HEAT RECOVERY

Therm-X | HRFL

E L SYSTEM
EV
L
NOISE
LOW

BASIC FEATURES

Therm-X / HRFL
Especially designed for false ceiling installation the Therm-X range of • 3 models with maximum air flows: 800, 1600 and 2400 m3/h
units offers a compact and packaged solution of mechanical supply • Compact in size with low installation height for efficient space usage
and extract ventilation with heat recovery.
• Easy access for maintenance
To suit the increasingly stringent requirements for local ventilation sys- • Smooth, crevice free and easy to clean interior surfaces
tems installed in ceiling voids the unit has been designed with reduced
• Fully compliant with the requirements for Part L of the UK Building
height and facilitated maintenance access.
Regulations and the Eco-design directive
Also equipped with state-of-the-art plug and play integrated controls • Very quiet operation
the Therm-X units offer the all-in-one heat recovery solution for local
• Low leakage and solid galvanized frameless construction
mechanical ventilation.
• Aluminum counter flow plate heat exchanger with bypass facility and
These features make the Therm-X units ideal for installation in high heat recovery efficiency up to 93%, exceeding ErP 2018
commercial interior applications, such as shops, offices, coffee bars,
• Energy-efficient EC fans with integrated electronic control and silent
restaurants and sport facilities.
operation
The units are fully compliant with the requirements for the UK Building • Low energy consumption M5 supply filter as standard for enhanced
Regulations and the European Eco-design directive. IAQ (F7 optional)

In addition to this the Therm-X selection software allows for detailed • Intelligent integrated control system with touch screen controller
selections with accurate energy consumption and acoustic figures. (modulating by-pass, antifreeze protection, CAV, VAV and DCV
regimes, BMS control via ModBUS RTU, etc.)
The unit is designed to be operated in a dry indoor environment at an
• Optional integrated electric pre-heater, post heater or LPHW coil
ambient temperature ranging from +5 to 40°C. For ventilation of air
that is free of dust, fats, chemical emissions and other pollutants and a • Optional changeover coil for heating and cooling operation
relative humidity up to 90%. • Extensive range of complimentary ancillaries for installation and
control
When the temperature of the drawn-in air is too low (from -10° up to
-20°C depending on the exhaust temperature) the unit will automatically • Detailed and accurate software selections
use the in-built preheater and modify the air flow through the plate heat
exchanger using the face and bypass dampers in order to prevent the
unit from freezing up.

The design of the ventilation unit must always be carried out by an


HVAC designer.

1
HEAT RECOVERY

Therm-X | HRFL

CONSTRUCTION

Casing The highly efficient aluminum impellers and


additional closed cell foam acoustical lining
The Therm-X unit casing is assembled from a
in the fan section ensure low noise levels
self-supporting frameless construction, manufac-
especially on the outlet of the fan.
tured with double skinned, corrosion resistant,
30mm deep galvanized sandwich panels (0.8mm The fan assembly is installed on a highly
gauge). rigid galvanized support structure mounted
with an aerodynamically designed galvanized inlet and an outlet casing
The outstanding mechanical strength, thermal and
designed to reduce swirl.
acoustic performance of the casing is assured
by packing the panels with high density rockwool The EC motors offer intelligent integrated control electronics allowing
(88kg/m3) with excellent thermal and acoustic soft start as well as over-temperature and short circuit protection.
performance (D=0.041 W/m.K, fire resistance class A1 to 13501-1 +
The motor insulation is Class ‘B’, rated IP 54 (acc. to EN 60529) and
A1: 2009 - non-combustible).
meets all relevant EMC directives and requirements.
The panels are T shaped and joined with internally enclosed
self-screwing fixings resulting in a smooth internal surface, crevice
free, which contributes to the cleanliness of the unit and the quality of Filters
the air supplied through it. Filtration for protection of the finned heat
To avoid external air leakage both fixed and access panels are sealed exchanger and treatment of the supply air is
provided by compact cardboard mounted,
with high tightness PVC foam tape.
synthetic media filters.

Grade of filtration according to BS EN779:2012


Installation is class M5 on supply and G4 on extract.
The unit is suitable for internal installation by The low pressure drop synthetic media makes for a low energy con-
suspension on the false ceiling and it’s supplied, sumption filter, to help reduce the overall energy consumption of the
as standard, with support brackets equipped with unit. For stricter indoor air quality requirements, a F7 supply air filter is
anti-vibration mounts to ensure a quick and reliable optionally available.
installation.
The filters are mounted on slides for easy removal and tightly sealed
against the rails to ensure reduced filter bypass leakage.
Maintenance
Access to all the unit compartments is
available through the bottom tool oper-
Counter flow plate heat exchanger
ated access panels as standard.
The heat recovery section is equipped
The bottom central panel is fully remov-
with a highly efficient counter flow air
able providing full maintenance access to the heat exchanger and
to air plate heat exchanger, exceeding
condensate tray.
the 2018 requirements of regulation
The bottom side hinged panels provide access to the fan, filter and 1253/2014 of the Eco-design directive
ancillary coil sections without need for complete removal of the panel, for ventilation units, with operational
facilitating access for periodic inspection while ensuring the safety of efficiency up to 93%.
the service engineer.
The heat exchanger finned area and casing are manufactured from
Side filter access is also provided as standard through easily remova- high thermal transmittance and corrosion resistant aluminum fins with
ble screwed panels. optimized pressure drop.

The control panel is installed in an easily accessible enclosure located The exchanger is Eurovent certified and fully tested to EN308:1997.
on the outside of the unit. Low internal leakage (<0,5% @ 250 Pa) is guaranteed as all the ex-
changers used on the Therm-X units are leakage tested before leaving
the factory.
Fans
The unit fan section comprises of high
performance supply and extract, single
inlet-backward curved plug fan.

The fans are directly driven by low energy


consumption IE4 electronically commutated
(EC) motors.

The fan exceeds the 2015 efficiency require-


ments of regulation 327/211 of the Eco-design directive for fans.

The assembly is statically and dynamically balanced as per DIN / ISO


1940 to balancing grade G 6.3.

2
HEAT RECOVERY

Therm-X | HRFL

The heat exchanger section is also provided with fully modulating Testing
face and by-pass dampers to provide close control of the supply air
All unit models undergo a stringent set of tests to the relevant European
temperature and enable free cooling operation when the conditions are
standards in an accredited laboratory to ensure accurate catalogue
favorable (e.g. summer night ventilation).
data.
In extreme conditions, where the temperature drops to the point of
Performance is tested to ISO 5801:2007 Industrial fans -- Performance
frost risk the unit control logic provides a defrost routine for the heat
testing using standardized airways.
exchanger.
Casing radiated noise acoustically tested to BS EN 3744:2010 - Acous-
Where not desirable to stop the fans an electrical pre-heater can be
tics - Determination of sound power levels and sound energy levels
offered to provide ambient air pre-heating and frost protection.
of noise sources using sound pressure - Engineering methods for an
A fully removable, epoxy coated, galvanized condensate tray fitted with essentially free field over a reflecting plane.
a 22mm drain connection is provided for condensate collection and
Published figures are for free field spherical propagation. In duct noise
disposal.
acoustically tested to BS EN ISO 5136:2010 - Acoustics - Determination
Due to the typical installation height restrictions a pumped drainage of sound power radiated into a duct by fans and other air-moving de-
system is offered, as standard, with all units. To minimize noise and vices - In-duct method. Heat recovery efficiency tested to EN 308:1997
prolong working life the condensate pump is equipped with a liquid - Heat exchangers - Test procedures for establishing performance of air
sensing mechanism so it operates only when there is condensate to to air and flue gases heat recovery devices.

pump and an alarm system which stops operation in the event of a


pump failure or condensate overflow risk. Building regulations and Eco-design directive
Where the depth of ceiling void allows, a gravity assisted conden- All models are performance tested and measurements are made to
sate drainage system can be offered. The trap can be recessed or obtain the power consumption of the units in several operating points.
wall-mounted and includes an integrated system to prevent air infiltra- These tests were conducted to evaluate the performance of the unit
tion to the unit. both at standard configuration (M5/G4 filters) and under the conditions
of the Eco - design directive (with F7/M5 filter configuration).
Optional features The units are able to operate within the limits of both of these regu-
lations under most conditions. To get accurate performance data a
Integrated electrical pre-heater and/or post heater detailed selection can be provided.

