Test Report issued under the responsibility of:

TEST REPORT
IEC 60335-2-40
Safety of household and similar electrical appliances
Part 2-40: Particular requirements for electrical heat pumps, air
conditioners and dehumidifiers
Report Number. .............................. : 180423126GZU-001
Date of issue ................................... : September 28, 2018; Modification 12: November 10, 2020
Total number of pages ................... : 177
Applicant’s name ............................ : Gree Electric Appliances, Inc. of Zhuhai
Address ........................................... : West Jinji Road, Qianshan, Zhuhai, Guangdong 519070, P.R.
China
Test specification:
Standard .......................................... : IEC 60335-2-40:2002 (Fourth Edition) + A1:2005 (incl. Corr.1:2006)
+ A2:2005 in conjunction with
IEC 60335-1:2010 (Fifth Edition)
Test procedure ............................... :
Non-standard test method………..: N/A
Test Report Form No...................... : IEC60335_2_40J
Test Report Form(s) Originator .... : VDE
Master TRF ...................................... : Dated 2014-06
Copyright © 2014 Worldwide System for Conformity Testing and Certification of Electrotechnical
Equipment and Components (IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from
the reader's interpretation of the reproduced material due to its placement and context.

If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB
Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and
appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 2 of 177 Modification 12: November 10, 2020

Test item description ..................... : Air conditioner, portable (Local air conditioner)
Trade Mark ...................................... : GREE
Manufacturer ................................... : Gree Electric Appliances, Inc. of Zhuhai
Model/Type reference .................... : GPC12AL-K5NNA3A, GPH12AL-K5NNA3A, GPH12AL-K5NNA2A,
GPC12AL-K5NNA3B, GPH12AL-K5NNA2B, GPC12AL-K5NNA2A,
GPC12AL-K5NNA3C, GPH12AL-K5NNA3C, GPH12AL-K5NNA1C,
GPH12AL-K5NNA1A, GPC12AL-K5NNA1C, GPC12AL-K5NNA2C;
GPH12AL-K5NNA2C, GPC12AL-K5NNA3D
Ratings ............................................ : 220-240V~, 50Hz, Class I, R290,
1500W for GPC12AL-K5NNA3C, GPC12AL-K5NNA1C, GPC12AL-
K5NNA2C, GPC12AL-K5NNA3D
1550W for other models

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 3 of 177 Modification 12: November 10, 2020

Testing procedure and testing location:

CB Testing Laboratory: Intertek Testing Services Shenzhen Ltd. Guangzhou


Branch
Testing location/ address ............................ : Room 02, & 101/E201/E301/E401/E501/E601/E701/E801
of Room 01 1-8/F., No. 7-2. Caipin Road, Science City,
GETDD, Guangzhou, Guangdong, China
Associated CB Testing Laboratory: N/A
Testing location/ address ............................ : N/A
Tested by (name + signature) ...................... : Sam Liu

Approved by (name + signature) ................ : Forest Wan

Testing procedure: TMP/CTF Stage 1: N/A


Testing location/ address ............................ : N/A
Tested by (name + signature) ...................... : N/A
Approved by (name + signature) ................ : N/A

Testing procedure: WMT/CTF Stage 2: N/A


Testing location/ address ............................ : N/A
Tested by (name + signature) ...................... : N/A
Witnessed by (name + signature) ............... : N/A
Approved by (name + signature) ................ : N/A

Testing procedure: N/A


SMT/CTF Stage 3 or 4:
Testing location/ address ............................ : N/A
Tested by (name + signature) ...................... : N/A
Witnessed by (name + signature) ............... : N/A
Approved by (name + signature) ................ : N/A
Supervised by (name + signature) .............. : N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD,
Guangzhou, Guangdong, China
Tel: (86-20) 82139688 Fax: (86-20) 32057538
Forest Wan
Report No.: 180423126GZU-001
Page 4 of 177 Modification 12: November 10, 2020

List of Attachments (including a total number of pages in each attachment):


None
Summary of testing:
The products comply with the requirement of the standard:
EN 60335-1:2012+A11:2014+A13:2017+A1:2019+A14:2019+A2:2019
EN 60335-2-40:2003+A11:2004+A12:2005+A1:2006+A2:2009+A13:2012+AC:2013
EN 62233:2008
Tests performed (name of test and test clause): Testing location:
Original: Intertek Testing Services Shenzhen Ltd.
Guangzhou Branch
Full tests were conducted on model GPH12AL-
Room 02, &
K5NNA3A.
101/E201/E301/E401/E501/E601/E701/E801 of
Modification 1: Room 01 1-8/F., No. 7-2. Caipin Road, Science
City, GETDD, Guangzhou, Guangdong, China
After review, no test was considered.
Modification 2:
After review, tests of clauses 10, 11, 13, 19 and 29
were conducted on model GPH12AL-K5NNA2B.
Modification 3:
After review, no test was considered.
Modification 4 (LVD only):
After review, tests of clauses 10, 11, 13, 19, 24.5
and annex EE were conducted on model
GPH12AL-K5NNA3A with compressor with
alternative compressor capacitor (40uF).
Modification 5:
After review, test of clause 10 was conducted on
model GPC12AL-K5NNA3C.
Modification 6:
After review, tests of clauses 10, 11, 13, 19.5, 19.7
and annex EE was conducted on model GPH12AL-
K5NNA3C.
Modification 7:
After review, no test was considered.
Modification 8:
After review, no test was considered.
Modification 9:
After review, test of clause 30 was conducted on
alternative components.
Modification 10 (LVD only):
After review, no test was considered.
Modification 11:
After review, tests of clause 29 were conducted on
alternative main boards.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 5 of 177 Modification 12: November 10, 2020

Tests of clause 30 were conducted on alternative


transformer (ECO20-07PA).
Modification 12:
After review, tests of clause 10, 11, 13, 19.2, 19.5,
19.7, 19.14, 24.5, 30 and annex EE were
conducted on GPC12AL-K5NNA3D.
Summary of compliance with National Differences:
The national differences of European Group have been considered.
The product fulfils the requirements of EN 60335-
1:2012+A11:2014+A13:2017+A1:2019+A14:2019+A2:2019; EN 60335-2-
40:2003+A11:2004+A12:2005+A1:2006+A2:2009+A13:2012+AC:2013; EN 62233:2008
Copy of marking plate:
The artwork below may be only a draft. The use of certification marks on a product must be authorized by
the respective NCBs that own these marks.
English:

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 6 of 177 Modification 12: November 10, 2020

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 7 of 177 Modification 12: November 10, 2020

German:

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 8 of 177 Modification 12: November 10, 2020

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 9 of 177 Modification 12: November 10, 2020

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 10 of 177 Modification 12: November 10, 2020

Warning mark:

Note:
1. the value for “X”, refer to user manual.
2. The symbol “Caution: risk of fire” including colour and format shall be permanently placed on the
appliance and the perpendicular height of the triangle shall be at least 30mm.
3. The symbol “Caution: risk of fire” shall be placed on the nameplate of the appliance, and perpendicular
height of the symbol shall be at least 10mm without the need of be in colour.
4. The symbols of “read operator’s manual”, “operator’s manual, and “service indicator shall be placed on
the appliance, and their perpendicular heights shall be at least 10mm.
Note:
1. When placing these electrical equipments on the market, the importer and manufacturer should indicate
on the electrical equipments his name, registered trade name or registered trade mark and the postal
address at which he can be contacted.
2. When placing these electric equipments on the market, Type, batch, or series number that allows their
identifications will be pasted on the appliance.

Test item particulars .................................................. :


Classification of installation and use ...................... : Stationary appliance
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 11 of 177 Modification 12: November 10, 2020

Supply Connection .................................................... : Type Y; Non detachable cord with plug


Possible test case verdicts:
- test case does not apply to the test object ...........: N/A
- test object does meet the requirement ..................: P (Pass)
- test object does not meet the requirement ...........: F (Fail)
Testing ..........................................................................:
Date of receipt of test item .........................................: 2020-10-22
Date (s) of performance of tests ...............................: 2020-10-22 to 2020-11-09

General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.

Throughout this report a comma / point is used as the decimal separator.


Determination of the test conclusion is based on IEC Guide 115 in consideration of measurement
uncertainty.
This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between
Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the
agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the
agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is
authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek
name or one of its marks for the sale or advertisement of the tested material, product or service must first be
approved in writing by Intertek. The observations and test results in this report are relevant only to the sample
tested. This report by itself does not imply that the material, product, or service is or has ever been under an
Intertek certification program.
The test report only allows to be revised only within the report defined retention period unless standard or
regulation was withdrawn or invalid.
This TRF includes an appendix EMF containing the IEC/EN 62233 requirements (see below).
IEC 62233:2005 (1. Edition)
EN 62233:2008 (incl. Corr.1:2008)
This test report is part of the product evaluation against the requirements of ProdSG in order to obtain the
GS-Mark.
PAH test according to AfPS GS 2019:01 PAK is considered and passed, please refer to PAH test report
180423126GZU-001-PAH for details.
Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:
The application for obtaining a CB Test Certificate Yes
includes more than one factory location and a
Not applicable
declaration from the Manufacturer stating that the
sample(s) submitted for evaluation is (are)
representative of the products from each factory has
been provided ................................................................ :
When differences exist; they shall be identified in the General product information section.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 12 of 177 Modification 12: November 10, 2020

Name and address of factory (ies) .......................... : Factory 1:


Gree Electric Appliances, Inc. of Zhuhai
West Jinji Road, Qianshan, Zhuhai, Guangdong
519070, P.R. China
Factory 2:
GREE ELECTRIC APPLIANCES (WUHU) CO., LTD.
North of Lianhe Road, West of Wuhua Road, East of
Yapeng Road, Economic Development District of
Sanshan, Wuhu City, 241000, AN’HUI, P. R. China
General product information:
Original:
The products are a local air conditioner intended for household and indoor use.
Models GPC12AL-K5NNA3A and GPH12AL-K5NNA3A are all the same except main board and model
GPC12AL-K5NNA3A has cooling mode only while GPH12AL-K5NNA3A has cooling and heating modes
incorporated with a 4-way valve.

Modification 1:
This test report replaces the original test report 180423126GZU-001 dated on September 28, 2018. It is
issued because of following additions and/or changes:
1. Adding one new model GPH12AL-K5NNA2A which is identical with original model GPH12AL-
K5NNA3A except front panel. See photo document for details.
2. Adding one alternative front panel for models GPH12AL-K5NNA3A, GPC12AL-K5NNA3A. See
photo document for details.
3. Adding alternative plug for all models. See table 24.1 for details.

Modification 2:
This test report replaces the original test report 180423126GZU-001 with modification 1, dated on January
07, 2019. It is issued because of following additions and/or changes:
1. Adding two new models GPC12AL-K5NNA3B and GPH12AL-K5NNA2B which are separately
identical with original models GPC12AL-K5NNA3A and GPH12AL-K5NNA3A except main board
and new models have WIFI function. See photos document for details.
2. Adding one new model GPC12AL-K5NNA2A which is identical with original model GPC12AL-
K5NNA3A except front panel. See photo document for details.
3. Adding alternative x capacitor and rectifier for all models. See table 24.1 for details.

Modification 3:
This test report bases on the test report 180423126GZU-001 with modification 2, dated on March 06, 2019.
It is issued because of following additions and/or changes:
1. Adding main board (M701F1PJ) which is identical with main board (M701F1NJ) except main board
(M701F1PJ) has deleted WIFI function for model GPC12AL-K5NNA3B, GPC12AL-K5NNA3A,
GPC12AL-K5NNA2A. See table 24.1 for details.
2. Adding main board which (M701F2SJ) is identical with main board (M701F2TJ) except main board
(M701F2SJ) has deleted WIFI function for model GPH12AL-K5NNA2B, GPH12AL-K5NNA3A,
GPH12AL-K5NNA2A. See table 24.1 for details.

Modification 4 (LVD only):


This test report bases on the test report 180423126GZU-001 with modification 2, dated on March 06, 2019
and modification 3, dated on April 08, 2019. It is issued because of adding alternative liquid level switch
(mechanical), compressor capacitor and overheat protector of fan motor. See table 24.1 for details.

Modification 5:
This test report replaces the test report 180423126GZU-001 with modification 2, dated on March 06, 2019,
modification 3, dated on April 08, 2019, modification 4, dated on July 01, 2019. It is issued because of
adding one new model GPC12AL-K5NNA3C which is identical with model GPC12AL-K5NNA3B except
model name, rated power and refrigerant charge. See marking plate for details.
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 13 of 177 Modification 12: November 10, 2020

Modification 6:
This test report replaces the test report 180423126GZU-001 with modification 5, dated on August 21, 2019.
It is issued because of following addition:
1. Adding one new model GPH12AL-K5NNA3C which is identical with model GPH12AL-K5NNA2B
except model name, weight, refrigerant charge, condenser and evaporator. See marking plate and
photos document for details.
2. Adding one new model GPH12AL-K5NNA1C which is identical with model GPH12AL-K5NNA3C
except front panel. See photos document for details.

Modification 7:
This test report replaces the test report 180423126GZU-001 with modification 6, dated on September 20,
2019. It is issued because of following addition:
1. Adding one new model GPH12AL-K5NNA1A which is identical with model GPH12AL-K5NNA3A
except front panel. See photos document for details.
2. Adding alternative front panel for model GPH12AL-K5NNA1C. See photos document for details.
3. Adding alternative 4-way valve for all models which have heating mode. See table 24.1 for details.

Modification 8:
This test report replaces the test report 180423126GZU-001 with modification 7, dated on November 22,
2019. It is issued because of following addition:
1. Adding one new model GPC12AL-K5NNA1C which is identical with model GPC12AL-K5NNA3C
except front panel. See photos document for details.
2. Adding one new factory as below:
Name: GREE ELECTRIC APPLIANCES (WUHU) CO., LTD.
Address: North of Lianhe Road, West of Wuhua Road, East of Yapeng Road, Economic Development
District of Sanshan, Wuhu City, 241000, AN’HUI, P. R. China
3. Adding alternative X2 capacitor. See table 24.1 for details.

Modification 9:
This test report replaces the test report 180423126GZU-001 with modification 8, dated on January 02,
2020. It is issued because of following addition:
1. Adding a new model GPC12AL-K5NNA2C which is the same as GPC12AL-K5NNA3C except the front
panel.
2. Adding a new model GPH12AL-K5NNA2C which is the same as GPH12AL-K5NNA3C except the front
panel.
3. Adding some alternative Y capacitor and high frequency transformer for all model, details refer to table
24,1.

Modification 10 (LVD only):


This test report bases on the test report 180423126GZU-001 with modification 9 dated on April 3, 2020. It is
issued because of updating the standards from “EN 60335-1:2012+A11:2014+A13:2017” to “EN 60335-
1:2012+A11:2014+A13:2017+A1::2019+A14:2019+A2:2019”.

Modification 11:
This test report replaces the test report 180423126GZU-001 modification 9 dated on April 3, 2020 and test
report 180423126GZU-001 modification 10 dated on June 17, 2020. It is issued because of the following
additions and changes:
1. Updating the standards from “EN 60335-1:2012+A11:2014+A13:2017” to “EN 60335-1:2012+A11:2014
+A13:2017+A1::2019+A14:2019+A2:2019”.
2. Adding alternative main board (M701F2ASJ), main board (M701F2BKJ), main board (M701F1BLJ) and
main board (M701F1BKJ) which have the same circuit diagram as main board (M701F2TJ), main board
(M701F2SJ), main board (M701F1NJ) and main board (M701F1PJ) respectively except for PCB layout.
See photos of documents for details.
3. Adding alternative control board, see photos documents for details.
4. Adding alternative high frequency transformer for all models. See table 24.1 for details.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 14 of 177 Modification 12: November 10, 2020

Modification 12:
This test report replaces the test report 180423126GZU-001 modification 11 dated on July 20, 2020. It is
issued because of the following additions and changes:
1. Adding a new model GPC12AL-K5NNA3D which is the same as GPC12AL-K5NNA3C except for no
WIFI module in GPC12AL-K5NNA3D and the mass of refrigerant charge.
2. Adding alternative relay (HF160F/12-H5), fan motor (YD28X-L Tongde) and high frequency transformer
(ECO20-07PA XIN YUAN) for all model. See table 24.1 for details.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 15 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

5 GENERAL CONDITIONS FOR THE TESTS ----


Tests performed according to clause 5, e.g. nature P
of supply, sequence of testing, etc.
5.2 Tests of clause 21 carried out on separate samples. P
Tests of clauses 11, 19 and 21 require pressure
measurements made at various points in
refrigerating system (IEC 60335-2-40/A1)
At least one additional specially prepared sample N/A
required for tests of annex FF (Leak simulation
tests) (IEC 60335-2-40/A1)
Temperatures on refrigerant piping measured P
during test of clause 11 (IEC 60335-2-40/A1)
5.6 Appropriate controls rendered inoperative during P
test (IEC 60335-2-40)
5.7 Tests of clauses 10 and 11 carried out under most P
severe operating conditions within operating
temperature range specified by manufacturer.
Annex AA provide examples of such temperature
conditions (IEC 60335-2-40)
5.10 For split-package units, refrigerant lines installed in N/A
accordance with installation instructions
(IEC 60335-2-40)
Refrigerant line length is maximum length stated in N/A
installation instructions or (IEC 60335-2-40)
7,5 m, whichever is shorter (IEC 60335-2-40) N/A
Thermal insulation of refrigerant lines applied in N/A
accordance with installation instructions
(IEC 60335-2-40)
5.101 Motor-compressor subjected to relevant test of P
clause 19 of IEC 60335-2-34, unless
(IEC 60335-2-40)
motor-compressor comply with that standard N/A
(IEC 60335-2-40)
5.102 Motor-compressors tested and comply with N/A
IEC 60335-2-34 need not additionally tested for
clause 21 (IEC 60335-2-40/A1)
6 CLASSIFICATION ----
6.1 Protection against electric shock: Class I P
Class I, II, III (IEC 60335-2-40) ............................. :
6.2 Protection against harmful ingress of water, IP degree in accordance with ----
IEC 60529 (IEC 60335-2-40)
- appliances or parts intended for outdoor use be at N/A
least IPX4 (IEC 60335-2-40);

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 16 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

- appliances intended only for indoor use (excluding P


laundry rooms) be IPX0 (IEC 60335-2-40);
- appliances intended to be used in laundry rooms N/A
be at least IPX1 (IEC 60335-2-40).
6.101 Degree of accessibility (accessible/not accessible Accessible to the general P
to the general public) (IEC 60335-2-40) public
7 MARKING AND INSTRUCTIONS ----
7.1 Rated voltage or voltage range (V) ....................... : 220-240 P
Symbol for nature of supply including number of N/A
phases, unless for single phase operation
(IEC 60335-2-40) .................................................. :
Rated frequency (Hz)............................................ : 50 P
Rated power input (W), or ..................................... : (See marking plate) P
Rated current (A) ................................................. : N/A
Manufacturer's or responsible vendor's name, GREE P
trademark or identification mark ........................... :
Model or type reference ........................................ : (See marking plate) P
Symbol IEC 60417-5172, for class II appliances N/A
IP number, other than IPX0 .................................. : N/A
Symbol IEC 60417-5180, for class III appliances, N/A
unless
the appliance is operated by batteries only N/A
Symbol IEC 60417-5036, for the enclosure of N/A
electrically-operated water valves in external
hose-sets for connection of an appliance to the
water mains, if the working voltage exceeds
extra-low voltage
Mass of refrigerant or of each refrigerant in blend (See marking plate) P
(except for azeotropic type) (IEC 60335-2-40) ..... :
Refrigerant identification (IEC 60335-2-40) .......... : R290 P
Permissible excessive operating pressure for N/A
sanitary hot water heat pumps (IEC 60335-2-40). :
Maximum operating pressure for heat exchanger N/A
for hydronic fan coil/air handling units
(IEC 60335-2-40/A2) ............................................. :
Permissible excessive operating pressure of (See marking plate) P
refrigerant circuit for suction and discharge, if they
differ (IEC 60335-2-40) ......................................... :
Symbol for degree of protection against ingress of N/A
water, other than IPX0 (IEC 60335-2-40) ............. :

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 17 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Separate marking of appliances with all rated N/A


characteristics of supplementary heaters
(IEC 60335-2-40) .................................................. :
Marking of direction of fluid flow (IEC 60335-2-40) N/A
Flame symbol and instruction manual symbol of 7.6 visible when flammable ----
refrigerant employed and following conditions exist (IEC 60335-2-40/A1):
- accessing parts expected to be subjected to P
maintenance or repair (IEC 60335-2-40/A1);
- observing appliance under sale or installed P
conditions (IEC 60335-2-40/A1);
- observing appliance packaging, if appliance P
charged with refrigerant (IEC 60335-2-40/A1).
If flammable refrigerant used, symbols for “read P
operator’s manual”, “operator’s manual; operating
instructions” and “service indicator; read technical
manual” (symbols 0790, 1641 and 1659 of
ISO 7000) placed on appliance in location visible to
persons required to know information.
Perpendicular height be at least 10 mm
(IEC 60335-2-40/A1 corr.1)
Additional warning symbol (flame symbol: B.3.2 of P
ISO 3864) placed on nameplate of unit near
declaration of refrigerant type and charge
information. Perpendicular height be at least
10 mm, and symbol need not be in colour
(IEC 60335-2-40/A1)
Following warning also applied to appliance when P
flammable refrigerant employed.
WARNING
Appliance shall be installed, operated and stored in
a room with a floor area larger than ‘X’ m² (only
applies to appliances that are not fixed appliances)
(IEC 60335-2-40/A1)
Not fixed appliances, minimum room size X >15m2 P
specified on appliance. X in marking determined in
m²by procedure described in paragraph 2 of
annex GG for unventilated areas and X in marking
be 4 if refrigerant charge of appliance is less than
m1 (see annex GG, paragraph 1.1)
(IEC 60335-2-40/A1)
Maximum allowable pressure for low-pressure side P
and high-pressure side marked on product
(IEC 60335-2-40/A1)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 18 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

If not already visible when accessing service port P


and if service port provided, service port marked to
identify type of refrigerant. If refrigerant is
flammable, symbol B.3.2 of ISO 3864, be included,
without specifying the colour (IEC 60335-2-40/A1)
7.2 Warning for stationary appliances for multiple N/A
supply
Warning placed in vicinity of terminal cover N/A
7.3 Range of rated values marked with the lower and 220-240V P
upper limits separated by a hyphen
Different rated values marked with the values N/A
separated by an oblique stroke
7.4 Appliances adjustable for different rated voltages, N/A
the voltage setting is clearly discernible
Requirement met if frequent changes are not N/A
required and the rated voltage to which the
appliance is to be adjusted is determined from a
wiring diagram
7.5 Appliances with more than one rated voltage or one P
or more rated voltage ranges, marked with rated
input or rated current for each rated voltage or
range, unless
the power input is related to the arithmetic mean P
value of the rated voltage range
Relation between marking for upper and lower N/A
limits of rated power input or rated current and
voltage is clear
7.6 Correct symbols used P
Flammable refrigerant, warning symbol B.3.2 of P
ISO 3864, including colour and format, permanently
placed on appliance. Perpendicular height of
triangle containing
"Caution, risk of fire"
symbol be at least 30 mm (IEC 60335-2-40/A1)
Flammable refrigerant, symbol requiring reference P
to manual [0790 of ISO 7000], including colour and
format, permanently placed on appliance
(IEC 60335-2-40/A1 corr.1)
Symbol for nature of supply placed next to rated P
voltage
Symbol for class II appliances placed unlikely to be N/A
confused with other marking
Units of physical quantities and their symbols P
according to international standardized system

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 19 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

7.7 Connection diagram fixed to appliances to be N/A


connected to more than two supply conductors and
appliances for multiple supply, unless
correct mode of connection is obvious P
7.8 Except for type Z attachment, terminals for connection to the supply mains ----
indicated as follows:
- marking of terminals exclusively for the neutral N/A
conductor (letter N)
- marking of protective earthing terminals (symbol P
IEC 60417-5019)
- marking not placed on removable parts P
7.9 Marking or placing of switches which may cause a N/A
hazard
7.10 Indications of switches on stationary appliances By letters or other visual P
and controls on all appliances by use of figures, means
letters or other visual means................................. :
This applies also to switches which are part of a N/A
control
If figures are used, the off position indicated by the N/A
figure 0
The figure 0 indicates only OFF position, unless no N/A
confusion with the OFF position
7.11 Indication for direction of adjustment of controls P
7.12 Instructions for safe use provided P
Details concerning precautions during user P
maintenance
Appliances not accessible to general public, N/A
classification of clause 6.101 included
(IEC 60335-2-40)
Appliances using flammable refrigerants, an P
installation, service and operation manual, either
separate or combined manuals, provided and
include information given in annex DD
(IEC 60335-2-40/A1)
The instructions state that: ----
- the appliance is not to be used by persons Replaced by EN 60335- ----
(including children) with reduced physical, sensory 1:2012
or mental capabilities, or lack of experience and
knowledge, unless they have been given
supervision or instruction
- children being supervised not to play with the Replaced by EN 60335- ----
appliance 1:2012

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 20 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

For a part of class III construction supplied from a N/A


detachable power supply unit, the instructions state
that the appliance is only to be used with the unit
provided
Instructions for class III appliances state that it must N/A
only be supplied at SELV, unless
it is a battery-operated appliance, the battery being N/A
charged outside the appliance
7.12.1 Sufficient details for installation supplied P
For an appliance intended to be permanently N/A
connected to the water mains and not connected by
a hose-set, this is stated
Sufficient details for installation or maintenance supplied (IEC 60335-2-40): ----
- that the appliance shall be installed in accordance P
with national wiring regulations (IEC 60335-2-40);
- the dimensions of the space necessary for correct P
installation of the appliance including the minimum
permissible distance to adjacent structures
(IEC 60335-2-40);
- for appliances with supplementary heaters, the N/A
minimum clearance from the appliance to
combustible surfaces (IEC 60335-2-40);
- a wiring diagram with a clear indication of the N/A
connections and wiring to external control devices
and supply cord (IEC 60335-2-40);
- the range of external static pressures at which the N/A
appliance was tested (add-on heat pumps and
appliances with supplementary heaters only)
(IEC 60335-2-40);
- the method of connection to the appliance to the P
electrical supply and interconnection of separate
components (IEC 60335-2-40);
- indication of which parts of the appliance are N/A
suitable for outdoor use, if applicable
(IEC 60335-2-40);
- details of type and rating of fuses N/A
(IEC 60335-2-40);
- details of supplementary heating elements that N/A
may be used in conjunction with the appliance,
including fitting instructions either with the
appliance or with the supplementary heater
(IEC 60335-2-40);
- maximum and minimum water or brine operating N/A
temperatures (IEC 60335-2-40);

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 21 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

- maximum and minimum water or brine operating N/A


pressures (IEC 60335-2-40).
Open storage tanks of heat pumps for water N/A
heating, accompanied by an instruction sheet which
state that the vent shall not be obstructed
(IEC 60335-2-40)
7.12.2 Stationary appliances not fitted with means for N/A
disconnection from the supply mains having a
contact separation in all poles that provide full
disconnection under overvoltage category III, the
instructions state that means for disconnection
must be incorporated in the fixed wiring in
accordance with the wiring rules
7.12.3 Insulation of the fixed wiring in contact with parts N/A
exceeding 50 K during clause 11; instructions state
that the fixed wiring must be protected
7.12.4 Instructions for built-in appliances: ----
- dimensions of space N/A
- dimensions and position of supporting and fixing N/A
- minimum distances between parts and N/A
surrounding structure
- minimum dimensions of ventilating openings and N/A
arrangement
- connection to supply mains and interconnection of N/A
separate components
- allow disconnection of the appliance after N/A
installation, by accessible plug or a switch in the
fixed wiring, unless
a switch complying with 24.3 N/A
7.12.5 Replacement cord instructions, type X attachment N/A
with a specially prepared cord
Replacement cord instructions, type Y attachment P
Replacement cord instructions, type Z attachment N/A
7.12.6 Caution in the instructions for appliances N/A
incorporating a non-self-resetting thermal cut-out
that is reset by disconnection of the supply mains, if
this cut-out is required to comply with the standard
7.12.7 Instructions for fixed appliances stating how the N/A
appliance is to be fixed
7.12.8 Instructions for appliances connected to the water mains: ----
- max. inlet water pressure (Pa) ............................ : N/A
- min. inlet water pressure, if necessary (Pa) ....... : N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 22 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Instructions concerning new and old hose-sets for N/A


appliances connected to the water mains by
detachable hose-sets
7.13 Instructions and other texts in an official language English and German P
7.14 Marking clearly legible and durable, rubbing test as P
specified
7.15 Markings on a main part P
Marking clearly discernible from the outside, if P
necessary after removal of a cover
For portable appliances, cover can be removed or N/A
opened without a tool
For stationary appliances, name, trademark or P
identification mark and model or type reference
visible after installation
For fixed appliances, name, trademark or N/A
identification mark and model or type reference
visible after installation according to the instructions
Indications for switches and controls placed on or P
near the components. Marking not on parts which
can be positioned or repositioned in such a way
that the marking is misleading
Marking on panel allowed, provided panel in place N/A
for intended operation of appliance
(IEC 60335-2-40)
7.16 Marking of a possible replaceable thermal link or N/A
fuse link clearly visible with regard to replacing the
link
7.101 Marking of fuses and overload protective devices, if replaceable (IEC 60335-2-40): ----
- fuse rated current in amperes, type and rated N/A
voltage or (IEC 60335-2-40)
- manufacturer and model of overload protective N/A
device (IEC 60335-2-40)
7.102 Marking for connection with aluminium wire, if N/A
necessary (IEC 60335-2-40)
8 PROTECTION AGAINST ACCESS TO LIVE PARTS ----
8.1 Adequate protection against accidental contact with P
live parts
8.1.1 Requirement applies for all positions, detachable P
parts removed
Lamps behind a detachable cover not removed, if N/A
conditions met
Insertion or removal of lamps, protection against N/A
contact with live parts of the lamp cap

