Columns Short and Slender2
Columns Short and Slender2
Columns Short and Slender2
Columns are element with height larger or equal three times the least dimension; primary
designed for compressive loads, and classified to short and Long (slender) columns.
Types of columns:
1- Tied columns: with separate ties at distance as allowable.
3- Composite columns
1
Limits for reinforcement of compression members ( ACI-CODE 08):
1- Area of longitudinal reinforcement: For compression members shall be not less than
0.01Ag or more than 0.08Ag. Minimum number of longitudinal bars in compression
members shall be 4 for bars within rectangular or circular ties, 3 for bars within
triangular ties, and 6 for bars enclosed by spirals.
2- Tie reinforcement for compression members shall conform to the following:
3.1- Tie reinforcement for compression members shall conform to the following:
All bars shall be enclosed by lateral ties, at least No. 10 in size for longitudinal bars
No. 32 or smaller and at least No. 13 in size for No. 36, No. 43, No. 57, and bundled
longitudinal bars.
3.2- Vertical spacing of ties shall not exceed 16 longitudinal bar diameters, 48 tie bar
or wire diameters, or least dimension of the compression member. Ties shall be
arranged such that every corner and alternate longitudinal bar shall have lateral
support provided by the corner of a tie with an included angle of not more than 135
degrees and no bar shall be farther than 150 mm clear on each side along the tie from
such a laterally supported bar. Where longitudinal bars are located around the
perimeter of a circle, a complete circular tie shall be permitted.
3.3- Ties shall be located vertically not more than one-half a tie spacing above the top of
footing or slab in any story, and shall be spaced as provided herein to not more than
one-half a tie spacing below the lowest horizontal reinforcement in slab, drop panel,
or shear cap above.
3- Spirals: Spirals shall consist of evenly spaced continuous bar or wire of such size and so
assembled to permit handling and placing without distortion from designed dimensions. For
cast-in-place construction, size of spirals shall not be less than 10 mm diameter.
Clear spacing between spirals shall not exceed 75 mm, nor be less than 25 mm.
Volumetric spiral reinforcement ratio, , shall be not less than the value given by
2
2
2
= 0.45 2 1
Or = 0.45 2 1
4 (
)
And the spacing
=
2
Anchorage of spiral reinforcement shall be provided by 1-1/2 extra turns of spiral bar or wire
at each end of a spiral unit. Spiral reinforcement shall be spliced, if needed, by any one of the
following methods:
(a) Lap splices not less than the larger of 300 mm and the length indicatedbelow:
(1) deformed uncoated bar or wire............... 48d
(2) plain uncoated bar or wire ...................... 72d
(3) epoxy-coated deformed bar or wire........ 72d
$[LDOVWUHQJWKij3Q :
for compression members shall not be taken greater than ij3QPD[ computed by ;
1- For nonprestressed members with spiral reinforcement ;
! = ", #$ = 0.85 "[0.85 (
) + ]
2- For nonprestressed members with tie reinforcement;
! = ", #$ = 0.8 "[0.85 (
) + ]
3
Compression-controlled sections, as defined above the " value:
(a) Members with spiral reinforcement .................................0.75
(b) Other reinforced members ............................0.65
For sections in which the net tensile strain in the extreme tension steel at nomiQDOVWUHQJWKİt, is
between the limits for compression-controlled and tension-FRQWUROOHG VHFWLRQV ij shall be
permitted to be linearly increased from that for compression-FRQWUROOHGVHFWLRQVWRDVİt
increases from the compression controlled strain limit to 0.005.
Ex.1: For the two columns shown below compare the capacity of the columns if they specify
the minimum ACI-Code requirements. (f’c=25MPa, and fy = 414MPa)
For spiral:
&450 2 6&20 2 6&20 2
! = 0.85 0.75 %0.85 25( )+ 414'= 2627.36kN
4 4 4
The ratio = 2627.36/2494.37 = 1.05
Ex.2: Design a short tied column support service dead load of 1600kN and service live load of
900kN try
*- #
= 28## 1.7% with f’c= 20.7MPa and fy =
350MPa.
