Nothing Special   »   [go: up one dir, main page]

Installation of Electrical Lighting System On Auxiliary Outlet & Lighting Fixtures

Download as pdf or txt
Download as pdf or txt
You are on page 1of 81

DLM 03 Developing print-based Learner’s Guide including all related documents

Notes Format of Learner’s Guide

VIRGILIO I. LABICANE
Course: ELECTRICAL INSTALLATION & MAINTENANCE NC II
Unit of competency: INSTALL ELECTRICAL LIGHTING SYSTEM ON AUXILLIARY OUTLET &
LIGHTING FIXTURES
Module: INSTALLATION OF ELECTRICAL LIGHTING SYSTEM ON AUXILLIARY
OUTLET & LIGHTING FIXTURES
Learning outcomes: At the end of the session, learners should be able to:

1. Layout and install electrical wiring using knob and tube method.
2. Layout and install PVC raceway/molding.
3. Layout and install rigid non-metallic conduit.
4. Layout and install flexible non-metallic conduit.
5. Assemble fluorescent lighting fixtures.
6. Layout and install fluorescent lighting fixtures.
7. Layout and install incandescent lamps.
Duration: 60 hours
Situating Learning:
You are a electrician in a Mc Builders Construction company. The construction
company has assigned you to perform installation in electrical lighting fixtures.
To ensure that electrical work will be done successfully before the date, your
engineer instructed you to perform the work as per job requirements and follow
safety procedures in line standard operating procedures. He left you with the
following instructions.
Refer all Learning Outcomes…

Assessment Criteria:  Matrials,tools and equipment are prepared in line with the job requirements.
 Electrical wiring is installed in line with PEC and job requirements.
 Safety procedures in installing electrical wiring are strictly followed in line
with the Occupational Safety and Health Standards.
 Schematic diagram of electical lighting fixtures are interpreted.
 Uses and application of flexible non-metallic conduit are discussed according
to job requirements.
 Workplace is cleaned and made safe upon completion of work.
 Final reportis prepared upon completion of work.

Learning chunk Learning Activities Learning documents


(Brief description of (Documents referenced
strategies, sequence by each learning
of lesson, evaluation) activity)

1. Layout and install  Principles of knob 1. Identify the  Information sheet.1.1.1


electrical wiring tube are identified principles of knob
tube.
using knob and  Types of knob and Refer to:
tube method tube must be  Perform the  Operation sheet.1.1.1
identified performance test on
 Test installed one installing one bulb  Operation sheet.1.1.2
bulb controlled by controlled by one
one single pole single pole single
single throw switch

Pedagogical Training in Instructional Design & Delivery for TVET


© 2010, Institute of Technical Education, Singapore Page 1
DLM 03 Developing print-based Learner’s Guide including all related documents
Notes Format of Learner’s Guide

Learning chunk Learning Activities Learning documents


(Brief description of (Documents referenced
strategies, sequence by each learning
of lesson, evaluation) activity)
in one location throw switch in one
 Test installed two location.
bulbs controlled
individually by single  Perform the  Operation sheet.1.1.3
pole single throw performance test on
switch in two installing two bulbs
locations. controlled individually
 Test installed one by single pole single
bulb controlled by throw switch in two
two three way switch locations.
in two locations.
 Perform the
performance test on
installing one bulb
controlled by two
three way switch in
two locations.

2. Lay out and install  Rigid non-metallic  Identify Rigid Non-  Information sheet.2.1.1
PVC raceway/ conduits are Metallic Conduit  Job Sheet.2.1.1
molding identified.  Perform bending  Job sheet.2.2.2
 Know how to bend 90’PVC elbow
90’PVC elbow.  Perform offset
 Offset bend must be bending
performed.

 Knows how to install  Perform how to install  Job Sheet.3.1.1


3. Layout and install two bulbs by two to bulbs controlled by
rigid non-metallic three way switch two three way switch
conduit and one SPST and one SPST switch
switch with two with two convenience
convenience outlet outlet.

4. Layout and install  Flexible non-metallic  Identify the flexible  Information sheet
flexible non-metallic conduits are non-metallic conduit about.4.1.1
conduit identified.  Work sheet.4.1.1
 Knows how to install  Perform how to install  Answer work sheet 1
conduit and conduit and electrical
electrical wiring from wiring from indoor
indoor using flexible unit to outdoor using
non-metallic tubing. flexible non-metallic
tubing

5. Assemble  Types of electric  Identify types of  Read Information


fluorescent lighting discharge lamps are electric discharge sheet.5.1.1
fixtures identified. lamps  Work Sheet.5.1.1
 Do assemble open  Perform assembling  Work Sheet.5.1.2

Pedagogical Training in Instructional Design & Delivery for TVET


© 2010, Institute of Technical Education, Singapore Page 2
DLM 03 Developing print-based Learner’s Guide including all related documents
Notes Format of Learner’s Guide

Learning chunk Learning Activities Learning documents


(Brief description of (Documents referenced
strategies, sequence by each learning
of lesson, evaluation) activity)
type 20 watts open type 20 watts
fluorescent lamp. fluorescent lamp
 Assembled 40 watts  Perform assembling  Work Sheet.5.1.3
fluorescent fixtures 40 watts fluorescent
using 2x40 watts fixtures using 2x40
high power factor watts high power
ballast. factor (H.P.F) ballast
 Assembled two unit  Perform assembling  Job Sheet.5.1.1
40 watts fluorescent two unit 40 watts
fixtures rapid start fluorescent fixtures
ballast. rapid start ballast
 Assemble fluorescent
lighting fixtures

6. Layout and install  Fluorescent lamp  Install fluorescent  Job Sheet.6.1.1


fluorescent lighting controlled by 3 lamp controlled by 3
fixtures. SPST switch using SPST switch using
flexible non-metallic flexible non-metallic
conduit are installed conduit
 Fluorescent lamp
controlled by two  Install two fluorescent  Job Sheet.6.1.2
three way switch lamp controlled by
and one SPST using two three-way switch
flexible non-metallic and one SPST using
conduit are installed. flexible non-metallic
conduit

7. Layout and install  History and  Identify the history  Information Sheet.7.1.1
incandescent lamp development of and development of  Job Sheet.7.1.1
incandescent lamp incandescent lamp  Answer work sheet 1-3.
are identified.  Install incandescent
 Incandescent lamp lamp using rigid non-
using rigid non- metallic
metallic is installed.

Pedagogical Training in Instructional Design & Delivery for TVET


© 2010, Institute of Technical Education, Singapore Page 3
Information Sheet 1.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures
Learning outcome:
1.1 Layout and install electrical wiring using knob and tube method

Learning activities:
1.1.1 Principles of knob and tube

PRINCIPLES OF KNOB AND TUBE

The open or exposed wiring method is sometimes referred to as the Open


Wiring on Insulators. (PEC section 212) It uses cleats, knobs (split or solid),
porcelain tubes and mica tubing for the support and protection of insulated
conductors run in or on buildings. It may be used for exposed work, either outside
or inside building in dry or wet locations. It shall not be used however, in the
following:

1. Commercial Garages
2. Theaters
3. Motion Picture Studious
4. Hoist ways
5. Hazardous Location

In the open or exposed wiring method, the wires are visible and are
supported by the knobs. These knobs may be the split or solid type. This is shown
in figure 1.

Figure 1. The Split and Solid knobs

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 1
Information Sheet 1.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

Split knobs are used to support wires smaller than No. 8. Solid knobs are used
to support or anchor wires as big as No. 8 or bigger. Screws or nails may be used
to fasten the knobs. When a nail is used a leather washer should be placed
between the nail head and the insulator to form cushion and protect the insulator
from breaking. See figure 2.

Height of Knob

Figure 2. The Solid Knob with Leather washer for Protection

Figure 3. Shows the correct and wrong way of tying wires to the groove of a solid
knob with the wires.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 2
Information Sheet 1.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

In installing an electrical wiring system with the exposed knob and tube wiring
method, the distance between conductors should be maintained at a minimum
distance of 6 cm. (2 ½ inches) apart. The knobs should also spaced 30 cm (1 feet)
apart. Figure 4 illustrates this provision of PEC.

30 cm. 1
Ft.