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 23 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Use of test probe B of IEC 61032, with a force not P


exceeding 1 N: no contact with live parts
Use of test probe B of IEC 61032 through P
openings, with a force of 20 N: no contact with live
parts
8.1.2 Use of test probe 13 of IEC 61032, with a force not P
exceeding 1 N, through openings in class 0
appliances and class II appliances/constructions:
no contact with live parts
Test probe 13 also applied through openings in P
earthed metal enclosures having a non-conductive
coating: no contact with live parts
8.1.3 For appliances other than class II, use of test N/A
probe 41 of IEC 61032, with a force not exceeding
1 N: no contact with live parts of visible glowing
heating elements
8.1.4 Accessible part not considered live if: ----
- safety extra-low a.c. voltage: peak value not N/A
exceeding 42,4 V
- safety extra-low d.c. voltage: not exceeding 42,4 V N/A
- or separated from live parts by protective N/A
impedance
If protective impedance: d.c. current not exceeding N/A
2 mA, and
a.c. peak value not exceeding 0,7 mA N/A
- for peak values over 42,4 V up to and including N/A
450 V, capacitance not exceeding 0,1 F
- for peak values over 450 V up to and including N/A
15 kV, discharge not exceeding 45 C
- for peak values over 15kV, the energy in the N/A
discharge not exceeding 350 mJ
8.1.5 Live parts protected at least by basic insulation before installation or assembly: ----
- built-in appliances N/A
- fixed appliances N/A
- appliances delivered in separate units N/A
8.2 Class II appliances and constructions constructed P
so that there is adequate protection against
accidental contact with basic insulation and metal
parts separated from live parts by basic insulation
only
Only possible to touch parts separated from live P
parts by double or reinforced insulation
9 STARTING OF MOTOR-OPERATED APPLIANCES ----
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 24 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Requirements and tests are specified in part 2 N/A


when necessary
10 POWER INPUT AND CURRENT ----
10.1 Power input at normal operating temperature, rated (see appended table) P
voltage and normal operation not deviating from
rated power input by more than shown in table 1 . :
Test carried out at upper and lower limits of the N/A
ranges for appliances with one or more rated
voltage ranges, unless
the rated power input is related to the arithmetic P
mean value
10.2 Current at normal operating temperature, rated N/A
voltage and normal operation not deviating from
rated current by more than shown in table 2 ........ :
Test carried out at upper and lower limits of the N/A
ranges for appliances with one or more rated
voltage ranges, unless
the rated current is related to the arithmetic mean N/A
value of the range
11 HEATING ----
11.1 No excessive temperatures in normal use P
(IEC 60335-2-40)
Compliance is checked by the tests of annex C, if (IEC 60335-2-40): ----
- temperature of motor winding exceeds values N/A
shown in table 3 (IEC 60335-2-40)
- there is doubt about classification of insulation N/A
system of the motor (IEC 60335-2-40)
11.2 Placing and mounting of appliance (IEC/EN 60335-2-40): ----
- clearances to adjacent surfaces (IEC 60335-2-40); P
- flow rates for liquid source or sink equipment be N/A
minimum, except for fan coils where flow rates
and liquid temperatures be maximum
(IEC 60335-2-40/A2);
- static pressures (IEC 60335-2-40); N/A
- means of adjusting the flow, flow for tests be N/A
minimum obtainable (IEC 60335-2-40);
- adjustable limit controls set at maximum cut-out P
setting and minimum differential (IEC 60335-2-40).
Appliances with supplementary heaters, use test N/A
casing of clause 11.9 (IEC 60335-2-40)
11.2.1 Appliances with supplementary heaters, inlet duct N/A
connected to inlet air opening (IEC 60335-2-40)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 25 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

11.2.2 Appliance without supplementary heaters, air outlet N/A


used (IEC 60335-2-40)
11.3 Temperature rise determine by thermocouples or P
resistance method (IEC 60335-2-40)
11.4 Test performed at supply voltage between 0,94 and 1,06 x 240=254,4V P
1,06 times the rated voltage (IEC 60335-2-40)
Heating elements energized at voltage which gives N/A
an electrical input of 1,15 times maximum rated
power input (IEC 60335-2-40)
11.5 Test conducted in heating mode and cooling mode, P
if both exist (IEC 60335-2-40)
All supplementary heating elements operative N/A
simultaneously (IEC 60335-2-40)
11.6 Defrost test in most unfavourable conditions, if N/A
needed (IEC/EN 60335-2-40)
11.7 Appliances operated continuously until steady P
conditions except for defrost tests (IEC 60335-2-40)
11.8 Temperatures not exceeding values of table 3 (See appended tables) P
(IEC 60335-2-40/A2)
Protective devices do not operate (IEC 60335-2-40) P
Sealing compound not flowing out P
(IEC 60335-2-40)
Temperature of air in outlet duct not exceed 90 °C N/A
(IEC 60335-2-40)
11.9 Test casing and installation of appliances in N/A
accordance with manufacturer’s instructions
(IEC 60335-2-40)
Glass fibre insulation for appliances without N/A
indication of minimum clearances according to
manufacturer; thermocouple in contact with
enclosure (IEC 60335-2-40)
13 LEAKAGE CURRENT AND ELECTRIC STRENGTH AT OPERATING ----
TEMPERATURE
13.1 Leakage current not excessive and electric strength P
adequate
Heating appliances operated at 1,15 times the N/A
rated power input (W) ........................................... :
Motor-operated appliances and combined 1,06 x 240=254,4V P
appliances supplied at 1,06 times the rated voltage
(V) ......................................................................... :
Protective impedance and radio interference filters N/A
disconnected before carrying out the tests

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 26 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

13.2 For class 0, class II and class III appliances, P


leakage current measured by means of the circuit
described in figure 4 of IEC 60990
For other appliances, a low impedance ammeter N/A
may be used
Leakage current measurements ........................... : (see appended table) P
(IEC 60335-2-40)
13.3 The appliance is disconnected from the supply P
Electric strength tests according to table 4 ........... : (see appended table) P
No breakdown during the tests P
14 TRANSIENT OVERVOLTAGES ----
Appliances withstand the transient over-voltages to N/A
which they may be subjected
Clearances having a value less than specified in N/A
table 16 subjected to an impulse voltage test, the
test voltage specified in table 6............................. :
No flashover during the test, unless N/A
of functional insulation if the appliance complies N/A
with clause 19 with the clearance short-circuited
15 MOISTURE RESISTANCE ----
15.1 Enclosure provides degree of moisture protection N/A
against ingress of water (rain, overflow from drain
pan or defrosting), tests of clause 15.2, 15.3, 11.6
and 16) (IEC 60335-2-40)
Motor-compressor not operated and detachable P
parts removed during tests of clause 15.2 and 15.3
(IEC 60335-2-40/A2)
15.2 Tests in accordance with IEC 60529 in appliances N/A
other than IPX0, as specified (IEC 60335-2-40) ... :
15.3 Drain pan filled to brim and subjected to continuous P
overflow and fan(s) switched on (IEC 60335-2-40)
15.101 Spillage test as specified (IEC 60335-2-40/A2) P
After spillage completed, appliance withstand test P
of clause 16 (IEC 60335-2-40/A2)
16 LEAKAGE CURRENT AND ELECTRIC STRENGTH ----
16.1 Leakage current not excessive and electric strength P
adequate
Protective impedance disconnected from live parts N/A
before carrying out the tests
Tests carried out at room temperature and not P
connected to the supply

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 27 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

16.2 Single-phase appliances: test voltage 1,06 times 1,06 x 240=254,4V P


rated voltage (V) ................................................... :
Three-phase appliances: test voltage 1,06 times N/A
rated voltage divided by 3 (V) ............................. :
Leakage current measurements ........................... : (see appended table) P
(IEC 60335-2-40)
Limit values doubled if: ----
- all controls have an off position in all poles, or N/A
- the appliance has no control other than a thermal N/A
cut-out, or
- all thermostats, temperature limiters and energy N/A
regulators do not have an off position, or
- the appliance has radio interference filters N/A
With the radio interference filters disconnected, the N/A
leakage current do not exceed limits specified ..... :
16.3 Electric strength tests according to table 7 ........... : (see appended table) P
Test voltage applied between the supply cord and (see appended table) P
inlet bushing and cord guard and cord anchorage
as specified ........................................................... :
No breakdown during the tests P
17 OVERLOAD PROTECTION OF TRANSFORMERS AND ASSOCIATED CIRCUITS ----
No excessive temperatures in transformer or N/A
associated circuits in event of short-circuits likely to
occur in normal use .............................................. :
Appliance supplied with 1,06 or 0,94 times rated N/A
voltage under the most unfavourable short-circuit or
overload likely to occur in normal use (V) ............. :
Basic insulation is not short-circuited N/A
Temperature rise of insulation of the conductors of N/A
safety extra-low voltage circuits not exceeding the
relevant value specified in table 3 by more than
15 K
Temperature of the winding not exceeding the N/A
value specified in table 8
However, limits do not apply to fail-safe N/A
transformers complying with sub-clause 15.5 of
IEC 61558-1
18 ENDURANCE ----
Requirements and tests are specified in part 2 N/A
when necessary
19 ABNORMAL OPERATION ----

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 28 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

19.1 The risk of fire or mechanical damage under P


abnormal or careless operation obviated (tests
19.2-19.14) (IEC 60335-2-40)
Failure of transfer medium flow or of any control P
device not result in a hazard (IEC 60335-2-40)
Electronic circuits so designed and applied that a P
fault will not render the appliance unsafe (electric
shock, fire or mechanical hazard, dangerous
malfunction) (test 19.11 and 19.12)
(IEC 60335-2-40)
19.2 Test of appliance with motor rotors, other than P
motor-compressors, operated for 15 days (360 h) or
until protection device opens circuit
(IEC 60335-2-40)
Insulation of motor windings (IEC 60335-2-40) .... : (See appended table) P
Temperature of enclosure does not exceed (C) (See appended table) P
(IEC 60335-2-40) .................................................. :
Temperature of the windings does not exceed the (See appended table) P
values shown in the table ; temperature (C)
(IEC 60335-2-40) .................................................. :
Electric strength test as specified in 16.3, 72 h after P
the beginning of the test (IEC 60335-2-40)
30 mA residual current device does not open P
(IEC 60335-2-40)
At the end, leakage current between windings and (See appended table) P
enclosure does not exceed 2 mA (IEC 60335-2-40)
19.3 Motor-compressor complies with IEC 60335-2-34 N/A
(IEC 60335-2-40)
Test of motor-compressor with rotor locked as P
specified in clause 19.101 of IEC 60335-2-34 and
comply with 19.104 of that standard
(IEC 60335-2-40)
19.4 Test of three-phase motors operated under N/A
conditions of clause 11 with one phase
disconnected until steady conditions or protective
device operates (IEC 60335-2-40)
19.5 Test of appliance with heat transfer medium flow of P
the outdoor heat exchanger restricted or shut off
when reaching steady conditions (IEC 60335-2-40)
Test of appliance with heat transfer flow of the P
indoor heat exchanger restricted or shut off when
reaching steady conditions (IEC 60335-2-40)
Disconnection of motor common to both the N/A
outdoor and the indoor heat exchangers when
reaching steady conditions (IEC 60335-2-40)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 29 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

19.6 Test of appliances using water as heat transfer N/A


medium (IEC 60335-2-40)
19.7 Test of air to air appliances at rated voltage or at P
the upper limit of the rated voltage range. Dry-bulb
temperature is 5 K below values specified by
manufacturer (IEC 60335-2-40)
Test with the dry-bulb temperature 10 K over the P
values specified by manufacturer (IEC 60335-2-40)
19.8 Test of appliances with supplementary heaters N/A
(IEC 60335-2-40)
19.9 Test at temperature permitting continuous operation N/A
of the motor-compressor and electric heating
elements at same time (IEC 60335-2-40)
19.10 Test of appliance with any defect which expected P
during normal use (IEC 60335-2-40)
19.10.101 Test of clause 19.10 repeated on class 0I N/A
appliances and class I appliances incorporating
tubular sheathed or embedded heating elements
(IEC 60335-2-40/A2)
However, controls not short-circuited but one end of N/A
element connected to sheath of heating element
(IEC 60335-2-40/A2)
Test repeated with polarity of supply to appliance N/A
reversed and with other end of element connected
to sheath (IEC 60335-2-40/A2)
Test not carried out on appliances intended to N/A
permanently connected to fixed wiring and on
appliances where an all-pole disconnection occurs
during test of clause 19.10 (IEC 60335-2-40/A2)
19.11 Electronic circuits, compliance checked by P
evaluation of the fault conditions specified in
clause 19.11.2 for all circuits or parts of circuits
(IEC 60335-2-40), unless
they comply with conditions specified in P
clause 19.11.1 (IEC 60335-2-40)
Windings temperature not exceeding values shown P
in table 8 (IEC 60335-2-40)
Appliance comply with conditions of clause 19.14 P
(IEC 60335-2-40)
Appliance withstands test: a conductor becomes N/A
open circuited and three conditions are met
(IEC 60335-2-40)
19.11.1 Before applying the fault conditions a) to f) in 19.11.2, it is checked if circuits or ----
parts of circuit meet both of following conditions (IEC 60335-2-40):

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 30 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

- electronic circuit is low-power circuit, that is, P


maximum power at low-power points not exceed
15 W according to tests specified
(IEC 60335-2-40)
- protection against electric shock, fire hazard, P
mechanical hazard or dangerous malfunction in
other parts of appliance does not rely on correct
functioning of electronic circuit (IEC 60335-2-40)
19.11.2 Fault conditions applied one at a time, appliance operated under conditions ----
specified in clause 11, but supplied at rated voltage, duration of tests as specified
(IEC 60335-2-40):
a) short circuit of creepage distances and P
clearances between live parts of different
potential, if these distances less than values
specified in clause 29.1, unless relevant part is
adequately encapsulated (IEC 60335-2-40)
b) open circuit at terminals of any component P
(IEC 60335-2-40)
c) short circuit if capacitors, unless they comply P
with IEC 60384-14 (IEC 60335-2-40)
d) short circuit of any two terminals of an electronic P
component, other than integrated circuits. This
fault condition not applied between circuits of an
optocoupler (IEC 60335-2-40)
e) failure of triacs in diode mode (IEC 60335-2-40) P
f) failure of an integrated circuit. Possible P
hazardous situations of appliance assessed to
ensure that safety not rely on correct functioning
of such component (IEC 60335-2-40)
Short-circuit of low-power circuits (IEC 60335-2-40) P
Duration of tests (IEC 60335-2-40): ----
- as specified in clause 11.7 but only for one N/A
operating cycle, if fault cannot recognised by user
(IEC 60335-2-40);
- as specified in clause 19.2, if fault can recognised P
by user (IEC 60335-2-40);
- until steady conditions established P
(IEC 60335-2-40).
Test ended if interruption of supply occurs within P
the appliance (IEC 60335-2-40)
If electronic circuit operates to ensure compliance N/A
with clause 19, relevant test repeated with single
fault a) to f) simulated (IEC 60335-2-40)
Fault condition f) applied to encapsulated or similar P
components (IEC 60335-2-40)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 31 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

PTC’s, NTC’s and VDR’s resistors not P


short-circuited if used as specified by manufacturer
(IEC 60335-2-40)
19.12 If safety of appliance for any of fault conditions P
specified in clause 19.11.2 depends on operation of
miniature fuse-link complying with IEC 60127, test
repeated with fuse-link replaced by an ammeter
(IEC 60335-2-40)
Current  2,1 times rated current of fuse-link, circuit N/A
not adequately protected (fuse-link short-circuited)
(IEC 60335-2-40)
Current  2,75 times rated current of fuse-link, P
circuit adequately protected (IEC 60335-2-40)
Current  2,1 and  2,75 times rated current, N/A
fuse-link short-circuited and test carried out during
specified time (IEC 60335-2-40)
19.13 Appliances with PTC heating elements test as N/A
specified (IEC 60335-2-40)
19.14 During tests of clause 19.2 to 19.10.101 and 19.11, P
19.12 and 19.13 if appropriate, appliances not emit
flames, molten metal, poisonous or ignitable gas in
hazardous amounts (IEC 60335-2-40/A2)
Enclosures not deform (IEC 60335-2-40) P
Temperature rise not exceed values shown in (See appended table) P
table 9 (IEC 60335-2-40)
Electric strength test, test voltage as specified in P
table 4 (IEC 60335-2-40)
19.15 For appliances with a mains voltage selector N/A
switch, the switch is set to the lowest rated voltage
position and the highest value of rated voltage is
applied
19.101 All appliances provided with supplementary heaters N/A
and free air discharge subjected to specified test in
each mode of operation (IEC 60335-2-40/A2)
During test temperature not exceed 150 °C but an N/A
overshoot of 25 °C is permitted during first hour
(IEC 60335-2-40/A2)
20 STABILITY AND MECHANICAL HAZARDS ----
20.1 Appliances having adequate stability P
Tilting test through an angle of 10, appliance P
placed on an inclined plane/horizontal support, not
connected to the supply mains; appliance does not
overturn
Tilting test repeated on appliances with heating N/A
elements, angle of inclination increased to 15
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 32 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Possible heating test in overturned position; N/A


temperature rise does not exceed values shown in
table 9
20.2 Moving parts adequately arranged or enclosed as P
to provide protection against personal injury
Protective enclosures, guards and similar parts are P
non-detachable, and
have adequate mechanical strength P
Enclosures that can be opened by overriding an N/A
interlock are considered to be detachable parts
Self-resetting thermal cut-outs and overcurrent P
protective devices not causing a hazard by
unexpected closure
Not possible to touch dangerous moving parts with P
the test probe described
21 MECHANICAL STRENGTH ----
21.1 Appliance has adequate mechanical strength and is P
constructed as to withstand rough handling
Checked by applying 3 blows to every point of the (see appended table) P
enclosure like to be weak, in accordance with test
Ehb of IEC 60068-2-75, spring hammer test, with
an impact energy of 0,5 J
The appliance shows no damage impairing P
compliance with this standard, and
compliance with 8.1, 15.1 and clause 29 not P
impaired
If doubt, supplementary or reinforced insulation N/A
subjected to the electric strength test of 16.3
If necessary, repetition of groups of three blows on N/A
a new sample
Safety requirements specified in annex EE applied. P
Pressure test in annex EE applies to parts other
than pressure vessels (IEC 60335-2-40/A1)
Safety requirements of ISO 5149 applied P
(IEC 60335-2-40/A2)
21.2 Accessible parts of solid insulation having strength P
to prevent penetration by sharp implements
Test not applicable if the thickness of P
supplementary insulation is at least 1 mm and
reinforced insulation at least 2 mm
The insulation is tested as specified, and does N/A
withstand the electric strength test of 16.3
22 CONSTRUCTION ----

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 33 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

22.1 Appliance marked with the first numeral of the IP N/A


system, relevant requirements of IEC 60529 are
fulfilled
22.2 Stationary appliance: means to ensure all-pole disconnection from the supply being ----
provided:
- a supply cord fitted with a plug, or P
- a switch complying with 24.3, or N/A
- a statement in the instruction sheet that a N/A
disconnection incorporated in the fixed wiring is to
be provided, or
- an appliance inlet N/A
Singe-pole switches and single-pole protective N/A
devices for the disconnection of heating elements
in single-phase, permanently connected class 01
and class I appliances, connected to the phase
conductor
22.3 Appliance provided with pins: no undue strain on N/A
socket-outlets
Applied torque not exceeding 0,25 Nm N/A
Pull force of 50 N to each pin after the appliance N/A
has being placed in the heating cabinet; when
cooled to room temperature the pins are not
displaced by more than 1 mm
Each pin subjected to a torque of 0,4 Nm; the pins N/A
are not rotating, unless
rotating does not impair compliance with this N/A
standard
22.4 Appliance for heating liquids and appliance causing P
undue vibration not provided with pins for insertion
into socket-outlets
22.5 No risk of electric shock when touching the pins of P
the plug, for appliances having a capacitor with
rated capacitance exceeding 0,1 F, the appliance
being disconnected from the supply at the instant of
voltage peak
Voltage not exceeding 34 V (V) ............................ : Max. 0,67V P
22.6 Electrical insulation not affected by condensing P
water or leaking liquid
Electrical insulation of class II appliances not P
affected if a hose ruptures or seal leaks
In case of doubt, test as described N/A
Electrical insulation not affected by snow P
penetration to appliance enclosure
(IEC 60335-2-40)
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 34 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

22.7 Adequate safeguards against the risk of excessive N/A


pressure in appliances containing liquid or gases or
having steam-producing devices
22.8 Electrical connections not subject to pulling during P
cleaning of compartments to which access can be
gained without the aid of a tool, and that are likely
to be cleaned in normal use
22.9 Insulation, internal wiring, windings, commutators P
and slip rings not exposed to oil, grease or similar
substances, unless
the substance has adequate insulating properties N/A
22.10 Not possible to reset voltage-maintained N/A
non-self-resetting thermal cut-outs by the operation
of an automatic switching device incorporated
within the appliance, if:
- a non-self-resetting thermal cut-out is required by N/A
the standard, and
- a voltage maintained non-self-resetting thermal N/A
cut-out is used to meet it
Non-self-resetting thermal motor protectors have a N/A
trip-free action, unless
they are voltage maintained N/A
Reset buttons of non-self-resetting controls so N/A
located or protected that accidental resetting is
unlikely
22.11 Reliable fixing of non-detachable parts that provide P
the necessary degree of protection against electric
shock, moisture or contact with moving parts
Obvious locked position of snap-in devices used for N/A
fixing such parts
No deterioration of the fixing properties of snap-in N/A
devices used in parts that are likely to be removed
during installation or servicing
Tests as described P
22.12 Handles, knobs etc. fixed in a reliable manner N/A
Fixing in wrong position of handles, knobs etc. N/A
indicating position of switches or similar
components not possible
Axial force 15 N applied to parts, the shape being N/A
so that an axial pull is unlikely to be applied
Axial force 30 N applied to parts, the shape being N/A
so that an axial pull is likely to be applied

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 35 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

22.13 Unlikely that handles, when gripped as in normal N/A


use, make the operator’s hand touch parts having a
temperature rise exceeding the value specified for
handles which are held for short periods only
22.14 No ragged or sharp edges creating a hazard for the P
user in normal use, or during user maintenance
No exposed pointed ends of self-tapping screws or P
other fasteners, likely to be touched by the user in
normal use or during user maintenance
22.15 Storage hooks and the like for flexible cords N/A
smooth and well rounded
22.16 Automatic cord reels cause no undue abrasion or N/A
damage to the sheath of the flexible cord, no
breakage of conductors strands and no undue wear
of contacts
Cord reel tested with 6000 operations, as specified N/A
Electric strength test of 16.3, voltage of 1000 V N/A
applied
22.17 Spacers not removable from the outside by hand or N/A
by means of a screwdriver or a spanner
22.18 Current-carrying parts and other metal parts P
resistant to corrosion
22.19 Driving belts not relied upon to provide the required N/A
level of insulation, unless
constructed to prevent inappropriate replacement N/A
22.20 Direct contact between live parts and thermal P
insulation effectively prevented, unless
material used is non-corrosive, non-hygroscopic N/A
and non-combustible
22.21 Wood, cotton, silk, ordinary paper and fibrous or P
hygroscopic material not used as insulation, unless
impregnated N/A
This requirement does not apply to magnesium N/A
oxide and mineral ceramic fibres used for the
electrical insulation of heating elements
22.22 Appliances not containing asbestos P
22.23 Oils containing polychlorinated biphenyl (PCB) not P
used
22.24 Bare heating elements adequately supported to N/A
prevent contact with accessible metal parts in case
of rupture or sagging (IEC 60335-2-40)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 36 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Bare heating elements only used with metal N/A


enclosures (wood or composite enclosures not
allowed) (IEC 60335-2-40)
22.25 Sagging heating conductors, except in class III N/A
appliances or class III constructions that do not
contain live parts, cannot come into contact with
accessible metal parts
22.26 For class III constructions the insulation between N/A
parts operating at safety extra-low voltage and
other live parts complies with the requirements for
double or reinforced insulation
22.27 Parts connected by protective impedance N/A
separated by double or reinforced insulation
22.28 Metal parts of class II appliances conductively N/A
connected to gas pipes or in contact with water,
separated from live parts by double or reinforced
insulation
22.29 Class II appliances permanently connected to fixed N/A
wiring so constructed that the required degree of
access to live parts is maintained after installation
22.30 Parts serving as supplementary or reinforced N/A
insulation fixed so that they cannot be removed
without being seriously damaged, or
so constructed that they cannot be replaced in an P
incorrect position, and so that if they are omitted,
the appliance is rendered inoperable or manifestly
incomplete
22.31 Neither clearances nor creepage distances over P
supplementary and reinforced insulation reduced
below values specified in clause 29 as a result of
wear
Neither clearances nor creepage distances P
between live parts and accessible parts reduced
below values for supplementary insulation if wires,
screws etc. become loose
22.32 Supplementary and reinforced insulation P
constructed or protected against pollution so that
clearances or creepage distances are not reduced
below the values in clause 29
Supplementary insulation of natural or synthetic N/A
rubber resistant to ageing, or arranged and
dimensioned so that creepage distances are not
reduced below values specified in 29.2
Ceramic material not tightly sintered, similar N/A
materials or beads alone not used as
supplementary or reinforced insulation

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 37 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Insulating material in which heating conductors are N/A


embedded is considered to be basic insulation, not
reinforced insulation
Oxygen bomb test at 70 °C for 96 h and 16 h at N/A
room temperature
22.33 Conductive liquids that are or may become P
accessible in normal use and conductive liquids
that are in contact with unearthed accessible metal
parts are not in direct contact with live parts
Electrodes not used for heating liquids N/A
For class II constructions, conductive liquids that P
are or may become accessible in normal use and
conductive liquids that are in contact with
unearthed accessible metal parts, not in direct
contact with basic or reinforced insulation, unless
the reinforced insulation consists of at least 3 layers N/A
For class II constructions, conductive liquids which N/A
are in contact with live parts, not in direct contact
with reinforced insulation, unless
the reinforced insulation consists of at least 3 layers N/A
An air layer not used as basic or supplementary N/A
insulation in a double insulation system if likely to
be bridged by leaking liquid
22.34 Shafts of operating knobs, handles, levers etc. not P
live, unless
the shaft is not accessible when the part is N/A
removed
22.35 For other than class III constructions, handles, N/A
levers and knobs, held or actuated in normal use,
not becoming live in the event of a failure of basic
insulation
Such parts being of metal, and their shafts or N/A
fixings are likely to become live in the event of a
failure of basic insulation, are either adequately
covered by insulation material or their accessible
parts are separated from their shafts or fixings by
supplementary insulation
This requirement does not apply to handles, levers N/A
and knobs on stationary appliances, other than
those of electrical components, provided they are
reliably connected to an earthing terminal or
earthing contact, or separated from live parts by
earthed metal
Insulating material covering metal handles, levers N/A
and knobs withstand the electric strength test of
16.3 for supplementary insulation

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 38 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

22.36 For appliances other than class III, handles N/A


continuously held in the hand in normal use so
constructed that when gripped as in normal use,
the operators hand is not likely to touch metal parts,
unless
they are separated from live parts by double or N/A
reinforced insulation
22.37 Capacitors in class II appliances not connected to N/A
accessible metal parts and their casings, if of
metal, separated from accessible metal parts by
supplementary insulation, unless
the capacitors comply with 22.42 N/A
22.38 Capacitors not connected between the contacts of P
a thermal cut-out
22.39 Lamp holders used only for the connection of lamps N/A
22.40 Motor-operated appliances and combined N/A
appliances intended to be moved while in
operation, or having accessible moving parts, fitted
with a switch to control the motor. The actuating
member of the switch being easily visible and
accessible
If the appliance cannot operate continuously, N/A
automatically or remotely without giving rise to a
hazard, appliances for remote operation being fitted
with a switch for stopping the operation. The
actuating member of the switch being easily visible
and accessible
22.41 No components, other than lamps, containing P
mercury
22.42 Protective impedance consisting of at least two N/A
separate components
Values specified in 8.1.4 not exceeded if any one of N/A
the components are short-circuited or
open-circuited
Resistors checked by the test of 14.1 a) in N/A
IEC 60065
Capacitors checked by the tests for class Y N/A
capacitors in IEC 60384-14
22.43 Appliances adjustable for different voltages, N/A
accidental changing of the setting of the voltage
unlikely to occur
22.44 Appliances not having an enclosure that is shaped P
or decorated like a toy

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 39 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

22.45 When air is used as reinforced insulation, P


clearances not reduced below the values specified
in 29.1.3 due to deformation as a result of an
external force applied to the enclosure
22.46 For programmable protective electronic circuits N/A
used to ensure compliance with the standard, the
software contains measures to control the
fault/error conditions in table R.1
Software that contains measures to control the N/A
fault/error conditions specified in table R.2 is to be
specified in parts 2 for particular constructions or to
address specific hazards
These requirements are not applicable to software N/A
used for functional purpose or compliance with
clause 11
22.47 Appliances connected to the water mains withstand N/A
the water pressure expected in normal use
No leakage from any part, including any inlet water N/A
hose
22.48 Appliances connected to the water mains N/A
constructed to prevent backsiphonage of
non-potable water
22.49 For remote operation, the duration of operation is to N/A
be set before the appliance can be started, unless
the appliance switches off automatically or can P
operate continuously without hazard
22.50 Controls incorporated in the appliance take priority P
over controls actuated by remote operation
22.51 There is a control on the appliance manually N/A
adjusted to the setting for remote operation before
the appliance can be operated in this mode
There is a visual indication showing that the N/A
appliance is adjusted for remote operation
These requirements not necessary on appliances that can operate as follows, ----
without giving rise to a hazard:
- continuously, or P
- automatically, or P
- remotely P
22.52 Socket-outlets on appliances accessible to the user N/A
in accordance with the socket-outlet system used in
the country in which the appliance is sold
22.101 Appliances intended to be fixed, securely fixed N/A
(IEC 60335-2-40)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 40 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

22.102.1 At least two thermal cut-outs in appliances with N/A


supplementary heating elements for air (first one be
self-resetting and other non-self-resetting thermal
cut-out) (IEC 60335-2-40/A2)
22.102.2 Appliances provided with supplementary heaters for N/A
water incorporate non-self-resetting thermal cut-out,
providing all-pole disconnection that operates
separately from water thermostats
(IEC 60335-2-40/A2)
However, for appliances intended to be connected N/A
to fixed wiring, the neutral conductor need not be
disconnected (IEC 60335-2-40/A2)
22.102.3 Thermal cut-outs of capillary type open in event of N/A
leakage from capillary tube (IEC 60335-2-40/A2)
22.103 Non-self-resetting cut-outs independent of other N/A
control devices (IEC 60335-2-40)
22.104 Containers of sanitary hot water heat pumps N/A
withstand twice permissible operating pressure in
closed containers (IEC 60335-2-40) or
0,15 MPa in open containers (IEC 60335-2-40) N/A
without leakage or rupture (IEC 60335-2-40) N/A
22.105 Air or vapour cushion in closed containers not N/A
exceeding 10 % (IEC 60335-2-40)
22.106 Pressure relief devices operating at 0,1 MPa over N/A
permissible operating pressure (IEC 60335-2-40)
22.107 Water outlet systems of open containers free from N/A
obstruction causing over-pressure
(IEC 60335-2-40)
Vented containers of sanitary hot water heat pumps N/A
always open to the atmosphere through appropriate
aperture (IEC 60335-2-40)
22.108 Not vented open containers subjected to test in N/A
accordance with clause 22.104 to vacuum of
33 kPa for 15 min (IEC 60335-2-40)
Container show no deformation which result in a N/A
hazard (IEC 60335-2-40)
22.109 Replacement of non-self-resetting thermal cut-outs N/A
does not damage other connections
(IEC 60335-2-40)
22.110 Non-self-resetting thermal cut-outs operate without N/A
short-circuiting live parts of different potential and
without causing contact between live parts and
enclosure (IEC 60335-2-40)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 41 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Test repeated five times without blowing 3 A fuse N/A


which connects appliance to earth
(IEC 60335-2-40)
Electric strength test as specified in clause 16.3 for N/A
supplementary heating elements (IEC 60335-2-40)
22.111 Manual resetting of thermostats not necessary after N/A
power supply interruption (IEC 60335-2-40)
22.112 Construction of refrigerating system comply with P
requirements of Section 3 of ISO 5149
(IEC 60335-2-40/A1)
22.113 Flammable refrigerant used, refrigerant tubing P
protected or enclosed to avoid mechanical damage
(IEC 60335-2-40/A1)
Tubing protected to extent that it will not be handled P
or used for carrying during moving of product
(IEC 60335-2-40/A1)
Tubing located within confines of cabinet P
considered to be protected from mechanical
damage (IEC 60335-2-40/A1)
22.114 Flammable refrigerant used, low temperature solder P
alloys, such as lead/tin alloys, not acceptable for
pipe connections (IEC 60335-2-40/A1)
22.115 Total refrigerant mass (M) of all refrigerating P
systems within appliance employing flammable
refrigerants, not exceed m3 defined in annex GG
(IEC 60335-2-40/A1)
22.116 Appliances using flammable refrigerants N/A
constructed that any leaked refrigerant not flow or
stagnate so as to cause fire or explosion hazard in
areas within appliance where electrical
components, which could be a source of ignition
and which could function under normal conditions
or in event of leak, fitted (IEC 60335-2-40/A1)
Separate components, such as thermostats, which N/A
charged with less than 0,5 g of flammable gas not
considered to cause fire or explosion hazard in
event of leakage of gas within component itself
(IEC 60335-2-40/A1)
All electrical components that could be a source of ignition and which could function ----
under normal conditions or in the event of a leak, comply with one of the following
(IEC 60335-2-40/A1):
- IEC 60079-15:2001, Cl. 9 to 26, for group IIA N/A
gases or the refrigerant used or an applicable
standard that makes electrical components
suitable for use in Zone 2, 1 or 0 as defined in
IEC 60079-14 (IEC 60335-2-40/A1)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 42 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