! = 0.8 "[0.85 (
) + ]
3360 1000 = 0.8 0.65[0.85 20.7(
0.017
) + 0.017
350]
4
Ag= 277963.45mm2 the - = 9277963.45 = 527.2## use 530mm
8 & 142
= = 0.0175 ;. > 1% < 8%
530 530
For ties use 10mm bars with spacing ? 16 28 = 448##
? 48 10 = 480##
? 530##
530240210328
Sect. B= = 177## > 150##
@ .
2
Ex.3: Design a short circular spirally reinforced column support service dead load of 1100kN
and service live load of 950kN try
*- #
= 25## 2% with f’c=
27.5 MPa and fy = 400MPa.
! = 0.8 "[0.85 (
) + ]
2840 1000 = 0.8 0.65[0.85 27.5(
0.02
) + 0.02
400]
4176705 .93
Ag= 176705.93 mm2 the = A = 474.3## use 480 mm
&
5
& 4802
2840 1000 = 0.8 0.65 B0.85 27.5( ) + 400C
4
3270 .36
Ast = 3270.36 mm2 try bars with 30 mm diameter, then no. of bars = = 4.6 bars use
&15 2
minimum of 6 bars
6 & 152
= = 0.0234 ;. > 1% < 8%
& 4802
4
For spirals use bars with 10mm diameter then:
Ex.4: Design a rectangular short tied column with h/b ratio of 1.5 , support service dead load of
300kN and service live load of 500kN try
*- #
= 20## 2% with
f’c= 20.7MPa and fy = 400MPa.
! = 0.8 "[0.85 (
) + ]
1160 1000 = 0.8 0.65[0.85 20.7(
0.02
) + 0.02
400]
88371 .526
Ag= 88371.526mm2 = - = 1.5 2 - = A = 242.7## use 250mm
1.5
6
6 & 102
= = 0.0198 ;. > 1% < 8%
250 380
For ties use 10mm bars with spacing ? 16 20 = 320##
? 48 10 = 480##
? 250##
Plastic centroid: the point that the resultant of compressive loading should be applied through
and it coincide with the section center if symmetry exist.
Po = Cc + Cs = 0.85*f’c*b*h+As*fy+As’ *fy
-
X = $ = Y + (- ) +
2
Where:
Po= resultant of forces
Cc= concrete compressive strength
Cs= steel compressive strength.
Ex.5: Find the position of plastic centroid for the column section shown below, use f’c=30MPa
and fy= 400MPa. (As total = 10 ѫ 20mm )
Po= [0.85*30(300*600+200*200)+10*314*400]/1000
Po= 6866kN
Cc*Xc= 0.85*30[300*600*350+200*200*100]/106
= 1708.5kN.m
As*fyx=400[2*314*40+4*314*240+4*314*460]/106
= 361.73 kN.m
7
M= Cc*Xc +As*fyx= 1708.5+361.73=2070.23kN.m
Po*X= M then X= 2070.23/6866 = 0.302= 302mm
:ΞΘϨΘδϧΕϻΎόϔϧϻϖϓϮΗϦϣϭ
ƍ
Z = Z! and Z = Z! then = 600 and ƍ = 600
:(ϥΪϠϟΰϛήϤϟϝϮΣϡϭΰόϟάΧΎΑ)ϯϮϘϟϥίϮΗϦϣϭ
\ = 0 = Y + Y ^ then = 0.85 . . + . + .
8
- - -
_X = 0 . = Y + Y + ^( )
2 2 2 2
- - -
X = 0.85 . . + . ( ) + . ( )
2 2 2 2
Ex.1; A short column 300*500mm supports load with eccentricity of e= 150 mm find nominal
section axial capacity and moment, use d’ =60mm, f’c=
25MPa and fy= 350MPa?
Cc = 0.85*25*255*300/1000 =1625.63kN
Cc = 0.85*25*298*300/1000 =1899.75kN
9
X = 1899.75(0.25 0.15) + 431.2(0.25 0.06) + 189.73(0.44 0.25) = 307.95;`. #
e= 307.95/2414.22= 0.144m = 144mm less more than 150 mm try another value of c.