Figure 4. Spacing of Split Knobs and Conductors

Whenever wires pass through studs, rafters, floor joists or any wooden part
of a building, the wires are inserted in porcelain tubes or flexible mica tubing.
Porcelain tubes and mica tubing are also provided whenever wires cross each
other. It gives the wire extra protection from injury.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 3
Information Sheet 1.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

Figure 5. Application of Porcelain Tubes and Mica Tubing

Some advantages of the Knob and Tube wiring:

1. It is used in temporary installation, such as construction jobs.

2. It has economical when properly installed.

3. It has a lower operating temperature because of ventilating hence, the


higher current carrying capacity of the wire.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 4
Information Sheet 1.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

Safety reminders when installing knob and tube wiring

1. Apply enough pressure on the gimlet when driving it to the word board.
Never hammer it.

2. Have the auger brace oiled regularly especially the ratchet type.

3. Have your electrician’s knife sharpened enough in order not to nick the wire.

4. Use the right-sized screw driver for the right size of screw.

5. Be sure that the conductors in contact with the wiring surface are enclosed
in mica tubing.

6. Be sure your teacher has checked your work before testing.

7. Be sure the safety switch is off before making any connection. Apply tape on
all joints/splices.

8. Do not drive the split-knobs completely before the conductors or wires are
run/inserted along the grooves of the knobs.

9. Be sure to test the insulation for short and ground circuit before putting on
the power.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 5
Information Sheet 1.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 6
Job Sheet 2.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Learning outcome:
2.1 Layout and Install PVC raceway/molding

Learning activities:
2.1.1 Bending 90o PVC Elbow

Tools, Materials and Equipment Needed

Equipment:
 Heat gun - 1 unit
Materials:
 Pencil or Chalk - 1 pc
 PVC pipe - 1m
Tools:
 Steel meter stick/Straight edge - 1 pc
 Try square - 1 pc
 Pull and push rule - 1 pc
 Wet rug - 1 pc
Personal Protective Equipment:
 Gloves - 1 pair
 Respirator - 1 pc

Procedures:

Instruction: When you are ready to perform this task, ask your teacher to observe
the procedure and rate your performance using the assessment
criteria.

1. Prepare the necessary tools, materials and equipments.

2. Wear appropriate PPE.

Note: The greatest danger comes from vinyl chloride, a primary component
of polyvinylchloride (PVC) and an odorless gas which could be released
using this process. Vinyl Chloride is a toxic carcinogen which has
been proven to cause angiosarcoma, a deadly primary liver cancer.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxiliary Outlet and Sept.28,2010 1
Electrical Lighting System Lighting Fixtures
on Auxiliary Outlet and
Lighting Fixtures
Job Sheet 2.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures
Use a good respirator and adequate ventilation to protect yourself
from this toxin.

Respirator Gloves

3. Draw a right angle on the floor using your try square and chalk. This will
serve as your guide when forming your conduit into 90o angle. (A tile on the
floor can serve as a guide.)

4. If you are in a room with a tiled floor, you can use it as your guide for 90o
angle.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxiliary Outlet and Sept.28,2010 2
Electrical Lighting System Lighting Fixtures
on Auxiliary Outlet and
Lighting Fixtures
Job Sheet 2.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

5. Draw an arc near the corner with a radius of 100 mm; this will aid you in
forming your elbow correctly.

Note: 20 mm diameter of PVC should have a radius of 100 mm as mentioned in


the previous information sheet.

100 mm

6. Mark off 200 mm from the end of PVC pipe. This will be the center of your
elbow bend.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxiliary Outlet and Sept.28,2010 3
Electrical Lighting System Lighting Fixtures
on Auxiliary Outlet and
Lighting Fixtures
Job Sheet 2.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

7. Plug-in the heat gun and apply heat to the conduit. Apply heat 100mm on
both sides of your marking. Apply heat evenly by turning over the conduit
while swaying your heat gun back and forth to avoid kinks during bending.

8. Notice that when the conduit is softening, it will sag as shown.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxiliary Outlet and Sept.28,2010 4
Electrical Lighting System Lighting Fixtures
on Auxiliary Outlet and
Lighting Fixtures
Job Sheet 2.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

If the conduit is soften, turn off the heat gun and bend the PVC to the desired
shape using your arc and 90o angle guide drawn on the floor.

9. If the desired shape is formed, damp the conduit with wet rug to harden it
immediately. (You can use your foot to hold one end of the conduit while
wiping.)

10. Perform housekeeping.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxiliary Outlet and Sept.28,2010 5
Electrical Lighting System Lighting Fixtures
on Auxiliary Outlet and
Lighting Fixtures
Job Sheet 2.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Assessment Criteria
VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Bending 90°,

2. Accuracy: Dimension, Accurate bending

3. Method: Safety, Observance of safety measures.


4. Speed: Submission on time +1, before the expected
time +2, after the expected time – 2.

Rating Scale:

VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxiliary Outlet and Sept.28,2010 6
Electrical Lighting System Lighting Fixtures
on Auxiliary Outlet and
Lighting Fixtures
Operation Sheet 1.1.2 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Learning outcome:
1.2 Layout and Install electrical wiring using knob and Tube method

Learning activities:
1.1.2 Install two bulb controlled individually by two single pole single throw (SPST)
switch in two locations

Name: ________________________________________

Date: _________________________________________ Rating:____

I – Materials Required

Qty Unit Description


2 pcs single pole, tumbler switch, surface type
2 pcs porcelain/plastic receptacle, surface type
2 pcs incandescent bulb, 220v, 25w
10 mts solid wire # 14 t.w.
17 pcs porcelain/plastic split knobs with screws
3 ft mica tubing or loom
1 roll electric tape
1 pc safety switch/cut out
2 pcs fuse, 10-a, cartridge type

II – Procedure

Instruction: When you are ready to perform this task, ask your teacher to observe
the procedure and rate your performance using the assessment
criteria. Follow the pictorial diagram

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 1
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Operation Sheet 1.1.2 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Perform this procedure:

1. Install porcelain/plastic receptacle and porcelain cut out/safety switch to


desired location.

2. Fasten split knobs to proper location and distances. Do not tighten


screws. Provide clearance for insertion of wires.

3. Provide mica tubing in every connection of the wires. Follow the


figure/drawing as shown.

4. Connect wires from receptacles to safety switch and switch them from
switch to safety switch. Tighten screw of knobs. Apply tape on the joints.

5. Fasten switches with base under it.

6. Mount the bulbs and fuses on their respective locations.

7. Connect power and test the installation.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 2
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Operation Sheet 1.1.2 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Perform this procedure:

8. Install porcelain/plastic receptacle and porcelain cut out/safety switch to


desired location.

9. Fasten split knobs to proper location and distances. Do not tighten


screws. Provide clearance for insertion of wires.

10. Provide mica tubing in every connection of the wires. Follow the
figure/drawing as shown.

11. Connect wires from receptacles to safety switch and switch them from
switch to safety switch. Tighten screw of knobs. Apply tape on the
joints.

12. Fasten switches with base under it.

13. Mount the bulbs and fuses on their respective locations.

14. Connect power and test the installation.

Assessment Criteria

VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Verticality,
Horizontality

2. Accuracy: Dimension, Accurate function of elements

3. Method: Safety, Observance of safety measures


4. Speed: Submission on time +1, before the expected
time +2, after the expected time – 2

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 3
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Operation Sheet 1.1.2 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below

I do hereby certify that the student has satisfactorily demonstrated ability in


installing two outlets, controlled individually by two single pole single throw switch
in two location by passing this performance test.

Conforme: Attested:

_________________ __________ _______________ _______


Trainee Date Trainer Date

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 4
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Operation Sheet 1.1.3 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Learning outcome:
1.3 Layout and Install electrical wiring using knob and Tube method

Learning activities:
1.1.3 Installing one bulb, controlled from two location by two-3-way switch

Name: ________________________________________

Date: _________________________________________ Rating : ____

I – Materials Required

Qty Unit Description


2 pcs three-way switch, surface type
1 pc porcelain/plastic receptacle, surface type
1 pc incandescent bulb, 220v, 25w
12 mts solid wire # 14 t.w.
20 pcs porcelain/plastic split knobs with screws
3 ft mica tubing or loom
1 roll electric tape
1 pc safety switch/cut out

II – Procedures
Instruction: When you are ready to perform this task, ask your teacher to observe
the procedure and rate your performance using the assessment criteria. Follow the
pictorial diagram.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 1
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Operation Sheet 1.1.3 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 2
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Operation Sheet 1.1.3 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Perform this procedure:

1. Install porcelain/plastic receptacle and porcelain cut out/safety switch to


desired locations.

