Foxboro DCS: Field Mounted Intelligent Enclosure
Foxboro DCS: Field Mounted Intelligent Enclosure
Foxboro DCS: Field Mounted Intelligent Enclosure
PSS 41H-2I20
Product Specification
March 2024
https://www.se.com
Legal Information
The information provided in this document contains general descriptions, technical
characteristics and/or recommendations related to products/solutions.
This document is not intended as a substitute for a detailed study or operational and
site-specific development or schematic plan. It is not to be used for determining
suitability or reliability of the products/solutions for specific user applications. It is the
duty of any such user to perform or have any professional expert of its choice
(integrator, specifier or the like) perform the appropriate and comprehensive risk
analysis, evaluation and testing of the products/solutions with respect to the relevant
specific application or use thereof.
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this document are the property of Schneider Electric SE or
its subsidiaries. All other brands may be trademarks of their respective owner.
This document and its content are protected under applicable copyright laws and
provided for informative use only. No part of this document may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the
document or its content, except for a non-exclusive and personal license to consult it
on an "as is" basis.
Schneider Electric reserves the right to make changes or updates with respect to or in
the content of this document or the format thereof, at any time without notice.
To the extent permitted by applicable law, no responsibility or liability is
assumed by Schneider Electric and its subsidiaries for any errors or omissions
in the informational content of this document, as well as any non-intended use
or misuse of the content thereof.
Overview Field Mounted Intelligent Enclosure
Overview
The EcoStruxure™ Foxboro™ DCS Field Mounted Intelligent Enclosure provides an
integrated solution designed to be mounted close to instruments in the field to reduce
cables. The Field Mounted Enclosure includes Universal Input/Output (UIO) modules,
power supplies, and Termination Assemblies (TAs) that are pre-installed and tested,
and can be connected to a wide range of field devices. The enclosure supports
Schneider Electric’s Flexible Lean Execution strategy, which shortens project
schedules and reduces the risk of startup delays.
The Field Mounted Intelligent Enclosure is designed to be mounted in the field, and
connects through redundant single mode fiber to the Field Control Processors located
in the Equipment Room Intelligent Enclosure. For more information, see Equipment
Room Intelligent Enclosure (PSS 41H-2I30).
The enclosure supports up to 64 standard Universal I/O channels in simplex,
redundant, or simplex and redundant combinations, and optionally accommodates
integration of third party PLCs using simplex or redundant Field Device System
Integration modules supporting Modbus TCP.
A second enclosure can be cascaded from the first enclosure using single mode fiber
or copper cable, saving on communication home run cable to the equipment room.
Field cables, communication cables, and power cables enter the enclosure through
cable glands or a multi-cable transit (optional) located at the bottom of the enclosure.
The channel-to-channel isolated Universal I/O Module supports DI, DO, AI, AO,
HART, NAMUR, Pulse, and 1 ms SOE signal types.
Field cables terminate directly on Termination Assemblies (TAs) with signal
conditioners for optional field signal processing. See Termination Assemblies and
Signal Conditioners, page 8.
Terminals are provided to terminate spare field cable cores and screens. This rugged,
unpainted SS316L stainless steel enclosure can be mounted in harsh environmental
and hazardous areas.
Features
• Protection against harsh environments and hazardous locations:
◦ NEMA® 4X/IP66 rated
◦ Class G3 (harsh) environment
◦ ATEX
• Universal I/O and TAs support any one of these options:
◦ 64 Simplex I/O
◦ 64 Redundant I/O
◦ 48 Simplex and 16 Redundant I/O
• Up to 16 Universal Standard I/O modules (8 x FBM247, 16 x FBM248, or
4 x FBM248 and 6 x FBM247) that support 64 simplex, redundant, or simplex and
redundant I/O Channels using TAs and signal conditioners
• Redundant Field Communication Modules (FCM2F10) for single mode fiber
communication to FCP280
• Up to two Field Device System Integrator Standard modules
(1 x or 2 x FBM232, 2 x FBM233) for Modbus TCP Communication
• Daisy chain from one enclosure to the next to reduce home run cables for
communication and power. Alternatively, the power output used to daisy chain an
enclosure can be used to provide power to a wireless field device access point
installed outside of the enclosure
• Up to two Fieldbus Isolator/Repeator modules for daisy chaining enclosures
using Copper (FBI200) or Fiber Optic cable (FCM2F10)
• 12-port fiber optic patch panel with ST connectors for terminating and distributing
fiber-optic cables for communication to the enclosure and wireless field device
access point
• Document pocket inside front door
• Door stoppers to help prevent the door from swinging or opening too widely
• 120 VAC, 230 VAC system supply
• Supports the Intelligent Commissioning Wizard, which significantly reduces
commissioning effort and shortens the time to plant start-up (see Field Device
Expert for HART Devices (PSS 41S-10FDMHRT))
Environmental Protection
The enclosure provides NEMA4X/IP66 environmental protection, allowing it to be
used in harsh locations.
Thermal Protection
Heat from the equipment mounted within the enclosure is convected naturally and is
dissipated by the exterior surfaces of the enclosure. For operating in ambient
temperatures up to 55°C (131°F), natural convection is supplemented by two
redundant fans that circulate air within the sealed enclosure.
The fans and temperature within the enclosure are monitored by the Enclosure
Monitoring Unit (EMU) that provides a diagnostic alarm on fan deterioration or
enclosure over temperature.
Leave a minimum of 150 mm (6 in) space between adjacent cabinets or a cabinet and
a wall, to allow the flow of air to cool the cabinet.
