BASIC FEATURES
Therm-X / HRFL
Especially designed for false ceiling installation the Therm-X range of • 3 models with maximum air flows: 800, 1600 and 2400 m3/h
units offers a compact and packaged solution of mechanical supply • Compact in size with low installation height for efficient space usage
and extract ventilation with heat recovery.
• Easy access for maintenance
To suit the increasingly stringent requirements for local ventilation sys- • Smooth, crevice free and easy to clean interior surfaces
tems installed in ceiling voids the unit has been designed with reduced
• Fully compliant with the requirements for Part L of the UK Building
height and facilitated maintenance access.
Regulations and the Eco-design directive
Also equipped with state-of-the-art plug and play integrated controls • Very quiet operation
the Therm-X units offer the all-in-one heat recovery solution for local
• Low leakage and solid galvanized frameless construction
mechanical ventilation.
• Aluminum counter flow plate heat exchanger with bypass facility and
These features make the Therm-X units ideal for installation in high heat recovery efficiency up to 93%, exceeding ErP 2018
commercial interior applications, such as shops, offices, coffee bars,
• Energy-efficient EC fans with integrated electronic control and silent
restaurants and sport facilities.
operation
The units are fully compliant with the requirements for the UK Building • Low energy consumption M5 supply filter as standard for enhanced
Regulations and the European Eco-design directive. IAQ (F7 optional)
In addition to this the Therm-X selection software allows for detailed • Intelligent integrated control system with touch screen controller
selections with accurate energy consumption and acoustic figures. (modulating by-pass, antifreeze protection, CAV, VAV and DCV
regimes, BMS control via ModBUS RTU, etc.)
The unit is designed to be operated in a dry indoor environment at an
• Optional integrated electric pre-heater, post heater or LPHW coil
ambient temperature ranging from +5 to 40°C. For ventilation of air
that is free of dust, fats, chemical emissions and other pollutants and a • Optional changeover coil for heating and cooling operation
relative humidity up to 90%. • Extensive range of complimentary ancillaries for installation and
control
When the temperature of the drawn-in air is too low (from -10° up to
-20°C depending on the exhaust temperature) the unit will automatically • Detailed and accurate software selections
use the in-built preheater and modify the air flow through the plate heat
exchanger using the face and bypass dampers in order to prevent the
unit from freezing up.
1
HEAT RECOVERY
Therm-X | HRFL
CONSTRUCTION
The control panel is installed in an easily accessible enclosure located The exchanger is Eurovent certified and fully tested to EN308:1997.
on the outside of the unit. Low internal leakage (<0,5% @ 250 Pa) is guaranteed as all the ex-
changers used on the Therm-X units are leakage tested before leaving
the factory.
Fans
The unit fan section comprises of high
performance supply and extract, single
inlet-backward curved plug fan.
2
HEAT RECOVERY
Therm-X | HRFL
The heat exchanger section is also provided with fully modulating Testing
face and by-pass dampers to provide close control of the supply air
All unit models undergo a stringent set of tests to the relevant European
temperature and enable free cooling operation when the conditions are
standards in an accredited laboratory to ensure accurate catalogue
favorable (e.g. summer night ventilation).
data.
In extreme conditions, where the temperature drops to the point of
Performance is tested to ISO 5801:2007 Industrial fans -- Performance
frost risk the unit control logic provides a defrost routine for the heat
testing using standardized airways.
exchanger.
Casing radiated noise acoustically tested to BS EN 3744:2010 - Acous-
Where not desirable to stop the fans an electrical pre-heater can be
tics - Determination of sound power levels and sound energy levels
offered to provide ambient air pre-heating and frost protection.
of noise sources using sound pressure - Engineering methods for an
A fully removable, epoxy coated, galvanized condensate tray fitted with essentially free field over a reflecting plane.
a 22mm drain connection is provided for condensate collection and
Published figures are for free field spherical propagation. In duct noise
disposal.
acoustically tested to BS EN ISO 5136:2010 - Acoustics - Determination
Due to the typical installation height restrictions a pumped drainage of sound power radiated into a duct by fans and other air-moving de-
system is offered, as standard, with all units. To minimize noise and vices - In-duct method. Heat recovery efficiency tested to EN 308:1997
prolong working life the condensate pump is equipped with a liquid - Heat exchangers - Test procedures for establishing performance of air
sensing mechanism so it operates only when there is condensate to to air and flue gases heat recovery devices.