The unit can be optionally fitted with an electrical pre-heater manufac-


tured with open coil heating elements and galvanized casing.

The heater is complete with fully modulating SCR (Silicon Controlled


Rectifier) control (0-10V) and 2 stages of overheat protection (automat-
ic and manual reset) all integrated on the unit’s control logic.

The SCR control provides accurate, supply air temperature regulation.


The heat output is precisely controlled from 0 to 100% by using the unit
in-built temperature sensors or a space temperature sensor.

The electrical pre-heater is recommended when there is the need to


protect the plate heat exchanger from freezing under low ambient con-
ditions and to avoid dead times on the unit operation due to shut down
of the fans for defrost routine.

The electrical post heater is recommended where no hot water supply


is available on site and there is need for top-up heating of the supply
air.

Integrated LPHW after heater or changeover coil


The unit can be supplied with an integrated water heater battery operat-
ing with LPHW to provide supply air top up heating.

Where cooling is also required a changeover water coil can be provid-


ed operating with either chilled or heated water by a common water
circuit depending on the seasonal requirements.

The coils are manufactured with aluminum fins, copper tubes and
assembled on a corrosion resistant galvanized casing.

Maximum operating pressure 1.6 Mpa, 110°C.

The heating output is automatically regulated by the in-built tempera-


ture sensors and the integrated unit controls.

3
HEAT RECOVERY

Therm-X | HRFL

Operational diagram
Funktionsschema
TOP PLAN VIEW

SUP EHA

EC
Fanplug fan
/ Ventilator ETA OTA
Counter flow heat
Heat exchanger exchanger
/ Wärmetauscher
Filter
Filter /M5,G4
Filters supply/M5,
Filter Filter M5,G4
extract G4
Control
Regulation panel dieRegulation
/ die Regelung OTA - Outside air
Condensate
Condesate exhaustcollection and disposal
/ Kondensatausscheidung SUP - Supply air
After-heater – Electric, LPHW or change
Afterheater / Nachheizeinrichtung over coil
/ DX / CO ETA - Extract air
Face
By-passandflap
by-pass damper
/ By-pass Klappe EHA - Exhaust air
Electric
Preheater pre-heater
/ Vorwärmer

Heat recovery efficiency:

Air flow [m3/s]


0 0,069 0,139 0,208 0,278 0,347 0,417 0,486 0,556 0,625 0,694
100

95

90

85 3
2
Efficiency [%]

1
80

75
ERP2018 - minimum efficiency 73%

70
ERP2016 - minimum efficiency 67%

65

60
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
Air flow [m3/h]

1 HRFL1-080 2 HRFL1-160 3 HRFL1-250

The data is measured under following conditions:


Outdoor air temperature is 5°C, relative humidity 72%
Indoor air temperature is 25°C, relative humidity 28%
Efficiencies stated are for dry conditions.
Heat recovery efficiency tested to EN 308:1997

4
HEAT RECOVERY

Therm-X | HRFL

Quick Selection Example For Therm-X HRFL Units

Tabulated data and performance graphics allow for a quick selection of All information on these datasheets is indicative of the unit perfor-
the suitable Therm-X HRFL model. mance. If detailed data is required a software selection should be
requested.

1200 m3/h (0.33 m3/s) @ 150 Pa


ErP 2018 compliant!
Fan speed = 75%
Approximated acoustic figures can be consulted in page 8
Casing breakout @ 3m < 47.3 dB

1000 m3/h (0.278 m3/s) @ 150 Pa


SFP < 1.9 W/l/s – compliant with BR 2010 Part L!
Dimensional data can be consulted in page 11 - Height 390mm!
After heater performance can be consulted in page 9-10

5
HEAT RECOVERY

Therm-X | HRFL

PRIMARY PARAMETERS

Performance characteristics

Performance is shown for standard configuration with M5 supply and For detailed performance figures please request a detailed software
G4 extract filter selection.

ERP compliance area is shown for reference configuration with F7/M5 Performance tested to ISO 5801:2007, Installation category D
filter

HRFL1-080 Air flow [m3/s]


0 m3/s 0,028 m3/s 0,056 m3/s 0,083 m3/s 0,111 m3/s 0,139 m3/s 0,167 m3/s 0,194 m3/s 0,222 m3/s
900

800
10V
9V
External static pressure (Pa)

700

600 8V

500
7V
400

6V
300

5V
200 ERP 2016 / 2018 compliant
4V
100
3V

0
0 100 200 300 400 500 600 700 800
Air flow [m3/h]

HRFL1-160
0 m3/s 0,056 m3/s 0,111 m3/s 0,167 m3/s 0,222 m3/s 0,278 m3/s 0,333 m3/s 0,389 m3/s 0,444 m3/s 0,5 m3/s
800

10V
700
9V
External static pressure (Pa)

600
8V
500

400
7V

300
6V
ERP 2018 compliant ERP 2016 compliant
200
5V

100 4V

0
0 200 400 600 800 1000 1200 1400 1600 1800
Air flow [m3/h]

6
HEAT RECOVERY

Therm-X | HRFL

HRFL1-250

Air flow [m3/s]


0 m3/s 0,056 m3/s 0,111 m3/s 0,167 m3/s 0,222 m3/s 0,278 m3/s 0,333 m3/s 0,389 m3/s 0,444 m3/s 0,5 m3/s 0,556 m3/s 0,611 m3/s 0,667 m3/s 0,722 m3/s
900

800 10V

700
External static pressure (Pa)

9V
600

500
8V
400
7V
300

6V ERP 2016 / 2018 compliant


200
5V
100
4V

0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600
Air flow [m3/h]

SFP characteristics

HRFL1-080
Air flow [m3/s]
0 m3/s 0,028 m3/s 0,056 m3/s 0,083 m3/s 0,111 m3/s 0,139 m3/s 0,167 m3/s 0,194 m3/s 0,222 m3/s 0,25 m3/s
800 Pa

700 Pa

600 Pa
External static pressure (Pa)

500 Pa

400 Pa

300 Pa

,9
200 Pa SFP 1
SFP 1,6
SFP 1,5
100 Pa

0 Pa
0 m3/h 100 m3/h 200 m3/h 300 m3/h 400 m3/h 500 m3/h 600 m3/h 700 m3/h 800 m3/h 900 m3/h
Air flow [m3/h]

7
HEAT RECOVERY

Therm-X | HRFL

HRFL1-160 Air flow [m3/s]


0 m3/s 0,056 m3/s 0,111 m3/s 0,167 m3/s 0,222 m3/s 0,278 m3/s 0,333 m3/s 0,389 m3/s 0,444 m3/s 0,5 m3/s 0,556 m3/s
800 Pa

700 Pa

600 Pa
External static pressure (Pa)

500 Pa

400 Pa

300 Pa

SFP 1,9
200 Pa
SFP 1,6
SFP 1
100 Pa ,5

0 Pa
0 m3/s
m3/h 200 m3/s
m3/h 400 m3/s
m3/h 600 m3/s
m3/h 800 m3/s
m3/h 1000 m3/s
m3/h 1200 m3/s
m3/h 1400 m3/s
m3/h 1600 m3/s
m3/h 1800 m3/s
m3/h 2000 m3/s
m3/h
Air flow [m3/h]

HRFL1-250
Air flow [m3/s]
0 m3/s 0,139 m3/s 0,278 m3/s 0,417 m3/s 0,556 m3/s 0,694 m3/s
900 Pa

800 Pa

700 Pa
External static pressure (Pa)

600 Pa

500 Pa

400 Pa

,9
300 Pa SFP 1
SFP 1,6
200 Pa
SFP 1,5

100 Pa

0 Pa
0 m3/h 500 m3/h 1000 m3/h 1500 m3/h 2000 m3/h 2500 m3/h
Air flow [m3/h]

8
HEAT RECOVERY

Therm-X | HRFL

Acoustic characteristics:
Sound pressure levels calculated at 3 meters for Q1 – Free space - spherical
All stated sound power levels are for maximum operating air flow for
propagation
the stated fan velocity at an external static pressure of approximately
Casing radiated noise acoustically tested to BS EN 3744:2010
100Pa.
In duct noise acoustically tested to BS EN ISO 5136:2010
For accurate noise levels please request a detailed software selection.