- Not be located in an area where a potentially N/A


flammable gas mixture will accumulate as
demonstrated by the test of annex FF
(IEC 60335-2-40/A1)
- Be located in an enclosure. The enclosure P
containing the electrical components comply with
IEC 60079-15:2001 for enclosures suitable for use
with group IIA gases or the refrigerant used
(IEC 60335-2-40/A1)
22.117 Temperatures on surfaces that exposed to leakage P
of flammable refrigerants not exceed auto-ignition
temperature of refrigerant reduced by 100 K; some
typical values given in annex BB
(IEC 60335-2-40/A1)
22.118 Flammable refrigerant used, all appliances charged P
with refrigerant at manufacturing location or
charged on site as recommended by manufacturer
(IEC 60335-2-40/A1)
Part of appliance that charged on site, which requires brazing or welding in ----
installation not shipped with flammable refrigerant charge. Joints made in
installation between parts of refrigerating system, with at least one part charged,
made in accordance with following (IEC 60335-2-40/A1):
- A brazed, welded, or mechanical connection shall N/A
be made before opening the valves to permit
refrigerant to flow between the refrigerating
system parts. A vacuum valve shall be provided to
evacuate the interconnecting pipe and/or any
uncharged refrigerating system part
(IEC 60335-2-40/A1)
- Reusable mechanical connectors and flared joints N/A
are not allowed indoors (IEC 60335-2-40/A1)
- Refrigerant tubing shall be protected or enclosed N/A
to avoid damage (IEC 60335-2-40/A1)
Flexible refrigerant connectors (such as connecting N/A
lines between the indoor and outdoor unit) that may
be displaced during normal operations shall be
protected against mechanical damage
(IEC 60335-2-40/A1)
23 INTERNAL WIRING ----
23.1 Wireways smooth and free from sharp edges P
Wires protected against contact with burrs, cooling P
fins etc.
Wire holes in metal well-rounded or provided with P
bushings
Wiring effectively prevented from coming into P
contact with moving parts

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 43 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

23.2 Beads etc. on live wires cannot change their N/A


position, and are not resting on sharp edges
Beads inside flexible metal conduits contained N/A
within an insulating sleeve
23.3 Electrical connections and internal conductors N/A
movable relatively to each other not exposed to
undue stress
Flexible metallic tubes not causing damage to N/A
insulation of conductors
Open-coil springs not used N/A
Adequate insulating lining provided inside a coiled N/A
spring, the turns of which touch one another
No damage after 10 000 flexings for conductors N/A
flexed during normal use, or
100 flexings for conductors flexed during user N/A
maintenance
Electric strength test of 16.3, 1000 V between live N/A
parts and accessible metal parts
Not more than 10 % of the strands of any conductor N/A
broken, and
not more than 30 % for wiring supplying circuits that N/A
consume no more than 15 W
23.4 Bare internal wiring sufficiently rigid and fixed N/A
23.5 The insulation of internal wiring subjected to the P
supply mains voltage withstanding the electrical
stress likely to occur in normal use
Basic insulation electrically equivalent to the basic N/A
insulation of cords complying with IEC 60227 or
IEC 60245, or
no breakdown when a voltage of 2000 V is applied P
for 15 min between the conductor and metal foil
wrapped around the insulation
23.6 Sleeving used as supplementary insulation on N/A
internal wiring retained in position by clamping at
both ends, or
be such that it can only be removed by breaking or P
cutting
23.7 The colour combination green/yellow only used for P
earthing conductors
23.8 Aluminium wires not used for internal wiring P
23.9 Stranded conductors not consolidated by soldering P
where they are subjected to contact pressure,
unless

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 44 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

the contact pressure is provided by spring terminals N/A


23.10 The insulation and sheath of internal wiring, N/A
incorporated in external hoses for the connection of
an appliance to the water mains, at least equivalent
to that of light polyvinyl chloride sheathed flexible
cord (60227 IEC 52)
24 COMPONENTS ----
24.1 Components comply with safety requirements in P
relevant IEC standards
List of components ................................................ : (see appended table) P
If components have not been tested and found to N/A
comply with relevant IEC standard for the number
of cycles specified, they are tested in accordance
with 24.1.1 to 24.1.9
For components mentioned in 24.1.1 to 24.1.9 no P
additional tests specified in the relevant component
standard are necessary other than those specified
in 24.1.1 to 24.1.9
Components not tested and found to comply with P
relevant IEC standard and components not marked
or not used in accordance with its marking, tested
under the conditions occurring in the appliance
Lampholders and starterholders that have not being N/A
tested and found to comply with the relevant IEC
standard, tested as a part of the appliance and
additionally according to the gauging and
interchangeability requirements of the relevant IEC
standard
No additional tests specified for nationally P
standardized plugs such as those detailed in
IEC/TR 60083 or connectors complying with the
standard sheets of IEC 60320-1 and IEC 60309
Motor-compressors not tested according to P
IEC 60335-2-34 (not necessary to meet all
requirements of IEC 60335-2-34) (IEC 60335-2-40)
24.1.1 Capacitors likely to be permanently subjected to the P
supply voltage and used for radio interference
suppression or for voltage dividing, complying with
IEC 60384-14
If the capacitors have to be tested, they are tested N/A
according to annex F
24.1.2 Safety isolating transformers complying with N/A
IEC 61558-2-6
If they have to be tested, they are tested according N/A
to annex G

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 45 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

24.1.3 Switches complying with IEC 61058-1, the number P


of cycles of operation being at least 10 000
If they have to be tested, they are tested according N/A
to annex H
If the switch operates a relay or contactor, the N/A
complete switching system is subjected to the test
If the switch only operates a motor staring relay N/A
complying with IEC 60730-2-10 with the number of
cycles of a least 10 000 as specified, the complete
switching system need not be tested
24.1.4 Automatic controls complying with IEC 60730-1 with the relevant part 2. The ----
number of cycles of operation being at least:
- thermostats: ................................................. 10 000 N/A
- temperature limiters: ...................................... 1 000 N/A
- self-resetting thermal cut-outs: ......................... 300 N/A
- voltage maintained non-self-resetting thermal cut- N/A
outs: .................................................................. 1 000
- other non-self-resetting thermal cut-outs: .......... 30 N/A
- timers:.............................................................3 000 N/A
- energy regulators: ..................................... 10 000 N/A
- thermostats which control motor-compressor N/A
(IEC/EN 60335-2-40): ............................. 100 000
- motor-compressor starting relays N/A
(IEC/EN 60335-2-40): ............................. 100 000
- automatic thermal motor-protectors for hermetic P
and semi-hermetic type motor-compressors (not
less than number of operations during locked rotor
test) (IEC/EN 60335-2-40): ................... min 2000
- manual reset thermal motor-protectors for N/A
hermetic and semi-hermetic type
motor-compressors (IEC/EN 60335-2-40): ...... 50
- other automatic thermal motor-protectors P
(IEC/EN 60335-2-40): .................................. 2000
- other manual reset thermal motor-protectors N/A
(IEC/EN 60335-2-40): ...................................... 30
The number of cycles for controls operating during N/A
clause 11 need not be declared, if the appliance
meets the requirements of this standard when they
are short-circuited
Thermal motor protectors are tested in combination N/A
with their motor under the conditions specified in
annex D

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 46 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

For water valves containing live parts and that are N/A
incorporated in external hoses for connection of an
appliance to the water mains, the degree of
protection declared for subclause 6.5.2 of
IEC 60730-2-8 is IPX7
24.1.5 Appliance couplers complying with IEC 60320-1 N/A
However, for appliances classified higher than N/A
IPX0, the appliance couplers complying with
IEC 60320-2-3
Interconnection couplers complying with N/A
IEC 60320-2-2
24.1.6 Small lamp holders similar to E10 lampholders N/A
complying with IEC 60238, the requirements for
E10 lampholders being applicable
24.1.7 For remote operation of the appliance via a N/A
telecommunication network, the relevant standard
for the telecommunication interface circuitry in the
appliance is IEC 62151
24.1.8 The relevant standard for thermal links is N/A
IEC 60691
Thermal links not complying with IEC 60691 are N/A
considered to be an intentionally weak part for the
purposes of clause 19
24.1.9 Contactors and relays, other than motor starting P
relays, tested as part of the appliance
They are also tested in accordance with clause 17 P
of IEC 60730-1, the number of cycles of operations
in 24.1.4 selected according to the contactor or
relay function in the appliance .............................. :
24.2 Appliances not fitted with: ----
- switches or automatic controls in flexible cords P
- devices causing the protective device in the fixed P
wiring to operate in the event of a fault in the
appliance
- thermal cut-outs that can be reset by soldering, P
unless
the solder has a melding point of at least 230 °C N/A
24.3 Switches intended for all-pole disconnection of N/A
stationary appliances are directly connected to the
supply terminals and have a contact separation in
all poles, providing full disconnection under
overvoltage category III conditions

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 47 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

24.4 Plugs and socket-outlets for extra-low voltage N/A


circuits and heating elements, not interchangeable
with plugs and socket-outlets listed in
IEC/TR 60083 or IEC 60906-1 or with connectors
and appliance inlets complying with the standard
sheets of IEC 60320-1
24.5 Capacitors in auxiliary windings of motors marked P
with their rated voltage and capacitance, and used
accordingly
Voltage across capacitors in series with a motor Max.: 398V P
winding does not exceed 1,1 times rated voltage,
when the appliance is supplied at 1,1 times rated
voltage under minimum load
24.6 Working voltage of motors connected to the supply N/A
mains and having basic insulation that is
inadequate for the rated voltage of the appliance,
not exceeding 42 V
In addition, the motors comply with the N/A
requirements of annex I
24.7 Detachable hose-sets for connection of appliances N/A
to the water mains comply with IEC 61770
They are supplied with the appliance N/A
Appliances intended to be permanently connected N/A
to the water mains not connected by a detachable
hose-set
24.8 Motor running capacitors in appliances for which P
30.2.3 is applicable and that are permanently
connected in series with a motor winding, not
causing a hazard in event of a failure
One or more of the following conditions are to be met: ----
- the capacitors are of class P2 according to P
IEC 60252-1
- the capacitors are housed within a metallic or N/A
ceramic enclosure
- the distance of separation of the outer surface to N/A
adjacent non-metallic parts exceeds 50 mm
- adjacent non-metallic parts within 50 mm N/A
withstand the needle-flame test of annex E
- adjacent non-metallic parts within 50 mm N/A
classified as at least V-1 according to
IEC 60695-11-10
24.101 Replaceable parts of thermal control devices N/A
identified by marking (IEC 60335-2-40)
25 SUPPLY CONNECTION AND EXTERNAL FLEXIBLE CORDS ----

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 48 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

25.1 Appliance not intended for permanent connection to fixed wiring, means for ----
connection to the supply:
- supply cord fitted with a plug, P
- an appliance inlet having at least the same degree N/A
of protection against moisture as required for the
appliance, or
- pins for insertion into socket-outlets N/A
Supply cord fitted with plug provided, if (IEC 60335-2-40): ----
- appliance only for indoor use (IEC 60335-2-40), P
- marked with rating of 25 A or less and P
(IEC 60335-2-40)
- complies with code requirements of country where N/A
it will be used (IEC 60335-2-40).
Appliance inlet not allowed (IEC 60335-2-40) N/A
25.2 Appliance not provided with more than one means P
of connection to the supply mains
Stationary appliance for multiple supply may be N/A
provided with more than one means of connection,
provided electric strength test of 1250 V for 1 min
between each means of connection causes no
breakdown
25.3 Appliance intended to be permanently connected to fixed wiring provided with one ----
of the following means for connection to the supply mains:
- a set of terminals allowing the connection of a N/A
flexible cord
- a fitted supply cord N/A
- a set of supply leads accommodated in a suitable N/A
compartment
- a set of terminals for the connection of cables of N/A
fixed wiring, cross-sectional areas specified in 26.6,
and the appliance allows the connection of the
supply conductors after the appliance has been
fixed to its support
- a set of terminals and cable entries, conduit N/A
entries, knock-outs or glands, allowing connection
of appropriate types of cable or conduit, and the
appliance allows the connection of the supply
conductors after the appliance has been fixed to its
support
For a fixed appliance constructed so that parts can N/A
be removed to facilitate easy installation, this
requirement is met if it is possible to connect the
fixed wiring without difficulty after a part of the
appliance has been fixed to its support

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 49 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

25.4 Cable and conduit entries, rated current of N/A


appliance not exceeding 16 A, dimension according
to table 10 (mm) .................................................... :
Introduction of conduit or cable does not reduce N/A
clearances or creepage distances below values
specified in clause 29
25.5 Method for assembling the supply cord to the appliance: ----
- type X attachment N/A
- type Y attachment P
- type Z attachment, if allowed in relevant part 2 N/A
Type X attachment, other than those with a N/A
specially prepared cord, not used for flat twin tinsel
cords
For multi-phase appliances supplied with a supply N/A
cord and that are intended to be permanently
connected to fixed wiring, the supply cord is
assembled to the appliance by type Y attachment
25.6 Plugs fitted with only one flexible cord N/A
25.7 Supply cords, other than for class III appliances, being one of the following types: ----
- rubber sheathed (at least 60245 IEC 53) N/A
- polychloroprene sheathed (at least 60245 IEC 57) N/A
- cross-linked polyvinyl chloride sheathed (at least N/A
60245 IEC 88)
- polyvinyl chloride sheathed. Not used if they are likely to touch metal parts having ----
a temperature rise exceeding 75 K during the test of clause 11
- light polyvinyl chloride sheathed cord N/A
(60227 IEC 52), for appliances not exceeding
3 kg
- ordinary polyvinyl chloride sheathed cord H05VV-F P
(60227 IEC 53), for other appliances
- heat resistant polyvinyl chloride sheathed. Not used for type X attachment other ----
than specially prepared cords
- heat-resistant light polyvinyl chloride sheathed N/A
cord (60227 IEC 56), for appliances not
exceeding 3 kg
- heat-resistant polyvinyl chloride sheathed cord N/A
(60227 IEC 57), for other appliances
Supply cords for class III appliances adequately N/A
insulated
Test with 500 V for 2 min for supply cords of N/A
class III appliances that contain live parts

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 50 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Supply cords for outdoor use not lighter than N/A


polychloroprene sheathed flexible cord
(60245 IEC 57) (IEC 60335-2-40)
25.8 Nominal cross-sectional area of supply cords not Measured current: <16A, P
less than table 11; rated current (A); cross-sectional Cross-sectional area: 1,0mm2
area (mm²) ............................................................ :
25.9 Supply cords not in contact with sharp points or P
edges
25.10 Supply cord of class I appliances have a P
green/yellow core for earthing
25.11 Conductors of supply cords not consolidated by P
soldering where they are subject to contact
pressure, unless
the contact pressure is provided by spring terminals N/A
25.12 Insulation of the supply cord not damaged when N/A
moulding the cord to part of the enclosure
25.13 Inlet openings so constructed as to prevent P
damage to the supply cord
If the enclosure at the inlet opening is not of N/A
insulating material, a non-detachable lining or
bushing complying with 29.3 for supplementary
insulation provided
If unsheathed supply cord, a similar additional N/A
bushing or lining is required, unless the appliance is
class 0, or N/A
a class III appliance not containing live parts N/A
25.14 Supply cords moved while in operation adequately N/A
protected against excessive flexing
Flexing test, as described: ----
- applied force (N) ................................................. : N/A
- number of flexings .............................................. : N/A
The test does not result in: ----
- short-circuit between the conductors, such that the N/A
current exceeds a value of twice the rated current
- breakage of more than 10 % of the strands of any N/A
conductor
- separation of the conductor from its terminal N/A
- loosening of any cord guard N/A
- damage to the cord or the cord guard N/A
- broken strands piercing the insulation and N/A
becoming accessible

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 51 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

25.15 For appliances with supply cord and appliances to P


be permanently connected to fixed wiring by a
flexible cord, conductors of the supply cord relieved
from strain, twisting and abrasion by use of cord
anchorage
The cord cannot be pushed into the appliance to P
such an extent that the cord or internal parts of the
appliance can be damaged
Pull and torque test of supply cord, values shown in 100N, 0,35Nm P
table 12: mass (kg); pull (N); torque (not on
automatic cord reel) (Nm) ..................................... :
Cord not damaged and max. 2 mm displacement of P
the cord
25.16 Cord anchorages for type X attachments constructed and located so that: ----
- replacement of the cord is easily possible N/A
- it is clear how the relief from strain and the N/A
prevention of twisting are obtained
- they are suitable for different types of supply cord N/A
- cord cannot touch the clamping screws of cord N/A
anchorage if these screws are accessible, unless
they are separated from accessible metal parts by N/A
supplementary insulation
- the cord is not clamped by a metal screw which N/A
bears directly on the cord
- at least one part of the cord anchorage securely N/A
fixed to the appliance, unless
it is part of a specially prepared cord N/A
- screws which have to be operated when replacing N/A
the cord do not fix any other component, unless
the appliance becomes inoperative or incomplete or N/A
the parts cannot be removed without a tool
- if labyrinths can be bypassed the test of 25.15 is N/A
nevertheless withstood
- for class 0, 0I and I appliances they are of N/A
insulating material or are provided with an
insulating lining, unless
failure of the insulation of the cord does not make N/A
accessible metal parts live
- for class II appliances they are of insulating N/A
material, or
if of metal, they are insulated from accessible metal N/A
parts by supplementary insulation

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 52 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

After the test of 25.15, under the conditions N/A


specified, the conductors have not moved by more
than 1 mm in the terminals
25.17 Adequate cord anchorages for type Y and Z P
attachment, test with the cord supplied with the
appliance
25.18 Cord anchorages only accessible with the aid of a P
tool, or
Constructed so that the cord can only be fitted with N/A
the aid of a tool
25.19 Type X attachment, glands not used as cord N/A
anchorage in portable appliances
Tying the cord into a knot or tying the cord with N/A
string not used
25.20 The insulated conductors of the supply cord for P
type Y and Z attachment additionally insulated from
accessible metal parts
25.21 Space for supply cord for type X attachment or for connection of fixed wiring ----
constructed:
- to permit checking of conductors with respect to N/A
correct positioning and connection before fitting any
cover
- so there is no risk of damage to the conductors or N/A
their insulation when fitting the cover
- for portable appliances, so that the uninsulated N/A
end of a conductor, if it becomes free from the
terminal, prevented from contact with accessible
metal parts
2 N test to the conductor for portable appliances; N/A
no contact with accessible metal parts
25.22 Appliance inlets: ----
- live parts not accessible during insertion or N/A
removal
Requirement not applicable to appliance inlets N/A
complying with IEC 60320-1
- connector can be inserted without difficulty N/A
- the appliance is not supported by the connector N/A
- not for cold conditions if temp. rise of external N/A
metal parts exceeds 75 K during clause 11, unless
the supply cord is unlikely to touch such metal parts N/A
25.23 Interconnection cords comply with the requirements N/A
for the supply cord, except that:

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 53 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

- the cross-sectional area of the conductors is N/A


determined on the basis of the maximum current
during clause 11
- the thickness of the insulation may be reduced N/A
If necessary, electric strength test of 16.3 N/A
25.24 Interconnection cords not detachable without the N/A
aid of a tool if compliance with this standard is
impaired when they are disconnected
25.25 Dimensions of pins that are inserted into N/A
socket-outlets compatible with the dimensions of
the relevant socket-outlet.
Dimensions of pins and engagement face in N/A
accordance with the dimensions of the relevant
plug in IEC/TR 60083
26 TERMINALS FOR EXTERNAL CONDUCTORS ----
26.1 Appliances provided with terminals or equally P
effective devices for connection of external
conductors
Terminals only accessible after removal of a P
non-detachable cover, except
for class III appliances that do not contain live parts N/A
Earthing terminals may be accessible if a tool is N/A
required to make the connections and means are
provided to clamp the wire independently from its
connection
26.2 Appliances with type X attachment and appliances N/A
for the connection of cables to fixed wiring provided
with terminals in which connections are made by
means of screws, nuts or similar devices, unless
the connections are soldered N/A
Screws and nuts not used to fix any other N/A
component, except
internal conductors, if so arranged that they are N/A
unlikely to be displaced when fitting the supply
conductors
If soldered connections used, the conductor so N/A
positioned or fixed that reliance is not placed on
soldering alone, unless
barriers provided so that neither clearances nor N/A
creepage distances between live parts and other
metal parts reduced below the values for
supplementary insulation if the conductor becomes
free at the soldered joint

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 54 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

26.3 Terminals for type X attachment and for connection N/A


of cables of fixed wiring so constructed that the
conductor is clamped between metal surfaces with
sufficient contact pressure but without damaging
the conductor
Terminals fixed so that when the clamping means is tightened or loosened: ----
- the terminal does not become loose N/A
- internal wiring is not subjected to stress N/A
- neither clearances nor creepage distances are N/A
reduced below the values in clause 29
Compliance checked by inspection and by the test N/A
of subclause 9.6 of IEC 60999-1, the torque applied
being equal to two-thirds of the torque specified
(Nm) ...................................................................... :
No deep or sharp indentations of the conductors N/A
26.4 Terminals for type X attachment, except those N/A
having a specially prepared cord and those for the
connection of cables of fixed wiring, no special
preparation of conductors such as by soldering, use
of cable lugs, eyelets or similar, and
so constructed or placed that conductors prevented N/A
from slipping out when clamping screws or nuts are
tightened
26.5 Terminals for type X attachment so located or N/A
shielded that if a wire of a stranded conductor
escapes, no risk of accidental connection to other
parts that result in a hazard
Stranded conductor test, 8 mm insulation removed N/A
No contact between live parts and accessible metal N/A
parts and,
for class II constructions, between live parts and N/A
metal parts separated from accessible metal parts
by supplementary insulation only
26.6 Terminals for type X attachment and for connection N/A
of cables of fixed wiring suitable for connection of
conductors with cross-sectional area according to
table 13; rated current (A); nominal cross-sectional
area (mm²) ............................................................ :
If a specially prepared cord is used, terminals need N/A
only be suitable for that cord
26.7 Terminals for type X attachment, except in class III N/A
appliances not containing live parts, accessible
after removal of a cover or part of the enclosure

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 55 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

26.8 Terminals for the connection of fixed wiring, N/A


including the earthing terminal, located close to
each other
26.9 Terminals of the pillar type constructed and located N/A
as specified
26.10 Terminals with screw clamping and screwless N/A
terminals not used for flat twin tinsel cords, unless
conductors ends fitted with means suitable for N/A
screw terminals
Pull test of 5 N to the connection N/A
26.11 For type Y and Z attachment, soldered, welded, P
crimped or similar connections may be used
For class II appliances, the conductor so positioned N/A
or fixed that reliance is not placed on soldering,
welding or crimping alone
If soldering, welding or crimping alone used, N/A
barriers provided so that clearances and creepage
distances between live parts and other metal parts
are not reduced below the values for
supplementary insulation if the conductor becomes
free
27 PROVISION FOR EARTHING ----
27.1 Accessible metal parts of class 0I and I appliances P
permanently and reliably connected to an earthing
terminal or earthing contact of the appliance inlet
Earthing terminals and earthing contacts not P
connected to the neutral terminal
Class 0, II and III appliances have no provision for N/A
earthing
Safety extra-low voltage circuits not earthed, unless N/A
protective extra-low voltage circuits N/A
27.2 Clamping means of earthing terminals adequately P
secured against accidental loosening
Terminals for the connection of external N/A
equipotential bonding conductors allow connection
of conductors of 2,5 to 6 mm², and
do not provide earthing continuity between different N/A
parts of the appliance, and
conductors cannot be loosened without the aid of a N/A
tool

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 56 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

27.3 For a detachable part having an earth connection N/A


and being plugged into another part of the
appliance, the earth connection is made before and
separated after current-carrying connections when
removing the part
For appliances with supply cords, current-carrying P
conductors become taut before earthing conductor,
if the cord slips out of the cord anchorage
27.4 No risk of corrosion resulting from contact between P
parts of the earthing terminal and the copper of the
earthing conductor or other metal
Parts providing earthing continuity, other than parts P
of a metal frame or enclosure, have adequate
resistance to corrosion
If of steel, these parts provided with an P
electroplated coating with a thickness at least 5 µm
Adequate protection against rusting of parts of P
coated or uncoated steel, only intended to provide
or transmit contact pressure
In the body of the earthing terminal is a part of a N/A
frame or enclosure of aluminium or aluminium
alloys, precautions taken to avoid risk of corrosion
27.5 Low resistance of connection between earthing P
terminal and earthed metal parts
This requirement does not apply to connections P
providing earthing continuity in the protective
extra-low voltage circuit, provided the clearances of
basic insulation are based on the rated voltage of
the appliance
Resistance not exceeding 0,1 at the specified Max. 0,028Ω P
low-resistance test ( ) ......................................... :
27.6 The printed conductors of printed circuit boards not N/A
used to provide earthing continuity in hand-held
appliances.
They may be used to provide earthing continuity in N/A
other appliances if at least two tracks are used with
independent soldering points and the appliance
complies with 27.5 for each circuit
28 SCREWS AND CONNECTIONS ----
28.1 Fixings, electrical connections and connections P
providing earthing continuity withstand mechanical
stresses
Screws not of soft metal liable to creep, such as P
zinc or aluminium
Diameter of screws of insulating material min. N/A
3 mm
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 57 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Screws of insulating material not used for any N/A


electrical connections or connections providing
earthing continuity
Screws used for electrical connections or P
connections providing earthing continuity screwed
into metal
Screws not of insulating material if their P
replacement by a metal screw can impair
supplementary or reinforced insulation
For type X attachment, screws to be removed for N/A
replacement of supply cord or for user
maintenance, not of insulating material if their
replacement by a metal screw impairs basic
insulation
For screws and nuts; torque-test as specified in (see appended table) P
table 14 ................................................................. :
28.2 Electrical connections and connections providing P
earthing continuity constructed so that contact
pressure is not transmitted through non-ceramic
insulating material liable to shrink or distort, unless
there is resiliency in the metallic parts to N/A
compensate for shrinkage or distortion of the
insulating material
This requirement does not apply to electrical connections in circuits of appliances ----
for which:
- 30.2.2 is applicable and that carry a current not N/A
exceeding 0,5 A
- 30.2.3 is applicable and that carry a current not N/A
exceeding 0,2 A
28.3 Space-threaded (sheet metal) screws only used for N/A
electrical connections if they clamp the parts
together
Thread-cutting (self-tapping) screws and thread N/A
rolling screws only used for electrical connections if
they generate a full form standard machine screw
thread
Thread-cutting (self-tapping) screws not used if N/A
they are likely to be operated by the user or
installer
Thread-cutting, thread rolling and space threaded screws may be used in ----
connections providing earthing continuity provided it is not necessary to disturb the
connection:
- in normal use, N/A
- during user maintenance, N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 58 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

- when replacing a supply cord having a type X N/A


attachment, or
- during installation N/A
At least two screws being used for each connection N/A
providing earthing continuity, unless
the screw forms a thread having a length of at least N/A
half the diameter of the screw
28.4 Screws and nuts that make mechanical connection P
secured against loosening if they also make
electrical connections or connections providing
earthing continuity
This requirement does not apply to screws in the P
earthing circuit if at least two screws are used, or
if an alternative earthing circuit is provided N/A
Rivets for electrical connections or connections N/A
providing earthing continuity secured against
loosening if the connections are subjected to
torsion
29 CLEARANCES, CREEPAGE DISTANCES AND SOLID INSULATION ----
Clearances, creepage distances and solid P
insulation withstand electrical stress
For coatings used on printed circuits boards to N/A
protect the microenvironment (Type 1) or to provide
basic insulation (Type 2), annex J applies ............ :
The microenvironment is pollution degree 1 under N/A
type 1 protection
For type 2 protection, the spacing between the N/A
conductors before the protection is applied is not
less than the values specified in Table 1 of
IEC 60664-3
These values apply to functional, basic, N/A
supplementary and reinforced insulation .............. :
For motor-compressor not complying with P
IEC 60335-2-34, additions and modifications as
specified (IEC 60335-2-40)
29.1 Clearances not less than the values specified in (see appended table) P
table 16, taking into account the rated impulse
voltage for the overvoltage categories of table 15,
unless.................................................................... :
for basic insulation and functional insulation they N/A
comply with the impulse voltage test of clause 14

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 59 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

However, if the distances are affected by wear, P


distortion, movement of the parts or during
assembly, the clearances for rated impulse
voltages of 1500 V and above are increased by
0,5 mm and the impulse voltage test is not
applicable
Impulse voltage test is not applicable: ----
- when the microenvironment is pollution degree 3, N/A
or
- for basic insulation of class 0 and class 01 N/A
appliances
Appliances are in overvoltage category II P
A force of 2 N is applied to bare conductors, other P
than heating elements
A force of 30 N is applied to accessible surfaces P
29.1.1 Clearances of basic insulation withstand the P
overvoltages, taking into account the rated impulse
voltage
The values of table 16 or the impulse voltage test of (see appended table) P
clause 14 are applicable ....................................... :
Clearance at the terminals of tubular sheathed N/A
heating elements may be reduced to 1,0 mm if the
microenvironment is pollution degree 1
Lacquered conductors of windings considered to be P
bare conductors
29.1.2 Clearances of supplementary insulation not less (see appended table) P
than those specified for basic insulation in table 16
.............................................................................. :
29.1.3 Clearances of reinforced insulation not less than (see appended table) P
those specified for basic insulation in table 16,
using the next higher step for rated impulse voltage
.............................................................................. :
For double insulation, with no intermediate N/A
conductive part between basic and supplementary
insulation, clearances are measured between live
parts and the accessible surface, and the insulation
system is treated as reinforced insulation
29.1.4 Clearances for functional insulation are the largest values determined from: ----
- table 16 based on the rated impulse voltage ...... : (see appended table) P
- table F.7a in IEC 60664-1, frequency not N/A
exceeding 30 kHz
- clause 4 of IEC 60664-4, frequency exceeding N/A
30 kHz

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 60 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