The coils are manufactured with aluminum fins, copper tubes and
assembled on a corrosion resistant galvanized casing.
3
HEAT RECOVERY
Therm-X | HRFL
Operational diagram
Funktionsschema
TOP PLAN VIEW
SUP EHA
EC
Fanplug fan
/ Ventilator ETA OTA
Counter flow heat
Heat exchanger exchanger
/ Wärmetauscher
Filter
Filter /M5,G4
Filters supply/M5,
Filter Filter M5,G4
extract G4
Control
Regulation panel dieRegulation
/ die Regelung OTA - Outside air
Condensate
Condesate exhaustcollection and disposal
/ Kondensatausscheidung SUP - Supply air
After-heater – Electric, LPHW or change
Afterheater / Nachheizeinrichtung over coil
/ DX / CO ETA - Extract air
Face
By-passandflap
by-pass damper
/ By-pass Klappe EHA - Exhaust air
Electric
Preheater pre-heater
/ Vorwärmer
95
90
85 3
2
Efficiency [%]
1
80
75
ERP2018 - minimum efficiency 73%
70
ERP2016 - minimum efficiency 67%
65
60
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
Air flow [m3/h]
4
HEAT RECOVERY
Therm-X | HRFL
Tabulated data and performance graphics allow for a quick selection of All information on these datasheets is indicative of the unit perfor-
the suitable Therm-X HRFL model. mance. If detailed data is required a software selection should be
requested.
5
HEAT RECOVERY
Therm-X | HRFL
PRIMARY PARAMETERS
Performance characteristics
Performance is shown for standard configuration with M5 supply and For detailed performance figures please request a detailed software
G4 extract filter selection.
ERP compliance area is shown for reference configuration with F7/M5 Performance tested to ISO 5801:2007, Installation category D
filter
800
10V
9V
External static pressure (Pa)
700
600 8V
500
7V
400
6V
300
5V
200 ERP 2016 / 2018 compliant
4V
100
3V
0
0 100 200 300 400 500 600 700 800
Air flow [m3/h]
HRFL1-160
0 m3/s 0,056 m3/s 0,111 m3/s 0,167 m3/s 0,222 m3/s 0,278 m3/s 0,333 m3/s 0,389 m3/s 0,444 m3/s 0,5 m3/s
800
10V
700
9V
External static pressure (Pa)
600
8V
500
400
7V
300
6V
ERP 2018 compliant ERP 2016 compliant
200
5V
100 4V
0
0 200 400 600 800 1000 1200 1400 1600 1800
Air flow [m3/h]
6
HEAT RECOVERY
Therm-X | HRFL
HRFL1-250
800 10V
700
External static pressure (Pa)
9V
600
500
8V
400
7V
300
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600
Air flow [m3/h]
SFP characteristics
HRFL1-080
Air flow [m3/s]
0 m3/s 0,028 m3/s 0,056 m3/s 0,083 m3/s 0,111 m3/s 0,139 m3/s 0,167 m3/s 0,194 m3/s 0,222 m3/s 0,25 m3/s
800 Pa
700 Pa
600 Pa
External static pressure (Pa)
500 Pa
400 Pa
300 Pa
,9
200 Pa SFP 1
SFP 1,6
SFP 1,5
100 Pa
0 Pa
0 m3/h 100 m3/h 200 m3/h 300 m3/h 400 m3/h 500 m3/h 600 m3/h 700 m3/h 800 m3/h 900 m3/h
Air flow [m3/h]
7
HEAT RECOVERY
Therm-X | HRFL
700 Pa
600 Pa
External static pressure (Pa)
500 Pa
400 Pa
300 Pa
SFP 1,9
200 Pa
SFP 1,6
SFP 1
100 Pa ,5
0 Pa
0 m3/s
m3/h 200 m3/s
m3/h 400 m3/s
m3/h 600 m3/s
m3/h 800 m3/s
m3/h 1000 m3/s
m3/h 1200 m3/s
m3/h 1400 m3/s
m3/h 1600 m3/s
m3/h 1800 m3/s
m3/h 2000 m3/s
m3/h
Air flow [m3/h]
HRFL1-250
Air flow [m3/s]
0 m3/s 0,139 m3/s 0,278 m3/s 0,417 m3/s 0,556 m3/s 0,694 m3/s
900 Pa
800 Pa
700 Pa
External static pressure (Pa)
600 Pa
500 Pa
400 Pa
,9
300 Pa SFP 1
SFP 1,6
200 Pa
SFP 1,5
100 Pa
0 Pa
0 m3/h 500 m3/h 1000 m3/h 1500 m3/h 2000 m3/h 2500 m3/h
Air flow [m3/h]
8
HEAT RECOVERY
Therm-X | HRFL
Acoustic characteristics:
Sound pressure levels calculated at 3 meters for Q1 – Free space - spherical
All stated sound power levels are for maximum operating air flow for
propagation
the stated fan velocity at an external static pressure of approximately
Casing radiated noise acoustically tested to BS EN 3744:2010
100Pa.