ΕϻΎΤϟϭ (e )ΔϳΰϛήϣϼϟΔϤϴϗϰϠϋϚϟΫΪϤΘόϳϭΕϻΎΣΙϼΛϰϟϞθϔϟϞϜηϰϠϋΩΎϤΘϋΓΪϤϋϻϒϨμΗ
-:ϲϫΔϴϟΎΘϟ
1- Balanced Failure ϥίϮΘϤϟϞθϔϟ:
The failure happened when the stresses in steel reach the value of maximum (fy) at the
same moment the strain in concrete reaches the maximum value of (Z! = 0.003)
= 0.85 . . + . + .
- - -
X = 0.85 . . + . ( ) + . ( )
2 2 2 2
= X/
3- Compression failureρΎϐπϧϻϞθϓ
ςϠδϤϟϡΰόϟϭϞϤΤϟϰϠϋΩΎϤΘϋΔόϗϮΘϤϟϞθϔϟϝΎϜηϦϴΒϳϭΓΪϤϋϼϟϡϭΰόϟΎΑϯϮϘϟΔϗϼϋϊοϮϳϩΎϧΩϞϜθϟϥ
10
:ΔϴϟΎΘϟΕϻΩΎόϤϟΐδΣ
11
Ex. 2: Find the balanced eccentricity for the column shown use f’c= 30MPa and Fy= 400MPa?
12
Ex.3: The column shown in figure below finds the axial strength and moment capacity, use
f’c=30MPa, fy= 400MPa and 4 bars with 28mm diameter if:
1- ex= 250mm
=0.85*264=
2- ey= 250mm
224.4mm
13
14
Ex.4: A short tied column with 400x550mm supports Pu=4000kN and Mu= 220kN.m .find area
of steel required if f’c =30MPa and fy= 400MPa and d’= 70mm use two layer one at each side.
4000 1000
d = = 0.93
0.65 30 400 550
For c = 0.7 -
= 0.023
For c = 0.8 -
= 0.021
Then for c = 0.75 -
= 0.022
15
Ex.5: Design the rectangular column if it supports Pu= 2200kN and Mu= 660kN.m, using f’c=
30MPa and fy= 400MPa( assume
= 0.03
).
2200 1000
d = = = 0.48 e = 392## ! = 400##
- 0.65 30 600
Ex. 6: A circular column with diameter of 400mm supports design load of 2800kN and design
moment of 135kN.m. Find area of steel and stirrups required for the section, use f’c= 30MPa,
d’= 60mm and fy= 400MPa.
X! 135 48
= = = 0.048# = 48## - = = 0.12
! 2800 400
& 4002
= = 125664 ##2
4
Try ѫ = 0.75 then
400260
and c= = 0.7
400
from the chart
= 0.045 - = 0.045 125664 = 5655##2
Use 8ѫ 30mm for stirrups use ѫ10mm dcore= 400 - 2*40= 320mm
16
2
ƍ 4002 30
= 0.45 R 1T = 0.45 f 1g = 0.016
2 (320)2 400
17
18
19
Ex.7: Check the adequency of the column shown below the loads Pu= 1200kN and the moments
are Mux= 90kN.m and Muy= 180kN.m, use f’c= 30MPa and fy= 400MPa.
Try ѫ = 0.65
4&30 2
= = 0.01414 from charts Kn = 0.36=
4005004 f’c bh
Ex.8: The circular spiral column with diameter of 500mm is reinforced by 8 bars of 25mm the
axial aplied load was Pu =2250kN , what moment would cause the column fail? Use f’c=
30MPa, and fy= 400MPa.
500275
c= = 0.7
500
2250 1000
Kn = = = 0.507
"f’c Ag 0.7530&500 2 /4
8 & 252 /4
= = .02
& 5002 /4
Ex.9 : The circular spiral column with diameter of 500mm is reinforced by 8 bars of 25mm the
axial aplied load was Pu = 1200kN , the moments are Mux= 90kN.m and Muy= 180kN.m, use
f’c= 30MPa, d’= 75mm and fy= 400MPa. Check the adequency of the column shown below.
X!$ 90
= = = 0.075# = 75##
! 1200
from charts Kn = 0.41=
f’c Ag
From the figure below it seen that the buckling stress (or load)
decreases rapidly with increasing slenderness
ratio for short column the value of buckling loads exceeds
the direct crushing strength
Pn = 0.85 f ƍ c Ac + Ast fy
;r! ;r!
