alarms (meets NFPA 72
requirements).
Detector sensitivity is automatically measured by the
detector, which automatically adjusts its sensitivity back to
the factory settings when it becomes more sensitive due to
contaminants settling in the chamber.
Wireless handheld sensitivity meter eliminates the need for
voltmeters, magnets, and a physical connection to the
detector. The reader displays sensitivity in terms of percent
per foot obscuration and provides text status indication.
Supervisory LED (per zone) provides warning if a detector
senses temperature approaching freezing.
Special test protocol and LED indication allows quick test of
all detectors without need for a ladder.
NAC synchronization features:
Synchronization of standard ANSI audible signals as
required by NFPA 72.
Synchronization of ADA compliant strobes per NFPA 72.
Selectable for System Sensor, Wheelock, and Gentex
protocols.
Selective Silence for manual silence of horns while
strobes continue to flash on the same NAC.
Alarm verification selectable for each zone.
Disable switches provided per zone.
MS2.jpg
Power Trouble
Walk Test
Alarm Silence
Earth Fault (on circuit board)
Battery Fault (on circuit board)
Charger Fault (on circuit board)
Optional dress panel.
Operation
Activation of a compatible smoke detector or any normally-open
fire alarm initiating device activates audible and visual signaling
devices, illuminates an indicating LED, sounds the piezo
sounder at the FACP, activates the FACP alarm relay and operates an optional module used to notify a remote station or initiate an auxiliary control function.
CABINET DIMENSIONS
Door: 15.342 (38.97 cm) high x 14.667 (37.28 cm) wide x
0.375 (0.95 cm) deep.
Specifications
Backbox: 15.0 (38.10 cm) high x 14.5 (36.83 cm) wide x 3.0
(7.62 cm) deep.
AC POWER TB8
BACKBOX MOUNTING
Ordering Information
One NAC.
Power-limited circuitry.
Normal operating voltage: nominal 24 VDC.
Maximum signalling current: 2.5 A total with standard transformer.
End-of-line resistor: 4.7K ohm, watt (P/N 71252).
Compatible devices: refer to the FireLite Device Compatibility Document PN 15384 for a complete list of compatible
devices.
FORM-C RELAYS