In duct noise acoustically tested to BS EN ISO 5136:2010
For accurate noise levels please request a detailed software selection.
HRFL1-080
Sound power level per frequency band (dB) Casing breakout
Fan speed
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz @3m dB (A)
Duct inlet noise 73,7 71,6 62,0 61,9 53,5 43,3 39,5 36,6
100% 37,5
Duct outlet noise 83,6 78,5 77,3 78,4 70,5 64,0 60,9 56,0
Duct inlet noise 71,4 68,8 59,7 55,3 48,6 38,7 35,0 31,5
80% 32,6
Duct outlet noise 80,7 75,0 76,3 74,7 67,5 59,0 56,0 50,4
Duct inlet noise 69,1 66,8 60,6 45,5 39,9 30,7 26,5 20,0
60% 27,3
Duct outlet noise 76,9 72,0 76,0 62,4 55,4 50,0 46,1 39,5
Duct inlet noise 67,9 66,1 49,1 34,4 30,0 20,2 14,2 11,2
40% 20,6
Duct outlet noise 76,7 69,9 61,5 51,3 45,7 40,0 34,2 26,9
HRFL1-160
Sound power level per frequency band (dB) Casing breakout
Fan speed
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz @3m dB (A)
Duct inlet noise 83,0 75,5 71,1 64,5 57,9 50,1 45,0 39,7
100% 48,3
Duct outlet noise 90,3 85,2 85,8 84,2 75,3 71,3 65,7 60,5
Duct inlet noise 81,2 74,0 70,3 62,7 55,8 46,9 41,2 35,3
80% 47,3
Duct outlet noise 88,8 83,3 84,5 81,7 73,4 69,4 63,7 59,9
Duct inlet noise 73,5 68,4 67,7 58,1 48,5 38,6 31,2 24,7
60% 41,8
Duct outlet noise 82,9 77,9 83,2 74,6 65,7 61,2 55,7 51,8
Duct inlet noise 69,6 64,8 54,8 40,3 32,6 20,7 15,1 10,2
40% 31,5
Duct outlet noise 77,2 72,7 71,0 57,3 49,9 44,6 39,5 33,2
HRFL1-250
Sound power level per frequency band (dB) Casing breakout
Fan speed
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz @3m dB (A)
Duct inlet noise 76,9 77,2 72,6 59,5 56,3 47,4 42,8 33,6
100% 46,9
Duct outlet noise 88,0 94,1 90,3 79,2 76,9 69,1 63,9 58,4
Duct inlet noise 75,2 77,5 68,9 56,7 53,3 45,0 39,2 33,0
80% 43,0
Duct outlet noise 85,9 94,1 84,2 75,3 73,5 65,7 60,6 54,6
Duct inlet noise 71,1 75,8 61,7 50,2 50,4 40,4 31,9 29,5
60% 38,3
Duct outlet noise 81,9 88,0 74,3 67,9 66,7 58,7 52,7 46,3
Duct inlet noise 66,6 55,4 46,9 40,2 34,6 24,9 20,9 19,9
40% 25,9
Duct outlet noise 73,1 65,6 58,8 54,2 52,8 42,6 37,3 29,0
Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [kW] Rated current [A]
Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [kW] Rated current [A]
9
HEAT RECOVERY
Therm-X | HRFL
Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [kW] Rated current [A]
Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [kW] Rated current [A]
Insulation
Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [W] Rated current [A] Speed [r/min] Protection IP
class
HRFL1-080 1 230 50 175 1,3 2800 44 B
HRFL1-160 1 230 50 455 3,1 2600 54 B
HRFL1-250 1 230 50 500 3,15 1970 54 B
Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [kW] ∆ T [°C]
Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power[kW] ∆ T [°C]
Type Rated capacity * [kW] Water pressure loss [kPa] Air pressure loss [Pa] Air flow [m³/h] Connections diameter
„
HRFL1-080 6,3 20 20,8 800 1/2
„
HRFL1-160 12,1 58,3 28,4 1500 1/2
„
HRFL1-250 20,3 27,8 27 2500 1/2
* For water temperature gradient 90/70 and inlet air temperature 15°C
* To apply to the rated capacity in the characteristics of the hot water coil..