2. Fasten split knobs to proper location and distances. Do not tighten


screw. Provide clearance for insertion of wires.

3. Provide mica tubing in every connection of the wires. Follow the


figure/drawing as shown.

4. Connect wires from receptacle to safety switch and switch them from
switch to safety switch. Tighten screw of knobs. Apply tape on the joints.

5. Fasten switches with base under it.

6. Mount the bulb and fuses on their respective locations.

7. Connect power and test the installation.

Assessment Criteria

VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Verticality,
Horizontality

2. Accuracy: Dimension, Accurate function of elements

3. Method: Safety, Observance of safety measures


4. Speed: Submission on time +1, before the expected
time +2, after the expected time – 2

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 3
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Operation Sheet 1.1.3 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below

I do hereby certify that the student has satisfactorily demonstrated ability in


installing two outlets, controlled individually by two single pole single throw switch
in two location by passing this performance test.

Conforme: Attested:

_________________ __________ _______________ _______


Trainee Date Trainer Date

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 4
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Information Sheet 2.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures
Learning outcome:
2.1 Layout and Install PVC raceway/molding

Learning activities:
2.1.1 Identify Rigid Non- Metallic Conduit (PVC)

Rigid Non-Metallic Conduit (PVC)

Non-metallic conduits are electrical materials which are manufactured to be


resistant to moisture and chemical atmosphere. They are also manufactured to be
flame retardant or not easily burned. They are resistant to impact and crushing,
they do not easily get out shape because of heat. These conduits are classified
according to the materials they are made of. The most common ones are asbestos
cement conduit, polyvinyl chloride, conduit and high density polyethylene conduit.
The Philippine Electrical Code provides that rigid non-metallic conduit may
be used under the following conditions:
1. Concealed in floors, walls and ceilings
2. Direct earth burial or underground
 300 mm in trench below 50mm thick concrete or equivalent
 600 mm under streets, highways, roads, alleys, driveway and parking
lots
 460 mm under driveways and parking lots of single and two family
dwelling units
 460 mm under airport runways, including adjacent areas where
trespassing is prohibited
3. In locations subject to severe corrosive influences
4. and where subject chemicals for which the materials are specifically
approved
5. Cinder fill
6. In wet locations, provided water is prevented from entering the conduit
7. In dry and damp locations

The Philippine Electrical Code prohibits the use of rigid non-metallic conduit
under the following conditions:
1. Hazardous (Classified) locations
2. Support of fixtures
3. Physical Damage – Where subject to physical damage unless identified for
such use.
4. Ambient Temperature. Where subject to ambient temperatures in excess of
50oC unless listed otherwise
5. Insulation Temperature Limitations. For conductors whose insulation
temperature limitations would exceed those for which the conduit is listed.
6. Theaters and Similar Locations.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 1
Information Sheet 2.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

INSTALLATION OF NON-METALLIC CONDUIT PEC REQUIREMENTS

1. TRIMMING - rough edges or burrs at the cut ends of non-metallic conduit


shall be trimmed at the insides and outside
2. JOINTS - joints between lengths of conduit and between conduit couplings,
fittings and, boxes shall be made with approved coupling and adapter. For
water proofing, PVC cement should be spread around the surfaces to be
.joined together
3. SECURING and SUPPORTS - rigid non-metallic conduit shall be rigidly
supported as indicated below

Table 3.47.1.8 Support of Rigid Nonmetallic Conduit


(Based on Philippine Electrical Code, 2000, Part I)

Conduit Size Maximum Spacing


[mm (mm)]* Between Supports (mm)
15 (20) – 25 (32) 900
32 (40) – 50 (63) 1500
65 (75) – 80 (90) 1800
90 (100) – 125 (135) 2100
150 (160) 2400

4.EXPANSION FITTINGS – Expansion fitting for rigid nonmetallic conduit shall


be provided to compensate for thermal expansion and contraction.
5.MINIMUM SIZE – Rigid nonmetallic conduit smaller than 15 mm (20 mm)
electrical trade size shall not be used.
6.MAXIMUM - Rigid nonmetallic conduit larger than 150 mm (160 mm)
electrical trade size shall not be used.
7.BUSHING – Where conduit enters a box, fitting or other enclosure, a bushing
or adapter shall be provided to protect wires from abrasion unless the box,
fitting or enclosure design provides equivalent protection.
8.BENDS-HOW MADE – Bends of rigid nonmetallic conduit shall be so made
that the conduit will not be damaged and that the internal diameter of the
conduit will not effectively reduced.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 2
Information Sheet 2.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

Table 3.46.2.6 Radius of Conduit Bends


(Based on Philippine Electrical Code, 2000, Part I)

Size of Conduit Conductors Without Lead


(mm) Sheath
15 100
20 125
25 150
32 200
40 250
50 300
65 375
80 450
90 525
100 600
125 750
150 900

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 3
Information Sheet 2.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

TYPES OF PVC CODUIT FITTINGS

PVC Coupling PVC elbow

Adapter PVC Conduit Pipe

PVC 2G box LL Access Fitting

1/2 Inch Type T PVC


1 Inch Type T Condulet
Condulet

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 4
Information Sheet 2.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

3/4" Type LL PVC Access


PVC Conduit Clamps
Fitting

Surface Raceway is a one piece, non-metallic, adhesive backed latching


raceway designed to aesthetically organize and route low voltage communications
cables. It features a low profile design which blends into any environment whether
it is new construction or a renovation. It is easy to cut and trim and is also
printable with a latex based paint. It provides a complete line of fittings to manage
connectivity requirements.

The fittings are available for each size raceway and color option. Single or
Dual gang, junction boxes are versatile enough for any electrical application.
Boxes are equipped with concentric knockouts for all 3 sizes of raceway.
Knockouts are provided on all four sides. Junction boxes come with adhesive
strips and #6 screws to secure the box to the base.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 5
Information Sheet 2.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

Different types of Surface Raceway

Identifying Different Types of Bend

The PVC or polyvinyl chloride rigid conduit is one of the most commonly
used conduits in electrical wiring installation today. Its preparation for installation
is much easier than the metallic rigid conduit. In preparing a non-metallic rigid
conduit for installation, an electrician needs to do cutting, heating and bending.
Like in metallic rigid conduit offset bends, 90o angle bends and other bends are
also made on PVC rigid conduit. In making bends on PVC rigid conduit, the
electrician should see to it that the internal diameter of the conduit is not reduced
and damaged so that the capacity of the conduit to accommodate maximum
number of conductors will not be lessen and to facilitate easy pulling of
conductors.
Since PVC conduits are somewhat easier to bend than a rigid conduit, it
likewise requires patience as in any other type of conduit. It is first pre-heated
over a fire or a heat gun to a desired softness. Little by little, it is bent to its
desired shape. When such is attained, it is then hardened by soaking it to cold or
lukewarm water or dampened with a wet rag.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 6
Information Sheet 2.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

1. Elbow

2. Offset bend is less than 90o


bend, it is used when the
conduit crosses an obstacle
or when the conduit is
entering an electrical box.

3. Round saddle bend is used


when the conduit run across
circular objects like pipes.

4. Square saddle bend is


similar to round saddle, it is
used when the conduit run
across rectangular obstacles.
Square saddle is just a
combination of two offset Obstacl
bends. e

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 7
Information Sheet 2.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

Bend Defects

1. Burned

2. Kinks or groove
Kinks

3.The diameter of the conduit is


greatly reduced due to improper
bending procedure.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 8
Job Sheet 2.2.2 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Learning outcome:
2.2 Layout and Install PVC raceway/molding

Learning activities:
2.2.2 PVC offset bending

Tools, Materials and Equipment Needed

Equipment:
 Heat gun - 1 unit
Materials:
 Pencil or Chalk - 1 pc
 PVC pipe - 1m
Tools:
 Steel meter stick/Straight edge - 1 pc
 Try square - 1 pc
 Pull and push rule - 1 pc
 Wet rug - 1 pc
Personal Protective Equipment:
 Gloves - 1 pair
 Respirator - 1 pc

Procedures:

Instruction: When you are ready to perform this task, ask your teacher to observe
the procedure and rate your performance using the assessment
criteria.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 1
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 2.2.2 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

1.Prepare the necessary tools, materials and equipments.

