RCU_210 Unit control is a Load Weighing device of the New devices from Dinacell Electronic.
3
User manual RCU_210
3. MENU STRUCTURE
The menu has the cyclic structure shown in the following figure.
Press key for 2 seconds to enter and then press it repeatedly to move from a parameter to another. Press it for 2
seconds to exit to weight indication.
System calibration. These menus shows all parameters related with the load cell
Configuration.
Pressing Menu for 2 seconds inside the internal navigation menu will end the menu navigation and return to
measure Display.
Press to change the value of the Current Flashing digit position. (if there’s no flashing digit, change the
After any of these operations, the display will show the current parameter.
4
User manual RCU_210
5. DEVICE INFO
Menu Info stores some important information for the identification of the unit.
Submenu :
Press
Check value Enter to modify
to enter
Ver: Firmware Version of Unit RCU
Valid Values: 1.00 and above
V_Har: Hardware Version of Unit RCU
6. SYSTEM CONFIGURATION
This section describes how to configure the Unit to get the best measure accuracy. The configuration is done in
Menu.
Press
Check value Enter to modify
to enter
2) Power up the unit with the correct voltage (see the SPECIFICATIONS chapter).
4) Go to Submenu.
5
User manual RCU_210
5.2 ) Load Point adjustment: With This function the Unit will be adjusted with the best accuracy.
Put a well known weight inside the cabin. It Is recommendable to set up to 60% of elevator duty load.
To make the Load point adjustment:
5.3 ) Cell Value: Cell value is automatically calculated after a Load Point adjustment, so users
don´t need to adjust it. This parameter stores the Sensor Sensibility. If Cell Value is changed by
the user, the previous calibrating process will be overwritten. Contact your local distributor If you
need to modify this parameter.
7. ALARMS CONFIGURATION
The alarms values correspond to the load thresholds or limit at which each relay change its state.
The relays allow to be configured individually as make (Normally Close) or break contact (Normally Open)
Alarms are activated when their thresholds are exceeded. The Unit RCU_2Ra has to 2 different alarms:
AL1-F (Full Load, Relay #1):
parameter. Valid values are (Close) for the operating mode MAKE and (Open) for the operating
mode BREAK. Alarm LEDs indicators will be activated when the display measured value overload corresponding
alarm level
6
User manual RCU_210
Go to Submenu
Press
Check value Enter to modify
to enter
Important: When an error appears, all alarms are activated and relay Status is set to the active
state. For example if idle mode is set to Close, the Relay status will change to Open
when any error appears.
7
User manual RCU_210
Submenu
Press
to enter Check value Enter to modify
Time 1: Starting Time to hold the weight before Hold input is activated.
It is and optional correction on installations where the Hold Input
is activated too fast. (Units are Decs of seconds). (Default
Recommended Value: 2 (0.2secs)).
This function compensates the weighting difference between floors produced by the extra weight of the chain
and travelling cables. The unit needs the HOLD signal to be active when the doors closed to compensate the weight
during the elevator movement.
Set the estimated weight of the chain. This parameter will be the maximum value compensated by
software compensation. (200kg is the recommended value )
In this parameter you can check the value that the RCU is compensating by software each time
the HOLD signal is deactivated.
8
User manual RCU_210
9. HOLD FUNCTION
During the elevator travel, the measured loads can heavily fluctuate due to friction in the rails, loads
movements, etc. The Hold Input inhibits the measure while the elevator is travelling, so this ensures that the
movement of the cabin will not affect the weighing process and therefore, no alarms or relay will be activated during
elevator travel.
How Hold Input Function works:
When a voltage in the range 24-125V (DC or AC) is applied in this input, the unit holds the last stable
measure of weight acquired.
The voltage must be applied when the doors close and it must be removed as the doors open.
The RCU_210 has a internal register that stores all previous weighting measures of the last 3 seconds.
As some installations sets the HOLD input at the same time the doors closes, it may happen that the last
measure obtained could not be as stable as desired. The same issue might happen when removing the HOLD input
as the doors Open.
To improve the hold of a stable measure, two parameters have been added at menu;
and .
For example:
Time in tenth of seconds to take the measure before the hold Signal is active.
Time in tenth of seconds to update the measure after the hold Signal is released.
Note: With T_1 = 10 and T2 = 15:
In this case, if hold signal is activated, then, the RCU will take as a valid measure the last stable weighing
value that was stored 1 second before hold was activated. In the same way, when hold is released the first stable
value will be taken 1.5 seconds after the hold signal is deactivated.
This option offers great flexibility to resolve problems in some critical installations.
The Auto_Zero compensation is designed to automatically eliminate small measurement errors lower than
parameter of Submenu.
The Auto-Zero function will happen whenever the RCU measures a static offset of ± for a period of
at least 120 seconds. During this time the measured load must not change by more than 20kg. The RCU will apply an
internal compensation value equal to the inverse value of the currently measured offset.
The Auto_Zero compensation value is stored in internal memory. After power cycling the unit the measure in the
display should not change therefore. To eliminate the stored Auto_Zero compensation, a Zero operation should be
done.
9
User manual RCU_210
Analog_High: Load Value for which the unit will deliver the
maximum analog output ( 10v )
Analog_Low: Load Value for which the unit will deliver the minimum
analog output ( 0v )
This function reflects the Display measure over the range between analog Low and analog High values
When hold (inhibit) input is activated the analog output will not change during elevator
travel, until hold input deactivation.
Negative overflow. The load cell is giving a Check the load cell connection. It should be
too high negative signal. no negative charge.
Positive overflow. Load cell is holding a Change the load cell by another with higher
higher load than its nominal value. nominal load.
Wrong Data in memory. Power cycle the unit. If err6 remains, then
Note: When this error appears, All relays will reset the unit to its default values from
change to Break(OPEN) state. Menu INFO->Reset-> (All)
The unit was not properly adjusted. Adjust the zero and Load again.
Load cell with very low sensibility. Replace the load cell by another one with
lower nominal load.
Important: When an error appears, all alarms are activated and relays state are set to the alarm
Important: When appears or if power supply is lost, All Relay Contact will stay OPENED.
10
User manual RCU_210
Short-circuitable.
Power supply characteristics
It is not necessary to replace any fuse.
Nominal voltage 12-40 Vdc
11
User manual RCU_210
5. . Empty the elevator and set the countdown value for calibrating operations. Confirm the value .for
Empty elevator Operation. A countdown will start.
6. . Set a well-known weight inside the cabin (60% of the nominal load at least ) and set parameter
with the weight added. A countdown will start.
8. Set the Full load alarm limit and set the deactivated state for the full load relay.
9. Set the Overload load alarm limit and set the deactivated state for the Overload load
relay.
10. Go to submenu If chain compensation is desired, select the type of compensation to Soft.
11. Auto Zero Function: Set approximately the Chain weight value in for and auto zero function
corrections and Chain compensation, (default value is 100). If value is set to 00000, auto zero function will be disabled.