Cable Entry
Bottom cable entry for power, communication, and field cables is through customer
supplied cable glands that maintain the enclosure protection classification, or optional
factory fitted Multi Cable Transit (MCT).
Grounding
All enclosure structural elements are integrally grounded by the enclosure design to
meet the appropriate industry regulations and standards. The enclosure is equipped
with two instrument earth bars. It also has a protective connection point at the outside
bottom of the enclosure for customer grounding purposes. Field wiring shields can be
terminated either to the Terminal Assemblies or to the instrument ground bus bar.
Spare signal wires and shields can be terminated either to the Terminal Assemblies or
to the instrument ground bus bar.
Enclosure Security
The enclosure can be physically locked with a customer-supplied padlock to provide
physical security. The enclosure is also fitted with a door open switch that is alarmed
via the Enclosure Monitoring Unit to alert plant personnel.
Enclosure Options
The enclosure can be configured with the following options:
• 120 VAC or 230 VAC supply
• Customer supplied cable glands or factory fitted Multi Cable Transit (MCT)
• Termination Assembly selection for IS, Non-IS, and manufacturer
• 64 simplex UIO points, 64 redundant UIO points, or 48 simplex and 16 redundant
UIO points
• Third party communications through FBM232 modules for simplex Ethernet or
FBM233 modules for redundant Ethernet
• Fiber-optic connection to the HDLC Fieldbus using FCM2F10 modules
• Extended twinaxial connection to the HDLC Fieldbus using FBI200 modules
Functional Specifications
Enclosure SS316L stainless steel field enclosure
Input Power (Redundant) See Compact Power Supply - FPS480-24 (PSS 41H-2C480)
Maximum Dissipated Power 148 W
Maximum Input Power 480 W
Enclosure Over Temperature Alarm 70°C (158°F)
Setting
Regulatory Compliance, Electromagnetic
• EMC Directive 2014/30/EU:
Compatibility (EMC)
Meets: EN 61326-1:2013 and EN 61000-6-2:2005
Product Safety • Underwriters Laboratories (UL) for U.S. and Canada:
UL/UL-C listed as suitable for use in UL/UL-C listed Class I,
Groups A-D; Division 2; Hazardous locations when installed as
described in I-Series Intelligent Enclosures Planning and
Installation Guide (B0700GX).
Communications circuits also meet the requirements for Class 2
as defined in Article 725 of the National Electrical Code (NFPA
No.70) and Section 16 of the Canadian Electrical Code (CSA
C22.1). Conditions for use are as specified in I-Series Intelligent
Enclosures Planning and Installation Guide (B0700GX).
• European Low Voltage Directive 2014/35/EU and Explosive
Atmospheres (ATEX) Directive 2014/34/EU:
II 3G Ex ic ec nC IIC T3 Gc
II 3 D Ex tc IIIC T60 °C Dc
certified when installed as described in I-Series Intelligent
Enclosures Planning and Installation Guide (B0700GX).
RoHS Compliance Complies with European RoHS Directive 2011/65/EU when FBM232
and FBM233 options are not fitted
Environmental Specifications
Operating Storage
Temperature -20° to +55°C (-4° to +131°F) (External -40° to +70°C (-40° to +158°F)
Ambient)
Altitude -300 to +3,000 m (-1,000 to +10,000 ft) -300 to +12,000 m (-1,000 to +40,000 ft)
Relative Humidity 5 to 95% (noncondensing)
Ingress NEMA 4X, IP66 (per EN 60 529/IEC 529)
Protection
Ratings
Contamination Class G3 (Severe) as defined in ISA Standard, S71.04
Class
Enclosure Over 70° C (158° F)
Temperature
Alarm
Vibration • 2.0 to 13.2 Hz, 1.0 mm
• 13.2 to 100 Hz, 0.7 g
Sound Power 47.2 dB
Level (SWL)
Physical Specifications
Mounting Wall mounted
WARNING
POTENTIAL RISK OF INJURY
The enclosure must be securely mounted. See I-Series Intelligent Enclosures Planning
and Installation Guide (B0700GX) for instructions to mount the enclosure.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Dimensions-Nominal
Related Documents
• Compact Power Supply - FPS480-24 (PSS 41H-2C480)
• Environmental Conditions for Process Measurement and Control Systems:
Airborne Contaminants, ISA-S71.04-1985 (not Foxboro-supplied)
• Equipment Room Intelligent Enclosure (PSS 41H-2I30)
• FBI200 Fieldbus Isolator/Filter (PSS 41H-2FBI200)
• FBM232 Field Device System Integrator Module, 10/100 Mbps Ethernet, Single
(PSS 41H-2S232)
• FBM233 Field Device System Integrator Module, 10/100 Mbps Ethernet,
Redundant (PSS 41H-2S233)
• FBM247, Current/Voltage Analog/Digital/Pulse I/O Configurable Module (PSS
41H-2S247)
• FBM248, Current/Voltage Analog/Digital/Pulse I/O Configurable Module
(Redundant) (PSS 41H-2S248)
• Field Control Processor 280 (FCP280) (PSS 41H-1FCP280)
• Fieldbus Communications Module, FCM2F2/FCM2F4/FCM2F1 (PSS 41H-2FCM)
• I-Series Intelligent Enclosures Planning and Installation Guide (B0700GX)
• Standard 200 Series Baseplates (PSS 41H-2SBASPLT)
• Standard and Compact 200 Series I/O - Agency Certifications (PSS 41H-
2CERTS)