2. Wear appropriate PPE.

Respirator Gloves

3. Measure the elevation of the obstruction. In this case, let’s use this
wooden box.
Note: Remember, offset bent is used if the conduit crosses an
obstruction. In this case, the elevation is about 70 mm.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 2
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 2.2.2 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

4. Draw the depth of elevation on the floor as shown in the figure using
your try square and chalk. This will guide you how high your offset bend
would be.

4.You should have two lines as shown in the figure.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 3
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 2.2.2 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

5.Mark off 100 mm from the end of PVC pipe. This will be the center of the first
bend of the offset.

5. Put another mark of about 200 mm from your first marker.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 4
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 2.2.2 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

8.Plug-in the heat gun and apply heat to the conduit. Apply heat between your
markers. Apply heat evenly by turning over the conduit while swaying your heat
gun back and forth to avoid kinks during bending.

9.If the conduit is soften, turn off the heat gun and bend the PVC to the desired
shape using your guide drawn on the floor. Pull the left portion of the conduit
while pushing the other end.

10.If the desired shape is formed, damp the conduit with wet rug to harden it
immediately. (You can use your foot to hold one end of the conduit while
wiping.)

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 5
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 2.2.2 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

11.Your bend should look like this.

Assessment Criteria

VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Offset Bending

2. Accuracy: Dimension, Accurate bending

3. Method: Safety, Observance of safety measures.


4. Speed: Submission on time +1, before the expected
time +2, after the expected time – 2.

Rating Scale:

VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 6
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 3.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Learning outcome:
3.1 Install Rigid Non-Metallic Conduit

Learning activities:
3.1.1 Install two bulbs controlled by two (2) three-switch switch and one (1)
SPST switch with two convenience outlet.

Please refer to Learning Outcome No. 2, Layout and Install PVC


raceway/molding the important PEC provisions in installing rigid non-metallic
conduit and personal safety

TOOLS, EQUIPMENT AND MATERIALS

Equipment:
 Heat gun 1 unit
Materials:
 Pencil or Chalk 1 pc
 PVC pipe 3 pcs
 PVC adapter with lock nuts 18 pcs
 Utility box 5 pcs
 Junction box 4 pcs
 Lamp socket 2 pcs
 Safety switch 1 pc
 3 way switch 2 pcs
 SPST switch 1 pc
 1 gang plate cover 3 pcs
 2 gang plate cover 2 pcs
 Conduit clamps/straps 15 pcs
 Wood screws (1/4 x ½) 50 pcs
Tools:
 Steel meter stick/Straight edge 1 pc
 Try square 1 pc
 Pull and push rule 1 pc
 Wet rug 1 pc

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxiliary Outlet and Sept.28,2010 1
Electrical Lighting System Lighting Fixtures
on Auxiliary Outlet and
Lighting Fixtures
Job Sheet 3.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Personal Protective Equipment:


 Gloves 1 pair
 Respirator 1 pc

Procedure:

Instruction: When you are ready to perform this task, ask your teacher to observe
the procedure and rate your performance using the assessment
criteria.

1. Prepare the necessary tools, materials and equipments.

2. Wear appropriate PPE.

3. Mark on the wiring board the location of the safety switch, utility boxes, and
junction boxes.

4. Fasten the safety switch and PVC boxes with wood screws at the desired
locations.

5. Prepare the PVC conduit for installation.

a. Measure and cut each PVC pipe to desired length


b. Make an offset bend at each end of PVC conduit which will be
connected to a box.
c. Bend 90º based on the diagram.

6. Install and connect ends of PVC pipe to the electrical boxes, safety switch.

7. Support the conduit with conduit clamps or straps.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxiliary Outlet and Sept.28,2010 2
Electrical Lighting System Lighting Fixtures
on Auxiliary Outlet and
Lighting Fixtures
Job Sheet 3.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

8. Place the cover of junction box, utility box, and convenience outlet.

9. Perform good housekeeping.

10. Have your teacher check your work.

Note: The teacher will determine the distance of each circuit.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxiliary Outlet and Sept.28,2010 3
Electrical Lighting System Lighting Fixtures
on Auxiliary Outlet and
Lighting Fixtures
Job Sheet 3.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

S3 S3 S
w w

Line diagram of two bulbs controlled by two (2) three-way switches and one
(1) SPST switch with two convenience outlet in different location.

Assessment Criteria

VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Offset Bending,
Bending 90º

2. Accuracy: Dimension, Accurate bending

3. Method: Safety, Observance of safety measures.


4. Speed: Submission on time +1, before the expected
time +2, after the expected time – 2.

Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxiliary Outlet and Sept.28,2010 4
Electrical Lighting System Lighting Fixtures
on Auxiliary Outlet and
Lighting Fixtures
Information Sheet 4.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures
Learning outcome:
4.1 Layout and Install Flexible Non-Metallic Conduit

Learning activities:
4.1.1 Identify Flexible Non-Metallic Conduit

Flexible Nonmetallic Conduit

This portion of information sheet is lifted from Philippine Electrical Code,


2000, Part I.

3.51.2.1 Definition. Liquidtight flexible nonmetallic conduit is a listed raceway of


circular cross section of various types as follows:

1. A smooth seamless inner core and cover bonded together and having one
or more reinforcement layers between the core and cover designated as
Type LFNC-A

2. A smooth inner surface with integral reinforcement within the conduit


wall, designated as Type LFNC-B

3. A corrugated internal and external surface without integral reinforcement


within the conduit wall, designated as Type LFNC-C

This conduit is flame resistant and, with fittings, is approved for the
installation of electrical conductors.

3.51.2.2 Uses.

(a) Permitted. Listed liquidtight flexible nonmetallic conduit shall be


permitted to be used in exposed or concealed locations for the following
purposes. FPN: Extreme cold may cause some types of nonmetallic
conduits to become brittle and therefore more susceptible to damage
from physical contact.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 1
Information Sheet 4.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

(1) Where flexibility is required for installation, operation, or


maintenance.

(2) Where protection of the contained conductors is required from vapors,


liquids, or solids.

(3) For outdoor locations where listed and marked as suitable for the
purpose. FFN: For marking requirements, see Section 110.1.21

(4) For direct burial where listed and marked for the purpose.

(5) Liquid tight flexible nonmetallic conduit as defined in Section


3.51.2.1(2) shall be permitted to be installed in lengths longer than 1
800 mm where secured in accordance with Section 3.51.2.6.
(6) As a listed manufactured prewired assembly, 15, mm (20mm) through
25 mm (32 mm) conduit, as defined in Section 3.51 .2.1(2).

(b) Not Permitted. Liquidtight flexible nonmetallic conduit shall not be used
in the following:

(1) Where subject to physical damage

(2) Where any combination of ambient and conductor temperature is in


excess of that for which the liquidtight flexible nonmetallic conduit is
approved

(3) In lengths longer than 1 800 mm, except as permitted by Section 3.51
.2.2(a)(5) or where a longer length is approved as essential for a
required degree of flexibility.

(4) Where voltage of the contained conductors is in excess of 600 volts,


nominal

Exception. As permitted in Section 6.0.2.3(a) for electric signs over


600 volts.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 2
Information Sheet 4.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

3.51.2.3 Size. The electrical trade sizes of liquidtight flexible nonmetallic conduit
shall be in accordance with (a) or (b):

(a) 15mm (20 mm) to 100mm (110mm) inclusive

(b) 10 mm (15 mm) as permitted below


(1) For enclosing the leads of motors as permitted in Section 4.30.13.5(b)
(2) In lengths not exceeding 1 800 mm as part of a listed assembly for
tap connections to lighting fixtures as required in Section
4.10.13.4(c), or for utilization equipment (3) For electric sign
conductors in accordance with Section 6.0 .2 .3 (a)

3.51.2.4 Number of Conductors. The number of conductors permitted in a


single conduit shall be in accordance with the percentage fill specified in Table
9.1.1.1.