10
HEAT RECOVERY
Therm-X | HRFL
Type Rated capacity [kW]* Water pressure loss [kPa] Air pressure loss [Pa] Air flow [m³/h] Connection diameter
„
HRFL1-080 5,89 1,3 59,2 800 3/4
„
HRFL1-160 10,85 0,9 74,8 1500 3/4
„
HRFL1-250 18,8 1,4 71 2500 3/4
* For water temperature gradient 60/40 and inlet air temperature 15°C.
Correction coefficients of the capacities of the hot water coil operation (C/O)*
Type Rated capacity [kW]* Water pressure loss [kPa] Air pressure loss [Pa] Air flow [m³/h] Connection diameter
„
HRFL1-080 2,78 3,2 65,9 800 3/4
„
HRFL1-160 3,94 1,4 74,8 1500 3/4
„
HRFL1-250 7,52 2,2 71 2500 3/4
* For water temperature gradient 7/12 and inlet air temperature 25°C with 70% of relative humidity.
Correction coefficients of the capacities of the cool water coil operation (C/O)*
11
HEAT RECOVERY
Therm-X | HRFL
DIMENSIONS
K
D
D
B
B
22
H
M M R R
J
C C
A A
HRFL1-080HXCBE54-...S0(E1) 1400 840 900 872 675 90 350 350 x x 200 300 690 x x 336 x x x 112
HRFL1-160HXCBE54-...S0 (E1) 1700 1280 1200 1312 885 90 420 390 x 45 250 500 855 x x 424 x x x 198
HRFL1-250HXCBE54-...S0 (E1) 2000 1600 2x700 1632 1003 90 500 480 x 45 300 600 1005 x x 523 x x x 296
P P
O O
D
D
B
W
H
22
S
S
T
M M R R
J
C C
A A
„
HRFL1-080HXCBE54-...V1 1400 840 900 872 675 90 350 350 x x 200 300 690 303 332 336 132 65 in 1/2 112
„
HRFL1-160HXCBE54-...V1 1700 1280 1200 1312 675 90 420 390 x 45 250 500 855 433 457 424 141 74 in 1/2 188
„
HRFL1-250HXCBE54-...V1 2000 1600 2x700 1632 735 90 500 480 x 45 300 600 1005 519 542 523 169 102 in 1/2 274
12
HEAT RECOVERY
Therm-X | HRFL
HRB2-080EC-CF-HBXX(E)
HRB2-080EC-CF-HBXW
HRB2-080EC-CF-HBXC
HRB2-150EC-CF-HBXX(E)
HRB2-150EC-CF-HBXW
Type A B C D E F G H I J K L M O P R S T W Weight [kg]
HRB2-150EC-CF-HBXC
HRB2-250EC-CF-HBXX(E)
„
HRFL1-080HXCBE54-...C3 1400 840 900 872 675 90 350 350 252 45 200 300 690 305 332 336 140 76 out3/4 117
HRB2-250EC-CF-HBXW
„
HRFL1-160HXCBE54-...C3
HRB2-250EC-CF-HBXC 1700 1280 1200 1312 675 90 420 390 364 45 250 500 855 432 422 424 165 100 out 3/4 193
„
HRFL1-250HXCBE54-...C3 2000 1600 2x700 1632 735 90 500 480 430 45 300 600 1005 500 504 523 187 115 out 3/4 279
HRB2-080EC-CF-HBXX(E)
HRB2-080EC-CF-HBXW
HRB2-080EC-CF-HBXC
HRB2-150EC-CF-HBXX(E)
HRB2-150EC-CF-HBXW
HRB2-150EC-CF-HBXC
HRB2-250EC-CF-HBXX(E)
HRB2-250EC-CF-HBXW
HRB2-250EC-CF-HBXC
2-080EC-CF-HBXX(E)
2-080EC-CF-HBXW
2-080EC-CF-HBXC
2-150EC-CF-HBXX(E)
2-150EC-CF-HBXW
2-150EC-CF-HBXC
2-250EC-CF-HBXX(E)
2-250EC-CF-HBXW
2-250EC-CF-HBXC
13
HEAT RECOVERY
Therm-X | HRFL
Description of control
The Therm-X units are equipped with a fully integrated intelligent control Time scheduling
package to enable regulation of the ventilation rate and indoor air
Allows setting the unit operation, airflow in daily or weekly periods with
quality requirements.