When < [ failur occurs by simple crushing
@#
22
;r! ;r!
When > [failure occurs by buckling]
@#
Note: From above Pc value for braced column is larger than Pc for unbraced column and
depending on degree of restrained k value could be calculated from the chart below.
23
Slenderness effects:
ACI-Code 318 allow to neglect slenderness effect and design as short column if :
a) Braced columns (non- sway)
N
neglect slenderness if ? VE NM ? ED
M
24
where : M 1 (smaller) and M 2 (larger) end moments
N N
D. F the sign of is (+) for single curvature and (-) for double curvature.
M M
= D. V
!
!@
@!#
( *-
- -
#@ #
)
= D. MF
!@
@!# ( D is the diamerter)
Pu o
= ? 0.05
Vu Lc
Where:
Pu = sum of axial load in the floor (kN).
Vu= sum of shear force in floor (kN).
o = horizontal displacement ( difference between displacement at the ends due to horizontal
loads) (m)
Lc = length of column center to center between floors (m).
25
Increase in moment
Main
moments
Increase in moment
due to double
curvature
26
X1
Y# = 0.6 + 0.4 0.4
X2
¡¢£¤¤¥ N
(sign of is (+) for single curvature and (-) for double curvature) (for other cases Cm
¤£¦¥ M
=1.0) . To calculate Pc it is required:
EI
Lc columns
1- Calculate k for the column = EI (for hing support=WDNH = 10 and for
Lc beams
fixed support =0 take = 1)
p = 4700o and Ig moment of interia of section without reinforcement.
Beams I b = 0.35I g , Lc for beams are taken span cneter to center.
Columns I c = 0.7I g , Lc for columns are taken span cneter to center.
Walls no cracks I w = 0.7I g ,
Walls with cracks I w = 0.35I g ,
Slabs without beams I s = 0.25I g
Area for beams, columns and slabs is taken Ag without reinforcements, Ig moment of interia
for hall section. For (T) or (I) beams use Ig = 2I web .
0.4 p q
Ex.1) A rectangular tied braced column is reinforced with 6-28mm bars as shown in figure
below check the adeqancy of the column for the followning gravity loads . Service dead load=
900kN, service live loads = 800kN both are at eccentricity of 40mm. Service dead load
moments=34kN.m, service live load moments =25kN.m, F’c =27.5MPa, fy = 400MPa, Lu
=5m , = # = 1.0 ? Sol:
27
k= 0.77 from chart , r= 0.3* h= 0.3* 500=150mm
kLu 0.775000
= = 25.7 < 100
r 150
X1
34 12 = 34 12(+1) = 22
X2
kLu
= 25.7 > 22 the column is slender
r
5003
0.4 p q
0.4 350 12 4700927.5
pq = =
1 + a (1 + 0.534) 109
= 23431.26 ;`. #2
4
&
& 284 & 282
q = 6 R + 2 T = 6 R + (186)2 T = 6(0 + 21302561) = 127815370.4 ##4
64 64 4
500 3
o.2Ec Ig +Es .Ise 0.2350 4700 927.5+200000 127815370 .4
12
EI = = (1+0.534)10 9
= 28379.95 kN.m2
1+§d
«¬ N
= = MVWD = 1.199 1
N N
D.UFI D.UF18896 .87
28
28
5002(40+10+ )
2
c= = 0.75
500
! 2360 1000
; = = = 0.754
" - 0.65 27.5 350 500
For c = 0.7 = 0.018
c = 0.8 =0.017
c = 0.75 =0.0175
As = 0.0175*350*500 = 3062.5 mm2
As provided 6-28 As= 3694mm2 more than required. The column is adequate.Ties -10mm
spaecing ? 16*28= 448mm
?48*10= 480mm
?350mm then adequate.