If values of table 16 are largest, the impulse voltage N/A


test of clause 14 may be applied instead, unless
the microenvironment is pollution degree 3, or N/A
the distances can be affected by wear, distortion, N/A
movement of the parts or during assembly
However, clearances are not specified if the N/A
appliance complies with clause 19 with the
functional insulation short-circuited
Lacquered conductors of windings considered to be P
bare conductors
However, clearances at crossover points are not P
measured
Clearance between surfaces of PTC heating N/A
elements may be reduced to 1mm
29.1.5 Appliances having higher working voltages than rated voltage, clearances for basic ----
insulation are the largest values determined from:
- table 16 based on the rated impulse voltage ...... : P
- table F.7a in IEC 60664-1, frequency not N/A
exceeding 30 kHz
- clause 4 of IEC 60664-4, frequency exceeding N/A
30 kHz
If clearances for basic insulation are selected from N/A
Table F.7a of IEC 60664-1 or clause 4 of
IEC 60664-4, the clearances of supplementary
insulation are not less than those specified for basic
insulation
If clearances for basic insulation are selected from N/A
Table F.7a of IEC 60664-1, the clearances of
reinforced insulation dimensioned as specified in
Table F.7a are to withstand 160% of the withstand
voltage required for basic insulation
If clearances for basic insulation are selected from N/A
clause 4 of IEC 60664-4, the clearances of
reinforced insulation are twice the value required
for basic insulation
If the secondary winding of a step-down N/A
transformer is earthed, or if there is an earthed
screen between the primary and secondary
windings, clearances of basic insulation on the
secondary side not less than those specified in
table 16, but using the next lower step for rated
impulse voltage
Circuits supplied with a voltage lower than rated N/A
voltage, clearances of functional insulation are
based on the working voltage used as the rated
voltage in table 15
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 61 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

29.2 Creepage distances not less than those appropriate (see appended table) P
for the working voltage, taking into account the
material group and the pollution degree ............... :
Pollution degree 2 applies, unless Main power box P
- precautions taken to protect the insulation; N/A
pollution degree 1
- insulation subjected to conductive pollution; Parts in airflow P
pollution degree 3
A force of 2 N is applied to bare conductors, other P
than heating elements
A force of 30 N is applied to accessible surfaces P
In a double insulation system, the working voltage N/A
for both the basic and supplementary insulation is
taken as the working voltage across the complete
double insulation system
Insulation located in airflow, pollution degree 3 P
unless (IEC 60335-2-40)
insulation enclosed or located so that unlikely to be N/A
exposed to pollution due to normal use
(IEC 60335-2-40)
29.2.1 Creepage distances of basic insulation not less (see appended table) P
than specified in table 17 ...................................... :
However, if the working voltage is periodic and has N/A
a frequency exceeding 30 kHz, the creepage
distances are also determined from table 2 of
IEC 60664-4, these values being used if exceeding
the values in table 17 ............................................ :
Except for pollution degree 1, corresponding N/A
creepage distance not less than the minimum
specified for the clearance in table 16, if the
clearance has been checked according to the test
of clause 14........................................................... :
29.2.2 Creepage distances of supplementary insulation at (see appended table) P
least those specified for basic insulation in table 17,
or ........................................................................... :
Table 2 of IEC 60664-4, as applicable ................. : N/A
29.2.3 Creepage distances of reinforced insulation at least (see appended table) P
double those specified for basic insulation in table
17, or ..................................................................... :
Table 2 of IEC 60664-4, as applicable ................. : N/A
29.2.4 Creepage distances of functional insulation not less (see appended table) P
than specified in table 18 ...................................... :

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 62 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

However, if the working voltage is periodic and has N/A


a frequency exceeding 30 kHz, the creepage
distances are also determined from table 2 of
IEC 60664-4, these values being used if exceeding
the values in table 18 ............................................ :
Creepage distances may be reduced if the N/A
appliance complies with clause 19 with the
functional insulation short-circuited
29.3 Supplementary and reinforced insulation have P
adequate thickness, or a sufficient number of
layers, to withstand the electrical stresses
Compliance checked: ----
- by measurement, in accordance with 29.3.1, or P
- by an electric strength test in accordance with N/A
29.3.2, or
- by an assessment of the thermal quality of the N/A
material combined with an electric strength test, in
accordance with 29.3.3, and
for accessible parts of reinforced insulation N/A
consisting of a single layer, by measurement in
accordance with 29.3.4, or
- as specified in subclause 6.3 of IEC 60664-4 for N/A
insulation that is subjected to any periodic voltage
having a frequency exceeding 30 kHz
29.3.1 Supplementary insulation have a thickness of at P
least 1 mm
Reinforced insulation have a thickness of at least N/A
2 mm
29.3.2 Each layer of material withstand the electric N/A
strength test of 16.3 for supplementary insulation
Supplementary insulation consist of at least 2 N/A
layers
Reinforced insulation consist of at least 3 layers N/A
29.3.3 The insulation is subjected to the dry heat test Bb N/A
of IEC 60068-2-2, followed by
the electric strength test of 16.3 N/A
If the temperature rise during the tests of clause 19 N/A
does not exceed the value specified in table 3, the
test of IEC 60068-2-2 is not carried out
29.3.4 Thickness of accessible parts of reinforced N/A
insulation consisting of a single layer not less than
specified in table 19 .............................................. :
30 RESISTANCE TO HEAT AND FIRE ----

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 63 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

30.1 External parts of non-metallic material, P


parts supporting live parts, and P
parts of thermoplastic material providing P
supplementary or reinforced insulation
sufficiently resistant to heat P
Ball-pressure test according to IEC 60695-10-2 P
External parts tested at 40 °C plus the maximum (see appended table) P
temperature rise determined during the test of
clause 11, or at 75 °C, whichever is the higher;
temperature (C) ................................................... :
Parts supporting live parts tested at 40 °C plus the (see appended table) P
maximum temperature rise determined during the
test of clause 11, or at 125 °C, whichever is the
higher; temperature (C) ....................................... :
Parts of thermoplastic material providing N/A
supplementary or reinforced insulation tested at
25 °C plus the maximum temperature rise
determined during clause 19, if higher; temperature
(C)........................................................................ :
30.2 Parts of non-metallic material resistant to ignition P
and spread of fire
This requirement does not apply to: ----
parts having a mass not exceeding 0,5 g, provided P
the cumulative effect is unlikely to propagate flames
that originate inside the appliance by propagating
flames from one part to another, or
decorative trims, knobs and other parts unlikely to P
be ignited or to propagate flames that originate
inside the appliance
Compliance checked by the test of 30.2.1, and in P
addition:
- for attended appliances, 30.2.2 applies N/A
- for unattended appliances, 30.2.3 applies P
For appliances for remote operation, 30.2.3 applies N/A
For base material of printed circuit boards, 30.2.4 P
applies
30.2.1 Parts of non-metallic material subjected to the P
glow-wire test of IEC 60695-2-11 at 550 °C
However, test not carried out if the material is N/A
classified as having a glow-wire flammability index
according to IEC 60695-2-12 of at least 550 °C, or
the material is classified at least HB40 according to N/A
IEC 60695-11-10

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 64 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Parts for which the glow-wire test cannot be carried N/A


out need to meet the requirements in ISO 9772 for
material classified HBF
30.2.3 Appliances operated while unattended, tested as P
specified in 30.2.3.1 and 30.2.3.2
The tests are not applicable to conditions as P
specified ................................................................ :
30.2.3.1 Parts of non-metallic material supporting P
connections carrying a current exceeding 0,2 A
during normal operation, and
parts of non-metallic material, other than small P
parts, within a distance of 3 mm,
subjected to the glow-wire test of IEC 60695-2-11 P
with a test severity of 850 °C
Glow-wire applied to an interposed shielding N/A
material, if relevant
The glow-wire test is not carried out on parts of N/A
material classified as having a glow-wire
flammability index according to IEC 60695-2-12 of
at least 850 °C
30.2.3.2 Parts of non-metallic material supporting P
connections, and
parts of non-metallic material within a distance of P
3 mm,
subjected to glow-wire test of IEC 60695-2-11 P
The test severity is: ----
- 750 °C, for connections carrying a current P
exceeding 0,2 A during normal operation
- 650 °C, for other connections P
Glow-wire applied to an interposed shielding N/A
material, if relevant
However, the glow-wire test of 750 °C or 650 °C as appropriate, is not carried out ----
on parts of material fulfilling both or either of the following classifications:
- a glow-wire ignition temperature according to N/A
IEC 60695-2-13 of at least:
- 775 °C, for connections carrying a current N/A
exceeding 0,2 A during normal operation
- 675 °C, for other connections N/A
- a glow-wire flammability index according to N/A
IEC 60695-2-12 of at least:
- 750 °C, for connections carrying a current N/A
exceeding 0,2 A during normal operation

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 65 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

- 650 °C, for other connections N/A


The glow-wire test is also not carried out on small parts. These parts are to: ----
- comprise material having a glow-wire ignition N/A
temperature of at least 775 °C or 675 °C as
appropriate, or
- comprise material having a glow-wire flammability N/A
index of at least 750 °C or 650 °C as appropriate,
or
- comply with the needle-flame test of annex E, or N/A
- comprise material classified as V-0 or V-1 N/A
according to IEC 60695-11-10
The consequential needle-flame test of annex E applied to non-metallic parts that ----
encroach within the vertical cylinder placed above the centre of the connection zone
and on top of the non-metallic parts supporting current-carrying connections, and
parts of non-metallic material within a distance of 3 mm of such connections if these
parts are those:
- parts that withstood the glow-wire test of N/A
IEC 60695-2-11 of 750 °C or 650 °C as
appropriate, but produce a flame that persist longer
than 2 s, or
- parts that comprised material having a glow-wire N/A
flammability index of at least 750 °C or 650 °C as
appropriate, or
- small parts, that comprised material having a N/A
glow-wire flammability index of at least 750 °C or
650 °C as appropriate, or
- small parts for which the needle-flame test of N/A
annex E was applied, or
- small parts for which a material classification of N/A
V-0 or V-1 was applied
However, the consequential needle-flame test is not carried out on non-metallic ----
parts, including small parts, within the cylinder that are:
- parts having a glow-wire ignition temperature of at N/A
least 775 °C or 675 °C as appropriate, or
- parts comprising material classified as V-0 or V-1 N/A
according to IEC 60695-11-10, or
- parts shielded by a flame barrier that meets the N/A
needle-flame test of annex E or that comprises
material classified as V-0 or V-1 according to
IEC 60695-11-10
30.2.4 Base material of printed circuit boards subjected to P
the needle-flame test of annex E
Test not applicable to conditions as specified ...... : P
31 RESISTANCE TO RUSTING ----

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 66 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Relevant ferrous parts adequately protected P


against rusting
Tests specified in part 2 when necessary P
Salt mist test of IEC 60068-2-52, severity 2 P
(IEC 60335-2-40)
Before test, coatings are scratched by means of a P
harden steel pin as specified (IEC 60335-2-40)
Five scratches made at least 5 mm apart and at P
least 5 mm from the edges (IEC 60335-2-40)
Appliance not deteriorated to such an extent that P
compliance with clause 8 and 27 is impaired
(IEC 60335-2-40)
Coating not be broken and not loosened from the P
metal surface (IEC 60335-2-40)
A ANNEX A (INFORMATIVE) ----
ROUTINE TESTS
Description of routine tests to be carried out by the N/A
manufacturer
B ANNEX B (NORMATIVE) ----
APPLIANCES POWERED BY RECHARGEABLE BATTERIES
The following modifications to this standard are N/A
applicable for appliances powered by batteries that
are recharged in the appliance
This annex does not apply to battery chargers N/A
3.1.9 Appliance operated under the following conditions: ----
- the appliance, supplied by its fully charged N/A
battery, operated as specified in relevant part 2
- the battery is charged, the battery being initially N/A
discharged to such an extent that the appliance
cannot operate
- f possible, the appliance is supplied from the N/A
supply mains through its battery charger, the
battery being initially discharged to such an extent
that the appliance cannot operate. The appliance is
operated as specified in relevant part 2
- if the appliance incorporates inductive coupling N/A
between two parts that are detachable from each
other, the appliance is supplied from the supply
mains with the detachable part removed
3.6.2 Part to be removed in order to discard the battery is N/A
not considered to be detachable
5.B.101 Appliances supplied from the supply mains tested N/A
as specified for motor-operated appliances

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 67 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

7.1 Battery compartment for batteries intended to be N/A


replaced by the user, marked with battery voltage
and polarity of the terminals
The positive terminal indicated by symbol N/A
IEC 60417-5005 and the negative terminal by
symbol IEC 60417-5006
7.6 Symbols 60417-5005 and IEC 60417-5006 N/A
7.12 The instructions give information regarding N/A
charging
The instructions for appliances incorporating N/A
batteries intended to be replaced by the user
includes required information
Details about how to remove batteries containing N/A
materials hazardous to the environment given
7.15 Markings placed on the part of the appliance N/A
connected to the supply mains
8.2 Appliances having batteries that according to the N/A
instruction may be replaced by the user need only
have basic insulation between live parts and the
inner surface of the battery compartment
If the appliance can be operated without batteries, N/A
double or reinforced insulation required
11.7 The battery is charged for the period stated in the N/A
instructions or 24 h ............................................... :
19.1 Appliances subjected to tests of 19.B.101, 19.B.102 N/A
and 19.B.103
19.10 Not applicable N/A
19.B.101 Appliances supplied at rated voltage for 168 h, the N/A
battery being continually charged
19.B.102 For appliances having batteries that can be N/A
removed without the aid of a tool, short-circuit of
the terminals of the battery, the battery being fully
charged,
19.B.103 Appliances having batteries replaceable by the user N/A
supplied at rated voltage under normal operation
with the battery removed or in any position allowed
by the construction
21.B.101 Appliances having pins for insertion into N/A
socket-outlets have adequate mechanical strength
Part of the appliance incorporating the pins subjected to the free fall test, procedure ----
2, of IEC 60068-2-31, the number of falls being:
- 100, if the mass of the part does not exceed 250 g N/A
(g).......................................................................... :
- 50, if the mass of the part exceeds 250 g........... : N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 68 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

After the test, the requirements of 8.1, 15.1.1, 16.3 N/A


and clause 29 are met
22.3 Appliances having pins for insertion into N/A
socket-outlets tested as fully assembled as
possible
25.13 An additional lining or bushing not required for N/A
interconnection cords in class III appliances or
class III constructions operating at safety extra-low
voltage not containing live parts
30.2 For parts of the appliance connected to the supply N/A
mains during the charging period, 30.2.3 applies
For other parts, 30.2.2 applies N/A
C ANNEX C (NORMATIVE) ----
AGEING TEST ON MOTORS
Tests, as described, carried out when doubt with N/A
regard to the temperature classification of the
insulation of a motor winding
Test conditions as specified N/A
E ANNEX E (NORMATIVE) ----
NEEDLE-FLAME TEST
Needle-flame test carried out in accordance with IEC 60695-11-5, with the following ----
modifications:
7 Severities ----
The duration of application of the test flame is P
30 s ± 1 s
9 Test procedure ----
9.1 The specimen so arranged that the flame can be P
applied to a vertical or horizontal edge as shown in
the examples of figure 1
9.2 The first paragraph does not apply P
If possible, the flame is applied at least 10 mm from P
a corner
9.3 The test is carried out on one specimen P
If the specimen does not withstand the test, the test N/A
may be repeated on two additional specimens, both
withstanding the test
11 Evaluation of test results ----
The duration of burning not exceeding 30 s N/A
However, for printed circuit boards, the duration of P
burning not exceeding 15 s
F ANNEX F (NORMATIVE) ----
CAPACITORS

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 69 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Capacitors likely to be permanently subjected to the supply voltage, and used for ----
radio interference suppression or voltage dividing, comply with the following clauses
of IEC 60384-14, with the following modifications:
1.5 Terms and definitions ----
1.5.3 Class X capacitors tested according to subclass X2 N/A
1.5.4 This subclause is applicable N/A
1.6 Marking ----
Items a) and b) are applicable N/A
3.4 Approval testing ----
3.4.3.2 Table 3 is applicable as described N/A
4.1 Visual examination and check of dimensions ----
This subclause is applicable N/A
4.2 Electrical tests ----
4.2.1 This subclause is applicable N/A
4.2.5 This subclause is applicable N/A
4.2.5.2 Only table 11 is applicable N/A
Values for test A apply N/A
However, for capacitors in heating appliances the N/A
values for test B or C apply
4.12 Damp heat, steady state ----
This subclause is applicable N/A
Only insulation resistance and voltage proof are N/A
checked
4.13 Impulse voltage ----
This subclause is applicable N/A
4.14 Endurance ----
Subclauses 4.14.1, 4.14.3, 4.14.4 and 4.14.7 are N/A
applicable
4.14.7 Only insulation resistance and voltage proof are N/A
checked
No visible damage N/A
4.17 Passive flammability test ----
This subclause is applicable N/A
4.18 Active flammability test ----
This subclause is applicable N/A
G ANNEX G (NORMATIVE) ----
SAFETY ISOLATING TRANSFORMERS

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 70 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

The following modifications to this standard are applicable for safety isolating ----
transformers:
7 Marking and instructions ----
7.1 Transformers for specific use marked with: ----
- name, trademark or identification mark of the N/A
manufacturer or responsible vendor ..................... :
- model or type reference ...................................... : N/A
17 Overload protection of transformers and associated circuits ----
Fail-safe transformers comply with subclause 15.5 N/A
of IEC 61558-1
22 Construction ----
Subclauses 19.1 and 19.1.2 of IEC 61558-2-6 are N/A
applicable
29 Clearances, creepage distances and solid insulation ----
29.1, 29.2, The distances specified in items 2a, 2c and 3 in N/A
29.3 table 13 of IEC 61558-1 apply
For insulated winding wires complying with N/A
subclause 19.12.3 of IEC 61558-1 there are no
requirements for clearances or creepage distances
For windings providing reinforced insulation, the N/A
distance specified in item 2c of table 13 of
IEC 61558-1 is not assessed
For safety isolating transformers subjected to N/A
periodic voltages with a frequency exceeding
30 kHz, the clearances, creepage distances and
solid insulation values specified in IEC 60664-4 are
applicable, if greater than the values specified in
items 2a, 2c and 3 in table 13 of IEC 61558-1
H ANNEX H (NORMATIVE) ----
SWITCHES
Switches comply with the following clauses of IEC 61058-1, as modified below: ----
The tests of IEC 61058-1 carried out under the N/A
conditions occurring in the appliance
Before being tested, switches are operated 20 N/A
times without load
8 Marking and documentation ----
Switches are not required to be marked N/A
However, a switch that can be tested separately N/A
from the appliance marked with the manufacturer’s
name or trade mark and the type reference
13 Mechanism ----
The tests may be carried out on a separate sample N/A
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 71 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

15 Insulation resistance and dielectric strength ----


15.1 Not applicable N/A
15.2 Not applicable N/A
15.3 Applicable for full disconnection and N/A
micro-disconnection
17 Endurance ----
Compliance is checked on three separate N/A
appliances or switches
For 17.2.4.4, the number of cycles declared N/A
according to 7.1.4 is 10 000, unless
otherwise specified in 24.1.3 of the relevant part 2 N/A
of IEC 60335 ......................................................... :
Switches for operation under no load and which N/A
can be operated only by a tool, and
switches operated by hand that are interlocked so N/A
that they cannot be operated under load,
are not subjected to the tests N/A
However, switches without this interlock are N/A
subjected to the test of 17.2.4.4 for 100 cycles of
operation
Subclauses 17.2.2 and 17.2.5.2 not applicable N/A
The ambient temperature during the test is that N/A
occurring in the appliance during the test of
clause 11 in IEC 60335-1
The temperature rise of the terminals not more than N/A
30 K above the temperature rise measured in
clause 11 of IEC 60335-1 (K) ............................... :
20 Clearances, creepage distances, solid insulation and coatings of rigid printed board ----
assemblies
This clause is applicable to clearances and N/A
creepage distances for functional insulation, across
full disconnection and micro-disconnection, as
stated in table 24
J ANNEX J (NORMATIVE) ----
COATED PRINTED CIRCUIT BOARDS
Testing of protective coatings of printed circuit boards carried out in accordance ----
with IEC 60664-3 with the following modifications:
5.7 Conditioning of the test specimens ----
When production samples are used, three samples N/A
of the printed circuit board are tested
5.7.1 Cold ----
The test is carried out at -25 °C N/A
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 72 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

5.7.3 Rapid change of temperature ----


Severity 1 is specified N/A
5.9 Additional tests ----
This subclause is not applicable N/A
K ANNEX K (NORMATIVE) ----
OVERVOLTAGE CATEGORIES
The information on overvoltage categories is P
extracted from IEC 60664-1
Overvoltage category is a numeral defining a P
transient overvoltage condition
Equipment of overvoltage category IV is for use at N/A
the origin of the installation
Equipment of overvoltage category III is equipment N/A
in fixed installations and for cases where the
reliability and the availability of the equipment is
subject to special requirements
Equipment of overvoltage category II is energy P
consuming equipment to be supplied from the fixed
installation
If such equipment is subjected to special N/A
requirements with regard to reliability and
availability, overvoltage category III applies
Equipment of overvoltage category I is equipment N/A
for connection to circuits in which measures are
taken to limit transient overvoltages to an
appropriate low level
L ANNEX L (INFORMATIVE) ----
GUIDANCE FOR THE MEASUREMENT OF CLEARANCES AND CREEPAGE
DISTANCES
Information for the determination of clearances and P
creepage distances
M ANNEX M (NORMATIVE) ----
POLLUTION DEGREE
The information on pollution degrees is extracted P
from IEC 60664-1
Pollution ----
The microenvironment determines the effect of P
pollution on the insulation, taking into account the
macroenvironment
Means may be provided to reduce pollution at the P
insulation by effective enclosures or similar
Minimum clearances specified where pollution may P
be present in the microenvironment

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 73 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Degrees of pollution in the microenvironment ----


For evaluating creepage distances, the following degrees of pollution in the ----
microenvironment are established:
- pollution degree 1: no pollution or only dry, N/A
non-conductive pollution occurs. The pollution has
no influence
- pollution degree 2: only non-conductive pollution Main power box P
occurs, except that occasionally a temporary
conductivity caused by condensation is to be
expected
- pollution degree 3: conductive pollution occurs or Parts in airflow P
dry non-conductive pollution occurs that becomes
conductive due to condensation that is to be
expected
- pollution degree 4: the pollution generates N/A
persistent conductivity caused by conductive dust
or by rain or snow
N ANNEX N (NORMATIVE) ----
PROOF TRACKING TEST
The proof tracking test is carried out in accordance with IEC 60112 with the ----
following modifications:
7 Test apparatus ----
7.3 Test solutions ----
Test solution A is used P
10 Determination of proof tracking index (PTI) ----
10.1 Procedure ----
The proof voltage is 100 V, 175 V, 400 V or 600 V 175V P
.............................................................................. :
The test is carried out on five specimens P
In case of doubt, additional test with proof voltage N/A
reduced by 25 V, the number of drops increased to
100
10.2 Report ----
The report states if the PTI value was based on a N/A
test using 100 drops with a test voltage of (PTI-25)
V
O ANNEX O (INFORMATIVE) ----
SELECTION AND SEQUENCE OF THE TESTS OF clause 30
Description of tests for determination of resistance P
to heat and fire
P ANNEX P (INFORMATIVE) ----
GUIDANCE FOR THE APPLICATION OF THIS STANDARD TO APPLIANCES
USED IN WARM DAMP EQUABLE CLIMATES
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 74 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Modifications applicable for class 0 and 01 appliances having a rated voltage ----
exceeding 150 V, intended to be used in countries having a warm damp equable
climate and that are marked WDaE
Modifications may also be applied to class 1 appliances having a rated voltage ----
exceeding 150 V, intended to be used in countries having a warm damp equable
climate and that are marked WDaE, if liable to be connected to a supply mains that
excludes the protective earthing conductor
5.7 The ambient temperature for the tests of clauses 11 N/A
and 13 is 40 +3/0 °C
7.1 The appliance marked with the letters WDaE N/A
7.12 The instructions state that the appliance is to be N/A
supplied through a residual current device (RCD)
having a rated residual operating current not
exceeding 30 mA
The instructions state that the appliance is N/A
considered to be suitable for use in countries
having a warm damp equable climate, but may also
be used in other countries
11.8 The values of Table 3 are reduced by 15 K N/A
13.2 The leakage current for class I appliances not N/A
exceeding 0,5 mA
15.3 The value of t is 37 °C N/A
16.2 The leakage current for class I appliances not N/A
exceeding 0,5 mA (mA):
19.13 The leakage current test of 16.2 is applied in N/A
addition to the electric strength test of 16.3
Q ANNEX Q (INFORMATIVE) ----
SEQUENCE OF TESTS FOR THE EVALUATION OF ELECTRONIC CIRCUITS
Description of tests for appliances incorporating electronic circuits P
R ANNEX R (NORMATIVE) ----
SOFTWARE EVALUATION
Programmable electronic circuits requiring software N/A
incorporating measures to control the fault/error
conditions specified in table R.1 or R.2 validated in
accordance with the requirements of this annex
R.1 Programmable electronic circuits using software ----
Programmable electronic circuits requiring software N/A
incorporating measures to control the fault/error
conditions specified in table R.1 or R.2 constructed
so that the software does not impair compliance
with the requirements of this standard
R.2 Requirements for the architecture ----

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 75 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Programmable electronic circuits requiring software N/A


incorporating measures to control the fault/error
conditions specified in table R.1 or R.2 use
measures to control and avoid software-related
faults/errors in safety-related data and
safety-related segments of the software
R.2.1.1 Programmable electronic circuits requiring software incorporating measures to ----
control the fault/error conditions specified in table R.2 have one of the following
structures:
- single channel with periodic self-test and N/A
monitoring
- dual channel (homogenous) with comparison N/A
- dual channel (diverse) with comparison N/A
Programmable electronic circuits requiring software incorporating measures to ----
control the fault/error conditions specified in table R.1 have one of the following
structures:
- single channel with functional test N/A
- single channel with periodic self-test N/A
- dual channel without comparison N/A
R.2.2 Measures to control faults/errors ----
R.2.2.1 When redundant memory with comparison is N/A
provided on two areas of the same component, the
data in one area is stored in a different format from
that in the other area
R.2.2.2 Programmable electronic circuits with functions N/A
requiring software incorporating measures to
control the fault/error conditions specified in table
R.2 and that use dual channel structures with
comparison, have additional fault/error detection
means for any fault/errors not detected by the
comparison
R.2.2.3 For programmable electronic circuits with functions N/A
requiring software incorporating measures to
control the fault/error conditions specified in table
R.1 or R.2, means are provided for the recognition
and control of errors in transmissions to external
safety-related data paths
R.2.2.4 For programmable electronic circuits with functions N/A
requiring software incorporating measures to
control the fault/error conditions specified in table
R.1 or R.2, the programmable electronic circuits
incorporate measures to address the fault/errors in
safety-related segments and data indicated in table
R.1 and R.2 as appropriate

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 76 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

R.2.2.5 For programmable electronic circuits with functions N/A


requiring software incorporating measures to
control the fault/error conditions specified in table
R.1 or R.2, detection of a fault/error occur before
compliance with clause 19 is impaired
R.2.2.6 The software is referenced to relevant parts of the N/A
operating sequence and the associated hardware
functions
R.2.2.7 Labels used for memory locations are unique N/A
R.2.2.8 The software is protected from user alteration of N/A
safety-related segments and data
R.2.2.9 Software and safety-related hardware under its N/A
control is initialized and terminates before
compliance with clause 19 is impaired
R.3 Measures to avoid errors ----
R.3.1 General ----
For programmable electronic circuits with functions requiring software incorporating ----
measures to control the fault/error conditions specified in table R.1 or R.2, the
following measures to avoid systematic fault in the software are applied
Software that incorporates measures used to N/A
control the fault/error conditions specified in table
R.2 is inherently acceptable for software required to
control the fault/error conditions specified in table
R.1
R.3.2 Specification ----
R.3.2.1 Software safety requirements: Software Id: N/A
The specification of the software safety N/A
requirements includes the descriptions listed
R.3.2.2 Software architecture ----
R.3.2.2.1 The specification of the software architecture Document ref. No: N/A
includes the aspects listed
- techniques and measures to control software
faults/errors (refer to R.2.2);
- interactions between hardware and software;
- partitioning into modules and their allocation to the
specified safety functions;
- hierarchy and call structure of the modules
(control flow);
- interrupt handling;
- data flow and restrictions on data access;
- architecture and storage of data;
- time-based dependencies of sequences and data

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 77 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

R.3.2.2.2 The architecture specification is validated against N/A


the specification of the software safety
requirements by static analysis
R.3.2.3 Module design and coding ----
R.3.2.3.1 Based on the architecture design, software is N/A
suitably refined into modules
Software module design and coding is implemented N/A
in a way that is traceable to the software
architecture and requirements
R.3.2.3.2 Software code is structured N/A
R.3.2.3.3 Coded software is validated against the module N/A
specification by static analysis
The module specification is validated against the N/A
architecture specification by static analysis
R.3.3.3 Software validation ----
The software is validated with reference to the N/A
requirements of the software safety requirements
specification
Compliance is checked by simulation of: ----
- input signals present during normal operation N/A
- anticipated occurrences N/A
- undesired conditions requiring system action N/A

TABLE R.1 e – GENERAL FAULT/ERROR CONDITIONS


Component Fault/error Acceptable measures b, c Definitions Document Document Ver-dic
a reference reference t
for applied for applied
measure test
1 CPU N/A
1.1
Registers Stuck at Functional test, or H.2.16.5
periodic self-test using either: H.2.16.6
- static memory test, or H.2.19.6
- word protection with single H.2.19.8.2
bit redundancy
1.2 VOID N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 78 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

1.3 Stuck at Functional test, or H.2.16.5 N/A


Programme
Periodic self-test, or H.2.16.6
counter
Independent time-slot H.2.18.10.4
monitoring, or
Logical monitoring of the H.2.18.10.2
programme sequence
2 No Functional test, or H.2.16.5 N/A
Interrupt interrupt or
time-slot monitoring H.2.18.10.4
handling too
and frequent
execution interrupt

3 Wrong Frequency monitoring, or H.2.18.10.1 N/A


Clock frequency
time slot monitoring H.2.18.10.4
(for quartz
synchroniz
ed clock:
harmonics/
sub-harmo
nics only)
4. Memory N/A
4.1 All single Periodic modified checksum, or H.2.19.3.1
Invariable bit faults
multiple checksum, or H.2.19.3.2
memory
word protection with single bit H.2.19.8.2
redundancy
4.2 DC fault Periodic static memory test, or H.2.19.6 N/A
Variable
word protection with single bit H.2.19.8.2
memory
redundancy

4.3 Stuck at Word protection with single bit H.2.19.8.2 N/A


Addressing redundancy including the
(relevant to address
variable and
invariable
memory)
5 Stuck at Word protection with single bit H.2.19.8.2 N/A
Internal redundancy
data path
5.1 VOID N/A
5.2 Wrong Word protection with single bit H.2.19.8.2 N/A
Addressing address redundancy including the
address

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 79 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

6 Hamming Word protection with multi-bit H.2.19.8.1 N/A


External distance 3 redundancy, or
communicat
CRC – single work, or H.2.19.4.1
ion
Transfer redundancy, or H.2.18.2.2
Protocol test H.2.18.14
6.1 VOID N/A
6.2 VOID N/A
6.3 Wrong Time-slot monitoring, or H.2.18.10.4 N/A
Timing point in
scheduled transmission H.2.18.18
time
Time-slot and logical H.2.18.10.3
monitoring, or
comparison of redundant
communication channels by
either:
- reciprocal comparison H.2.18.15
- independent hardware H.2.18.3
comparator
Logical monitoring, or H.2.18.10.2
Wrong
sequence time-slot monitoring, or H.2.18.10.4
Scheduled transmission H.2.18.18
7 Fault Plausibility check H.2.18.13 N/A
Input/output conditions
periphery specified in
19.11.2
7.1 VOID N/A
7.2 N/A
Analog I/O
7.2.1 Fault Plausibility check H.2.18.13
A/D and conditions
D/A- specified in
converter 19.11.2
7.2.2 Wrong Plausibility check H.2.18.13 N/A
Analog addressing
multiplexer
8 VOID N/A
9 Any output Periodic self-test H.2.16.6 N/A
Custom outside the
chips d e.g. static and
ASIC, GAL, dynamic
gate array functional
specificatio
n

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 80 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

NOTE A Stuck-at fault model denotes a fault model representing an open circuit or a non-varying signal
level. A DC fault model denotes a stuck-at fault model incorporating short circuit between signal lines.
a) For fault/error assessment, some components are divided into their sub-functions.
b) For each sub-function in the table, the Table R.2 measure will cover the software fault/error.
c) Where more than one measure is given for a sub-function, these are alternatives.
d) To be divided as necessary by the manufacturer into sub-functions.
e) Table R.1 is applied according to the requirements of R.1 to R.2.2.9 inclusive.