up to 4 time windows.
The in-built controls include:
• 4 temperature sensors (fresh air, supply air, return air and extract air) Air temperature control
• 1 sensor for antifreeze protection
The supply air temperature can be regulated by the use of the integrat-
• 2 digital pressure sensors for filters ed temperature sensors or an external room temperature sensor.
• 3 digital pressure sensors for constant air flow / pressure control
The unit’s control unit automatically controls the recuperative exchang-
• 2 water temperature sensors (only versions with water battery) er efficiency by regulating the face and bypass dampers positions.
When the conditions for free cooling are favorable (e.g. summer night
Airflow control ventilation) the unit adjusts the bypass damper in order to utilize the
colder outside air and save on space cooling.
The unit controls offers continuous flow rate regulation of the airflow
range of the unit in 10% steps. Where an electrical post heater is installed the supply air temperature
is continuously regulated to match the pre-set temperature on the
The unit can be set to operate in 3 distinct ventilation modes to regulate
controller.
the supply of outside air for ventilation purposes.
For continuous (PID) water coil performance regulation, the unit outputs
a 0-10 V signal for analog valve actuation to control the water flow
CAV (Constant air volume) operation across the coil.
The control unit is programmed to supply a constant amount of air to
Where the maximum re-heater performance is not enough to achieve
the ventilated space.
the requested value, the unit reduces the inlet flow rate to achieve the
The unit will self-adjust the fans output according to the pressure in the requested temperature.
supply air duct in order to maintain the amount of air being supplied to
the rooms.
Additional features
• Soft start
VAV (Variable air volume) constant pressure operation
• Record of operational state
The control unit adjusts the fan output to maintain a constant pressure
• Fire mode
in the duct while varying the air volume according to the demand of the
• Fan failure alarm and overheat protection
ventilated space.
• Electric pre and post heater overheat protection
The unit adjusts the supply flow rate according to the total opening of
the supply VAV terminal units or extract grilles in the duct system. • Condensate overflow protection
• Integrated plate heat exchanger frost protection
The fan output is determined by a 0-10V input from an air quality sensor
(CO2 or Relative Humidity).
14
HEAT RECOVERY
ALFA Vent
Therm-X | HRFL
VENTILATION
176 UNITS LÜFTUNGSGERÄTE
LÜFTUNGSGERÄTE VENTILATION UNITS
189
Produced in EU The company reserves the right of change without previous announcement. ©2VV, spol. s r.o.
15
HEAT RECOVERY
Therm-X | HRFL
Valves Actuators
Range of valve and actuator kits specifically selected and matched for Range of actuators selected for Open/Close operation of the rectangu-
application with the Therm-X units with post LPHW heater. lar and circular shut-off dampers for the Therm-X units.
Unit type 2 way, 2 port 3 way, 3 port 3 way, 4 port HRFL1-160 SERVO-TD-04-230-1 ACT-SR-230-1
HRFL1-080 VALL22-HRFL-080 VALL33-HRFL-080 VALL34-HRFL-080 HRFL1-250 SERVO-TD-04-230-1 ACT-SR-230-1
HRFL1-160 VALL22-HRFL-160 VALL33-HRFL-160 VALL34-HRFL-160
NOTE:
HRFL1-250 VALL22-HRFL-250 VALL33-HRFL-250 VALL34-HRFL-250
Actuators supplied loose for mounting on site and wiring by others.
HRFL1-080 VALP22-HRFL-080
HRFL1-160 VALP22-HRFL-160
HRFL1-250 VALP22-HRFL-250
NOTE:
Coil valves / actuators supplied loose for mounting on site and wiring
by others.
