1MRK511404-BEN A en Product Guide Bay Control REC670 Version 2.2
1MRK511404-BEN A en Product Guide Bay Control REC670 Version 2.2
1MRK511404-BEN A en Product Guide Bay Control REC670 Version 2.2
R E L I O N ® 670 SERIES
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document. Drawings and diagrams are not binding.
© Copyright 2017 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
2 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1 Issued: October 2017
Revision: A
A number of protection functions are available for flexibility in Flexible Product Naming allows the customer to use an IED-
use for different station types and busbar arrangements. To vendor independent IEC 61850 model of the IED. This
fulfil the user's application requirements, the IED features, for customer model will be used as the IEC 61850 data model,
example, up to six instantaneous phase and earth overcurrent but all other aspects of the IED will remain unchanged (e.g.,
functions, 4–step directional or non-directional delayed-phase names on the local HMI and names in the tools). This offers
and earth overcurrent functions, thermal overload and significant flexibility to adapt the IED to the customers'
frequency functions, two instances of 2–step under- and system and standard solution.
overvoltage functions, autorecloser functions and several SEMOD51278-4 v11
different measuring functions. This, together with the multi- Four packages have been defined for following applications:
display local HMI that can show one or more pages per
feeder allows using the IED for protection and control for up • Single breaker (double or single bus) arrangement (A30)
to six bays in a substation. • Double breaker arrangement (B30)
• 1 ½ breaker arrangement for a complete diameter (C30)
The auto-reclose for single-, two-, and/or three-phase reclose • Single breaker (double bus) arrangement with PMU
includes priority circuits for multi-breaker arrangements. It co- functionality (D30)
operates with the synchrocheck function with high-speed or
delayed reclosing. Several breaker failure functions are Optional functions are available in PCM600 Application
available to provide a breaker failure function independent Configuration Tool and can be configured by the user.
from the protection IEDs, also for a complete one- and a half Interface to analog and binary IO:s are configurable without
breaker diameter. need of configuration changes. Analog and control circuits
have been pre-defined. Other signals need to be applied as
Disturbance recording and fault locator are available to allow required for each application. The main differences between
independent post-fault analysis after primary disturbances in the packages above are the interlocking modules and the
case of a failure in the protection system. number of apparatuses to control.
ABB 3
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
WA1 REC670 A30 – Double busbar in single breaker arrangement 12AI (6I + 6U)
WA2_VT MET UN
VN MMXU
QC2
3 Control 3 Control 3 Control
S CILO S CSWI S XSWI
LINE_CT Control
Control
Control MET I MET Isqi MET P/Q U>/I<
SSSCBR
S SCBR
SCBR C MMXU C MSQI CV MMXN FUF SPVC
60 Ud>
VDC PTOV
Optional Functions
50BF 3I>BF 2(I>/U<) 85 85 50N IN>> 51N_67N 4(IN>) 32 P> 37 P< 87 Id>
CC RBRF CV GAPC EC PSCH ECRW PSCH EF PIOC EF4 PTOC GOP PDOP GUP PDUP HZ PDIF
26 θ> 26 θ> 46I2 4(I2>) 51_67 4(3I>) 59 2(3U>) 50 3I>> 59N 2(U0>) 81 df/dt<>
LC PTTR LF PTTR NS4 PTOC OC4 PTOC OV2 PTOV PH PIOC PMU REP ROV2 PTOV SA PFRC
81 f> 81 f< 67N IN> 79 5(0 1) 50STB 3I>STB 49 θ> 90 U↑↓ 90 U↑↓ 27 2(3U<)
SA PTOF SA PTUF SDE PSDE SMB RREC STB PTOC TR PTTR TR1 ATCC TR8 ATCC UV2 PTUV
IEC05000837-5-en.vsd
IEC05000837 V5 EN-US
4 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
WA1
REC670 B30 - Double breaker arrangement 12AI (6I + 6U)
WA2
LINE_CT1 Control
Control
Control
SSSSCBR
SCBR
SCBR
MET I MET Isqi U>/I<
60 Ud>
VDC PTOV
Optional Functions
50BF 3I>BF 2(I>/U<) 85 85 50N IN>> 51N_67N 4(IN>) 32 P> 37 P< 87 Id>
CC RBRF CV GAPC EC PSCH ECRW PSCH EF PIOC EF4 PTOC GOP PDOP GUP PDUP HZ PDIF
=IEC05000838=5=en=Original.vsd
IEC05000838 V5 EN-US
ABB 5
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
WA1
REC670C30 – Complete one-and a half breaker diameter arrangement 24AI (6I + 6U, 6I+6U)
TIE_QA1
3 Control 3 Control 3 Control MET U MET Usqi MET UN
S CILO S CSWI S XCBR V MMXU V MSQI VN MMXU
TIE_CT
MET I MET Isqi MET P/Q U>/I<
Control
Control
Σ
Control C MMXU C MSQI CV MMXN FUF SPVC
QB62
SSSCBR
S SCBR
SCBR
LINE2_QB9
3 Control 3 Control 3 Control MET W/Varh
S CILO S CSWI S XSWI ETP MMTR
Optional Functions
50BF 3I>BF U</I> 85 85 50N IN>> 51N_67N 4(IN>) 32 P> 37 P< 87 Id> 26 θ>
CC RBRF CV GAPC EC PSCH ECRW PSCH EF PIOC EF4 PTOC GOP PDOP GUP PDUP HZ PDIF LC PTTR
26 θ> 46I2 4(I2>) 51_67 4(3I>) 59 2(3U>) 50 3I>> 59N 2(U0>) 81 df/dt<> 81 f> 81 f<
LF PTTR NS4 PTOC OC4 PTOC OV2 PTOV PH PIOC PMU REP ROV2 PTOV SA PFRC SA PTOF SA PTUF
67N IN> 79 5(0 1) 50STB 3I>STB 49 θ> 90 U↑↓ 90 U↑↓ 27 2(3U<) 60 Ud> 51V 2(I>/U<)
↓
SDE PSDE SMB RREC STB PTOC TR PTTR TR1 ATCC TR8 ATCC UV2 PTUV VD SPVC VR PVOC ZCLC PSCH
85 85
ZC PSCH ZCRW PSCH
IEC05000839-5-en.vsd
IEC05000839 V5 EN-US
6 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
WA1 REC670 D30 – Double busbar in single breaker arrangement with PMU functionality
12AI (6I + 6U)
WA2_VT MET UN
VN MMXU
LINE_CT Control
Control
Control MET I MET Isqi MET P/Q U>/I<
SSCBR
S
S SCBR
SCBR C MMXU C MSQI CV MMXN FUF SPVC
LINE_VT DRP RDRE Q CBAY Q CRSV PMU REP IEEE Std C37.118
60 Ud>
VDC PTOV
Optional Functions
50BF 3I>BF 2(I>/U<) 85 85 50N IN>> 51N_67N 4(IN>) 32 P> 37 P< 87 Id>
CC RBRF CV GAPC EC PSCH ECRW PSCH EF PIOC EF4 PTOC GOP PDOP GUP PDUP HZ PDIF
26 θ> 26 θ> 46I2 4(I2>) 51_67 4(3I>) 59 2(3U>) 50 3I>> 59N 2(U0>) 81 df/dt<> 81 f>
LC PTTR LF PTTR NS4 PTOC OC4 PTOC OV2 PTOV PH PIOC ROV2 PTOV SA PFRC SA PTOF
81 f< 67N IN> 79 5(0 1) 50STB 3I>STB 49 θ> 90 U↑↓ 90 U↑↓ 27 2(3U<) 60 Ud>
SA PTUF SDE PSDE SMB RREC STB PTOC TR PTTR TR1 ATCC TR8 ATCC UV2 PTUV VD SPVC
51V 2(I>/U<) 85 85
VR PVOC ZCLC PSCH ZC PSCH ZCRW PSCH
IEC16000194=IEC16000194=1=en=Original
.vsdx
IEC16000194 V1 EN-US
GUID-79B8BC84-4AAB-44E7-86CD-FF63098B009D v2
ABB 7
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
The basic delivery includes one binary input module and one are specific to the system, object or application. Optional
binary output module, which is sufficient for the default functions and optional IO ordered will not be configured at
configured IO to trip and close circuit breaker. All IEDs can be delivery. It should be noted that the standard only includes
reconfigured with the help of the application configuration tool one binary input and one binary output module and only the
in PCM600. The IED can be adapted to special applications key functions such as tripping are connected to the outputs
and special logic can be developed, such as logic for in the signal matrix tool. The required total IO must be
automatic opening of disconnectors and closing of ring bays, calculated and specified at ordering.
automatic load transfer from one busbar to the other, and so
on. The configurations are as far as found necessary provided
with application comments to explain why the signals have
The basic IED configuration is provided with the signal matrix, been connected in the special way. On request, ABB is
single line diagram and the application configuration prepared available to support the re-configuration work, either directly
for the functions included in the product by default. All or to do the design checking.
parameters should be verified by the customer, since these
8 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
2. Available functions
GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1
are not exposed to the user or do not need
to be configured are not described in this
The following tables list all the functions manual.
available in the IED. Those functions that
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
Differential protection
HZPDIF 87 High impedance differential protection, 0-6 3-A02 3-A02 6-A07 3-A02
single phase
ABB 9
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
Current protection
OC4PTOC 51_671) Directional phase overcurrent protection, 0-6 1-C51 2-C52 2-C53 1-C51
four steps
EFPIOC 50N Instantaneous residual overcurrent 0-6 1-C51 2-C52 2-C53 1-C51
protection
EF4PTOC 51N Directional residual overcurrent 0-6 1-C51 2-C52 2-C53 1-C51
67N2) protection, four steps
NS4PTOC 46I2 Four step directional negative phase 0-6 1-C51 2-C52 2-C53 1-C51
sequence overcurrent protection
SDEPSDE 67N Sensitive directional residual overcurrent 0-6 1-C16 1–C16 1-C16 1-C16
and power protection
LCPTTR 26 Thermal overload protection, one time 0-6 1-C51 1-C52 2-C53 1-C51
constant, Celsius
LFPTTR 26 Thermal overload protection, one time 0-6 1-C51 1-C52 2-C53 1-C51
constant, Fahrenheit
TRPTTR 49 Thermal overload protection, two time 0-6 1-C51 1-C52 2-C53 1-C51
constants
CCRBRF 50BF Breaker failure protection 0-6 1-C51 2-C52 3-C53 1-C51
VRPVOC 51V Voltage restrained overcurrent protection 0-3 1-C35 1-C35 1-C35 1-C35
Voltage protection
UV2PTUV 27 Two step undervoltage protection 0-2 2-D02 2-D02 2-D02 2-D02
OV2PTOV 59 Two step overvoltage protection 0-2 2-D02 2-D02 2-D02 2-D02
ROV2PTOV 59N Two step residual overvoltage protection 0-2 2-D02 2-D02 2-D02 2-D02
Frequency protection
10 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
Multipurpose protection
CVGAPC General current and voltage protection 0-9 4-F01 4-F01 4-F01 4-F01
General calculation
1) 67 requires voltage
2) 67N requires voltage
ABB 11
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
Control
TR1ATCC 90 Automatic voltage control for tap changer, single control 0-4 1-H11 1-H11 2-H16 1-H11
TR8ATCC 90 Automatic voltage control for tap changer, parallel 0-4 1-H15 1-H15 2-H18 1-H15
control
Secondary system
supervision
12 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
VDSPVC 60 Fuse failure supervision based on voltage difference 0-2 1-G03 1-G03 1-G03 1-G03
Logic
AND, GATE, INV, Basic configurable logic blocks (see Table 2) 40-420 40-420 40-420 40-420 40-420
LLD, OR,
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
ABB 13
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
AND 280
GATE 40
INV 420
LLD 40
OR 298
PULSETIMER 40
RSMEMORY 40
SRMEMORY 40
TIMERSET 60
XOR 40
14 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
SCILO Interlocking 10
BB_ES 3
A1A2_BS 2
A1A2_DC 3
ABC_BC 1
BH_CONN 1
BH_LINE_A 1
BH_LINE_B 1
DB_BUS_A 1
DB_BUS_B 1
DB_LINE 1
ABC_LINE 1
AB_TRAFO 1
RESIN1 1
RESIN2 59
ABB 15
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
SCILO Interlocking 15
BB_ES 3
A1A2_BS 2
A1A2_DC 3
ABC_BC 1
BH_CONN 1
BH_LINE_A 1
BH_LINE_B 1
DB_BUS_A 1
DB_BUS_B 1
DB_LINE 1
ABC_LINE 1
AB_TRAFO 1
RESIN1 1
RESIN2 59
16 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
SCILO Interlocking 30
BB_ES 6
A1A2_BS 4
A1A2_DC 6
ABC_BC 2
BH_CONN 2
BH_LINE_A 2
BH_LINE_B 2
DB_BUS_A 3
DB_BUS_B 3
DB_LINE 3
ABC_LINE 6
AB_TRAFO 4
RESIN1 1
RESIN2 59
ANDQT 120
INDCOMBSPQT 20
INDEXTSPQT 20
INVALIDQT 22
INVERTERQT 120
ORQT 120
PULSETIMERQT 40
RSMEMORYQT 40
SRMEMORYQT 40
TIMERSETQT 40
XORQT 40
ABB 17
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
AND 180
GATE 49
INV 180
LLD 49
OR 180
PULSETIMER 89
RSMEMORY 40
SLGAPC 74
SRMEMORY 130
TIMERSET 109
VSGAPC 120
XOR 89
18 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
Monitoring
LOLSPTR 26/49 Transformer insulation loss of life monitoring 0-4 4-M21 4-M21 4-M21 4-M21
HS
ABB 19
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
Metering
20 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Communication
GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v15
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
Station communication
RS485GEN RS485 1 1 1 1 1
MULTICMDRCV, Multiple command and transmit 60/10 60/10 60/10 60/10 60/10
MULTICMDSND
ABB 21
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
PRP IEC 62439-3 Parallel redundancy protocol 0-1 1-P23 1-P23 1-P23 1-P23
HSR IEC 62439-3 High-availability seamless 0-1 1-P24 1-P24 1-P24 1-P24
redundancy
Remote communication
BinSignRec1_1 Binary signal transfer receive 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6
BinSignRec1_2
BinSignReceive2
22 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
REC670 (C30)
REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)
BinSignTrans1_1 Binary signal transfer transmit 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6
BinSignTrans1_2
BinSignTransm2
LDCMRecBinStat1 Receive binary status from remote LDCM 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3
LDCMRecBinStat2
LDCMRecBinStat3
Scheme communication
ZCPSCH 85 Scheme communication logic with delta 0-1 1-K01 1-K01 1-K01 1-K01
based blocking scheme signal transmit
ZCRWPSCH 85 Current reversal and weak-end infeed logic 0-1 1-K01 1-K01 1-K01 1-K01
for distance protection
ECPSCH 85 Scheme communication logic for residual 0-1 1-C51 1-C52 1-C53 1-C51
overcurrent protection
ECRWPSCH 85 Current reversal and weak-end infeed logic 0-1 1-C51 1-C52 1-C53 1-C51
for residual overcurrent protection
PHASORREPORT1 Protocol reporting of phasor data via IEEE 1344 and C37.118, phasors 1-8 1
ANALOGREPORT1 Protocol reporting of analog data via IEEE 1344 and C37.118, analogs 1-8 1
BINARYREPORT1 Protocol reporting of binary data via IEEE 1344 and C37.118, binary 1-8 1
ABB 23
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
24 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
For systems, which can run asynchronously, a synchronizing The apparatus control functions are used for control and
feature is also provided. The main purpose of the supervision of circuit breakers, disconnectors and earthing
synchronizing feature is to provide controlled closing of circuit switches within a bay. Permission to operate is given after
breakers when two asynchronous systems are in phase and evaluation of conditions from other functions such as
can be connected. The synchronizing feature evaluates interlocking, synchrocheck, operator place selection and
voltage difference, phase angle difference, slip frequency and external or internal blockings.