AA ANNEX AA (INFORMATIVE) (IEC 60335-2-40) ----


EXAMPLES FOR OPERATING TEMPERATURES OF THE APPLIANCE

BB ANNEX BB (NORMATIVE) (IEC 60335-2-40) ----


SELECTED INFORMATION ABOUT REFRIGERANTS

CC ANNEX CC (INFORMATIVE) (IEC/EN 60335-2-40/A1) ----


TRANSPORTATION, MARKING AND STORAGE FOR UNITS THAT EMPLOY
FLAMMABLE REFRIGERANTS
CC.1 Transport of equipment containing flammable P
refrigerants (IEC 60335-2-40/A1)
CC.2 Marking of equipment using signs P
(IEC 60335-2-40/A1)
CC.3 Disposal of equipment using flammable refrigerants P
(IEC 60335-2-40/A1)
CC.4 Storage of equipment/appliances P
(IEC 60335-2-40/A1)
CC.5 Storage of packed (unsold) equipment P
(IEC 60335-2-40/A1)

DD ANNEX DD (NORMATIVE) (IEC/EN 60335-2-40/A1) ----


SERVICE OPERATIONS
DD.1 Generals (IEC 60335-2-40/A1) P
DD.2 Symbols (IEC 60335-2-40/A1) P
DD.3 Information in manual (IEC 60335-2-40/A1 corr.1) P
DD.4 Information on servicing (IEC 60335-2-40/A1) P
DD.5 Repairs to sealed components N/A
(IEC 60335-2-40/A1)
DD.6 Repair to intrinsically safe components P
(IEC 60335-2-40/A1)
DD.7 Cabling (IEC 60335-2-40/A1) P
DD.8 Detection of flammable refrigerants P
(IEC 60335-2-40/A1)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 81 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

DD.9 Leak detection methods (IEC 60335-2-40/A1) P


DD.10 Removal and evacuation (IEC 60335-2-40/A1) P
DD.11 Charging procedures (IEC 60335-2-40/A1) P
DD.12 Decommissioning (IEC 60335-2-40/A1) P
DD.13 Labelling (IEC 60335-2-40/A1) P
DD.14 Recovery (IEC 60335-2-40/A1) P

EE ANNEX EE (NORMATIVE) (IEC/EN 60335-2-40/A1) ----


PRESSURE TESTS
EE.1 General (IEC 60335-2-40/A1) P
EE.2 Pressure test value determined under testing P
carried out in clause 11 (IEC 60335-2-40/A1)
EE.3 Pressure test value determined under testing P
carried out in clause 19 (IEC 60335-2-40/A1)
EE.4 Pressure test value determined under testing P
carried out under standstill conditions
(IEC 60335-2-40/A1)
EE.5 Fatigue test option for Clauses EE.1 and EE.4.1 N/A
(IEC 60335-2-40/A1)

FF ANNEX FF (NORMATIVE) (IEC/EN 60335-2-40/A1) ----


LEAK SIMULATION TESTS
FF.1 General (IEC 60335-2-40/A1) N/A
FF.2 Test methods (IEC 60335-2-40/A1 corr.1) N/A

GG ANNEX GG (NORMATIVE) (IEC/EN 60335-2-40/A1) ----


CHARGE LIMITS, VENTILATION REQUIREMENTS AND REQUIREMENTS FOR
SECONDARY CIRCUITS
GG.1 Requirements for charge limits in ventilated areas P
(IEC 60335-2-40/A1 Corr.1)
GG.2 Requirements for charge limits in unventilated P
areas (IEC 60335-2-40/A1 Corr.1)
GG.3 Requirements for charge limits in areas with N/A
mechanical ventilation (IEC 60335-2-40/A1)
GG.4 Requirements for mechanical ventilation within the N/A
appliance enclosure (IEC 60335-2-40/A1)
GG.5 Requirements for mechanical ventilation for rooms N/A
complying with ISO 5149 (IEC 60335-2-40/A1)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 82 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

GG.6 Requirements for refrigeration systems employing N/A


secondary heat exchangers
(IEC 60335-2-40/A1 Corr.1)
GG.7 The appliance shall then be tested with a maximum N/A
water flow under the conditions described in g)
(IEC 60335-2-40/A1)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 83 of 177 Modification 12: November 10, 2020

10.1 TABLE: Power input deviation P


Input deviation of/at: P rated (W) P measured (W) ΔP Required Δ P Remark

Compressor capacitor is 30uF:


GPH12AL-K5NNA3A at 1550 1311,3 -15,4% +15% Cooling mode
230V/50Hz
1550 1379,3 -11,0% +15% Heating mode
GPC12AL-K5NNA3A at 1550 1413,2 -8,8% +15% Cooling mode
230V/50Hz
GPH12AL-K5NNA2B at 1550 1421,5 -8,1% +15% Cooling mode
230V/50Hz
1550 1359,7 -12,3% +15% Heating mode
GPC12AL-K5NNA3B at 1550 1388,7 -10,4% +15% Cooling mode
230V/50Hz
GPC12AL-K5NNA3C at 1500 1311,4 -12,6% +15% Cooling mode
230V/50Hz
GPH12AL-K5NNA3C at 1550 1341,4 -13,5% +15% Cooling mode
230V/50Hz
1550 1196,6 -22,8% +15% Heating mode
GPC12AL-K5NNA3D at 1500 1356,0 -9,6% +15% Cooling mode
230V/50Hz
Note: tested with all alternative components and recorded the maximum value.
Compressor capacitor is 40uF:
GPH12AL-K5NNA3A at 1550 1368,5 -11,7% +15% Cooling mode
230V/50Hz
1550 1392,1 -10,2% +15% Heating mode

10.2 TABLE: Current deviation P


Current deviation of/at: I rated (A) I measured (A) ΔI Required Δ I Remark

— — — — — —

11.8-1 TABLE: Heating test, thermocouples for GPH12AL-K5NNA3A P


Test voltage (V) ..................................................... : 254,4 ⎯
Ambient, t1 (°C) ..................................................... : Cooling:35/23;
Ambient, t2 (°C) ..................................................... : Heating:27/-; ⎯
Thermocouple locations T (°C) Max. T (°C)
Cooling Heating
Running capacitor of Fan Motor (top) 36,7 37,6 T70
Running capacitor of compressor 36,3 42,3 T70
X capacitor 42,3 41,7 T110
High Frequency Transformer 46,6 44,4 Class B: 110
Running capacitor of Fan Motor (down) 36,4 39,4 T70

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 84 of 177 Modification 12: November 10, 2020

Electric box 42,2 40,7 For clause 30.1


PCB (high voltage board) 44,2 46,2 145
Varistor 45,1 44,3 T85
Relay 1# 49,9 52,8 T70
Relay 2# 50,2 47,0 T70
Relay 3# 50,9 51,6 T70
Relay 4# 43,8 47,3 T70
4-way valve 59,6 32,8 Class B: 110
PCB (main board) 37,6 40,1 145
Terminal block 32,5 41,3 For clause 30.1
Compressor internal wire 56,7 21,3 For reference
Compressor discharge 75,4 69,9 For reference
Compressor 79,5 71,2 For reference
Fan Motor (top)_YD28X (Kaibang) 30,4 18,5 For reference
Fan Motor (top)_YD28X (Tongde) 31,5 19,3 For reference
Fan Motor (Down)_YD23X (Kaibang) 24,9 71,5 For reference
Fan Motor (Down)_YD23X (Tongde) 25,1 72,3 For reference
Splash motor 56,7 13,4 Class E: 105
Power cord 36,8 30,2 75
Test corner 35,6 28,1 90
Note: tested with all alternative components and recorded the maximum value.

11.8-1 TABLE: Heating test, resistance method P


Test voltage (V) ..........................................: 254,4 ⎯
Ambient. t (C) Cooling:35/23; ⎯
Heating:27/-;

Temperature of winding R1 (Ω) R2 (Ω) T (C) Max. T Insulation


at 25C (C) class
Cooling Heating Cooling Heating
Main winding of fan motor 124 134,1 128,1 46,1 33,6 120 B
(YD28X_Kaibang)
Aux. winding of fan motor 89 96,2 91,7 46,0 32,9 120 B
(YD28X_Kaibang)
Main winding of fan motor 131 142,1 135,8 47,0 34,5 120 B
(YD28X_Tongde)
Aux. winding of fan motor 90 97,4 93,1 46,3 33,9 120 B
(YD28X_ Tongde)
Main winding of fan motor 353 373,7 436,7 40,2 86,5 120 B
(YD23X_Kaibang)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 85 of 177 Modification 12: November 10, 2020

Aux. winding of fan motor 96 101,4 118,5 39,6 85,8 120 B


(YD23X_Kaibang)
Main winding of fan motor 430 458,7 533,2 42,3 87,3 120 B
(YD23X_Tongde)
Aux. winding of fan motor 82 87,3 101,6 41,8 87,0 120 B
(YD23X_ Tongde)
Main winding of compressor 3,11 3,9 3,8 90,9 82,6 140 Synthetic
Aux. winding of compressor 3,12 3,9 3,9 89,9 89,9 140 Synthetic
4-way valve valve (DSF-9- 2000 2386,1 2175,0 75,1 47,7 120 B
R410A_Dunan)
4-way valve valve (SHF- 2180 2610,1 2374,1 76,2 48,1 120 B
7_Gangli)
4-way valve valve (SHF-7H- 2200 2631,5 2394,1 75,9 47,9 120 B
34U-PG_Sanhua)
Splash motor (SN03N- 562 663,4 569,8 71,8 28,6 115 E
1_Kaibang)

11.8-2 TABLE: Heating test, thermocouples for GPH12AL-K5NNA2B P


Test voltage (V) ..................................................... : 254,4 ⎯
Ambient, t1 (°C) ..................................................... : Cooling:35/23;
Ambient, t2 (°C) ..................................................... : Heating:27/- ⎯
Thermocouple locations T (°C) Max. T (°C)
Cooling Heating
Running capacitor of Fan Motor (top) 38,9 39,7 T70
Running capacitor of compressor 37,8 43,1 T70
X capacitor 43,6 42,8 T110
High Frequency Transformer 46,5 45,2 Class B: 110
Running capacitor of Fan Motor (down) 39,5 40,1 T70
Electric box 36,9 38,4 For clause 30.1
PCB (high voltage board) 40,3 42,6 145
Varistor 46,5 45,3 T85
Relay 1# 48,9 50,2 T70
Relay 2# 45,6 47,6 T70
Relay 3# 50,2 51,7 T70
Relay 4# 45,6 44,3 T70
4-way valve 62,1 52,4 Class B: 110
PCB (main board) 38,5 40,3 145
Terminal block 33,2 41,5 For clause 30.1
Compressor internal wire 48,4 32,1 For reference

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 86 of 177 Modification 12: November 10, 2020

Compressor discharge 77,5 70,1 For reference


Compressor 79,5 72,3 For reference
Fan Motor (top)_YD28X (Kaibang) 32,5 20,6 For reference
Fan Motor (top)_YD28X (Tongde) 35,6 22,6 For reference
Fan Motor (Down)_YD23X (Kaibang) 39,1 42,3 For reference
Fan Motor (Down)_YD23X (Tongde) 38,4 44,2 For reference
Splash motor 57,6 30,2 Class E: 105
Power cord 36,5 32,1 75
Test corner 35,4 27,8 90

11.8-3 TABLE: Heating test, thermocouples for GPH12AL-K5NNA3A with compressor P


capacitor 40uF
Test voltage (V) ..................................................... : 254,4 ⎯
Ambient, t1 (°C) ..................................................... : Cooling:35/23;
Ambient, t2 (°C) ..................................................... : Heating:27/-; ⎯
Thermocouple locations T (°C) Max. T (°C)
Cooling Heating
Running capacitor of Fan Motor (top) 40,7 68,6 T70
Running capacitor of compressor 53,5 38,4 T70
High Frequency Transformer 52,1 46,4 Class B: 110
Running capacitor of Fan Motor (down) 38,4 31,3 T70
Compressor 80,6 74,7 For reference
Fan Motor (top)_YD28X 38,4 42,4 For reference
Fan Motor (Down)_YD23X 52,4 67,1 For reference
Power cord 36,8 37,2 75
Test corner 40,5 26,3 90

11.8-3 TABLE: Heating test, resistance method P


Test voltage (V) ..........................................: 254,4 ⎯
Ambient. t (C) Cooling:35/23; ⎯
Heating:27/-;

Temperature of winding R1 (Ω) R2 (Ω) T (C) Max. T Insulation


at 25C (C) class
Cooling Heating Cooling Heating
Main winding of compressor 3,18 4,06 3,98 96,8 90,3 140 Synthetic
Aux. winding of compressor 3,13 3,98 3,93 95,5 91,3 140 Synthetic

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 87 of 177 Modification 12: November 10, 2020

11.8-4 TABLE: Heating test, thermocouples for GPH12AL-K5NNA3C P


Test voltage (V) ..................................................... : 254,4 ⎯
Ambient, t1 (°C) ..................................................... : Cooling:35/23;
Ambient, t2 (°C) ..................................................... : Heating:27/-; ⎯
Thermocouple locations T (°C) Max. T (°C)
Cooling Heating
Running capacitor of Fan Motor (top) 39,1 38,4 T70
Running capacitor of compressor 36,2 44,8 T70
X capacitor 42,5 48,3 T110
High Frequency Transformer 48,2 41,5 Class B: 110
Running capacitor of Fan Motor (down) 35,6 39,1 T70
Electric box 38,2 35,6 For clause 30.1
PCB (high voltage board) 44,1 39,8 145
Varistor 45,1 42,5 T85
Relay 1# 47,2 49,3 T70
Relay 2# 46,1 48,5 T70
Relay 3# 49,2 49,6 T70
Relay 4# 41,2 40,5 T70
Liquid Level Switch 36,4 38,2 For reference
4-way valve 64,2 50,2 Class B: 110
PCB (main board) 39,6 42,3 145
Terminal block 34,8 31,2 For clause 30.1
Compressor 78,5 72,6 For reference
Fan Motor (top) 30,5 28,5 For reference
Fan Motor (Down) 41,4 38,4 For reference
Splash motor 55,6 31,5 Class E: 105
Power cord 35,1 29,8 75
Test corner 35,5 27,4 90

11.8-5 TABLE: Heating test, thermocouples for GPC12AL-K5NNA3D P


Test voltage (V) ..................................................... : 254,4 ⎯
Ambient, t1 (°C) ..................................................... : Cooling:35/23
Ambient, t2 (°C) ..................................................... : ⎯
Thermocouple locations T (°C) Max. T (°C)
Cooling Heating
Electrolytic capacitor 42,2 — T105

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 88 of 177 Modification 12: November 10, 2020

Relay 51,5 — T70


Upper fan motor enclosure 44,4 — For reference
Compressor capacitor 34,8 — T70
Lower fan motor 38,7 — For reference
Upper fan motor capacitor 34,5 — T70
Compressor surface 73,3 — For reference
PCB 37,8 — 145
Winding of high frequency transformer 43,1 — Class B: 110
Supply cord 37,8 — 75
Lower fan motor capacitor 34,8 — T70
Varistor 38,0 — T85
Test corner 28,6 — 90
Appliance enclosure 37,8 — 85

11.8-5 TABLE: Heating test, resistance method P


Test voltage (V) ......................................... : 254,4 ⎯
Ambient. t (C) Cooling:35/23; ⎯
Heating:27/-;

Temperature of winding R1 (Ω) R2 (Ω) T (C) Max. T Insulation


at 25C (C) class
Cooling Heating Cooling Heating
Main winding of fan motor 498,5 569,8 — 62,1 — 120 B
(YD28X-L Tongde)
Aux. winding of fan motor 116,5 133,8 — 63,5 — 120 B
(YD28X-L Tongde)

13.2 TABLE: Leakage current P


Heating appliances: 1,15 x rated power input : — ⎯
Motor-operated and combined appliances: 254,4 ⎯
1,06 x rated voltage :
Leakage current between I (mA) Max. allowed I (mA)

L/N and earthing metal parts Max. 1,587 3,5


L/N and plastic enclosure /Control panel Max. 0,04 peak 0,35 peak

13.3 TABLE: Dielectric strength P


Test voltage applied between: Test potential applied Breakdown / flashover
(V) (Yes/No)
Live parts and earthing metal part 1,2x500+700=1300 No

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 89 of 177 Modification 12: November 10, 2020

Supplementary insulation 1,2x500+1450=2050 No


Live parts and reinforced insulation 2,4x500+2400=3600 No
Supplementary information: the max. working voltage measure <500V.

14 TABLE: Transient overvoltages N/A


Clearance between: Cl (mm) Required Cl Rated impulse Impulse test Flashover
(mm) voltage (V) voltage (V) (Yes/No)
— — — — — —

16.2 TABLE: Leakage current P


Single phase appliances: 1,06 x rated voltage ... : 254,4V ⎯
Three phase appliances 1,06 x rated voltage — ⎯
divided by 3: ...................................................... :
Leakage current between I (mA) Max. allowed I (mA)
Live parts and earthing metal parts 0,333 3,5
Live parts and plastic enclosure /Control panel 0,009 0,25

16.3 TABLE: Dielectric strength P


Test voltage applied between: Test potential applied Breakdown / flashover
(V) (Yes/No)
Live parts and earthing metal part 1,2x500+950=1550 No
Supplementary insulation 1,2x500+1450=2050 No
Live parts and reinforced insulation 2,4x500+2400=3600 No
Supplementary information: the max. working voltage measure <500V.

17 TABLE: Overload protection N/A


Thermocouple locations Max. temperature rise Max. temperature rise
measured, Δ T (K) limit, Δ T (K)
— — —

17 TABLE: Overload protection, resistance method N/A


Test voltage (V)..................................................... : — ⎯
Ambient, t1 (C) .................................................... : — ⎯
Ambient, t2 (C) .................................................... : — ⎯
Temperature of winding R1 () R2 () Δ T (K) T (C) Max. T (°C)
— — — — — —

19 Abnormal operation conditions N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 90 of 177 Modification 12: November 10, 2020

Operational characteristics YES/NO Operational conditions


Are there electronic circuits to N/A N/A
control the appliance operation?
Are there “off” or “stand-by” N/A N/A
position?
The unintended operation of the N/A N/A
appliance results in dangerous
malfunction?
Sub-clause Operating Test results PEC EMP Software 19.11.3 Final
conditions description description 19.11.4 type PEC result
description required
19.2 N/A N/A N/A N/A N/A N/A N/A
19.3 N/A N/A N/A N/A N/A N/A N/A
19.4 N/A N/A N/A N/A N/A N/A N/A
19.5 N/A N/A N/A N/A N/A N/A N/A
19.6 N/A N/A N/A N/A N/A N/A N/A
19.7 N/A N/A N/A N/A N/A N/A N/A
19.8 N/A N/A N/A N/A N/A N/A N/A
19.9 N/A N/A N/A N/A N/A N/A N/A
19.10 N/A N/A N/A N/A N/A N/A N/A
19.11.2 N/A N/A N/A N/A N/A N/A N/A
19.11.4.8 N/A N/A N/A N/A N/A N/A N/A
19.10X N/A N/A N/A N/A N/A N/A N/A

19.2 TABLE: Lock motor test, temperature measurements. P


Test voltage: supplied by the main controller
Ambient temperature: 25 °C
Duration: 15 days endurance test, after 3 days high-voltage test performed.
Insulation Enclosure Winding Max. T (C) HV test Leakage
Measured sample class temperature temperature performed current
(°C) (°C) Enclosure Winding with 1250V (mA)
Fan motor YD23X B 108,7 139,8 150 225 Pass 0,083
(Kaibang)
Fan motor YD23X B 137,1 155,2 150 225 Pass 0,187
(Tongde)
Fan motor YD28X B 117,4 143,8 150 225 Pass 0,104
(Kaibang)
Fan motor YD28X B 134,0 155,2 150 225 Pass 0,147
(Tongde)
Water pump E 60,2 66,3 150 215 Pass 0,034
SN03N-1

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 91 of 177 Modification 12: November 10, 2020

Fan motor YD28X- B 137,0 145,0 150 225 Pass 0,142


L (Tongde)

19.3 Abnormal operation conditions – Locked rotor test motor-compressor P


Motor-compressor ................................................. : QXD-B222A030
Start device ........................................................... : —
Protector ................................................................ : HPA-030
Start capacitor ....................................................... : —
Run capacitor .......................................................: 30μF
Cooling; (static); (fan-m3/h); (oil); ......................... : —
Thermal motor-protection system ........................ : —
Manually
Self-resetting
reset
Vn max
Rated voltage Vn max (V) Vn min (V)
(V)
After After After After After
72 h 288 h 360 h 363 h 50 cycles
High-voltage test (see 16.3) Pass —
— — —
(1250V)
Leakage current (mA) (see 16.2) — — 0,163 0,162 —
Electric strength (see 13.3) — — — — —
Room temperature (C) (20 ± 5°C) — 23 23 —

Number of cycles ( 2000 or 50) — — 2000 — —


Housing temperature (C) ( 150°C) — — 68 62 —

19.3 Abnormal operation conditions – Locked rotor test motor-compressor P


Motor-compressor ................................................. : QXD-B222A030
Start device ........................................................... : —
Protector ................................................................ : HPA-030
Start capacitor ....................................................... : —
Run capacitor .......................................................: 40uF
Cooling; (static); (fan-m3/h); (oil); ......................... : —
Thermal motor-protection system ........................ : Synthetic
Manually
Self-resetting
reset
Vn max
Rated voltage Vn max (V) Vn min (V)
(V)
After After After After After
72 h 288 h 360 h 363 h 50 cycles
High-voltage test (see 16.3) P — P — —

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 92 of 177 Modification 12: November 10, 2020

Leakage current (mA) (see 16.2) — — 0,52 — —


Electric strength (see 13.3) — — P — —
Room temperature (C) (20 ± 5°C) 25 — 25 — —
Number of cycles ( 2000 or 50) — — 6363 — —
Housing temperature (C) ( 150°C) — — 88,5 — —
supplementary information:—

19.5-19.9 Abnormal operation conditions P


Subclause Effect Verdict
19.5 No hazards during and after the test. P
19.6 — N/A
19.7 No hazards during and after the test. P
19.8 — N/A
19.9 — N/A

19.10 Abnormal operation conditions P


Failure description Effect Verdict
Open-circuit fan motor capacitor No hazards during and after the test. P
Short-circuit fan motor capacitor No hazards during and after the test. P
Open-circuit compressor capacitor No hazards during and after the test. P
Short-circuit compressor capacitor No hazards during and after the test. P

19.11.2 Abnormal Operation P


Fault condition Short Open Effect Verdict
circuit circuit

According to a) to g) of X X 1. The appliance can not work normally. Pass


clause 19.11.2 2. The current fuse in the bus of circuit
operated.
Above two phenomenons occurred. No hazard
during and after all tests.

19.14 TABLE: Abnormal operation, temperature rises P


Thermocouple locations T (C) Required T (C)
Supply cord <100 175
Test corner <100 175

21.1 TABLE: Impact resistance P


Impacts per surface Surface tested Impact energy (Nm) Comments
3 Enclosure 0,5 Pass
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 93 of 177 Modification 12: November 10, 2020

3 Display panel 0,5 Pass

24.1 TABLE: Critical components information P


Object / part No. Manufacturer/ Type / model Technical data Standard Mark(s) of
trademark conformity1)
Plug Guangdong CT-104 16A; 250V DIN VDE 0620-1 VDE
Huasheng 40006002
Electrical
Appliances Co.,
Ltd.
Alternative Changzhou DTIII-2P-05 16A; 250V DIN VDE 0620-1 VDE
Hongchang 40015536
Electronics CO.,
LTD.
BS plug Guangdong CT-307 13A; 250V~ BS 1363-1 ASTA NO
Huasheng 885
Electrical
Appliances Co.,
Ltd.
Power Cord Guangdong H05VV-F 3G1,0mm² DIN VDE 0282-1 VDE
Huasheng HD 21.5 S3 40005362
Electrical
Appliances Co.,
Ltd.
Alternative Changzhou H05VV-F 3G1,0mm² DIN VDE 0282-1 VDE124978
Hongchang HD 21.5 S3
Electronics CO.,
LTD.
Splash motor Zhuhai Kaibang SN03N-1 220-240V; 0,05A; EN 60335-1 Tested with
Motor 50Hz; 0,32W; EN 60335-2-40 appliance
Manufacturing Main: 561±8%Ω;
CO., LTD. Class E
Liquid Level zhejiang fushi LS-8 24VDC/AC;10mA EN 60335-2-40 Tested with
Switch precision IEC 60079-15 appliance
(mechanical) technology Co.,
Ltd
Compressor ZHUHAI LANDA QXD- 220-240V; 50Hz; EN 60335-1 Tested with
and Fittings COMPRESSOR B222A030 1000W; EN 60335-2-40 appliance
CO. LTD. 3,09±7%Ω;
3,04±7%Ω;
Compressor Changzhou HPA-030 open: 125±5°C; EN 60730-1 TÜV
Overload Changrong close: 80±10°C EN 60730-2-4 Rheinland R
Protector Electrical 50349841
(Internal) Appliance Co.,
Ltd.
Compressor Zhuhai Gree CBB65 30μF; 450VAC; EN 60252-1 VDE
capacitor Xinyuan Electronic T70; P2/S3 40030641
Co., Ltd.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 94 of 177 Modification 12: November 10, 2020

Alternative Zhuhai Gree CBB65 30μF; 450VAC; EN 60252-1 TÜV


Xinyuan Electronic T70; P2/S2 Rheinland R
Co., Ltd. 50127276
Alternative Ningbo Shine CBB65A 30μF; 450V; T70; EN 60252-1 TÜV
Electrical Co., Ltd. P2/S3 Rheinland R
50199650
Alternative Ningbo Shine CBB65A-1 30μF; 450V; T70; EN 60252-1 VDE
Electrical Co. Ltd. P2/S3 40031628
Alternative Anhui Feida CBB65A-1 30μF; 450V; T85; EN 60252-1 VDE
Industry Stock P2/S3 40019572
Co., Ltd.
Alternative Zhuhai Gree CBB65 40μF/450VAC/T70 EN 60252-1 TÜV
Xinyuan Electronic ; P2/S2 Rheinland R
Co., LTD 50127276
Fan Motor Zhuhai Kaibang YD23X 220-240V; 0,53A; EN 60335-2-40 Tested with
(Down) Motor 50Hz; 50W; Main: appliance
Manufacturing 123±8%Ω; Aux:
CO., LTD. 88±8%Ω; Class B
Alternative Zhuhai city YD23X 220-240V; 0,5A; EN 60335-2-40 Tested with
Tongde electric 50Hz; 50W; appliance
equipment co., ltd M:130,5±8%Ω;
A:89,0±8%Ω;
Class B
Fan Motor (top) Zhuhai Kaibang YD28X 220-240V; 0,28A; EN 60335-2-40 Tested with
Motor 50Hz; 16W; Main: appliance
Manufacturing 352,6±8%Ω; Aux:
CO., LTD. 95±8%Ω; Class B
Alternative Zhuhai city YD28X 220-240V; 0,28A; EN 60335-2-40 Tested with
Tongde electric 50Hz; 16W; appliance
equipment co., ltd M:429±8%Ω;
A:81,5±8%Ω;
Class B
Alternative Zhuhai city YD28X-L 220-240V; 50Hz; EN 60335-2-40 Tested with
Tongde electric 16W; Class B; appliance
equipment co.,ltd. Main:498±8%Ω;
Aux:114±8%Ω
-Overheat Jiangsu BR-A Series 250V 5A EN 60730-1 VDE
protector of fan Changsheng Operation: 135°C EN 60730-2-2 40015893
motor Electric Appliance IEC 60079-15
Co. Ltd.
-Alternative Jiangsu 17AM-D 250V 8A EN 60730-1 VDE
Changsheng Series Operation: EN 60730-2-2 40016509
Electric Appliance 135±5°C IEC 60079-15
Co. Ltd.
-Alternative Jiangsu BR-A2D 250V 6A/125V EN 60730-1 VDE
Changsheng Series 10A Operation: EN 60730-2-2 40015893
Electric Appliance 135°C IEC 60079-15
Co. Ltd.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 95 of 177 Modification 12: November 10, 2020

-Alternative Changzhou KW Series 250V 6A EN 60730-1 VDE


Changhong Tongli Operation: 135°C EN 60730-2-2 40020906
Electric Appliance IEC 60079-15
Co. Ltd.
-Alternative Zhejiang KSD-II Series 250V 5A EN 60730-1 VDE 139430
Dongyang Operation: 135°C EN 60730-2-2
Hengdian Thermal IEC 60079-15
Protector Factory
-Alternative Sensata 17AM Series 250V; 10A EN 60730-1 KEMA:20145
Technologies Operation: 135°C EN 60730-2-2 31.05
Holland; B.V. IEC 60079-15
-Alternative Sensata BW Series 250V 6A EN 60730-1 KEMA:20947
Technologies Operation: 135°C EN 60730-2-2 54.01
Holland; B.V. IEC 60079-15
-Alternative Jiangsu BR-A-135°C AC250V; EN 60730-1 VDE
Changsheng Operation: 135°C EN 60730-2-2 40040873
Electric Appliance IEC 60079-15
Co.;Ltd
-Alternative Jiangsu 18AM-B AC250V6A; EN 60730-1 VDE
Changsheng 135°C Operation: 135°C EN 60730-2-2 40022813
Electric Appliance IEC 60079-15
Co.;Ltd
-Alternative Jiangsu BR-A Series AC250V; 6A; EN 60730-1 VDE
Changsheng Operation: 135°C EN 60730-2-2 40040873
Electric Appliance IEC 60079-15
Co. Ltd.
-Alternative Sensata BW Series 250V; 16A; EN 60730-1 KEMA:20947
Technologies Operation: 135°C EN 60730-2-2 54.01
Holland; B.V. IEC 60079-15
Fan motor Xiamen Faratronic C6G 3,5μF;450V;T85; EN 60252-1 TÜV
capacitor Co., Ltd. P2/S3 Rheinland R
50266163
Alternative Ningbo Shine CBB61S 3,5μF/450V/T70; EN 60252-1 TÜV
Electrical Co., Ltd. P2/S3 Rheinland R
50076953
Alternative Shanghai Haoye MKPS 3,5μF/450V; T70; EN 60252-1 TÜV
Electric Co., Ltd. P2/S3 Rheinland R
50035566
Alternative Shanghai Haoye MKP-1 3,5μF/450V; T85; EN 60252-1 VDE
Electric Co., Ltd. P2/S3 40023685
Alternative Guangdong CBB61 3,5μF/450VAC/T7 EN 60252-1 TÜV
Fengming 0; P2/S3 Rheinland R
Electronic Tech. 50274996
Co., Ltd.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 96 of 177 Modification 12: November 10, 2020