3.51.2.5 Fittings. Liquidtight flexible nomnetallic conduit shall be used only with
listed terminal fittings. Angle connectors shall not be used for concealed
raceway installations.

3.51.2.6 Securing and Supporting. Liquidtight flexible nonmetallic conduit, as


defined in Section 3.51.2.1(2), shall be securely fastened and supported in
accordance with one of the following.
(a) The conduit shall be securely fastened at intervals not exceeding 900 mm
and within 300 mm on each side of every outlet box, junction box,
cabinet, or fitting.

(b) Securing and supporting of the conduit shall not be required where it is
fished, installed in lengths not exceeding 900 mm at terminals where
flexibility is required, or where installed in lengths not exceeding 1 800
mm from a fixture terminal connection for tap conductors to lighting
fixtures as permitted in Section 4.10.13.4(c)

(c) Horizontal runs of liquidtight flexible nonmetallic conduit supported by


openings through framing members at intervals not exceeding 900 mm
and securely fastened within 300 mm of termination points shall be
permitted.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 3
Information Sheet 4.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

3.51.2.7 Equipment Grounding. When an equipment grounding conductor is


required for the circuits installed in liquidtight flexible nonmetallic conduit, it
shall be permitted to be installed on the inside or outside of the conduit.
When installed on the outside, the length of the equipment grounding
conductor shall not exceed 1 800 mm and shall be routed with the raceway or
enclosure. Fittings and boxes shall be bonded or grounded in accordance with
Article 2.50.

3.51.2.8 Splices and Taps. Splices and taps shall be made in accordance with
Section 3.0.1 13. See Article 3.70 for rules on the installation and use of
boxes and conduit bodies.

3.51.2.9 Bends-Number in One Run. There shall not be more than the equivalent
of four quarter bends (360 degrees total) between pull points, e.g., conduit
bodies and boxes.

Flexible Nonmetallic Conduit Fittings

Coupling

Flexible Nonmetallic Conduit

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 4
Information Sheet 4.1.1 Install Electrical Lighting System on
Auxilliary Outlet and Lighting Fixtures

Liquidtight angle connector Adapter

Liquidtight straight connector Adapter

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 5
Information Sheet 5.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures
Learning outcome:
5.1 Assemble Fluorescent Lighting Fixtures

Learning activities:
4.1.1 Identify the parts of a fluorescent lighting fixtures

Fluorescent lighting fixtures

PEC Rules on Wire Dressing and Termination

Article 6.3.1.3 Live Parts. Fixtures, lamp holders, lamps, rosettes, and
receptacles shall have no live parts normally exposed to contact. Exposed
accessible terminals in lamp holders, receptacles, and switches shall not be
installed in metal fixture canopies or in open bases of portable table or floor
lamps.
All joints/splices to be done must be properly insulated with spaghetti
sleeving, wire nut or taped with electrical tape having a thickness like the
conductor used.

Fluorescent Lamp –is a form of electric discharge light source. It consists of a


glass tube containing mercury vapor at a low pressure and inert gas like argon
and krypton. The interior is coated with phosphor, which glows or fluoresces when
exposed to ultraviolet light.

Kinds/types of electric discharge lamps

1. Pre-heat starting, hot-cathode – requires starter (glow switch) and is pre-


heated during starting. It uses a ballast to produce high voltage to start the
lamp into operation and to limit the flow of current.

2. Cold cathode – requires high voltage in its operation. This lamp has
electrodes made of thimble-type iron. It is not pre-heated and does not require
a starter for starting. Special high voltage transformers operate it. Neon and
mercury lamps are classified under cold cathode lamps.

3. Instant-starting, hot-cathode – the lamp cathode in the instant-start is not


pre-heated. Sufficient voltage is applied across the cathodes to create an
instantaneous arc. As in preheat circuit; the cathodes are heated during lamp
operation by the arc. The instant-start lamp require single-pin bases, are
generally called slim line lamps.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 1
Information Sheet 5.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

4. Hot-cathode, rapid-start – these are similar in construction to the preheat


lamps; the basic difference is in the circuitry. This circuit eliminates the delay
inherent in preheat circuits by keeping the lamp cathodes constantly energized
(preheated). When the lamp circuit is energized, the arc is struck immediately.
No external starter is required. Because of this similarity of operation, rapid
start lamps will operate satisfactorily in a preheat circuit. The reverse is not
true, because the preheat requires more current to heat the cathode than the
rapid-start ballast provides.

Operation of pre-heat type fluorescent lamp

The tube filaments, starter (glow switch), and ballast are all connected in series, which
constitute a complete circuit once the switch, is closed. As a current flow through, the gas
(inert) inside the starter glows and the electrodes are heated. Since one of the electrodes is
a bi-metal, it bends and makes contact with the other. At this instant, the circuit is
metallically complete. The filaments of the fluorescent tube are then heated and partial
ionization takes place. The bi-metals in the starter cools and the contacts open. The
magnetic field in the ballast collapses rapidly producing an inductive kick, which
establishes a current between the filaments and fires the tube into operation.
Classifications of Fluorescent Lamp

1. Regular Fluorescent Lamp

Circular type fluorescent lamp

Open type fluorescent

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 2
Information Sheet 5.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Box type fluorescent lamp

Different types of Compact Fluorescent Lamp

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 3
Information Sheet 5.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Parts and functions of fluorescent lamp

1. Fluorescent tube – is a circular bulb containing mercury vapor and inert


gas with phosphor coating inside.

Parts of Fluorescent tube

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 4
Information Sheet 5.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

1. Ballast –is an induction coil, which produces high voltage to start the
lamp into operation. It also limits the flow of current during the
2. operation of the lamp. Ballast consumes power, which is between 10-20%
of power consumed by the lamp itself.

Induction type ballast

Electronic type ballast

Different types of Ballast

3. Starter –is a glow switch that opens and closes the circuit so as to
produce a high voltage or inductive kick across the bulb at the filament
during the starting period.

Different types of starter

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 5
Information Sheet 5.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

4. Lamp holder and starter socket – are the point of connection of the
fluorescent and starter.

5. Frame –is the metal housing of the whole fixture.

Parts of fluorescent lamp starter

Starter housing

Base contact
Connecting
wire

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 6
Information Sheet 5.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Current moves in utilizing the rare gas as conducting means and the rare
gas produces a “GLOW”. The glow generates heat and causes the bimetallic blade
to expand.
When the bimetallic blade is heated, it changes shape and touches the fixed
contact. The close contacts of the two starter contacts produce an easy path for
current flow.

Parts and operation function of ballast

Coil inside

Laminated iron core

Ballast frame
Ballast frame
Terminal block

In common with all gaseous discharge lamps, the fluorescent must be provided
with some device for limiting the current drawn by the discharge. Without a
limiting device, the current would rise to a value that would destroy the lamp. A
device or auxiliary called ballast can best meet this requirement.

The ballast for operating lamps on an alternating current consists of a small


choke coil woven on an iron core.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 7
Information Sheet 5.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

This ballast serves three important functions:

1. It preheats the electrodes to make available a large supply of the electron.


2. It provides a surge of relatively large potential to start the arc between
the electrodes.
3. It prevents the arc current to increase beyond the limit set for each size
and lamp.

THE LIFE SPAN OF FLUORESCENT LAMP

The life of fluorescent lamp is affected not only in the fluctuation of voltage
and current but also by the number of times it is started. Electron emission
material is “sputtered off” from the electrodes continuously during the operation of
the lamp and in larger quantities each time the lamp starts.

Many fluorescent lamps have a rated average life span up to 30,000


continuous burning hours but with an average of 3 hours burning per start, it
could only last for 12,000 hours.
Procedure in installing lighting fixtures

1. Gather all necessary materials for the work then secure tools, equipment
and PPE’s from the tool room.

2. On your work area, layout all the measurement of installation based on the
given work plan, use pencil to mark the location dimensions.

3. All measurement should be taken from center to center of conduits,


raceways and devices.

4. Level the horizontality and verticality position of the layout.

5. Use chalk line to make final mark of the layout of conduits, raceways, boxes
and devices. Make sure that all marks are horizontally and vertically leveled.

6. Install/mount all boxes to be followed by connector and adopter, if


necessary and required by the job then tighten snugly according to
manufacturer’s torque specification.