HRFL1-080
Sound power level per frequency band (dB) Casing breakout
Fan speed
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz @3m dB (A)

Duct inlet noise 73,7 71,6 62,0 61,9 53,5 43,3 39,5 36,6
100% 37,5
Duct outlet noise 83,6 78,5 77,3 78,4 70,5 64,0 60,9 56,0
Duct inlet noise 71,4 68,8 59,7 55,3 48,6 38,7 35,0 31,5
80% 32,6
Duct outlet noise 80,7 75,0 76,3 74,7 67,5 59,0 56,0 50,4
Duct inlet noise 69,1 66,8 60,6 45,5 39,9 30,7 26,5 20,0
60% 27,3
Duct outlet noise 76,9 72,0 76,0 62,4 55,4 50,0 46,1 39,5
Duct inlet noise 67,9 66,1 49,1 34,4 30,0 20,2 14,2 11,2
40% 20,6
Duct outlet noise 76,7 69,9 61,5 51,3 45,7 40,0 34,2 26,9

HRFL1-160
Sound power level per frequency band (dB) Casing breakout
Fan speed
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz @3m dB (A)

Duct inlet noise 83,0 75,5 71,1 64,5 57,9 50,1 45,0 39,7
100% 48,3
Duct outlet noise 90,3 85,2 85,8 84,2 75,3 71,3 65,7 60,5
Duct inlet noise 81,2 74,0 70,3 62,7 55,8 46,9 41,2 35,3
80% 47,3
Duct outlet noise 88,8 83,3 84,5 81,7 73,4 69,4 63,7 59,9
Duct inlet noise 73,5 68,4 67,7 58,1 48,5 38,6 31,2 24,7
60% 41,8
Duct outlet noise 82,9 77,9 83,2 74,6 65,7 61,2 55,7 51,8
Duct inlet noise 69,6 64,8 54,8 40,3 32,6 20,7 15,1 10,2
40% 31,5
Duct outlet noise 77,2 72,7 71,0 57,3 49,9 44,6 39,5 33,2

HRFL1-250
Sound power level per frequency band (dB) Casing breakout
Fan speed
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz @3m dB (A)

Duct inlet noise 76,9 77,2 72,6 59,5 56,3 47,4 42,8 33,6
100% 46,9
Duct outlet noise 88,0 94,1 90,3 79,2 76,9 69,1 63,9 58,4
Duct inlet noise 75,2 77,5 68,9 56,7 53,3 45,0 39,2 33,0
80% 43,0
Duct outlet noise 85,9 94,1 84,2 75,3 73,5 65,7 60,6 54,6
Duct inlet noise 71,1 75,8 61,7 50,2 50,4 40,4 31,9 29,5
60% 38,3
Duct outlet noise 81,9 88,0 74,3 67,9 66,7 58,7 52,7 46,3
Duct inlet noise 66,6 55,4 46,9 40,2 34,6 24,9 20,9 19,9
40% 25,9
Duct outlet noise 73,1 65,6 58,8 54,2 52,8 42,6 37,3 29,0

Basic technical parameters of the heat recovery units:


Model without coil / with water heating coil / with change-over coil

Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [kW] Rated current [A]

HRFL1-080 1 230 50 0,4 2,8


HRFL1-160 1 230 50 1 6,5
HRFL1-250 1 230 50 1 6,2

Model with electric preheater

Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [kW] Rated current [A]

HRFL1-080 1 230 50 3,10 14,5


HRFL1-160 3 400 50 6,30 13,3
HRFL1-250 3 400 50 9,40 18,6

9
HEAT RECOVERY

Therm-X | HRFL

Model with electric afterheater

Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [kW] Rated current [A]

HRFL1-080 1 230 50 1,8 8,8


HRFL1-160 1 230 50 3,7 18
HRFL1-250 3 400 50 5,8 13,5

Model with electric preheater and electric afterheater

Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [kW] Rated current [A]

HRFL1-080 3 400 50 4,5 11,7


HRFL1-160 3 400 50 9 18
HRFL1-250 3 400 50 14,2 24,8

Characteristics of electric motors (1 Fan only)

Insulation
Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [W] Rated current [A] Speed [r/min] Protection IP
class
HRFL1-080 1 230 50 175 1,3 2800 44 B
HRFL1-160 1 230 50 455 3,1 2600 54 B
HRFL1-250 1 230 50 500 3,15 1970 54 B

Characteristics of electric preheater coil

Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power [kW] ∆ T [°C]

HRFL1-080 1 230 50 2,7 10


HRFL1-160 3 400 50 5,3 10
HRFL1-250 3 400 50 8,4 10

Characteristics of electric afterheater coil

Type Phase [pcs] Voltage [V] Frequency [Hz] Rated power[kW] ∆ T [°C]

HRFL1-080 1 230 50 1,6 6,3


HRFL1-160 1 230 50 2,7 5,3
HRFL1-250 3 400 50 4,8 6,3

Characteristics of water heating coil

Type Rated capacity * [kW] Water pressure loss [kPa] Air pressure loss [Pa] Air flow [m³/h] Connections diameter

HRFL1-080 6,3 20 20,8 800 1/2

HRFL1-160 12,1 58,3 28,4 1500 1/2

HRFL1-250 20,3 27,8 27 2500 1/2
* For water temperature gradient 90/70 and inlet air temperature 15°C

Correction coefficients for the capacities of the hot water coil*

Water temperature gradient


Air inlet temperature [°C]
90/70 85/65 80/60 75/55 70/50 65/45
0 1,31 1,22 1,13 1,04 0,95 0,86
5 1,2 1,11 1,02 0,94 0,85 0,76
10 1,1 1,01 0,92 0,84 0,76 0,67
15 1,0 0,91 0,83 0,74 0,66 0,58
20 0,9 0,82 0,74 0,66 0,58 0,50

* To apply to the rated capacity in the characteristics of the hot water coil..

10
HEAT RECOVERY

Therm-X | HRFL

Recommended Kvs for different temperature gradients

Kvs [flow / kPa]


Type Recommended pump pressure [kPa]
90/70 [°C] 85/65 [°C] 80/60 [°C] 75/55 [°C] 70/50 [°C] 65/45 [°C]
HRFL1-080 1,6 1,6 0,6 0,6 0,6 0,6 60
HRFL1-160 2,5 2,5 1,6 1,6 1,6 1,6 60
HRFL1-250 4,0 4,0 2,5 2,5 2,5 2,5 60

Characteristics of water cooling / heating coil (C/O) - heating

Type Rated capacity [kW]* Water pressure loss [kPa] Air pressure loss [Pa] Air flow [m³/h] Connection diameter

HRFL1-080 5,89 1,3 59,2 800 3/4

HRFL1-160 10,85 0,9 74,8 1500 3/4

HRFL1-250 18,8 1,4 71 2500 3/4
* For water temperature gradient 60/40 and inlet air temperature 15°C.

Correction coefficients of the capacities of the hot water coil operation (C/O)*

Water temperature gradient


Air inlet temperature [°C]
60/40 55/50 45/40 35/30
0 1,55 1,73 1,39 1,05
5 1,36 1,54 1,21 0,87
10 1,18 1,35 1,03 0,69
15 1 1,18 0,85 0,52
20 0,82 1 0,68 0,36
* To apply to the rated capacity in the characteristics of the water coil.

Characteristics of water cooling / heating coil (C/O) - cooling

Type Rated capacity [kW]* Water pressure loss [kPa] Air pressure loss [Pa] Air flow [m³/h] Connection diameter

HRFL1-080 2,78 3,2 65,9 800 3/4

HRFL1-160 3,94 1,4 74,8 1500 3/4

HRFL1-250 7,52 2,2 71 2500 3/4
* For water temperature gradient 7/12 and inlet air temperature 25°C with 70% of relative humidity.