frequency rate of change before issuing a controlled closing
Apparatus control features:
of the circuit breaker. Breaker closing time is a setting.
• Select-Execute principle to give high reliability
Autorecloser SMBRREC • Selection function to prevent simultaneous operation
M12390-3 v16
The auto reclosing function provides: • Selection and supervision of operator place
• Command supervision
• Block/deblock of operation
• Block/deblock of updating of position indications
ABB 25
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
• Substitution of position and quality indications Each apparatus control function has interlocking modules
• Overriding of interlocking functions included for different switchyard arrangements, where each
• Overriding of synchrocheck function handles interlocking of one bay. The interlocking
• Operation counter function is distributed to each IED and is not dependent on
• Suppression of mid position any central function. For the station-wide interlocking, the
IEDs communicate via the system-wide interbay bus (IEC
61850-8-1) or by using hard wired binary inputs/outputs. The
Two types of command models can be used:
interlocking conditions depend on the circuit configuration
• Direct with normal security
and apparatus position status at any given time.
• SBO (Select-Before-Operate) with enhanced security
For easy and safe implementation of the interlocking function,
Normal security means that only the command is evaluated the IED is delivered with standardized and tested software
and the resulting position is not supervised. Enhanced interlocking modules containing logic for the interlocking
security means that the command is evaluated with an conditions. The interlocking conditions can be altered, to
additional supervision of the status value of the control meet the customer’s specific requirements, by adding
object. The command sequence with enhanced security is configurable logic by means of the graphical configuration
always terminated by a CommandTermination service tool.
primitive and an AddCause telling if the command was
The following interlocking modules are available:
successful or if something went wrong.
• Line for double and transfer busbars, ABC_LINE
Control operation can be performed from the local HMI with
• Bus coupler for double and transfer busbars, ABC_BC
authority control if so defined.
• Transformer bay for double busbars, AB_TRAFO
M16909-3 v3
Features of the apparatus control function are: • Bus-section breaker for double busbars, A1A2_BS
• Bus-section disconnector for double busbars, A1A2_DC
• Operation of primary apparatuses • Busbar earthing switch, BB_ES
• Select-Execute principle to give high reliability • Double CB Bay, DB_BUS_A, DB_LINE, DB_BUS_B
• Selection and reservation function to prevent • 1 1/2-CB diameter, BH_LINE_A, BH_CONN, BH_LINE_B
simultaneous operation
• Selection and supervision of operator place
Switch controller SCSWI
• Command supervision M13486-3 v8
The Switch controller (SCSWI) initializes and supervises all
• Block/deblock of operation
functions to properly select and operate switching primary
• Block/deblock of updating of position indications
apparatuses. The Switch controller may handle and operate
• Substitution of position indications
on one multi-phase device or up to three one-phase devices.
• Overriding of interlocking functions
• Overriding of synchrocheck Circuit breaker SXCBR
• Pole discordance supervision
M13489-3 v6
The purpose of Circuit breaker (SXCBR) is to provide the
• Operation counter actual status of positions and to perform the control
operations, that is, pass all the commands to primary
The apparatus control function is realized by means of a
apparatuses in the form of circuit breakers via binary output
number of function blocks designated:
boards and to supervise the switching operation and position.
• Bay control QCBAY
Circuit switch SXSWI
• Switch controller SCSWI M16492-3 v6
The purpose of Circuit switch (SXSWI) function is to provide
• Circuit breaker SXCBR
the actual status of positions and to perform the control
• Circuit switch SXSWI
operations, that is, pass all the commands to primary
The three latter functions are logical nodes according to IEC apparatuses in the form of disconnectors or earthing switches
61850-8-1. To realize the reservation function also the via binary output boards and to supervise the switching
function blocks Reservation input (RESIN) and Bay reserve operation and position.
(QCRSV) are included in the apparatus control function.
Reservation function QCRSV
M13506-3 v4
26 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
supervision, 6 binary inputs (TCMYLTC) and Tap changer function block is a collection of 8 single point commands that
control and supervision, 32 binary inputs (TCLYLTC) are used can be used for direct commands for example reset of LEDs
for control of power transformers with an on-load tap or putting IED in "ChangeLock" state from remote. In this
changer. The functions provide automatic regulation of the way, simple commands can be sent directly to the IED
voltage on the secondary side of transformers or alternatively outputs, without confirmation. Confirmation (status) of the
on a load point further out in the network. result of the commands is supposed to be achieved by other
means, such as binary inputs and SPGAPC function blocks.
Control of a single transformer, as well as control of up to
The commands can be pulsed or steady with a settable pulse
eight transformers in parallel is possible. For parallel control of
time.
power transformers, three alternative methods are available:
the master-follower method, the circulating current method Automation bits, command function for DNP3.0 AUTOBITS
and the reverse reactance method. The first two methods SEMOD158591-5 v8
Automation bits function for DNP3 (AUTOBITS) is used within
require exchange of information between the parallel PCM600 to get into the configuration of the commands
transformers and this is provided for within IEC 61850-8-1. coming through the DNP3 protocol. The AUTOBITS function
ABB 27
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
61850) and MULTICMDRCV (for LON). The phasor measurement reporting block moves the phasor
calculations into an IEEE C37.118 and/or IEEE 1344
Single command, 16 signals synchrophasor frame format. The PMUREPORT block
M12446-6 v5
The IEDs can receive commands either from a substation contains parameters for PMU performance class and
automation system or from the local HMI. The command reporting rate, the IDCODE and Global PMU ID, format of the
function block has outputs that can be used, for example, to data streamed through the protocol, the type of reported
control high voltage apparatuses or for other user defined synchrophasors, as well as settings for reporting analog and
functionality. digital signals.
• IEEE Std C37.118-2005 (Both measurements and data (OC4PTOC) has an inverse or definite time delay for each
communication) step.
• IEEE Std C37.118.1–2011 and C37.118.1a-2014
(Measurements) All IEC and ANSI inverse time characteristics are available
• IEEE Std C37.118.2-2011 (Data communication) together with an optional user defined time characteristic.
28 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Directional residual overcurrent protection, four steps Sensitive directional residual overcurrent and power
EF4PTOC protection SDEPSDE
M13667-3 v19 SEMOD171438-5 v6
Directional residual overcurrent protection, four steps In isolated networks or in networks with high impedance
(EF4PTOC) can be used as main protection for phase-to- earthing, the earth fault current is significantly smaller than
earth faults. It can also be used to provide a system back-up, the short circuit currents. In addition to this, the magnitude of
for example, in the case of the primary protection being out of the fault current is almost independent on the fault location in
service due to communication or voltage transformer circuit the network. The protection can be selected to use either the
failure. residual current or residual power component 3U0·3I0·cos j,
for operating quantity with maintained short circuit capacity.
EF4PTOC has an inverse or definite time delay independent There is also available one nondirectional 3I0 step and one
for each step. 3U0 overvoltage tripping step.
All IEC and ANSI time-delayed characteristics are available No specific sensitive current input is needed. Sensitive
together with an optional user-defined characteristic. directional residual overcurrent and power protection
(SDEPSDE) can be set as low 0.25% of IBase.
EF4PTOC can be set to be directional or non-directional
independently for each step. Thermal overload protection, one time constant LCPTTR/
LFPTTR
IDir, UPol and IPol can be independently selected to be either M12020-4 v14
The increasing utilization of the power system closer to the
zero sequence or negative sequence.
thermal limits has generated a need of a thermal overload
A second harmonic blocking can be set individually for each protection for power lines.
step.
A thermal overload will often not be detected by other
Directional operation can be combined together with the protection functions and the introduction of the thermal
corresponding communication logic in permissive or blocking overload protection can allow the protected circuit to operate
teleprotection scheme. The current reversal and weak-end closer to the thermal limits.
infeed functionality are available as well.
The three-phase current measuring protection has an I 2 t
The residual current can be calculated by summing the three- characteristic with settable time constant and a thermal
phase currents or taking the input from the neutral CT. memory. The temperature is displayed in either Celsius or
Fahrenheit, depending on whether the function used is
Four step directional negative phase sequence overcurrent Thermal overload protection (LCPTTR) (Celsius) or (LFPTTR)
protection NS4PTOC (Fahrenheit).
GUID-485E9D36-0032-4559-9204-101539A32F47 v6
Four step directional negative phase sequence overcurrent
protection (NS4PTOC) has an inverse or definite time delay An alarm level gives early warning to allow operators to take
independent for each step separately. action well before the line is tripped.
All IEC and ANSI time delayed characteristics are available Estimated time to trip before operation, and estimated time to
together with an optional user defined characteristic. reclose after operation are presented.
The directional function is voltage polarized. Thermal overload protection, two time constants TRPTTR
M13243-3 v11
If a power transformer reaches very high temperatures the
NS4PTOC can be set directional or non-directional equipment might be damaged. The insulation within the
independently for each of the steps. transformer will experience forced ageing. As a consequence
of this the risk of internal phase-to-phase or phase-to-earth
NS4PTOC can be used as main protection for unsymmetrical
faults will increase.
fault; phase-phase short circuits, phase-phase-earth short
circuits and single phase earth faults.