16
ýrobků.
HEAT RECOVERY
Therm-X | HRFL
měry:
ACCESSORIES
Rozměry
rozměrRKx-AT;
Rectangular
RKx-ZT; RKx-NTshut off damper RKx-A RKx-Z; RKx-N
00 [mm]. matic shutting off the unit inlets/outlets and prevent drafts when the
The MLKR/S rectangular damper can be unit mounted to allow auto-
Actuator supplied separately. Power and control for the damper actu-
a - pro regulační klapky RKII-x; RKIII-x
ator provided by the unit control panel. Damper is supplied loose for A šířka [mm]
b - pro regulační klapky RKI-x
fitting on site.
B výška
Regulační klapky větších rozměrů jsou [mm]
děleny na menší pole.
Orientační hmotnost (kg)
Při objednávání
Type regulačních klapek,
které nejsou sériově vyráběné, se musí
Rectangular damper Recommended Actuator Všeobecné inform
HRFL1-080
uvést rozměry regulačních klapek AxB, MLKR/S-300200
varianta a druh mechanismu podle
HRFL1-160
zásad značení výrobků. Nomogram I
MLKR/S-500250 SERVO-TD-04-230-1
hlost proudění
Upozornění:
HRFL1-250
vzduchu Vliv rychlosti V a stupně otevření regulační klapky
MLKR/S-600300
Maximální rozměry:
ková tlaková ztráta
A ≤ 2500 [mm], na snížení tlaku ∆p.
B ≤ 2005 [mm].
el natočení listu Úhel otevření regulační klapky
dina intenzity zvuku
Vyrábíme každý rozměr
A = 0,1 [m²]
B od 200 do 2000 [mm].
S ohledem na šířku listu 100 [mm]
Rectangular damper A B
Všeobecné informace
Označení: Nomogram I
V [m/s] rychlost proudění vzduchu Vliv rychlosti V a stupně otevření regulační klapky
Δp [Pa] celková tlaková ztráta na snížení tlaku ∆p.
α [º] úhel natočení listu Opening angle of
Úhel otevření thedamper
regulační blades
klapky
LWA [dB(A)] hladina intenzity zvuku
pro A = 0,1 [m²]
A [m²] plocha příčného průřezu
regulační klapky
Snížení
Snížení
tlaku
drop
tlaku
Pressure
Δp [Pa]
Δp [Pa]
V [m/s]
verze 5.2.1 w w w. v z t - v y s ko c i l . c z 19
V [m/s]
w w w. v z t - v y s ko c i l . c z 17
BASIC FEATURES HEAT RECOVERY
КРАТКАЯ ХАРАКТЕРИСТИКА
L2 L1 L2
L
18
HEAT RECOVERY
Therm-X | HRFL
It can be used for pre-heating or re-heating air from the Therm-X unit’s
recuperative exchanger were the optional in-built heater capacity is not
sufficient to achieve the required temperature or when closer tempera-
ture control of the room is required.
Recommended combinations:
HRFL1-080 EOKO-250-4,5-3-D
HRFL1-160 EOKO-315-6,0-3-D
HRFL1-250 EOKO-400-9,0-3-D
250-4,5 315-6-3/9
EOKO-250-4,5-3-D EOKO-315-6,0-3-D
250
150
200
ps (Pa)
[P a] ps (Pa)
150
100
Static pressure
Static pressure
[P a]
100
50
50
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000 3500 4000
Air flow[m3/h]
[m3/h] Air flow[m3/h]
[m3/h]
400-9
EOKO-400-9,0-3-D
150
Static pressure ps (Pa)
100
[P a]
50
0
0 1000 2000 3000 4000 5000 6000 7000
Air flow[m3/h]
[m3/h]
19
EOKO-450-18-3 450 18,0 3x400 delta / Delta 26,0 1060 55
EOKO-500-9-3 500 9,0 3x400HEAT RECOVERY
delta / Delta 13,0 530 60
EOKO-500-18-3 500 18,0 3x400 delta / Delta 26,0 1060 60
EOKO-560-12-3 560 12,0 3x400 Therm-X | HRFL
delta / Delta 17,3 707 66
EOKO-560-24-3 560 24,0 3x400 delta / Delta 34,6 1414 66
EOKO-630-12-3 630 12,0 3x400 delta / Delta 17,3 707 73
EOKO-630-24-3 630 24,0 3x400 delta / Delta 34,6 1414 73
Bushings / Tüllen
A
iD
C C
B
Voltage [V]
Nominal Output Connection Current Airflow Min. Dimensions [mm] Weight
Type
diameter [mm] [kW] Coils only Heater [type] [A] [m3/h] [kg]
A B C D
COMPONENTS KOMPONENTEN
ЕОКО-250-4,5-3 250 4,5 3x230 3x400 star 6,7 265 350 380 40 250 3,8
EOKO-315-6-3 315 6,0 3x230 3x400 star 8,8 353 430 380 60 315 6,2
Internal control system It can be used for pre-heating or re-heating air fromthe Therm-X unit’s
recuperative exchanger were the optional in-built heater capacity is not
The heater is supplied with fully integrated control panel with regulation
sufficient to achieve the required temperature or when closer tempera-
knob to adjust the desired set temperature.