Ex.2: The column with (300*375mm) and single curvature about y-axis shown
below in a building braced against side sway,and ultimate loads shwon in figure
(the service dead load of 133kN). Find steel area required and check the slenderness
about bending axis (y-axis) use Lu=4.8m and k=0.85 f’c = 30 MPa fy = 400MPa,
& 2 pq ª 2 9837.2
= (;r! ))2 = (0.834.8)2
= 5832 ;`
Y# 0.983
= = = 1.107 1
! 490
1 1
0.75 0.75 5832
Mmin = Pu*e min = 490*(15+0.03*370)/1000= 12.86 kN.m
Mc= X2 = 1.107 117 = 128.7 ;`. #
Design values:
Pu = 490kN , Mc = 128.7 kN.m
X! 128.7 1000000
® = = = 0.16
" -2 0.65 30 300 3752
30
Ex.3: The figure below indicates the plan and side veiw of reinforced concrete
building with 10 stories.The ground floor has clear hight of 6.4m the other with
3.4m, the size of beams 500x600mm, External columns 500x500mm, Interior
columns 600x600mm and f’c=30MPa and fy= 400 MPa, Design the columns A3
and C3 of ground floor the shear wall used for bracing and side sway pevent, and
a = 0.8 . Check slenderness in the north-south N-S direction, the columns are
under double curvature, the axial loads and bending moments are:
31
For column C3 try d’= 75mm
6002(75)
c= = 0.75
600
! 8950 1000
; = = = 1.28
" - 0.65 30 6002
X! 16 1000000
® = = = 0.003
" -2 0.65 30 6003
Then from charts find = 0.052 Check slenderness use k=1:
kLu 16400
= = 35.6 < 100
r 0.3600
X1 8.4
34 12 = 34 12 = 40.3 > 40 ! 40 *-- > 35.6 - -
@!#
X2 16
32
EI
Lc columns
Check k exactly : = EI
Lc beams
0.7 5004
q 12
# = = 0.548 106 ##4
r 6650
0.7 5004
q 12
= = 0.935 106 ##4
r 3900
0.35 600 5003
q 12
= = 0.26 106 ##4
r 8400
EI
Lc columns 0.54810 6 +0.93510 6
= EI = = 5.7
0.2610 6
Lc beams
# = 1.0 $
# #
kLu 0.846400
k = 0.84 and : = = 35.9 <40
r 0.3500
X1 81
34 12 = 34 12 = 27.85 < 35.9
@ !
¯!
- @
@!#
X2 158
X1 81
Y# = 0.6 + 0.4 = 0.6 + 0.4 = 0.8 0.4 DQGȕG WKHQ
X2 138
5004
0.4
0.4 p q
12 4700930
pq = = = 29795 ;`. #2
1 + a (1 + 0.8) 109
& 2 pq ª 2 29795
= (;r! ))2 = (0.846.4)2
= 10175 ;`
Y# 0.8
= = = 2.21 1
! 4870
1 1
0.75 0.75 10175
M2 min= 4870(15+0.03*500)/1000=146.1 kN.m < M2=158kN.m
Mc= X2 = 2.21 158 = 349.2 ;`. #
Design values:
5002(75)
c= = 0.7
500
33
! 4870 1000
; = = = 1.0
" - 0.65 30 5002
X! 349.2 1000000
® = = = 0.14
" -2 0.65 30 5003
For c = 0.7 = 0.042
As = 0.042* 500*500= 10500 mm2
As provided 12 ѫ 36 As = 12215 mm2 more than required.
Ties -12mm spacing
? 16*36= 576mm
? 48*12= 576mm
? 500mm then adequate. Use ѫ 12mm @500mm c/c
34
Moment magnification for un-brasecd frames
For compression members (columns) not braced against sidesway effect of slenderness may be
neglected when:
kLu
? 22
r
The moments M1 and M2 at the ends of an individual compression member shall be taken as:
X1 = X1 + X1
X2 = X2 + X2
Where:
X1 = factored end moments on a compression members at end at which X1 acts, due to loads
that cause no appreciable side sway.
X2 = factored end moments on a compression members at end at which X2 acts, due to loads
that cause no appreciable side sway.
X1 = factored end moments on a compression members at end at which X1 acts, due to loads
that cause appreciable side sway.
X2 = factored end moments on a compression members at end at which X1 acts, due to loads
that cause appreciable side sway.
= moment magnification factor for frames not braced against sidesway to reflect drift
results from lateral (wind , earth pressure and gravity loads… etc.).