ABB 29
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
The thermal overload protection estimates the internal heat Normally the own breaker is tripped to correct such a
content of the transformer (temperature) continuously. This situation. If the situation persists the surrounding breakers
estimation is made by using a thermal model of the should be tripped to clear the unsymmetrical load situation.
transformer with two time constants, which is based on
current measurement. The Pole discordance protection function (CCPDSC) operates
based on information from auxiliary contacts of the circuit
Two warning levels are available. This enables actions in the breaker for the three phases with additional criteria from
power system to be done before dangerous temperatures are unsymmetrical phase currents when required.
reached. If the temperature continues to increase to the trip
value, the protection initiates a trip of the protected Directional over/underpower protection GOPPDOP/
transformer. GUPPDUP
SEMOD175421-4 v7
The directional over-/under-power protection (GOPPDOP/
The estimated time to trip before operation is presented. GUPPDUP) can be used wherever a high/low active, reactive
or apparent power protection or alarming is required. The
Breaker failure protection CCRBRF functions can alternatively be used to check the direction of
M11550-6 v17
Breaker failure protection (CCRBRF) ensures a fast backup active or reactive power flow in the power system. There are
tripping of the surrounding breakers in case the own breaker a number of applications where such functionality is needed.
fails to open. CCRBRF can be current-based, contact-based Some of them are:
or an adaptive combination of these two conditions.
• detection of reversed active power flow
A current check with extremely short reset time is used as • detection of high reactive power flow
check criterion to achieve high security against unwanted
operation. Each function has two steps with definite time delay.
Contact check criteria can be used where the fault current Broken conductor check BRCPTOC
SEMOD171446-5 v2
through the breaker is small. The main purpose of the function Broken conductor check
(BRCPTOC) is the detection of broken conductors on
CCRBRF can be single- or three-phase initiated to allow use protected power lines and cables (series faults). Detection
with single phase tripping applications. For the three-phase can be used to give alarm only or trip the line breaker.
version of CCRBRF the current criteria can be set to operate
only if two out of four for example, two phases or one phase Voltage-restrained time overcurrent protection VRPVOC
GUID-935E1CE8-601F-40E2-8D22-2FF68420FADF v6
plus the residual current start. This gives a higher security to Voltage-restrained time overcurrent protection (VRPVOC)
the back-up trip command. function can be used as generator backup protection against
short-circuits.
CCRBRF function can be programmed to give a single- or
three-phase re-trip of its own breaker to avoid unnecessary The overcurrent protection feature has a settable current level
tripping of surrounding breakers at an incorrect initiation due that can be used either with definite time or inverse time
to mistakes during testing. characteristic. Additionally, it can be voltage controlled/
restrained.
Stub protection STBPTOC
M12902-3 v10
When a power line is taken out of service for maintenance One undervoltage step with definite time characteristic is also
and the line disconnector is opened in multi-breaker available within the function in order to provide functionality
arrangements the voltage transformers will mostly be outside for overcurrent protection with undervoltage seal-in.
on the disconnected part. The primary line distance
protection will thus not be able to operate and must be Capacitor bank protection CBPGAPC
GUID-D55CEBF7-9377-4E36-BD8B-533609048A1E v3
UV2PTUV has two voltage steps, each with inverse or definite Underfrequency occurs as a result of a lack of generation in
time delay. the network.
It has a high reset ratio to allow settings close to the system Underfrequency protection (SAPTUF) measures frequency
service voltage. with high accuracy, and is used for load shedding systems,
remedial action schemes, gas turbine startup and so on.
Two step overvoltage protection OV2PTOV Separate definite time delays are provided for operate and
M13798-3 v15
Overvoltages may occur in the power system during abnormal restore.
conditions such as sudden power loss, tap changer
regulating failures, and open line ends on long lines. SAPTUF is provided with undervoltage blocking.
Two step overvoltage protection (OV2PTOV) function can be The operation is based on positive sequence voltage
used to detect open line ends, normally then combined with a measurement and requires two phase-phase or three phase-
directional reactive over-power function to supervise the neutral voltages to be connected.
system voltage. When triggered, the function will cause an
alarm, switch in reactors, or switch out capacitor banks. Overfrequency protection SAPTOF
M14953-3 v12
Overfrequency protection function (SAPTOF) is applicable in
OV2PTOV has two voltage steps, each of them with inverse all situations, where reliable detection of high fundamental
or definite time delayed. power system frequency is needed.
OV2PTOV has a high reset ratio to allow settings close to Overfrequency occurs because of sudden load drops or
system service voltage. shunt faults in the power network. Close to the generating
plant, generator governor problems can also cause over
Two step residual overvoltage protection ROV2PTOV frequency.
M13808-3 v11
Residual voltages may occur in the power system during
earth faults. SAPTOF measures frequency with high accuracy, and is used
mainly for generation shedding and remedial action schemes.
Two step residual overvoltage protection (ROV2PTOV) It is also used as a frequency stage initiating load restoring. A
function calculates the residual voltage from the three-phase definite time delay is provided for operate.
voltage input transformers or measures it from a single
voltage input transformer fed from an open delta or neutral SAPTOF is provided with an undervoltage blocking.
point voltage transformer.
The operation is based on positive sequence voltage
ROV2PTOV has two voltage steps, each with inverse or measurement and requires two phase-phase or three phase-
definite time delay. neutral voltages to be connected.
A reset delay ensures operation for intermittent earth faults. Rate-of-change of frequency protection SAPFRC
M14965-3 v13
The rate-of-change of frequency protection function
Voltage differential protection VDCPTOV (SAPFRC ) gives an early indication of a main disturbance in
SEMOD153862-5 v7
A voltage differential monitoring function is available. It the system. SAPFRC measures frequency with high accuracy,
compares the voltages from two three phase sets of voltage and can be used for generation shedding, load shedding and
transformers and has one sensitive alarm step and one trip remedial action schemes. SAPFRC can discriminate between
step. Alternatively, it can be used as voltage differential a positive or negative change of frequency. A definite time
protection (VDCPTOV) for shunt capacitor banks. delay is provided for operate.
Loss of voltage check LOVPTUV SAPFRC is provided with an undervoltage blocking. The
SEMOD171457-5 v8
Loss of voltage check (LOVPTUV ) is suitable for use in operation is based on positive sequence voltage
networks with an automatic system restoration function. measurement and requires two phase-phase or three phase-
LOVPTUV issues a three-pole trip command to the circuit neutral voltages to be connected.
breaker, if all three phase voltages fall below the set value for
a time longer than the set time and the circuit breaker Frequency time accumulation protection FTAQFVR
GUID-020CE8CF-9BEA-455D-ACBD-13023B93B4D1 v5
START signal triggers the individual event timer, which is the with the neutral point current on a separate input taken from
continuous time spent within the given frequency band, and another set of cores on the current transformer.
the accumulation timer, which is the cumulative time spent
within the given frequency band. Once the timers reach their A detection of a difference indicates a fault in the circuit and
limit, an alarm or trip signal is activated to protect the turbine is used as alarm or to block protection functions expected to
against the abnormal frequency operation. This function is give inadvertent tripping.
blocked during generator start-up or shut down conditions by
Fuse failure supervision FUFSPVC
monitoring the circuit breaker position and current threshold SEMOD113820-4 v12
The aim of the fuse failure supervision function (FUFSPVC) is
value. The function is also blocked when the system positive
to block voltage measuring functions at failures in the
sequence voltage magnitude deviates from the given voltage
secondary circuits between the voltage transformer and the
band limit which can be enabled by EnaVoltCheck setting.
IED in order to avoid inadvertent operations that otherwise
It is possible to create functionality with more than one might occur.
frequency band limit by using multiple instances of the
The fuse failure supervision function basically has three
function. This can be achieved by a proper configuration
different detection methods, negative sequence and zero
based on the turbine manufacturer specification.
sequence based detection and an additional delta voltage
and delta current detection.
9. Multipurpose protection
The negative sequence detection algorithm is recommended
General current and voltage protection CVGAPC for IEDs used in isolated or high-impedance earthed
M13083-11 v9
The General current and voltage protection (CVGAPC) can be networks. It is based on the negative-sequence quantities.
utilized as a negative sequence current protection detecting
unsymmetrical conditions such as open phase or The zero sequence detection is recommended for IEDs used
unsymmetrical faults. in directly or low impedance earthed networks. It is based on
the zero sequence measuring quantities.
CVGAPC can also be used to improve phase selection for
high resistive earth faults, outside the distance protection The selection of different operation modes is possible by a
reach, for the transmission line. Three functions are used, setting parameter in order to take into account the particular
which measures the neutral current and each of the three earthing of the network.
phase voltages. This will give an independence from load
A criterion based on delta current and delta voltage
currents and this phase selection will be used in conjunction
measurements can be added to the fuse failure supervision
with the detection of the earth fault from the directional earth
function in order to detect a three phase fuse failure, which in
fault protection function.
practice is more associated with voltage transformer
switching during station operations.
10. General calculation
Fuse failure supervision VDSPVC
GUID-6AF2219A-264F-4971-8D03-3B8A9D0CB284 v5
Multipurpose filter SMAIHPAC Different protection functions within the protection IED
GUID-EB0B11C3-FF79-4B8D-A335-649623E832F9 v3
The multi-purpose filter function block (SMAIHPAC) is operates on the basis of measured voltage at the relay point.
arranged as a three-phase filter. It has very much the same Some example of protection functions are:
user interface (e.g. inputs and outputs) as the standard pre-
processing function block SMAI. However the main difference • Distance protection function.
is that it can be used to extract any frequency component • Undervoltage function.
from the input signal. Thus it can, for example, be used to • Energisation function and voltage check for the weak
build sub-synchronous resonance protection for synchronous infeed logic.
generator.
These functions can operate unintentionally, if a fault occurs
in the secondary circuits between voltage instrument
11. Secondary system supervision transformers and the IED. These unintentional operations can
be prevented by fuse failure supervision (VDSPVC).
Current circuit supervision CCSSPVC
M12444-3 v10
Open or short circuited current transformer cores can cause VDSPVC is designed to detect fuse failures or faults in voltage
unwanted operation of many protection functions such as measurement circuit, based on phase wise comparison of
differential, earth-fault current and negative-sequence current voltages of main and pilot fused circuits. VDSPVC blocking
functions. output can be configured to block functions that need to be
blocked in case of faults in the voltage circuit.
Current circuit supervision (CCSSPVC) compares the residual
current from a three phase set of current transformer cores
32 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
12. Scheme communication including a channel transmission time, can be achieved. This
short operate time enables rapid autoreclosing function after
Scheme communication logic with delta based blocking the fault clearance.
scheme signal transmit ZCPSCH
M13860-3 v10
To achieve instantaneous fault clearance for all line faults, The communication logic module for directional residual
scheme communication logic is provided. All types of current protection enables blocking as well as permissive
communication schemes for permissive underreaching, under/overreaching, and unblocking schemes. The logic can
permissive overreaching, blocking, delta based blocking, also be supported by additional logic for weak-end infeed and
unblocking and intertrip are available. current reversal, included in Current reversal and weak-end
infeed logic for residual overcurrent protection (ECRWPSCH)
The built-in communication module (LDCM) can be used for function.
scheme communication signaling when included.
Current reversal and weak-end infeed logic for residual
Current reversal and weak-end infeed logic for distance overcurrent protection ECRWPSCH
protection ZCRWPSCH M13928-3 v8
The Current reversal and weak-end infeed logic for residual
M13896-3 v15
The ZCRWPSCH function provides the current reversal and overcurrent protection (ECRWPSCH) is a supplement to
weak end infeed logic functions that supplement the standard Scheme communication logic for residual overcurrent
scheme communication logic. It is not suitable for standalone protection ECPSCH.
use as it requires inputs from the distance protection
functions and the scheme communications function included To achieve fast fault clearing for all earth faults on the line, the
within the terminal. directional earth fault protection function can be supported
with logic that uses tele-protection channels.
On detection of a current reversal, the current reversal logic
provides an output to block the sending of the teleprotection This is why the IEDs have available additions to the scheme
signal to the remote end, and to block the permissive tripping communication logic.
at the local end. This blocking condition is maintained long M13928-6 v2
enough to ensure that no unwanted operation will occur as a If parallel lines are connected to common busbars at both
result of the current reversal. terminals, overreaching permissive communication schemes
can trip unselectively due to fault current reversal. This
On verification of a weak end infeed condition, the weak end unwanted tripping affects the healthy line when a fault is
infeed logic provides an output for sending the received cleared on the other line. This lack of security can result in a
teleprotection signal back to the remote sending end and total loss of interconnection between the two buses. To avoid
other output(s) for local tripping. For terminals equipped for this type of disturbance, a fault current reversal logic
single- and two-pole tripping, outputs for the faulted phase(s) (transient blocking logic) can be used.
are provided. Undervoltage detectors are used to detect the M13928-8 v5
protection ECPSCH A function block for protection tripping and general start
M13918-4 v11
To achieve fast fault clearance of earth faults on the part of indication is always provided as a basic function for each
the line not covered by the instantaneous step of the residual circuit breaker. It provides a settable pulse prolongation time
overcurrent protection, the directional residual overcurrent to ensure a trip pulse of sufficient length, as well as all
protection can be supported with a logic that uses functionality necessary for correct co-operation with
communication channels. autoreclosing functions.