Correction coefficients of the capacities of the cool water coil operation (C/O)*

Water temperature gradient


Air inlet temperature [°C]
7/12 6/11 5/10
20 0,43 0,53 0,62
25 1 1,09 1,18
30 1,66 1,75 1,84

* To apply to the rated capacity in the characteristics of the water coil.

Recommended Kvs for different temperature gradients

Kvs [flow / kPa]


Type Recommended pump pressure [kPa]
7/12 [°C] 6/11 [°C] 5/10 [°C]
HRFL1-080 4,0 4,0 4,0 60
HRFL1-160 12,0 12,0 12,0 60
HRFL1-250 12,0 12,0 12,0 60

11
HEAT RECOVERY

Therm-X | HRFL

DIMENSIONS

THERM-X (HRFL) with electric coil / without coil


L L
G G E E

K
D

D
B

B
22

H
M M R R

J
C C
A A

Type A B C D E F G H I J K L M O P R S T W Weight [kg]

HRFL1-080HXCBE54-...S0(E1) 1400 840 900 872 675 90 350 350 x x 200 300 690 x x 336 x x x 112

HRFL1-160HXCBE54-...S0 (E1) 1700 1280 1200 1312 885 90 420 390 x 45 250 500 855 x x 424 x x x 198

HRFL1-250HXCBE54-...S0 (E1) 2000 1600 2x700 1632 1003 90 500 480 x 45 300 600 1005 x x 523 x x x 296

THERM-X (HRFL) with water coil


L L
G G E E
F

P P
O O
D

D
B

W
H

22
S

S
T

M M R R
J

C C
A A

Type A B C D E F G H I J K L M O P R S T W Weight [kg]


HRFL1-080HXCBE54-...V1 1400 840 900 872 675 90 350 350 x x 200 300 690 303 332 336 132 65 in 1/2 112

HRFL1-160HXCBE54-...V1 1700 1280 1200 1312 675 90 420 390 x 45 250 500 855 433 457 424 141 74 in 1/2 188

HRFL1-250HXCBE54-...V1 2000 1600 2x700 1632 735 90 500 480 x 45 300 600 1005 519 542 523 169 102 in 1/2 274

12
HEAT RECOVERY

Therm-X | HRFL

THERM-X (HRFL) with changer over coil

HRB2-080EC-CF-HBXX(E)
HRB2-080EC-CF-HBXW
HRB2-080EC-CF-HBXC
HRB2-150EC-CF-HBXX(E)
HRB2-150EC-CF-HBXW
Type A B C D E F G H I J K L M O P R S T W Weight [kg]
HRB2-150EC-CF-HBXC
HRB2-250EC-CF-HBXX(E)

HRFL1-080HXCBE54-...C3 1400 840 900 872 675 90 350 350 252 45 200 300 690 305 332 336 140 76 out3/4 117
HRB2-250EC-CF-HBXW

HRFL1-160HXCBE54-...C3
HRB2-250EC-CF-HBXC 1700 1280 1200 1312 675 90 420 390 364 45 250 500 855 432 422 424 165 100 out 3/4 193

HRFL1-250HXCBE54-...C3 2000 1600 2x700 1632 735 90 500 480 430 45 300 600 1005 500 504 523 187 115 out 3/4 279

HRB2-080EC-CF-HBXX(E)
HRB2-080EC-CF-HBXW
HRB2-080EC-CF-HBXC
HRB2-150EC-CF-HBXX(E)
HRB2-150EC-CF-HBXW
HRB2-150EC-CF-HBXC
HRB2-250EC-CF-HBXX(E)
HRB2-250EC-CF-HBXW
HRB2-250EC-CF-HBXC

2-080EC-CF-HBXX(E)
2-080EC-CF-HBXW
2-080EC-CF-HBXC
2-150EC-CF-HBXX(E)
2-150EC-CF-HBXW
2-150EC-CF-HBXC
2-250EC-CF-HBXX(E)
2-250EC-CF-HBXW
2-250EC-CF-HBXC

13
HEAT RECOVERY

Therm-X | HRFL

Description of control

The Therm-X units are equipped with a fully integrated intelligent control Time scheduling
package to enable regulation of the ventilation rate and indoor air
Allows setting the unit operation, airflow in daily or weekly periods with
quality requirements.
up to 4 time windows.
The in-built controls include:

• 4 temperature sensors (fresh air, supply air, return air and extract air) Air temperature control
• 1 sensor for antifreeze protection
The supply air temperature can be regulated by the use of the integrat-
• 2 digital pressure sensors for filters ed temperature sensors or an external room temperature sensor.
• 3 digital pressure sensors for constant air flow / pressure control
The unit’s control unit automatically controls the recuperative exchang-
• 2 water temperature sensors (only versions with water battery) er efficiency by regulating the face and bypass dampers positions.

When the conditions for free cooling are favorable (e.g. summer night
Airflow control ventilation) the unit adjusts the bypass damper in order to utilize the
colder outside air and save on space cooling.
The unit controls offers continuous flow rate regulation of the airflow
range of the unit in 10% steps. Where an electrical post heater is installed the supply air temperature
is continuously regulated to match the pre-set temperature on the
The unit can be set to operate in 3 distinct ventilation modes to regulate
controller.
the supply of outside air for ventilation purposes.
For continuous (PID) water coil performance regulation, the unit outputs
a 0-10 V signal for analog valve actuation to control the water flow
CAV (Constant air volume) operation across the coil.
The control unit is programmed to supply a constant amount of air to
Where the maximum re-heater performance is not enough to achieve
the ventilated space.
the requested value, the unit reduces the inlet flow rate to achieve the
The unit will self-adjust the fans output according to the pressure in the requested temperature.
supply air duct in order to maintain the amount of air being supplied to
the rooms.
Additional features
• Soft start
VAV (Variable air volume) constant pressure operation
• Record of operational state
The control unit adjusts the fan output to maintain a constant pressure
• Fire mode
in the duct while varying the air volume according to the demand of the
• Fan failure alarm and overheat protection
ventilated space.
• Electric pre and post heater overheat protection
The unit adjusts the supply flow rate according to the total opening of
the supply VAV terminal units or extract grilles in the duct system. • Condensate overflow protection
• Integrated plate heat exchanger frost protection

DCV (Demand Controlled Ventilation)


The unit regulates the supplied airflow according to the occupancy on
the ventilated space matching the outdoor air supply to the ventilation
demand.

The fan output is determined by a 0-10V input from an air quality sensor
(CO2 or Relative Humidity).

The supply flow rate is regulated according to the 0-10V signal.

Stand by (no occupancy) -CAV


If an PIR occupancy sensor is installed, in the event of no occupancy
the unit operates at minimum defined airflow to save energy.

Boost mode – CAV and DCV


When there is a high demand for ventilation or a swift heating or cool-
ing of the space is necessary (unit start up) the boost mode operates
the unit at maximum airflow for a determined time period