ture control of the room is required.
To detect the temperature of the air an temperature sensor for duct
installation is provided with the heater. The heater shall be installed indoor in a dry area with ambient tempera-
tures ranging from 5 °C up to 60 °C and relative humidity of up to 80 %.
Notes:
The heater frame is made of galvanized steel with copper tubes and
The heater is supplied as a standalone product. Power and control to
aluminium fins.
the heater must be provided by an external source.
The controller regulates the heater output only. All other emergency and
safety functions shall be ensured by an external control system. Note:
Temperature sensor installation must be carried by the installer.
Additional heater control options are available by request. Please The water coil is designed for the maximum operating water tempera-
contact the office. ture of +100 °C and maximum operating pressure of 1.6 MPa.
Heater supplied loose for fitting and wiring on site Heater supplied loose for fitting on site.
Valves not included
20
HEAT RECOVERY
Therm-X | HRFL
80/60 Water temperature gradient 60/40 Water temperature gradient Dimensions [mm]
200
VOK-01-T-250 1500 25,9 41
D 13 0,31 18,33 26,7 8,69 0,22 250 1 390 2
390 60 280 3
9,0
80
B
i
VOK-01-T-315 1500 25,9 41 13 0,31 18,33 26,7 8,69 0,22 315 390 390 60 280 9,0
150
VOK-01-T-400 2000 36 43 10,4 0,43 25,48 28,27 5,26 0,3 400 460 460 80 320 11,2
G 1/2" 65 C
G1"
50
G1" 200
D
1 2 3
80
B
2000
i
D
150
i
Air volume [m .h ]
3 -1
G 1/2" 65 C
Pressure loss [Pa]
150
A 90 160
G 1/2" 65 C
Pressure loss [Pa]
1 250
A 90 L160 100 2 315
1 250
L 100 3 400
2 315
3 400
50
50
0
00 500 1000 1500 2000 2500 3000 3500
0 500 1000 1500 20003 2500 3000 3500
Air volume [m .h ]
-1
Air volume [m .h ]
3 -1
Counter Parallelflow
flow connection
connection
Counter flowflow installation
installation Parallel
21
HEAT RECOVERY
Therm-X | HRFL
SK-HL138
The trap cover is transparent for easy monitoring of the water level.
Note:
Note:
22
HEAT RECOVERY
Therm-X | HRFL
Note:
Power can be provided by the unit to a single air quality sensor only
The unit only accepts input from a single air quality sensor
Sensor supplied loose for wiring and fitting on site.
Cable not included. Use of shielded cable for wiring is recommended.
Seite 3 Page 3
unit control panel for regulation in the DCV operation. Zubehör optional Optional Accessories
(MF19-PA) Montageflansch zur Befestigung des Fühlers am (MF19-PA) Mounting flange for installation on ventilation duct
The sensor has an analogue voltage output 0-10V, corresponding to Lüftungskanal
Note:
Out Temp 0-10V
Power can be provided by the unit to a single air quality sensor only. UB 15-24V=/24V~
(min. 5kOhm)
(min. 5kOhm)
LCN-FTKxVV
+U
Gnd
The unit only accepts input from a single air quality sensor
Load
Load
RL
RL
Temp.Sensor (Option)
Thermokon Sensortechnik GmbH - Aarstrasse 6 - 35756 Mittenaar - Tel.: 02772/65010 - Fax: 02772/6501400 - www.thermokon.de - email@thermokon.de
produktblatt_lcn_ftk_vv 2010 23
HEAT RECOVERY
Therm-X | HRFL
CI‑PS 1003
Room (Passive Infrared) motion sensor for occupancy detection. When
something enters into controlled space, this sensor detects heat emis-
sion from bodies and switches its contacts on or off.