In the directional scheme, information of the fault current The trip function block includes a settable latch function for
direction must be transmitted to the other line end. With the trip signal and circuit breaker lockout.
directional comparison, a short operate time of the protection
ABB 33
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
The trip function can collect start and directional signals from • INVERTER function block that inverts the input signal to the
different application functions. The aggregated start and output.
directional signals are mapped to the IEC 61850 logical node
data model. • LLD function block. Loop delay used to delay the output
signal one execution cycle.
General start matrix block SMAGAPC
GUID-BA516165-96DE-4CD9-979B-29457C7653C0 v3
The Start Matrix (SMAGAPC) merges start and directional • OR function block. The OR function is used to form general
output signals from different application functions and creates combinatory expressions with boolean variables. The OR
a common start and directional output signal (STDIR ) to be function block has up to six inputs and two outputs. One of
connected to the Trip function. the outputs is inverted.
The purpose of this functionality is to provide general start • PULSETIMER function block can be used, for example, for
and directional information for the IEC 61850 trip logic data pulse extensions or limiting of operation of outputs, settable
model SMPPTRC. pulse time.
Trip matrix logic TMAGAPC • RSMEMORY function block is a flip-flop that can reset or
M15321-3 v12
The trip matrix logic TMAGAPC function is used to route trip set an output from two inputs respectively. Each block has
signals and other logical output signals to different output two outputs where one is inverted. The memory setting
contacts on the IED. controls if, after a power interruption, the flip-flop resets or
returns to the state it had before the power interruption.
The trip matrix logic function has 3 output signals and these RESET input has priority.
outputs can be connected to physical tripping outputs
according to the specific application needs for settable pulse • SRMEMORY function block is a flip-flop that can set or
or steady output. reset an output from two inputs respectively. Each block
has two outputs where one is inverted. The memory setting
Group alarm logic function ALMCALH controls if, after a power interruption, the flip-flop resets or
GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v4
The group alarm logic function (ALMCALH) is used to route returns to the state it had before the power interruption.
several alarm signals to a common indication, LED and/or The SET input has priority.
contact, in the IED.
• TIMERSET function has pick-up and drop-out delayed
Group warning logic function WRNCALH outputs related to the input signal. The timer has a settable
GUID-F7D9A012-3AD4-4D86-BE97-DF2A99BE5383 v4
The group warning logic function (WRNCALH) is used to route time delay.
several warning signals to a common indication, LED and/or
contact, in the IED. • XOR is used to generate combinatory expressions with
boolean variables. XOR has two inputs and two outputs.
Group indication logic function INDCALH One of the outputs is inverted. The output signal OUT is 1 if
GUID-D8D1A4EE-A87F-46C6-8529-277FC1ADA9B0 v4
The group indication logic function (INDCALH) is used to the input signals are different and 0 if they are the same.
route several indication signals to a common indication, LED
and/or contact, in the IED.
Configurable logic blocks Q/T
GUID-0CA6511A-E8BD-416E-9B59-5C6BD98C60B7 v5
Basic configurable logic blocks The configurable logic blocks QT propagate the time stamp
M11396-4 v16
The basic configurable logic blocks do not propagate the time and the quality of the input signals (have suffix QT at the end
stamp and quality of signals (have no suffix QT at the end of of their function name).
their function name). A number of logic blocks and timers are
The function blocks assist the user to adapt the IEDs'
always available as basic for the user to adapt the
configuration to the specific application needs. The list below
configuration to the specific application needs. The list below
shows a summary of the function blocks and their features.
shows a summary of the function blocks and their features.
• ANDQT AND function block. The function also
These logic blocks are also available as part of an extension
propagates the time stamp and the quality of input
logic package with the same number of instances.
signals. Each block has four inputs and two outputs
• AND function block. The AND function is used to form where one is inverted.
general combinatory expressions with boolean variables.
• INDCOMBSPQT combines single input signals to group
The AND function block has up to four inputs and two
signal. Single position input is copied to value part of
outputs. One of the outputs is inverted.
SP_OUT output. TIME input is copied to time part of
• GATE function block is used for whether or not a signal SP_OUT output. Quality input bits are copied to the
should be able to pass from the input to the output. corresponding quality part of SP_OUT output.
34 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
signal input. The value part of single position input is The Fixed signals function (FXDSIGN) has nine pre-set (fixed)
copied to SI_OUT output. The time part of single signals that can be used in the configuration of an IED, either
position input is copied to TIME output. The quality bits for forcing the unused inputs in other function blocks to a
in the common part and the indication part of inputs certain level/value, or for creating certain logic. Boolean,
signal are copied to the corresponding quality output. integer, floating point, string types of signals are available.
• INVALIDQT function which sets quality invalid of outputs One FXDSIGN function block is included in all IEDs.
according to a "valid" input. Inputs are copied to
Elapsed time integrator with limit transgression and overflow
outputs. If input VALID is 0, or if its quality invalid bit is
supervision TEIGAPC
set, all outputs invalid quality bit will be set to invalid. GUID-2D64874A-F266-4251-8EED-E813F40513D7 v3
The Elapsed time integrator function (TEIGAPC) is a function
The time stamp of an output will be set to the latest time
that accumulates the elapsed time when a given binary signal
stamp of INPUT and VALID inputs.
has been high.
• INVERTERQT function block that inverts the input signal
The main features of TEIGAPC
and propagates the time stamp and the quality of the
input signal. • Applicable to long time integration (≤999 999.9
seconds).
• ORQT OR function block that also propagates the time
• Supervision of limit transgression conditions and
stamp and the quality of the input signals. Each block
overflow.
has six inputs and two outputs where one is inverted.
• Possibility to define a warning or alarm with the
• PULSETIMERQT Pulse timer function block can be used, resolution of 10 milliseconds.
for example, for pulse extensions or limiting of operation • Retaining of the integration value.
of outputs. The function also propagates the time stamp • Possibilities for blocking and reset.
and the quality of the input signal. • Reporting of the integrated time.
ABB 35
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
value. It is a basic arithmetic function that can be used for The Disturbance report function is characterized by great
monitoring, supervision, interlocking and other logics. flexibility regarding configuration, starting conditions,
recording times, and large storage capacity.
Disturbance report (DRPRDRE), always included in the IED, The Indication list function shows all selected binary input
acquires sampled data of all selected analog input and binary signals connected to the Disturbance recorder function that
signals connected to the function block with a maximum of have changed status during a disturbance.
40 analog and 352 binary signals.
Event recorder DRPRDRE
M12033-3 v8
The Disturbance report functionality is a common name for Quick, complete and reliable information about disturbances
several functions: in the primary and/or in the secondary system is vital, for
example, time-tagged events logged during disturbances.
• Event list This information is used for different purposes in the short
• Indications term (for example corrective actions) and in the long term (for
• Event recorder example functional analysis).
• Trip value recorder
• Disturbance recorder The event recorder logs all selected binary input signals
• Fault locator connected to the Disturbance recorder function. Each
• Settings information recording can contain up to 150 time-tagged events.
36 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
disturbance record (Comtrade file). Generic communication function for Single Point indication
(SPGAPC) is used to send one single logical signal to other
Trip value recorder DRPRDRE systems or equipment in the substation.
M12128-3 v7
Information about the pre-fault and fault values for currents
and voltages are vital for the disturbance evaluation. Generic communication function for measured values
MVGAPC
SEMOD55872-5 v10
The Trip value recorder calculates the values of all selected Generic communication function for measured values
analog input signals connected to the Disturbance recorder (MVGAPC) function is used to send the instantaneous value
function. The result is magnitude and phase angle before and of an analog signal to other systems or equipment in the
during the fault for each analog input signal. substation. It can also be used inside the same IED, to attach
a RANGE aspect to an analog value and to permit
The trip value recorder information is available for the measurement supervision on that value.
disturbances locally in the IED.
Measured value expander block RANGE_XP
The trip value recorder information is an integrated part of the
SEMOD52450-4 v7
The current and voltage measurements functions (CVMMXN,
disturbance record (Comtrade file). CMMXU, VMMXU and VNMMXU), current and voltage
sequence measurement functions (CMSQI and VMSQI) and
Disturbance recorder DRPRDRE
M12156-3 v11 IEC 61850 generic communication I/O functions (MVGAPC)
The Disturbance recorder function supplies fast, complete
are provided with measurement supervision functionality. All
and reliable information about disturbances in the power
measured values can be supervised with four settable limits:
system. It facilitates understanding system behavior and
low-low limit, low limit, high limit and high-high limit. The
related primary and secondary equipment during and after a
measure value expander block (RANGE_XP) has been
disturbance. Recorded information is used for different
introduced to enable translating the integer output signal from
purposes in the short perspective (for example corrective
the measuring functions to 5 binary signals: below low-low
actions) and long perspective (for example functional
limit, below low limit, normal, above high limit or above high-
analysis).
high limit. The output signals can be used as conditions in the
The Disturbance recorder acquires sampled data from configurable logic or for alarming purpose.
selected analog and binary signals connected to the
Insulation supervision for gas medium function SSIMG
Disturbance recorder function (maximum 40 analog and 352 GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6
Insulation supervision for gas medium (SSIMG) is used for
binary signals). The binary signals available are the same as
monitoring the circuit breaker condition. Binary information
for the event recorder function.
based on the gas pressure in the circuit breaker is used as
The function is characterized by great flexibility and is not input signals to the function. In addition, the function
dependent on the operation of protection functions. It can generates alarms based on received information.
record disturbances not detected by protection functions. Up
Insulation supervision for liquid medium SSIML
to ten seconds of data before the trigger instant can be saved GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v6
Insulation supervision for liquid medium (SSIML) is used for
in the disturbance file.
monitoring the transformer condition. Binary information
The disturbance recorder information for up to 100 based on the oil level in the transformer is used as input
disturbances are saved in the IED and the local HMI is used signals to the function. In addition, the function generates
to view the list of recordings. alarms based on received information.
Generic communication function for Single Point indication Fault locator LMBRFLO
M13970-3 v13
ABB 37
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
The fault locator is an impedance measuring function giving taken through sensors or the one calculated by the function.
the distance to the fault in km, miles or % of line length. The This decision is made based on the top oil temperature
main advantage is the high accuracy achieved by sensor quality. Top oil temperature calculation is done using
compensating for load current and for the mutual zero- the method explained in IEC 60076-7 standard.
sequence effect on double circuit lines.
Inputs required for hot spot temperature calculation are:
The compensation includes setting of the remote and local • Transformer oil time constant
sources and calculation of the distribution of fault currents • Winding time constant
from each side. This distribution of fault current, together with • Loss ratio at different tap positions
recorded load (pre-fault) currents, is used to exactly calculate • Ambient temperature around the transformer
the fault position. The fault can be recalculated with new
source data at the actual fault to further increase the
The oil and winding time constants can be calculated by the
accuracy.
function based on transformer parameters if the inputs are
Especially on heavily loaded long lines, where the source not available from the transformer manufacturer.
voltage angles can be up to 35-40 degrees apart, the
Ambient temperature to the function can either be provided
accuracy can be still maintained with the advanced
through the sensor or monthly average ambient temperature
compensation included in fault locator.
settings. This decision is made based on the ambient
Event counter with limit supervison L4UFCNT temperature sensor quality. Additionally, LOLSPTR function
GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v6
The Limit counter (L4UFCNT) provides a settable counter with provides difference between measured value and calculated
four independent limits where the number of positive and/or value of the top oil temperature.
negative flanks on the input signal are counted against the
Additionally, the function calculates loss of life in form of days
setting values for limits. The output for each limit is activated
and years. This information is updated at settable intervals,
when the counted value reaches that limit.
for example, hourly or daily. Transformer winding percentage
Overflow indication is included for each up-counter. loss of life is calculated every day and the information is
provided as total percentage loss of life from the installation
Running hour-meter TEILGAPC date and yearly percentage loss of life.
GUID-464FB24F-B367-446C-963A-A14841943B87 v2
The Running hour-meter (TEILGAPC) function is a function
that accumulates the elapsed time when a given binary signal
15. Metering
has been high.
Pulse-counter logic PCFCNT
The main features of TEILGAPC are: M13394-3 v7
Pulse-counter logic (PCFCNT) function counts externally
• Applicable to very long time accumulation (≤ 99999.9 generated binary pulses, for instance pulses coming from an
hours) external energy meter, for calculation of energy consumption
• Supervision of limit transgression conditions and rollover/ values. The pulses are captured by the binary input module
overflow and then read by the PCFCNT function. A scaled service
• Possibility to define a warning and alarm with the value is available over the station bus. The special Binary
resolution of 0.1 hours input module with enhanced pulse counting capabilities must
• Retain any saved accumulation value at a restart be ordered to achieve this functionality.