7. For box type lighting fixture and surface type receptacle, mount them to the
specified measurement and locations, but for lighting materials (such as
incandescent bulb) that uses flush type receptacles, provide junction box for
the mounting of flush type receptacle.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 8
Information Sheet 5.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures
8. Install/mount wire ways such as conduit, raceway, NM cables. Place the
desired kind and size of support according to manufacturer’s specification.

9. Cut, bend wire ways to desired length and bends based on the job
requirements. Avoid installing nicked conduits. All ends must be free of
burrs.

10. Fish-in conductors/wires inside conduits/wire ways based on the required


size of wire as prescribe by the PEC.

11. Cut wire to the desired length. Always provide allowance (6-8” for smaller
size of wire) for future tapping or termination.

12. Strip wires in the boxes then connect them to the terminals of the
switches, breakers, and fuse clip holder.

Note: All loop termination must be turning clockwise and tighten snugly
according to manufacturer’s torque specification. Avoid excess wire
termination.

13. Splice, joint wires in junction boxes based on the circuit design operation.
Joining or splicing of conductors inside conduits, raceways is strictly
prohibited. Make sure the wires joined have 6-8” allowances from the edge
of the box to the outstripped joined end of wires.

14. Connect all lighting materials based on the circuit design operation.

15. Check the continuity of circuit to identify and troubleshoot possible


defects.

16. When installation is completed, ask your teacher to evaluate your


performance based on the rating sheet provided.

Code No. Date: Developed Date: Revised Page #


Module Name
Unit of Competency Doc created date Doc modified date 9
Job Sheet 3.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Learning outcome:
5.1 Assemble Lighting Fixtures
Learning activities:
5.1.1 1. Assembling Open type 20 watts Fluorescent Lamp
2. Assembling two-unit 40 watt fluorescent fixture using rapid start ballast

Instruction: When you are ready to perform this task, ask your teacher to
observe the procedure and rate your performance using the
assessment criteria.
(Refer the procedure to the activity sheet 1 .1 and 1.2)

Assessment Criteria

Needs
Very Good Good Fair
CRITERIA Improvement
(5) (4) (3)
(2)
1. Accuracy Lamp lights Lamp lights Lamp lights Lamp does not
(25%) but flickers light
Wirings are Wirings are Wirings are Wirings are
secured, neat secured, neat not secured; loose; finished
2. Quality and clean and clean finished work work is not
(25%) presentation of presentation of is not presentable.
work. work. presentable

Followed Followed Incorrect Did not follow


procedure procedure usage of the required
correctly, correctly, tools. procedures.
economical economical
3. Method
use of tools is use of tools is
(25%) followed; followed;
observed observed
safety while safety while
working. working.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 1
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 3.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures
Submitted Submitted Submitted Unable to
work two (2) work on a work two (2) finish the
4. Speed minutes ahead given time. or more work.
(25%) of time. minutes after
the given
time.

Rating: 5.0 – 4.6 = Very Good


– 3.9 = Good
– 3.0 = Fair
2.9 and below = Needs Improvement

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 2
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 6.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Learning outcome:
6.1 Layout and Install Lighting Fixtures
Learning activities:
6.1.1 Install three (3) fluorescent lamp controlled by three (3) SPST switch
using Flexible Non-metallic Conduit.

PEC Rules on Wire Dressing and Termination


Article 6.3.1.3 Live Parts. Fixtures, lamp holders, lamps, rosettes, and
receptacles shall have no live parts normally exposed to contact. Exposed
accessible terminals in lamp holders, receptacles, and switches shall not be
installed in metal fixture canopies or in open bases of portable table or floor
lamps.
All joints/splices to be done must be properly insulated with spaghetti
sleeving, wire nut or taped with electrical tape having a thickness like the
conductor used.
Wiring termination

Correct terminal
position loop and
length

Stripped wire is Wrong position of


too long terminal loop

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 1
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 6.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Tools, Materials Needed

Materials:
 Fluorescent Lamp (20 watts) - 3 set
 Lamp socket - 3 pcs
 Utility box - 2 pcs
 Safety switch - 1 set
 SPST switch - 3 pcs
 Junction box - 5 pcs
 Adapter with lock nuts - 15 pcs
 Conduit clamps/straps - 25 pcs
 1 gang plate cover - 1 pc
 2 gang plate cover - 1 pc
 Wood screws (¼ x ½) - 50 pcs
 Electrical tape - 1 roll
Tools:
 Philip Screw driver - 1 pc
 Flat Screw driver - 1 pc
 Side cutting pliers - 1 pc
 Long nose pliers - 1 pc
 Push pull tape rule - 1 pc
Personal Protective Equipment:
 Gloves - 1 pair
 Goggles - 1 pc

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 2
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 6.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Instruction: When you are ready to perform this task, ask your teacher to observe
the procedure and rate your performance using the assessment
criteria. Strictly follow the line diagram and the teacher will
determine the distance of each circuit.

S S2

Line diagram of three (3) fluorescent lamp controlled by three (3) SPST
switch using Flexible Non-metallic Conduit.
Procedure:

1. Prepare the necessary tools, materials.

2. Wear appropriate PPE.

3. On your work area, layout all the measurement of installation based on the
given work plan, used pencil to mark the location dimensions.

4. All measurement should be taken from center to center of conduits, junction


box, utility box, and other devices.

5. Use chalk line to make final mark of the layout of conduits, boxes, and
devices. Make sure that all marks are horizontally and vertically levelled.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 3
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 6.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

6. Install/mount all boxes to be followed by connector and adopter, if


necessary and required by the job then tighten snugly according
manufacturer’s torque specification.

7. Install/mount the conduit. Place the desired kind and size of support
according manufacturer’s specification.

8. Cut, bend wire ways to desired length and bends based on the job
requirements. Avoid installing nicked conduits.

9. Fish-in conductors/wires inside conduits/wire ways based on the required


size of wire as prescribe by the PEC.

10. Cut wire to the desired length. Always provide allowance (6-8” for smaller
size of wire) for future tapping or termination.

11. Strip wires in the boxes then connect them to the terminals of the switches
and fuse clip holder. Note: All loop termination must be turning clockwise
and tighten snugly according to manufacturer’s torque specification. Avoid
excess wire termination.

12. Splice, joint wires in junction boxes based on the circuit design operation.
Joining or splicing of conductors inside conduits, raceways is strictly
prohibited. Make sure the wires joined have 6-8” allowances from the edge
of the box to the outstripped joined end of wires.

13. Mount/Connect fluorescent lamp based on the circuit design operation.


(Line diagram)

14. Check the continuity of circuit to identify and troubleshoot possible


defects.

15. When installation is completed, ask your teacher to evaluate your


performance based on the assessment criteria.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 4
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 6.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Assessment Criteria

The students will be evaluated based on the following:

MEASUREMENT
All dimensions will be in mm center to center with a tolerance
20 pts.
of + - 3mm.

WORKMANSHIP 10 pts.
Includes bending, cutting, supporting and installing flexible
non-metallic conduit.
 Bending 10 pts
 Cutting 10 pts.
 Supporting 10 pts.
 Horizontality and verticality 10 pts.
SPEED 10 pts.
SAFETY 10 pts.
USE OF TOOLS 10 pts.
TOTAL 100%

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 5
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 6.2.2 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Learning outcome:
6.2 Layout and Install Lighting Fixtures
Learning activities:
6.2.2 Install two (2) fluorescent lamp controlled by two (2) three –way-switch
and One (1) SPST switch using Flexible Non-metallic Conduit.

PEC Rules on Wire Dressing and Termination (Refer to Job sheet 6.1)

Tools, Materials Needed

Materials:
 Fluorescent Lamp (20 watts) - 2 set
 Lamp socket - 2 pcs
 Utility box - 3 pcs
 Safety switch - 1 set
 SPST switch - 1 pcs
 Junction box - 4 pcs
 Adapter with lock nuts - 15 pcs
 Conduit clamps/straps - 25 pcs
 1 gang plate cover - 3 pcs
 Wood screws (¼ x ½) - 50 pcs
 Electrical tape - 1 roll

Tools:
 Philip Screw driver - 1 pc
 Flat Screw driver - 1 pc
 Side cutting pliers - 1 pc
 Long nose pliers - 1 pc
 Push pull tape rule - 1 pc
Personal Protective Equipment:
 Gloves - 1 pair
 Goggles - 1 pc

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 1
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 6.2.2 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Instruction: When you are ready to perform this task, ask your teacher to observe
the procedure and rate your performance using the assessment
criteria. Strictly follow the line diagram and the teacher will
determine the distance of each circuit.