14
HEAT RECOVERY
ALFA Vent
Therm-X | HRFL

The control panel also provides power and control


Control using a wired remote control
to the following:
• Optional inlet and outlet damper actuators BMS integration (RS 485/ModBUS)
BASIC FEATURES KURZE CHARAKTERISTIK
• Optional integrated electric pre and post heater Dual ModBus
- Air capacity
• Room500 up to 12sensor
temperature 000 m3/h - Luftleistung 500 bis 12000 m3/h
- Water heater, electric heater, water cooler - Fünf Größen Controls based on CO2 concentration or relative humidity with
• Duct or room mounted air quality sensor - Relative humidity
- Nordic model for very cold regions - Wasseraufwärmer, elektrischer
ancillary Aufwärme, Wasserkühler
air quality sensors
or CO2
- Integrated control system with a remote controller - „Nordic“ Ausführung für sehr kalte Gebiete
- CompactPIR
• design
occupancy sensor Controlmit
- Integrierte Reglung based on occupancy with ancillary PIR sensor
Fernbedienung
- 36-month guarantee - Kompakte Ausführung
CAV system operation
BMS integration - Gewährleistung 36 Monate
The ALFA Vent supply and exhaust ventilation units are a
VAV system operation
HVAC device whichis provided
BMS integration suppliesby or extracts
connecting aircontrol
the unit from the Die Zuführungsbelüftungseinheit ALFA Vent ist eine
building, filters
through it, heats
a Modbus it up,allowing
RTU protocol and control
cools and it monitoring
down, if Lufttechnische Einrichtung, welche die Luft aus dem Freien
DCV system operation
necessaryof the(depending
unit. on the accessories installed in the zuführt, diese filtert, aufwärmt und ggf. auch abkühlt (in
unit). The unit is not designed for the hot-air heating. Abhängigkeit von der (Night
Free cooling Ausführung der Einheit). In
time ventilation)
The ALFA BacNet
Ventprotocol is available
ventilation unitby is
request.
particularly suitable for umgekehrter Richtung fürt die Ablufteinheit ALFA die Luft
ventilating offices, smaller shops, cafés, restaurants, sport aus Räume ab und Boostbläst
modediese ins Freie hinaus. Die Einheit
centers, and other facilities. ist für keine Heißluftheizung bestimmt.
The unitRemote
shall becontroller allows:in a dry area with ambient
installed indoor Fire protection
Die Belüftungseinheit ALFA Ventmodeist besonders zum Belüften
temperatures ranging from +5 °C up to +35 °C and relative
• Adjust operational parameters; von Büros kleinerer Geschäfte, Kaffees, Restaurants,
Sportzentren und Fan failure alarm
weiterer Räumlichkeiten geeignet.
humidity of up to 80 %. It is designed for conveying air free
of rough • Display
dust,the grease,
alarms; chemical fumes, and other Die Einheit ist für den Betrieb in innerem trockenen Umfeld
Filter monitoring and clogging indication
impurities with
• Full set auptemperature
and calibration of ranging
the unit; from -30 °C (from - mit einer Umgebungstemperatur im Bereich von +5°C bis
40 °C for• Nordic model) up to +40 °C and relative humidity
Time scheduling; +35°C, relativer Luftfeuchtigkeit
Condensate bis 80%, für den
overflow protection
of up to 90 %. The complete unit installed in a duct has an IP Transport der Luft ohne groben Staub, Fettigkeit, Dämpfe
rating of• 20.
Monitoring of the unit operation;
The ventilation unit project shall always von Chemikalien und weiterer Verschmutzungen mit einer
be developed by the HVAC designer. Temperatur im Bereich
Monitoring von -30°C
system („Nordic“ Ausführung ab
pressures
The housing of the
Data cable shall unit is made
not exceed lengthofof sandwich
20 m. Standardpanels. The
supplied von -40°C) bis +40°C und relativer Luftfeuchtigkeit bis
externallength:
surface
8 m. of the unit is painted silver. The control 90% bestimmt. Supply
Die Geräteeinheit ist in einer Rohrleitung
temperature regulation
system allows controlling the air capacity of the unit in five eingebaut und hat als Einheit die elektrische Schutzart IP
levels. In addition, it allows controlling the air heating and 20. Den Entwurf Room der Belüftungseinheit
temperature regulation hat stets der
cooling, adjusting the flaps, and identification of failure Projektant von der Lufttechnik zu lösen.
conditions. Das Gehäuse der ElectricEinheit ist aus Sandwich-Paneelen
coil regulation
hergestellt, die Außenseite ist lackiert in silberner Farbe.
Die Reglung ermöglicht
Hot water die Steuerung
coil regulation der Luftleistung von
(0-10V)
der Einheit in fünf Stufen, Steuerung der Luftaufwärmung
Control of ancillary shut-off
und -kühlung, Klappenbetätigung unddampers
Identifizierung der
Störungszustände.
Weekly and daily programming

VENTILATION
176 UNITS LÜFTUNGSGERÄTE
LÜFTUNGSGERÄTE VENTILATION UNITS
189

Produced in EU The company reserves the right of change without previous announcement. ©2VV, spol. s r.o.

15
HEAT RECOVERY

Therm-X | HRFL

Valves Actuators
Range of valve and actuator kits specifically selected and matched for Range of actuators selected for Open/Close operation of the rectangu-
application with the Therm-X units with post LPHW heater. lar and circular shut-off dampers for the Therm-X units.

The actuator can be supplied with or without spring return.


Zone rotary valves
Brass ball valves with linear characteristic and matching rotary modu- Actuator for rectangular or circular damper
lating actuator.
Unit type Non-Spring Return Spring Return

Valve & Actuator Kit HRFL1-080 SERVO-TD-04-230-1 ACT-SR-230-1

Unit type 2 way, 2 port 3 way, 3 port 3 way, 4 port HRFL1-160 SERVO-TD-04-230-1 ACT-SR-230-1
HRFL1-080 VALL22-HRFL-080 VALL33-HRFL-080 VALL34-HRFL-080 HRFL1-250 SERVO-TD-04-230-1 ACT-SR-230-1
HRFL1-160 VALL22-HRFL-160 VALL33-HRFL-160 VALL34-HRFL-160
NOTE:
HRFL1-250 VALL22-HRFL-250 VALL33-HRFL-250 VALL34-HRFL-250
Actuators supplied loose for mounting on site and wiring by others.

Characterized control rotary valves


Brass ball valves with characterized control and matching rotary mod-
ulating actuator.

Valve & Actuator Kit

Unit type 2 way, 2 port 3 way, 3 port

HRFL1-080 VALR22-HRFL-080 VALR33-HRFL-080

HRFL1-160 VALR22-HRFL-160 VALR33-HRFL-160

HRFL1-250 VALR22-HRFL-250 VALR33-HRFL-250

Pressure independent zone valves


Brass ball valves pressure independent valves and matching rotary
modulating actuator for facilitated commissioning and installation.

Valve & Actuator Kit

Unit type 2 way, 2 port

HRFL1-080 VALP22-HRFL-080

HRFL1-160 VALP22-HRFL-160

HRFL1-250 VALP22-HRFL-250

NOTE:

All valves are selected to operate with a water inlet temperature of


80oC and a water return temperature of 60˚C. Should other operating
conditions please contact Barkell for further information.

Coil valves / actuators supplied loose for mounting on site and wiring
by others.

16
ýrobků.
HEAT RECOVERY

Therm-X | HRFL
měry:

ACCESSORIES
Rozměry

rozměrRKx-AT;
Rectangular
RKx-ZT; RKx-NTshut off damper RKx-A RKx-Z; RKx-N

00 [mm]. matic shutting off the unit inlets/outlets and prevent drafts when the
The MLKR/S rectangular damper can be unit mounted to allow auto-

ířku listu 100 [mm]


unit is not in operation. The flanged damper frame is manufactured of
galvanized steel. The blades are made of aluminum.
ý rozměr Typické rozměry
Notes:

Actuator supplied separately. Power and control for the damper actu-
a - pro regulační klapky RKII-x; RKIII-x
ator provided by the unit control panel. Damper is supplied loose for A šířka [mm]
b - pro regulační klapky RKI-x
fitting on site.
B výška
Regulační klapky větších rozměrů jsou [mm]
děleny na menší pole.
Orientační hmotnost (kg)
Při objednávání
Type regulačních klapek,
které nejsou sériově vyráběné, se musí
Rectangular damper Recommended Actuator Všeobecné inform
HRFL1-080
uvést rozměry regulačních klapek AxB, MLKR/S-300200
varianta a druh mechanismu podle
HRFL1-160
zásad značení výrobků. Nomogram I
MLKR/S-500250 SERVO-TD-04-230-1

hlost proudění
Upozornění:
HRFL1-250
vzduchu Vliv rychlosti V a stupně otevření regulační klapky
MLKR/S-600300

Maximální rozměry:
ková tlaková ztráta
A ≤ 2500 [mm], na snížení tlaku ∆p.
B ≤ 2005 [mm].
el natočení listu Úhel otevření regulační klapky
dina intenzity zvuku
Vyrábíme každý rozměr
A = 0,1 [m²]
B od 200 do 2000 [mm].
S ohledem na šířku listu 100 [mm]
Rectangular damper A B

MLKR/S-300200 300 205


cha příčného průřezu
je doporučovaný rozměr
B = n x 100 + 5. MLKR/S-500250 500 255
ulační klapky
MLKR/S-600300 600 305

