Detention
Detention
Detention
Electric Power
Specifications
Generator Set Specifications
Height - Maximum 2336 mm 92 in
Length - Maximum 5269 mm 207.5 in
Width - Maximum 2015 mm 79.3 in
Minimum Rating 1000 kVA
Maximum Rating 1400 kVA
Voltage 400 to 415 Volts
Frequency 50 Hz
Speed 1500 rpm
Duty Cycle Continuous, Prime, Standby, Mission Critical
Engine Specifications
Engine Model 3512 TA, V-12, 4-Stroke Water-Cooled Diesel
Compression Ratio 13.5:1
Aspiration TA
Governor Type Woodward
Fuel System Direct Unit Injection
Bore 170 mm 6.69 in
Displacement 51.8 l 3161.03 in³
Stroke 190 mm 7.48 in
Air Inlet Single element canister style with service indicator
Exhaust Flange Size 203.2 mm (8.0 in)
Standard Equipment
Air Inlet System
• Air cleaner; single element canister type with service indicator
Control Panel
• EMCP4.2 controls including:
• Emergency stop pushbutton
• 24 Volt DC operation
• Environmental sealed front face
• Text alarm / event descriptions
• Generator mounted - rear facing
• Controls:
• Speed adjust
• Auto / start / stop control
• Engine cool-down timer
• Engine cycle crank
• Alarm acknowledge
• Lamp test
• True RMS AC metering, 3 phase, +/-2% accuracy
• Digital indication for:
• RPM
• DC volts
• Operating hours
• Oil pressure (psi, kPa or bar)
• Co olant temperature
• Volts (L-L & L-N)
• Frequency (Hz)
• Amps (per phase & average)
• Power Factor (per phase & average)
• kW (per phase, average & percent)
• kVA (per phase, average & percent)
• kVAr (per phase, average & percent)
• kW-hr (total)
• kVAr-hr (total)
• Warning / shutdown with common LED indication of shutdowns for:
• Low oil pressure
• High coolant temperature
• Overspeed
• Emergency stop
• Failure to start (overcrank)
• Low coolant temperature
• Low coolant level
• Programmable protective relaying functions:
• Generator phase sequence
• Over / under voltage (27 / 59)
• Over / under frequency (81 o/u)
• Reverse Power (kW) (32)
• Reverse Reactive Power (kVAr) (32RV)
• Overcurrent (50 / 51)
• Communication:
Optional Equipment
Air Inlet System
• Dual Element air cleaners
• Remote air inlet adaptors
• Air Inlet protection
Circuit Breakers
• Optional busbar power connections
• Breaker harnesses
• Center posts busbars
• Cable entry options
• Controls packaging - Enclosures
MSS-EPG-1000006024-054.pdf © 2018 Caterpillar All Rights Reserved Page: M-5 of M-8
3512 Generator Set
Electric Power
• 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, random wound, permanent magnet, No. of leads = 6, pitch=
0.6667
• 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, form wound, permanent magnet, No. of leads = 6, pitch=
0.6667
• Generator conversion
• Space heater
Instrumentation
• Pyrometer and thermocouples
Lube System
• Oil level Reg-1 shallow pan
• Electric prelube pumps
• Manual prelube sump pumps
Mounting System
• Spring-type vibration isolator
• IBC vibration isolators
Protection System
• Explosion relief valve
Special Tests / Reports
• Neutral grounding connection
• Neutral ground-LV
• PGS test report @ 1.0 power factor
• PGS test report @ 0.80 power factor
• IBC seismic certifications
Starting / Charging Systems
• 10 Amp battery chargers
• 20 Amp battery charger
• Oversize battery set
• 24 Volt dual electric starting motor
• Ether starting aid
• Jacket water heaters
General
• Engine barring group
Dimensional Art
The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their
respective logos, ADEM, EUI, S•O•S, "Caterpillar Yellow" and the "Power Edge" trade dress, as well
as corporate and product identity used herein, are trademarks of Caterpillar and may not be used
without permission.