S S3w S3w

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 2
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 6.2.2 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Line diagram of two (2) fluorescent lamp controlled by two (2) three –way-switch
and One (1) SPST switch using Flexible Non-metallic Conduit.

Procedure:
Refer to Job Sheet 3.1
Note: Job sheet 6.2 is no convenience outlet

Assessment Criteria
Needs
Very Good Good Fair
CRITERIA Improvement
(5) (4) (3)
(2)
1. Accuracy Lamp lights Lamp lights Lamp lights Lamp does not
(25%) but flickers light
Wirings are Wirings are Wirings are Wirings are
completely neat and not secured; loose; finished
2. Quality installed and clean; the finished work is not
(25%) energized work is work is not presentable.
presentable presentable

Followed Followed Incorrect Did not follow


procedure procedure usage of the required
correctly, correctly, tools. procedures.
observed economical
3. Method
safety while use of tools
(25%) working, and followed;
perform good observed
housekeeping safety while
working.
Submitted Submitted Submitted Unable to
work two (2) work on a work two (2) finish the
4. Speed minutes given time. or more work.
(25%) ahead of minutes
time. after the
given time.

Rating: 5.0 – 4.6 = Very Good


– 3.9 = Good
– 3.0 = Fair
2.9 and below = Needs Improvement

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 3
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Information Sheet 7.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures
Learning outcome:
7.1 Layout and Install Incandescent Lamp

Learning activities:
7.1.1 Identify the history and development of an Incandescent Lamp

History and development of incandescent lamp

THE INCANDESCENT LIGHT BULB

The first incandescent electric light was made in 1800 by Humphry Davy,
an English scientist. He experimented with electricity and invented an electric
battery. When he connected wires to his battery and a piece of carbon, the carbon
glowed, producing light. This is called an electric arc.

Much later, in 1860, the English physicist Sir Joseph Wilson Swan (1828-
1914) was determined to devise a practical, long-lasting electric light. He found
that a carbon paper filament worked well, but burned up quickly. In 1878, he
demonstrated his new electric lamps in Newcastle, England.

The inventor Thomas Alba Edison (in the USA) experimented with
thousands of different filaments to find just the right materials to glow well and be
long-lasting. In 1879, Edison discovered that a carbon filament in an oxygen-free
bulb glowed but did not burn up for 40 hours. Edison eventually produced a bulb
that could glow for over 1500 hours.

Lewis Howard Latimer (1848-1928) improved the light bulb by inventing a


carbon filament (patented in 1881); Latimer was a member of Edison's research
team, which was called "Edison's Pioneers." In 1882, Latimer developed and
patented a method of manufacturing his carbon filaments.

In 1903, Willis R. Whitney invented a treatment for the filament so that it


would not darken the inside of the bulb as it glowed. In 1910, William David
Coolidge (1873-1975) invented a tungsten filament, which lasted even longer than
the older filaments. The incandescent bulb revolutionized the world.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of Electrical System on Auxiliary Outlet and Sept.28,2010 1
Lighting System on Auxiliary Lighting Fixtures
Outlet and Lighting Fixtures
Information Sheet 7.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

PARTS OF AN INCANDESCENT BULB

Coiled tungsten filament - the metal wires that glow brightly when electricity
flows through them.

Connecting wires - The wires that carry electricity from the bulb's electrical
contact to the filament.

Electrical contacts - the metallic base of the bulb, which connects to the
electrical contacts of the lamp when the bulb is in the lamp.

Glass envelope - the thin layer of glass that surrounds the light bulb mechanism
and the inert gases.

Glass fuse enclosure - glass that insulates the bulb's fuses - located in the stem
of the bulb.

Mixture of inert gases at low pressures - the bulb is filled with inert (non-
reactive) gases.

Screw cap - the threaded base of the bulb that secures it to a lamp.

Support wires - wires that physically hold up the filament.

Parts of an incandescent bulb

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of Electrical System on Auxiliary Outlet and Sept.28,2010 2
Lighting System on Auxiliary Lighting Fixtures
Outlet and Lighting Fixtures
Information Sheet 7.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Edison’s first successful lamp

It is certainly true that Edison did invent the light


bulb (or at least "a" light bulb), but he was not the first. In
1860, an English physicist and electrician, Sir Joseph
Wilson Swan, produced his first experimental light bulb
using carbonized paper as a filament. Unfortunately, Swan
did not have a strong enough vacuum or sufficiently
powerful batteries and his prototype did not achieve
complete incandescence, so he turned his attentions to
other pursuits.

So it is reasonable to wonder why Edison received all of the credit, while


Swan was condemned to obscurity. The more cynical among us may suggest that
Edison was thrust into the limelight (see note below) because many among us
learn their history through films, and the vast majority of early films were made in
America by patriotic Americans.

However, none of this should detract from Edison who, working


independently, experimented with thousands of filament materials and expended
tremendous amounts of effort before discovering carbonized thread. It is also
probably fair to say that Edison did produce the first commercially viable light
bulb.

The reason why this is of interest to us here is that Edison's experiments


with light bulbs led him to discover the Edison Effect, which ultimately led to the
invention of the vacuum tube

As one final nugget of trivia, the term "limelight" comes from the
incandescent light produced by a rod of lime bathed in a flame of oxygen and
hydrogen. At the time it was invented, limelight was the brightest source of
artificial light known. One of its first uses was for lighting theater stages, and
actors and actresses were keen to position themselves "in the limelight" so as to be
seen to their best effect.

Furthermore, in 1880, Swan gave the world's first large-scale public


exhibition of electric lamps at Newcastle, England.

Edison's light bulbs employed a conducting filament mounted in a glass


bulb from which the air was evacuated leaving a vacuum. Passing electricity
through the filament caused it to heat up enough to become incandescent and
radiate light, while the vacuum prevented the filament from oxidizing and burning
up.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of Electrical System on Auxiliary Outlet and Sept.28,2010 3
Lighting System on Auxiliary Lighting Fixtures
Outlet and Lighting Fixtures
Information Sheet 7.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Operation of incandescent lamp

What makes a light bulb glow?

The thin wire, or filament, inside a light bulb resists the flow of current through it.
When electricity is passed through the bulb, the filament becomes hot and glows brightly.
To prevent the filament burning away completely, the glass bulb filled with a mixture of
inert gas (usually argon and nitrogen). The filament in most light bulbs is made of
tungsten.

Elements used in manufacturing incandescent lamp

1. Lead-in wire
2. Glass
3. Argon gas
4. Inert gas
5. Coiled tungsten
6. Brass
7. Mica
8. Copper
9. Nitrogen

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of Electrical System on Auxiliary Outlet and Sept.28,2010 4
Lighting System on Auxiliary Lighting Fixtures
Outlet and Lighting Fixtures
Information Sheet 7.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Classification of Incandescent Lamp

1. Large lamps –are those normally used for interior and exterior general and
task lighting. (See figure next page)

1. Miniature lamps –are generally used in automotive, aircraft, and appliance


applications.

3. Photographic lamps –as the name implies, are used in photography and
projection service.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of Electrical System on Auxiliary Outlet and Sept.28,2010 5
Lighting System on Auxiliary Lighting Fixtures
Outlet and Lighting Fixtures
Information Sheet 7.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Kinds of High Intensity discharge lamp

1. Mercury lamp –is an electric discharge lamp in which the major portion of
the radiation is produced by the excitation of mercury atoms.

2. Metal halide lamp –is an electric discharge lamp in which the light is
produced by the radiation from an excited mixture of a metallic vapor
(mercury) and the products of the dissociation of halides (for example,
halides of thallium, indium, sodium).

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of Electrical System on Auxiliary Outlet and Sept.28,2010 6
Lighting System on Auxiliary Lighting Fixtures
Outlet and Lighting Fixtures
Information Sheet 7.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

2. High-pressure sodium lamp –is an electric discharge lamp in which the


radiation is produced by an excitation of sodium vapor in which the partial
pressure of the vapor during operation is of the order of 104 N/m2.