Všeobecné informace

Označení: Nomogram I
V [m/s] rychlost proudění vzduchu Vliv rychlosti V a stupně otevření regulační klapky
Δp [Pa] celková tlaková ztráta na snížení tlaku ∆p.
α [º] úhel natočení listu Opening angle of
Úhel otevření thedamper
regulační blades
klapky
LWA [dB(A)] hladina intenzity zvuku
pro A = 0,1 [m²]
A [m²] plocha příčného průřezu
regulační klapky
Snížení
Snížení
tlaku
drop
tlaku
Pressure
Δp [Pa]
Δp [Pa]

V [m/s]

verze 5.2.1 w w w. v z t - v y s ko c i l . c z 19
V [m/s]

w w w. v z t - v y s ko c i l . c z 17
BASIC FEATURES HEAT RECOVERY
КРАТКАЯ ХАРАКТЕРИСТИКА

- Diameters: 100, 125, 150, 160, 200, 250, 315, 355 mm


- Manual or servo drive control Therm-X | HRFL
- диаметры: 100, 125, 150, 160, 200, 250, 315, 355 мм
- управление ручное или посредством сервопривода

The KRTK-A shutting flap is designed for tight closing of З а п о р н ы й к л а п а н K RT K - A п р е д н а з н а ч е н д л я


individual branches in HVAC systems. The flap is designed герметичного закрытия отдельных воздуховодов
for operation in the basic environment for conveying air вентиляционных систем. Клапан предназначен для
free of rough dust, grease, chemical fumes, and other эксплуатации в основной среде и устанавливается
contaminants. The flap housing is made of galvanized в системах, в которых движется воздух без грубой пыли,
plate. The flap may be fitted with a servo drive after жиров, химических испарений и других загрязнений.
removing the manual control lever. Корпус клапана изготовлен из оцинкованного листа.
Circular shut off damper После демонтажа рычага ручного управления можно
оборудовать клапан сервоприводом.
TThe KRTK circular damper can be duct mounted to allow automatic
shutting off the ventilation system and prevent drafts when the unit is
not in operation.The damper housing is manufactured of galvanized
PRIMARY
steel. The damper mayPARAMETERS
be fitted with a actuator after removing the ГЛАВНЫЕ ПАРАМЕТРЫ
manual control lever.
h
iD

L2 L1 L2
L

Type Dimensions [mm] Sheet thickness [mm] Weight [kg]


Тип Размеры [мм]Dimensions [mm] Толщиналиста Bес [кг]
Unit type Circular damper Sheet
[мм] thickness [mm] Weight [kg]
D L L1 L2 h
D L L1 L2 h
KRTK-A-100 100 280 200 40 76 0,55 0,4
KRTK-A-125
HRFL1-080 125
KRTK-A-250 280 250 200
320 20040 60 73 65 0,55 0,80 0,6 2,1
KRTK-A-150 150 280 200 40 71 0,55 0,7
KRTK-A-160
HRFL1-160 160
KRTK-A-315 280 315 200
320 20040 60 70 64 0,55 0,80 1,0 3,6
KRTK-A-200 200 280 200 40 67 0,55 1,4
KRTK-A-250
HRFL1-250 250
KRTK-A-400 320 400 200
520 30060 60 65 65 0,80 0,80 2,1 6,3
KRTK-A-315 315 320 200 60 64 0,80 3,6
KRTK-A-355 355 420 300 60 63 0,80 5,1

COMPONENTS КОМПОНЕНТЫ 451

Transition square to circular


Produced in EU The company reserves the right of change without previous announcement. ©2VV, spol. s r.o.
PR-O – Galvanized transition piece from square to circular ducting.
Can be easily installed in the unit through the use of factory fitted nut
inserts.

Unit type Transition X Y D L M F

HRFL1-080 HRB-PR-02 300 200 250 200 50 20

HRFL1-160 HRB-PR-03 500 250 315 250 70 20

HRFL1-250 HRB-PR-04 600 300 400 300 70 20

18
HEAT RECOVERY

Therm-X | HRFL

Duct mounted electric heater


The EOKO electric duct mounted heater is designed for heating or
re-heating the supply air in HVAC systems.

It can be used for pre-heating or re-heating air from the Therm-X unit’s
recuperative exchanger were the optional in-built heater capacity is not
sufficient to achieve the required temperature or when closer tempera-
ture control of the room is required.

The heater is manufactured of galvanized steel and open coil electric


heating elements.

The electric IP rating of the cabling housing of the heater is IP 20.

Recommended combinations:

Unit type Type of el. heater

HRFL1-080 EOKO-250-4,5-3-D

HRFL1-160 EOKO-315-6,0-3-D

HRFL1-250 EOKO-400-9,0-3-D

250-4,5 315-6-3/9
EOKO-250-4,5-3-D EOKO-315-6,0-3-D
250

150
200
ps (Pa)
[P a] ps (Pa)

150
100
Static pressure
Static pressure

[P a]

100

50

50

0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000 3500 4000
Air flow[m3/h]
[m3/h] Air flow[m3/h]
[m3/h]

400-9
EOKO-400-9,0-3-D
150
Static pressure ps (Pa)

100
[P a]

50

0
0 1000 2000 3000 4000 5000 6000 7000
Air flow[m3/h]
[m3/h]

19
EOKO-450-18-3 450 18,0 3x400 delta / Delta 26,0 1060 55
EOKO-500-9-3 500 9,0 3x400HEAT RECOVERY
delta / Delta 13,0 530 60
EOKO-500-18-3 500 18,0 3x400 delta / Delta 26,0 1060 60
EOKO-560-12-3 560 12,0 3x400 Therm-X | HRFL
delta / Delta 17,3 707 66
EOKO-560-24-3 560 24,0 3x400 delta / Delta 34,6 1414 66
EOKO-630-12-3 630 12,0 3x400 delta / Delta 17,3 707 73
EOKO-630-24-3 630 24,0 3x400 delta / Delta 34,6 1414 73

Bushings / Tüllen

A
iD
C C
B

Voltage [V]
Nominal Output Connection Current Airflow Min. Dimensions [mm] Weight
Type
diameter [mm] [kW] Coils only Heater [type] [A] [m3/h] [kg]
A B C D

COMPONENTS KOMPONENTEN
ЕОКО-250-4,5-3 250 4,5 3x230 3x400 star 6,7 265 350 380 40 250 3,8

EOKO-315-6-3 315 6,0 3x230 3x400 star 8,8 353 430 380 60 315 6,2

EOKO-400-9-3 400 9,0 in EU 3x400


Produced 3x400 delta 13 530company
The 500 reserves
380 60 400 of change
the right 8,9 without prev

Determination of air temperature increase Duct mounted water heater


P[W] = V [m3/h] x 0,34 x Δt [°C] The VOK-01 water heater is designed for heating or re-heating the
supply air in HVAC systems.

Internal control system It can be used for pre-heating or re-heating air fromthe Therm-X unit’s
recuperative exchanger were the optional in-built heater capacity is not
The heater is supplied with fully integrated control panel with regulation
sufficient to achieve the required temperature or when closer tempera-
knob to adjust the desired set temperature.
ture control of the room is required.
To detect the temperature of the air an temperature sensor for duct
installation is provided with the heater. The heater shall be installed indoor in a dry area with ambient tempera-
tures ranging from 5 °C up to 60 °C and relative humidity of up to 80 %.
Notes:
The heater frame is made of galvanized steel with copper tubes and
The heater is supplied as a standalone product. Power and control to
aluminium fins.
the heater must be provided by an external source.
The controller regulates the heater output only. All other emergency and
safety functions shall be ensured by an external control system. Note:
Temperature sensor installation must be carried by the installer.
Additional heater control options are available by request. Please The water coil is designed for the maximum operating water tempera-
contact the office. ture of +100 °C and maximum operating pressure of 1.6 MPa.
Heater supplied loose for fitting and wiring on site Heater supplied loose for fitting on site.
Valves not included

20
HEAT RECOVERY

Therm-X | HRFL

80/60 Water temperature gradient 60/40 Water temperature gradient Dimensions [mm]

Air flow Weight


Rated Outlet Water Rated Outlet Water
Type Water flow Water flow
[m3/h] capacity* tempera- pressure capacity* tempera- pressure ØD A B C L [kg]**
[l/s] [l/s]
[kW] ture* [°C] loss [kPa] [kW] ture* [°C] loss [kPa]
G1"