The signal can be connected to the Therm-X units turning the unit on or
off accordingly.
The sensor has a detection range of 12 meters at an 90° angle and can
be mounted on walls or installed in corners. It’s possible to switch on/off
light emission diodes (LED).
Pulse scaler 1 or 2
+ 12 V: DС
Installation method Installation on walls GND ANODE:DC
Height of installation 1,8 up to 2,2m ALARM CATHODE: relay output
ТАMPЕR: Anti tamper switch
Operating temperature range -10°C up to +50°C
Dimensions 106 mm x 54 mm x 36 mm
Spare filters
Spare replacement filters with the same design and manufacturing as
the ones supplied with the units.
24
HEAT RECOVERY SPTGLX
Therm-X | HRFL
Threaded rods
ZTZ-M8-1,0 – threaded rod, thread M8, length 1m, suitable for all types
BASIC FEATURES GRU
of Therm-X units
- Diameters: 100 up to 400 mm - Durchmes
Notes: - Length: 500 and 1,000 mm - Länge: 50
Fixing supports are pre-fitted on the unit The SPTGLX round sound attenuator is designed for Der Rundd
4 rods necessary for supporting model 060 and 150 reducing noise propagated through the HVAC ducting. It is durch die
6 rods necessary for supporting model 250 designed for operation in the basic environment for verbreiteten
Items supplied loose for installation on site conveying air free of rough dust, grease, chemical fumes, Grundumfe
Your partner in ventilation...
and other contaminants. The sound attenuator housing is Fettigkeit,
made of galvanized plate. The sleeves are fitted with Verunreinig
Circular sound attenuator packing. verzinktem
SPTGLX Dichtung ve
The SPTGLX circular sound attenuator is designed for reducing noise
propagated through the HVAC ducting. The sound attenuator housing
is manufactured of galvanized steel and rockwoll infill.
PRIMARY PARAMETERS WIC
Note:
BASIC FEATURES GRUNDEIGENSCHAFTEN
Attenuators supplied loose for installation on site
- Diameters: 100 up to 400 mm - Durchmesser: 100 bis 400 mm
- Length: 500 and 1,000 mm - Länge: 500 und 1000 mm
The SPTGLX round sound attenuator is designed for Der Runddämpfer SPTGLX ist für die Verringerung des
reducing noise propagated through the HVAC ducting. It is durch die Rohrleitung der lufttechnischen Systeme
designed for operation in the basic environment for verbreiteten Schalls bestimmt. Dieser ist für den Betrieb im
conveying air free of rough dust, grease, chemical fumes, Grundumfeld, für die Luftförderung ohne groben Staub,
and other contaminants. The sound attenuator housing is Fettigkeit, Dämpfe von Chemikalien und weiterer
made of galvanized plate. The sleeves are fitted with Verunreinigungen bestimmt. Das Dämpfergehäuse ist aus
packing. verzinktem Blech, die Dämpferstutzen sind mit einer
Dichtung versehen.
COMPONENTS KOMPONENTEN
COMPONENTS KOMPONENTEN 483
Produced in EU Produced
The company reserves the right of inprevious
change without EU announcement. ©2VV, spol. s r.o. The company reserves the right of
25
HEAT RECOVERY
Therm-X | HRFL
Connection cable
RJ12 6pin communication cable for connecting the remote controllers
to the Therm-X unit. The cable is supplied with all types of units in a
standard length 8 m. Other lengths are available based on the coding
key provided below.
KABEL-05M
KEY TO CODING
C Regulation
C Comfort regulation
S0 After heater
S0 Without after heater
E1 Electric after heater
V1 Water after heater
C3 Heater/cooler
X Preheater
X Without preheater
E Electric preheater
E Type of fans
E EC fans
CB By-pass
CB Counterflow plate heat
exchanger with bypass
X Version of access
X Universal
H Installation
Horizontal installation