• Possibilities for blocking and reset
Function for energy calculation and demand handling
• Possibility for manual addition of accumulated time
ETPMMTR
• Reporting of the accumulated time GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v3
Power system measurement (CVMMXN) can be used to
measure active as well as reactive power values. Function for
Estimation of transformer winding insulation life LOLSPTR energy calculation and demand handling (ETPMMTR) uses
GUID-CDE89397-8E99-4873-9701-FF642101A308 v2
Estimation of transformer winding insulation life (LOLSPTR) is measured active and reactive power as input and calculates
used to calculate transformer winding hot spot temperature the accumulated active and reactive energy pulses, in forward
using the empirical formulae. It is also used to estimate and reverse direction. Energy values can be read or
transformer loss of life from the winding hot spot temperature generated as pulses. Maximum demand power values are
value. The transformer winding insulation is degraded when also calculated by the function. This function includes zero
the winding hot spot temperature exceeds certain limit. point clamping to remove noise from the input signal. As
LOLSPTR gives warning and alarm signals when the winding output of this function: periodic energy calculations,
hot spot temperature reaches a set value. integration of energy values, calculation of energy pulses,
alarm signals for limit violation of energy values and maximum
Hot spot temperature calculation requires top oil temperature power demand, can be found.
at a given time. This value can either be a measured value
38 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
The values of active and reactive energies are calculated from • Graphical display capable of showing a user defined single
the input power values by integrating them over a selected line diagram and provide an interface for controlling
time tEnergy. The integration of active and reactive energy switchgear.
values will happen in both forward and reverse directions. • Navigation buttons and five user defined command buttons
These energy values are available as output signals and also to shortcuts in the HMI tree or simple commands.
as pulse outputs. Integration of energy values can be • 15 user defined three-color LEDs.
controlled by inputs (STARTACC and STOPACC) and EnaAcc • Communication port for PCM600.
setting and it can be reset to initial values with RSTACC
input.
The LHMI is used for setting, monitoring and controlling.
The maximum demand for active and reactive powers are
calculated for the set time interval tEnergy and these values 17. Basic IED functions
are updated every minute through output channels. The
active and reactive maximum power demand values are Time synchronization
M11344-3 v10
calculated for both forward and reverse direction and these The time synchronization function is used to select a common
values can be reset with RSTDMD input. source of absolute time for the synchronization of the IED
when it is a part of a control and a protection system. This
makes it possible to compare events and disturbance data
16. Human machine interface between all IEDs within a station automation system and in
between sub-stations. A common source shall be used for
Local HMI IED and merging unit when IEC/UCA 61850-9-2LE process
AMU0600442 v14
bus communication is used.
M11345-3 v10
18. Ethernet
Access points
GUID-6E5D2696-A8EE-43E7-A94B-69C3D0612127 v1
An access point is an Ethernet communication interface for
single or redundant station communication. Each access
point is allocated with one physical Ethernet port, two
physical Ethernet ports are allocated if redundant
communication is activated for the access point.
IEC13000239-3-en.vsd
IEC13000239 V3 EN-US
The LHMI of the IED contains the following elements: SFP_301 SFP_302 SFP_303 SFP_301 SFP_302 SFP_303
IEC16000092-1-en.vsdx
IEC16000092 V1 EN-US
ABB 39
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
DHCP is available for the front port, and a device connected systems or equipment, either on the Substation Automation
to it can thereby obtain an automatically assigned IP-address. (SA) bus or Substation Monitoring (SM) bus.
Redundant communication according to IEC 62439-3 PRP-0, IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in
IEC 62439-3 PRP-1 parallel redundancy protocol (PRP) is PCM600. The IED is equipped with up to six (order
available as an option when ordering IEDs. PRP according to dependent) optical Ethernet rear ports for IEC 61850-8-1
IEC 62439-3 uses two optical Ethernet ports. station bus communication. The IEC 61850-8-1
communication is also possible from the electrical Ethernet
IEC 62439-3 High-availability seamless redundancy HSR front port. IEC 61850-8-1 protocol allows intelligent electrical
Redundant station bus communication according to IEC devices (IEDs) from different vendors to exchange information
62439-3 Edition 2 High-availability seamless redundancy and simplifies system engineering. IED-to-IED communication
(HSR) is available as an option when ordering IEDs. using GOOSE and client-server communication over MMS are
Redundant station bus communication according to IEC supported. Disturbance recording file (COMTRADE) uploading
62439-3 uses two optical Ethernet ports. can be done over MMS or FTP.
The HSR ring supports the connection of up to 30 relays. If IEC 61850 quality expander QUALEXP
GUID-9C5DC78E-041B-422B-9668-320E62B847A2 v1
more than 30 relays are to be connected, it is recommended The quality expander component is used to display the
to split the network into several rings to guarantee the detailed quality of an IEC/UCA 61850-9-2LE analog channel.
performance for real-time applications. The component expands the channel quality output of a
Merging Unit analog channel received in the IED as per the
Routes IEC 61850-7-3 standard. This component can be used during
GUID-95F9C7BA-92F8-489F-AD0A-047410B5E66F v1
A route is a specified path for data to travel between the the ACT monitoring to get the particular channel quality of the
source device in a subnetwork to the destination device in a Merging Unit.
different subnetwork. A route consists of a destination
address and the address of the gateway to be used when IEC/UCA 61850-9-2LE communication protocol
GUID-C3AA21B4-730F-4327-943A-3C77102A80A0 v4
sending data to the destination device, see Figure 7. Optical Ethernet port communication standard IEC/UCA
61850-9-2LE for process bus is supported. IEC/UCA
61850-9-2LE allows Non Conventional Instrument
Transformers (NCIT) with Merging Units (MUs) or stand-alone
MUs to exchange information with the IED, and simplifies SA
engineering. IEC/UCA 61850-9-2LE uses the same port as
Default gateway IEC 61850-8-1.
Gateway Existing stations with ABB station bus LON can be extended
with use of the optical LON interface (glass or plastic). This
Source Destination allows full SA functionality including peer-to-peer messaging
IEC16000095 V1 EN-US
IEC16000095-1-en.vsdx
and cooperation between the IEDs.
Figure 7. Route from source to destination through gateway
SPA communication protocol
SEMOD120134-5 v1
A single glass or plastic port is provided for the ABB SPA
protocol. This allows extensions of simple substation
automation systems but the main use is for Substation
19. Station communication
Monitoring Systems SMS.
Communication protocols
M14815-3 v13
Each IED is provided with several communication interfaces
enabling it to connect to one or many substation level
40 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
In 64kbit/s mode, the LDCM can be configured to work in The static binary output module has six fast static outputs
either analog mode or binary mode. In analog mode, the IED and six change over output relays for use in applications with
can send and receive up to 3 analog signals and up to 8 high speed requirements.
binary signals. In binary mode, the LDCM can send and
Binary input/output module IOM
receive only binary data (up to 192 binary signals). M6939-3 v6
The binary input/output module is used when only a few input
The IED can be equipped with up to two short range, medium and output channels are needed. The ten standard output
range or long range LDCMs. channels are used for trip output or any signaling purpose.
The two high speed signal output channels are used for
Line data communication module, short, medium and long applications where short operating time is essential. Eight
range LDCM optically isolated binary inputs cater for required binary input
SEMOD168481-4 v10
The line data communication module (LDCM) is used for information.
communication between the IEDs situated at a distance <110
km/68 miles or from the IED to the optical-to-electrical mA input module MIM
M15020-3 v4
converter with G.703 or G.703E1 interface located at a The milli-ampere input module is used to interface transducer
distance < 3 km/1.9 miles away. The LDCM module sends signals in the –20 to +20 mA range from for example OLTC
and receives data to and from another LDCM module. The position, temperature or pressure transducers. The module
IEEE/ANSI C37.94 standard format is used. has six independent, galvanically separated channels.
separated signals for RX and TX multidrop communication Figure 8. Case with rear cover
with a dedicated Master and the rest are slaves. No special
control signal is needed in this case.
Electrical (BNC) and optical connection (ST) for 0XX and 12X
IRIG-B support.
High impedance resistor unit Figure 9. Case with rear cover and 19” rack mounting kit
M16727-3 v2
The high impedance resistor unit, with resistors for pick-up
value setting and a voltage dependent resistor, is available in
a single phase unit and a three phase unit. Both are mounted
on a 1/1 19 inch apparatus plate with compression type
terminals.
ABB 43
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M15243-12 v9
IEC06000182-2-en.vsd
IEC06000182 V2 EN-US
Case size A B C D E F G H J K
(mm)/(inches)
6U, 1/2 x 19” 265.9/ 223.7/ 242.1/ 255.8/ 205.7/ 190.5/ 203.7/ - 228.6/ -
10.47 8.81 9.53 10.07 8.10 7.50 8.02 9.00
6U, 3/4 x 19” 265.9/ 336.0/ 242.1/ 255.8/ 318.0/ 190.5/ 316.0/ - 228.6/ -
10.47 13.23 9.53 10.07 12.52 7.50 12.4 9.00
6U, 1/1 x 19” 265.9/ 448.3/ 242.1/ 255.8/ 430.3/ 190.5/ 428.3/ 465.1/ 228.6/ 482.6/19.00
10.47 17.65 9.53 10.07 16.86 7.50 16.86 18.31 9.00
The H and K dimensions are defined by the 19” rack mounting kit.
Mounting alternatives See ordering for details about available mounting alternatives.
M16079-3 v13
• 19” rack mounting kit
• Flush mounting kit with cut-out dimensions:
– 1/2 case size (h) 254.3 mm/10.01” (w) 210.1 mm/
8.27”
– 3/4 case size (h) 254.3 mm/10.01” (w) 322.4 mm/
12.69”
– 1/1 case size (h) 254.3 mm/10.01” (w) 434.7 mm/
17.11”
• Wall mounting kit
44 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
The latest versions of the connection diagrams can be Connection diagram, REC670 2.2, C30X00 1MRK002807-CC
downloaded from http://www.abb.com/protection-control.
Connection diagram, REC670 2.2, D30X00 1MRK002807-CE
Connection diagrams for IEC Customized products
Connection diagrams for ANSI Customized products
Connection diagram, 670 series 2.2 1MRK002801-AG
Connection diagram, 670 series 2.2 1MRK002802-AG
Connection diagrams for Configured products
ABB 45
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
General
M10993-1 v3 IP11376-1 v2
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Presumptions for Technical Data 6. Parameter SBase used by the tested function is set
GUID-1E949E38-E04D-4374-A086-912C25E9F93C v1
The technical data stated in this document are only valid equal to:
under the following circumstances: – √3 × IBase × UBase
7. The rated secondary quantities have the following
1. Main current transformers with 1 A or 2 A secondary values:
rating are wired to the IED 1 A rated CT inputs. – Rated secondary phase current I r is either 1 A or 5 A
2. Main current transformer with 5 A secondary rating are
depending on selected TRM.
wired to the IED 5 A rated CT inputs.
– Rated secondary phase-to-phase voltage U r is within
3. CT and VT ratios in the IED are set in accordance with
the range from 100 V to 120 V.
the associated main instrument transformers. Note that
– Rated secondary power for three-phase system S r =
for functions which measure an analogue signal which
√3 × U r × Ir
do not have corresponding primary quantity the 1:1 ratio
shall be set for the used analogue inputs on the IED. 8. For operate and reset time testing, the default setting
Example of such functions are: HZPDIF, ROTIPHIZ and values of the function are used if not explicitly stated
STTIPHIZ. otherwise.
4. Parameter IBase used by the tested function is set 9. During testing, signals with rated frequency have been
equal to the rated CT primary current. injected if not explicitly stated otherwise.
5. Parameter UBase used by the tested function is set
equal to the rated primary phase-to-phase voltage.
46 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Table 11. TRM - Energizing quantities, rated values and limits for protection transformer
Description Value
Frequency
Current inputs
Rated current Ir 1 or 5 A
Note! All current and voltage data are specified as RMS values at rated frequency
ABB 47
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Table 12. TRM - Energizing quantities, rated values and limits for measuring transformer
Description Value
Frequency
Current inputs
Rated current Ir 1A 5A
Voltage inputs *)
Note! All current and voltage data are specified as RMS values at rated frequency
M6389-1 v5
Power consumption -
each mA board £2W
each mA input £ 0.1 W
SEMOD55310-2 v11
Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for
communication using any protocol
48 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Table 15. SFP - Galvanic RJ45 Table 15. SFP - Galvanic RJ45, continued
Quantity Rated value
Quantity Rated value
Connector Type RJ45
Number of Up to 6 single or 3 redundant or a combination of single
channels and redundant links for communication using any Communi Fast Ethernet 100 Mbit/s
protocol cation
Speed
Standard IEEE 802.3u 100BASE-TX
Auxiliary DC voltage
M12286-1 v6 IP15843-1 v3
Binary inputs 16 -
Power consumption
24/30 V, 50 mA max. 0.05 W/input -
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
ABB 49
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M50609-2 v7
Table 18. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Binary inputs 8 -
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
50 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M12318-1 v8
Table 20. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
ABB 51
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M12584-1 v7
BOM/IOM/SOM should be activated
continuously due to power dissipation.