200
VOK-01-T-250 1500 25,9 41
D 13 0,31 18,33 26,7 8,69 0,22 250 1 390 2
390 60 280 3
9,0
80
B

i
VOK-01-T-315 1500 25,9 41 13 0,31 18,33 26,7 8,69 0,22 315 390 390 60 280 9,0
150
VOK-01-T-400 2000 36 43 10,4 0,43 25,48 28,27 5,26 0,3 400 460 460 80 320 11,2
G 1/2" 65 C

Pressure loss [Pa]


A 90 160
* temperature of inlet air: -10 °C 1 250
** weight including fluid
L 100 2 315
3 400

G1"
50

G1" 200
D

1 2 3
80
B

2000
i
D

0 500 1000 1500 1 2000 2 2500 3000 3 3500


80
B

150
i

Air volume [m .h ]
3 -1

G 1/2" 65 C
Pressure loss [Pa]

150
A 90 160
G 1/2" 65 C
Pressure loss [Pa]

1 250
A 90 L160 100 2 315
1 250
L 100 3 400
2 315
3 400

50
50

0
00 500 1000 1500 2000 2500 3000 3500
0 500 1000 1500 20003 2500 3000 3500
Air volume [m .h ]
-1

Air volume [m .h ]
3 -1

Counter flow installation Parallel flow connection

Counter Parallelflow
flow connection
connection
Counter flowflow installation
installation Parallel

21
HEAT RECOVERY

Therm-X | HRFL

Condensate trap siphon

SK-HL138

Condensate trap siphon with integrated foul air infiltration prevention


system for installation recessed on wall or flush mounting.

The trap cover is transparent for easy monitoring of the water level.

Note:

Use of siphon is only recommended where gravity assisted condensate


collection is achievable.
Accessory supplied loose for fitting on site.
Pipework not included

Room CO2 sensor: CI-EE80-2CT3/T55


Room sensor for measurement of the CO2 concentration on ventilated
spaces. The 0-10V output signal can be connected to the Therm-X
unit control panel for regulation in the DCV operation. The operation is
based on the infrared principle. Auto-calibration procedure compen-
sates for the aging of the infrared source and ensures outstanding long
term stability.

Note:

Power can be provided by the unit to a single air quality sensor.


The unit only accepts input from a single air quality sensor.
Sensor supplied loose for wiring and fitting on site.
Cable not included. Use of shielded cable for wiring is recommended.

Power source 24V AC ±20% or 15–35V DC

Output voltage 0-10V 4–20mA

0...2000 ppm: < ± (50 ppm +3% of


Measuring range
measuring value)

Operational temperature -20°C up to 60°C

Electrical protection IP30

22
HEAT RECOVERY

Therm-X | HRFL

Duct CO2 sensor: CI-EE850-C3XXFP-002

Duct CO2 sensor for measurement of CO2 concentration on the return


ductwork. The 0-10V output signal can be connected to the Therm-X
unit control panel for regulation in the DCV operation. The elegant,
compact housing enables easy installation directly at the ventilation
duct using a mounting flange.

Note:

Power can be provided by the unit to a single air quality sensor only
The unit only accepts input from a single air quality sensor
Sensor supplied loose for wiring and fitting on site.
Cable not included. Use of shielded cable for wiring is recommended.

Power source 24V AC ±20% or 15–35V DC

Output voltage 0–5/10V 4–20mA

0...2000 ppm: < ± (50 ppm < ± (50


Measuring range
ppm+2% of mv)

Operational temperature 0...+50 °C (32...122 °F)

Electrical protection IP65

Seite 3 Page 3

Anwenderhinweise Application Notice


Durch Luftumwälzungen können sich im Laufe der Zeit auf dem Sinterfilter, Due to air circulations dirt and dust particles can be piled up in the course
der die Sensoren schützt, Schmutz und Staubpartikel ansammeln, die die of time on the sintered filter which is protecting the sensor. Thus, the
Funktion des Fühlers behindern können. function of the sensor can be affected. After having dismantled the filter,
Nach erfolgter Demontage des Filters kann dieser durch Ausblasen mit the same can be cleaned by blowing it out with oil-free and filtered
ölfreier, gefilterter Pressluft, Reinstluft, Stickstoff oder Auswaschen mit compressed air, super-clean air or nitrogen or by washing it out with
destilliertem Wasser wieder gereinigt werden. distilled water. If the filter is too dirty, the same should be replaced.
Zu stark verschmutzte Filter sollten getauscht werden. Refrain from touching the sensitive humidity sensor. Any touch of the
Jegliche Berührung der empfindlichen Feuchtesensoren ist zu unterlassen
Relative humidity duct sensor: CI-LCN-FTK140VV
same will result in an expiration of the warranty.
und führt zum Erlöschen der Gewährleistung. With normal environmental conditions we recommend a recalibration
Bei normalen Umgebungsbedingungen empfehlen wir ein Intervall für die interval of around 1 year to maintain the indicated accuracy.
Nachkalibrierung von 1 Jahr um die angegebene Genauigkeit At high ambient temperatures and high humidity, or when using the sensor
beizubehalten. in aggressive gases, an early recalibration or a change of the humidity
Bei hohen Umgebungstemperaturen und hohen Luftfeuchtigkeiten, sowie sensor can become necessarily. Such a recalibration or a probable sensor
beim Einsatz in aggressiven Gasen kann ein vorzeitiges Nachkalibrieren change do not come under the general warranty.
Duct relative humidity sensor for measurement of humidity on the return oder ein Feuchtesensortausch notwendigt werden. Eine solche
Nachkalibrierung oder etwaiger Sensortausch fallen nicht unter die
ductwork. The 0-10V output signal can be connected to the Therm-X allgemeine Gewährleistung.

unit control panel for regulation in the DCV operation. Zubehör optional Optional Accessories
(MF19-PA) Montageflansch zur Befestigung des Fühlers am (MF19-PA) Mounting flange for installation on ventilation duct
The sensor has an analogue voltage output 0-10V, corresponding to Lüftungskanal

the range of relative air humidity 0-100%.


Anschlussplan

Note:
Out Temp 0-10V

Power can be provided by the unit to a single air quality sensor only. UB 15-24V=/24V~
(min. 5kOhm)

(min. 5kOhm)

LCN-FTKxVV
+U
Gnd
The unit only accepts input from a single air quality sensor
Load

Load
RL

RL

Temp.Sensor (Option)

Sensor supplied loose for wiring and fitting on site.


-
Cable not included. Use of shielded cable for wiring is recommended.

Abmessungen (mm) Dimensions (mm)

Power source 15-24VDC/24AC +/-10%

Output voltage 0-10V DC

Measuring range -20...+80°C

Operational temperature -20...+70°C

Electrical protection IP65

Thermokon Sensortechnik GmbH - Aarstrasse 6 - 35756 Mittenaar - Tel.: 02772/65010 - Fax: 02772/6501400 - www.thermokon.de - email@thermokon.de
produktblatt_lcn_ftk_vv 2010 23
HEAT RECOVERY

Therm-X | HRFL

CI­‑PS 1003
Room (Passive Infrared) motion sensor for occupancy detection. When
something enters into controlled space, this sensor detects heat emis-
sion from bodies and switches its contacts on or off.

The signal can be connected to the Therm-X units turning the unit on or
off accordingly.

The sensor has a detection range of 12 meters at an 90° angle and can
be mounted on walls or installed in corners. It’s possible to switch on/off
light emission diodes (LED).

Lower boundary mass sensing is 25 kilos.

Note: ALARM TAMPER + 12 GND

Power provided by the unit control panel


Sensor supplied loose for wiring and fitting on site.
Cable not included. Use of shielded cable for wiring is recommended.

Power source 15-24 VDC

Detection area 12m

Detection angle 90°

Pulse scaler 1 or 2
+ 12 V: DС
Installation method Installation on walls GND ANODE:DC
Height of installation 1,8 up to 2,2m ALARM CATHODE: relay output
ТАMPЕR: Anti tamper switch
Operating temperature range -10°C up to +50°C

Signalisation output 1NC/1C 60V DC, 300mA

Operational contacts capacity 1NC, 28V DC, 100mA

Dimensions 106 mm x 54 mm x 36 mm

Spare filters
Spare replacement filters with the same design and manufacturing as
the ones supplied with the units.