Main Board for GREE M701F2Z ---- EN 60335-2-40 Tested with


models appliance
GPH12AL-
K5NNA3A,
GPH12AL-
K5NNA2A,
GPH12AL-
K5NNA1A
-Main Board GREE M701F2Z ---- EN 60335-2-40 Tested with
(High voltage appliance
board) for
models
GPH12AL-
K5NNA3A,
GPH12AL-
K5NNA2A,
GPH12AL-
K5NNA1A
Main Board for GREE M701F1A ---- EN 60335-2-40 Tested with
model appliance
GPC12AL-
K5NNA3A
-Main Board GREE M701F1Z ---- EN 60335-2-40 Tested with
(High voltage appliance
board) for model
GPC12AL-
K5NNA3A
Main board for GREE M701F2TJ ---- EN 60335-2-40 Tested with
model appliance
GPH12AL-
K5NNA2B,
GPH12AL-
K5NNA3C,
GPH12AL-
K5NNA1C
Main board for GREE M701F2ASJ ---- EN 60335-2-40 Tested with
model appliance
GPH12AL-
K5NNA2B,
GPH12AL-
K5NNA3C,
GPH12AL-
K5NNA1C

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 97 of 177 Modification 12: November 10, 2020

Alternative Main GREE M701F2SJ ---- EN 60335-2-40 Tested with


board for model appliance
GPH12AL-
K5NNA2B,
GPH12AL-
K5NNA3A,
GPH12AL-
K5NNA2A,
GPH12AL-
K5NNA3C,
GPH12AL-
K5NNA1C,
GPH12AL-
K5NNA1A
Alternative Main GREE M701F2BKJ ---- EN 60335-2-40 Tested with
board for model appliance
GPH12AL-
K5NNA2B,
GPH12AL-
K5NNA3A,
GPH12AL-
K5NNA2A,
GPH12AL-
K5NNA3C,
GPH12AL-
K5NNA1C,
GPH12AL-
K5NNA1A
Main board for GREE M701F1NJ ---- EN 60335-2-40 Tested with
model appliance
GPC12AL-
K5NNA3B
Main board for GREE M701F1BLJ ---- EN 60335-2-40 Tested with
model appliance
GPC12AL-
K5NNA3B
Alternative Main GREE M701F1PJ ---- EN 60335-2-40 Tested with
board for model appliance
GPC12AL-
K5NNA3B,
GPC12AL-
K5NNA3A,
GPC12AL-
K5NNA2A
Alternative Main GREE M701F1BKJ ---- EN 60335-2-40 Tested with
board for model appliance
GPC12AL-
K5NNA3B,
GPC12AL-
K5NNA3A,
GPC12AL-
K5NNA2A,
GPC12AL-
K5NNA3D

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 98 of 177 Modification 12: November 10, 2020

WIFI modular GREE ZCS53A ---- EN 60335-2-40 Tested with


for GPH12AL- appliance
K5NNA2B,
GPC12AL-
K5NNA3B,
GPH12AL-
K5NNA3C,
GPH12AL-
K5NNA1C
Relay 1# Dongguan Sanyou SFK-112DM-E 250VAC; 80A; T85 EN 61810-1 TÜV
Electrical IEC/EN 60079-15 Rheinland R
Appliances Co., 50138321
Ltd.
Relay 2# Dongguan Churod CHF-S- 250VAC; 25A; T85 EN 61810-1 TÜV
Electronics Co., 112DA2 IEC/EN 60079-15 Rheinland R
Ltd. 50220099
Alternative Xiamen Hongfa HF160F/12-H5 250V; 25A; T85 EN 61810-1 VDE
Electroacoustics IEC/EN 60079-15 40024142
Co., Ltd.
Relay 3# Xiamen Hongfa JZC-32F 250VAC;5A; T70 EN 61810-1 VDE
Electroacoustics IEC/EN 60079-15 40012204
Co., Ltd.
Alternative Dongguan Sanyou SJ-SH- 250VAC;5A; T85 EN 61810-1 TÜV
Electrical 112DM2 IEC/EN 60079-15 Rheinland R
Appliances Co., 50142420
Ltd.
Alternative Dongguan Sanyou SJ-SH- 250VAC; 5A; T85 EN 61810-1 VDE
Electrical 112DM2 EN 60255-23 40002146
Appliances Co., IEC/EN 60079-15
Ltd.
Alternative Dongguan Churod A1-S-112DA 250VAC; 5A; T85 EN 61810-1 TÜV
Electronics Co., IEC/EN 60079-15 Rheinland R
Ltd. 50174892
Alternative Song Chuan 307-1AH-S 250VAC; 5A; T85 IEC/EN 61810-1 TÜV
Precision Co., Ltd. IEC/EN 60079-15 Rheinland R
50128391
Alternative Tyco OJE-SH- 5A; 250VAC; IEC/EN 61810-1 TÜV
Electronics(shenz 112DM 12VDC; T7 IEC/EN 60079-15 Rheinland R
hen)Co., Ltd 50139166
Fuse Hollyland 50CT 250V; 3,15A EN 60127-1 VDE
Company Limited EN 60127-2 40014896
Alternative Walter Electronic TSC 250V; 3,15A EN 60127-1 VDE
Co. Ltd. EN 60127-2 40016670
Alternative Dongguan Better 524 250V; 3,15A EN 60127-1 VDE
Electronics EN 60127-2 40025424
Technology Co.,
Ltd.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 99 of 177 Modification 12: November 10, 2020

Varistor Chengdu Tieda MYN15-621K 385V(r,m,s)AC; CECC 42000 VDE


Electronic Co., T85 CECC 42200 40008571
Ltd. CECC 42201
IEC 61051-1
IEC 61051-2
IEC 61051-2-2
Alternative Fenghua Adv. FNR-14K621 385V(r,m,s)AC; CECC 42000 VDE
Tech. (Holding) T85 CECC 42200 40008242
Co., Ltd. CECC 42201
IEC 61051-1
IEC 61051-2
IEC 61051-2-2
Y2 Capacitor TDK Corporation CS102M 250VAC;102M EN 60384-14 VDE
40029781
Alternative Murata Mfg. Co., KY102M 250VAC;102M EN 60384-14 VDE
Ltd. 40006273
Alternative Haohua Electronic CT7 250VAC; 102M EN 60384-14 VDE
Co. 40013601
Alternative ZHAOQING CD472M 472M/400V/T125 EN 60384-14 VDE
INFORMED 40048059
ELECTRONICS
FACTORY CO.,
LTD
X2 capacitor Xiamen Faratronic MKP62 104M/275V;T110 EN 60384-14 VDE
Co. Ltd. 40000358
Alternative Foshan City Xin MKP-X2 0,1μF; 275V; T105 EN 60384-14 VDE
Yuan Electronic 40027433
Co.,Ltd
Alternative Yangzhou Nissei MP1 104M/275VAC; EN 60384-14 VDE
Electronics Co., T110 40041628
Ltd
Optical Coupling Sharp Corporation PC817 Vceo: 80V;If: EN 60747-5-2 VDE
Electronic 50mA;Ic: 50mA 40008087
Components and
Devices Division
Optical Coupling Toshiba TLP785 Vceo: 80V;If: EN 60747-5-2 VDE
Corporation 60mA; Ic: 50mA 40031808
Semiconductor &
Storage Products
Company
High Frequency SHENZHEN EE19- ≤250V/AC 50Hz; EN 60335-2-40 Tested with
Transformer YAMAXI 8P(VDE) 12V; R1-4: 1,25Ω appliance
ELECTRONICS MAX,R6-7: 130mΩ
CO., LTD MAX; R10-9:
60mΩ MAX;
880uH±10%; 50uH
MAX; Class B
Alternative SHENZHEN EE19-08PA 85-265V AC; 12V; EN 60335-2-40 Tested with
JINGQUANHUA R(4-1)1.5Ω; R(6- appliance
ELECTRONICS 7)130mΩ; R(10-
CO.;LTD 9)65mΩ; Class B
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 100 of 177 Modification 12: November 10, 2020

Alternative DONGGUAN ECO20-07PA 85V~265V;15V;12 EN 60335-2-40 Tested with


DAZHONG V;0~132KHz; R(3- appliance
ELECTRONIC 1)=0.95ΩMAX;R(5
CO.;LTD -6)=0.2ΩMAX;R(8-
11)=45mΩMAX;91
8uH±10%;27.5uH
MAX; class B
Alternative SHENZHEN ECO20-07PA 85-265V; 5V; 12V; EN 60335-2-40 Tested with
JINGQUANHUA 15V; 0-132KHZ; appliance
ELECTRONICS R(3-1)0.95Ω MAX;
CO.;LTD R(6-5)0.20Ω MAX;
R(8-11)45.0mΩ
MAX; L(3-1)
918μH±10%;LK(3-
1)27.5μH MAX;
Class B
High Frequency GREE XIN YUAN ECO20-07PA 85~265V AC; EN 60335-2-40 Tested with
Transformer ELECTRONIC P2:6-5 15V; S3:8- appliance
CO.,LTD. 11 12V;
0~132KHz;
DCR(3-1)≤0,95Ω;
DCR(6-5)≤0,20Ω;
DCR(8-11)≤45mΩ;
918uH±10%;
27,5uH MAX;
Class B
Inductance XINJI 10uH 10uH/1,5A EN 60335-2-40 Tested with
ELECTRONICS appliance
COMPONENT(HA
NGZHOU) CO.
LTD
Alternative Shenzhen Yamaxi 10uH 10uH/1,5A EN 60335-2-40 Tested with
Electronic Co., appliance
Ltd.
Alternative Dongguan 10uH 10uH/1,5A EN 60335-2-40 Tested with
Dazhong appliance
Electronic Co.,
Ltd.
Filter XINJI SF2022A- AC250V/0,5A EN 60335-2-40 Tested with
ELECTRONICS 05220 appliance
COMPONENT(HA
NGZHOU)
CO.LTD
Alternative Qingdao Yunlu LB0522 AC250V/0,5A EN 60335-2-40 Tested with
energy technology appliance
Co., Ltd.
Alternative SHENZHEN SF2022A- AC250V/0,5A EN 60335-2-40 Tested with
YAMAXI 05220 appliance
ELECTRONIC
CO.LTD

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 101 of 177 Modification 12: November 10, 2020

Alternative DAZHONG SF2022A- AC250V/0,5A EN 60335-2-40 Tested with


ELECTRONIC 05220 appliance
CO.LTD
Rectifier 1# SHINDENGEN S1NBC80 (NC 800V;1,5A EN 60335-2-40 Tested with
ELECTRIC MFG 80) appliance
CO LTD
Rectifier 2# Tian Jin Zhong- T3SB60 600V; 4A EN 60335-2-40 Tested with
Huan appliance &
Semiconductor VDE
Joint-Stock Co. 40009662
Ltd.
Alternative Leshan Radio Co., D3SB60 600V; 4A EN 60335-2-40 Tested with
Ltd appliance
Alternative LITE-ON KBJ406GL 600V; 4A EN 60335-2-40 Tested with
SEMICONDUCTO appliance
R CORP.
(WANTAI
INTERNATION
TRADING
LIMITED)
Alternative Yangzhou HY 4GBJ406 Io=4.0A; Vr=600V EN 60335-2-40 Tested with
Technology appliance
Development Co.,
LTD.
Alternative SHINDENGEN D3SB 60 600V; 4A EN 60335-2-40 Tested with
ELECTRIC MFG appliance
CO LTD
Alternative SHINDENGEN D3SB 60 600V; 4A EN 60335-2-40 Tested with
ELECTRIC MFG appliance
CO LTD
Terminal Board Changzhou Kaidu JX02-8 AC250V;2,5mm² EN 60335-2-40 Tested with
Electrical Co Ltd appliance
Alternative Nantong Huaguan JXW-2-G AC250V;2,5mm² EN 60998-1 Tested with
Electric Co. Ltd. EN 60998-2-1 appliance &
EN 61210 VDE
EN 60335-2-40 40013197
4-way valve Zhejiang Dunan DSF-9-R410A AC220V-240V; EN 60730-1 VDE
Artificial 50/60Hz; 7/5W; 40013212
Environmental 1970±197Ω; Class
Equipment Co.; B
Ltd.
Alternative Zhejiang Dunan DSF-9-R410A AC220V-240V; EN 60730-1 TUV
Artificial 50/60Hz; 7/5W; R50197052
Environment Co.; 1970±197Ω; Class
Ltd. B
Alternative Zhongshan Gangli SHF-7 AC220-240V; EN 60730-1 VDE
Refrigeration 50/60Hz; 40026249
Accessory CO., 4.5/3.5W; Class B;
LTD 2100Ω±150Ω

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 102 of 177 Modification 12: November 10, 2020

Alternative Zhejiang Sanhua SHF-7H-34U- AC220-240V; EN 60730-1 VDE


Climate and PG 50/60Hz; 40003240
Appliance 4.5/3.5W; Class B;
Controls Group 2085±208Ω
Co., Ltd. (Zhejiang
Sanhua Trading
CO.,LTD)
Alternative Zhejiang Dunan DSF-4-R410A AC220V-240V; EN 60730-1 VDE
Artificial 50/60Hz;7/5W;197 40013212
Environmental 0±197Ω;ClassB
Equipment Co.,
Ltd.
Alternative Zhongshan City SHF-4 AC220-240V; EN 60730-1 VDE
Gangli 50/60Hz;4.5/3.5W; 40026249
Refrigertion Class B;
Fittings Co., Ltd. 2100Ω±150Ω
Alternative Zhejiang Sanhua SHF-4H-23U- 220-240V; EN 60730-1 VDE
Climate and P 50/60Hz;4.5/3.5W; 40003240
Appliance Class B;
Controls Group 2085±208Ω;
Co., Ltd.(Zhejiang
Sanhua Trading
Co., Ltd.)
Alternative Zhuhai ligao DHF-4T-01 AC220-240V; EN 60730-1 VDE
precision 50/60Hz;7W/5W 40045332
manufacturing 2030Ω±200Ω
Co., Ltd. (20℃); Class B

PCB Material Jiangxi Uniongain DS2 94V-0 EN 60335-2-40 Tested with


Electronics appliance
Technology
UL E464601
Co.,Ltd
Alternative PALWONNELECT D3 CEM-1; 94-V0; EN 60335-2-40 Tested with
RONICS(SHENZ CTI>175V
appliance
HEN) CO.LTD
UL E230435
Alternative CHANGCHUN CCP-508; CEM-1; 94-V0; EN 60335-2-40 Tested with
PLASTIC CO LTD CTI>175V appliance &
CCP-508U
UL E108591
Alternative SHENGYI S3116 CEM-1; 94-V0; EN 60335-2-40 Tested with
TECHNOLOGY CTI>175V appliance &
CO LTD UL E109769
Alternative SHENGYI S3110 CEM-1; 94-V0; EN 60335-2-40 Tested with
TECHNOLOGY CTI>175V appliance &
CO LTD UL E109769
Alternative SHENGYI S1141 FR-4; 94-V0; EN 60335-2-40 Tested with
TECHNOLOGY CTI>175V appliance &
CO LTD UL E109769
Alternative KINGBOARD KB3151C FR-1; 94-V0; EN 60335-2-40 Tested with
LAMINATES CTI>175V appliance &
HOLDINGS LTD UL E123995

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 103 of 177 Modification 12: November 10, 2020

Alternative SHENGYI S2130 CEM-3; 94-V0; EN 60335-2-40 Tested with


TECHNOLOGY CTI>175V appliance &
CO LTD UL E109769
Alternative KINGBOARD KB6160/P-138 FR-4; 94-V0; EN 60335-2-40 Tested with
LAMINATES CTI>175V appliance &
HOLDINGS LTD UL E123995
Alternative NAN YA FR-4-86 FR-4; 94V-0 EN 60335-2-40 Tested with
PLASTICS CORP appliance &
CCL DEPT UL E98983
ELECTRONIC
MATERIAL DIVL
DIV
Alternative Bomin Electronics BM2; BM6-1 94V-0 EN 60335-2-40 Tested with
Co., Ltd. appliance &
UL E213371
Alternative Huizhou XZG-P1; XZG- 94V-0 EN 60335-2-40 Tested with
Xingzhiguang Co., T1 appliance &
Ltd UL E246887
Alternative ZHUHAI JOINTEK JK-004 94V-0 EN 60335-2-40 Tested with
ELECTRIC CO appliance &
LTD UL E214852
Alternative GUANGDONG XI XD-102 94V-0 EN 60335-2-40 Tested with
NGDA HONGYE appliance &
ELECTRONIC CO UL E193079
., LTD
Alternative SHUNDE JUNDA JD-D; JD-E 94V-0 EN 60335-2-40 Tested with
appliance &
UL E173873
Alternative BaoYueJia BYJ-3 94V-0 EN 60335-2-40 Tested with
Electronics appliance &
(ZhongShan) Co., UL E230225
Ltd
Alternative TATCHUN TC-series 94V-0 EN 60335-2-40 Tested with
PRINTED appliance &
CIRCUIT BOARD UL E131175
CO., LTD
Alternative Jiangmen Benlida BLD-A 94V-0 EN 60335-2-40 Tested with
Printed Circuit appliance &
Co., Ltd UL E203640
Alternative SHENGYI S2130 CEM-3; 94V-0 EN 60335-2-40 Tested with
TECHNOLOGY appliance &
CO LTD UL E109769
Alternative KINGBOARD KB6160/P-138 FR-4 EN 60335-2-40 Tested with
LAMINATES appliance &
HOLDINGS LTD UL E123995
Alternative NAN YA FR-4-86 FR-4,94V-0 EN 60335-2-40 Tested with
PLASTICS CORP appliance &
CCL DEPT UL E98983
ELECTRONIC
MATERIAL DIV

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 104 of 177 Modification 12: November 10, 2020

Alternative NAN YA UV BLOCK FR-4,94V-0 EN 60335-2-40 Tested with


PLASTICS CORP FR-4-86 appliance &
CCL DEPT UL E98983
ELECTRONIC
MATERIAL DIV
Alternative SHENGYI S1141 FR-4,94V-0 EN 60335-2-40 Tested with
TECHNOLOGY appliance &
CO LTD UL E109769
Alternative KINGBOARD KB-6160 / FR-4,94V-0 EN 60335-2-40 Tested with
LAMINATES appliance &
KB-6160C
HOLDINGS LTD UL E123995
Alternative KINGBOARD KB5150/ FR-4,94V-0 EN 60335-2-40 Tested with
LAMINATES appliance &
KB-5150&
HOLDINGS LTD UL E123995
Alternative ZHUHAI JINHAO JP-3 FR-4,94V-0 EN 60335-2-40 Tested with
ELECTRONICS appliance &
CO LTD UL E309382
Alternative LONRAY(WUPIN LR-02 FR-4,94V-0 EN 60335-2-40 Tested with
G) ELECTRONIC appliance &
TECHNOLOGY UL E356536
CO LTD
Alternative SICHUAN CH-2 FR-4,94V-0 EN 60335-2-40 Tested with
CHANHONG appliance &
ELECTRONIC CO UL E169373
LTD
Supplementary information:
1) Provided evidence ensures the agreed level of compliance. See OD-CB2039.
2) License available upon request for all the certified components

28.1 TABLE: Threaded part torque test P


Threaded part identification Diameter of thread Column number Applied torque (Nm)
(mm) (I, II, or III)
Earthing screws 3,8 II 1,2

29.1 TABLE: Clearances P


Overvoltage category ........................................... : II ⎯
Type of insulation:
Rated impulse Min. cl (mm) Basic Supplementary Reinforced Functional Verdict / Remark
voltage (V): (mm) (mm) (mm) (mm)
330 0,2* / 0,5 / 0,8** — — — — —
500 0,2* / 0,5 / 0,8** — — — — —
800 0,2* / 0,5 / 0,8** — — — — —
1 500 0,5 / 0,8** / 1,0*** — — — — —
2 500 1,5 / 2,0*** 3,2 >10 — 4,8 P
4 000 3,0 / 3,5*** — — >10 — P

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 105 of 177 Modification 12: November 10, 2020

6 000 5,5 / 6,0*** — — — — —


8 000 8,0 / 8,5*** — — — — —
10 000 11,0 / 11,5*** — — — — —
Supplementary information:
*) For tracks on printed circuit boards if pollution degree 1 and 2
**) For pollution degree 3
***) If the construction is affected by wear, distortion, movement of the parts or during assembly

29.2 TABLE: Creepage distances, basic, supplementary and reinforced insulation P


Working voltage Creepage distance
(V) (mm)
Pollution degree
1 2 3 Type of insulation Verdict
Material group Material group
I II IIIa/IIIb I II IIIa/IIIb* B** S** R**
50 0,18 0,6 0,85 1,2 1,5 1,7 1,9 ⎯ ⎯ N/A
50 0,18 0,6 0,85 1,2 1,5 1,7 1,9 ⎯ ⎯ N/A
50 0,36 1,2 1,7 2,4 3,0 3,4 3,8 ⎯ ⎯ N/A
125 0,28 0,75 1,05 1,5 1,9 2,1 2,4 ⎯ ⎯ N/A
125 0,28 0,75 1,05 1,5 1,9 2,1 2,4 ⎯ ⎯ N/A
125 0,56 1,5 2,1 3,0 3,8 4,2 4,8 ⎯ ⎯ N/A
250 0,56 1,25 1,8 2,5 3,2 3,6 4,0 ⎯ ⎯ N/A
250 0,56 1,25 1,8 2,5 3,2 3,6 4,0 3,2 ⎯ ⎯ P
250 0,56 1,25 1,8 2,5 3,2 3,6 4,0 ⎯ >10 ⎯ P
250 1,12 2,5 3,6 5,0 6,4 7,2 8,0 ⎯ ⎯ >10 P
400 1,0 2,0 2,8 4,0 5,0 5,6 6,3 ⎯ ⎯ N/A
400 1,0 2,0 2,8 4,0 5,0 5,6 6,3 ⎯ ⎯ N/A
400 2,0 4,0 5,6 8,0 10,0 11,2 12,6 ⎯ ⎯ N/A
500 1,3 2,5 3,6 5,0 6,3 7,1 8,0 ⎯ ⎯ N/A
500 1,3 2,5 3,6 5,0 6,3 7,1 8,0 ⎯ ⎯ N/A
500 2,6 5,0 7,2 10,0 12,6 14,2 16,0 ⎯ ⎯ N/A
630 and 800 1,8 3,2 4,5 6,3 8,0 9,0 10,0 ⎯ ⎯ N/A
630 and 800 1,8 3,2 4,5 6,3 8,0 9,0 10,0 ⎯ ⎯ N/A
630 and 800 3,6 6,4 9,0 12,6 16,0 18,0 20,0 ⎯ ⎯ N/A
800 and 1000 2,4 4,0 5,6 8,0 10,0 11,0 12,5 ⎯ ⎯ N/A
800 and 1000 2,4 4,0 5,6 8,0 10,0 11,0 12,5 ⎯ ⎯ N/A
800 and 1000 4,8 8,0 11,2 16,0 20,0 22,0 25,0 ⎯ ⎯ N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 106 of 177 Modification 12: November 10, 2020

1000 and 1250 3,2 5,0 7,1 10,0 12,5 14,0 16,0 ⎯ ⎯ N/A
1000 and 1250 3,2 5,0 7,1 10,0 12,5 14,0 16,0 ⎯ ⎯ N/A
1000 and 1250 6,4 10,0 14,2 20,0 25,0 28,0 32,0 ⎯ ⎯ N/A
1250 and 1600 4,2 6,3 9,0 12,5 16,0 18,0 20,0 ⎯ ⎯ N/A
1250 and 1600 4,2 6,3 9,0 12,5 16,0 18,0 20,0 ⎯ ⎯ N/A
1250 and 1600 8,4 12,6 18,0 25,0 32,0 36,0 40,0 ⎯ ⎯ N/A
1600 and 2000 5,6 8,0 11,0 16,0 20,0 22,0 25,0 ⎯ ⎯ N/A
1600 and 2000 5,6 8,0 11,0 16,0 20,0 22,0 25,0 ⎯ ⎯ N/A
1600 and 2000 11,2 16,0 22,0 32,0 40,0 44,0 50,0 ⎯ ⎯ N/A
2000 and 2500 7,5 10,0 14,0 20,0 25,0 28,0 32,0 ⎯ ⎯ N/A
2000 and 2500 7,5 10,0 14,0 20,0 25,0 28,0 32,0 ⎯ ⎯ N/A
2000 and 2500 15,0 20,0 28,0 40,0 50,0 56,0 64,0 ⎯ ⎯ N/A
2500 and 3200 10,0 12,5 18,0 25,0 32,0 36,0 40,0 ⎯ ⎯ N/A
2500 and 3200 10,0 12,5 18,0 25,0 32,0 36,0 40,0 ⎯ ⎯ N/A
>2500 and 3200 20,0 25,0 36,0 50,0 64,0 72,0 80,0 ⎯ ⎯ N/A
3200 and 4000 12,5 16,0 22,0 32,0 40,0 45,0 50,0 ⎯ ⎯ N/A
3200 and 4000 12,5 16,0 22,0 32,0 40,0 45,0 50,0 ⎯ ⎯ N/A
3200 and 4000 25,0 32,0 44,0 64,0 80,0 90,0 100,0 ⎯ ⎯ N/A
4000 and 5000 16,0 20,0 28,0 40,0 50,0 56,0 63,0 ⎯ ⎯ N/A
4000 and 5000 16,0 20,0 28,0 40,0 50,0 56,0 63,0 ⎯ ⎯ N/A
4000 and 5000 32,0 40,0 56,0 80,0 100,0 112,0 126,0 ⎯ ⎯ N/A
5000 and 6300 20,0 25,0 36,0 50,0 63,0 71,0 80,0 ⎯ ⎯ N/A
5000 and 6300 20,0 25,0 36,0 50,0 63,0 71,0 80,0 ⎯ ⎯ N/A
5000 and 6300 40,0 50,0 72,0 100,0 126,0 142,0 160,0 ⎯ ⎯ N/A
6300 and 8000 25,0 32,0 45,0 63,0 80,0 90,0 100,0 ⎯ ⎯ N/A
6300 and 8000 25,0 32,0 45,0 63,0 80,0 90,0 100,0 ⎯ ⎯ N/A
6300 and 8000 50,0 64,0 90,0 126,0 160,0 180,0 200,0 ⎯ ⎯ N/A
8000 and 10000 32,0 40,0 56,0 80,0 100,0 110,0 125,0 ⎯ ⎯ N/A
8000 and 10000 32,0 40,0 56,0 80,0 100,0 110,0 125,0 ⎯ ⎯ N/A
8000 and 10000 64,0 80,0 112,0 160,0 200,0 220,0 250,0 ⎯ ⎯ N/A
10000 and 12500 40,0 50,0 71,0 100,0 125,0 140,0 160,0 ⎯ ⎯ N/A
10000 and 12500 40,0 50,0 71,0 100,0 125,0 140,0 160,0 ⎯ ⎯ N/A
10000 and 12500 80,0 100,0 142,0 200,0 250,0 280,0 320,0 ⎯ ⎯ N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 107 of 177 Modification 12: November 10, 2020

Supplementary information:
*) Material group IIIb is allowed if the working voltage does not exceed 50 V
**) B = Basic insulation, S = Supplementary insulation, R = Reinforced insulation
1) Lacquered conductors of windings are considered to be bare conductors, but creepage distances need

not be greater than the associated clearance specified in Table 16 taking into account 29.1.1.