Table 21. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
52 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
SEMOD175395-2 v7
BOM/IOM/SOM should be activated
continuously due to power dissipation.
Table 22. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Number of outputs 6 6
Test voltage across open contact, 1 min No galvanic separation No galvanic separation
Continuous 5A 5A
1.0 s 10 A 10 A
0.2 s 30 A 30 A
1.0 s 10 A 10 A
220 V/0.2 A
250 V/0.15 A
ABB 53
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Table 23. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Number of outputs 6
Continuous 8A
1.0 s 10 A
0.2 s 30 A
1.0 s 10 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
M12441-1 v8
Table 24. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Binary outputs 24
Influencing factors
M16705-1 v12 IP15846-1 v1
54 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
100-250 V DC ±20%
Interruption
interval
0–50 ms No restart
Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fr ±2.0%
Harmonic frequency dependence for high impedance differential 2nd, 3rd and 5th harmonic of fr ±10.0%
protection (10% content)
Harmonic frequency dependence for overcurrent protection 2nd, 3rd and 5th harmonic of fr ±3.0%
ABB 55
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV
Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.
Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Class V
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V
1.4-2.7 GHz
56 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Change of temperature test Test Nb for 5 cycles at -25°C to +70°C IEC 60068-2-14
Damp heat test, steady state Test Ca for 10 days at +40°C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and humidity 93 to 95% (1 cycle = IEC 60068-2-30
24 hours)
Test According to
Immunity EN 60255–26
Emissivity EN 60255–26
ABB 57
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Differential protection
M13081-1 v12
58 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Table 34. Protocol reporting via IEEE 1344 and C37.118 PMUREPORT
Signal magnitude:
Voltage phasor (0.1–1.2) x Ur
Current phasor (0.5–2.0) x Ir
Interfering signal:
Magnitude 10% of fundamental signal
Minimum frequency 0.1 x fr
Maximum frequency 1000 Hz
ABB 59
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Current protection
M12336-1 v13
60 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M12342-1 v20
Independent time delay at 0 to 2 x Iset, step (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
1-4
Minimum operate time for inverse curves , (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
step 1-4
Inverse time characteristics, see table 155, 16 curve types See table 155, table 156 and table 157
table 156 and table 157
Max. = 30 ms
ABB 61
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M15223-1 v17
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
Independent time delay at 0 to 2 x Iset, step (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
1-4
Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
step 1-4
Inverse time characteristics, see Table 155, 16 curve types See Table 155, Table 156 and Table 157
Table 156 and Table 157
62 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6
Table 39. Four step directional negative phase sequence overcurrent protection NS4PTOC
Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
step 1 - 4
Inverse time characteristics, see table 16 curve types See table 155, table 156 and table 157
155, table 156 and table 157
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
ABB 63
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
SEMOD173350-2 v16
Table 40. Sensitive directional residual overcurrent and power protection SDEPSDE
Independent time delay for non-directional (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is greater
residual overvoltage at 0.8 x Uset to 1.2 x Uset
Independent time delay for non-directional (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is greater
residual overcurrent at 0 to 2 x Iset
Independent time delay for directional (0.000 – 60.000) s ±0.2% or ± 170 ms whichever is greater
residual overcurrent at 0 to 2 x Iset
Inverse characteristics, see table 158, 16 curve types See Table 158, Table 159 and Table 160
Table 159 and Table 160
64 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M12352-1 v14
Operate time: Time constant t = (1–1000) IEC 60255-149, ±5.0% or ±200 ms whichever is greater
minutes
é ù
ê I - Ip
2 2 ú
t = t ln ê ú
ê 2 2 TTrip - TAmb 2 ú
ê I - Ip - T × I ref
ú
ë ref û
EQUATION13000039 V2 EN-US (Equation 1)
Operate time: Ip = load current before overload ±5.0% or ±200 ms whichever is greater
occurs
æ I 2 - I p2 ö Time constant τ = (0.10–500.00)
t = t × ln ç 2 ÷ minutes
ç I - I ref 2 ÷
è ø
EQUATION1356 V2 EN-US (Equation 2)
Alarm level 1 and 2 (50–99)% of heat content ±2.0% of heat content trip
operate value
Reset level temperature (10–95)% of heat content trip ±2.0% of heat content trip
ABB 65
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M12353-1 v14
Phase current level for blocking of contact function (5-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir
Time delay for re-trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Time delay for back-up trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Time delay for back-up trip at multi-phase start at (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
0 to 2 x Iset
Additional time delay for a second back-up trip at (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
0 to 2 x Iset
Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
M12350-1 v12
66 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
SEMOD175152-2 v11
S r = 1.732 × U r × I r
Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 2 x Sr to 0.5 x Sr and k=0.000
SEMOD175159-2 v9
Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 0.5 x Sr to 2 x Sr and k=0.000
SEMOD175200-2 v7
ABB 67
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-6A7DA510-E145-4C5B-A7DC-97BC4258E621 v9
Inverse time characteristic According to IEC 60871-1 (2005) and ±20% or ±200 ms whichever is greater
IEEE/ANSI C37.99 (2000)
68 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8
Max. = 30 ms
Max. = 30 ms
Independent time delay to operate at 0 to 2 x (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
Iset
Inverse time characteristics, 13 curve types See tables 155 and 156
see tables 155 and 156
Minimum operate time for inverse time (0.00 - 60.00) s ±0.2% or ±35 ms whichever is greater
characteristics
Max. = 30 ms
Independent time delay to operate, (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
undervoltage at 2 x Uset to 0
Overcurrent: -
Critical impulse time 10 ms typically at 0 to 2 x Iset
Impulse margin time 15 ms typically
Undervoltage: -
Critical impulse time 10ms typically at 2 x Uset to 0
Impulse margin time 15 ms typically
ABB 69
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Voltage protection
M13290-1 v15
Definite time delay, step 1 at 1.2 x Uset to (0.00-6000.00) s ±0.2% or ±40ms whichever is greater
0
Definite time delay, step 2 at 1.2 x Uset to (0.000-60.000) s ±0.2% or ±40ms whichever is greater
0
70 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M13304-1 v14
Definite time delay, low step (step 1) at 0 (0.00 - 6000.00) s ±0.2% or ±45 ms whichever is greater
to 1.2 x Uset
Definite time delay, high step (step 2) at 0 (0.000-60.000) s ±0.2% or ±45 ms whichever is greater
to 1.2 x Uset
ABB 71
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M13317-2 v14
Definite time delay low step (step 1) at 0 (0.00–6000.00) s ± 0.2% or ± 45 ms whichever is greater
to 1.2 x Uset
Definite time delay high step (step 2) at 0 (0.000–60.000) s ± 0.2% or ± 45 ms whichever is greater
to 1.2 x Uset
Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
differential alarm at 0.8 x UDAlarm to 1.2 x
UDAlarm
Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
differential trip at 0.8 x UDTrip to 1.2 x
UDTrip
Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
differential reset at 1.2 x UDTrip to 0.8 x
UDTrip
72 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
SEMOD175210-2 v6
Time delay for enabling the (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
functions after restoration
Time delay to block when all (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
three phase voltages are not low
ABB 73
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Frequency protection
M13360-1 v15
Operate time, definite time function at fset + 0.02 Hz (0.000-60.000)s ±0.2% or ±100 ms whichever is greater
to fset - 0.02 Hz
Reset time, definite time function at fset - 0.02 Hz to (0.000-60.000)s ±0.2% or ±120 ms whichever is greater
fset + 0.02 Hz
Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû
EQUATION1182 V1 EN-US (Equation 3)
U=Umeasured
M14964-1 v12
Operate value, start function at symmetrical three-phase voltage (35.00-90.00) Hz ±2.0 mHz
Min. = 65 ms
fn = 60 Hz
Max. = 80 ms
Operate time, definite time function at fset -0.02 Hz to fset +0.02 Hz (0.000-60.000)s ±0.2% ±100 ms
whichever is greater
Reset time, definite time function at fset +0.02 Hz to fset -0.02 Hz (0.000-60.000)s ±0.2% ±120 ms,
whichever is greater
74 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M14976-1 v9
Definite time delay for frequency gradient trip (0.200-60.000) s ±0.2% or ±120 ms whichever is
greater
Operate value, frequency high limit level at (35.00 – 90.00) Hz ±2.0 mHz
symmetrical three phase voltage
Operate value, voltage high and low limit (0.0 – 200.0)% of UBase ±0.5% of Ur at U ≤ Ur
for voltage band limit check ±0.5% of U at U > Ur
Operate value, current start level (5.0 – 100.0)% of IBase ±1.0% of Ir or 0.01 A at I≤Ir
Independent time delay for the continuous (0.0 – 6000.0) s ±0.2% or ±250 ms whichever is
time limit at fset+0.02 Hz to fset-0.02 Hz greater
Independent time delay for the (10.0 – 90000.0) s ±0.2% or ±250 ms whichever is
accumulation time limit at fset+0.02 Hz to greater
fset-0.02 Hz
ABB 75
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Multipurpose protection
M13095-2 v8
76 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Independent time delay, overcurrent at 0 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
to 2 x Iset, step 1 - 2
Independent time delay, undercurrent at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
2 x Iset to 0, step 1 - 2
Overcurrent (non-directional):
Undercurrent:
Overcurrent:
Inverse time characteristics, see table 16 curve types See table 155, 156 and table 157
155, 156 and table 157
Overcurrent:
Minimum operate time for inverse curves, (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
step 1 - 2
ABB 77
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Independent time delay, overvoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
0.8 x Uset to 1.2 x Uset, step 1 - 2
Independent time delay, undervoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
1.2 x Uset to 0.8 x Uset, step 1 - 2
Overvoltage:
Undervoltage:
Overvoltage:
Inverse time characteristics, see table 4 curve types See table 163
163
Undervoltage:
Inverse time characteristics, see table 3 curve types See table 164
164
High and low voltage limit, voltage (1.0 - 200.0)% of UBase ±1.0% of Ur at U ≤ Ur
dependent operation, step 1 - 2 ±1.0% of U at U > Ur
Overcurrent:
Undercurrent:
Overvoltage:
78 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Undervoltage:
ABB 79
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
80 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5
Max. = 15 ms
Max. = 30 ms
Operate value, alarm for pilot fuse failure (10.0-80.0)% of UBase ±0.5% of Ur
Max. = 15 ms
Max. = 30 ms
ABB 81
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Control
M12359-1 v15
Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz ±2.5 mHz
Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees ±2.0 degrees
Voltage difference limit between bus and line for synchronizing and (0.02-0.5) p.u ±0.5% of Ur
synchrocheck
Time delay output for synchrocheck when angle difference between bus (0.000-60.000) s ±0.2% or ±35 ms whichever is
and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees greater
Maximum closing angle between bus and line for synchronizing (15-30) degrees ±2.0 degrees
tMaxSynch, which resets synchronizing function if no close has been (0.000-6000.00) s ±0.2% or ±35 ms whichever is
made before set time greater
Time delay for energizing check when voltage jumps from 0 to 90% of (0.000-60.000) s ±0.2% or ±100 ms whichever is
Urated greater
Operate time for synchrocheck function when angle difference between Min. = 15 ms –
bus and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 Max. = 30 ms
degrees
Operate time for energizing function when voltage jumps from 0 to 90% Min. = 70 ms –
of Urated Max. = 90 ms
82 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M12379-1 v13
Dead time:
shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms
shot 1 “t1 2Ph” whichever is greater
shot 1 “t1 3Ph “
shot 1 “t1 3PhHS”
Extend three-phase dead time duration “tExtended t1” (0.000-60.000) s ±0.2% or ±35 ms
whichever is greater
Minimum time that circuit breaker must be closed before new sequence is allowed (0.00-6000.00) s ±0.2% or ±35 ms
“tCBClosedMin” whichever is greater
Wait time for the slave to close when WAIT input has reset “tSlaveDeadTime” (0.100-60.000) s ±0.2% or ±35 ms
whichever is greater
Maximum wait time for release from master “tWaitForMaster” (0.00-6000.00) s ±0.2% or ±15 ms
whichever is greater
Wait time after close command before proceeding to next shot “tAutoContWait” (0.000-60.000) s ±0.2% or ±45 ms
whichever is greater
Maximum wait time for fulfilled synchrocheck conditions “tSync” (0.00-6000.00) s ±0.2% or ±45 ms
whichever is greater
Delay time before indicating successful reclosing “tSuccessful” (0.000-60.000) s ±0.2% or ±50 ms
whichever is greater
Maximum wait time for circuit breaker closing before indicating unsuccessful “tUnsucCl” (0.00-6000.00) s ±0.2% or ±45 ms
whichever is greater
ABB 83
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
SEMOD175215-2 v14
Time delay for lower command when fast step down mode is activated (1.0–100.0) s -
Time delay (long) for automatic control commands (3–1000) s ±0.2% or ±600 ms
whichever is greater
Time delay (short) for automatic control commands (1–1000) s ±0.2% or ±600 ms
whichever is greater
Duration time for the reverse action block signal (30–6000) s ±0.2% or ±600 ms
whichever is greater
Level for number of counted raise/lower within one hour (0–30) operations/hour -
Alarm level of active power in forward and reverse direction at (-9999.99–9999.99) MW ±1.0% of Sr
(10-200)% of Sr and (85-120)% of UBase
Alarm level of reactive power in forward and reverse direction at (-9999.99–9999.99) MVAr ±1.0% of Sr
(10-200)% of Sr and (85-120)% of UBase
Time delay for alarms from power supervision (1–6000) s ±0.2% or ±600 ms
whichever is greater
84 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Time after position change before the value is accepted (1–60) s ±0.2% or ±200 ms
whichever is greater
ABB 85
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Scheme communication
M16038-1 v14