The Incandescent Filament Lamp

Construction

This lamp consist simply of a tungsten filament inside a gas-filled, sealed


glass envelop. Current passing through the high-resistance filament heats it to
incandescence, producing light. Gradual evaporation of the filament causes the
familiar blackening of the bulbs and eventual filament rupture and lamp failure.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of Electrical System on Auxiliary Outlet and Sept.28,2010 7
Lighting System on Auxiliary Lighting Fixtures
Outlet and Lighting Fixtures
Information Sheet 7.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures

Procedures in installing Incandescent Lamp

1. Gather all necessary materials for the work then secure tools, equipment
and PPE’s from the tool room.

2. On your work area, layout all the measurement of installation based on the
given work plan, use pencil to mark the location dimensions.

3. All measurement should be taken from center to center of conduits,


raceways and devices.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of Electrical System on Auxiliary Outlet and Sept.28,2010 8
Lighting System on Auxiliary Lighting Fixtures
Outlet and Lighting Fixtures
Information Sheet 7.1.1 Install Electrical Lighting System on
Auxiliary Outlet and Lighting Fixtures
4. Level the horizontality and verticality position of the layout.

5. Used chalk line to make final mark of the layout of conduits, raceways,
boxes and devices. Make sure that all marks are horizontally and vertically
leveled.

6. Install/mount all boxes to be followed by connector and adopter, if


necessary and required by the job then tighten snugly according
manufacturer’s torque specification.

7. For box type lighting fixture and surface type receptacle, mount them to the
specified measurement and locations, but for lighting materials (such as
incandescent bulb) that uses flush type receptacles, provide junction box for
the mounting of flush type receptacle.

8. Install/mount wire ways such as conduit, raceway, NM cables. Place the


desired kind and size of support according manufacturer’s specification.

9. Cut, bend wire ways to desired length and bends based on the job
requirements. Avoid installing nicked conduits. All ends must be free of
burrs.

10. Fish-in conductors/wires inside conduits/wire ways based on the required


size of wire as prescribe by the PEC.

11. Cut wire to the desired length. Always provide allowance (6-8” for smaller
size of wire) for future tapping or termination.

12. Strip wires in the boxes then connect them to the terminals of the
switches, breakers, and fuse clip holder. Note: All loop termination must
be turning clockwise and tighten snugly according to manufacturer’s
torque specification. Avoid excess wire termination.

Splice, joint wires in junction boxes based on the circuit design operation. Joining
or splicing of conductors inside conduits, raceways is strictly prohibited. Make
sure the wires joined have 6-8”
1. Allowances from the edge of the box to the outstripped joined end of wires.

2. Connect all lighting materials based on the circuit design operation.

3. Check the continuity of circuit to identify and troubleshoot possible defects.

4. When installation is completed, ask your teacher to evaluate your


performance based on the rating sheet provided.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of Electrical System on Auxiliary Outlet and Sept.28,2010 9
Lighting System on Auxiliary Lighting Fixtures
Outlet and Lighting Fixtures
Job Sheet 7.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Learning outcome:
7.1 Layout and Install Incandescent Lamp
Learning activities:
7.1.1 Installation of incandescent lamp using Rigid Non-metallic Conduit

PEC Rules on Wire Dressing and Termination (Refer to Job sheet 6.1)

Materials:
 Incandescent Lamp (25 watts) - 2 set
 Lamp socket - 2 pcs
 Utility box - 3 pcs
 Safety switch - 1 set
 SPST switch - 1 pcs
 Junction box - 4 pcs
 Adapter with lock nuts - 15 pcs
 Conduit clamps/straps - 25 pcs
 1 gang plate cover - 3 pcs
 Wood screws (¼ x ½) - 50 pcs
 Electrical tape - 1 roll

Tools:
 Philip Screw driver - 1 pc
 Flat Screw driver - 1 pc
 Side cutting pliers - 1 pc
 Long nose pliers - 1 pc
 Push pull tape rule - 1 pc
Personal Protective Equipment:
 Gloves - 1 pair
 Goggles - 1 pc

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 1
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 7.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Instruction: When you are ready to perform this task, ask your teacher to observe
the procedure and rate your performance using the assessment
criteria. Strictly follow the line diagram and the teacher will
determine the distance of each circuit.

S S3w S3w

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 2
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Job Sheet 7.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

Line diagram of two (2) incandescent lamp controlled by two (2) three –way-
switch and One (1) SPST switch using Flexible Non-metallic Conduit.
Procedure:
Refer to Job Sheet 3.1
Note: Job sheet 7.1 is no convenience outlet

Assessment Criteria

Needs
Very Good Good Fair
CRITERIA Improvement
(5) (4) (3)
(2)
1. Accuracy Lamp lights Lamp lights Lamp lights Lamp does not
(25%) but flickers light
Wirings are Wirings are Wirings are Wirings are
completely neat and not secured; loose; finished
2. Quality installed and clean; the finished work is not
(25%) energized work is work is not presentable.
presentable presentable

Followed Followed Incorrect Did not follow


procedure procedure usage of the required
correctly, correctly, tools. procedures.
observed economical
3. Method
safety while use of tools
(25%) working, and is followed;
perform good observed
housekeeping safety while
working.
Submitted Submitted Submitted Unable to
work two (2) work on a work two (2) finish the
4. Speed minutes given time. or more work.
(25%) ahead of minutes
time. after the
given time.

Rating: 5.0 – 4.6 = Very Good


– 3.9 = Good
– 3.0 = Fair
2.9 and below = Needs Improvement

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 3
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Work Sheet 7.1.1 Install Electrical Lighting System on Auxilliary
Outlet and Lighting Fixtures
Learning outcome:
7.1 Layout and Install Incandescent Lamp

Learning activities:
7.1.1 Answer the following questions by writing your answers on the blank before
the numbers

Test I. Identification: Identify the word/words being referred to by the following


statements.

1. It is used in photography and projection service.

2. These are generally used in automotive, aircraft, and


appliance applications.

3. These are normally used for interior and exterior general


and task lighting.

4. The metal wires that glow brightly when electricity flows


through them.

5. The wires that carry electricity from the bulb's electrical


contact to the filament.

6. The metallic base of the bulb which connects to the


electrical contacts of the lamp when the bulb is in the
lamp.
7. It is the thin layer of glass that surrounds the light bulb
mechanism and the inert gases.

8. A glass that insulates the bulb's fuses which is located in

9. the stem of the bulb.


10. It is the threaded base of the bulb that secures it to a
lamp.

11. It is a wire that physically hold up the filament.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxilliary Outlet and Sept.28,2010 1
Electrical Lighting System Lighting Fixtures
on Auxilliary Outlet and
Lighting Fixtures
Work Sheet 7.1.1 Install Electrical Lighting System on Auxilliary
Outlet and Lighting Fixtures

TEST II: Enumeration

1. Enumerate the nine elements used in manufacturing incandescent lamp.

2. Enumerate the (8) different parts of light bulb.

3. Enumerate the three different connections for incandescent lamp.

Code No. CON7412 Date: Developed: Date: Revised: Page #


Install Electrical Lighting
Perform Installation of System on Auxilliary Outlet and Sept.28,2010 2
Electrical Lighting System Lighting Fixtures
on Auxilliary Outlet and
Lighting Fixtures
Work Sheet 7.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures
Learning outcome:
7.1 Layout and Install Incandescent Lamp

Learning activities:
7.1.1 Label the different types of Flexible Nonmetallic Conduit Fittings. Write
your answer on a blank & underlined space.

1. Answer___________________________________________________

2. Answer___________________________________________________

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 1
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures
Work Sheet 7.1.1 Install Electrical Lighting System on Auxiliary
Outlet and Lighting Fixtures

3. Answer_________________________________________________

4. Answer___________________________________________________

5. Answer________________________________________________

Code No. CON7412 Date: Developed: Date: Revised: Page #


Perform Installation of Install Electrical Lighting Sept.28,2010 2
Electrical Lighting System System on Auxiliary Outlet
on Auxiliary Outlet and and Lighting Fixtures
Lighting Fixtures

You might also like