29.2 TABLE: Creepage distances, functional insulation P


Working voltage Creepage distance Verdict / Remark
(V) (mm)
Pollution degree
1 2 3
Material group Material group
I II IIIa/IIIb I II IIIa/IIIb*
10 0,08 0,4 0,4 0,4 1,0 1,0 1,0 N/A
50 0,16 0,56 0,8 1,1 1,4 1,6 1,8 N/A
125 0,25 0,71 1,0 1,4 1,8 2,0 2,2 N/A
250 0,42 1,0 1,4 2,0 2,5 2,8 3,2 P(4,8mm between L and N
on PCB board )
400 0,75 1,6 2,2 3,2 4,0 4,5 5,0 N/A
500 1,0 2,0 2,8 4,0 5,0 5,6 6,3 N/A
630 and 800 1,8 3,2 4,5 6,3 8,0 9,0 10,0 N/A
800 and 1000 2,4 4,0 5,6 8,0 10,0 11,0 12,5 N/A
1000 and 1250 3,2 5,0 7,1 10,0 12,5 14,0 16,0 N/A
1250 and 1600 4,2 6,3 9,0 12,5 16,0 18,0 20,0 N/A
1600 and 2000 5,6 8,0 11,0 16,0 20,0 22,0 25,0 N/A
2000 and 2500 7,5 10,0 14,0 20,0 25,0 28,0 32,0 N/A
2500 and 3200 10,0 12,5 18,0 25,0 32,0 36,0 40,0 N/A
3200 and 4000 12,5 16,0 22,0 32,0 40,0 45,0 50,0 N/A
4000 and 5000 16,0 20,0 28,0 40,0 50,0 56,0 63,0 N/A
5000 and 6300 20,0 25,0 36,0 50,0 63,0 71,0 80,0 N/A
6300 and 8000 25,0 32,0 45,0 63,0 80,0 90,0 100,0 N/A
8000 and 10000 32,0 40,0 56,0 80,0 100,0 110,0 125,0 N/A
10000 and 12500 40,0 50,0 71,0 100,0 125,0 140,0 160,0 N/A
Supplementary information:
*) Material group IIIb is allowed if the working voltage does not exceed 50 V

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 108 of 177 Modification 12: November 10, 2020

30 TABLE: Resistance to heat and fire


Object/ Manufac Type/ Ball pressure test Glow wire test Glow-wire Glow- wire Needle- Verdict
part No. turer/ model °C (GWT) flammability index ignition flame
tradema °C (GWFI) temp. test
rk °C (GWIT) (NFT)
°C
75 125 cl. 11 cl. 19 550 650 750 850 550 650 750 850 675 775
+40 +25
te ti te ti
Plastic enclosure — — P — — — P — — — — — — — — — — — — P
Bobbin of fan
— — — — — — P — — — — — — — — — — — — P
motor
Bobbin of No
— — — P — — — — — P — — — — — — — P
transformer flame
No
Relay — — — — — — — — — P — — — — — — — P
flame
No
Motor capacitor — — — — — — — — — P — — — — — — — P
flame
Bobbin of water No
— — — P — — — — — — — — — — — — — P
motor flame
Connector on No
— — — P — — — — — P — — — — — — — P
PCB flame
PCB — — — — — — — — — — — — — — — — — — P P
Supplementary information:1) Parts of material classified at least HB40 or if relevant HBF
2) Parts of material classified as V-0 or V-1 3) Flame persisting longer than 2 s (= te – ti) need only be reported for unattended appliances
4) Surrounding parts subjected to the needle-flame test of annex E
5) Base material classified as V-0 or if relevant VTM-0
6) The GWIT pre-selection option, the 850 ° C GWFI pre-selection option, and the 850 °C GWT are not applicable for attended appliances
7) Tested for all alternative components and recorded the most severe results.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou, Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 109 of 177 Modification 12: November 10, 2020

Appendix EMF P
TEST: Evaluation of the magnetic fields
Applied standards: IEC 62233:2005, EN 62233:2008 (incl. Corr.1:2008)
Method Used method: 5.5.2 Time domain evaluation —
Applied Limit ICNIRP Guidelines —
Identification of the appliance Type of apparatus Local air conditioner
Rated Voltage 220-240V
Rated Frequency 50Hz
Parameters required prior to the test Laboratory Ambient Temperature 25 °C ± 10 °C
Supply Voltage (Rated Voltage ± 2 %) V
Supply Frequency (Rated Frequency ± 2 %) Hz
Parameters recorded during the test Laboratory Ambient Temperature 25°C
Supply Voltage 230V
Supply Frequency 50Hz
Operating Mode
Method 5.5.2
Measuring Positions Measuring Distance Coupling Factor Measurement Uncertainty
Around 30cm — —
Frequency (kHz) Limit (%) Measured Maximum Value (%)
0,01 to 400 100 1,674%
Supplementary information:
The measured maximum value in this table may be weighted with the coupling factor if applicable, and the
measurement uncertainty is applied if the measured result is more than 75 % of the limit.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 110 of 177 Modification 12: November 10, 2020

Photo documents:

Top and front view for GPC12AL-K5NNA3A

Top and front view for GPH12AL-K5NNA3A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 111 of 177 Modification 12: November 10, 2020

Rear and side view

Rear view

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 112 of 177 Modification 12: November 10, 2020

Remove filter view

Supply cord inlet

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 113 of 177 Modification 12: November 10, 2020

Control panel

Internal view

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 114 of 177 Modification 12: November 10, 2020

Internal view

Internal view

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 115 of 177 Modification 12: November 10, 2020

Earthing marking

Internal of top cover view (control PCB board)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 116 of 177 Modification 12: November 10, 2020

Infrared control board

Control board

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 117 of 177 Modification 12: November 10, 2020

Control board

Control board

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 118 of 177 Modification 12: November 10, 2020

Alternative control panel

Alternative control panel

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 119 of 177 Modification 12: November 10, 2020

Electric box

Internal view of electric box (main board and main board (high voltage board))

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 120 of 177 Modification 12: November 10, 2020

Main board for model GPH12AL-K5NNA3A

Main board for model GPH12AL-K5NNA3A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 121 of 177 Modification 12: November 10, 2020

main board (high voltage board) for model GPH12AL-K5NNA3A

main board (high voltage board) for model GPH12AL-K5NNA3A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 122 of 177 Modification 12: November 10, 2020

main board (high voltage board) for model GPH12AL-K5NNA3A

Note: the main board (M701F2Z) of model GPH12AL-K5NNA3A and main board (M701F1A) of model
GPC12AL-K5NNA3A of are same except main board (M701F1A) has deleting one relay which control 4-way
valve.

Fan motor

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 123 of 177 Modification 12: November 10, 2020

Fan motor marking

Compressor

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 124 of 177 Modification 12: November 10, 2020

Compressor marking

Note: The photos of model GPC12AL-K5NNA3A is same as photos of model GPH12AL-K5NNA3A except
GPC12AL-K5NNA3A has not 4-way valve.

Alternative front panel for models GPH12AL-K5NNA3A, GPC12AL-K5NNA3A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 125 of 177 Modification 12: November 10, 2020

Front panel for model GPH12AL-K5NNA2A

Front panel for model GPC12AL-K5NNA2A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 126 of 177 Modification 12: November 10, 2020

Following photos for models GPC12AL-K5NNA3B, GPH12AL-K5NNA2B:

Front panel for model GPH12AL-K5NNA2B

Front panel for model GPC12AL-K5NNA3B

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 127 of 177 Modification 12: November 10, 2020

Front panel for model GPC12AL-K5NNA2C; GPH12AL-K5NNA2C

WIFI modular (ZCS53A) PCB baord

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 128 of 177 Modification 12: November 10, 2020

Internal view of electric box (Main PCB board (M701F2TJ))

Main PCB board (M701F2TJ)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 129 of 177 Modification 12: November 10, 2020

Main PCB board (M701F2TJ)

Main PCB board (M701F2ASJ)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 130 of 177 Modification 12: November 10, 2020

Main PCB board (M701F2ASJ)

Note: The other photos of models GPC12AL-K5NNA3B, GPH12AL-K5NNA2B can reference the photos of
models GPC12AL-K5NNA3A, GPH12AL-K5NNA3A for details.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 131 of 177 Modification 12: November 10, 2020

Main PCB M701F1NJ (Electrical box view)

Main PCB M701F1NJ

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 132 of 177 Modification 12: November 10, 2020

Main PCB M701F1NJ

Main PCB M701F1BLJ

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 133 of 177 Modification 12: November 10, 2020

Main PCB M701F1BLJ

Main PCB board (M701F1PJ)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 134 of 177 Modification 12: November 10, 2020

Main PCB board (M701F1PJ)

Main PCB board (M701F1BKJ)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 135 of 177 Modification 12: November 10, 2020

Main PCB board (M701F1BKJ)

Main PCB board (M701F2SJ)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 136 of 177 Modification 12: November 10, 2020

Main PCB board (M701F2SJ)

Main PCB board (M701F2BKJ)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 137 of 177 Modification 12: November 10, 2020

Main PCB board (M701F2BKJ)

Following photos for model GPH12AL-K5NNA3C:

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 138 of 177 Modification 12: November 10, 2020

Note: Other photos of model GPH12AL-K5NNA3C can reference photos of model GPH12AL-K5NNA2B.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 139 of 177 Modification 12: November 10, 2020

Front panel of GPH12AL-K5NNA1C

Alternative front panel of GPH12AL-K5NNA1C

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 140 of 177 Modification 12: November 10, 2020

Front panel GPH12AL-K5NNA1A

Front panel GPC12AL-K5NNA1C

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 141 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Appendix

ATTACHMENT TO TEST REPORT IEC 60335-2-40


EUROPEAN GROUP DIFFERENCES AND NATIONAL DIFFERENCES
Part-2-40: Particular requirements for electrical heat pumps, air conditioners and dehumidifiers
Differences according to : EN 60335-2-40:2003 (incl. Corr.:2006) + A11:2004 + A12:2005 +
A1:2006 + A2:2009 + A13:2012 (incl. Corr.:2013)
EN 60335-1:2012 (incl. Corr.:2014)
Attachment Form No. : EU_GD_IEC60335_2_40J
Attachment Originator : VDE
Master Attachment : 2014-06
Copyright © 2014 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.

CENELEC COMMON MODIFICATIONS


6.1 Delete “class 0” and “class 01” N/A
7.1 Single-phase appliances to be connected to the P
supply mains: 230 V covered
Multi-phase appliances to be connected to the N/A
supply mains: 400 V covered
7.10 Devices used to start/stop operational functions of P
the appliance distinguished from other manual
devices by means of shape, size, surface texture,
position, etc.
An indication that the device has been operated is given by: ----
- a tactile feedback, or P
- an audible and visual feedback P
7.12 The instructions include the substance of the following: ----
- this appliance can be used by children aged from P
8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of
experience and knowledge if they have been given
supervision or instruction concerning use of the
appliance in a safe way and understand the
hazards involved
- children shall not play with the appliance P
- cleaning and user maintenance shall not be made P
by children without supervision

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 142 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

7.12.1 Installation instructions for appliances intended to be N/A


permanently connected to fixed wiring, and have
leakage current exceed 10 mA, state that installation
of residual current device (RCD) having rated
residual operating current not exceeding 30 mA is
advisable (EN 60335-2-40)
For appliances not accessible to the general public N/A
and which are intended to be permanently
connected to fixed wiring and which may have
leakage currents exceeding 10 mA, the installation
instructions shall specify the rating of the residual
current device (RCD) to be installed
(EN 60335-2-40/A12)
7.12.Z1 The specific instructions related to the safe P
operation of this appliance is collated together in
the front section of the user instructions
The height of the characters, measured on the P
capital letters, is at least 3 mm
These instructions are also available in an P
alternative format, e.g. on a website
8.1.1 Also test probe 18 of EN 61032 is applied P
The appliance being in every possible position, P
except that appliances normally used on the floor
and having a mass exceeding 40 kg are not tilted.
(EN 60335-1:2012/AC:2014)
The force on the probe in the straight position is P
increased to 10 N when probe 18 is used
When using test probe 18 the appliance is fully P
assembled as in normal use without any parts
removed, and
parts intended to be removed for user maintenance P
are also not removed
8.2 Compliance is checked by applying the test probes P
of EN 61032
For built-in appliances and fixed appliances, the N/A
test probe B and probe 18 of EN 61032 are applied
only after installation
11.8 Footnotes to “External enclosure of motor-operated P
appliances” to be taken into account
13.2 Leakage current measurements (EN 60335-2-40) (See appended table) P
15.1.2 Appliances with an automatic cord reel tested with N/A
the cord in the most unfavourable position so that
the reeling of the wet cord may affect electrical
insulation during operation, the cord not being dried
before reeling

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 143 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

15.2 Drain pan filled to brim and subjected to continuous P


overflow and fan(s) switched on (EN 60335-2-40)
16.2 Leakage current measurements (EN 60335-2-40) (See appended table) P
20.2 When using the test probe similar to test probe B P
with a circular stop face, the accessories and
detachable covers are removed
Test probe 18 applied with a force of 2,5 N on the P
appliance fully assembled
24.1 Components comply with the safety requirements P
specified in the relevant standards as far as they
reasonably apply
The requirements of clause 29 of this standard P
apply between live parts of components and
accessible parts of the appliance.
The requirements of 30.2 of this standard apply to P
parts of non-metallic material in components
including parts of non-metallic material supporting
current-carrying connections inside components
Components that have not been previously tested P
or do not comply with the standard for the relevant
component are tested according to the
requirements of 30.2
Components that have been previously tested and shown to comply with the ----
resistance to fire requirements in the standard for the relevant component need not
be retested provided that:
- the severity specified in the component standard N/A
is not less than the severity specified in 30.2, and
- the test report for the component states whether it N/A
complied with the standard for the relevant
component with or without flame, flames not
exceeding 2 s during the test are ignored
Unless components have been previously tested P
and found to comply with the relevant standard for
the number of cycles specified, they are tested in
accordance with 24.1.1 to 24.1.9
For components mentioned in 24.1.1 to 24.1.9, no P
additional tests specified in the relevant standard
for the component are necessary other than those
specified in 24.1.1 to 24.1.9
Components that have not been separately tested P
and found to comply with the relevant standard,
and
components that are not marked or not used in N/A
accordance with their marking,

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 144 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

are tested in accordance with the conditions N/A


occurring in the appliance, the number of samples
being that required by the relevant standard
Lamp holders and starter holders that have not N/A
been previously tested and found to comply with
the relevant standard are tested as a part of the
appliance and additionally comply with the gauging
and interchangeability requirements of the relevant
standard under the conditions occurring in the
appliance
Where the relevant standard specifies these N/A
gauging and interchangeability requirements at
elevated temperatures, the temperatures measured
during the tests of clause 11 are used
Plugs and socket-outlets and other connecting N/A
devices of interconnection cords are not
interchangeable with plugs and socket-outlets listed
in IEC/TR 60083 or IEC 60906-1, or
with connectors and appliance inlets complying with N/A
the standard sheets of IEC 60320-1,
if direct supply to these parts from the supply mains N/A
gives rise to a hazard
24.1.7 If the remote operation of the appliance is via a N/A
telecommunication network, the relevant standard
for the telecommunication interface circuitry in the
appliance is EN 41003
Compliance with clause 8 of this standard is not N/A
impaired by connecting the appliance to a device
covered by EN 41003
24.Z1 For motor running capacitors (IEC 60252-1 type N/A
P2) with a metallic enclosure having an
overpressure fuse the flame testing of internal
plastic parts supporting current carrying
connections as required in 30.2.2 and 30.2.3.1 is
not necessary
25.6 Supply cords of single-phase portable appliances having a rated current not ----
exceeding 16 A, fitted with a plug complying with the following standard sheets of
IEC/TR 60083:
- for class I appliances: N/A
standard sheet C2b, C3b or C4 ............................ :
- for class II appliances: N/A
standard sheet C5 or C6....................................... :
25.7 Rubber sheathed cords (60245 IEC 53) are not N/A
suitable for appliances intended to be used
outdoors or when they are liable to be exposed to
significant amount of ultraviolet radiation

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 145 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Halogen-free thermoplastic compound sheathed supply cords have properties at ----


least those of:
- halogen-free thermoplastic compound N/A
sheathed cords (H03Z1Z1H2-F or H03Z1Z1-F),
for appliances having a mass not exceeding 3
kg
- halogen-free thermoplastic compound N/A
sheathed cords (H05Z1Z1H2-F or H05Z1Z1-F),
for other appliances
Cross-linked halogen-free compound sheathed N/A
supply cords have properties at least those of
cross-linked halogen-free compound sheathed
cords (H07ZZ-F)
26.11 Conductors connected by soldering are not N/A
considered to be positioned or fixed so that reliance
is not placed upon the soldering alone to maintain
them in position unless they are held in place near
the terminals independently of the solder
29.3.Z1 Appliance constructed so that if there is a possibility N/A
of damaging the insulation during installation, the
insulation withstands the scratch and penetration
test of 21.2
32 Compliance regarding electromagnetic fields is P
checked according to EN 62233
GG.2 Requirements for charge limits in unventilated areas P
(EN 60335-2-40/A1)
GG.Z1 Non fixed factory sealed single package units with a P
charge amount of m1 < M ≤ 2 x m1
(EN 60335-2-40/A1)
Annex I, The appliance is supplied at rated voltage and N/A
19.I.101 operated under normal operation with each of the
fault conditions specified
The duration of the test is as specified in 19.7 N/A
ZA ANNEX ZA (NORMATIVE) ---
SPECIAL NATIONAL CONDITIONS

Norway ----
19.5 The test is also applicable to appliances intended to N/A
be permanently connected to fixed wiring

Norway ----

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 146 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

22.2 The second paragraph of this subclause, dealing N/A


with single-phase, permanently connected class I
appliances having heating elements, is not
applicable due to the supply system

All CENELEC countries ----


25.6 and Information concerning National plug and N/A
25.25 socket-outlets is available from the CENELEC
website. Normative national requirements
concerning plug and socket-outlets are shown in
the relevant National standard

Ireland and United Kingdom ----


25.8 In the table, the lines for 10 A and 16 A are replaced by: ----
> 10 and ≤ 13 1,25 P
(1,0)b(EN 60335-1:2012/AC:2014)
> 13 and ≤ 16 1,5 (1,0)b N/A
(EN 60335-1:2012/AC:2014)

ZB ANNEX ZB (INFORMATIVE) ----


A-DEVIATIONS

Ireland ----
25.6 These regulations apply to all plugs for domestic N/A
use at a voltage of not less than 200 V and in
general allow only plugs complying with I.S.
401:1997, or equivalent, to be fitted to domestic
appliances

United Kingdom ----


25.6 These regulations apply to all plugs for domestic P
use at a voltage of not less than 200 V and in
general allow only plugs to BS 1363 to be fitted to
domestic appliances. It also allows plugs to
BS 4573 and EN 50075 to be fitted to shavers and
toothbrushes

ZC ANNEX ZC (NORMATIVE) ----


NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH
THEIR CORRESPONDING EUROPEAN PUBLICATIONS
A list of referenced documents in this standard P

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 147 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

ZD ANNEX ZD (INFORMATIVE) ----


IEC and CENELEC CODE DESIGNATIONS FOR FLEXIBLE CORDS
A table with IEC and CENELEC code designations P
for flexible cords

ZE ANNEX ZE (INFORMATIVE) ----


SPECIFIC ADDITIONAL REQUIREMENTS FOR APPLIANCES AND MACHINES
INTENDED FOR COMMERCIAL USE
7.1 Business name and full address of the N/A
manufacturer and, where applicable, his authorized
representative ....................................................... :
Model or type reference ........................................ : N/A
Serial number, if any ............................................. : N/A
Production year N/A
Designation of the appliance ................................ : N/A
7.12 Instructions provided with the appliance so that the N/A
appliance can be used safely
The instructions contain at least the following information: ----
- the business name and full address of the N/A
manufacturer and, where applicable, his authorized
representative
- model or type reference of the appliance as N/A
marked on the appliance itself, except for the serial
number
- the designation of the appliance together with its N/A
explanation in case it is given by a combination of
letters and/or numbers
- the general description of the appliance, when N/A
needed due to the complexity of the appliance
- specific precautions if required during installation, N/A
operation, adjusting, user maintenance, cleaning,
repairing or moving
- when needed drawings, diagrams, descriptions N/A
and explanations necessary for the safe use and
user maintenance of the appliance
- the possible reasonably foreseeable misuse and, N/A
whenever relevant, a warning against the effects it
may have on the safe use of the appliance
The words “Original instructions” appear on the N/A
language version(s) verified by the manufacturer or
by the authorized representative

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 148 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

When a translation of the original instructions has N/A


been provided by a person introducing the
appliance on the market; the meaning of the
sentence “Translation of the original instructions”
appear in the relevant instructions delivered with
the appliance
The instructions for maintenance/service to be N/A
done by specialized personnel, mandated by the
manufacturer or the authorized representative may
be supplied in only one Community language which
the specialized personnel understand
The instructions indicate the type and frequency of N/A
inspections and maintenance required for safe
operation including the preventive maintenance
measures
“This appliance is intended to be used by expert or N/A
trained users in shops, in light industry and on
farms, or for commercial use by lay persons”.
(EN 60335-2-40/A13)
7.12.ZE1 If needed for specific appliances, the following information to be given: ----
- on use, transportation, assembly, dismantling N/A
when out of service, testing or foreseeable
breakdowns, if these operations have
consequences on stability of the appliance in
order to avoid overturning, falling or uncontrolled
movements of the appliance or of its component
parts
- on how to maintain adequate mechanical N/A
stability when in use, during transportation,
assembly, dismantling, scrapping and any other
action involving the appliance
- on the protective measures to be taken by the N/A
user, including, where appropriate, the personal
protective equipment to be provided
- on the operating method to be followed in the N/A
event of accident or breakdown; if a blockage is
likely to occur the operating method to safely
unblock the appliance
- on the specifications on the spare parts to be N/A
used, when these affect the health and safety of
the operator
- on airborne noise emissions, determined and declared in accordance with the ----
Annex ZAB, which includes: (EN 60335-2-40/A13)
- the A-weighted emission sound pressure N/A
level at workstations, where this exceeds
70 dB(A) ......................................................... ;
(EN 60335-2-40/A13)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 149 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

- where this level does not exceed 70 dB(A), N/A


no value needs to be given, but the instructions
shall state that the A-weighted sound pressure
level is below 70 dB. (EN 60335-2-40/A13)
- the peak C-weighted instantaneous sound N/A
pressure value at workstations, where this
exceeds 63 Pa (130 dB in relation to 20 μPa)
:
- the A-weighted sound power level emitted by N/A
the machinery, where the A-weighted emission
sound pressure level at workstations exceeds
80 dB(A) ......................................................... :
7.12.ZE2 The instructions includes a warning to disconnect N/A
the appliance from its power source during service
and when replacing parts
If the removal of the plug is foreseen, it is clearly N/A
indicated that the removal of the plug has to be
such that an operator can check from any of the
points to which he has access that the plug remains
removed
If this is not possible, due to the construction of the N/A
appliance or its installation, a disconnection with a
locking system in the isolated position is provided
19.11.4.8 The appliance continues to operate, without N/A
causing any hazard to the user, from the same
point in its operating cycle at which the voltage
fluctuation occurred, or
a manual operation is required to restart it N/A
20.1 Appliances and their components and fittings have N/A
adequate mechanical stability during transportation,
assembly, dismantling and any other action
involving the appliance
20.2 Dangerous moving transmission parts safeguarded N/A
either by design or guards
When guards are used, they are fixed guards, N/A
interlocking movable guards or protective devices
Moving parts directly involved in the function of the appliance which cannot be ----
made completely inaccessible fitted with:
- fixed guards or interlocking movable guards N/A
preventing access to those sections of the parts
that are not used in the work, and
- adjustable guards restricting access to those N/A
sections of the moving parts where access is
necessary
Interlocking movable guards used where frequent N/A
access is required

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 150 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

21.1 Appliances and their components and fittings have N/A


adequate mechanical strength and is constructed to
withstand such rough handling that may be
expected in normal use, during transportation,
assembly, dismantling, scrapping and any other
action involving the appliance
22.ZE.1 For appliances provided with a seat, the seat gives N/A
adequate stability
The distance between the seat and the control N/A
devices capable of being adapted to the operator
22.ZE.2 For appliances provided with separate devices for N/A
the start and the stop functions, the stop function is
unambiguously identifiable and does always
override the start function
For appliances provided with one device performing N/A
the start and the stop function, the stop function is
unambiguously identifiable and does always
override the start function
22.ZE.3 Appliances designed in such a way that incorrect N/A
mounting is avoided, if this can lead to an unsafe
situation
If this is not possible, information on the correct N/A
mounting is given directly on the part and/or the
enclosure
22.ZE.4 Where the weight, size or shape prevents N/A
appliances from being moved manually, they are
fitted with attachments for lifting gear, or
so designed that they can be fitted with such N/A
attachments, or
be shaped in such a way that standard lifting gear N/A
can easily be used
Appliances to be moved manually are constructed N/A
or equipped so that they can be moved easily and
safely
22.ZE.5 The fixing systems of fixed guards which prevent N/A
access to dangerous moving transmission parts
only removable with the use of tools
If such guards have to be removed by the user for N/A
routine cleaning or maintenance their fixing
systems remain attached to the fixed guards or to
the machine after removal
Where possible, guards are incapable of remaining N/A
in place without their fixings
This does not apply if, after removal of the screws, N/A
or if the component is incorrectly repositioned, the
appliance becomes inoperative

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 151 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Movable guards are interlocked N/A


The interlocking devices prevent the start of N/A
hazardous appliance functions until the guards are
fixed in their position, and give a stop command
whenever they are no longer closed
Where it is possible for an operator to reach the danger zone before the risk due to ----
hazardous appliance functions has ceased, movable guards associated with a
guard locking device in addition to an interlocking device that:
- prevents the start of hazardous appliance N/A
functions until the guard is closed and locked, and
- keeps the guard closed and locked until the risk of N/A
injury from the hazardous appliance functions has
ceased
Interlocking movable guards remain attached to the N/A
appliance when open, and
they are designed and constructed in such a way N/A
that they can be adjusted only by means of an
intentional action
22.ZE.6 Interlocking movable guards designed in such a N/A
way that the absence or failure of one of their
components prevents starting or stops the
hazardous appliance functions
The guard is opened at the extent needed to cause N/A
the interlocking to operate and is then closed. This
operation is carried out for 5 000 cycles at a rate of
5 cycles per min. (EN 60335-2-40/A13/AC)
After this test any defect that may be expected in N/A
normal use is applied to the interlock system,
including interruption of the supply, only one defect
being simulated at a time
After these tests the interlock system is fit for N/A
further use
22.ZE.7 Adjustable guards restricting access to areas of the moving parts strictly necessary ----
for the work are:
- adjustable manually or automatically, depending N/A
on the type of work involved, and
- readily adjustable without the use of tools N/A
22.ZE.8 In case of interruption, re-establishment after an N/A
interruption or fluctuation in whatever manner of the
power supply, the appliance does not restart
However, automatic restarting of the operation is N/A
allowed if the appliance may continue to operate,
without causing any hazard to the user, from the
same point in its operating cycle at which the
voltage interruption or fluctuation occurred

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 152 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

22.ZE.9 Appliances fitted with means to isolate them from N/A


all energy sources
Such isolators are clearly identified, and N/A
they are capable of being locked if reconnection N/A
endanger persons
After the energy source is disconnected, it is N/A
possible to dissipate any energy remaining or
stored in the circuits of the appliance without risk to
persons

ZF ANNEX ZF (INFORMATIVE) ----


CRITERIA APPLIED FOR THE ALLOCATION OF PRODUCTS COVERED BY
STANDARDS IN THE EN 60335 SERIES UNDER LVD OR MD
List of standards under CENELEC/TC61 with the LVD P
allocation under the LVD (Low Voltage Directive) or
the MD (Machinery Directive) ............................... :

ZG ANNEX ZG (NORMATIVE) ----


UV APPLIANCES
The following modifications to this standard apply to N/A
appliances having UV emitters
This annex is not applicable to appliances covered N/A
by the scopes of IEC 60335-2-27, IEC 60335-2-59
or IEC 60335-2-109
7.12.ZG The instructions for appliances incorporating UVC N/A
emitters include the substance of the following:
WARNING — This appliance contains a UV
emitter. Do not stare at the light source
32 For appliances incorporating UV emitters the N/A
manufacturer delivers a declaration providing
evidence that the plastic material exposed to the
radiation is UV resistant

ZZ ANNEX ZZ (INFORMATIVE) ----


COVERAGE OF ESSENTIAL REQUIREMENTS OF EC DIRECTIVES
Description of the relation between this European Low Voltage Directive P
standard and the LVD (Low Voltage Directive, 2014/35/EU
2006/95/EC) and the MD (Machinery Directive,
2006/42/EC)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 153 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

ZAA ANNEX ZAA (INFORMATIVE) (EN 60335-2-40/A11) ----


THE RELEVENCE OF THE PRESSURE EQUIPMENT DIRECTIVE
Refrigerating systems having a pressure greater P
than 0,05 MPa are considered to be assemblies
falling within the scope of the Pressure Equipment
Directive, 97/23/EC. However, according to
Article 1, item 3.6 of the directive, equipment
classified no higher than category I and covered by
the low voltage directive is excluded from its scope.
(EN 60335-2-40/A11)
According to guideline 1/39 of the directive, this P
exclusion applies to both components and
assemblies (refrigerant circuits). This applies to
appliances containing vessels (e.g. compressors,
receivers) or piping with limits in accordance with
the following (EN 60335-2-40/A11):
Vessels (EN 60335-2-40/A11) ----
- dangerous refrigerants (Annex II, Table 1) (EN 60335-2-40/A11): ----
- volume not exceeding 1 l, or N/A
(EN 60335-2-40/A11)
- pressure x volume not exceeding 5 MPa l P
(EN 60335-2-40/A11)
- non-dangerous refrigerants (Annex II, Table 2) (EN 60335-2-40/A11): ----
- volume not exceeding 1 l, or N/A
(EN 60335-2-40/A11)
- pressure x volume not exceeding 20 MPa l N/A
(EN 60335-2-40/A11)
Piping (EN 60335-2-40/A11) ----
- dangerous refrigerants (Annex II, Table 6) (EN 60335-2-40/A11): ----
- numerical designation not exceeding 25, or N/A
(EN 60335-2-40/A11)
- pressure not exceeding 1 MPa and numerical N/A
designation not exceeding 100, or
(EN 60335-2-40/A11)
- pressure exceeding 1 MPa and pressure x P
numerical designation not exceeding 100 MPa
(EN 60335-2-40/A11).
- non-dangerous refrigerants (Annex II, Table 7) (EN 60335-2-40/A11): ----
- numerical designation not exceeding 100, or N/A
(EN 60335-2-40/A11)
- pressure x numerical designation not exceeding N/A
350 MPa (EN 60335-2-40/A11).
For other components, the most onerous limit of the P
two applies (EN 60335-2-40/A11)
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 154 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

The volume is the internal volume of the vessel and N/A


includes the volume of pipework up to the first
connection. It excludes the volume of fixed internal
parts (EN 60335-2-40/A11)
The pressure is the maximum pressure the vessel N/A
or piping system is exposed to, as specified by the
manufacturer of the appliance
(EN 60335-2-40/A11)
The numerical designation designates the size N/A
common to all components in the piping system
(EN 60335-2-40/A11)
If any component exceeds the limits given above, N/A
the appliance has to comply with the directive. The
technical requirements are given in Annex I and the
conformity assessment tables and procedures in
Annexes II and III of the directive
(EN 60335-2-40/A11)
Commonly used dangerous refrigerants, identified N/A
as Group 1 in the directive, are listed in table ZAA.1
(EN 60335-2-40/A11)
Commonly used non-dangerous refrigerants, N/A
identified as Group 2 in the directive, are listed in
table ZAA.2 (EN 60335-2-40/A11)
ZAB ANNEX ZAA (NORMATIVE) (EN 60335-2-40/A13) ----
EMISSION OF ACOUSTICAL NOISE FROM APPLIANCES COVERED BY
ANNEX ZE
ZAB.1 Noise reduction is an integral part of the design N/A
process and achieved by particularly applying
measures at source to control noise, see for
example EN ISO 11688-1. (EN 60335-2-40/A13)
Success of the applied noise reduction measures is N/A
assessed on the basis of the actual noise emission
values in relation to other machines of the same
type with comparable non-acoustical technical data.
(EN 60335-2-40/A13)
ZAB.2.1 A-weighted emission sound pressure level N/A
determined in accordance with EN 11203:2009,
6.2.3 d) with the surface S being the measurement
surface used for the sound power level
determination. (EN 60335-2-40/A13)
If the sound power level determination is based on N/A
a measurement method requiring a reverberant
sound field, the surface S to define Q, shall be a
parallelepiped measurement surface at a distance
of 1 m from the reference box enclosing the source
and assuming only one reflecting surface.
(EN 60335-2-40/A13)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 155 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

ZAB.2.2 A-weighted sound power level determined in N/A


accordance with EN 12102 applying a
measurement method of at least grade 2.
(EN 60335-2-40/A13)
If a grade 3 measurement method used for N/A
determining the A-weighted sound power level, the.
reasons are explicitly mentioned
(EN 60335-2-40/A13)
ZAB.2.3 Total measurement uncertainty is depending on the N/A
standard deviation of reproducibility σR0 of the
measurement method and the standard deviation
σomc representing the instability of the operating and
mounting conditions. (EN 60335-2-40/A13)
σR0 has an upper value for a grade 2 measurement N/A
method of about 1,5 dB, whereas σomc may have
values between 0,5 dB for small variations of the
sound power due on the mounting and operating
conditions or 4 dB for very instable sources
(EN 60335-2-40/A13)
Total measurement uncertainty for the A-weighted N/A
emission sound pressure level is of the same order
as the one for the respective sound power level
measurement. (EN 60335-2-40/A13)
ZAB.2.4 Information to be recorded covers all the technical N/A
requirements of this noise test code.
(EN 60335-2-40/A13)
Any deviations from this noise test code or from the N/A
basic standards upon which it is based are to be
recorded together with the technical justification for
such deviations. (EN 60335-2-40/A13)
ZAB.2.5 Information to be given in the test report includes : N/A
(EN 60335-2-40/A13)
- he data required by the manufacturer for inclusion N/A
in the noise declaration,. (EN 60335-2-40/A13)
- the data required by the user to verify the declared N/A
values. (EN 60335-2-40/A13)
Thus the following information shall be included .. : N/A
(EN 60335-2-40/A13)
- reference to the noise test code and the basic N/A
noise emission standards used;
(EN 60335-2-40/A13)
- description of the installation and operation N/A
conditions used; (EN 60335-2-40/A13)
- location of the work station(s) and other specified N/A
positions; (EN 60335-2-40/A13)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 156 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