Unit type Filter, class M5 Filter, class G4 Filter, class F7

HRFL1-080 FILTR-HRFL-080 M5 FILTR-HRFL-080 G4 FILTR-HRFL-080 F7

HRFL1-160 FILTR-HRFL-160 M5 FILTR-HRFL-160 G4 FILTR-HRFL-160 F7

HRFL1-250 FILTR-HRFL-250 M5 FILTR-HRFL-250 G4 FILTR-HRFL-250 F7

24
HEAT RECOVERY SPTGLX
Therm-X | HRFL

Threaded rods
ZTZ-M8-1,0 – threaded rod, thread M8, length 1m, suitable for all types
BASIC FEATURES GRU
of Therm-X units
- Diameters: 100 up to 400 mm - Durchmes
Notes: - Length: 500 and 1,000 mm - Länge: 50

Fixing supports are pre-fitted on the unit The SPTGLX round sound attenuator is designed for Der Rundd
4 rods necessary for supporting model 060 and 150 reducing noise propagated through the HVAC ducting. It is durch die
6 rods necessary for supporting model 250 designed for operation in the basic environment for verbreiteten
Items supplied loose for installation on site conveying air free of rough dust, grease, chemical fumes, Grundumfe
Your partner in ventilation...
and other contaminants. The sound attenuator housing is Fettigkeit,
made of galvanized plate. The sleeves are fitted with Verunreinig
Circular sound attenuator packing. verzinktem
SPTGLX Dichtung ve
The SPTGLX circular sound attenuator is designed for reducing noise
propagated through the HVAC ducting. The sound attenuator housing
is manufactured of galvanized steel and rockwoll infill.
PRIMARY PARAMETERS WIC

Note:
BASIC FEATURES GRUNDEIGENSCHAFTEN
Attenuators supplied loose for installation on site
- Diameters: 100 up to 400 mm - Durchmesser: 100 bis 400 mm
- Length: 500 and 1,000 mm - Länge: 500 und 1000 mm

The SPTGLX round sound attenuator is designed for Der Runddämpfer SPTGLX ist für die Verringerung des
reducing noise propagated through the HVAC ducting. It is durch die Rohrleitung der lufttechnischen Systeme
designed for operation in the basic environment for verbreiteten Schalls bestimmt. Dieser ist für den Betrieb im
conveying air free of rough dust, grease, chemical fumes, Grundumfeld, für die Luftförderung ohne groben Staub,
and other contaminants. The sound attenuator housing is Fettigkeit, Dämpfe von Chemikalien und weiterer
made of galvanized plate. The sleeves are fitted with Verunreinigungen bestimmt. Das Dämpfergehäuse ist aus
packing. verzinktem Blech, die Dämpferstutzen sind mit einer
Dichtung versehen.

PRIMARY PARAMETERS WICHTIGSTE PARAMETER Dimensions [mm] Attenuation value


Type Abmessungen [mm] Dämpfwerte [dB]
Dimensions [mm] Insertion losses [dB] in frequency bands [Hz]
Тyp
Type L d D Weight
250[kg] 500 10
L d D 250 500 1000
SPTGLX-0,5-100 2000
500 4000
100 8000
200 7 16 2
SPTGLX-1,0-100 1000 100 200 14 22 4
SPTGLX-0,5-250 500 250 350 4 9 19 8 5 4 8,6
SPTGLX-0,5-125 500 125 225 5 13 2
SPTGLX-1,0-250 1000 250 350 6 14 SPTGLX-1,0-125
27 151000 9 125 7 225 12
12,6 22 4
SPTGLX-0,5-160 500 160 260 6 15 3
SPTGLX-0,5-315 500 315 415 3 9 14
SPTGLX-1,0-160 61000 4 160 3 260 10,3
10 19 3
Dimensions [mm] Attenuation values [dB] in frequency bands [Hz]
Type Abmessungen [mm] Dämpfwerte [dB] SPTGLX-0,5-200
in Frequenzbereichen [Hz] von 500 200
Weight [kg] 300 5 8 2
Тyp Gewicht [Kg]
SPTGLX-1,0-315 1000 315 L 415
d D 7250 500 15 27
SPTGLX-1,0-200
1000 2000 4000 111000
8000 8 200 6 300 15,2
9 17 3
SPTGLX-0,5-100 500 100 200 7 16 28 25 11 13 4,7
SPTGLX-1,0-100 1000 100 200 14 22 43SPTGLX-0,5-250
28 16 500
12 6,7 250 350 4 9 1
SPTGLX-0,5-00 500 SPTGLX-0,5-125
400 500
500
125 225
45 13
8 26 14
13 8
5 7 5,2
5 3 12,6
SPTGLX-1,0-250 1000 250 350 6 14 2
SPTGLX-1,0-125 1000 125 225 12 22 42 22 15 10 7,7
3 9 1
SPTGLX-1,0-400 1000 SPTGLX-0,5-160
400 500
1000
500
160
160
260
260
5106 15
19
13 30SPTGLX-0,5-315
36
8
21
26
5
11
9 5005
13
6,2
8 315 5 415 18,5
SPTGLX-1,0-160 9,1
SPTGLX-1,0-315 1000 315 415 7 15 2
SPTGLX-0,5-200 500 200 300 5 8 23 10 5 5 7,3
SPTGLX-1,0-200 1000 200 300 9 17 35SPTGLX-0,5-355
18 10 500
9 10,6 355 455 4 8 1
SPTGLX-0,5-250 500 250 350 4 9 19 8 5 4 8,6
SPTGLX-1,0-250 1000 250 350 6 14
SPTGLX-1,0-355
27 15 9
1000
7 12,6
355 455 6 12 2
SPTGLX-0,5-315 500 315 415 3 9 14SPTGLX-0,5-400
6 4 500
3 10,3 400 500 4 8 1
SPTGLX-1,0-315 1000 315 415 7 15 27 11 8 6 15,2
Pressure loss determination graph for
SPTGLX-0,5-355 500 SPTGLX,
355 length
455 1m.
4 8 Pressure loss3 determination
14SPTGLX-1,0-400
5 1000
3 graph for SPTGLX,
11,2 400 500 length
5 0.5m.13 2
SPTGLX-1,0-355 1000 355 455 6 12 23 10 9 4 16,5
SPTGLX-0,5-400 500 400 500 4 8 13 5 5 3 12,6
SPTGLX-1,0-400 1000 400 500 5 13 21 9 8 5 18,5

COMPONENTS KOMPONENTEN
COMPONENTS KOMPONENTEN 483

Produced in EU Produced
The company reserves the right of inprevious
change without EU announcement. ©2VV, spol. s r.o. The company reserves the right of

25
HEAT RECOVERY

Therm-X | HRFL

Connection cable
RJ12 6pin communication cable for connecting the remote controllers
to the Therm-X unit. The cable is supplied with all types of units in a
standard length 8 m. Other lengths are available based on the coding
key provided below.

KABEL-05M

03, 05, 08, 10, 15, 20, 30, 40– cable


length in m
(unless otherwise stated in the order, the
cable is a standard 8 m) Maximum cable
length is 40 m.
KABEL - connection cable

KEY TO CODING

HRFL1-080 H X CB E 54-X S0 C-1A0

C Regulation
C Comfort regulation

S0 After heater
S0 Without after heater
E1 Electric after heater
V1 Water after heater
C3 Heater/cooler

X Preheater
X Without preheater
E Electric preheater

54 Filtration (inlet / outlet)


54 inlet M5; outlet G4

E Type of fans
E EC fans

CB By-pass
CB Counterflow plate heat
exchanger with bypass

X Version of access
X Universal

H Installation
Horizontal installation

080 Nominal airflow


080 Nominal flow rate 800 m3/h
160 Nominal flow rate 1600 m3/h
250 Nominal flow rate 2500 m3/h

HRFL1 Unit Type
Commercial recovery
unit THEMR-X

26