(Note if ? 2.5 the frame must be stiffened to reduce and not exceed 2.5 )
! = sum of axil vertical factored loads for all columns in the floor under consideration.
= sum of all buckling loads for all columns in the floor under consideration.
35
& 2 pq
= (;r! ))2 *-
1 ? ; <
0.4 p q
Find EI for columns in Pc equation pq = or more exact and if steel is known and
1+a
o.2Ec Ig +Es .Ise
exist EI =
1+§d
Es = 200000MPa for steel and Ise moment of interia of reinforcement about centroidal axis of
cross section.
§d = ratio of maximum factored sustained lateral dead load to maximum total factored latera
load ( effect of creep)
for wind load and earthquake loads ±² = D because are generally at short duration but
for other cases like earth pressure ±² ³ D £´² ¡µ¶¥·¸¥² ¹´ ¹´¥ ¡º²¥.
X1 = X1 + X1
X2 = X2 + X2
Thus the moments will be magnify two times first as non sway and second sway case with
moments equal that gained from the first magnify as:
Mc = ¼ns M2 = ¼ns ( M2ns + ¼s M2s )
Where; D= dead loads , L = live loads, W = wind loads, H = lateral soil pressure.
36
Ex. 4: The figure below indicates the side veiw of reinforced concrete building not braced
against sidesway dimension of beams are (1200x300mm), interior columns (450x450mm),
exterior columns 400x400mm clear height Lu= 3.9m, f’c= 30MPa , fy=400MPa, and horizontal
displacement due to total shear wind loads (250 kN) at third floor = 20mm. Design the column
C, the service loads and moments from linear analysis for third floor are :
37
Vu= 1.6*250 =400kN
¨o= 1.6* 20 = 32mm
\ ! ¾ 9800 32
= = = 0.19 > 0.05 !
#
¿! r 400 4200
0.7 4504
q 12
= = 570 103 ##4
r 4200
0.35 1200 3003
q 12
= = 263 103 ##4
r 7200
EI
Lc columns 2 570
= = = 2.17 = #
EI 2 263
Lc beams
kLu 1.643900 X1
k = 1.64 and : = = 47.4 > 34 12 X2 = 34 12(1) = 22
r 0.3450
38
39
40
Ex.5: Design a typical exterior column (col.D4) of the third multi-stroy building . The stability
index for this story Q= 0.36 f’c=27.5MPa and fy=400MPa. All columns are 500x500mm and
height center to center of floor 5.8m, all the beams are 300*600mm.
41
Loading Exterior columns Interior columns Notes
Factored axial load 2600 3500 for a assume factored
(kN) dead load is 50% of total
factored loads
Factored non-sway M top= 100 M top= 60
moment Mns Mbottom= 170 Mbottom= 100
(kN.m)
Factored sway M top= 70 M top= 100 Assume all lateral loads
moment Ms (kN.m) Mbottom= 80 Mbottom= 100 are live loads a=0
0.7(900 + 900)
Àext. col. = Àtop = Àbottom = =3
0.35(1200)
since Q = 0.36 the story is not braced against sidesway k(ext.) unbraced=1.82
0.7(900 + 900)
Àint. col. = Àtop = Àbottom = = 1.5
0.35(1200 + 1200)
then k(int.) unbraced = 1.45
t 2 51348
for int. columns Pcunbraced = = 8914 kN
(1.455.2)2
1 1
= = = 1.563 > 1.5
$. @. . ;.
1 10.36
42
1
= ! 1.0 > 2.5 -
# or increase number
1
0.75
35 35 r!
= = 56.91 > = 34.67 -
X = X2
! 2600 103
A A
27.5 500 500
r! 35
If >
!
A
then take M2 new and magnified by as braced col. and use a for axial load.
3511000
Design Pu =2600 kN M2 = 351kN.m = = 135##
2600
5002(40+10+11)
assume using bars with 22mm and ties 10mm; c = = 0.756
500
43
Spacing ? 16 22 = 352##
? 10 48 = 480##
? 500## then use 10mm @350mm c/c
500(240+522+210)
Clear spacing in side the stirrups= = 72.5## < 150##
4
44
45