- the noise emission values obtained N/A


(EN 60335-2-40/A13)
Test report states that all requirements of the noise N/A
test code have been fulfilled, or, if this is not the
case, it shall identify any unfulfilled requirements.
(EN 60335-2-40/A13)
Deviations from the requirements stated and a N/A
technical justification for these deviations shall be
given. (EN 60335-2-40/A13)
ZAB.2.6 Noise emission declaration is made according to N/A
EN ISO 4871 (EN 60335-2-40/A13)
Emission sound pressure level LpA is made as a N/A
dual number noise emission declaration, thus
declaring the determined value for LpA and the
respective uncertainty KpA. (EN 60335-2-40/A13)
Sound power level LWA is declared as single N/A
number noise emission declaration declaring the
sum of the measured sound power level and its
uncertainty KWA. (EN 60335-2-40/A13)
Noise declaration states that the noise emission N/A
values have been obtained according to this noise
test code. (EN 60335-2-40/A13)
Any deviations from this noise test code or from the N/A
basic standards upon which it is based are clearly
indicated. (EN 60335-2-40/A13)
Additional noise emission values are given in the N/A
declaration. (EN 60335-2-40/A13)
If undertaken, verification of the noise emission N/A
values shall be conducted according to
EN ISO 4871, using the same mounting and
operating conditions as those used for the initial
determination. (EN 60335-2-40/A13)

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 157 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Appendix

Variations to EN 60335-1:2012/A13:2017
ZZA ANNEX ZZA (INFORMATIVE) ----
REALATIONSHIP BETWEEN THIS EUROPEAN STANDARD AND THE SAFETY
OBJECTIVES OF DIRECTIVE 2014/35/EU [2014 OJ L96] AIMED TO BE
COVERED
Description relating to harmonized standards in the P
field of the Low Voltage Directive, M/511, to provide
one voluntary means of conforming to safety
objectives of Directive 2014/35/EU of the European
Parliament and of the Council of 26 February 2014
on the harmonization of the laws of the Member
States relating to the making available on the
market of electrical equipment designed for use
within certain voltage limits [2014 OJ L96]
A table with correspondence between this P
European standard and Annex I of Directive
2014/35/EU [2014 OJ L96]
ZZB ANNEX ZZB (INFORMATIVE) ----
REALATIONSHIP BETWEEN THIS EUROPEAN STANDARD AND THE
ESSENTIAL REQUIREMENTS OF DIRECTIVE 2006/42/EC AIMED TO BE
COVERED
Description relating to Mandate for standardisation N/A
in the field of machinery “M/396” to provide one
voluntary means of conforming to essential
requirements of EU Directive 2006/42/EC
A table with correspondence between this N/A
European standard and Annex I of Directive
2006/42/E [OJ No L 157]

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 158 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Appendix

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
5 GENERAL CONDITIONS FOR THE TESTS ----
5.17 Modification: N/A
Appliances powered by rechargeable batteries that
are recharged in the appliance are tested in
accordance with Annex B.
Addition: N/A
Battery-operated appliances powered by
batteries that are non-rechargeable or not
recharged in the appliance are tested in
accordance with Annex S.
7 MARKING AND INSTRUCTIONS ----
7.1 Addition: N/A
Class II appliances and class III appliances
incorporating a functional earth shall be marked
with the symbol IEC 60417-5018 (2011-07).
7.4 Modification: N/A
Appliances adjustable for different rated voltages or
rated frequencies, the voltage or the frequency
setting is clearly discernible
Modification: N/A
Requirement met if frequent changes are not
required and the rated voltage or rated frequency to
which the appliance is to be adjusted is determined
from a wiring diagram
7.8 Except for type Z attachment, terminals for connection to the supply mains ----
indicated as follows:
Addition: N/A
- functional earthing terminals shall be indicated by
symbol IEC 60417-5018 (2011-07).
7.12 Modification: P
“Instructions for use…”. Delete for use
Addition: N/A
For appliances intended for use at altitudes
exceeding 2 000 m, the maximum altitude of use
shall be stated.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 159 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
Addition: ----
The instructions for appliances incorporating a functional earth shall state the
substance of the following:
Addition: N/A
This appliance incorporates an earth connection for
functional purposes only.
7.12.1 Addition: N/A
For appliances marked with different rated
voltages or different rated frequencies (separated
by a /), instructions shall be included to indicate to
the user or installer what action must be taken to
adjust the appliance for operation at the required
rated voltage or rated frequency.
7.15 Addition: N/A
The symbol IEC 60417-5018 (2011-07) shall be
placed next to the symbol IEC 60417-5172 (2003-
02) or the symbol IEC 60417-5180 (2003-02) as
appropriate.
10 POWER INPUT AND CURRENT ----
10.1 Modification: N/A
If the power input varies throughout the operating
cycle and the maximum value of the power input
exceeds, by a factor greater than two, the
arithmetic mean value of the power input occurring
during a representative period, then the power input
is the maximum value that is exceeded for more
than 10 % of the representative period. Otherwise
the power input is taken as the arithmetic mean
value.
10.2 Modification: N/A
If the current varies throughout the operating cycle
and the maximum value of the current exceeds, by
a factor greater than two, the arithmetic mean value
of the current occurring during a representative
period, then the current is the maximum value that
is exceeded for more than 10 % of the
representative period. Otherwise the current is
taken as the arithmetic mean value.
11 HEATING ----
11.8 Modification: P
“Table 3 - Maximum normal temperature rises” to
be taken into account

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 160 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
13 LEAKAGE CURRENT AND ELECTRIC STRENGTH AT OPERATING ----
TEMPERATURE
13.2 For class 0 appliances, class II appliances, P
class II constructions and class III appliances,
the leakage current is measured by means of the
circuit described in Figure 4 of IEC 60990
Modification: N/A
For class 0I appliances and class I appliances, a
low impedance ammeter responding to the rated
frequency of the appliance may be used
19 ABNORMAL OPERATION ----
19.7 Addition: N/A
If the timer or programmer is an electronic type that
operates to ensure compliance with the test before
the maximum period under the conditions of Clause
11 is reached, it is considered to be a protective
electronic circuit as well as a control that operates
under the conditions of Clause 11.
22 CONSTRUCTION ----
22.5 Addition: N/A
If compliance relies on the operation of an
electronic circuit, the electromagnetic phenomena
tests of 19.11.4.3 and 19.11.4.4 are applied one at
a time to the appliance.
Addition: N/A
The discharge test is then repeated three times and
for each test, the voltage shall not exceed 34 V.
22.32 Modification: N/A
Ceramic and similar porous material in which
heating conductors are embedded is considered to
be basic insulation, not reinforced insulation
22.33 Modification: P
Conductive liquids that are or may become
accessible in normal use and conductive liquids
that are in contact with unearthed accessible
metal parts shall not be in direct contact with live
parts or unearthed metal parts that are separated
from live parts by basic insulation only.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 161 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
22.53 Addition: N/A
Class II appliances and class III appliances that
incorporate functionally earthed parts shall have at
least double insulation or reinforced insulation
between live parts and the functionally earthed
parts.
22.54 Addition: N/A
Button cells and batteries designated R1 shall not
be accessible without the aid of a tool unless the
cover of their compartment can only be opened
after at least two independent movements have
been applied simultaneously.
23 INTERNAL WIRING ----
23.5 Addition: N/A
For class II construction, the requirements for
supplementary insulation and reinforced
insulation apply except that the sheath of a cord
complying with IEC 60227 or IEC 60245 may
provide supplementary insulation.
A single layer of internal wiring insulation does not P
provide reinforced insulation.
24 COMPONENTS ----
24.1 Addition: P
Compliance with the IEC standard for the relevant
component does not necessarily ensure
compliance with the requirements of this standard.
Addition: P
Motors are not required to comply with IEC 60034-
1. They are tested as part of the appliance
according to this standard.
Addition: P
Relays shall be tested as part of the appliance
according to this standard. They may be
alternatively tested to IEC 60730-1, in which case
they must also meet the additional requirements in
IEC 60335-1.
Addition: P
Unless otherwise specified, the requirements of
Clause 29 of this standard apply between live
parts of components and accessible parts of the
appliance.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 162 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
Addition: P
Unless otherwise specified, components may
comply with the requirements for clearances and
creepage distances for functional insulation as
specified in the relevant component standard.
Addition: P
Unless otherwise specified, the requirements of
30.2 of this standard apply to parts of non-metallic
material in components including parts of non-
metallic material supporting current-carrying
connections inside components.
Addition: P
Components that have not been previously tested
and shown to comply with the IEC standard for the
relevant component are tested according to the
requirements of 30.2 of this standard.
Addition: N/A
Power electronic converter circuits are not required
to comply with IEC 62477-1. They are tested as
part of the appliance according to this standard.
24.1.2 Addition: P
The relevant standard for transformers in
associated switch mode power supplies is Annex
BB of IEC 61558-2-16.
Addition: P
Clause 26 of IEC 61558-1 and Annex H of IEC
61558-1 are not applicable.
24.1.4 Addition: N/A
Thermal cut-outs of the capillary type shall comply
with the requirements for type 2.K controls in IEC
60730-2-9.
24.1.5 Modification: N/A
However, for class II appliances classified higher
than IPX0, the appliance couplers complying with
IEC 60320-2-3
25 SUPPLY CONNECTION AND EXTERNAL FLEXIBLE CORDS ----
25.1 Appliance not intended for permanent connection to fixed wiring, means for ----
connection to the supply:

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 163 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
Modification: P
- supply cord fitted with a plug, the current rating
and voltage rating of the plug being not less than
the corresponding ratings of its associated
appliance;
25.7 Supply cords, other than for class III appliances, being one of the following types: ----
Deleting: N/A
- cross-linked polyvinyl chloride sheathed (at least
60245 IEC 88)
25.10 Addition: N/A
In multi-phase appliances, the colour of the neutral
conductor of the supply cord, if any, shall be blue.
25.20 Modification: P
The conductors of the supply cord for type Y and Z
attachment shall be from accessible metal parts
27 PROVISION FOR EARTHING ----
27.1 Addition: N/A
Class II appliances and class III appliances may
incorporate an earth for functional purposes.
27.2 Addition: N/A
These requirements are not applicable to class II
appliances and class III appliances that
incorporate an earth for functional purposes.
27.3 Addition: N/A
These requirements are not applicable to class II
appliances and class III appliances that
incorporate an earth for functional purposes.
27.4 Addition: N/A
These requirements are not applicable to class II
appliances and class III appliances that
incorporate an earth for functional purposes.
27.5 Addition: N/A
These requirements are not applicable to class II
appliances and class III appliances that
incorporate an earth for functional purposes.
Addition: P
The test is carried out until steady conditions have
been established.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 164 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
Addition: P
The resistance of the supply cord is not included
in the resistance calculation.
27.6 Addition: N/A
This requirement is not applicable to class II
appliances and class III appliances that
incorporate an earth for functional purposes.
29 CLEARANCES, CREEPAGE DISTANCES AND SOLID INSULATION ----
29.1 Addition: N/A
For appliances intended for use at altitudes
exceeding 2 000 m, the clearances in Table 16
shall be increased according to the relevant
multiplier values in Table A.2 of IEC 60664-1.
Impulse voltage test is not applicable: ----
Addition: N/A
- for basic insulation of class 0 and class 01
appliances or to appliances intended for use at
altitudes exceeding 2 000 m.
29.3 Compliance checked: ----
Modification: N/A
- for insulation, other than single layer internal
wiring insulation, by an assessment of the thermal
quality of the material combined with an electric
strength test, in accordance with 29.3.3, and
Addition: N/A
- by an assessment of the thermal quality of the
material according to 29.3.3 combined with an
electric strength test in accordance with 23.5, for
each single layer internal wiring insulation touching
each other, or
B Modification: ----
ANNEX B (NORMATIVE)
APPLIANCES POWERED BY RECHARGEABLE BATTERIES THAT ARE
RECHARGED IN THE APPLIANCE
Addition: N/A
These appliances take one of the following three forms of construction:

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 165 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
Addition: N/A
a) The appliance can be supplied directly from the
supply mains or a renewable energy source such
as a solar cell, the battery charging circuitry and
other supply unit circuitry being incorporated within
the appliance.
Addition: N/A
b) The part of the appliance incorporating the
battery is supplied from the supply mains or a
renewable energy source such as a solar cell, via a
detachable supply unit. The battery charging
circuitry is incorporated within the part of the
appliance containing the battery. In this case, the
complete appliance is the detachable supply unit
plus the part of the appliance containing the battery
and the battery charging circuitry.
Addition: N/A
c) The part of the appliance incorporating the
battery is supplied from the supply mains or a
renewable energy source such as a solar cell, via a
detachable supply unit. The battery charging
circuitry is incorporated within the detachable
supply unit. In this case, the complete appliance is
the detachable supply unit with the battery charging
circuitry plus the part of the appliance containing
the battery.
7.1 Addition: N/A
Appliances intending to be supplied from a
detachable supply unit for the purposes of
recharging the battery shall be marked with symbol
IEC 60417-6181 (2013-03) and its type reference
along with symbol ISO 7000-0790 (2004-01) or with
the substance of the following:
Addition: N/A
Use only with <model designation> supply unit
7.6 Addition: N/A
Symbols 60417-6181
7.12 Addition: N/A
For appliances intending to be supplied from a
detachable supply unit for the purposes of
recharging the battery, the type reference of the
detachable supply unit shall be stated along with
the substance of the following:

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 166 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
Addition: N/A
WARNING: For the purposes of recharging the
battery, only use the detachable supply unit
provided with this appliance.
Addition: N/A
If the symbol for detachable supply unit is used,
its meaning shall be explained.
7.15 Addition: N/A
The type reference of the detachable supply unit
shall be placed in close proximity to the symbol.
11.8 Addition: N/A
The temperature rise of the battery surface shall
not exceed the temperature rise limit in the battery
manufacturer’s specification for the type of battery
supplied.
Addition: N/A
If no limit is specified, the temperature rise shall not
exceed 20 K.
19.13 Addition: N/A
The battery shall not rupture or ignite.
H ANNEX H (NORMATIVE) ----
SWITCHES
20 Clearances, creepage distances, solid insulation and coatings of rigid printed board ----
assemblies
Modification: N/A
Clause 20 is applicable to clearances across full
disconnection and micro-disconnection.
Modification: N/A
It is also applicable to creepage distances for
functional insulation, across full disconnection and
micro-disconnection, as stated in Table 24.
S Addition: ----
ANNEX S (NORMATIVE)
BATTERY-OPERATED APPLIANCES POWERED BY BATTERIES THAT ARE
NON-RECHARGEABLE OR NOT RECHARGED IN THE APPLIANCE
The following modifications to this standard are N/A
applicable for battery-operated appliances where
the batteries are either non-rechargeable (primary
batteries) or rechargeable batteries (secondary
batteries) that are not recharged in the appliance.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 167 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
5 General condition for the tests ----
5.8.1 Where the supply terminals for the connection of N/A
the battery have no indication of polarity, the more
unfavourable polarity shall be applied.
5.S.101 Battery-operated appliances intended for use N/A
with a battery box are tested with the battery box
supplied with the appliance or with the battery box
recommended in the instructions.
5.S.102 Battery-operated appliances are tested as N/A
motor-operated appliances.
7 Marking and instructions ----
7.1 Battery-operated appliances shall be marked with N/A
the battery voltage and the polarity of the terminals
unless the polarity is irrelevant.
Battery-operated appliances shall also be marked N/A
with the
- name, trade mark or identification mark of the N/A
manufacturer or responsible vendor;
- model or type reference; N/A
- IP number according to degree of protection N/A
against ingress of water, other than IPX0;
- type reference of battery or batteries. N/A
If relevant, the positive terminal shall be indicated N/A
by the symbol IEC 60417-5005 (2002-10) and the
negative terminal by the symbol IEC 60417-5006
(2002-10).
If appliances use more than one battery, they shall N/A
be marked to indicate correct polarity connection of
the batteries.
7.6 Symbols 60417-5005 and Symbols 60417-5006 N/A
7.12 The instructions for battery-operated appliances shall contain the substance of ----
the following, as applicable:
- the types of batteries that may be used; N/A
- how to remove and insert the batteries; N/A
- non-rechargeable batteries are not to be N/A
recharged;
- rechargeable batteries are to be removed from the N/A
appliance before being charged;
- different types of batteries or new and used N/A
batteries are not to be mixed;

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 168 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
- batteries are to be inserted with the correct N/A
polarity;
- exhausted batteries are to be removed from the N/A
appliance and safely disposed of;
- if the appliance is to be stored unused for a long N/A
period, the batteries should be removed;
- the supply terminals are not to be short-circuited. N/A
11 Heating ----
11.5 By means of an external power supply, battery-operated appliances are supplied ----
at the terminals for the connection of the battery with the most unfavourable supply
voltage between
- 0,55 and 1,0 times the battery voltage, if the N/A
appliance can be used with non-rechargeable
batteries;
- 0,75 and 1,0 times battery voltage, if the N/A
appliance is designed for use with rechargeable
batteries only.
The values specified in Table S.101 for the internal N/A
resistance per cell of the battery shall be taken into
account.
19 Abnormal operation: ----
19.1 For battery-operated appliances, the tests are N/A
carried out with the battery fully charged unless
otherwise specified.
19.13 The battery shall not rupture or ignite. N/A
19.S.101 Battery-operated appliances are supplied with the N/A
voltage specified in 11.5. The supply terminals
having an indication of polarity are connected to the
opposite polarity, unless such a connection is
unlikely to occur due to the construction of the
appliance.
19.S.102 For battery-operated appliances with provision for N/A
multiple batteries, one or more of the batteries shall
be reversed and the appliance shall be operated, if
reversal of batteries is allowed by the construction.
25 Supply connection and external flexible cords ----
25.5 The flexible leads or flexible cord used to connect N/A
an external battery or battery box in battery-
operated appliances shall be connected to the
appliance by a type X attachment.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 169 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

A1:2013 to IEC 60335-1:2010


Clause Requirement – Test Result – Remark Verdict
25.13 This requirement is not applicable to the flexible N/A
leads or flexible cord connecting external batteries
or a battery box with an appliance.
25.S.101 Battery-operated appliances shall have suitable N/A
means for connection of the battery.
If the type of battery is marked on the appliance, N/A
the means of connection shall be suitable for this
type of battery.
26 Terminal for external conductors ----
26.5 Terminal devices in an appliance for the connection N/A
of the flexible leads or flexible cord connecting an
external battery or battery box shall be so located
or shielded that there is no risk of accidental
connection between supply terminals.
30 Resistance to heat and fire N/A
30.2.3.2 Addition: N/A
There shall be no battery in the area of the vertical
cylinder used for the consequential needle flame
test unless the battery is shielded by a barrier that
meets the needle flame test of Annex E or that
comprises material classified as V-0 or V-1
according to IEC 60695-11-10 provided that the
test sample used for the classification was no
thicker than the relevant part of the appliance.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 170 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

AMENDMENT 2: 2016 TO IEC 60335-1:2010

Clause Requirement – Test Result – Remark Verdict


5 GENERAL CONDITIONS FOR THE TESTS —
5.10 Addition: N/A
A class III construction part of the appliance is
tested connected to its detachable power supply
part taking into account the instructions provided
with the appliance.
6 CLASSIFICATION —
6.1 Addition: N/A
For a class III construction with a detachable
power supply part the appliance is classified
according to the detachable power supply part
7 MARKING AND INSTRUCTIONS —
7.1 Symbol IEC 60417-5180, for class III appliances, N/A
unless
the appliance is operated by batteries only, or N/A
for appliances powered by rechargeable batteries N/A
recharged in the appliance
7.12.9 Instructions specified in 7.12 and from 7.12.1 to P
7.12.8 appear together before any other
instructions supplied with the appliance
These instructions may be supplied with the P
appliance separately from any functional use
booklet
They may follow the description of the appliance P
that identifies parts, or follow the
drawings/sketches
In addition, instructions are also available in an P
alternative format such as on a website or on
request from the user in a format such as a DVD
7.14 Markings clearly legible and durable: —
Signal words WARNING, CAUTION, DANGER in P
uppercase having a height as specified ..... .. :
Uppercase letter of the text explaining the signal P
word not smaller than 1,6 mm ................... ......... :
Moulded in, engraved, or stamped markings either N/A
raised above or have a depth below the surface of
at least 0,25 mm, unless
contrasting colours are used N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 171 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Clause Requirement – Test Result – Remark Verdict


Markings checked by inspection, measurement P
and rubbing test as specified
8 PROTECTION AGAINST ACCESS TO LIVE PARTS --
8.1.3 For appliances other than class II, use of test N/A
probe 41 of IEC 61032, with a force not exceeding
1 N: no contact with live parts of visible glowing
heating elements or supporting parts
For a single switching action obtained by a N/A
switching device, requirements as specified
For appliances with a supply cord and without a N/A
switching device, the single switching action may
be obtained by the withdrawal of the plug
13 LEAKAGE CURRENT AND ELECTRIC STRENGTH AT OPERATING --
TEMPERATURE
13.2 The leakage current is measured by means of the P
circuit described in figure 4 of IEC 60990 :1999
For class 0I appliances and class I appliances, N/A
except parts of class II construction, C may be
replaced by a low impedance ammeter
19 ABNORMAL OPERATION —
19.1 If the control performs more than one function, only N/A
that aspect of the control under consideration is
rendered inoperative. Other functions of the control
may continue to operate normally.
19.7 the capacitor is of class S2 or S3 of IEC 60252-1 P
19.11.3 If the appliance incorporates a protective electronic N/A
circuit that operates to ensure compliance with
clause 19, the appliance is tested as specified
19.11.4.2 The appliance is subjected to radiated fields in N/A
accordance with IEC 61000-4-3, at frequency
ranges specified
22 CONSTRUCTION --
22.5 No risk of electric shock when touching pins, for P
appliances having a capacitor with rated
capacitance equal to or greater than 0,1F, the
appliance being disconnected from the supply at
the instant of voltage peak
22.12 Handles, knobs etc. fixed in a reliable manner , if P
loosening result in a hazard
Removing or Fixing in wrong position of handles, P
knobs etc. indicating position of switches or similar
components not possible , if resulting in a hazard

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 172 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Clause Requirement – Test Result – Remark Verdict


A choking hazard does not apply to appliances for N/A
commercial use
If the part is removed and can be contained within N/A
the small parts cylinder, it is considered to be a
choking hazard
22.55 Devices operated to stop the intended function of P
the appliance, if any, are be distinguished from
other manual devices by means of shape, size,
surface texture or position ................................... :
The requirement concerning position does not P
preclude use of a push on push off switch
An indication when the device has been operated is given by: —
– tactile feedback from the actuator or from the P
appliance, or
– reduction in heat output; or N/A
– audible and visible feedback P
22.56 Detachable power supply part provided with the N/A
part of class III construction
22.57 The properties of non-metallic materials do not N/A
degrade from exposure to UV-C radiation, as
specified in Annex T
This requirement does not apply to glass, ceramics N/A
or similar materials
24 COMPONENTS --
24.2 Appliances not fitted with: --
- switches, automatic controls or power supplies in P
flexible cords
24.8 - the capacitors are of class S2 or S3 according to P
IEC 60252-1
25 SUPPLY CONNECTION AND EXTERNAL FLEXIBLE CORDS —
25.7 - halogen-free, low smoke, thermoplastic insulated and sheathed —
• light duty halogen-free low smoke flexible N/A
cable (62821 IEC 101) for circular cable
and (62821 IEC 101f) for flat cable
• Ordinary duty halogen-free low smoke N/A
flexible cable (62821 IEC 102) for circular
cable and (62821 IEC 102f( for flat cable
25.10 Where additional neutral conductors are provided N/A
in the supply cord:
– other colours may be used for these additional N/A
neutral conductors;
TRF No. IEC60335_2_40J
Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 173 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Clause Requirement – Test Result – Remark Verdict


– all of the neutral conductors and line conductors N/A
are identified by marking using the alpha numeric
notation specified in IEC 60445
– the supply cord is fitted to the appliance N/A
25.23 - for class I or class II appliance with class III N/A
construction, the cross sectional areas of the
conductors need not comply with 25.8 if specified
conditions are met
B ANNEX B (NORMATIVE) —
APPLIANCES POWERED BY RECHARGEABLE BATTERIES THAT ARE
RECHARGED IN THE APPLIANCE
7.12 instructions for appliances incorporating batteries N/A
intended to be replaced by the user include
required information
Instructions for appliances containing non user- N/A
replaceable batteries state the substance of the
following:
This appliance contains batteries that are only N/A
replaceable by skilled persons
Instructions for appliances containing non-replaceable batteries shall state the N/A
substance of the following:
This appliance contains batteries that are non- N/A
replaceable
P ANNEX P (INFORMATIVE) --
GUIDANCE FOR THE APPLICATION OF THIS STANDARD TO APPLIANCES
USED IN TROPICAL CLIMATES
Modifications applicable for class 0 and 01 appliances having a rated voltage --
exceeding 150V, intended to be used in countries having a tropical climate and that
are marked with symbol IEC 60417-6332
Modifications may also be applied to class 1 appliances having a rated voltage --
exceeding 150V, intended to be used in countries having a tropical climate and that
are marked with symbol IEC 60417-6332, if liable to be connected to a supply
mains that excludes the protective earthing conductor
7.1 The appliance marked with symbol IEC 60417- N/A
6332
If symbol IEC 60417-6332 is used, its meaning N/A
is explained
T ANNEX T (NORMATIVE) --
UV-C RADIATION EFFECT ON NON-METALLIC MATERIALS
Requirements for non-metallic materials subject to N/A
direct or reflected UV-C radiation exposure and
whose mechanical and electrical properties are
relied upon for compliance with the

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 174 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Clause Requirement – Test Result – Remark Verdict


Does not apply to glass, ceramic and similar N/A
materials
Tested as specified in ISO 4892-1 and ISO 4892-2, with the following modifications: --
Modifications to ISO 4892-1: --
5.1.6 The UV-C emitter is a low pressure mercury lamp N/A
with a quartz envelope having a continuous
spectral irradiance of 10 W/m2 at 254 nm
Subclause 5.1.6.1 and Table 1 are not applicable N/A
5.2.4 The black-panel temperature shall be 63 °C +/- N/A
3 °C
5.3.1 Humidification of the chamber air is specified in N/A
part 2 when necessary
9 This clause is not applicable N/A
Modifications to ISO 4892-2: N/A
7.1 At least three test specimens are tested N/A
Ten samples of internal wiring is tested N/A
7.2 The specimens are attached to the specimen N/A
holders such that they are not subject to any stress
7.3 Apparatus prepared as specified N/A
The test specimens and, if used, the irradiance- N/A
measuring instrument are exposed for 1 000 h
7.4 If used, a radiometer is mounted and calibrated N/A
such that it measures the irradiance at the exposed
surface of the test specimen
7.5 Material properties and test methods for parts N/A
providing mechanical support or impact resistance
as specified in Table T.1
Material properties and test method for electrical N/A
insulation of internal wiring as specified in Table
T.2
8 This clause is not applicable N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 175 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Variations to EN 60335-1:2012/ A1:2019


11.8 In Table 3 delete footnotes za, zb, zc, zd. N/A
24.1 Components shall comply with the safety P
requirements specified in the relevant EN
standards as far as they reasonably apply.
Annex ZC Normative references to international publications P
with their corresponding European publications

Variations to EN 60335-1:2012/ A14:2019


7.10 Add: N/A
A push-push button switch used for start and stop
the operation shall not be used for other functions
such as changing the motor speed.
For hand-held appliances with rated power input N/A
50 W or lower it is acceptable to have a push-push
button for different functions including on / off if
there is an immediate feedback to the user e.g. by
tactile feedback or audible and visible feedback.
Audible feedback is any audible response got N/A
immediately after the operation of the switch. The
click of a switch can be accepted as an audible
feedback provided that it is originated inside the
switch that is operated and can be heard at a
distance of 77 cm from the switch. The sound of the
motor is regarded as an audible feedback.
Constructions with switches that have two different N/A
stable positions (meaning that it can be seen or felt
when they have been pressed or rotated) are
considered to have a tactile feedback.
8.1.1 Replace by P
Test probe B and probe 18 of EN 61032 are
applied with a force not exceeding 1 N, the
appliance being in every possible position, except
that appliances normally used on the floor and
having a mass exceeding 40 kg are not tilted.
8.1.3 Add the text “, test probe 18” after “test probe B,” P
20.2 replace Note 1: the word “movable” by “moving” P
and replace “main function” by “working function”.
22.12 Add: N/A
Other parts that are intended to be detached during
use, maintenance or cleaning (examples are
batteries, battery covers, lids, attachments, steam
nozzles) are not considered as parts providing a
similar function as handles, knobs, grips, levers.

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 176 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

22.17 Add: N/A


This is not applicable to built-in appliances.
24.1 Add: N/A
NOTE Z3 For details of plugs used in CENELEC
countries listed in IEC TR 60083 see Annex ZH.
25.1 Add: N/A
Plugs and pins for insertion into socket outlets shall
follow the relevant standards sheets in Annex ZH.
25.6 Delete the addition: N/A
Supply cords of single-phase portable appliances
having a rated current not exceeding 16 A shall be
fitted with a plug complying with the following
standard sheets of IEC/TR 60083.
for class I appliances standard sheet C2b, C3b
or C4;
for class II appliances standard sheet C5 or
C6.
25.25 Replace and add: N/A
Dimensions of the pins and engagement face of
plugs of appliances that are inserted into socket-
outlets are to be in accordance with the dimensions
of the relevant plug standard.
NOTE Z1 Common plugs and socket-outlets types
in CENELEC countries as shown in Annex ZH.
32 Delete in the third paragraph “EN 50366 or” N/A

TRF No. IEC60335_2_40J


Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD, Guangzhou,
Guangdong, China
Tel: (86-20) 8213 9688 Fax: (86-20) 32057538
Report No.: 180423126GZU-001
Page 177 of 177 Modification 12: November 10, 2020

IEC 60335-2-40
Clause Requirement + Test Result - Remark Verdict

Variations to EN 60335-1:2012/ A2:2019


7.10 Delete the paragraphs starting with “Devices used N/A
to start/stop….” until the end of the requirement
“……by vulnerable persons.”. This includes Notes
Z1 and Z2.
22.12 Delete Note Z1 N/A
Hazard includes ingestion or a choking hazard for
vulnerable people.
24.Z1 Replacement P
Type S2 and S3 capacitors according to EN 60252-
1 are not required to undergo the testing as
required by 30.2.2 and 30.2.3.1.
25.7 Delete the existing text starting “Halogen free N/A
thermoplastic……..” until ”……..designation H07ZZ-
F).

--- End of report ---