Table 67. Scheme communication logic with delta based blocking scheme signal transmit ZCPSCH
Security timer for loss of guard (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
signal detection
Table 68. Current reversal and weak-end infeed logic for distance protection ZCRWPSCH
Operate time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
logic
Delay time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Table 69. Scheme communication logic for residual overcurrent protection ECPSCH
86 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-CC9A02C2-AAE8-4B8C-A091-D4ED584A2EA7 v1
Delay time on pick-up for current release (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
Delay time on drop-off for current release (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
Delay time on pick-up for MinCurr value (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
M16051-2 v11
Table 71. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH
Operate time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
logic
Delay time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
ABB 87
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Logic
M12380-1 v12
3 ms 8 ms 100 ms
SMAGAPC 12 - -
3 ms 8 ms 100 ms
STARTCOMB 32 - -
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
3 ms 8 ms 100 ms
TMAGAPC 6 6 -
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v1
3 ms 8 ms 100 ms
ALMCALH - - 5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v1
3 ms 8 ms 100 ms
WRNCALH - - 5
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v1
3 ms 8 ms 100 ms
INDCALH - 5 -
88 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v2
3 ms 8 ms 100 ms
AND 60 60 160
GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v2
3 ms 8 ms 100 ms
GATE 10 10 20
GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v2
3 ms 8 ms 100 ms
INV 90 90 240
GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v1
3 ms 8 ms 100 ms
LLD 10 10 20
GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v3
3 ms 8 ms 100 ms
OR 78 60 160
GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v1
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
RSMEMORY 10 10 20
GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v1
3 ms 8 ms 100 ms
SRMEMORY 10 10 20
ABB 89
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-C6C98FE0-F559-45EE-B853-464516775417 v2
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
XOR 10 10 20
GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1
3 ms 8 ms 100 ms
ANDQT - 20 100
GUID-27DF23C0-A0B2-4BB0-80B5-FC7B7F7FE448 v1
3 ms 8 ms 100 ms
INDCOMBSPQT - 10 10
GUID-C1E61AE5-22CF-4198-97CF-8C8043EE96D2 v1
3 ms 8 ms 100 ms
INDEXTSPQT - 10 10
GUID-77FEBE9B-0882-4E85-8B1A-7671807BFC02 v2
3 ms 8 ms 100 ms
INVALIDQT 10 6 6
GUID-F25B94C6-9CC9-48A0-A7A3-47627D2B56E2 v1
3 ms 8 ms 100 ms
INVERTERQT - 20 100
GUID-88B27B3C-26D2-47AF-9878-CC19018171B1 v1
3 ms 8 ms 100 ms
ORQT - 20 100
90 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
RSMEMORYQT - 10 30
GUID-341562FB-6149-495B-8A63-200DF16A5590 v1
3 ms 8 ms 100 ms
SRMEMORYQT - 10 30
GUID-B6231B97-05ED-40E8-B735-1E1A50FDB85F v1
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
XORQT - 10 30
ABB 91
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v7
3 ms 8 ms 100 ms
SLGAPC 10 10 54
VSGAPC 10 10 100
AND 40 40 100
OR 40 40 100
PULSETIMER 20 20 49
GATE — — 49
TIMERSET 30 30 49
XOR 10 10 69
LLD — — 49
SRMEMORY 10 10 110
INV 40 40 100
RSMEMORY 10 10 20
GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v2
3 ms 8 ms 100 ms
B16I 6 4 8
GUID-3820F464-D296-4CAD-8491-F3F997359D79 v1
3 ms 8 ms 100 ms
BTIGAPC 4 4 8
GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v1
3 ms 8 ms 100 ms
IB16 6 4 8
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v1
3 ms 8 ms 100 ms
ITBGAPC 4 4 8
92 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v3
Table 105. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
3 ms 8 ms 100 ms
TEIGAPC 4 4 4
GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v2
3 ms 8 ms 100 ms
INTCOMP 10 10 10
GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v3
3 ms 8 ms 100 ms
REALCOMP 10 10 10
ABB 93
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Monitoring
M12386-1 v15
Phase angle at symmetrical load (0.1-4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir
±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir
GUID-374C2AF0-D647-4159-8D3A-71190FE3CFE0 v5
94 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6
ABB 95
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M12760-1 v10
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording time and maximum number of 340 seconds (100 recordings) at -
channels, typical value) 50 Hz, 280 seconds (80
recordings) at 60 Hz
Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
96 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v7
Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v8
Independent time delay for spring charging (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
time alarm
Independent time delay for gas pressure alarm (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
lockout
ABB 97
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-F6B6ED6B-2488-483C-B068-3F4631F34DC8 v1
Operate level , Warning level 1 (50 - 700)°C/°F of hot spot temperature ±2.0% of hot spot temperature
and 2
Operate time, Warning level 1 (50 - 700)°C/°F of hot spot temperature ±200 ms typically
and 2
Function Value
Resolution 1 ms
Function Value
Buffer capacity Maximum number of indications presented for single disturbance 352
Function Value
Resolution 1 ms
Function Value
98 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M12384-1 v7
Function Value
Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100 recordings) at 50 Hz
of channels, typical value) 280 seconds (80 recordings) at 60 Hz
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3
Time limit for alarm supervision, tAlarm (0 - 99999.9) hours ±0.1% of set value
Time limit for warning supervision, tWarning (0 - 99999.9) hours ±0.1% of set value
ABB 99
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Metering
M13404-2 v5
Table 130. Function for energy calculation and demand handling ETPMMTR
Energy metering kWh Export/Import, kvarh Export/ Input from MMXU. No extra error at steady load
Import
100 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Station communication
M15031-1 v8
Function Value
Protocol DNP3.0
Protocol LON
Protocol SPA
Function Value
Function Value
Protocol LON
Function Value
Protocol SPA
Function Value
ABB 101
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M12589-1 v4
Function Value
102 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
M12756-1 v10
Remote communication
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Graded-index
multimode 50/125
µm
Transmission rate / Data rate 2 Mbit/s / 64 kbit/s 2 Mbit/s / 64 kbit/s 2 Mbit/s / 64 kbit/s
ABB 103
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Hardware
IED
M11778-1 v6 SEMOD53385-1 v1
Table 142. Water and dust protection level according to IEC 60529
Electrical safety
GUID-1CF5B10A-CF8B-407D-8D87-F4B48B43C2B2 v1 GUID-2825B541-DD31-4DAF-B5B3-97555F81A1C2 v1
Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by
condensation is to be expected)
Connection system
SEMOD53376-2 v6 SEMOD53371-1 v1
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)
M12583-1 v6
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
104 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v2
connections, one blank slot is necessary
between two adjacent IO modules. Please
refer to the ordering particulars for details.
ABB 105
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Data Value
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled ± 1.0 ms typically
measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
GUID-8AEB81D0-1731-46DF-A206-D2E758823575 v1
Supported types of clock Boundary Clock (BC), Ordinary Clock (OC), Transparent Clock (TC)
Function Value
Accuracy +/-1μs
106 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
SEMOD141136-2 v8
Electrical connector:
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Optical connector:
ABB 107
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Inverse characteristic
M12388-1 v21
Reset characteristic:
tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN-US
I = Imeasured/Iset
108 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
I = Imeasured/Iset
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US
I = Imeasured/Iset
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US
I = Imeasured/Iset
ABB 109
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v3
Table 158. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection
Reset characteristic:
tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN-US
I = Imeasured/Iset
110 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Table 159. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection
I = Imeasured/Iset
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US
I = Imeasured/Iset
Table 160. RI and RD type inverse time characteristics for Sensitive directional residual overcurrent and power protection
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US
I = Imeasured/Iset
ABB 111
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v1
Table 161. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection
Reset characteristic:
tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN-US
I = Imeasured/Iset
Table 162. IEC Inverse time characteristics for Voltage restrained time overcurrent protection
I = Imeasured/Iset
112 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
SEMOD116978-2 v10
U> = Uset
U = Umeasured
k 480
t 2.0
0.035
U Un
32 0.5
Un
IECEQUATION2423 V2 EN-US
k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U> ø
IECEQUATION2421 V1 EN-US
ABB 113
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
U< = Uset
U = Umeasured
k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN-US
U< = Uset
U = Umeasured
U< = Uset
U = Umeasured
114 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
U> = Uset
U = Umeasured
ABB 115
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the selection tables, as given in the example below.
The selected qty of each table must be filled in, if no selection is possible the code is 0.
Example of a complete code: REC670*2.2-F00X00 - A000006000000000 - B00000000000000000000000000 - C6600666666660036221300300 - D22206020 -
E6662 - F9 - S6 - G642 - H26461114444 - K10101110 - L1100 - M614 - P11100000000000100 - B1X0 - AC - CA - B - A3X0 - CD1D1ARGN1N1XXXXXXX -
KKKXXHKKLAGXSY
Impedance protection -
B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -
Current protection -
C 00 00 0 0 0 0 -
Product REC670*
Software version 2.2
Configuration alternative
Bay control REC670 F00
ACT configuration
No ACT configuration downloaded X00
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A 0 0 0 0 0 0 0 0 0 0 0 0 0 0
116 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
C 00 00 0 0 0 0
Position 1 2 3 4 5 6 7 8
D 0 0 0
Position 1 2 3 4
E
ABB 117
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Position 1
F
Position 1
S
Position 1 2 3
G
Position 1 2 3 4 5 6 7 8 9 10 11
H
118 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Position 1 2 3 4 5 6 7 8
K 0 0 0
Position 1 2 3
L 00
Position 1 2 3
M
ABB 119
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
P 0 0 0 0 0 0 0 0 0 0 0 0 0
Mounting details with IP40 of protection from the front Ordering no Selection Notes and rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB A
19" rack mounting kit for 3/4 x 19" case or 3xRHGS6 1MRK002420-BA B
19" rack mounting kit for 1/1 x 19" case 1MRK002420-CA C
Wall mounting kit 1MRK002420-DA D Wall mounting not recommended
with communication modules with
fibre connection
Flush mounting kit 1MRK002420-PA E
Flush mounting kit + IP54 mounting seal 1MRK002420-NA F
Selected
120 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Human machine hardware interface Case size Ordering no Selection Notes and rules
Medium size - graphic display, IEC keypad symbols 1/2 x 19", IEC 1MRK000028-AA B
3/4 x 19”, IEC 1MRK000028-CA
1/1 x 19”, IEC 1MRK000028-BA
Medium size - graphic display, ANSI keypad symbols 1/2 x 19", ANSI 1MRK000028-AB C
3/4 x 19”, ANSI 1MRK000028-CB
1/1 x 19”, ANSI 1MRK000028-BB
Selected
ABB 121
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
P40/X401
P41/X411
No Transformer input module included X0 X0
TRM 12I 1A, 50/60Hz, compression terminals 1MRK002247-CG A1 A1
TRM 12I 5A, 50/60Hz, compression terminals 1MRK002247-CH A2 A2
TRM 9I 1A + 3U 110/220V, 50/60Hz, compression terminals 1MRK002247-BG A3 A3
TRM 9I 5A + 3U 110/220V, 50/60Hz, compression terminals 1MRK002247-BH A4 A4
TRM 5I 1A + 4I 5A + 3U 110/220V, 50/60Hz, compression terminals 1MRK002247-BK A5 A5
TRM 6I 1A + 6U 110/220V, 50/60Hz, compression terminals 1MRK002247-AG A6 A6
TRM 6I 5A + 6U 110/220V, 50/60Hz, compression terminals 1MRK002247-AH A7 A7
TRM 6I 1A, 50/60Hz, compression terminals 1MRK002247-DG A8 A8
TRM 6I 5A, 50/60Hz, compression terminals 1MRK002247-DH A9 A9
TRM 7I 1A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-AP A12 A12
TRM 7I 5A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-AR A13 A13
TRM 6I 5A + 1I 1A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-AU A14 A14
TRM 3I 5A + 4I 1A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-AV A15 A15
TRM 3I 5A + 3I 1A + 6U 110/220V, 50/60Hz, compression terminals 1MRK002247-AE A16 A16
TRM 3IM 1A + 4IP 1A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-EA A17 A17
TRM 3IM 5A + 4IP 5A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-EB A18 A18
TRM 10I 1A + 2U 110/220V, 50/60Hz, compression terminals 1MRK002247-FA A19 A19
TRM 10I 5A + 2U 110/220V, 50/60Hz, compression terminals 1MRK002247-FB A20 A20
TRM 12I 1A, 50/60Hz, ring lug terminals 1MRK002247-CC B1 B1
TRM 12I 5A, 50/60Hz, ring lug terminals 1MRK002247-CD B2 B2
TRM 9I 1A + 3U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-BC B3 B3
TRM 9I 5A + 3U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-BD B4 B4
TRM 5I 1A + 4I 5A + 3U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-BF B5 B5
TRM 6I 1A + 6U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AC B6 B6
TRM 6I 5A + 6U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AD B7 B7
TRM 6I 1A, 50/60Hz, ring lug terminals 1MRK002247-DC B8 B8
TRM 6I 5A, 50/60Hz, ring lug terminals 1MRK002247-DD B9 B9
TRM 7I 1A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AS B12 B12
TRM 7I 5A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AT B13 B13
TRM 6I 5A + 1I 1A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AX B14 B14
TRM 3I 5A + 4I 1A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AY B15 B15
TRM 3I 5A + 3I 1A + 6U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AF B16 B16
TRM 3IM 1A + 4IP 1A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-EC B17 B17
TRM 3IM 5A + 4IP 5A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-ED B18 B18
TRM 10I 1A + 2U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-FC B19 B19
TRM 10I 5A + 2U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-FD B20 B20
Selected
122 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
When ordering I/O modules, observe the maximum quantities according to the tables below.
Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but
can also be freely placed.
Note: The maximum quantity of I/O modules depends on the type of connection terminals.
Case sizes BIM IOM BOM/ MIM Maximum in case
SOM
1/1 x 19” rack casing, 14 6 4 4 14 *)
one (1) TRM
1/1 x 19” rack casing, 11 6 4 4 11 *)
two (2) TRM
3/4 x 19” rack casing, 8 6 4 4 8 *)
one (1) TRM
3/4 x 19” rack casing, 5 5 4 4 5 *)
two (2) TRM
1/2 x 19” rack casing, 3 3 3 1 3
one (1) TRM
*) including a combination of maximum four modules of type BOM, SOM and MIM
ABB 123
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
P3/X31
P4/X41
P5/X51
P6/X61
P7/X71
P8/X81
P9/X91
P10/X101
P11/X111
P12/X121
P13/X131
P14/X141
P15/X151
P16/X161
(front view/rear
view)
124 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB 125
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Table 204. Station communication, remote end serial communication and time synchronization selection
P30:1/X301
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
P31:1/X311
P31:2/X312
P31:3/X313
P32:2/X322
P32:3/X323
LDCM mode
and type of LDCM
modules supported
depend on the total
amount of I/O and
communication modules
in the IED.
Available slots in 1/2, 3/4 and 1/1 █ █ █ █ █ █ █ █ █ █ █ █
case with 1 TRM
Available slots in 3/4 and 1/1 case █ █ █ █ █ █ █ █ █ █ █ █ █ █
with 2 TRM
No communication board included X X X X X X X X X X X X
Ethernet SFP, optical LC connector 1MRK005500-AA K K K K K K Ethernet SFP is basic in
P30:1. P30:6:1 and
Ethernet SFP, RJ45 connector 1MRK005500-BA P p p p p p
P30:6:2 require the
Optical Ethernet module
in P30:6.
Optical Ethernet module 1MRK002266-EA H
Serial SPA/LON/DNP/IEC 1MRK001608-AB L
60870-5-103 plastic interface
Serial SPA/LON/DNP/IEC 1MRK001608-BB M
60870-5-103 plastic/glass interface
Serial SPA/LON/DNP/IEC 1MRK001608-CB N
60870-5-103 glass interface
Galvanic RS485 communication 1MRK002309-AA G G G G
module
Optical short range LDCM 1MRK002122-AB A A A A A A Max 2 LDCMs can be
ordered. Always place
Optical medium range LDCM, 1310 1MRK002311-AA B B B B B B
LDCM modules on the
nm
same board to support
Optical long range LDCM, 1550 nm 1MRK002311-BA C C C C C C redundant
communication: in P30:5
and P30:6, P31:2 and
P31:3 or P32:2 and
P32:3.
Line data communication, default — X Default if no LDCM is
64kbps mode selected
Allow line data communication in 1MRK007002-AA Y
2Mbps mode
GPS time module 1MRK002282-AB S S S S
IRIG-B time synchronization module 1MRK002305-AA F F F F
Selected K
126 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: REC670 *2.2-A30X00- A02H02-B1A3-AC-CA-B-A3X0-CDAB1RGN1N1XXXXXXX-KKKXXHKKLAGXSY. Using the code of each position #1-11
specified as REC670*1-2 2-3 3-4 4-5 6-7 7-8-9 9 9-10 10 10 10 10 10 10 10-11 11 11 11 11 11 11 11 11 11 11
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 -
REC670* 2.2 - - - - - - - -
10 - 11
-
Position
SOFTWARE #1 Notes and rules
Version number
Version no. 2.2
Selection for position #1
ABB 127
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
128 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Mounting details with IP40 of protection from the front Ordering no #6 Notes and rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB A Only for A30/B30/D30
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 1MRK002420-BA B
19" rack mounting kit for 1/1 x 19" case 1MRK002420-CA C
Wall mounting kit 1MRK002420-DA D Wall mounting not recommended
with communication modules with
fibre connection
Flush mounting kit 1MRK002420-PA E
Flush mounting kit + IP54 mounting seal 1MRK002420-NA F
Selection for
position #6
Human machine hardware interface Case size Ordering no #8 Notes and rules
Medium size - graphic display, IEC keypad symbols 1/2 x 19", IEC 1MRK000028-AA B Only valid for A30/B30/D30
3/4 x 19”, IEC 1MRK000028-CA
1/1 x 19”, IEC 1MRK000028-BA
Medium size - graphic display, ANSI keypad symbols 1/2 x 19", ANSI 1MRK000028-AB C Only valid for A30/B30/D30
3/4 x 19”, ANSI 1MRK000028-CB
1/1 x 19”, ANSI 1MRK000028-BB
Selection for
position #8
P41/X411
ABB 129
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
P3/X31
P4/X41
P5/X51
P6/X61
P7/X71
P8/X81
P9/X91
P10/X101
P11/X111
P12/X121
P13/X131
P14/X141
P15/X151
P16/X161
view/rear view)
130 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB 131
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
P30:1/X301
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
P31:1/X311
P31:2/X312
P31:3/X313
P32:2/X322
P32:3/X323
LDCM mode
and type of LDCM
modules supported
depend on the total
amount of I/O and
communication modules
in the IED.
Available slots in 1/2 and 3/4 case █ █ █ █ █ █ █ █ █ █ █ █
with 1 TRM
Available slots in 3/4 and 1/1 case █ █ █ █ █ █ █ █ █ █ █ █ █ █
with 2 TRM
No communication board included X X X X X X X X X X X X
Ethernet SFP, optical LC connector 1MRK005500-AA K K K K K K Ethernet SFP is basic in
P30:1. P30:6:1 and
Ethernet SFP, RJ45 connector 1MRK005500-BA p p p p p p
P30:6:2 require Optical
Ethernet module in
P30:6.
Optical Ethernet module 1MRK002266-EA H
Serial SPA/LON/DNP/IEC 1MRK001608-AB L
60870-5-103 plastic interface
Serial SPA/LON/DNP/IEC 1MRK001608-BB M
60870-5-103 plastic/glass interface
Serial SPA/LON/DNP/IEC 1MRK001608-CB N
60870-5-103 glass interface
Galvanic RS485 communication 1MRK002309-AA G G G G
module
Optical short range LDCM 1MRK002122-AB A A A A A A Max 2 LDCMs can be
ordered. Always place
Optical medium range, LDCM 1310 1MRK002311-AA B B B B B B
LDCM modules on the
nm
same board to support
redundant
communication: in P30:5
and P30:6, P31:2 and
P31:3 or P32:2 and
P32:3.
Line data communication, default — X Default if no LDCM is
64kbps mode selected
Allow line data communication in 1MRK007002-AA Y
2Mbps mode
GPS time module 1MRK002282-AB S S S S
IRIG-B time synchronization module 1MRK002305-AA F F F F
Selection for K
position #11
132 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Accessories
IP15151-1 v1
GPS antenna and mounting details
M12374-3 v5
Cable for antenna, 40 m (Appx. 131 ft) Quantity: 1MRK 001 665-BA
Due to the high flexibility of our product and the wide variety The normally open "In test mode" contact 29-30 on the RTXP
of applications possible the test switches needs to be test switches should be connected to the input of the test
selected for each specific application. function block to allow activation of functions individually
during testing.
Select your suitable test switch base on the available
contacts arrangements shown in the reference Test switches type RTXP 24 is ordered separately. Please
documentation. refer to Section Related documents for references to
corresponding documents.
However our proposals for suitable variants are;
RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and
Single breaker/Single or Three Phase trip with internal neutral the on/off switch for dc-supply are ordered separately. Please
on current circuits (ordering number RK926 315-AK). refer to Section Related documents for references to
corresponding documents.
Single breaker/Single or Three Phase trip with external neutral
on current circuits (ordering number RK926 315-AC).
Protection cover
M15040-3 v6
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-TA
Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-SA
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-RA
ABB 133
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 1ph Quantity: 1 2 3
RK 795 101-MA
High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 3ph Quantity: RK 795 101-MB
High impedance resistor unit with resistor and voltage dependent resistor 100-400V, 1ph Quantity: 1 2 3
RK 795 101-CB
High impedance resistor unit with resistor and voltage dependent resistor 100-400V, 3ph Quantity: RK 795 101-DC
Combiflex
IP15161-1 v1
Key switch for lock-out of settings via LHMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
SEMOD130267-5 v6
Front connection cable between LHMI and PC Quantity: 1MRK 001 665-CA
SEMOD131414-4 v3
Manuals
M15161-3 v13
Note: One (1) IED Connect USB flash drive containing user documentation (Operation manual, Technical
manual, Installation manual, Commissioning manual, Application manual and Getting started guide),
Connectivity packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect USB flash drive requested. Quantity: 1MRK 002 290-AE
134 ABB
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
User documentation
Rule: Specify the number of printed manuals requested
Application manual IEC Quantity: 1MRK 511 401-UEN
Communication protocol manual, IEC 61850 Edition 1 IEC Quantity: 1MRK 511 392-UEN
Communication protocol manual, IEC 61850 Edition 2 IEC Quantity: 1MRK 511 393-UEN
Communication protocol manual, IEC 60870-5-103 IEC Quantity: 1MRK 511 394-UEN
ABB 135
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
Reference information
M2175-3 v4
For our reference and statistics we would be pleased to be provided with the following application data:
Related documents
GUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v5 670 series manuals Document numbers
Documents related to REC670 Document numbers Operation manual IEC:1MRK 500 127-UEN
ANSI:1MRK 500 127-UUS
Application manual IEC:1MRK 511 401-UEN
ANSI:1MRK 511 401-UUS Engineering manual IEC:1MRK 511 398-UEN
ANSI:1MRK 511 398-UUS
Commissioning manual IEC:1MRK 511 403-UEN
ANSI:1MRK 511 403-UUS Installation manual IEC:1MRK 514 026-UEN
ANSI:1MRK 514 026-UUS
Product guide 1MRK 511 404-BEN
Communication protocol manual, 1MRK 511 391-UUS
Technical manual IEC:1MRK 511 402-UEN DNP3
ANSI:1MRK 511 402-UUS
Communication protocol manual, 1MRK 511 394-UEN
Type test certificate IEC:1MRK 511 404-TEN IEC 60870-5-103
ANSI:1MRK 511 404-TUS
Communication protocol manual, 1MRK 511 392-UEN
IEC 61850 Edition 1
136 ABB
137
—
ABB AB
Grid Automation Products
721 59 Västerås, Sweden
Phone: +46 (0) 21 32 50 00
abb.com/protection-control
1MRK 511 404-BEN